digital i/o termination unit (ntdi02)...it provides a signal path between field i/o signals and the...

52
Instruction Harmony Series Digital I/O Termination Unit NTDI02

Upload: others

Post on 06-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

InstructionHarmony Series

Digital I/O Termination UnitNTDI02

Page 2: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0

Preface

The NTDI02 Digital I/O Termination Unit is a Harmony rackI/O device that is part of the Symphony Enterprise Manage-ment and Control System. It provides a signal path between field I/O signals and the following I/O modules.

• Analog output module (IMASO11).• Digital input module (IMDSI13, IMDSI14, and IMDSI22).• Pulse input module (IMDSM04).• Digital output module (IMDSO14 and IMDSO15).• Frequency counter module (IMFCS01).

The NTDI02 is not a direct replacement for the NTDI01; how-ever, it is a functional replacement for the NTDI01.

This instruction explains the NTDI02 termination unit specifi-cations and operation. It details the procedures necessary to complete setup, installation, maintenance, repair, and replace-ment of the termination unit.

NOTE: The NTDI02 termination unit is fully compatible with existing INFI 90® OPEN and Symphony™ Enterprise Management Systems.

Page 3: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0

List of Effective Pages

Total number of pages in this instruction is 46, consisting of the following:

Page No. Change Date

Preface OriginalList of Effective Pages Original

iii through ix Original1-1 through 1-6 Original2-1 through 2-8 Original3-1 through 3-4 Original4-1 through 4-3 OriginalA-1 through A-9 OriginalB-1 through B-6 Original

Index-1 Original

Page 4: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 iii

Table of Contents

Section 1 Introduction ..................................................................................................1-1Overview .................................................................................................................. 1-1Intended User .......................................................................................................... 1-1Description .............................................................................................................. 1-2Mounting Hardware ................................................................................................. 1-3Instruction Content.................................................................................................. 1-3How to Use this Instruction...................................................................................... 1-4Document Conventions ............................................................................................ 1-4Reference Documents .............................................................................................. 1-4Related Nomenclature .............................................................................................. 1-5Specifications........................................................................................................... 1-5

Section 2 Installation ....................................................................................................2-1Introduction............................................................................................................. 2-1Special Handling...................................................................................................... 2-1Unpacking and Inspection........................................................................................ 2-2Setup/Physical Installation ...................................................................................... 2-2

Fuse Installation .................................................................................................. 2-2Dipshunt Configuration........................................................................................ 2-2

Connector P1 Signal Paths ....................................................................................... 2-4Termination Unit Installation ................................................................................... 2-4

Mounting ............................................................................................................. 2-4Cable Connection ................................................................................................. 2-5Power Wiring .................................................................................................. 2-6Jumper Settings................................................................................................... 2-7Terminal Block Wiring.......................................................................................... 2-7

Startup Check List ................................................................................................... 2-7

Section 3 Maintenance .................................................................................................3-1Introduction............................................................................................................. 3-1Preventive Maintenance Schedule ............................................................................ 3-1Equipment and Tools Required ................................................................................ 3-1Preventive Maintenance Procedures ......................................................................... 3-2

Printed Circuit Board Cleaning ............................................................................ 3-2General Cleaning and Washing......................................................................... 3-3Edge Connector Cleaning.................................................................................. 3-3

Checking Connections.......................................................................................... 3-4

Page 5: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

iv WBPEEUI260050A0

Table of Contents (continued)

Section 4 Repair and Replacement .............................................................................4-1Introduction .............................................................................................................4-1Fuse Replacement ....................................................................................................4-1Termination Unit Replacement .................................................................................4-1

Appendix A Dipshunt and Jumper Settings ............................................................. A-1IMASO11................................................................................................................. A-1IMDSI13, IMDSI14 and IMDSI22 ............................................................................. A-2IMDSM04 ................................................................................................................ A-3IMDSO14 ................................................................................................................ A-5IMDSO15 ................................................................................................................ A-6IMFCS01 ................................................................................................................. A-9

Appendix B TB1 Through TB4 Schematics .............................................................. B-1P1 Connections ....................................................................................................... B-1P3 Connections ....................................................................................................... B-2TB1 Schematic ..................................................................................................... B-3TB2 Schematic ..................................................................................................... B-4TB3 Schematic ..................................................................................................... B-5TB4 Schematic ..................................................................................................... B-6

List of FiguresNo. Title Page

1-1. Harmony Rack I/O Architecture ................................................................1-21-2. Mounting Hardware...................................................................................1-32-1. Termination Unit Layout ...........................................................................2-32-2. Termination Unit Installation ....................................................................2-52-3. Cable Connection ......................................................................................2-5A-1. IMASO11 Analog Output Circuits ............................................................. A-1A-2. IMASO11 Internal Powered....................................................................... A-1A-3. Settings for IMDSI13, IMDSI14 and IMDSI22 Powered from E1................. A-2A-4. Settings for IMDSI13, IMDSI14 and IMDSI22 Powered from E2................. A-2A-5. Settings for IMDSI13, IMDSI14 and IMDSI22 Powered from Field ............. A-3A-6. Settings for IMDSM04 System Powered..................................................... A-3A-8. Settings for IMDSM04 Power for Preamplifiers .......................................... A-4A-7. Settings for IMDSM04 Field Powered ........................................................ A-4A-9. Settings for IMDSO14 Powered from E1.................................................... A-5

Page 6: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 v

List of Figures (continued)

No. Title Page

A-10. Settings for IMDSO14 Powered from E2 ....................................................A-5A-11. Settings for IMDSO14 Field Powered .........................................................A-6A-12. Custom Relay Contact/Terminal Block Assignment for the IMDSO15........A-6A-14. Settings for IMDSO15 XU8........................................................................A-8A-13. IMDSO15..................................................................................................A-8A-15. Settings for IMDSO15 XU12......................................................................A-9A-16. Settings for IMFCS01 ................................................................................A-9B-1. TB1 Schematic..........................................................................................B-3B-2. TB2 Schematic..........................................................................................B-4B-3. TB3 Schematic..........................................................................................B-5B-4. TB4 Schematic..........................................................................................B-6

List of TablesNo. Title Page

1-1. Reference Documents ............................................................................... 1-41-2. Related Nomenclature ............................................................................... 1-51-3. NTDI02 Termination Unit Specifications.................................................... 1-52-1. Fuse Ratings............................................................................................. 2-23-1. Preventive Maintenance Schedule ............................................................. 3-24-1. Parts List .................................................................................................. 4-1A-1. Relay Contact Assignment for IMDSO15....................................................A-7B-1. Connector P1 Signal Paths ........................................................................B-1B-2. Cable Connections for I/O Signals ............................................................B-2

Page 7: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

vi WBPEEUI260050A0

Safety Summary

Electrostatic Sensitive DeviceDevices labeled with this symbol require special handling precau-tions as described in the installation section.

