CPV Valley Energy Center 50 Braintree Hill Office Park Suite 300 Braintree, MA 02184 February 27, 2019 Mr. Christopher M. Hogan Chief, Major Project Management Unit New York State Department of Environmental Conservation Division of Environmental Permits 625 Broadway, 4 th Floor Albany, New York 12233-1750 Re: CPV Valley, LLC Title V and Title IV Air Permit Applications Dear Mr. Hogan: As discussed with Randy Orr, Andrew Chin, and Amit Chakraborti, CPV Valley, LLC (“CPV Valley”) noted some anomalies in the stack test results which were previously submitted to the Department for particulate matter while the facility was running on natural gas. As a result, CPV Valley retested for particulate matter while the facility was running on natural gas on February 8 -10, 2019. Enclosed please find the Test Report and backup data from Air Hygiene dated February 26, 2019 for the Method 201A and Method 202 retest on natural gas. As previously stated, CPV Valley respectfully submits that this information is in the nature of supplemental information to assist the Department in its review of the Title V permit application, and as a result, CPV Valley is entitled to the benefit of the application shield contained in Environmental Conservation Law § 19-0311(5)(b) and guidance issued by the Environmental Protection Agency (“EPA”) implementing the Title V application shield. Please feel free to contact me should you have any questions. Very truly yours, Donald G. Atwood DGA/rel enclosures

Upload: others

Post on 16-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Division of Environmental Permits Floor

C P V V a l l e y E n e r g y C e n t e r 5 0 B r a i n t r e e H i l l O f f i c e P a r k

S u i t e 3 0 0 B r a i n t r e e , M A 0 2 1 8 4

February 27, 2019 Mr. Christopher M. Hogan Chief, Major Project Management Unit New York State Department of Environmental Conservation Division of Environmental Permits 625 Broadway, 4th Floor Albany, New York 12233-1750 Re: CPV Valley, LLC Title V and Title IV Air Permit Applications Dear Mr. Hogan: As discussed with Randy Orr, Andrew Chin, and Amit Chakraborti, CPV Valley, LLC (“CPV Valley”) noted some anomalies in the stack test results which were previously submitted to the Department for particulate matter while the facility was running on natural gas. As a result, CPV Valley retested for particulate matter while the facility was running on natural gas on February 8 -10, 2019. Enclosed please find the Test Report and backup data from Air Hygiene dated February 26, 2019 for the Method 201A and Method 202 retest on natural gas.

As previously stated, CPV Valley respectfully submits that this information is in the nature of supplemental information to assist the Department in its review of the Title V permit application, and as a result, CPV Valley is entitled to the benefit of the application shield contained in Environmental Conservation Law § 19-0311(5)(b) and guidance issued by the Environmental Protection Agency (“EPA”) implementing the Title V application shield. Please feel free to contact me should you have any questions. Very truly yours,

Donald G. Atwood DGA/rel enclosures

Page 2: Division of Environmental Permits Floor

2

cc: George Sweikert, RAPCE, Region 3 Kelly Turturro, Regional Director, Region 3 Khai Gibbs, Esq. Mark Sanza, Esq. Randy Orr, DEC HQ Ruth Leistensnider, Esq. Ben Stanley, DGC Ops

Sarasi Sam, DGC Ops

Page 3: Division of Environmental Permits Floor

(918) 307-8865 or (888) 461-8778 www.airhygiene.com

Corporate Headquarters 1600 W Tacoma Street Broken Arrow, OK 74012

Remote Testing Offices Las Vegas, NV 89156 Ft. Worth, TX 76028 Humble, TX 77338 Shreveport, LA 71115 Miami, FL 33101 Pittsburgh, PA 15205

February 26, 2019 Jordan M. Haywood, MS, PE, QEP Fellow Engineer – Technical Group Lead Environmental Engineering Siemens Energy, Inc. 4400 Alafaya Trail, MC Q2-286 Orlando, Florida 32826-2399 Re: CPV Valley Energy Center – Natural Gas Particulate Retest Mr. Haywood, Please find the attached report presenting the Natural Gas Particulate Results from Units 11 and 12 obtained during the February 8-10, 2019 testing event. The results of all measured pollutant emissions were below the required limits. All testing was performed without any real or apparent errors and testing was conducted according to the approved testing protocol. Slightly negative filter weights were obtained for all but one of the runs; therefore, the Reportable Detection Limit (RDL) of 0.3mg was used to calculate the emission rates in the report. This approach provides a conservative compliance demonstration. Each individual filter weight is presented in the table below along with the total blank adjusted weights for the Method 201A PM2.5 fraction. U 11 U12 Filter (mg) Total PM 2.5 (mg) Filter (mg) Total PM 2.5 (mg) Base-R1 -0.5 1.07 Base-R1 -1.3 1.17 Base-R2 -0.2 1.67 Base-R2 -0.6 0.97 Base-R3 -1.1 0.17 Base-R3 -0.4 1.66 Base wDB-R1 -0.3 1.38 Base wDB-R1 -0.2 0.97 Base wDB-R2 -1.1 0.07 Base wDB-R2 -0.1 1.57 Base wDB-R3 -0.5 2.17 Base wDB-R3 -0.2 2.28 Please contact me anytime with questions or comments and reports can be updated upon your request. Sincerely,

Paul R. Little, QSTI Director of Customer Service Air Hygiene, Inc. [email protected]

Page 4: Division of Environmental Permits Floor

EMISSION COMPLIANCE TEST ON NATURAL GAS FUEL

FOR THE SIEMENS, SCC6-5000F, UNIT

#CTG-11 AND CTG-12 PREPARED FOR

CPV VALLEY, LLC AT THE

CPV VALLEY ENERGY CENTER MIDDLETOWN, NY

FEBRUARY 8-10, 2019

Permit No: 3-3356-00136/00001

Page 5: Division of Environmental Permits Floor

EMISSION COMPLIANCE TEST ON NATURAL GAS FUEL

FOR THE SIEMENS, SCC6-5000F, UNIT

#CTG-11 AND CTG-12 PREPARED FOR

CPV VALLEY, LLC AT THE

CPV VALLEY ENERGY CENTER MIDDLETOWN, NY

FEBRUARY 8-10, 2019

Prepared and Reviewed by: Thomas K. Graham, PE, QSTI Logan Tsotsoros Director of Education AHU Support Staff

I, Todd R. Sturgeon, QSTI Cole McBride, QSTI Sr. Manager – Test Reports Sr. Project Manager certify that this testing was conducted and this report was created in conformance

with the requirements of ASTM D7036

Page 6: Division of Environmental Permits Floor

(this page intentionally left blank)

Page 7: Division of Environmental Permits Floor

Created with Report-AHI v20181109 i

Table of Contents

1.0  INTRODUCTION __________________________________________________________________ 1 

1.1  TEST PURPOSE AND OBJECTIVES ______________________________________________________ 1 

1.2  SUMMARY OF TEST PROGRAM _________________________________________________________ 1 1.2.1  Participating Organizations ________________________________________________________________________ 1 1.2.2  Industry _______________________________________________________________________________________ 1 1.2.3  Air Permit Requirements __________________________________________________________________________ 1 1.2.4  Plant Location __________________________________________________________________________________ 1 1.2.5  Equipment Tested _______________________________________________________________________________ 1 1.2.6  Emission Points _________________________________________________________________________________ 2 1.2.7  Emission Parameters Measured ____________________________________________________________________ 2 1.2.8  Dates of Emission Test ___________________________________________________________________________ 2 1.2.9  Federal Certifications ____________________________________________________________________________ 2 

1.3  KEY PERSONNEL ______________________________________________________________________ 2 

2.0  SUMMARY OF TEST RESULTS ____________________________________________________ 2 

3.0   SOURCE OPERATION_____________________________________________________________ 3 

3.1  PROCESS DESCRIPTION _______________________________________________________________ 3 

3.2  SAMPLING LOCATION __________________________________________________________________ 3 

4.0   SAMPLING AND ANALYTICAL PROCEDURES ______________________________________ 4 

4.1   TEST METHODS ________________________________________________________________________ 4 

4.2  INSTRUMENT CONFIGURATION AND OPERATIONS FOR GAS ANALYSIS __________________ 4  APPENDICES Appendix A Test Results and Calculations Appendix B Emission Data Records Appendix C Calibration Gas Certifications Appendix D Quality Assurance and Quality Control Data Appendix E Fuel Analysis Records Appendix F Equipment Calibration Records

Page 8: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1 1

Emissions Compliance Test on Natural Gas Fuel

Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12 CPV Valley, LLC

CPV Valley Energy Center Middletown, NY

February 8-10, 2019

1.0 INTRODUCTION Air Hygiene International, Inc. (Air Hygiene) has completed the Emissions Compliance Test for particulate matter (PM) and opacity / visual emissions (VE) from the exhaust of the Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12 for CPV Valley, LLC at the CPV Valley Energy Center in Middletown, NY. This report details the background, results, process description, and the sampling/analysis methodology of the stack sampling survey conducted on February 8-10, 2019. 1.1 TEST PURPOSE AND OBJECTIVES The purpose of the test was to conduct a repeat of the initial compliance emission test to document levels of selected pollutants at base load and base load wDB on natural gas. The information will be used to confirm compliance with the operating permit issued by the New York Department of Environmental Conservation (NYDEC). The specific objective was to determine the emission concentration of PM, flow, VE, H₂O, CO₂, and O₂ from the exhaust of CPV Valley, LLC’s Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12. 1.2 SUMMARY OF TEST PROGRAM The following list details pertinent information related to this specific project:

1.2.1 Participating Organizations New York Department of Environmental Conservation (NYDEC) CPV Valley, LLC Siemens Energy, Inc. Air Hygiene

1.2.2 Industry Electric Utility / Electric Services

1.2.3 Air Permit Requirements Permit Number: 3-3356-00136/00001

1.2.4 Plant Location CPV Valley Energy Center in Middletown, NY GPS Coordinates [Latitude 41.14750, Longitude -80.85333] Physical Address: 3330 U.S. Route 6, Middletown, New York 10940 Federal Registry System / Facility Registry Service (FRS) No. – 110043332471 Source Classification Code (SCC)

20100201 (CTGs) 10100601 (DBs)

1.2.5 Equipment Tested Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12

Page 9: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1 2

1.2.6 Emission Points Exhaust from the Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12 For all gases (CO2, and O2), one sample point in the exhaust duct from the Siemens, SCC6-

5000F, Unit #CTG-11 and CTG-12 For all PM testing, 12 sampling points in the exhaust duct from the Siemens, SCC6-5000F,

Unit #CTG-11 and CTG-12 1.2.7 Emission Parameters Measured

PM Flow VE (Opacity) H2O CO2 O2

1.2.8 Dates of Emission Test February 8-10, 2019

1.2.9 Federal Certifications Stack Testing Accreditation Council AETB Certificate No. 3796.02 International Standard ISO/IEC 17025:2005 Certificate No. 3796.01

1.3 KEY PERSONNEL CPV Valley, LLC: Ben Stanley ([email protected]) 845-649-8300 Siemens Energy, Inc.: Jordan Haywood ([email protected]) 407-736-3045 Air Hygiene: Cole McBride ([email protected]) 918-307-8865 Air Hygiene: Sean Barnes 918-307-8865 Air Hygiene: Miguel Jimenez Martinez 918-307-8865 Air Hygiene: Axel Garrido Martinez 918-307-8865 Air Hygiene: Dana Albert 918-307-8865 2.0 SUMMARY OF TEST RESULTS Results from the sampling conducted on CPV Valley, LLC’s Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12 located at the CPV Valley Energy Center on February 8-10, 2019 are summarized in the following table and relate only to the items tested.

Page 10: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1 3

ParameterBase Load

CTG-11Base Load

wDB CTG-11Base Load

CTG-12Base Load

wDB CTG-12PermitLimits

Stack Flow (M2) (DSCFH) 51,628,702 49,489,969 51,299,918 48,947,815 --

Stack Moisture (% Method 4) 7.7 8.4 7.3 8.4 --

Total PM (mg) 4.14 6.97 4.63 4.80 --

Total PM (g/dscf) 4.80E-05 8.63E-05 5.45E-05 5.83E-05 --

Total PM (gr/dscf) 7.41E-04 1.33E-03 8.41E-04 8.99E-04 --

Total PM (kg/hr) 2.46 4.25 2.79 2.85 --

Total PM (lb/hr) 5.42 9.37 6.16 6.29 --

Total PM (ton/year) at 8760 hr/year 23.76 41.06 26.96 27.56 --

Total PM (lb/MMBtu) 0.0026 0.0041 0.0029 0.0028 0.0073

Total PM (mg/Nm3) 1.695 3.046 1.924 2.058 --

CO₂ (%) 4.40 5.00 4.20 4.67 --

O₂ (%) 13.50 12.60 13.40 12.75 --

TABLE 2.1SUMMARY OF SIEMENS, SCC6-5000F, NATURAL GAS RESULTS

The results of all measured pollutant emissions were below the required limits. All testing was performed without any real or apparent errors. All testing was conducted according to the approved testing protocol. On all runs where filter weights are below the Reportable Detection Limit (RDL) of 0.30mg, the RDL was used to determine the PM emissions rates. 3.0 SOURCE OPERATION 3.1 PROCESS DESCRIPTION The CPV Valley Energy Center is located at 3330 U.S. Route 6 in Middletown, New York. CPV Valley Energy Center is an electric generation facility. The facility consists of two Siemens SCC6-5000F Combined Cycle Combustion Turbines (CTGs), designated as CTG-11 and CTG-12. Each CTG is rated for the turbine at 2,234 million British thermal units per hour (MMBtu/hr) based on higher heating value (HHV) on natural gas; and 2,145 MMBtu/hr (HHV) on ultra-low sulfur diesel (ULSD) fuel oil; and is rated at 500 MMBtu/hr on natural gas for the duct burner (DB). The CTGs are equipped with dry low NOx combustors, selective catalytic reduction (SCR), and catalytic oxidizers. 3.2 SAMPLING LOCATION The stacks are vertical, circular, and measure 19 feet (ft) (228 inches) in diameter at the test ports which are approximately 175 ft above grade level with an exit elevation of approximately 275 ft above grade level. The test ports are located approximately 91.25 ft (1,095 inches) downstream and approximately 100 ft (1,200 inches) upstream from the nearest disturbances. All exhaust samples for gaseous emissions were continuously drawn from the exhaust system at the sample ports from a single point. For PM testing, an initial velocity traverse was performed across the stack from 12 total points. All PM sampling occurred from the same 12 points by leaving the probe at each for an equal amount of time in order to draw an isokinetic and representative sample.

