distributed generation protection eugeniusz roso protection ...• fault detection and fault removal...
TRANSCRIPT
Distributed Generation Protection
Eugeniusz Rosołowski
Protection and Controlof Distributed Energy Resources
Chapter 3
1. Introduction 3. Distributed Generation Protection
General Considerations
DG uses many forms of energy, such as wind, solar,biomass, hydroelectric, and fossil fuel energy.
During major system disturbances and blackouts, DGcan provide reliable on‐site generation that keepscritical loads in service.
Utilities typically prevent DG sources from feeding adisconnected section of the utility network afterutility system outage what results in islandingcondition.
2. Islanding Condition 3. Distributed Generation Protection
Islanding Condition
2. Islanding Condition 3. Distributed Generation Protection
Islanding Condition• When the utility breaker trips, the
DG source may continue supportingfault current and may also causeovervoltage in the network.
• Without utility network working inparallel, the DG source may notsatisfy quality standards and coulddamage customer equipment.
• Utility and DG equipment may sufferdamage if an asynchronous breakerreclosure occurs.
2. Islanding Condition 3. Distributed Generation Protection
Islanding Condition
• The continuity of service may be assured even duringislanding condition. As DG source control systemimprove, islanding operation will increasingly supportcontinuity of service.
• Successful islanded operation requires adaptive loadshedding to match DG to islanded load.
• Load shedding ‐ cutting off the electric load on certainlines/areas when the demand becomes greater thanthe supply.
3. Interconnection System 3. Distributed Generation Protection
Interconnection System• The interconnection system performs the functions
necessary to maintain the safety, power quality, andreliability of connected EPSs and DGs.
• System complexity depends on the level of interactionrequired between the DG and the EPS.
• Interconnection is not a simple issue.• Interconnection requirements are far from standard.
GUtility Grid
Coupling Point
DGInterconnection System
3. Interconnection System 3. Distributed Generation Protection
General Requirements• Protection must be provided for DG installations to
protect personnel, utility facilities, and equipment fromthe abnormal voltage and frequency that may occur whenthe DG is operating as an island.
• This protection must operate for short circuits, overloads,low or high voltage, and low or high frequency, and mustprevent out‐of‐phase reclosing and energization of a deadsupply line by the generator.
• The generator owner is responsible for the protection ofhis equipment, which is usually specified by his consultantor equipment manufacturer.
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection• Recent interest in distributed generator installation into
low voltage buses near electrical consumers, hascreated some new challenges for protection engineersthat are different from traditional radially basedprotection methodologies.
• Therefore, typical protection configurations need to bere-thought such as re-closures, out-of-step monitoring,impedance relay protection zones with the detection ofunplanned islanding of distributed generator systems.
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
Intertie protection requirements are influenced bythe size and characteristics of the DG, along with thecharacteristics of the associated utility supply system.
Large generators with utility transmission tie points• 10MVA or greater generators,• Usually dispatched directly with utility load dispatcher,• Relay protection and control as if it were part of the utility
system connected to transmission grid.
Generators with utility distribution tie points.
4. Intertie Protection 3. Distributed Generation Protection
Large Generator – Transmission Tie
G64KV and
Above
Utility Grid
Other Plant Loads
Point ofCommon Coupling
(PCC)
DG
4. Intertie Protection 3. Distributed Generation Protection
Small Generator – Distribution Tie
DG
64KV andAbove
Utility Grid
Tapped toRadial Distribution
Circuit
Transmission Distribution
13KV and Below
Radial Lines
PCC
• Transmission and Distribution kV levels vary
4. Intertie Protection 3. Distributed Generation Protection
Typical Utility Operation Requirements
• Maintain voltage ±10% approximately.• Maintain frequency ±0.1Hz approximately.• Power quality – Limits on voltage dips, sags, swells,
flicker and harmonics.• Minimize interference with communications
equipment. Outage times should be minimized.
4. Intertie Protection 3. Distributed Generation Protection
Typical Utility Operation
• Fault detection and fault removal promptly tominimize damage to equipment and voltagedistortions.
• Reclosing substation feeder breaker, as fast as 1/3second, to minimize outage times.
• Provide safe, de‐energized condition when dead linework is done or line is on the ground.
4. Intertie Protection 3. Distributed Generation Protection
Overcurrent Protection3-CT’s
3-PT’s
51N
1-PT
51
DG
PCC
51V
46UtilityBus
67
50
• Phase and ground overcurrent devices isolate DGfor faults on DG facility or on distribution system.• 67/67N may be used for anti-islanding in place of 32.• 51V may be optional to prevent nuisance 27 tripping.
4. Intertie Protection 3. Distributed Generation Protection
Voltage Protection
• UV and OV relays operate when voltage outside predetermines levelsand within predetermined times.