GENERAL WARNINGS

Equipment EnvironmentAll components, whether in transportation, operation or storage, must be in a noncorrosive environment.

Electrical Shock Hazard During MaintenanceDisconnect power or take precautions to insure that contact with energized parts is avoided when servicing.

SPECIFICWARNINGS

Verify the main power, field power, and power entry panel circuit breakers/switches are turned off before starting installation, retrofit, upgrade, or wiring procedures. Failure to do so could result in severe or fatal shock. Do not turn the power on until the installation, retrofit, upgrade, or wiring procedures are complete. (p. 2-6)

Never clean electrical parts or components with live power present. Doing so exposes the technician to an electrical shock hazard and may damage the equipment. (p. 3-2)

Wear eye protection whenever working with cleaning solvents. When removing solvents from printed circuit boards using com-pressed air, injury to the eyes could result from splashing solvent as it is removed from the printed circuit board. (p. 3-2)

There are exposed AC and DC connections inside the cabinet. These exposed electrical connections present a shock hazard that can cause injury or death. (p. 3-4)

If input or output circuits are a shock hazard after disconnecting sys-tem power at the power entry panel, then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist. (p. 3-4)

Page 8: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 vii

Safety Summary (continued)

SPECIFIC CAUTIONS

Remove a module from its assigned slot before installing or remov-ing a cable assigned to that slot. Failure to do so could result in damage to the module. (p. 2-6, 4-2)

Do not apply an input voltage to E1 or E2 if any of the sixteen field power inputs exceeds 120Vac. If the AC voltages are out of phase, the total voltage level will exceed the NTDI02 voltage rating which can cause damage to the termination unit. (p. 2-6)

Page 9: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

viii WBPEEUI260050A0

Support Services

ABB will provide assistance in the operation and repair of its products. Requests for sales or application services should be made to your nearest sales or service office. ABB can also pro-vide installation, repair and maintenance contract services.

When ordering parts, use nomenclature or part numbers and part descriptions from equipment manuals. Parts without a description must be ordered from the nearest sales or service office. Recommended spare parts lists, including prices are available through the nearest sales or service office.

ABB has modern training facilities available for training your personnel. On-site training is also available. Contact your nearest ABB sales office for specific information and scheduling.

Additional copies of this instruction, or other instructions, can be obtained from the nearest ABB sales office at a reasonable charge.

Page 10: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 ix

Trademarks and Registrations

Registrations and trademarks used in this document include:

® INFI 90 Registered trademark of ABB.™ Symphony Trademark of ABB.

Page 11: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0

Page 12: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 1 - 1

Section 1Introduction

OverviewThe NTDI02 Digital I/O Termination Unit is a Harmony rackI/O device that is part of the Symphony Enterprise Manage-ment and Control System. It provides a signal path for up to 16 input signals to the following I/O modules. The inputs are used by the controller to monitor and control a process.

• Analog output module (IMASO11).

• Digital input module (IMDSI13, IMDSI14, and IMDSI22).

• Pulse input module (IMDSM04).

• Digital output module (IMDSO14 and IMDSO15).

• Frequency counter module (IMFCS01).

Figure 1-1 shows the Harmony rack I/O architecture. A Har-mony area controller and the Harmony rack controllers can use the rack I/O module and termination units for I/O interface.

Intended UserPersonnel installing, operating, or maintaining the NTDI02 ter-mination unit should read this instruction before performing any installation, operation, or maintenance procedures. Instal-lation requires an engineer or technician with experience handling electronic circuitry. Those working with the NTDI02 termination unit should have experience working with and know the precautions to take around AC/DC power. A knowl-edge of the Symphony system and electronic principles is also required.

Page 13: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

1 - 2 WBPEEUI260050A0

Description

DescriptionThe NTDI02 termination unit is a seven-by-seven inch square printed circuit board. The board contains:

• Two fuses.• 16 programmable dipshunts.• 16 user configurable jumpers.• Four terminal strips.• One cable socket.• Two power source Faston connectors.• One system common Faston connector.

Figure 1-1. Harmony Rack I/O Architecture

H A R M O N YA R E AC O N TRO LLE R

I/OM O D U LE

I/OM O D U LE

I/OM O D U LE

TE R M IN ATIO NU N IT

TE R M IN ATIO NC A B LE

FIE LDW IR IN G

TE R M IN ATIO NU N IT

TER M IN ATIO NU N IT

T04882A

I/O E X PA N D E R BU S

FIE LD BU S

A N A LO G CO N TRO LS TATIO N S

P RO C E S S I/O P RO C E S S I/O

H AR M O N Y R AC KC O M M U N IC ATIO NM O D U LE S

H A R M O N YC O N TRO LLE R

C N E T

C O N TRO LW AY

Page 14: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Mounting Hardware

WBPEEUI260050A0 1 - 3

Mounting HardwareHarmony termination units mount in a standard ABB enclo-sure (P-ME-CAB). An NFTP01 Field Termination Panel is used for termination unit mounting (Fig. 1-2). The panel attaches to the side rails in EIA standard 19-inch enclosures.

Instruction ContentThis instruction contains the following sections:

Introduction Provides an overview of the NTDI02 termination unit.

Installation Explains the physical installation, wiring and cable requirements, fuse requirements, dipshunt settings, jumpers settings and handling of the termination unit.

Maintenance Contains a maintenance schedule.

Repair andReplacement

Explains how to replace the termination unit.