Page 11: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1 4

4.0 SAMPLING AND ANALYTICAL PROCEDURES 4.1 TEST METHODS The emission test on the Siemens, SCC6-5000F, Unit #CTG-11 and CTG-12 at the CPV Valley Energy Center was performed following United States Environmental Protection Agency (EPA) methods described by the Code of Federal Regulations (CFR). Table 4.1 outlines the specific methods performed on February 8-10, 2019.

TABLE 4.1 SUMMARY OF SAMPLING METHODS

Pollutant or Parameter Sampling Method Analysis Method

Sample Point Location EPA Method 1 Equal Area Method

Stack Flow Rate EPA Method 2 S-Type Pitot Tube

Oxygen EPA Method 3A Paramagnetic Cell

Carbon Dioxide EPA Method 3A Nondispersive Infrared Analyzer

Stack Moisture Content EPA Method 4 Gravimetric Analysis

Opacity EPA Method 9 Visual Observation

Particulate Matter EPA Method 201A Front Half Filterables

Particulate Matter EPA Method 202 Back Half Condensables

4.2 INSTRUMENT CONFIGURATION AND OPERATIONS FOR GAS ANALYSIS The sampling and analysis procedures used during these tests conform with the methods outlined in the Code of Federal Regulations (CFR), Title 40, Part 60, Appendix A, Methods 1, 2, 3A, 4, 9; 40 CFR 51, Appendix M, Methods 201A and 202. Figure 4.1 depicts the sample system used for the real-time gas analyzer tests. The gas sample was continuously pulled through the probe and transported, via heat-traced Teflon® tubing, to a stainless steel minimum-contact condenser designed to dry the sample. Transportation of the sample, through Teflon® tubing, continued into the sample manifold within the mobile laboratory via a stainless steel/Teflon® diaphragm pump. From the manifold, the sample was partitioned to the real-time analyzers through rotameters that controlled the flow rate of the sample. Figure 4.1 shows that the sample system was also equipped with a separate path through which a calibration gas could be delivered to the probe and back through the entire sampling system. This allowed for convenient performance of system bias checks as required by the testing methods. All instruments were housed in an air-conditioned, trailer-mounted mobile laboratory. Gaseous calibration standards were provided in aluminum cylinders with the concentrations certified by the vendor. EPA Protocol No. 1 was used to determine the cylinder concentrations where applicable (i.e. NOx calibration gases).

Page 12: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1 5

Table 4.2 provides a description of the analyzers used for the instrument portion of the tests. All data from the continuous monitoring instruments were recorded on a Logic Beach Portable Data Logging System which retrieves calibrated electronic data from each instrument every one second and reports an average of the collected data every 30 seconds. Figure 4.2 represents the sample system used for the PM tests. The sample system included a heated stainless steel probe sheath with a glass liner and nozzle. The nozzle and probe assembly were inserted into the sample ports of the stack to extract gas measurements from the emission stream through a filter and glass impinger train in an isokinetic fashion. Differential pressure was monitored with S-type Pitot tubes and oil filled manometers. Total sample volumes were measured with dry gas meters. The resulting Method 2 velocity heads were combined with Method 3A (molecular weight) and Method 4 (moisture content) data to determine the stack gas volumetric flow rates. These results were combined with pollutant concentrations (i.e. mg/scf, parts per million, etc.) to determine emission rates (i.e. pounds per hour). Per the requirements of Method 202, the back half of the test train included a condenser and dry impinger train configuration. Sample collection included a nitrogen purge and hexane rinse. Glassware that was used to collect and analyze Method 202 condensable particulate samples was cleaned prior to the test with soap and water, and rinsed using tap water, deionized water, acetone, and finally, hexane. After cleaning, Air Hygiene incorporated a glassware bake at 300° C for six hours rather than the alternative of collecting a field train proof blank. During testing the temperature of the CPM filter assembly was maintain as close as possible to 85° F in accordance with EPA Method 202. The stack gas analysis for O2 and CO2 concentrations was performed in accordance with procedures set forth in EPA Method 3A. The O2 analyzer uses a paramagnetic cell detector and the CO2 analyzer uses a continuous nondispersive infrared analyzer.

TABLE 4.2 ANALYTICAL INSTRUMENTATION

Parameter Manufacturer

and Model Range Sensitivity Detection Principle

CO2 SERVOMEX

1440 0-20% 0.1% Nondispersive infrared

O2 SERVOMEX

1440 0-25% 0.1% Paramagnetic cell, inherently linear.

Page 13: Division of Environmental Permits Floor

E:\S

HA

RE

D\D

RA

WIN

GS

\EM

ISS

ION

S T

ES

TIN

G L

AB

.PP

T

04/

18/0

8

DR

AW

ING

:08-

001

T

KG

CO

PY

RIG

HT

©20

11 A

IR H

YG

IEN

E I

NT

ER

NA

TIO

NA

L, IN

C.

Fig

ure

4.1

EM

ISS

ION

S T

ES

TIN

G L

AB

1600

W T

acom

a S

tree

t B

roke

n A

rrow

, Okl

ahom

a 74

012

ww

w.a

irhyg

iene

.com

(888

) 46

1-87

78

STACK EXHAUST

dual line heated sample umbilical

FLOW CONTROL MANIFOLD

GAS CONDITIONER

CALIBRATION/BIAS GAS BOTTLES

HO

T/W

ET

AN

ALY

ZE

RS

DA

TA

RE

CO

RD

ER

VE

NT

Sho

wn

fully

equ

ippe

d.

Som

e la

bs m

ay n

ot c

onta

in t

hese

fea

ture

s an

d ot

hers

may

con

tain

add

ition

al f

eatu

res

spec

ific

to c

erta

in s

cope

s.

CO

LD/D

RY

AN

ALY

ZE

RS

O2,

CO

2, N

Ox,

CO

, SO

2

TH

C, V

OC

G

AS

DIL

UT

ER

FT

IR

TE

ST

TR

AIL

ER

EX

TE

RIO

RT

ES

T T

RA

ILE

R IN

TE

RIO

R

PROBE

HEATED PROBE FILTER

Hea

ted

Tef

lon

Tub

ing

(pre

-con

ditio

ned

sam

ple)

Unh

eate

d T

eflo

n T

ubin

g (c

ondi

tione

d sa

mpl

e)

Dilu

ted

Cal

ibra

tion

Gas

Cal

ibra

tion

Gas

Ele

ctro

nic

Inpu

t/O

utpu

t

LEGEND

COMPUTER

PROCESS INLETOR 2ND STACK

dual line heatedsample umbilical

PROBE

HEATED PROBE FILTER

VE

NT

MA

NIF

OLD

CO

LD/D

RY

AN

ALY

ZE

RS

HO

T/W

ET

O2,

CO

2, N

Ox,

CO

, SO

2

TH

C, V

OC

CONDITIONER

MO

BIL

ES

EC

ON

DA

RY

AN

ALY

ZE

RS

FIX

ED

PR

IMA

RY

AN

ALY

ZE

RS

Page 9 of 431

Page 14: Division of Environmental Permits Floor

E:\S

HA

RE

D\D

RA

WIN

GS

\SA

MP

LIN

G T

RA

IN –

OT

M 2

7 an

d 28

.PP

T

10/

2910

D

RA

WIN

G:1

0-05

1

TK

GC

OP

YR

IGH

T ©

2011

AIR

HY

GIE

NE

IN

TE

RN

AT

ION

AL,

INC

.

Fig

ure 4.

2M

ET

HO

D 2

01a/

202

AS

SE

MB

LY

1600

W T

acom

a S

tree

t B

roke

n A

rrow

, Okl

ahom

a 74

012

ww

w.a

irhyg

iene

.com

(888

) 46

1-87

78

Tem

pera

ture

Sen

sor

Pro

be

Typ

e S

Pito

t Tub

e

Sta

ckW

all

Tem

pera

ture

Sen

sor

Typ

e S

Pito

tT

ube

Tem

pera

ture

Sen

sor

Line

r(i

ncon

el)

Pro

beH

ousi

ng(h

eate

d)

Impi

nger

s

Tem

pera

ture

Sen

sor

Filt

erH

olde

r

Hot

BoxH

eate

d A

rea

Col

d B

ox

Ice

Wat

erB

ath

Vac

uum

Line

Vac

uum

Gau

ge

Mai

nV

alve

Air-

Tig

htP

ump

By-

pass

Val

ve

Dry

Gas

Met

er

Tem

pera

ture

Sen

sor

Tem

pera

ture

Sen

sor

Orif

ice

Oil-

Fill

erM

anom

eter

Oil-

Fill

erM

anom

eter

Wet

Che

mis

try

Ass

embl

y(p

hoto

)

Vie

w o

f P

robe

End

(fro

m th

e bo

ttom

)

Con

dens

er

Rec

irc.

pum

p

Gla

ssF

ilter

Hol

der

Noz

zle

Page 10 of 431

Page 15: Division of Environmental Permits Floor

APPENDIX A

TEST RESULTS AND CALCULATIONS

Page 16: Division of Environmental Permits Floor

Unit Load Component Run Date Start Stop Time Sync

CTG-11 Base Preliminaries 11-PM-Base-V1 02/09/19 8:14:00 8:28:00 DAHS

CTG-11 Base Particulates 1-PM-Base-1 02/09/19 9:22:00 13:33:00 DAHS

CTG-11 Base Particulates 1-PM-Base-2 02/10/19 8:28:00 12:35:00 DAHS

CTG-11 Base Particulates 1-PM-Base-3 02/10/19 12:26:00 16:36:00 DAHS

CTG-11 Base w/db Preliminaries 1-PM-Base wDB-V1 02/08/19 8:14:00 8:33:00 DAHS

CTG-11 Base w/db Particulates 1-PM-Base wdb-1 02/08/19 9:24:00 13:44:00 DAHS

CTG-11 Base w/db Particulates 1-PM-Base wdb-2 02/08/19 13:52:00 17:55:00 DAHS

CTG-11 Base w/db Particulates 1-PM-Base wdb-3 02/09/18 13:48:00 17:50:00 DAHS

CTG-12 Base Preliminaries 2-PM-Base-V1 02/09/09 8:29:00 8:41:00 DAHS

CTG-12 Base Particulates 2-PM-Base-1 02/09/19 8:57:00 13:10:00 DAHS

CTG-12 Base Particulates 2-PM-Base-2 02/10/19 8:22:00 12:47:00 DAHS

CTG-12 Base Particulates 2-PM-Base-3 02/10/19 12:52:00 16:54:00 DAHS

CTG-12 Base w/db Preliminaries 2-PM-Base wdb-V1 02/08/19 8:13:00 8:23:00 DAHS

CTG-12 Base w/db Particulates 2-PM-Base wdb-1 02/08/19 9:02:00 13:15:00 DAHS

CTG-12 Base w/db Particulates 2-PM-Base wdb-2 02/08/19 13:20:00 17:40:00 DAHS

CTG-12 Base w/db Particulates 2-PM-Base wdb-3 02/08/19 13:28:00 17:35:00 DAHS

TABLE A.1: EMISSIONS TESTING SCHEDULE

Note: DAHS Time (EST)

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Table A.1

Page 17: Division of Environmental Permits Floor

ParameterBase Load, Run - 1-1

Base Load, Run - 1-2

Base Load, Run - 1-3

Average

Stack Flow (M2) (DSCFH) 52,942,456 48,673,298 53,270,352 51,628,702Stack Moisture (% Method 4) 7.6 8.1 7.5 7.7Total PM (mg) 4.15 4.74 3.53 4.14Total PM (g/dscf) 4.57E-05 6.00E-05 3.84E-05 4.80E-05Total PM (gr/dscf) 7.05E-04 9.25E-04 5.92E-04 7.41E-04Total PM (kg/hr) 2.42 2.92 2.05 2.46Total PM (lb/hr) 5.33 6.43 4.51 5.42Total PM (ton/year) at 8760 hr/year 23.34 28.18 19.75 23.76Total PM (lb/MMBtu) 0.0025 0.0032 0.0021 0.0026

Total PM (mg/Nm3) 1.613 2.118 1.356 1.695CO₂ (%) 4.40 4.40 4.40 4.40O₂ (%) 13.50 13.50 13.50 13.50

ParameterBase Load

wDB, Run - 2-1Base Load

wDB, Run - 2-2Base Load

wDB, Run - 2-3Average

Stack Flow (M2) (DSCFH) 52,061,607 47,746,643 48,661,657 49,489,969Stack Moisture (% Method 4) 9.4 8.1 7.8 8.4Total PM (mg) 5.25 4.43 11.23 6.97Total PM (g/dscf) 6.36E-05 5.75E-05 1.38E-04 8.63E-05Total PM (gr/dscf) 9.81E-04 8.87E-04 2.13E-03 1.33E-03Total PM (kg/hr) 3.31 2.74 6.70 4.25Total PM (lb/hr) 7.30 6.05 14.78 9.37Total PM (ton/year) at 8760 hr/year 31.96 26.50 64.72 41.06Total PM (lb/MMBtu) 0.0030 0.0028 0.0066 0.0041

Total PM (mg/Nm3) 2.245 2.030 4.864 3.046CO₂ (%) 4.99 5.00 5.00 5.00O₂ (%) 12.60 12.60 12.60 12.60