• UV relays have time delay to prevent unnecessary trips for externalfaults (may include inst 27R for very low levels)...
3-CT’s
3-PT’s
27
81O25
1-PT
47
DG
PCC
59TUtilityBus
27R59I81U
4. Intertie Protection 3. Distributed Generation Protection
Voltage Protection
• UV and OV relays operate when voltage outsidepredetermines levels and within predetermined times.
• UV relays have time delay to prevent unnecessary trips forexternal faults (may include inst 27R for very low levels).
• OV relays may include inst 59I for ferroresonance.• UF and OF relay levels operate when frequency outside
predetermined levels and within predetermined times.• 67/67N may be used for anti-islanding in place of 32.• 51V may be optional to prevent nuisance 27 tripping.
4. Intertie Protection 3. Distributed Generation Protection
Synchronizm
• Not required for induction generators or line commutatedinverters.
• Utility cannot synch to DG.• DG must not energize utility when utility is deenergized.
3-CT’s
3-PT’s
25
1-PT
DG
PCC
UtilityBus
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
• Manufacturers of Protective and Control Relays. This isthe most conventional and experienced source for thecontrol of DG protection. The protective relay industryhas supported the protection of transmission,distribution, and generation of electricity for many years.
• The relays are the main controlling elements ofinterconnection.
• For large DG systems connected at the transmissionlevel, the relaying design for interconnection is likelyintegrated into and coordinated with the existing designof transmission protection.
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
Conventional Independent Relaying Packages for Utility Feeder and Non-Utility Generators
UtilityBus DG
Distrib. Relays
EPS
End-use Load
Generator Relays
Interconnection equipment
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
• The distribution-feeder relay package and the generator-protection relay package can be provided by thetraditional protective relay industry.
• Paralleling control and transfer from utility to generatorsource may also be offered in this integrated package.
• This can add functionality while simplifying installationand reducing the overall cost of interconnection.
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
Integrated Distribution Feeder and Generator Protection in One Package
UtilityBus DG
Distribution Relays
EPS
End-use Load
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection – DG with Electronic Inverter
• In the case of smaller distributed generators that areinterconnected via an electronic inverter, the controlcapability of the inverter will play a role in making theconnection. In this case, the customer-side protectivefunctions can be completely addressed in the inverter.
• Depending on inverter size and design, a transformer maynot be required between the generator inverter and thelocal facility power system. If the inverter connection canbe made without a transformer and without additionalsynchronization and relaying protection, significantsavings in the interconnection costs can be realized.
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
Interconnection Functions Provided by Electronic Inverter and Transformer
UtilityBus DGEPS
End-use Load
In-verter
Interconnection equipment
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection – DG with Electronic Inverter
• If the inverter-connected DG is large compared to thelocally connected load, additional transformer isolationand additional relaying will likely be required.
• The protection is a hybrid between integrated inverter andseparate conventional relaying.
• In this case, a step-up isolation transformer is likely to berequired for both the load and the DG.
4. Intertie Protection 3. Distributed Generation Protection
Intertie Protection
Protection for a Large DG Inverter May Require for both Built-In and Conventional Relay Functions
UtilityBus DG
Distribution Relays
EPS
End-use Load
In-verter
Interconnection equipment
4. Intertie Protection 3. Distributed Generation Protection
DG - EPS Grid Interconnection Options
• No Interconnection - Complete Isolated Operation.• Isolated DG - Automatic Transfer to EPS.• Parallel DG Operation - No Power Export.• Parallel DG Operation with Power Export.
5. Loss of mains detection 3. Distributed Generation Protection
Anti-islanding Problem
The condition of islanding, defined as when a section of the non utility generation system
is isolated from the main utility system, is often considered undesirable because of:
• the potential damage to existing equipment,• utility liability concerns, • reduction of power reliability and• power quality.
5. Loss of mains detection 3. Distributed Generation Protection
Anti-islanding Problem
• If the total feeder load is approximately equal to DG output, then DG willtry to supply feeder load if utility feeder breaker trips.
• DG and Feeder are now islanded (loss of mains problem).• Can't close utility breaker without synch check (25).
LoadTotal
Utility Bus
Net Flow Zero
Utility Feeder
DG
3MVA
3MVA
5. Loss of mains detection 3. Distributed Generation Protection
Anti-islanding Problem
• If islanding did occur, to close thefeeder breaker would requiremonitoring the phase angleacross the breaker.
• The autosynchronizer (25A)would need to control voltageand frequency of the DG or theentire utility system. Notpractical.
• Islanding is usually avoided.