Dipshunt and JumperSettings

Provides detailed diagrams for dipshunt and jumper settings for specific modules.

Figure 1-2. Mounting Hardware

FIE LDTE R M IN ATIO NPAN EL

TE R M IN ATIO NU N IT

T038 87A

Page 15: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

1 - 4 WBPEEUI260050A0

How to Use this Instruction

How to Use this InstructionRead this instruction in sequence. It is important to become familiar with the entire contents of this instruction before using the termination unit. Refer to a specific section for infor-mation as needed.

1. Perform the steps in the installation section.

2. Refer to the maintenance section for scheduled mainte-nance requirements.

3. Refer to the repair and replacement procedures to replace a termination unit.

Document ConventionsThe ? in the nomenclature or in a part number indicates a variable for that position (e.g., IMMFP1?).

Reference DocumentsTable 1-1 lists ABB instructions for equipment that is refer-enced in this instruction.

Table 1-1. Reference Documents

Number Document

WBPEEUI200502?? Module Mounting Unit (IEMMU11, IEMMU12, IEMMU21, and IEMMU22)

WBPEEUI200505?? Site Planning

WBPEEUI240762?? Digital output module (IMDSO14)

WBPEEUI240763?? Digital output module (IMDSO15)

WBPEEUI240765?? Analog output module (IMASO11)

WBPEEUI240767?? Digital input module (IMDSI13, IMDSI14, and IMDSI22)

WBPEEUI240770?? Frequency counter module (IMFCS01)

WBPEEUI240772?? Pulse input module (IMDSM04)

Page 16: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Related Nomenclature

WBPEEUI260050A0 1 - 5

Related NomenclatureTable 1-2 lists nomenclature related to the NTDI02 termina-tion unit.

SpecificationsRefer to Table 1-3 for NTDI02 termination unit specifications.

Table 1-2. Related Nomenclature

Nomenclature Description

IEMMU11, IEMMU12, IEMMU21, IEMMU22 Module mounting unit

IMASO11 Analog output module

IMDSI13, IMDSI14, IMDSI22 Digital input module

IMDSM04 Pulse input module

IMDSO14, IMDSO15 Digital output module

IMFCS01 Frequency counter module

NFTP01 Field termination panel

NKTU01 Termination cable (PVC)

NKTU11 Termination cable (non-PVC)

Table 1-3. NTDI02 Termination Unit Specifications

Property Characteristic/Value

Wire sizeMaximumMinimum

12 AWG22 AWG

ElectricalMaximum voltageMaximum current

250Vac3A

Measurement Category(IEC 61010-1:2000)

I for circuits > 150 VII for circuits < 150 V

Mounting Mounts on the field termination panel.

Page 17: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

1 - 6 WBPEEUI260050A0

Specifications

Environmental

Ambient temperature

Relative humidity

Altitude

Air quality

0° to 70°C (32° to 158°F)

5% to 95% up to 55°C (131°F) (noncondensing)5% to 45% at 70°C (158°F) (noncondensing)Pollution degree: I

Sea level to 3 km (1.86 mi)

Noncorrosive

Cooling requirements No cooling is required when used in ABB cabinets and operated within environmental limits.

Certifications

Canadian StandardsAssociation (CSA)

Factory Mutual (FM)(pending)

Certified for use as process control equipment in an ordinary (nonhazardous) location.

Approval pending for use in Class I; Division 2;Group A, B, C, D; hazardous location.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

Table 1-3. NTDI02 Termination Unit Specifications (continued)

Property Characteristic/Value

Page 18: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 2 - 1

Section 2Installation

IntroductionThis section explains NTDI02 termination unit installation. Do not proceed with operation until the steps are read, under-stood, and performed in the order in which they appear.

Special HandlingObserve these steps when handling electronic circuitry:

1. Use Static Shielding Bag. Keep an assembly in its static shielding bag until ready to install it in the system. Save the bag for future use.

2. Ground Bags before Opening. Before opening a bag con-taining an assembly with static sensitive devices, touch it to the equipment housing or ground to equalize charges.

3. Avoid Touching Circuitry. Handle assemblies by the edges; avoid touching the circuitry.

4. Avoid Partial Connection of Semiconductors. Verify that all devices connected to the module are properly grounded before using them.

5. Ground Test Equipment.

6. Use an Antistatic Field Service Vacuum. Remove dust from assemblies if necessary.

7. Use a Grounded Wrist Strap. Use the ABB field static kit (part number 1948385A1 - consisting of two wrist straps, ground cord assembly, alligator clip, and static dissipative work surface) when working with modules. The kit grounds a technician and the static dissipative work surface to the same ground point to prevent damage to the circuitry by electro-static discharge. Connect the wrist strap to the appropriate grounding plug on the power supply or to an unpainted por-tion of the enclosure with the alligator clip. The wrist strap must be effectively connected to the earth grounding electrode system through the AC safety ground.

Page 19: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

2 - 2 WBPEEUI260050A0

Unpacking and Inspection

8. Do Not Use Lead Pencils to Set Switches. To avoid con-tamination of switch contacts that can result in unnecessary circuit board malfunction, do not use a lead pencil to set a switch.

Unpacking and Inspection1. Examine the hardware immediately to verify it has not been damaged in transit.

2. Notify the nearest ABB sales office of any such damage.

3. File a claim for any damage with the transportation com-pany that handled the shipment.

4. Use the original packing material and container to store the hardware.

5. Store the hardware in an environment of good air quality, free from temperature and moisture extremes.

Setup/Physical InstallationInstall the fuses and configure the dipshunts before installing or operating the NTDI02 termination unit. Figure 2-1 shows the layout of the termination unit.

Fuse Installation

There are two fuses on the termination unit. Fuse F1 protects the E1 power supply and fuse F2 protects the E2 power sup-ply. Determine the voltage required and refer to Table 2-1 to select the correct fuse.

Dipshunt Configuration

There are 16 dipshunts on the termination unit. Dipshunts XU1 through XU16 are for point (I/O) configuration of the 16

Table 2-1. Fuse Ratings

Voltage Required Part Number Description

24 VDC or 48 VDC 194776?13001 3 A

125 VDC or 120 VAC 194776?12500 0.25 A

Page 20: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Setup/Physical Installation

WBPEEUI260050A0 2 - 3

available I/O signals. The actual configuration of these dip-shunts depends on the I/O module being used. Refer to Appendix A for the required dipshunt configurations.