SIEMENS, SCC6-5000F, NATURAL GAS BASE LOAD CTG-11 DATA SUMMARYTABLE A.2

TABLE A.3SIEMENS, SCC6-5000F, NATURAL GAS BASE LOAD WDB CTG-11 DATA SUMMARY

sie-19-middletown.ny-comp#1-CTG11-gases App. A

Page 18: Division of Environmental Permits Floor

ParameterBase Load, Run - 3-1

Base Load, Run - 3-2

Base Load, Run - 3-3

Average

Stack Flow (M2) (DSCFH) 51,305,315 50,643,478 51,950,960 51,299,918Stack Moisture (% Method 4) 7.5 7.6 6.9 7.3Total PM (mg) 5.04 4.82 4.02 4.63Total PM (g/dscf) 5.89E-05 5.76E-05 4.70E-05 5.45E-05Total PM (gr/dscf) 9.09E-04 8.88E-04 7.25E-04 8.41E-04Total PM (kg/hr) 3.02 2.92 2.44 2.79Total PM (lb/hr) 6.66 6.43 5.38 6.16Total PM (ton/year) at 8760 hr/year 29.18 28.15 23.57 26.96Total PM (lb/MMBtu) 0.0031 0.0031 0.0025 0.0029

Total PM (mg/Nm3) 2.080 2.033 1.659 1.924CO₂ (%) 4.30 4.20 4.10 4.20O₂ (%) 13.40 13.40 13.40 13.40

ParameterBase Load

wDB, Run - 4-1Base Load

wDB, Run - 4-2Base Load

wDB, Run - 4-3Average

Stack Flow (M2) (DSCFH) 48,636,278 48,992,010 49,215,157 48,947,815Stack Moisture (% Method 4) 8.5 8.5 8.0 8.4Total PM (mg) 4.45 4.53 5.43 4.80Total PM (g/dscf) 5.51E-05 5.28E-05 6.69E-05 5.83E-05Total PM (gr/dscf) 8.51E-04 8.15E-04 1.03E-03 8.99E-04Total PM (kg/hr) 2.68 2.59 3.29 2.85Total PM (lb/hr) 5.91 5.71 7.26 6.29Total PM (ton/year) at 8760 hr/year 25.90 24.99 31.78 27.56Total PM (lb/MMBtu) 0.0027 0.0026 0.0033 0.0028

Total PM (mg/Nm3) 1.947 1.866 2.362 2.058CO₂ (%) 4.70 4.70 4.60 4.67O₂ (%) 12.70 12.74 12.80 12.75

TABLE A.4SIEMENS, SCC6-5000F, NATURAL GAS BASE LOAD CTG-12 DATA SUMMARY

TABLE A.5SIEMENS, SCC6-5000F, NATURAL GAS BASE LOAD WDB CTG-12 DATA SUMMARY

sie-19-middletown.ny-comp#1-CTG11-gases App. A

Page 19: Division of Environmental Permits Floor

EXAMPLE CALCULATIONS (Reference Method 1 - Circular Stack)

Diameter of Stack (in.) Area of Stack (ft2)

in.

in.

Stack Diameters Downstream

Stack Diameters Upstream

in.

in.

in.

in.

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

ft22 x 12in./ft

AD (dia.) =1200.00

=

As (ft2) =

228.00283.53

5.26 diameters228.00

228.00

BD (dia.) =1095.00

= 4.80 diameters228.00

D (in.) = 235.25 in. - 7.25 in. =

3.14 x ( )2 =

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 20: Division of Environmental Permits Floor

Carbon Monoxide Concentration (%)

Nitrogen Concentration (%)

/ 10,000 % = %

Stack Dry Molecular Weight (lb/lb-mole)

lb

Stack Wet Molecular Weight (lb/lb-mole)

lb % % lb

Average Calculated Fuel Factor (Fo)

%)

% + %

Average Excess Air (%)

% ) }

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

13.50 % - (0.5 x 0.000

= 1.6824.40 0.000

Fo(avg) = 20.9% - 13.50 % - (0.5 x 0.000

13.50 % - (0.5 x 0.000

MS (lb/lb-mol) = {29.24

x (1 - 7.60

%(%EA)AVG = ( 0.264 x 82.10 %) - {

lb-mol 100

44 lb/lb-molx 4.40

EXAMPLE CALCULATIONS (Reference Method 3a) [Values from Run 1 test]

x 13.50

% ) +

32 lb/lb-mol

%N2 (%) = 100 - 4.40 13.50 0.00% - % -

%) + (28 lb/lb-mol

100x [

%%CO (%) =0.00 ppm

10,000 ppm/%

18 lbx

7.60} =

28.39

lb-mol 100 lb-mol

= 0.0000

29.24

100

100 lb-mol

82.1

Md (lb/lb-mol) = (

+ 82.100.00

10,000

= 165.15

( ] ) =

) } + {

100 x {

%)}

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 21: Division of Environmental Permits Floor

Absolute Stack Pressure (in. Hg)

Average Stack Gas Velocity (ft/sec)

vsl (ft/sec) =

ft

Average Stack Dry Standard Flow Rate (dscfh)

% ft

Average Stack Wet Flow Rate (acfm)

ft

Average Stack Wet Standard Flow Rate (ascfh)

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

ft2acf

min

60 secx

73.26x

min sec

=

x

+ 460 oR 29.92 in. Hg hr

68.00 + 460 oRx

29.18 in. Hg

57,297,265.98 ascf

hr

1,246,339.45

EXAMPLE CALCULATIONS (Reference Method 2) [Values from Run 1 test]

acf

283.53

in. H2O= 29.18 in. Hg

13.6 in. H2O/in. HgPs (in. Hg) =

73.26x 283.53

=1,246,339.45

29.28 in. Hg +-1.30

x

((lb/lb-mol)(in. Hg)

dscf

212.17

)1/2 x in.H2O1/2

ft2sec

Qsd (dscf/hr) =3600 sec

x (1 -7.60

) xhr 100

=

85.49 ft0.79

212.17 + 460 oR 29.92 in. Hg

xhr min

68.00 + 460 oRx

29.18 in. Hg

Qsw (ascf/hr) =60 min

Qaw (acf/min) =

52,942,455.93

73.2

sec

+ 460 oR=

sec (oR)(in. H2O) 29.18 in. Hg x 28.39 lb/lb-molx 1.21 x

212.17

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 22: Division of Environmental Permits Floor

Water Volume Weighed (scf)

0.04715 ft3/g = scf

Standard Meter Volume (dscf)

oR

oF + oR

Calculated Moisture Content (%)

Saturated Moisture Content (%)

10

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

EXAMPLE CALCULATIONS (Reference Method 4) [Values from Run 1 test]

Bws(svp) = 100 x

3144

≤ 100 = 100.00

%7.47 dscf + 90.80 dscf

Bws(calc) = 100 x7.47 dscf

= 7.60

%212.17 oF + 390.86

29.28 in. Hg +-1.30 in. H2O

13.6 in. H2O / in. Hg

in. Hg +dscfin. Hg 13.6 in. H2O / in. Hg

45.58 460

7.469

0.45 in. H2O

90.80

Vwsg(std) = 158.40 g x

Vm(std) =

17.65x 1.01 x 87.69 29.28

=

)(6.691 -

)dcf x (

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 23: Division of Environmental Permits Floor

Desired Orifice (in. H2O) (first point) Absolute Meter Pressure (in. Hg)

x

Recommended Nozzle Diameter (in.)

%

%

lb % %

P to H Isokinetic Factor

%oF + 460oR

%

lb % %

in. Hg

lb % % in. Hg

Percent Isokinetic (%) (first point)

ft in. %

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

EXAMPLE CALCULATIONS (Isokinetic Sampling) [Values from Run 1 test]

1 -7.60

100in.

100 lb-mol

lb-mol

18 lb

Dni (in.) =

0.03575 (lb-mole•oR•in. H2O)1/2•min•in.2

29.24

lb-mole

29.18

%20.50 min x

74.57x 29.18 in. Hg x 3.14 x (

0.14x

ft.1 -

7.60

sec 2 12 in.

8.08 dscfsec•oR

)

0.00

xlb/mole 100 100

= 110.57

) xK =

x29.24

x ( 1 -0.00

)+(

100

I (%) = x ( 215.00

29.18= 0.27

29.24x ( 1 -

7.60)+(

18 lbx

7.60 29.41

lb/mole 100 lb-mol 100

0.0945 min•in. Hg

x (

= 0.215

x 0.75 acf x

1 -7.60

)2 x100 45.58849.8

x 0.79 2 x 1.83 in. H2O x 0.14in. H2O•in.4 oF + 460oR

1001 -

0.00 212.17

in. Hg x 1.21

in. H2O= 29.41 in. Hg

13.6 in. H2O/in. Hg

Hd (in. H2O) =

in. H2O =

x (

1 -0.00

) xacf•in. Hg3/4•lb1/2 100

45.58 oF + 460oR x 0.791 -

7.60

100

29.41 in. Hg

in. H2O

7.60)+(

18 lbx

212.17

in. H2OPm (in. Hg) = 29.28 in. Hg +

1.83

)

( oF + 460oR ) x

4 x (

(

)

)

oF + 460 oR) x

)2 x (

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 24: Division of Environmental Permits Floor

Cumulative Percent Isokinetic (%) (weighted average of all points)

Pt x = / =

A-1 x = / =

A-2 x = / =

A-3 x = / =

B-1 x = / =

B-2 x = / =

B-3 x = / =

C-1 x = / =

C-2 x = / =

C-3 x = / =

D-1 x = / =

D-2 x = / =

D-3 x = / =>Last Pt

Percent Isokinetic (%) (intermediate equation, all points)

ft in. %

Raw Data Percent Isokinetic (%)

[utilizes the raw data equation for isokinetics from Method 5]

oF + 460 oR

ft in.

= %

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

1.206) ]

ml•oR 45.58 13.6

60 x 243.00 min x73.26

x 29.18 in. Hg x 3.14 x (0.14

xft.

)2

sec 2 12 in. 106.35

87.69 dcf x 1.012ml +

%243.00 min x

73.26x 29.18 in. Hg x 3.14 x (

0.14x

ft.)2 x ( 1 -

7.60)

sec 2 12 in. 100

106.22

[equivalent to taking an average of point-by-point isokinetics without weighting the average (e.g. all points equal)]

I (%) =0.0945 min•in. Hg

x ( 212.17 oF + 460 oR) x 90.80 dscfsec•oR

=

I (%) =

100 x ( 212.17 oF + 460 oR) x [0.002669 ft3•in. Hg

x 158.7 29.28 in Hg +

103.92 7.914 822.43 9621.35 90.80 106.0

109.54 9.976 1092.84 7987.42 75.04 106.4

103.34 7.852 811.50 8798.92 82.89 106.2

58.13 105.7

108.18 6.932 749.88 6894.57 65.06 106.0

6144.69103.76 7.595 788.07

112.84 6.391 721.20 4578.25 42.98 106.5

103.05 7.554 778.38 5356.63 50.53 106.0

102.31 7.488 766.09 2435.46 23.36 104.2

108.27 6.668 721.96 3157.42 30.03 105.1

775.91 1669.37 15.88 105.2

106.71 6.557 699.63 3857.05 36.59 105.4

EXAMPLE CALCULATIONS (Isokinetic Sampling) [Values from Run 1 test]

Using Method 5, Eq 5-8 to determine intermediate isokinetics at each point, weighted averaging of the cumulative isokinetics is necessary since all points are not equal, and determined by using the dry standard meter volume collected at each point to weight the cumulative average. Intermediate isokinetics and dry standard meter volumes are found at each point. At each point the cumulative sum is found of each value and the quotient of the two used to determine the cumulative isokinetics for each residual point (n).

110.57 8.081 893.46 893.46

99.55 7.795

8.08 110.6

(

In (%) Vm(std)n I (%)n ∑(I (%)n) ∑(Vm(std)n) I (%)

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 25: Division of Environmental Permits Floor

g mg mg

ml

ml x mg/ml = mg

mg - mg = mg

0.1N NH4OH Correction (mg)

ml x 0.1 N = mg

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

1.40 0.04 1.36

mc (mg) = 17.03 x 0.00 0.00

Adjusted Sample Gain [Nozzle Wash PM>10] (mg)

mxadj (mg) =

Blank Concentration [Acetone Blank Weight of Solids] (mg/ml)

Cx (mg/ml) =250.00

=0.0080

ml

Method limited to 0.0001% of weight at 0.000791

mg/ml

0.0020x

g

1000 mg

49.00 0.040.0008

Blank Adjustment [Acetone Blank Weight of Solids and Nozzle Wash PM>10] (mg)

Wx (mg) =

=0.007910

EXAMPLE CALCULATIONS (Gravimetric Analysis) [Values from Run 1 test]

< Sample Gain

ml

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 26: Division of Environmental Permits Floor

Stack Total Concentration (g/dscf)

g

Stack Total Concentration (gr/dscf)

gr

Total Emissions Rate (kg/hr)

g kg

Total Emissions Rate (lb/hr)

lb

Total Emissions Rate (tpy)

hr lb ton

Total Emissions Rate (lb/MMBtu)

Oxygen Based:

lb

%

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

5.33

20.9lbx (

8,632.05 dscfx

=23.34

yr

8,760

E (kg/hr) =kg

x

E' (lb/hr) =g

x

2.42

1000 g dscf hr

2000 lb yr hrE'' (tpy) =

tonx x

1000 mg 453.592 g 90.80 dscf

=

dscf

E''' (lb/MMBtu) =g

x

=

) =0.0025

1000 mg 453.592 g 90.80 dscf MMBtu 20.9 - 13.5 MMBtu

4.15 mgx

4.57E-05

1000 mg 90.80 dscfcs (g/dscf) =

=5.33

hr

4.57E-05

hr hr

lbx

4.15 mgx

52,942,456

7.05E-04

x52,942,456 dscf

x4.15 mg

c's (gr/dscf) =g

x4.15 mg

1000 mg 90.80 dscf lb 453.592 g dscfx

7000 grx

lb=

g

dscf

EXAMPLE CALCULATIONS (Analysis) [Values from Run 1 test - Total PM₁₀/PM₂.₅ Mass]

′′′ /1000 453.592

20.920.9 %

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 27: Division of Environmental Permits Floor

Stack Gas Viscosity (μP) [based on preliminary data]

+ 460 + 3.86153x106 ( + 460 )-2 + 0.591123 ( x (1 - /100)

- 91.9723 ( /100) + 1.51761x10-5 ( /100)( + 460)2 = μP

Cunningham Correction Factor

[based on preliminary data for a 2.25 micrometer diameter particle]