UtilityBus
Utility Feeder
DG
25A
Open
5. Loss of mains detection 3. Distributed Generation Protection
Anti-islanding Problem
Typical distributed system with DG’s
5. Loss of mains detection 3. Distributed Generation Protection
1. Active Islanding Detection Methods
a) Communication based scheme: transfer trip scheme
5. Loss of mains detection 3. Distributed Generation Protection
1. Active Islanding Detection Methods
Power Line signaling scheme
5. Loss of mains detection 3. Distributed Generation Protection
1. Active Islanding Detection Methods
b) Method of impedance measurement
5. Loss of mains detection 3. Distributed Generation Protection
1. Active Islanding Detection Impact
Degradation of power quality and system stability as DGpenetration becomes higher.Currently the local islanding detection methods virtuallyguarantee that the DG will be unable to provide gridsupport or improve grid stability when the grid is stressedanti-islanding protection disconnects the DG when itdetects voltage and frequency excursions on the grid.Because of the reclosing practice, anti-islandingtechniques must trip DG’s within about 200 millisecondsbefore the breaker is reclosed. Failure to do so will lead toout-of-phase re-energization of the DG.
5. Loss of mains detection 3. Distributed Generation Protection
2. Non-active (Passive) Islanding Detection Methods
a) Over/Under Voltage Amplitude (O/U VA)Islanding is detected when the amplitude of VMP is out ofpre specified interval of voltage amplitude.
UtilityBus
Utility Feeder
DG
Open
Measurement point, VMP
IDG
5. Loss of mains detection 3. Distributed Generation Protection
2. Non-active (Passive) Islanding Detection Methodsb) Over/Under Voltage Frequency (O/U VF) and Rate of
Change of Frequency (ROCOF).Islanding is detected when the amplitude of VMP is out of
pre-specified interval of voltage amplitude. A df/dt detectionmethod (ROCOF) might decrease the detection time andNon Detective Zone. The ROCOF relay is generallyaccepted as the standard method for islanding protectionof the distributed system. These relays monitor the voltagewaveform, and operate when the rate-of-change offrequency exceeds a setting and duration exceeds a timedelay setting.
5. Loss of mains detection 3. Distributed Generation Protection
2. Non-active (Passive) Islanding Detection Methodsc) Voltage Phase Jump (VPJ).The phase difference between VMP and IDG is monitored. VMPwill jump in phase if IUtility ≠ 0 at the instant of islandingoccurs.d) Impedance measurement.Change of positive or negative sequence impedance isapplied for islanding detection.e) Mixture of some sellected methods is applied
(multicriteria method).Multicriteria decision making algorithm is needed forselection the final signal.
5. Loss of mains detection 3. Distributed Generation Protection
Anti-islanding Protection - example
DG
PCC
UtilityBus
TransferTrip
TransmitTT
Rec.
Trip
52b
3-PT’s
81O81U32
3-CT’s
27 59
• OF and UF used with load shedding for anti-islanding.• OV and UV trip for faults on distribution feeder.• 32 trips for export of power (may be specific level).• DG must consider utility reclosing to ensure clearing prior
to reclose.
6. Protection Issues 3. Distributed Generation Protection
DG Impact on Protection and Reclosing
DG must be disconnected here
6. Protection Issues 3. Distributed Generation Protection
DG Impact on Protection and Reclosing
The total fault current is composed of the followingcontributions from both the source IB and the distributedgeneration current IDB. The Relay B measures only current IBwhat reduces protected zone (relay under-reach).
5. Generator Protection 3. Distributed Generation Protection
Type of Generation
•Rotating machine - speed controlled to matchutility 50/60 Hz
- Synchronous - capable of supplying load as anindependent source with voltage and frequencycontrol.- Induction - cannot operate alone since it gets itsexcitation from the ac system to which it isconnected.- May be single phase or three phase
5. Generator Protection 3. Distributed Generation Protection
Type of Generation
Permanent Magnet Synchronous Generator
5. Generator Protection 3. Distributed Generation Protection
Type of Generation
Dobly Feed Induction Generator
5. Generator Protection 3. Distributed Generation Protection
Type of Generation
• Power inverters change DC to ACelectronically. The DC source could bebatteries, fuel cells or photovoltaic panels.
-Line commutated inverters need an externalsource of reactive power to operate and wouldnormally shut down when the utility tie opens.- Self commutated inverters can continue to supplypower independently and do not require a sourcefrom the utility. These inverters should be trippedwhen the utility tie opens.
5. Generator Protection 3. Distributed Generation Protection
Type of Generation
Power inverters change DC to ACelectronically. The DC source could bebatteries, fuel cells or change non-50Hzgeneration to 50Hz power. The AC sourcecould be micro-turbines generating 400Hz.
-These Static Power Converters can synchronize tothe 50Hz utility system faster than a synchronousgenerator where the excitation must be controlledto match voltage and frequency of the utility.- These static power converters are also known asisochronous generators.
5. Generator Protection 3. Distributed Generation Protection
Converters connected Generation