NOTE: The connections to TB1 through TB4 are different when using the digi-tal output module IMDSO15. Refer to Figure A-12 and Table A-1 in Appendix A for specific details.

Figure 2-1. Termination Unit Layout

T 04830A

1 1 11

2 2 22

3 3 33

4 4 44

5 5 55

6 6 66

7 7 77

8 8 88

TB4 TB3 TB1TB2

A1 A5 B 1B5

A2 A6 B 2B6

A3 A7 B 3B7

A4 A8 B 4B8

P 1

F2 F1

E2 E1E3

XU 13 XU 5

XU 14 XU 6

XU 15 XU 7

XU 16 XU 8

XU 9 XU 1

XU 10 XU 2

XU 11 XU 3

XU 12 XU 4

X J13 X J14 X J9 X J10 X J1 X J2X J5 X J6

X J15 X J16 X J11 X J12 X J3 X J4X J7 X J8

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

JU M P E RS J1 TH RU J161 2 3

Page 21: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

2 - 4 WBPEEUI260050A0

Connector P1 Signal Paths

Configure a dipshunt by either cutting straps or leaving straps uncut in certain sequences. Cut the dipshunt straps using a standard shunt cutting tool. Always cut straps completely (e.g. gap should be a minimum of 0.5mm). Install the configured dipshunt into the desired socket on the termination unit. To install a dipshunt, align the end of the dipshunt identified with the silver dot to the end of the socket having an identification mark and push the dipshunt into the socket. Be careful not to bend any pins during insertion.

Connector P1 Signal PathsRefer to TB1 Through TB4 Schematics in Appendix B for detailed drawings of TB1 through TB4 and tables defining pin connections P1 to P3.

Termination Unit InstallationThe termination unit is ready for installation when the fuses are installed, jumpers are set and dipshunts are properly con-figured. The termination unit mounts on a standard NFTP01 panel as shown in Figure 1-2.

Mounting

To mount the NTDI02 termination unit to the field termination panel:

1. Insert the tabs of the circuit board into the proper slots of the termination panel standoff as shown in Figure 2-2 and slide the circuit board into position.

2. Secure the termination unit circuit board to the field termi-nation panel with two No. 10 x 5/8 thread-forming screws.

Figure B-1 TB1

Figure B-2 TB2

Figure B-3 TB3

Figure B-4 TB4

Page 22: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Termination Unit Installation

WBPEEUI260050A0 2 - 5

Cable Connection

After mounting the termination unit to the field termination panel, install the NKTU01 or NKTU11 termination cable. Fig-ure 2-3 shows a diagram of cable connections to the I/O mod-ule and termination unit.

Figure 2-2. Termination Unit Installation

F IELD TER M IN AT IO NPAN EL

T ER M IN AT IO NU N IT

SC R EW (2)

T03619A

TAB SSTAN D O FF

Figure 2-3. Cable Connection

T04833A

I/O M O D U LE

N K TU 01N K TU 11

16 I/O P O IN TS

P 1

P 2

P 3 P 1 N TD I02

Page 23: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

2 - 6 WBPEEUI260050A0

Termination Unit Installation

To install the termination unit cable:

1. Install the J2 connector of the NKTU01 or NKTU11 termi-nation unit cable in the module mounting unit backplane slot assigned to the I/O module.

2. Insert the J1 connector of the cable into P1 of the termina-tion unit.

Power Wiring

There are three terminals that provide power and ground con-nections. Refer to Figure 2-1 for terminal locations. System power connects to the termination unit through Faston con-nectors E1 and E2 and can be distributed to the configuration sockets (XU1 - XU16) through fuses (F1 and F2) and jumpers (J1 - J16). Any combination of power can be connected to these connectors depending on the application. However, this requires careful system analysis to ensure circuit board trace amperage capacity is not exceeded. A single trace can handle a continuous three amperes. System ground or neutral connects through Faston connector E3.

CAUTIONRemove a module from its assigned slot before installing or removing a cable assigned to that slot. Failure to do so could result in damage to the module.

CAUTION

Do not apply an input voltage to E1 or E2 if any of the sixteen field power inputs exceeds 120Vac. If the AC voltages are out of phase, the total voltage level will exceed the NTDI02 voltage rating which can cause damage to the termination unit.

WARNING

Verify the main power, field power, and power entry panel cir-cuit breakers/switches are turned off before starting installa-tion, retrofit, upgrade, or wiring procedures. Failure to do so could result in severe or fatal shock. Do not turn the power on until the installation, retrofit, upgrade, or wiring procedures are complete.

Page 24: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Startup Check List

WBPEEUI260050A0 2 - 7

To connect the power wiring:

1. If required, attach a 12-14 AWG wire from the power distri-bution source (24 VDC, 48 VDC, 125 VDC, or 120 VAC) to the E1 terminal on the termination unit.

2. If required, attach a 12-14 AWG wire from the power distri-bution source (24 VDC, 48 VDC, 125 VDC, or 120 VAC) to the E2 terminal of the termination unit.

3. If required, attach a 12-14 AWG wire from the system ground or neutral to the E3 terminal of the termination unit.

NOTE: Do not mix AC and DC power on the E1 and E2 inputs on the termina-tion unit. Do not mix AC and DC commons.

Jumper Settings

1. Position the jumper for each socket used on the termina-tion unit. Use positions 1 and 2 for E2 power and positions 2 and 3 for E1 power.

2. Since socket pairs XU7/XU8 and XU11/XU12 share a common pin on connector P1, it is important to use care when setting these jumpers. These pairs should always have identi-cal jumper settings for power.

Terminal Block Wiring

Refer to Figure 2-1 for terminal block assignments and termi-nal polarity. Field wiring requirements will depend on the application. Refer to the Site Planning instruction for specific information on field wiring installation requirements (i.e., spacing, isolation, etc.). Connect the wiring from the input devices to the terminals.