μP

in Hg x µm lb / lb-mole

First calculation set using Cyclone I or Cyclone I and IV, assuming Nre<3,162

Lower Limit Cut Diameter for Cyclone I (µm)

[assumes Nre<3,162]

in Hg x lb / lb-mole

Cut Diameter for Cyclone I for the Middle of the Overlap Zone (µm)

[assumes Nre<3,162]

11 + µm

Sampling Rate Using Both PM10 and PM2.5 Cyclones (dscfm)

[assumes Nre<3,162]

Qs (dscfm) =

in Hg x lb / lb-mole µm

Reynolds Number (dimensionless)

[verification of Nre<3,162, using Cyclone I and IV]

in Hg x lb / lb-mole dscfm

μP

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

206.86Nre = 8.64 x 105 x

29.18 28.30x

0.51= 2627.63 < 3,162

208

0.07296 x 206.86 μP x (

206.86)(

208 + 460 oR)0.5 = 1.09

29.18 2.25 28.30

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Preliminary test]

D50LL (µm) = 9.507 x 1.09 0.3007 x (29.18 28.30

μ (μP) = -150.3162 μP + 13.4622 13.6 8.00208 208

8.00 8.00 208 206.86

C = 1 + 0.0057193 x (

)0.1993 = 10.17 µm208 + 460 oR

Correct

D50T (µm) =10.17

= 10.59 µm2

dscfm29.18 28.30 10.59

)0.2949 x (1

)1.4102 = 0.51

+ 460 oR

208 + 460 oR

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 28: Division of Environmental Permits Floor

Second calculation set using Cyclone IV, assuming Nre<3,162

Particle Cut Diameter for Nre Less than 3,162 for Cyclone IV (µm)

[assumes Nre<3,162]

D50 (µm) =

μP

dscfm

in Hg x lb / lb-mole

Sampling Rate Using Only PM2.5 Cyclone for Nre Less than 3,162 (dscfm)

QIV (dscfm) =

μP in Hg x lb / lb-mole0.4242

µm

Reynolds Number (dimensionless)

[verification of Nre<3,162, using Cyclone IV only]

in Hg x lb / lb-mole dscfm

μP

Third calculation set using Cyclone I or Cyclone I and IV, assuming Nre≥3,162

Lower Limit Cut Diameter for Cyclone I (µm)

[assumes Nre≥3,162]

in Hg x lb / lb-mole

Cut Diameter for Cyclone I for the Middle of the Overlap Zone (µm)

[assumes Nre≥3,162]

11 + µm

Sampling Rate Using Both PM10 and PM2.5 Cyclones (dscfm)

[assumes Nre≥3,162]

Qs (dscfm) =

in Hg x lb / lb-mole µm

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Preliminary test]

28.30x

0.51=Nre = 8.64 x 105 x

29.18

0.49)0.2949 x (1

)1.4102 =

1)0.5

1.09

x (208 + 460 oR

)0.6790 = 2.41 µm29.18 28.30

0.51 dscfm2.41

29.18

0.0024302 x (206.86

)1.1791 x (0.51

0.07296 x 206.86 μP x (208 + 460 oR

x (1

)0.8481 =

< 3,162+ 460 oR 206.86

29.18 28.30 10.80

D50T (µm) =10.61

= 10.80 µm2

28.30)0.06000.4400 x (

29.18

dscfm

28.30)-0.5759

1.09 208 + 460 oR

Correct

2627.60208

= 10.61 µm208 + 460 oR

0.0060639 x (206.86

) x (

D50LL (µm) = 10.0959 x 1.09

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 29: Division of Environmental Permits Floor

Fourth calculation set using Cyclone IV, assuming Nre≥3,162

Particle Cut Diameter for Nre Greater than or Equal to 3,162 for Cyclone IV (µm)

[assumes Nre≥3,162]

D50 (µm) =

μP

dscfm

in Hg x lb / lb-mole

Meter Box Orifice Pressure Drop (in H2O)

dscfm x ( 1 - /100) x in Hg

1.083 x ( + 460 oR) x lb / lb-mole x in H2O

in Hg

50 oF above stack temperature Ts+50 = ∆H+50 = in H2O

50 oF below stack temperature Ts+50 = ∆H+50 = in H2O

Average Probe Blockage Factor

in2

Velocity Pressure Adjusted for Blockage Factor (in H2O) [point A-1]

( 1 - )

Velocity of Stack Gas Adjusted for Blockage Factor (ft/sec)

vs (ft/sec) =

ft

in Hg x lb / lb-mole sec

Calculated Nozzle Diameter for Acceptable Sampling Rate (in)

3.056 x dscfm

ft/sec

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

29.20

206.86)0.8058 x (

1)0.5

29.28

∆H (in H2O) = (0.51 8.00 29.18

)2

208 + 460 oR

x (208 + 460 oR

)0.3058 =

0.450 in H2O

0.49 1.09

in H2O5.39E-04

)0.5 =

bf =

72.20

in H2O x (1

)2 = 1.61

85.49 ft/secx 0.79 x 1.19 x (

208 + 460 oR

lb/mole - oR 28.30

22.0= 5.39E-04

∆ps (in H2O) = 1.61

40828.14

D (in) = (0.51

)0.5 = 0.147 in72.20

29.18

1.830) =

258

158 0.526

0.019723 x (

x (85.00

µm29.18 28.30

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Preliminary test]

2.30

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Preliminary test]

0.390

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 30: Division of Environmental Permits Floor

Velocity of Gas in Nozzle 3 (diam. = 0.144 in), (ft/sec)

dscfm

ft

ft2 sec

Minimum Nozzle Velocity to Stack Velocity Ratio Parameter (dimensionless)

Nozzle 3 (diam. = 0.144 in)

Rmin =

0.2603 x μP x ( dscfm)0.5

in1.5

Maximum Nozzle Velocity to Stack Velocity Ratio Parameter (dimensionless)

Nozzle 3 (diam. = 0.144 in)

Rmax =

0.2603 x μP x ( dscfm)0.5

in1.5

Minimum Gas Velocity for Rmin Greater than or Equal to 0.5 (ft/sec) Nozzle 3 (diam. = 0.144 in)

ft ft

sec sec

Maximum Gas Velocity for Rmax Less than 1.5 (ft/sec) Nozzle 3 (diam. = 0.144 in)

ft ft

sec secNote: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

0.51

vn (ft/sec) =60 min / sec

= 74.971.13E-04

1.240.4457 + (0.5690 +

vmin (ft/sec) =

0.2457 + (0.3072 -206.86 0.51

74.97 x 0.74 = 55.76

vmax (ft/sec) = 74.97 x 1.24 = 92.83

206.86 0.51)0.5 =

74.97

)0.5 = 0.7474.97

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Preliminary test]

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 31: Division of Environmental Permits Floor

Minimum Velocity Pressure (in H2O)

∆pmin (in H2O) =

in Hg x lb / lb-mole ft/sec

Maximum Velocity Pressure (in H2O)

∆pmax (in H2O) =

in Hg x lb / lb-mole ft/sec

Average Probe Blockage Factor

in2

Velocity Pressure Adjusted for Blockage Factor (in H2O) [point A-1]

( 1 - )

Sampling Dwell Time at Each Point (minutes) [point A-1]

x ( )0.5 min

x

Dry Gas Volume Sampled at Standard Conditions (dscf) [point A-1]

in Hg + in H2O / 13.6

+ 460 oR

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

in H2Oin H2O x (5.39E-04

1)2 = 1.61

tn (min) = (0.79 1.61

bf =22.0

40828.14= 5.39E-04

∆ps (in H2O) = 1.61

7.61 dscf ) x

29.28 0.45

528) ( 1.012 x

33.00( ) = 8.08 dscf

vms (dscf) = (29.92

0.79

1.3686 x 10-4 x (29.18 28.30

) x (55.76

29.18 28.30) x (1.3686 x 10-4 x (

92.83)2 =

0.85208 + 460 oR 0.79

)2 =

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Preliminary test]

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Run 1 test]

) = 20.57 minutes0.79 1.23 12.00

2.34 in H2O208 + 460 oR

) x (240.00

in H2O

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 32: Division of Environmental Permits Floor

Sample Flow Rate at Standard Conditions (dscfm)

dscf dscf

min

Sampling Rate (dscfm) [e.g. cyclone flow rate]

Qs (dscfm) = dscf

(1- /100) in Hg

Reynolds Number (dimensionless)

in Hg x lb / lb-mole dscfm

μP

Actual Particle Cut Diameter for Cyclone I (µm)

μP

in Hg x lb / lb-mole dscfm

Actual Particle Cut Diameter for Cyclone IV is determined by:

Cunningham Correction Factor (dimensionless)

[for a 2.5 micrometer diameter particle (estimated size)]

μP

lb / lb-mole

Particle Cut Diameter for Nre Less than 3,162 for Cyclone IV (µm)

D50 (µm) =

μP

dscfm

in Hg x lb / lb-mole

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

+ 460 oR)0.6790 =

208.16

90.80

243.00=

0.37

min

x0.37

minx

7.60

1

x0.53

208.16

in Hg x 2.5 µm

dscfm

= 2700.22+ 460 oR

QsST (dscfm) =

28.3929.18

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Run 1 test]

+ 460 oR

29.18= 0.53

29.92 in Hg

528 oR

Nre = 8.64 x 105 x

0.53)1.1791 x (

1.08

10.0024302 x ( )0.5

212

x212

µm29.18 28.39

212x ( 2.33

10.37 µm29.18 28.39 0.53

C = 1 + 0.0057193 x (208.16

)(212 + 460 oR

)0.5 = 1.0829.18 28.39

D50 (µm) = 0.15625 x (212 + 460 oR

)0.2091 x (208.16

)0.7091 =

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 33: Division of Environmental Permits Floor

Re-calculated Particle Cut Diameter for Nre Less than 3,162 for Cyclone IV (µm)

D50-1 (µm) =

μP

dscfm

in Hg x lb / lb-mole

Ratio (Z) Between D50 and D50-1 Values (dimensionless)

µm

µm

Note: Lack of significant figures may cause rounding errors between actual calculations and example calculations.

EXAMPLE CALCULATIONS (Constant Flow, Variable Time Isokinetic QA/QC) [Values from Run 1 test]

0.0024302 x (208.16

)1.1791 x (

µm

1)0.5

0.53 1.09

x (212 + 460 oR

Z = 2.33

= 1.002.33

)0.6790 = 2.3329.18 28.39

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Calculations

Page 34: Division of Environmental Permits Floor

• %CO = carbon monoxide concentration (%)

• %CO2 = carbon dioxide concentration (%)

• %N2 = nitrogen concentration (%)

• %O2 = oxygen concentration (%)

• (%EA)avg = average excess air (%)

• (Fo)avg = average calculated fuel factor

• µ = Gas viscosity, micropoise

• 17.03 = mg/milliequivalents for ammonium ion

• A = distance upstream (in.)

• AD = stack diameters upstream (dia.)

• An = Area of nozzle, square feet

• As = area of stack (ft2)

• B = distance downstream (in.)

• BD = stack diameters downstream (dia.)

• bf = Average blockage factor calculated in Equation 26, dimensionless

• Bwm = meter moisture content (%)

• Bws = stack moisture content (%)

• C1 = -150.3162 (micropoise)

• C2 = 18.0614 (micropoise/K0.5) = 13.4622 (micropoise/R0.5)

• C3 = 1.19183 × 106 (micropoise/K2) = 3.86153 × 106 (micropoise/R2)

• C4 = 0.591123 (micropoise)

• C5 = 91.9723 (micropoise)

• C6 = 4.91705 × 10-5 (micropoise/K2) = 1.51761 × 10-5 (micropoise/R2)

• Ca = Acetone blank concentration, mg/mg

• Cb = Concentration of NH3 ion in the back half of train (breakthrough)

• Cf = Concentration of NH3 ion in the front half of train (main catch)

• CfPM10 = Conc. of filterable PM10, gr/dscf

• CfPM2.5 = Conc. of filterable PM2.5, gr/dscf

• Ck = K Factor Constant, 849.8

• Cn = nozzle diameter constant, 0.03575

• Cp' = Coefficient for the pitot used in the preliminary traverse, dimensionless

• Cp = Pitot coefficient for the combined cyclone pitot, dimensionless

Nomenclature

%O2,wet = Oxygen content of gas stream, % by volume of wet gas. (Note: The oxygen percentage used in Method 201A, Equation 3 is on a wet gas basis. That means that since oxygen is typically measured on a dry gas basis, the measured percent O2 must be multiplied by the quantity (1 - Bws) to convert to the actual volume fraction. Therefore, %O2,wet = (1 - Bws) * %O2, dry)

[(∆p)0.5]avg = Average of square roots of the velocity pressures measured during the preliminary traverse, inches W.C.

12.0 = Constant calculated as 60 percent of 20.5 square inch cross-sectional area of combined cyclone head, square inches

C = Cunningham correction factor for particle diameter, Dp, and calculated using the actual stack gas temperature, dimensionless

22.4 = liters of ideal gas per lb-mol of substance at 0oC and 1 atm (ref. Civil Engineering Reference Manual, 7th ed. - Michael R. Lindeburg)

5.02 x 104 = constant derived from the molecular weight and correcting standard temperature and pressure (ref. Bay Area Air Quality Management District, Source Test Procedure ST-1B, Ammonia Integrated Sampling, Adopted January 20, 1982, Regulation 7-303)

24.04 = liters of ideal gas per lb-mol of substance at 20oC and 1 atm (ref. Civil Engineering Reference Manual, 7th ed. - Michael R. Lindeburg)

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Nomenclature

Page 35: Division of Environmental Permits Floor

Nomenclature

• D50 = Particle cut diameter, micrometers

• D50(N+1) = D50 value for cyclone IV calculated during the N+1 iterative step, micrometers

• D50-1 = Re-calculated particle cut diameters based on re-estimated Cr, micrometers

• D50N = D50 value for cyclone IV calculated during the Nth iterative step, micrometers

• De = equivalent stack diameter (in.)

