distribution system control strategies. tank management/operations flushing rerouting water ...
TRANSCRIPT
Distribution System Control Strategies
Distribution System Control Strategies
Tank Management/Operations
Flushing
Rerouting Water
Others
optimizing existing booster chlorination (operation, control)
system modifications
tank modifications to enhance mixing, remove DBPs, adding booster chlorination
capital improvements after O&M options are exhausted/evaluated
Tank Management/Operations
Basis for Considering: Tank spreadsheet estimates tank to have:
High water age
Poor mixing
Poor water quality based on sampling: In tank
Immediate vicinity of tank
Other options exist to provide system pressure (i.e., multiple tanks serve same
area, booster pump station, etc.).
Concerns/Implementation Considerations: Maintaining system pressure.
Ability to satisfy peak demands (e.g., fire protection, line breaks, and seasonal
variations).
Drawing tank down (at least initially) may release poor water quality into the
system.
Tank
Man
agem
ent/
Ope
ratio
ns Level Modification
Change Fill Rate/Duration
Lower Max Level
Lower Min Level
Lower Both Levels
Faster Rate/ Shorter Duration
Slower Rate/Longer Duration
Remove Tank From Service
Tank Level Modification
Lower Max Level Lower Min Level Lower Both Levels
Pros• Lowers water age (due
to reduced volume in tank)
• Maintains minimum system pressure
Cons• Less water for
fires/emergencies
• Possibly reduces mixing
Pros• Lowers water age
• Improves mixing
Cons• Less water for
fires/emergencies
• Lowers minimum system pressure
Pros• Lowers water age
• May improve mixing (depends on level fluctuation)
Cons• Lowers minimum
system pressure
• Less water for fires/emergencies
Change Tank Fill Rate/Duration
Longer Fill Duration / Slower Fill Rate
Shorter Fill Duration /Faster Fill Rate
Pros• Increased water velocity to improve
mixing
• Tank filled fasterCons• Energy use considerations
• Uncertain impact on water quality
• Less water for fires/ emergencies
• Potential wear on control valve
• May not fill tank before next demand cycle
Pros• Longer mixing time
• Less stress on water mains
Cons• Energy use considerations
• Uncertain impact on water quality
• Possible over-pressurization of water mains
• Possible increased power bill
• May not fill tank before next demand cycle
Remove Tank from Service
Cons• Possible reduced system pressure.
• Less water for fires/emergencies.
• Possible change in ISO rating when re-evaluated.
• Transferring demand to another tank could be a problem.
• Increased energy costs (i.e., pumping costs).
• Empty storage tanks are more vulnerable to weather (especially wind).
Pros• Lowers overall water age in system.
• Transfers demand to another tank (may improve operations of that tank).
Operational Data
Water Quality Data
Flushing
Basis for Considering: Lower disinfectant residuals High disinfection byproducts Area is not influenced by a tank or tank operations cannot be
altered Dead-ends:
Physical Hydraulic
Concerns/Implementation Considerations: Lost revenue Discharge issues (e.g., dechlorination, water conservation)
Hydraulic limitations (e.g., pressure)
Flu
shin
g Unidirectional
Automatic
Blow-Off
Conventional
Flushing – Conventional
Cons• Labor intensive.
• Usually involves large volumes of water, relative to automated flushing.
• Can cause discolored water due to typical high water velocity.
• Usually not metered.
Pros• Immediate water quality improvement.
• Can obtain water quality data over time of flush.
• Can clean/scour the water main.
• Visual verification of water quality.
Flushing – Unidirectional
Cons• Very time intensive/consuming.
• Usually involves large volumes of water, although tends to be less than conventional flushing.
Pros• Immediate water quality improvement.
• Scours/cleans biofilm and debris from mains.
• Controlled flushing, should not disturb adjacent lines.
• Can target specific flushing concerns.
• May reduce chlorine demand and DBP precursors in area.
• May use less water than conventional flushing.
Flushing – Automatic
Cons• Typically, no water quality data is collected except for when
visited (monthly or less).
• Can be tampered with.
• Discharge issues (e.g., dechlorination and erosion).
• “Good” citizens (turning them off).
• If they fail, you don’t know until you visit the station.
Pros• Localized water quality improvement.
• Not labor intensive once installed.
• Water is typically metered.
• Flow is typically slow enough to avoid discolored water issues.
• Some installations can be hidden.
• Easy to control amount of water flushed.
• Reliable designs exist.
Flushing – Blow-off
Cons• Typically no water quality data is collected except for when
visited (monthly or less).
• Can be tampered with.
• Discharge issues.
• “Good” citizens (turning them off).
• If they fail, you don’t know until you visit the station.
• Usually forgotten about.
Pros• Immediate water quality improvement.
• Constantly moving water.
• Flow is typically slow enough to avoid discolored water issues.
Rerouting Water
Basis for Considering: Lower disinfectant residuals
High disinfection byproducts
Parallel lines and/or functional valves exist: to allow for changing the flow of water into/out of an area
to allow for a line to be taken out of service
single line capacity can handle required flow
Concerns/Implementation Considerations: May move problem from one area to another
Flushing may still be needed
Rer
outin
g W
ater
Parallel Lines
Valve Changes
Rerouting Water – Parallel Lines
Cons• One or more of the pipes is not in good condition.
• Required flow may be too much for one line to handle by itself.
• Must maintain adequate fire protection.
• Connecting the two lines could be difficult and/or expensive:• Required permits• Distance• Rock
Pros• Valve & reroute (assumes two different size parallel lines – i.e., 6” and 3”):
• majority of flow can be handled by larger line, reducing stress on smaller line.
• Rerouting flow through the larger line and into the smaller line helps keep water moving.
• Remove a line from service: reduce underground storage (water age).
Rerouting Water – Valve Changes
Cons• Sufficient valves do not exist or locations of valves are unknown.
• Valves are old and may break when operated.
• No connection to other sections of the system.
• Line sizes are small and cannot handle the additional flow.
• If insufficient records are kept, problems could arise (i.e., hydraulic “bottleneck,” inadvertently opening the valve, etc.).
Pros• Sufficient control valves exist.
• Connections exist or are close enough to connect other areas of the system together.
• Lines are of sufficient size to handle the additional flow.
• Can reroute water through low demand areas, towards high demand area, to keep water moving.
“Others”optimize booster chlorination, capital improvements
Not “primary strategies” because they are system- specific
(i.e., optimize booster chlorination) or not true optimization
strategies (i.e., cost $$).
Optimizing booster chlorination. Basis to consider:
System has booster chlorination and process monitoring/control capability.
Lower (or higher) disinfectant residuals in area of system influenced by
booster chlorine station.
Concerns/Implementation Considerations: May elevate DBP formation.
May still have high water age (i.e., require additional strategies discussed
previously).
“Others”optimize booster chlorination, capital improvements
Capital improvements may include: Adding a mixer in a tank
DBP control in the distribution system
Adding booster chlorination
Others(?)
Should be considered advanced strategies once optimization (O&M) options are exhausted.
Questions?