Startup Check ListThe termination unit is ready for operation when:

1. The fuses are installed.

2. The dipshunts are configured.

3. Jumpers J1 through J16 are configured.

Page 25: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

2 - 8 WBPEEUI260050A0

Startup Check List

4. The termination unit is installed on the field termination panel.

5. The cables are connected.

6. Power wiring is connected and applied to the termination unit.

7. Terminal block wiring is connected to the termination unit and field device.

Page 26: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 3 - 1

Section 3Maintenance

IntroductionThe reliability of any stand-alone product or control system is affected by the maintenance of the equipment. ABB recom-mends that all equipment receive preventive maintenance to keep the equipment operating at an optimum level.

This section presents procedures that the customer should be able to perform on site. These preventive maintenance proce-dures should be used as a guideline to assist in establishing good preventive maintenance practices.

Personnel performing preventive maintenance should meet the following qualifications.

• Personnel should be qualified electrical technicians or engineers that know the proper use of test equipment.

• Personnel should be familiar with the module mounting unit and field termination panel, have experience working with process control systems, and know what precautions to take when working on live AC and/or DC systems.

Preventive Maintenance ScheduleTable 3-1 is the preventive maintenance schedule for the NTDI02 termination unit. The table lists the preventive main-tenance tasks in groups according to their specified mainte-nance interval. Tasks that require further explanation are covered under Preventive Maintenance Procedures.

NOTE: The preventive maintenance schedule is for general purposes only. Your application may require special attention.

Equipment and Tools RequiredTools and equipment required for maintenance procedures:

• Antistatic vacuum.• Screwdriver (medium length).

Page 27: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

3 - 2 WBPEEUI260050A0

Preventive Maintenance Procedures

• Isopropyl alcohol (99.5 percent electronic grade).• Distilled water.• Compressed air.• Foam-tipped swabs.• Lint-free cloths. • Nonabrasive eraser.

Preventive Maintenance ProceduresThis section covers tasks from Table 3-1 that require specific instructions or further explanation.

Printed Circuit Board Cleaning

There are several circuit board cleaning procedures in this sec-tion. These procedures cover circuit board cleaning and wash-ing, cleaning edge connectors and circuit board laminate between edge connectors. Use the procedures that meet the needs of each circuit board. Remove all dust, dirt, oil, corro-sion or any other contaminant from the circuit board.

Table 3-1. Preventive Maintenance Schedule

Task Frequency

Check cabinet air filters. Clean or replace them as necessary. Check the air filter more frequently in excessively dirty environments.

3 months

Check cabinet and termination unit for dust. Clean using an antistatic vacuum.

Check all termination unit signal, power and ground connections within the cabinet. Verify that they are secure. Refer to procedure.

Check termination unit circuit board, giving special attention to power contacts and edge connectors. Clean as necessary. Refer to procedure.

12 months

Complete all tasks in this table. Shutdown

WARNING

Never clean electrical parts or components with live power present. Doing so exposes the technician to an electrical shock hazard and may damage the equipment.

Wear eye protection whenever working with cleaning solvents. When removing solvents from printed circuit boards using compressed air, injury to the eyes could result from splashing solvent as it is removed from the printed circuit board.

Page 28: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Preventive Maintenance Procedures

WBPEEUI260050A0 3 - 3

Perform all cleaning and handling of the printed circuit boards at static safe work stations. Always observe the steps under Special Handling in Section 2 when handling printed circuit boards.

General Cleaning and Washing

If the printed circuit board needs minor cleaning, remove dust and residue from the printed circuit board surface using clean, dry, filtered compressed air or an antistatic field service vac-uum cleaner.

To wash the printed circuit board:

1. Clean the printed circuit board by spraying or wiping it with isopropyl alcohol (99.5% electronic grade). Use a foam-tipped swab to wipe the circuit board.

2. Remove excess solvent by using compressed air to blow it free of the circuit board.

Edge Connector Cleaning

1. Use a solvent mixture of 80% isopropyl alcohol (99.5% electronic grade) and 20% distilled water.

2. Soak a lint-free cloth with the solvent mixture.

3. Work the cloth back and forth parallel to the edge connec-tor contacts.

4. Repeat with a clean cloth that is soaked with the solvent mixture.

5. Dry the edge connector contact area by wiping with a clean lint-free cloth.

To clean tarnished or deeply stained edge connector contacts:

1. Use a nonabrasive eraser or equivalent to remove tarnish or stains. Fiberglass or nylon burnishing brushes may also be used.

2. Minimize electrostatic discharge by using the 80/20 iso-propyl alcohol/water solution during burnishing.

3. Do not use excessive force while burnishing. Use only enough force to shine the contact surface. Inspect the edge connector after cleaning to assure no loss of contact surface.

Page 29: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

3 - 4 WBPEEUI260050A0

Preventive Maintenance Procedures

4. Wipe clean with a lint-free cloth.

Checking Connections

NOTE: Power to the cabinet should be off while performing this preventive maintenance task.

Check all signal wiring, power and ground connections within the cabinet to verify their integrity. When checking connec-tions, always turn a screw, nut or other fastening device in the direction to tighten only. If the connection is loose, it will be tightened. If the connection is tight, the tightening action will verify that it is secure. There must not be any motion done to loosen the connection.

1. Verify that all power connections within the cabinet are secure.

2. Verify that all wiring connections to the termination unit are secure.

WARNING

There are exposed AC and DC connections inside the cabinet. These exposed electrical connections present a shock hazard that can cause injury or death.

If input or output circuits are a shock hazard after disconnect-ing system power at the power entry panel, then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist.

Page 30: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 4 - 1

Section 4Repair and Replacement

IntroductionThis section explains the repair and replacement procedures for an NTDI02 termination unit. Table 4-1 is a replacement and spare parts list.