• ∆H@ = ∆H @ 0.75 scfm (in. H2O)

• Havg = average orifice pressure (in. H2O)

• Dn = Inner diameter of sampling nozzle mounted on Cyclone I, inches

• Dna = actual nozzle diameter (in.)

• Dp = Physical particle size, micrometers

• p = velocity head (in. H2O)

• p1 = velocity head at first current traverse point (in. H2O)

• p'1 = velocity head at first preliminary traverse point (in. H2O)

• pavg = average pitot tube differential pressure (in. H2O)

• pn = velocity head at subsequent current traverse point (in. H2O)

• pRM2 = method 2 velocity head (in. H2O)

• Ds = diameter of stack (in.)

• Fd = fuel f-factor (dscf/MMBtu)

• fO2 = stack gas fraction of O2, by volume, dry basis

• I = Percent isokinetic sampling, dimensionless

• K1 = standard volume correction, 17.65oR/in. Hg

• K4 = isokinetic conversion constant, 0.0945min•in.Hg/sec•oR

• K5 = water mass to std water vapor, 0.04715 ft3/g

• Kp = 85.49, ((ft/sec)/(pounds/mole -oR))

• L = length of stack (in.)

• Lfw = distance to far wall of stack (in.)

• Lnw = distance to near wall of stack (in.) [reference]

• m#x = weight measurements (g)

• M1 = Milligrams of PM collected on the filter, less than or equal to 2.5 micrometers

• ma = Mass of residue of acetone after evaporation, mg

• mc = Mass of the NH4+ added to sample to form ammonium sulfate, mg

• mcpm = Mass of the total condensable PM, mg

• Md = Molecular weight of dry gas, pounds/pound mole

• mfb = Mass of total CPM in field train recovery blank, mg

• mfx = final weight, avg of last two measurements (g)

D50LL = Cut diameter for cyclone I corresponding to the 2.25 micrometer cut diameter for cyclone IV, micrometer

D50T = Cyclone I cut diameter corresponding to the middle of the overlap zone shown in Method 201A, Figure 10 of Section 17, micrometers

M2 = Milligrams of PM recovered from Container #2 (acetone blank corrected), greater than 10 micrometers

M3 = Milligrams of PM recovered from Container #3 (acetone blank corrected), less than or equal to 10 and greater than 2.5 micrometers

M4 = Milligrams of PM recovered from Container #4 (acetone blank corrected), less than or equal to 2.5 micrometers

Cr = Re-estimated Cunningham correction factor for particle diameter equivalent to the actual cut size diameter and calculated using the actual stack gas temperature, dimensionless

Ccpm = Concentration of the condensable PM in the stack gas, dry basis, corrected to standard conditions, milligrams/dry standard cubic foot.

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Nomenclature

Page 36: Division of Environmental Permits Floor

Nomenclature

• mg = Milligram

• mg/L = Milligram per liter

• mi = Mass of inorganic CPM, mg

• mib = Mass of inorganic CPM in field train recovery blank, mg

• Mn = total particulates (mg)

• mo = Mass of organic CPM, mg

• mob = Mass of organic CPM in field train blank, mg

• mr = Mass of dried sample from inorganic fraction, mg

• mtx = tare weight (g)

• MW = molecular weight (lb/lb-mole)

• Mw = Molecular weight of wet gas, pounds/pound mole

• N = Normality of ammonium hydroxide titrant

• Na = null angle (deg.)

• Nre = Reynolds number, dimensionless

• Ntp = Number of iterative steps or total traverse points

• Pb = Pbar = barometric pressure (in. Hg)

• Pbar = barometric pressure (in. Hg)

• ppmCO = carbon monoxide concentration (ppm)

• ppmv = Parts per million by volume

• ppmw = Parts per million by weight

• Ps = absolute stack pressure (in. Hg)

• Pstatic = static pressure (in. H2O)

• Pstd = standard pressure, 29.92 in. Hg

• = total sampling time (min)

• Qaw = average stack wet flow rate (ascf/min)

• QI = Sampling rate for cyclone I to achieve specified D50

• Qm = estimated orifice flow rate, 0.750 acfm, else Vm/Q from previous run

• Qs = Sampling rate for cyclone I to achieve specified D50

• Qs(std) = total cyclone flow rate at standard conditions (dscf/min)

• Qsd = dry standard stack flow rate (dscfm)

• QsST = Dry gas sampling rate through the sampling assembly, dscfm

• Qsw = wet standard stack flow rate (ascfm)

• Rmax = Nozzle/stack velocity ratio parameter, dimensionless

• Rmin = Nozzle/stack velocity ratio parameter, dimensionless

• t1 = Sampling time at point 1, min

• tm = average gas meter temperature (oF)

• tm = average meter temperature (oF)

• Tm = Meter box and orifice gas temperature, oR

• tn = Sampling time at point n, min

• tr = Total projected run time, min

• Ts = Absolute stack gas temperature, oR

• Tstd = standard temperature, 68oF, 528oR

• Tu = absolute temperature offset, 460oR

• Va = Volume of acetone blank, ml

• Vaw = Volume of acetone used in sample recovery wash, ml

• Vb = Volume of aliquot taken for IC analysis, ml

• Vc = Quantity of water captured in impingers and silica gel, ml

• Vf = final impinger volume (ml)

• Vi = initial impinger volume (ml)

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Nomenclature

Page 37: Division of Environmental Permits Floor

Nomenclature

• Vic = Volume of impinger contents sample, ml

• Vm = Dry gas meter volume sampled, acf

• Vm(std) = standard meter volume (dscf)

• vmax = Maximum gas velocity calculated from Equations 18 or 19, ft/sec

• vmax = maximum nozzle velocity (ft/sec)

• Vmf = final dry gas meter reading (dcf)

• Vmi = initial dry gas meter reading (dcf)

• vmin = Minimum gas velocity calculated from Method 201A, Equations 16 or 17, ft/sec

• Vms = Dry gas meter volume sampled, corrected to standard conditions, dscf

• vn = Sample gas velocity in the nozzle, ft/sec

• vorg = organics wash volume (ml)

• Vp = Volume of water added during train purge

• vs = average stack gas velocity (ft/sec)

• vsl = local velocity (ft/sec)

• Vt = total impinger volume (ml) = (Vf-Vi)

• Vt = Volume of NH4OH titrant, ml

• Vw(std) = volume of water vapor in gas sample at standard conditions (scf)

• vx = blank volume (ml)

• W = width of stack (in.)

• W2,3,4 = Weight of PM recovered from Containers #2, #3, and #4, mg

• Wa = Weight of blank residue in acetone used to recover samples, mg

• Wf = final impinger weight (g)

• Wi = initial impinger weight (g)

• Wt = total impinger weight (g) = (Wf-Wi)

• wx = blank weight of solids (g)

• Y = meter calibration factor (a.k.a gamma)

• Z = Ratio between estimated cyclone IV D50 values, dimensionless

• γ = Dry gas meter gamma value, dimensionless

• ∆H = Meter box orifice pressure drop, inches W.C.

• ∆p1 = Velocity pressure measured at point 1, inches W.C.

• ∆pavg = Average velocity pressure, inches W.C.

• ∆pm = Observed velocity pressure using S-type pitot tube in preliminary traverse, inches W.C.

• ∆pmax = Maximum velocity pressure, inches W.C.

• ∆pmin = Minimum velocity pressure, inches W.C.

• ∆pn = Velocity pressure measured at point n during the test run, inches W.C.

• ∆ps = Velocity pressure calculated in Method 201a, Equation 25, inches W.C.

• ∆ps1 = Velocity pressure adjusted for combined cyclone pitot tube, inches W.C.

• ∆ps2 = Velocity pressure corrected for blockage, inches W.C.

• θ = Total run time, min

• ρa = Density of acetone, mg/ml (see label on bottle)

• Σn = total number of sampling points

∆H@ = Pressure drop across orifice at flow rate of 0.75 scfm at standard conditions, inches W.C. (Note: Specific to each orifice and meter box.)

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Nomenclature

Page 38: Division of Environmental Permits Floor

APPENDIX B

EMISSION DATA RECORDS

Page 39: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-11 Base Load

Unit Operating Data

Page 40: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 11 CTG-1 WO/DB Run 1DCS Data - 20190209 - 0920-1800

Unit 11 GT Power Unit 11 GT PowerUnit 11 Total GT

Gas FlowUnit 11 HRSG DB Fuel Flow

Unit 11 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 11HAD00EU001 11MKA01EU902A 11MBP10CF910 11HHA10CF001 11HNE10CQ109 11MBL05CT1012019/02/09 09:22:00:000 225.408 100.2 94.591 0.002 13.40 11.12019/02/09 09:23:00:000 225.050 100.3 94.449 0.002 13.40 10.92019/02/09 09:24:00:000 225.446 100.2 94.702 0.002 13.40 11.12019/02/09 09:25:00:000 225.446 100.2 94.638 0.002 13.40 11.32019/02/09 09:26:00:000 225.446 100.2 94.638 0.002 13.40 11.12019/02/09 09:27:00:000 225.446 100.3 94.638 0.002 13.40 11.32019/02/09 09:28:00:000 225.674 100.1 94.638 0.002 13.40 11.32019/02/09 09:29:00:000 225.674 100.1 94.639 0.002 13.40 11.32019/02/09 09:30:00:000 225.409 100.2 94.639 0.002 13.40 11.62019/02/09 09:31:00:000 225.409 100.1 94.538 0.002 13.40 11.62019/02/09 09:32:00:000 225.409 100.4 94.538 0.002 13.40 11.62019/02/09 09:33:00:000 225.065 100.0 94.455 0.002 13.41 11.62019/02/09 09:34:00:000 225.065 100.1 94.455 0.002 13.41 11.62019/02/09 09:35:00:000 225.006 100.1 94.455 0.002 13.41 11.62019/02/09 09:36:00:000 225.006 100.3 94.455 0.002 13.41 11.62019/02/09 09:37:00:000 225.006 100.2 94.455 0.002 13.41 11.62019/02/09 09:38:00:000 225.006 100.2 94.455 0.002 13.41 11.82019/02/09 09:39:00:000 225.006 100.2 94.438 0.002 13.41 12.12019/02/09 09:40:00:000 224.836 100.2 94.438 0.002 13.41 12.12019/02/09 09:41:00:000 224.836 100.3 94.343 0.002 13.40 12.12019/02/09 09:42:00:000 224.836 100.2 94.427 0.002 13.40 12.32019/02/09 09:43:00:000 224.836 100.2 94.427 0.002 13.40 12.32019/02/09 09:44:00:000 224.836 100.3 94.427 0.002 13.41 12.32019/02/09 09:45:00:000 225.260 100.3 94.427 0.002 13.41 12.32019/02/09 09:46:00:000 225.260 100.4 94.427 0.002 13.41 12.32019/02/09 09:47:00:000 225.260 100.4 94.512 0.002 13.41 12.12019/02/09 09:48:00:000 225.260 100.2 94.631 0.002 13.41 12.12019/02/09 09:49:00:000 225.260 100.2 94.637 0.002 13.41 12.12019/02/09 09:50:00:000 225.260 100.2 94.501 0.002 13.40 12.12019/02/09 09:51:00:000 225.260 100.3 94.501 0.002 13.40 12.32019/02/09 09:52:00:000 225.260 100.2 94.572 0.002 13.40 12.32019/02/09 09:53:00:000 225.014 100.2 94.373 0.003 13.43 12.52019/02/09 09:54:00:000 225.014 100.2 94.440 0.003 13.43 12.52019/02/09 09:55:00:000 224.673 100.2 94.383 0.003 13.41 12.72019/02/09 09:56:00:000 224.673 100.2 94.383 0.003 13.41 12.72019/02/09 09:57:00:000 225.144 100.4 94.481 0.003 13.41 12.52019/02/09 09:58:00:000 225.144 100.3 94.560 0.003 13.39 12.52019/02/09 09:59:00:000 225.144 100.3 94.560 0.003 13.39 12.52019/02/09 10:00:00:000 225.144 100.3 94.501 0.003 13.39 12.32019/02/09 10:01:00:000 224.690 100.3 94.501 0.003 13.40 12.72019/02/09 10:02:00:000 224.690 100.3 94.354 0.003 13.40 12.92019/02/09 10:03:00:000 224.690 100.4 94.354 0.003 13.40 12.92019/02/09 10:04:00:000 224.690 100.3 94.474 0.003 13.40 12.92019/02/09 10:05:00:000 225.013 100.3 94.233 0.003 13.40 12.92019/02/09 10:06:00:000 224.431 100.1 94.397 0.003 13.40 13.22019/02/09 10:07:00:000 224.431 100.3 94.226 0.003 13.40 13.22019/02/09 10:08:00:000 224.431 100.3 94.226 0.003 13.40 13.22019/02/09 10:09:00:000 224.431 100.2 94.282 0.003 13.41 13.22019/02/09 10:10:00:000 224.431 100.2 94.282 0.003 13.41 12.92019/02/09 10:11:00:000 224.431 100.2 94.304 0.003 13.41 12.92019/02/09 10:12:00:000 224.431 100.2 94.304 0.003 13.41 13.22019/02/09 10:13:00:000 224.431 100.2 94.304 0.003 13.41 13.22019/02/09 10:14:00:000 224.693 100.2 94.404 0.003 13.41 13.42019/02/09 10:15:00:000 224.693 100.2 94.244 0.003 13.41 13.42019/02/09 10:16:00:000 224.693 100.3 94.356 0.003 13.41 13.42019/02/09 10:17:00:000 224.693 100.2 94.356 0.003 13.41 13.42019/02/09 10:18:00:000 224.693 100.2 94.356 0.003 13.41 13.42019/02/09 10:19:00:000 224.693 100.3 94.356 0.003 13.41 13.42019/02/09 10:20:00:000 224.693 100.4 94.408 0.003 13.41 13.02019/02/09 10:21:00:000 225.024 100.4 94.439 0.003 13.41 13.02019/02/09 10:22:00:000 225.024 100.3 94.439 0.003 13.41 13.02019/02/09 10:23:00:000 225.024 100.3 94.439 0.003 13.41 13.22019/02/09 10:24:00:000 224.495 100.3 94.280 0.003 13.41 13.22019/02/09 10:25:00:000 224.495 100.5 94.280 0.003 13.41 13.72019/02/09 10:26:00:000 224.495 100.5 94.280 0.003 13.41 13.72019/02/09 10:27:00:000 224.833 100.4 94.280 0.003 13.41 13.72019/02/09 10:28:00:000 224.584 100.4 94.280 0.003 13.40 13.7

