differential pressure overflow valve
TRANSCRIPT
-
8/9/2019 Differential Pressure Overflow Valve
1/4
-
8/9/2019 Differential Pressure Overflow Valve
2/4
Hydrolux
2
HEIMEIER Hydrolux is a proportionalworking, p-band controlled overflowvalve with low proportional deviation.
Body made of corrosion-resistant gun-metal with threads according toDIN 2999.
Direct setting scale display.
Highest reaction precision due to aninner setting value spring with generousdimensions, made of special steel.
Low friction central valve disc guide.
Progressive setting, secured againstunauthorised adjustment. Setting range50500 mbar. Adjusted on the operatingside and preset to 200 mbar.
Models NW 20 to NW 32.
Female thread connections on the in-coming side; female thread or flat sealinglockshield on the out going side.
Description
HEIMEIER Hydrolux is used in warm waterpump heating systems. The current outputof the circulating pump changes accor-ding to the heating load and operating
condition of a heating system. Dependingon the characterization of the pumpcharacteristic line, a decrease in currentoutput causes an increase in the outputrate. In addition, the pressure loss in thepipe network decreases, creating the pos-
sibility of an oversupply and noise build-upin parts of the system.
The Hydrolux overflow valve prevents an
undesirable increase in the output rateand ensures that the current outputremains constant.
For gas fired wall mounted heatingsystems, the minimum circulating waterlevel is guaranteed. We particularly recom-
mend that an overflow valve be usedwhen the maximum output rate is signifi-cantly greater than the set opening pres-sure.
To improve the effect of the overflowvalve, the bypass connection should be setup in a current-efficient way, or in such away that pressure loss is low, i. e. as shortas possible, with generous dimensions andwithout unnecessary individual resistances.
Application
Assembly
Hydrolux Direct setting scaledisplay
Low proportionaldeviation
Extremely low noise,current efficient construction
Low friction valve disc
center guide Body made of corrosion-
resistant gunmetal
The p-band which applies when theheating system is in full operationis set on the overflow valve.
When the current output is reduced, thevalve opens, causing the output rate ofthe circulating pump to remain constant
within a proportional band necessary forcontrol purposes.
Function
Setting scaleHandwheel
Setting valuespring
Body made
of corrosion-
resistant
gunmetal
-
8/9/2019 Differential Pressure Overflow Valve
3/4
Hydrolux
3
Structure Recommended Max. max.
max. heat flow heat flow
volume flow at t 20 K at t 10 K
V [m3/h] Q
[kW] Q
[kW] NW Art. no.
2.0 46.5 23.3 20 (3
/4) 5501-03.0003.5 81.4 40.7 25 (1) 5501-04.000
7.0 162.8 81.4 32 (11/4) 5501-05.000
2.0 46.5 23.3 20 (3/4) 5503-03.000
3.5 81.4 40.7 25 (1) 5503-04.000
7.0 162.8 81.4 32 (11/4) 5503-05.000
Article numbers
mbar
100
200
300
400
500
mbar
100
200
300
400
500
Sleeve female thread
Flat sealing
with fitting
Permitted operating temperature TB 120C (248F).Permitted operating pressure PB 10 bar.
Sample applicationsThe contents of the heat transfermedium should comply with VDI guide-line 2035 to prevent damage and scaledeposit formation in warm water heatingsystems.
For industrial and long-distance energysystems, see the applicable codesVdTV 1466 and AGFW 5/15.
Mineral oils in the heat transfer mediumor lubricants containing mineral oils ofany type lead to strong swelling and inmost cases cause EPDM seals to fail.
When using nitrite-free frost andcorrosion-resistance solutions with anethylene glycol base, pay close attentionto the details outlined in the manu-facturers documentation, particularlydetails concerning concentration andspecific additives.
Note
Oil/gas boiler Wall-mounted gas fired
heater Heating circuit Radiator 3-/ 4-way mixer Manifold
TA STAD balancing valve
Heating system with gas-fired wall mounted heater.Installed between the supplyand return pipes (minimum
circulating water level).
System with several heatingcircuits. Installed betweenthe supply pipe and themanifold.
System without mixer.Installed between the
pressure and suction-support pieces of thecirculating pump.
System with three-waymixer. Installed between the
supply and return pipes.
Heating system withfourway mixer. Installed
between the supply andreturn pipes.
-