Fuse ReplacementIf a fuse opens, replace it with a fuse having an equivalent rat-ing. To replace a fuse:

1. Turn off power to the cabinet.

2. Verify that there is no power on E1 or E2.

3. Remove the blown fuse from its holder.

4. Replace the blown fuse with an equivalent fuse.

5. Turn on power to the cabinet.

Termination Unit ReplacementIf the termination unit is faulty, replace it with a new one. Do not try to repair the unit. Replacing components of a termina-tion unit may affect performance and certification. Refer to

Table 4-1. Parts List

Part Number Description

1946715?8 Dipshunt

194776?12500 Fuse, 0.25 A

194776?13001 Fuse, 3 A

NFWAB17010 0.19-16 (no.10) x 5/8 in. Phillips-head thread forming screw

Page 31: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

4 - 2 WBPEEUI260050A0

Termination Unit Replacement

Special Handling in Section 2 when replacing a termination unit.

NOTE: Turn off power to the field devices before removing the cables from the termination unit.

Follow Steps 1 through 14 to replace the termination unit.

1. Turn off power to the cabinet.

2. Disconnect the power source and ground wiring from the E1, E2, and E3 Faston connectors of the termination unit. Mark the wires according to their terminal assignment as they are removed.

3. If the termination unit is connected to an I/O module, pull the I/O module out of its cable connection on the module mounting unit backplane.

4. If there is a termination cable connected, disconnect it from the P1 connector on the termination unit.

5. Turn off power to the field devices. Disconnect I/O wiring from the terminal blocks. Mark the wires according to their terminal assignment.

6. When all cables and wires are removed from the termina-tion unit, remove the two mounting screws and remove the ter-mination unit from the field termination panel.

7. Verify the proper fuses are installed in fuse holders F1 and F2 of the replacement termination unit.

8. Verify that the dipshunt settings and jumper settings on the replacement termination unit are the same as the dipshunt settings and jumper settings on the faulty termina-tion unit.

NOTE: NTDI01 and NTDI02 may not be interchangeable. The settings may not be the same.

9. Secure the replacement termination unit circuit board to the field termination panel with the two mounting screws.

CAUTIONRemove a module from its assigned slot before installing or removing a cable assigned to that slot. Failure to do so could result in damage to the module.

Page 32: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Termination Unit Replacement

WBPEEUI260050A0 4 - 3

10. Connect the termination unit cables to their assigned con-nector on the termination unit.

11. Connect the I/O wiring to the terminal strips.

12. Connect the power source and ground wiring to the E1, E2, and E3 Faston connectors of the termination unit.

13. Push on the faceplate of the I/O module to fully insert it into its module mounting unit slot. The I/O modules should be seated in the termination unit cable at the rear of the module mounting unit when fully inserted.

14. After all cables and wiring have been replaced, return power to the field devices.

15. Return power to the cabinet.

16. Check I/O points for good quality to ensure the new termi-nation unit is functioning properly.

Page 33: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0

Page 34: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 A - 1

Appendix ADipshunt and Jumper Settings

IMASO11

Figure A-1. IMASO11 Analog Output Circuits

Figure A-2. IMASO11 Internal Powered

T 04845A

12345678

161514131211109

P 1

FU S E E2

FU S E E13

1

2

TE R M IN A LBLO C KS

C O M

+

+

JU M PE R PO SIT IO NN OT IM P O RTAN T

4-20 m A O R 1-5 V O U TP U TS

14 C IR C U ITS :XU 1 - XU 7XU 9 - XU 11XU 13 - X U 16ALSO S ET X U 12 A S SH O W NXU 8 N OT U SED

T 04846A

12345678

161514131211109

FU S E E2

FU S E E13

1

2

T ER M IN ALB LO C KS

C O M

XU 12 FO R 24 V TO A SO M O D U LE(24 V M U ST B E C O N N E C TE D TO TD I02 E1 FASTO N )

N /C

+24 VP 1

+

Page 35: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

A - 2 WBPEEUI260050A0

IMDSI13, IMDSI14 and IMDSI22

IMDSI13, IMDSI14 and IMDSI22

Figure A-3. Settings for IMDSI13, IMDSI14 and IMDSI22 Powered from E1

Figure A-4. Settings for IMDSI13, IMDSI14 and IMDSI22 Powered from E2

T04 839 A

12345678

1 61 51 41 31 21 11 09

P 1

FU S E E 2

FU S E E 13

1

2

C O M

+

X U 1 - X U 7X U 9 - X U 15X U 8 A N D X U 1 6 N OT U S E D

T E R M IN A LB LO C K S

+

T04 840 A

12345678

1 61 51 41 31 21 11 09

P 1

FU S E E 2

FU S E E 13

1

2

T E R M IN A LB LO C K S

C O M

+

X U 1 - X U 7X U 9 - X U 15X U 8 A N D X U 1 6 N OT U S E D

+

Page 36: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

IMDSM04

WBPEEUI260050A0 A - 3

IMDSM04

Figure A-5. Settings for IMDSI13, IMDSI14 and IMDSI22 Powered from Field

T0 484 1A

12345678

161514131211109

P1

FU S E E 2

FU S E E 13

1

2

TE RM IN A LBLO C KS

C OM

+

+

JU M PE R PO S ITIO NNOT IM P ORTA N T

O R

XU 1 - XU 16 W HE N SW ITC HIN G C O M M O N

XU 1 - XU 7XU 9 - XU 15 W H EN SW ITC H ING P OW E R

Figure A-6. Settings for IMDSM04 System Powered

T 04850 A

12345678

161514131211109

P1

FU S E E2

FU S E E13

1

2

TE R M IN A LBLO C KS

C O M

+

XU 1 - XU 4XU 13 - XU 16

+

Page 37: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

A - 4 WBPEEUI260050A0

IMDSM04

Figure A-7. Settings for IMDSM04 Field Powered

Figure A-8. Settings for IMDSM04 Power for Preamplifiers

T 04851A

12345678

161514131211109

P 1

FU S E E2

FU S E E13

1

2

T ER M IN ALB LO C K S

C O M

+

JU M PE R P O SIT IO NN OT IM PO RTA N T

+

+ 24 V

XU 1 - X U 4XU 13 - XU 16

T 04853 A

12345678

161514131211109

P1

FU S E E2

FU S E E13

1

2

T ER M IN ALB LO C K S

C O M

+

N OT E: D IPSH U N TS XU 5, XU 6, XU 8-XU 12 A R E N OT U SE D FO R TH E IM D S M 04. M A KE N O FIELD C O N N E C TIO N S TO TB 2 A N D T B3.