Page 41: Division of Environmental Permits Floor

2019/02/09 10:29:00:000 224.584 100.4 94.280 0.003 13.40 13.92019/02/09 10:30:00:000 224.584 100.3 94.280 0.003 13.40 13.92019/02/09 10:31:00:000 224.584 100.3 94.280 0.003 13.40 13.92019/02/09 10:32:00:000 224.394 100.3 94.280 0.003 13.41 14.12019/02/09 10:33:00:000 224.394 100.4 94.266 0.003 13.41 14.12019/02/09 10:34:00:000 224.394 100.5 94.300 0.003 13.41 14.12019/02/09 10:35:00:000 224.891 100.5 94.300 0.003 13.41 14.12019/02/09 10:36:00:000 224.891 100.5 94.424 0.003 13.41 14.12019/02/09 10:37:00:000 224.891 100.4 94.255 0.003 13.40 13.92019/02/09 10:38:00:000 224.355 100.4 94.255 0.003 13.40 14.12019/02/09 10:39:00:000 224.355 100.4 94.192 0.003 13.40 14.42019/02/09 10:40:00:000 224.355 100.5 94.192 0.003 13.40 14.42019/02/09 10:41:00:000 224.355 100.4 94.290 0.003 13.40 14.42019/02/09 10:42:00:000 224.355 100.4 94.192 0.003 13.40 14.12019/02/09 10:43:00:000 224.355 100.4 94.192 0.003 13.40 14.12019/02/09 10:44:00:000 224.081 100.6 94.192 0.003 13.40 14.42019/02/09 10:45:00:000 224.081 100.4 94.232 0.003 13.41 14.42019/02/09 10:46:00:000 224.081 100.4 94.120 0.003 13.41 14.62019/02/09 10:47:00:000 224.081 100.4 94.029 0.003 13.41 14.62019/02/09 10:48:00:000 224.081 100.6 94.029 0.003 13.41 14.42019/02/09 10:49:00:000 224.081 100.5 94.168 0.003 13.41 14.42019/02/09 10:50:00:000 224.081 100.3 94.339 0.003 13.41 14.42019/02/09 10:51:00:000 224.269 100.3 94.220 0.003 13.41 14.12019/02/09 10:52:00:000 224.796 100.4 94.231 0.003 13.41 14.12019/02/09 10:53:00:000 224.226 100.3 94.376 0.003 13.41 14.42019/02/09 10:54:00:000 224.644 100.3 94.278 0.003 13.41 14.42019/02/09 10:55:00:000 224.644 100.4 94.322 0.003 13.41 14.12019/02/09 10:56:00:000 224.644 100.2 94.322 0.003 13.41 14.12019/02/09 10:57:00:000 224.644 100.4 94.159 0.003 13.41 14.12019/02/09 10:58:00:000 224.473 100.4 94.360 0.003 13.41 14.12019/02/09 10:59:00:000 224.473 100.3 94.208 0.003 13.41 14.12019/02/09 11:00:00:000 224.171 100.3 94.208 0.003 13.39 14.12019/02/09 11:01:00:000 224.171 100.2 94.190 0.003 13.39 14.12019/02/09 11:02:00:000 224.171 100.2 94.190 0.003 13.41 13.92019/02/09 11:03:00:000 224.171 100.2 94.190 0.003 13.41 13.92019/02/09 11:04:00:000 224.171 100.3 94.190 0.003 13.41 13.92019/02/09 11:05:00:000 224.171 100.3 94.190 0.003 13.41 14.42019/02/09 11:06:00:000 224.171 100.3 94.102 0.003 13.41 14.42019/02/09 11:07:00:000 224.371 100.3 94.175 0.003 13.41 14.42019/02/09 11:08:00:000 224.371 100.3 94.175 0.003 13.41 14.62019/02/09 11:09:00:000 224.051 100.3 94.175 0.003 13.41 14.82019/02/09 11:10:00:000 224.051 100.4 94.175 0.003 13.40 14.82019/02/09 11:11:00:000 224.332 100.4 94.175 0.003 13.40 14.82019/02/09 11:12:00:000 224.332 100.5 94.333 0.003 13.40 14.42019/02/09 11:13:00:000 224.632 100.5 94.333 0.003 13.40 14.42019/02/09 11:14:00:000 224.632 100.4 94.270 0.003 13.40 14.42019/02/09 11:15:00:000 224.171 100.6 94.193 0.003 13.40 14.42019/02/09 11:16:00:000 224.171 100.6 94.193 0.003 13.40 14.42019/02/09 11:17:00:000 224.455 100.4 94.076 0.003 13.40 14.62019/02/09 11:18:00:000 224.105 100.6 94.076 0.003 13.40 14.62019/02/09 11:19:00:000 224.105 100.4 94.076 0.003 13.40 14.92019/02/09 11:20:00:000 224.105 100.5 94.076 0.003 13.40 14.92019/02/09 11:21:00:000 224.105 100.5 94.135 0.003 13.41 14.92019/02/09 11:22:00:000 224.105 100.5 94.135 0.003 13.41 15.12019/02/09 11:23:00:000 224.105 100.5 94.135 0.003 13.41 15.12019/02/09 11:24:00:000 223.805 100.6 94.135 0.003 13.41 15.52019/02/09 11:25:00:000 224.152 100.5 94.135 0.003 13.41 15.52019/02/09 11:26:00:000 224.152 100.4 93.981 0.003 13.41 15.32019/02/09 11:27:00:000 223.970 100.6 94.159 0.003 13.41 15.32019/02/09 11:28:00:000 223.970 100.5 94.033 0.003 13.41 15.32019/02/09 11:29:00:000 224.272 100.5 94.220 0.003 13.41 15.32019/02/09 11:30:00:000 224.272 100.5 94.278 0.003 13.41 15.32019/02/09 11:31:00:000 224.272 100.5 94.332 0.003 13.41 15.12019/02/09 11:32:00:000 224.272 100.4 94.263 0.003 13.41 15.12019/02/09 11:33:00:000 224.272 100.4 94.159 0.003 13.41 15.12019/02/09 11:34:00:000 224.272 100.4 94.159 0.003 13.41 14.92019/02/09 11:35:00:000 224.272 100.5 94.234 0.003 13.41 14.92019/02/09 11:36:00:000 224.595 100.5 94.139 0.003 13.41 14.92019/02/09 11:37:00:000 224.251 100.4 94.139 0.003 13.40 15.12019/02/09 11:38:00:000 224.251 100.3 94.139 0.003 13.40 15.32019/02/09 11:39:00:000 223.730 100.4 94.019 0.003 13.40 15.52019/02/09 11:40:00:000 223.730 100.4 93.859 0.003 13.40 15.52019/02/09 11:41:00:000 223.730 100.4 93.979 0.003 13.41 15.72019/02/09 11:42:00:000 223.398 100.6 93.818 0.003 13.41 15.72019/02/09 11:43:00:000 223.398 100.7 93.989 0.003 13.41 15.72019/02/09 11:44:00:000 223.790 100.5 93.989 0.003 13.42 15.72019/02/09 11:45:00:000 223.790 100.5 94.089 0.003 13.42 15.7

Page 42: Division of Environmental Permits Floor

2019/02/09 11:46:00:000 223.790 100.5 93.931 0.003 13.42 16.02019/02/09 11:47:00:000 223.790 100.5 93.931 0.003 13.42 16.02019/02/09 11:48:00:000 223.790 100.4 94.108 0.003 13.42 16.22019/02/09 11:49:00:000 223.790 100.4 94.056 0.003 13.42 16.22019/02/09 11:50:00:000 223.239 100.6 93.919 0.003 13.41 16.02019/02/09 11:51:00:000 223.729 100.6 93.919 0.003 13.41 16.22019/02/09 11:52:00:000 223.729 100.6 94.095 0.003 13.41 16.22019/02/09 11:53:00:000 224.088 100.5 94.095 0.003 13.41 16.22019/02/09 11:54:00:000 224.088 100.5 94.095 0.003 13.41 16.02019/02/09 11:55:00:000 224.088 100.4 94.195 0.003 13.41 16.02019/02/09 11:56:00:000 223.815 100.4 94.091 0.003 13.41 15.72019/02/09 11:57:00:000 224.135 100.4 94.091 0.003 13.41 15.72019/02/09 11:58:00:000 224.135 100.5 94.091 0.003 13.41 15.72019/02/09 11:59:00:000 223.624 100.5 93.916 0.003 13.41 16.02019/02/09 12:00:00:000 223.624 100.5 94.008 0.003 13.41 16.02019/02/09 12:01:00:000 223.624 100.4 93.937 0.003 13.41 16.22019/02/09 12:02:00:000 223.624 100.5 93.937 0.003 13.41 16.22019/02/09 12:03:00:000 223.969 100.5 94.090 0.003 13.41 16.22019/02/09 12:04:00:000 223.969 100.5 94.013 0.003 13.41 16.02019/02/09 12:05:00:000 223.756 100.6 94.013 0.003 13.42 16.22019/02/09 12:06:00:000 223.756 100.4 94.013 0.003 13.42 16.02019/02/09 12:07:00:000 223.756 100.4 93.792 0.003 13.42 16.52019/02/09 12:08:00:000 223.039 100.4 93.837 0.003 13.41 16.52019/02/09 12:09:00:000 223.518 100.4 93.837 0.003 13.41 16.52019/02/09 12:10:00:000 223.518 100.7 93.837 0.003 13.41 16.52019/02/09 12:11:00:000 223.518 100.4 93.837 0.003 13.41 16.72019/02/09 12:12:00:000 223.004 100.5 93.760 0.003 13.42 17.22019/02/09 12:13:00:000 223.284 100.5 93.760 0.003 13.42 17.22019/02/09 12:14:00:000 223.284 100.6 93.841 0.003 13.42 17.22019/02/09 12:15:00:000 223.284 100.5 93.841 0.003 13.42 17.42019/02/09 12:16:00:000 223.284 100.5 93.971 0.003 13.42 17.22019/02/09 12:17:00:000 223.487 100.5 93.874 0.003 13.42 16.92019/02/09 12:18:00:000 223.487 100.6 93.874 0.003 13.42 16.92019/02/09 12:19:00:000 223.487 100.5 93.874 0.003 13.42 16.92019/02/09 12:20:00:000 223.487 100.6 93.874 0.003 13.42 16.72019/02/09 12:21:00:000 223.487 100.5 93.874 0.003 13.42 16.72019/02/09 12:22:00:000 223.487 100.4 93.874 0.003 13.42 16.72019/02/09 12:23:00:000 223.317 100.5 93.643 0.003 13.42 16.72019/02/09 12:24:00:000 223.317 100.4 93.780 0.003 13.42 16.72019/02/09 12:25:00:000 223.317 100.5 93.780 0.003 13.42 16.92019/02/09 12:26:00:000 222.797 100.4 93.780 0.003 13.42 16.92019/02/09 12:27:00:000 223.255 100.5 93.892 0.003 13.42 17.22019/02/09 12:28:00:000 223.255 100.5 93.761 0.003 13.42 17.22019/02/09 12:29:00:000 223.255 100.5 93.861 0.003 13.42 17.22019/02/09 12:30:00:000 223.255 100.6 93.773 0.003 13.42 17.62019/02/09 12:31:00:000 223.504 100.6 93.956 0.003 13.42 17.42019/02/09 12:32:00:000 223.504 100.6 93.926 0.003 13.42 17.42019/02/09 12:33:00:000 223.504 100.6 93.926 0.003 13.42 17.42019/02/09 12:34:00:000 223.504 100.5 93.926 0.003 13.42 17.22019/02/09 12:35:00:000 223.504 100.5 93.926 0.003 13.41 17.22019/02/09 12:36:00:000 223.504 100.5 93.858 0.003 13.41 17.22019/02/09 12:37:00:000 223.292 100.5 93.858 0.003 13.41 17.42019/02/09 12:38:00:000 223.292 100.5 93.729 0.003 13.41 17.62019/02/09 12:39:00:000 223.292 100.6 93.729 0.003 13.41 17.62019/02/09 12:40:00:000 222.841 100.5 93.824 0.003 13.41 17.92019/02/09 12:41:00:000 222.841 100.5 93.663 0.003 13.42 17.62019/02/09 12:42:00:000 223.167 100.5 93.759 0.003 13.42 17.62019/02/09 12:43:00:000 223.167 100.5 93.611 0.003 13.42 17.62019/02/09 12:44:00:000 223.039 100.4 93.735 0.003 13.42 17.92019/02/09 12:45:00:000 222.723 100.5 93.680 0.003 13.42 18.32019/02/09 12:46:00:000 222.723 100.4 93.680 0.003 13.42 18.32019/02/09 12:47:00:000 223.237 100.5 93.785 0.003 13.42 18.32019/02/09 12:48:00:000 223.237 100.6 93.785 0.003 13.42 18.12019/02/09 12:49:00:000 223.237 100.5 93.719 0.003 13.42 18.12019/02/09 12:50:00:000 223.237 100.6 93.719 0.003 13.42 17.82019/02/09 12:51:00:000 223.091 100.5 93.600 0.003 13.42 17.82019/02/09 12:52:00:000 223.091 100.5 93.797 0.003 13.42 17.82019/02/09 12:53:00:000 223.091 100.5 93.797 0.003 13.42 17.82019/02/09 12:54:00:000 223.091 100.3 93.760 0.003 13.42 17.62019/02/09 12:55:00:000 223.091 100.4 93.545 0.003 13.42 17.62019/02/09 12:56:00:000 222.682 100.5 93.545 0.003 13.42 17.92019/02/09 12:57:00:000 223.114 100.4 93.759 0.003 13.42 18.12019/02/09 12:58:00:000 223.114 100.4 93.759 0.003 13.43 17.92019/02/09 12:59:00:000 223.114 100.4 93.698 0.003 13.43 17.92019/02/09 13:00:00:000 222.870 100.6 93.698 0.003 13.43 18.12019/02/09 13:01:00:000 222.870 100.5 93.462 0.003 13.43 17.92019/02/09 13:02:00:000 222.870 100.4 93.716 0.003 13.42 18.1

