    Hydrolux

    2

    HEIMEIER Hydrolux is a proportionalworking, p-band controlled overflowvalve with low proportional deviation.

    Body made of corrosion-resistant gun-metal with threads according toDIN 2999.

    Direct setting scale display.

    Highest reaction precision due to aninner setting value spring with generousdimensions, made of special steel.

    Low friction central valve disc guide.

    Progressive setting, secured againstunauthorised adjustment. Setting range50500 mbar. Adjusted on the operatingside and preset to 200 mbar.

    Models NW 20 to NW 32.

    Female thread connections on the in-coming side; female thread or flat sealinglockshield on the out going side.

    Description

    HEIMEIER Hydrolux is used in warm waterpump heating systems. The current outputof the circulating pump changes accor-ding to the heating load and operating

    condition of a heating system. Dependingon the characterization of the pumpcharacteristic line, a decrease in currentoutput causes an increase in the outputrate. In addition, the pressure loss in thepipe network decreases, creating the pos-

    sibility of an oversupply and noise build-upin parts of the system.

    The Hydrolux overflow valve prevents an

    undesirable increase in the output rateand ensures that the current outputremains constant.

    For gas fired wall mounted heatingsystems, the minimum circulating waterlevel is guaranteed. We particularly recom-

    mend that an overflow valve be usedwhen the maximum output rate is signifi-cantly greater than the set opening pres-sure.

    To improve the effect of the overflowvalve, the bypass connection should be setup in a current-efficient way, or in such away that pressure loss is low, i. e. as shortas possible, with generous dimensions andwithout unnecessary individual resistances.

    Application

    Assembly

    Hydrolux Direct setting scaledisplay

    Low proportionaldeviation

    Extremely low noise,current efficient construction

    Low friction valve disc

    center guide Body made of corrosion-

    resistant gunmetal

    The p-band which applies when theheating system is in full operationis set on the overflow valve.

    When the current output is reduced, thevalve opens, causing the output rate ofthe circulating pump to remain constant

    within a proportional band necessary forcontrol purposes.

    Function

    Setting scaleHandwheel

    Setting valuespring

    Body made

    of corrosion-

    resistant

    gunmetal

  • 8/9/2019 Differential Pressure Overflow Valve

    3/4

    Hydrolux

    3

    Structure Recommended Max. max.

    max. heat flow heat flow

    volume flow at t 20 K at t 10 K

    V [m3/h] Q

    [kW] Q

    [kW] NW Art. no.

    2.0 46.5 23.3 20 (3

    /4) 5501-03.0003.5 81.4 40.7 25 (1) 5501-04.000

    7.0 162.8 81.4 32 (11/4) 5501-05.000

    2.0 46.5 23.3 20 (3/4) 5503-03.000

    3.5 81.4 40.7 25 (1) 5503-04.000

    7.0 162.8 81.4 32 (11/4) 5503-05.000

    Article numbers

    mbar

    100

    200

    300

    400

    500

    mbar

    100

    200

    300

    400

    500

    Sleeve female thread

    Flat sealing

    with fitting

    Permitted operating temperature TB 120C (248F).Permitted operating pressure PB 10 bar.

    Sample applicationsThe contents of the heat transfermedium should comply with VDI guide-line 2035 to prevent damage and scaledeposit formation in warm water heatingsystems.

    For industrial and long-distance energysystems, see the applicable codesVdTV 1466 and AGFW 5/15.

    Mineral oils in the heat transfer mediumor lubricants containing mineral oils ofany type lead to strong swelling and inmost cases cause EPDM seals to fail.

    When using nitrite-free frost andcorrosion-resistance solutions with anethylene glycol base, pay close attentionto the details outlined in the manu-facturers documentation, particularlydetails concerning concentration andspecific additives.

    Note

    Oil/gas boiler Wall-mounted gas fired

    heater Heating circuit Radiator 3-/ 4-way mixer Manifold

    TA STAD balancing valve

    Heating system with gas-fired wall mounted heater.Installed between the supplyand return pipes (minimum

    circulating water level).

    System with several heatingcircuits. Installed betweenthe supply pipe and themanifold.

    System without mixer.Installed between the

    pressure and suction-support pieces of thecirculating pump.

    System with three-waymixer. Installed between the

    supply and return pipes.

    Heating system withfourway mixer. Installed

    between the supply andreturn pipes.