X U 7 C O N N EC T S 24 VD C I/O PO W ER TO T H E P R EA M P LIF IER O N T H E IM D SM 04 M O D U LE. IF N O P R EAM PLIF IER S U SED, D O N OT IN STALL X U 7.

+

X U 7

N /C

Page 38: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

IMDSO14

WBPEEUI260050A0 A - 5

IMDSO14

Figure A-9. Settings for IMDSO14 Powered from E1

Figure A-10. Settings for IMDSO14 Powered from E2

T 04843 A

12345678

161514131211109

P1

FU S E E2

FU S E E13

1

2

TER M IN A LBLO C KS

C O M

+

+LOA D

XU 1 - XU 16

T 04844 A

12345678

161514131211109

P1

FU S E E2

FU S E E13

1

2

TER M IN A LBLO C KS

C O M

+

+LOA D

XU 1 - XU 16

Page 39: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

A - 6 WBPEEUI260050A0

IMDSO15

IMDSO15

The digital output module IMDSO15 has specific connections to TB1 through TB4. Refer to Figure A-12 and Table A-1 for details.

Figure A-11. Settings for IMDSO14 Field Powered

T 04842 A

12345678

161514131211109

P1

FU S E E2

FU S E E13

1

2

TER M IN A LBLO C KS

C O M

+

JU M PER P O S ITIO NN OT IM PO RTA N T

+

LOA D

XU 1 - XU 16

+24 V

Figure A-12. Custom Relay Contact/Terminal Block Assignment for the IMDSO15

TE R M IN A LN U M B E R

D IP S H U N TU S E D

D IP S H U N TU S E D

D IP S H U N TU S E D

D IP S H U N TU S E DTB 4 TB 1TB 2TB 3

1

2X U 13

C O M 1 N C 3 N C 7 C O M 5

N O 1 C O M 4 C O M 8 N O 5

N C 1 N O 4 N O 8 N C 5

X U 1X U 5X U 9

X U 14 X U 2X U 6X U 10

X U 15 X U 3X U 7X U 11

X U 16 X U 4X U 8X U 12

3

4

5

6

7

8

C O M 2 N C 4 N C 8 C O M 6

C O M 3 C O M 7

N O 2 N O 6

N O 3 N O 7

N C 2 N C 6

T04905A

Page 40: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

IMDSO15

WBPEEUI260050A0 A - 7

Table A-1. Relay Contact Assignment for IMDSO15

SignalTerminal

No.

COM1 TB4-1

NO1 TB4-2

NC1 TB4-3

COM2 TB4-4

NO2 TB4-5

NC2 TB4-6

COM3 TB4-7

NO3 TB4-8

NC3 TB3-1

COM4 TB3-2

NO4 TB3-3

NC4 TB3-4

COM5 TB1-1

NO5 TB1-2

NC5 TB1-3

COM6 TB1-4

NO6 TB1-5

NC6 TB1-6

COM7 TB1-7

NO7 TB1-8

NC7 TB2-1

COM8 TB2-2

NO8 TB2-3

NC8 TB2-4

Page 41: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

A - 8 WBPEEUI260050A0

IMDSO15

Figure A-13. IMDSO15

Figure A-14. Settings for IMDSO15 XU8

T 04847 A

12345678

161514131211109

P 1

FU S E E2

FU S E E13

1

2

TER M IN A LBLO C KS

C O M

+

JU M PER P O S ITIO NN OT IM PO RTA N T

XU 1 - X U 6XU 9 - X U 10XU 13 - X U 16

XU 7 AN D X U 11 N OT U SED

T 04880 A

12345678

161514131211109

P 1

FU S E E2

FU S E E13

1

2

C O M

+

T ER M IN ALBLO C KS

+

XU 8

Page 42: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

IMFCS01

WBPEEUI260050A0 A - 9

IMFCS01

Figure A-15. Settings for IMDSO15 XU12

T 04881 A

12345678

161514131211109

P 1

FU S E E2

FU S E E13

1

2

C O M

+

T ER M IN ALBLO C KS

+

XU 12

Figure A-16. Settings for IMFCS01

T 04852A

12345678

161514131211109

P 1

FU S E E2

FU S E E13

1

2

T ER M IN ALB LO C KS

C O M

+

N OTE : D O N OT IN S TA LL D IPSH U N TS IN LO C ATIO N S XU 1-XU 12 AN D XU 14-XU 16

+

JU M PE R PO SIT IO NN OT IM PO RTA N T

XU 13

Page 43: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0

Page 44: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 B - 1

Appendix BTB1 Through TB4 Schematics

P1 ConnectionsTable B-1 defines the signal paths for P1.

Table B-1. Connector P1 Signal Paths

Pin Socket Jumper I/O Pin Socket Jumper I/O

1 XU13 J13 A1 19 XU11/XU12 J11/J12 A7/A8

2 XU13 J13 A1 20 XU11 J11 A7

3 XU14 J14 A2 21 XU8 J8 B8

4 XU14 J14 A2 22 XU12 J12 A8

5 XU15 J15 A3 23 XU1 J1 B1

6 XU15 J15 A3 24 XU1 J1 B1

7 XU16 J16 A4 25 XU2 J2 B2

8 XU16 J16 A4 26 XU2 J2 B2

9 NC 27 XU3 J3 B3

10 NC 28 XU3 J3 B3

11 NC 29 XU4 J4 B4

12 NC 30 XU4 J4 B4

13 XU9 J9 A5 31 XU5 J5 B5

14 E3 COM 32 XU5 J5 B5

15 NC 33 XU6 J6 B6

16 XU9 J9 A5 34 XU6 J6 B6

17 XU10 J10 A6 35 XU7/XU8 J7/J8 B7/B8

18 XU10 J10 A6 36 XU7 J7 B7

Page 45: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

B - 2 WBPEEUI260050A0

P3 Connections

P3 ConnectionsTable B-2 shows the cable pin connections from connector P3 of the I/O module to connector P1 of the termination unit.