Page 43: Division of Environmental Permits Floor

2019/02/09 13:03:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:04:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:05:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:06:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:07:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:08:00:000 222.870 100.5 93.716 0.003 13.42 17.92019/02/09 13:09:00:000 222.870 100.5 93.532 0.003 13.42 18.32019/02/09 13:10:00:000 222.870 100.4 93.715 0.003 13.42 18.32019/02/09 13:11:00:000 222.870 100.4 93.715 0.003 13.42 18.32019/02/09 13:12:00:000 222.870 100.5 93.715 0.003 13.42 18.52019/02/09 13:13:00:000 222.870 100.6 93.715 0.003 13.42 18.52019/02/09 13:14:00:000 222.028 100.2 93.421 0.003 13.42 18.52019/02/09 13:15:00:000 221.397 100.0 93.214 0.003 13.42 18.52019/02/09 13:16:00:000 222.402 100.4 93.495 0.003 13.46 18.52019/02/09 13:17:00:000 222.963 100.6 93.801 0.003 13.46 18.52019/02/09 13:18:00:000 223.370 100.6 93.801 0.003 13.43 18.32019/02/09 13:19:00:000 222.890 100.4 93.838 0.003 13.43 18.12019/02/09 13:20:00:000 222.890 100.4 93.681 0.003 13.41 18.12019/02/09 13:21:00:000 222.890 100.4 93.681 0.003 13.41 17.92019/02/09 13:22:00:000 222.890 100.4 93.715 0.003 13.41 17.92019/02/09 13:23:00:000 222.890 100.4 93.715 0.003 13.41 17.92019/02/09 13:24:00:000 223.204 100.5 93.791 0.003 13.41 17.92019/02/09 13:25:00:000 222.853 100.5 93.713 0.003 13.42 17.92019/02/09 13:26:00:000 222.853 100.4 93.713 0.003 13.42 17.42019/02/09 13:27:00:000 222.853 100.6 93.713 0.003 13.42 17.62019/02/09 13:28:00:000 222.853 100.6 93.713 0.003 13.42 17.62019/02/09 13:29:00:000 223.184 100.5 93.713 0.003 13.42 17.62019/02/09 13:30:00:000 223.184 100.5 93.713 0.003 13.42 17.82019/02/09 13:31:00:000 222.784 100.5 93.713 0.003 13.42 17.82019/02/09 13:32:00:000 222.784 100.5 93.672 0.003 13.42 17.82019/02/09 13:33:00:000 222.784 100.4 93.672 0.003 13.42 17.8

AVERAGE: 223.99 100.40 94.09 0.00 13.41 15.20

Page 44: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 11 CTG-1 WO/DB Run 2DCS Data - 20190210 - 0820-1640

Unit 11 GT Power Unit 11 GT PowerUnit 11 Total GT

Gas FlowUnit 11 HRSG DB Fuel Flow

Unit 11 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 11HAD00EU001 11MKA01EU902A 11MBP10CF910 11HHA10CF001 11HNE10CQ109 11MBL05CT1012019/02/10 08:28:00:000 228.199 100.6 95.563 0.002 13.36 8.12019/02/10 08:29:00:000 227.375 100.6 95.451 0.002 13.36 8.32019/02/10 08:30:00:000 227.782 100.6 95.420 0.002 13.36 8.32019/02/10 08:31:00:000 227.782 100.7 95.420 0.002 13.36 8.82019/02/10 08:32:00:000 228.149 100.7 95.506 0.002 13.38 8.52019/02/10 08:33:00:000 228.149 100.7 95.506 0.002 13.38 8.52019/02/10 08:34:00:000 228.149 100.7 95.548 0.002 13.38 8.52019/02/10 08:35:00:000 228.149 100.7 95.426 0.002 13.37 8.52019/02/10 08:36:00:000 228.149 100.6 95.498 0.003 13.37 8.52019/02/10 08:37:00:000 228.149 100.6 95.498 0.003 13.37 8.32019/02/10 08:38:00:000 227.691 100.6 95.432 0.003 13.37 8.32019/02/10 08:39:00:000 227.691 100.6 95.308 0.003 13.37 8.32019/02/10 08:40:00:000 227.691 100.6 95.173 0.003 13.37 9.02019/02/10 08:41:00:000 227.269 100.5 95.070 0.003 13.37 9.72019/02/10 08:42:00:000 227.269 100.5 95.285 0.003 13.37 9.92019/02/10 08:43:00:000 226.869 100.6 95.105 0.003 13.37 9.92019/02/10 08:44:00:000 226.869 100.5 95.105 0.003 13.38 9.92019/02/10 08:45:00:000 227.086 100.5 95.105 0.003 13.38 10.62019/02/10 08:46:00:000 227.086 100.7 95.140 0.003 13.38 10.62019/02/10 08:47:00:000 227.086 100.6 95.302 0.003 20.77 10.12019/02/10 08:48:00:000 227.503 100.6 95.281 0.003 20.81 9.72019/02/10 08:49:00:000 227.503 100.6 95.281 0.003 -0.01 9.72019/02/10 08:50:00:000 227.503 100.6 95.281 0.003 -0.01 9.72019/02/10 08:51:00:000 226.901 100.5 95.189 0.003 13.26 9.72019/02/10 08:52:00:000 227.151 100.5 95.153 0.003 13.33 9.92019/02/10 08:53:00:000 227.151 100.5 95.252 0.003 13.38 9.92019/02/10 08:54:00:000 227.151 100.5 95.147 0.003 13.38 9.92019/02/10 08:55:00:000 227.151 100.6 95.031 0.003 13.38 9.92019/02/10 08:56:00:000 227.151 100.6 95.109 0.003 13.38 10.12019/02/10 08:57:00:000 227.151 100.6 95.109 0.003 13.38 10.42019/02/10 08:58:00:000 227.151 100.6 95.258 0.003 13.38 10.42019/02/10 08:59:00:000 227.151 100.6 95.104 0.003 13.38 10.42019/02/10 09:00:00:000 226.673 100.6 95.062 0.003 13.38 10.12019/02/10 09:01:00:000 227.168 100.6 95.062 0.003 13.38 10.42019/02/10 09:02:00:000 226.776 100.5 95.062 0.003 13.38 10.42019/02/10 09:03:00:000 226.776 100.6 95.062 0.003 13.38 10.42019/02/10 09:04:00:000 227.194 100.6 95.081 0.003 13.38 10.42019/02/10 09:05:00:000 227.194 100.5 95.149 0.003 13.38 10.42019/02/10 09:06:00:000 226.824 100.6 95.149 0.003 13.38 10.42019/02/10 09:07:00:000 227.009 100.6 95.149 0.003 13.39 10.42019/02/10 09:08:00:000 227.009 100.6 95.087 0.003 13.39 10.42019/02/10 09:09:00:000 227.009 100.6 95.152 0.003 13.39 10.42019/02/10 09:10:00:000 227.009 100.6 95.152 0.003 13.39 10.12019/02/10 09:11:00:000 227.009 100.6 95.152 0.003 13.39 10.12019/02/10 09:12:00:000 227.009 100.5 95.070 0.003 13.37 10.42019/02/10 09:13:00:000 226.338 100.5 94.907 0.003 13.37 10.42019/02/10 09:14:00:000 226.338 100.5 94.907 0.003 13.37 11.12019/02/10 09:15:00:000 226.338 100.4 94.907 0.003 13.39 11.32019/02/10 09:16:00:000 226.338 100.5 94.733 0.003 13.39 11.62019/02/10 09:17:00:000 226.086 100.6 94.719 0.003 13.39 11.62019/02/10 09:18:00:000 226.086 100.6 94.840 0.002 13.39 11.62019/02/10 09:19:00:000 226.381 100.6 94.881 0.002 13.39 11.32019/02/10 09:20:00:000 226.381 100.6 95.019 0.002 13.39 11.32019/02/10 09:21:00:000 226.449 100.5 94.802 0.002 13.39 11.32019/02/10 09:22:00:000 226.449 100.6 94.881 0.002 13.39 11.32019/02/10 09:23:00:000 226.449 100.5 94.881 0.002 13.39 11.62019/02/10 09:24:00:000 226.449 100.5 94.881 0.002 13.39 11.62019/02/10 09:25:00:000 226.449 100.5 94.881 0.002 13.39 11.62019/02/10 09:26:00:000 226.449 100.3 94.935 0.002 13.39 11.32019/02/10 09:27:00:000 226.094 100.5 94.820 0.002 13.38 11.62019/02/10 09:28:00:000 226.094 100.7 94.820 0.002 13.38 11.62019/02/10 09:29:00:000 226.390 100.5 94.998 0.002 13.38 11.82019/02/10 09:30:00:000 226.390 100.5 94.824 0.002 13.39 11.62019/02/10 09:31:00:000 226.096 100.5 94.806 0.002 13.39 11.62019/02/10 09:32:00:000 226.096 100.5 94.806 0.002 13.39 11.82019/02/10 09:33:00:000 226.096 100.4 94.729 0.002 13.39 11.82019/02/10 09:34:00:000 225.680 100.5 94.729 0.002 13.39 11.8

Page 45: Division of Environmental Permits Floor

2019/02/10 09:35:00:000 225.680 100.6 94.729 0.002 13.39 12.02019/02/10 09:36:00:000 226.176 100.3 94.729 0.002 13.39 12.02019/02/10 09:37:00:000 225.569 100.4 94.564 0.002 13.39 12.02019/02/10 09:38:00:000 225.569 100.5 94.754 0.002 13.39 12.32019/02/10 09:39:00:000 225.569 100.5 94.645 0.002 13.40 12.72019/02/10 09:40:00:000 226.065 100.5 94.734 0.002 13.40 13.02019/02/10 09:41:00:000 225.600 100.5 94.579 0.002 13.40 13.02019/02/10 09:42:00:000 225.600 100.4 94.688 0.002 13.40 13.02019/02/10 09:43:00:000 225.600 100.5 94.688 0.002 13.40 12.72019/02/10 09:44:00:000 225.600 100.4 94.556 0.002 13.40 12.92019/02/10 09:45:00:000 225.048 100.4 94.397 0.002 13.40 13.22019/02/10 09:46:00:000 225.048 100.7 94.686 0.002 13.40 13.72019/02/10 09:47:00:000 225.770 100.7 94.686 0.002 13.40 13.72019/02/10 09:48:00:000 225.770 100.3 94.682 0.002 13.40 13.42019/02/10 09:49:00:000 225.063 100.4 94.388 0.002 13.40 13.42019/02/10 09:50:00:000 225.063 100.3 94.328 0.002 13.40 13.22019/02/10 09:51:00:000 225.063 100.5 94.389 0.002 13.39 13.72019/02/10 09:52:00:000 225.063 100.5 94.540 0.002 13.39 13.72019/02/10 09:53:00:000 225.321 100.5 94.540 0.002 13.39 13.92019/02/10 09:54:00:000 225.321 100.6 94.540 0.002 13.39 14.12019/02/10 09:55:00:000 225.321 100.6 94.613 0.002 13.40 14.12019/02/10 09:56:00:000 225.686 100.5 94.613 0.002 13.40 14.12019/02/10 09:57:00:000 225.076 100.3 94.412 0.002 13.40 13.92019/02/10 09:58:00:000 224.618 100.6 94.221 0.002 13.40 14.42019/02/10 09:59:00:000 225.211 100.5 94.383 0.002 13.40 14.42019/02/10 10:00:00:000 225.211 100.4 94.518 0.002 13.40 14.62019/02/10 10:01:00:000 225.211 100.6 94.384 0.002 13.40 14.62019/02/10 10:02:00:000 225.211 100.5 94.640 0.002 13.40 14.62019/02/10 10:03:00:000 225.211 100.4 94.424 0.002 13.40 14.62019/02/10 10:04:00:000 225.211 100.6 94.540 0.002 13.40 14.62019/02/10 10:05:00:000 225.730 100.6 94.607 0.002 13.40 14.62019/02/10 10:06:00:000 225.730 100.5 94.607 0.002 13.40 14.42019/02/10 10:07:00:000 225.347 100.5 94.607 0.002 13.40 14.42019/02/10 10:08:00:000 224.707 100.3 94.474 0.002 13.40 14.42019/02/10 10:09:00:000 224.707 100.5 94.330 0.002 13.40 14.82019/02/10 10:10:00:000 224.707 100.5 94.330 0.002 13.40 15.32019/02/10 10:11:00:000 224.707 100.5 94.492 0.002 13.40 15.32019/02/10 10:12:00:000 225.000 100.5 94.338 0.002 13.41 15.32019/02/10 10:13:00:000 225.000 100.5 94.478 0.002 13.41 15.32019/02/10 10:14:00:000 225.470 100.5 94.580 0.002 13.41 14.82019/02/10 10:15:00:000 225.470 100.5 94.580 0.002 13.41 14.62019/02/10 10:16:00:000 225.022 100.4 94.449 0.002 13.39 14.62019/02/10 10:17:00:000 225.022 100.5 94.449 0.002 13.39 14.42019/02/10 10:18:00:000 225.022 100.4 94.449 0.002 13.39 14.62019/02/10 10:19:00:000 224.621 100.5 94.288 0.002 13.39 14.92019/02/10 10:20:00:000 224.993 100.5 94.400 0.002 13.41 14.92019/02/10 10:21:00:000 224.993 100.4 94.400 0.002 13.41 15.12019/02/10 10:22:00:000 224.993 100.4 94.502 0.002 13.41 15.12019/02/10 10:23:00:000 224.993 100.6 94.355 0.002 13.41 14.82019/02/10 10:24:00:000 224.993 100.3 94.371 0.002 13.41 14.82019/02/10 10:25:00:000 224.993 100.5 94.371 0.002 13.41 15.12019/02/10 10:26:00:000 224.882 100.5 94.209 0.002 13.41 15.12019/02/10 10:27:00:000 223.928 100.5 94.043 0.002 13.41 15.52019/02/10 10:28:00:000 223.928 100.7 93.983 0.002 13.39 16.02019/02/10 10:29:00:000 223.928 100.5 94.125 0.002 13.41 16.02019/02/10 10:30:00:000 223.928 100.6 94.004 0.002 13.41 16.22019/02/10 10:31:00:000 223.535 100.6 93.873 0.002 13.41 16.52019/02/10 10:32:00:000 223.535 100.6 93.991 0.002 13.41 16.92019/02/10 10:33:00:000 223.590 100.5 93.785 0.002 13.41 17.22019/02/10 10:34:00:000 223.590 100.7 93.910 0.002 13.41 17.22019/02/10 10:35:00:000 224.423 100.7 94.111 0.002 13.41 16.92019/02/10 10:36:00:000 224.423 100.6 94.241 0.002 13.43 16.92019/02/10 10:37:00:000 224.423 100.6 94.241 0.002 13.43 16.92019/02/10 10:38:00:000 224.423 100.4 94.241 0.002 13.41 16.92019/02/10 10:39:00:000 223.816 100.6 93.985 0.002 13.41 16.72019/02/10 10:40:00:000 223.816 100.8 94.013 0.002 13.41 17.42019/02/10 10:41:00:000 223.816 100.7 94.013 0.002 13.41 17.82019/02/10 10:42:00:000 223.453 100.4 93.934 0.002 13.41 17.82019/02/10 10:43:00:000 223.068 100.5 93.795 0.002 13.41 18.12019/02/10 10:44:00:000 223.068 100.4 93.697 0.002 13.41 18.32019/02/10 10:45:00:000 223.068 100.6 93.697 0.002 13.41 18.32019/02/10 10:46:00:000 223.068 100.7 93.800 0.002 13.41 18.82019/02/10 10:47:00:000 223.068 100.6 93.800 0.002 13.41 18.82019/02/10 10:48:00:000 223.068 100.7 93.717 0.002 13.41 19.02019/02/10 10:49:00:000 223.068 100.5 93.691 0.002 13.43 18.52019/02/10 10:50:00:000 223.068 100.9 93.868 0.002 13.43 18.52019/02/10 10:51:00:000 223.736 100.7 93.868 0.002 13.43 18.3