Table B-2. Cable Connections for I/O Signals

NKTU01/NKTU11

P31 P12 P31 P12 P31 P12

1 1 6 17 11 27

A 2 F 18 M 28

2 3 7 19 12 29

B 4 H 20 N 30

3 5 8 21 13 31

C 6 J 22 P 32

4 7 9 23 14 33

D 8 K 24 R 34

5 13 10 25 15 35

E 16 L 26 S 36

NOTES:1. P3 on I/O module.

2. P1 on termination unit.

Page 46: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

TB1 Schematic

WBPEEUI260050A0 B - 3

TB1 Schematic

Figure B-1. TB1 Schematic

T04873A

12345678

161514131211109

P1

123

J1

+

2

1

TB 1

23

24

E 2

E 1

P39

K

B R N /B LK

O R N

XU 1

N KTU 01/N K TU 11

12345678

161514131211109

P1

123

J2

+

4

325

26

E 2

E 1

P310

L

B LK /R E D

O R N

XU 2

12345678

161514131211109

P1

123

J3

+

6

527

28

E 2

E 1

P311

M

B LU /R E D

O R N

XU 3

12345678

161514131211109

P1

123

J4

+

8

729

30

E 2

E 1

P312

N

Y E L/R E D

O R N

XU 4

Page 47: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

B - 4 WBPEEUI260050A0

TB2 Schematic

TB2 Schematic

Figure B-2. TB2 Schematic

T04874A

12345678

161514131211109

P 1

123

J5

+

2

1

TB 2

31

32

E 2

E 1

P 313

P

B R N /R E D

O R N

X U 5

N K TU 01/N K TU 11

12345678

161514131211109

P 1

123

J6

+

4

333

34

E 2

E 1

P 314

R

B LK /B LU

O R N

X U 6

12345678

161514131211109

P 1

123

J7

+

6

535

36

E 2

E 1

P 315

S

R E D /B LU

O R N

X U 7

12345678

161514131211109

123

J8

+

8

7

E 2

E 1 X U 8

P 1

21

P 3

8

Y E L/B LK

Page 48: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

TB3 Schematic

WBPEEUI260050A0 B - 5

TB3 Schematic

Figure B-3. TB3 Schematic

T 04875A

12345678

161514131211109

P 1

123

J9

+

2

1

TB3

13

16

E 2

E 1

P35

E

B R N

O R N

X U 9

N K TU 01 /N K TU 11

12345678

161514131211109

P 1

123

J10

+

4

317

18

E 2

E 1

P36

F

R E D /B LK

O R N

XU 10

12345678

161514131211109

P 1

123

J11

+

6

519

20

E 2

E 1

P37

H

B LU /B LK

O R N

XU 11

12345678

161514131211109

P 1

123

J12

+

8

722

E 2

E 1

P3

JO R N

XU 12

P 1

14

P3

N /CS H LD

E 1F 1

F 2 E 2

E 3

C O M

E 2

E 1

Page 49: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

B - 6 WBPEEUI260050A0

TB4 Schematic

TB4 Schematic

Figure B-4. TB4 Schematic

T04876A

12345678

161514131211109

P 1

123

J13

+

2

1

TB 4

1

2

E 2

E 1

P 31

A

B LK

O R N

X U 13

N K TU 01/N K TU 11

12345678

161514131211109

P 1

123

J14

+

4

33

4

E 2

E 1

P 32

B

R E D

O R N

X U 14

12345678

161514131211109

P 1

123

J15

+

6

55

6

E 2

E 1

P 33

C

B LU

O R N

X U 15

12345678

161514131211109

P 1

123

J16

+

8

77

8

E 2

E 1

P 34

D

Y E L

O R N

X U 16

Page 50: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0 Index - 1

Index

C

Checking connections .............................. 3-4Cleaning

Edge connectors.................................... 3-3Printed circuit boards ............................. 3-2

Conventions, documents .......................... 1-4

F

Field static kit ............................................ 2-1Fuse

Installation.............................................. 2-2Replacement.......................................... 4-1

H

How to use this instruction........................ 1-4

I

I/O wiring .................................................. 2-7Installation

Cables.................................................... 2-5Fuse....................................................... 2-2I/O wiring................................................ 2-7Power wiring .......................................... 2-6Termination unit ..................................... 2-4

M

Maintenance ............................................. 3-1Schedule................................................ 3-1Tools required........................................ 3-1

Mounting hardware................................... 1-3

N

Nomenclature............................................1-5

O

Overview ...................................................1-1

P

Parts list ....................................................4-1PCB cleaning ............................................3-2Power wiring..............................................2-6Preventive maintenance

Checking connections ............................3-4Schedule ................................................3-1Tools and equipment..............................3-1

R

Replacing fuses.........................................4-1

S

Setup/physical installation.........................2-2Special handling........................................2-1

T

Termination unitCables ....................................................2-5Dipshunt configuration ...........................2-2Installation ..............................................2-4Replacement ..........................................4-1

U

Unpacking and inspection.........................2-2User qualifications.....................................1-1

Page 51: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

WBPEEUI260050A0

Page 52: Digital I/O Termination Unit (NTDI02)...It provides a signal path between field I/O signals and the following I/O modules. •Analog output module (IMASO11). •Digital input module

Form WBPEEUI260050A0 Litho in U.S.A. Nov2001Copyright © 2001 by ABB, as an Unpublished Work, All Rights Reserved® Registered Trademark of ABB™ Trademark of ABB

For the latest information on ABB and Year 2000 Product Compatibility Visit us on the World Wide Web at http://www.abb.com

Our worldwide staff of professionals is ready to meet your needs for process automation. For the location nearest you, please contact the appropriate regional office.

GermanyIndustriestrasse 28D-65760 EschbornGermanyTelephone 49-6196-800-0Telefax 49-6196-800-1119

Europe, Africa, Middle EastVia Puccini 216154 Genoa, ItalyTelephone 39-010-6584-943Telefax 39-010-6584-941

Asia/Pacific539 Yishun Industrial Park ASingapore 768740Telephone 65-756-7655Telefax 65-756-7309

Americas29801 Euclid AvenueWickliffe, Ohio USA 44092Telephone 1-440-585-8500Telefax 1-440-585-8756