Page 46: Division of Environmental Permits Floor

2019/02/10 10:52:00:000 223.149 100.6 93.862 0.002 13.42 18.12019/02/10 10:53:00:000 223.149 100.6 93.862 0.002 13.42 18.32019/02/10 10:54:00:000 222.568 100.7 93.597 0.002 13.41 18.52019/02/10 10:55:00:000 222.568 100.7 93.597 0.002 13.41 18.82019/02/10 10:56:00:000 222.568 100.7 93.462 0.002 13.41 18.82019/02/10 10:57:00:000 222.568 100.8 93.599 0.002 13.41 19.32019/02/10 10:58:00:000 223.326 100.6 93.801 0.002 13.43 19.32019/02/10 10:59:00:000 223.326 100.6 93.801 0.002 13.43 18.52019/02/10 11:00:00:000 222.944 100.4 93.801 0.002 13.43 18.52019/02/10 11:01:00:000 222.944 100.6 93.582 0.002 13.43 18.32019/02/10 11:02:00:000 222.521 100.6 93.582 0.002 13.43 18.32019/02/10 11:03:00:000 222.521 100.6 93.582 0.002 13.42 18.82019/02/10 11:04:00:000 222.521 100.6 93.582 0.002 13.42 18.82019/02/10 11:05:00:000 222.747 100.5 93.582 0.002 13.42 19.02019/02/10 11:06:00:000 222.747 100.5 93.582 0.002 13.42 18.82019/02/10 11:07:00:000 222.747 100.5 93.668 0.002 13.42 19.32019/02/10 11:08:00:000 222.747 100.5 93.860 0.002 13.42 19.72019/02/10 11:09:00:000 222.747 100.5 93.780 0.002 13.42 19.72019/02/10 11:10:00:000 222.926 100.5 93.632 0.002 13.42 19.02019/02/10 11:11:00:000 222.926 100.6 93.764 0.002 13.42 19.02019/02/10 11:12:00:000 222.926 100.5 93.654 0.002 13.42 18.82019/02/10 11:13:00:000 222.416 100.4 93.467 0.002 13.42 18.82019/02/10 11:14:00:000 222.416 100.6 93.467 0.002 13.42 18.82019/02/10 11:15:00:000 222.050 100.6 93.467 0.002 13.42 19.32019/02/10 11:16:00:000 222.050 100.7 93.556 0.002 13.42 19.52019/02/10 11:17:00:000 222.565 100.7 93.770 0.002 13.44 19.52019/02/10 11:18:00:000 223.175 100.4 93.770 0.002 13.44 19.52019/02/10 11:19:00:000 222.788 100.3 93.432 0.002 13.44 19.32019/02/10 11:20:00:000 222.397 100.4 93.545 0.002 13.41 19.52019/02/10 11:21:00:000 222.397 100.4 93.545 0.002 13.41 20.02019/02/10 11:22:00:000 222.852 100.5 93.728 0.002 13.44 19.72019/02/10 11:23:00:000 222.852 100.4 93.546 0.002 13.44 19.72019/02/10 11:24:00:000 222.075 100.5 93.546 0.002 13.41 19.52019/02/10 11:25:00:000 222.209 100.6 93.440 0.002 13.41 20.22019/02/10 11:26:00:000 221.430 100.5 93.332 0.002 13.41 20.62019/02/10 11:27:00:000 222.087 100.9 93.332 0.002 13.41 20.62019/02/10 11:28:00:000 222.087 100.5 93.542 0.002 13.43 20.82019/02/10 11:29:00:000 222.087 100.6 93.342 0.002 13.43 21.12019/02/10 11:30:00:000 222.087 100.4 93.290 0.002 13.43 21.12019/02/10 11:31:00:000 221.573 100.5 93.167 0.002 13.43 21.12019/02/10 11:32:00:000 221.573 100.6 93.167 0.002 13.43 21.62019/02/10 11:33:00:000 221.573 100.6 93.335 0.002 13.43 21.62019/02/10 11:34:00:000 221.573 100.7 93.381 0.002 13.43 21.62019/02/10 11:35:00:000 221.980 100.6 93.507 0.002 13.43 21.32019/02/10 11:36:00:000 222.276 100.5 93.412 0.002 13.43 21.32019/02/10 11:37:00:000 222.276 100.6 93.412 0.002 13.43 21.12019/02/10 11:38:00:000 221.599 100.5 93.412 0.002 13.43 21.12019/02/10 11:39:00:000 221.983 100.5 93.299 0.002 13.43 20.82019/02/10 11:40:00:000 221.983 100.6 93.386 0.002 13.43 20.82019/02/10 11:41:00:000 221.983 100.4 93.386 0.002 13.43 20.62019/02/10 11:42:00:000 221.983 100.5 93.292 0.002 13.43 20.62019/02/10 11:43:00:000 221.486 100.3 93.292 0.002 13.43 20.42019/02/10 11:44:00:000 221.486 100.4 93.151 0.002 13.43 21.12019/02/10 11:45:00:000 222.137 100.5 93.306 0.002 13.43 20.62019/02/10 11:46:00:000 221.472 100.3 93.306 0.002 13.43 20.22019/02/10 11:47:00:000 221.472 100.4 93.291 0.002 13.43 20.42019/02/10 11:48:00:000 221.472 100.3 93.174 0.002 13.43 20.42019/02/10 11:49:00:000 220.922 100.5 93.046 0.002 13.43 21.12019/02/10 11:50:00:000 221.117 100.4 93.046 0.002 13.43 21.62019/02/10 11:51:00:000 221.117 100.4 93.084 0.002 13.44 21.62019/02/10 11:52:00:000 221.117 100.5 93.084 0.002 13.44 21.62019/02/10 11:53:00:000 221.117 100.4 93.187 0.002 13.44 21.82019/02/10 11:54:00:000 221.214 100.5 93.120 0.002 13.44 21.62019/02/10 11:55:00:000 221.214 100.5 93.120 0.002 13.44 21.62019/02/10 11:56:00:000 221.553 100.4 93.262 0.002 13.44 21.12019/02/10 11:57:00:000 221.553 100.4 93.150 0.002 13.44 20.82019/02/10 11:58:00:000 221.188 100.3 93.150 0.002 13.44 21.12019/02/10 11:59:00:000 220.940 100.2 93.026 0.002 13.44 21.12019/02/10 12:00:00:000 220.940 100.5 93.097 0.002 13.44 21.62019/02/10 12:01:00:000 221.573 100.5 93.306 0.002 13.44 21.32019/02/10 12:02:00:000 221.573 100.5 93.306 0.002 13.44 20.62019/02/10 12:03:00:000 221.746 100.4 93.306 0.002 13.44 20.62019/02/10 12:04:00:000 221.120 100.3 93.159 0.002 13.44 20.42019/02/10 12:05:00:000 221.120 100.5 92.956 0.002 13.44 21.32019/02/10 12:06:00:000 221.120 100.5 93.175 0.002 13.44 21.32019/02/10 12:07:00:000 221.912 100.5 93.420 0.002 13.44 20.82019/02/10 12:08:00:000 221.419 100.2 93.102 0.002 13.44 21.1

Page 47: Division of Environmental Permits Floor

2019/02/10 12:09:00:000 220.700 100.4 92.996 0.002 13.44 21.12019/02/10 12:10:00:000 220.700 100.5 92.996 0.002 13.44 21.82019/02/10 12:11:00:000 221.050 100.5 93.125 0.002 13.44 22.12019/02/10 12:12:00:000 221.692 100.4 93.310 0.002 13.44 21.82019/02/10 12:13:00:000 221.692 100.4 93.257 0.002 13.44 21.82019/02/10 12:14:00:000 221.272 100.2 92.996 0.002 13.44 21.62019/02/10 12:15:00:000 220.640 100.4 92.996 0.002 13.42 22.52019/02/10 12:16:00:000 221.278 100.5 93.139 0.002 13.42 23.02019/02/10 12:17:00:000 221.278 100.5 93.341 0.002 13.45 22.52019/02/10 12:18:00:000 221.579 100.4 93.130 0.002 13.45 22.12019/02/10 12:19:00:000 221.579 100.5 93.179 0.002 13.45 22.12019/02/10 12:20:00:000 221.362 100.4 93.333 0.003 13.44 21.82019/02/10 12:21:00:000 221.362 100.2 93.117 0.003 13.44 21.82019/02/10 12:22:00:000 220.558 100.3 92.920 0.003 13.44 22.32019/02/10 12:23:00:000 221.004 100.4 92.920 0.003 13.44 22.32019/02/10 12:24:00:000 221.004 100.4 93.082 0.003 13.44 23.02019/02/10 12:25:00:000 221.004 100.4 93.082 0.003 13.44 23.0

AVERAGE: 224.24 100.52 94.16 0.00 13.36 15.91

Page 48: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 11 CTG-1 WO/DB Run 3DCS Data - 20190210 - 0820-1640

Unit 11 GT Power Unit 11 GT PowerUnit 11 Total GT

Gas FlowUnit 11 HRSG DB Fuel Flow

Unit 11 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 11HAD00EU001 11MKA01EU902A 11MBP10CF910 11HHA10CF001 11HNE10CQ109 11MBL05CT1012019/02/10 12:26:00:000 221.297 100.4 93.082 0.003 13.44 23.02019/02/10 12:27:00:000 221.297 100.4 93.082 0.003 13.44 23.02019/02/10 12:28:00:000 221.137 100.3 93.082 0.003 13.44 22.82019/02/10 12:29:00:000 221.137 100.3 93.082 0.003 13.44 22.82019/02/10 12:30:00:000 220.777 100.1 92.957 0.003 13.44 23.22019/02/10 12:31:00:000 220.577 100.5 92.813 0.003 13.44 23.22019/02/10 12:32:00:000 220.577 100.5 93.026 0.003 13.44 23.42019/02/10 12:33:00:000 220.577 100.4 92.812 0.003 13.44 23.42019/02/10 12:34:00:000 220.577 100.5 93.015 0.003 13.44 23.42019/02/10 12:35:00:000 220.577 100.4 92.758 0.003 13.44 23.02019/02/10 12:36:00:000 219.950 100.2 92.669 0.003 13.44 23.02019/02/10 12:37:00:000 219.950 100.5 92.669 0.003 13.44 22.82019/02/10 12:38:00:000 220.474 100.5 92.887 0.003 13.44 22.82019/02/10 12:39:00:000 220.474 100.3 92.887 0.003 13.44 23.22019/02/10 12:40:00:000 220.659 100.4 92.887 0.003 13.44 23.02019/02/10 12:41:00:000 220.659 100.4 92.954 0.003 13.44 23.42019/02/10 12:42:00:000 220.659 100.3 92.954 0.003 13.44 23.42019/02/10 12:43:00:000 220.659 100.3 92.937 0.003 13.44 23.42019/02/10 12:44:00:000 220.659 100.3 92.838 0.003 13.44 23.62019/02/10 12:45:00:000 220.659 100.5 92.838 0.003 13.44 23.42019/02/10 12:46:00:000 220.659 100.2 92.996 0.003 13.46 23.42019/02/10 12:47:00:000 220.659 100.3 92.746 0.003 13.42 23.02019/02/10 12:48:00:000 220.659 100.3 92.748 0.003 13.42 23.02019/02/10 12:49:00:000 220.266 100.5 92.840 0.003 13.42 23.02019/02/10 12:50:00:000 220.654 100.5 92.990 0.003 13.45 23.42019/02/10 12:51:00:000 220.654 100.3 92.990 0.003 13.45 23.42019/02/10 12:52:00:000 220.654 100.3 92.955 0.003 13.45 23.42019/02/10 12:53:00:000 220.026 100.3 92.787 0.003 13.45 23.42019/02/10 12:54:00:000 220.530 100.6 92.873 0.003 13.45 23.42019/02/10 12:55:00:000 220.530 100.5 92.992 0.003 13.45 23.62019/02/10 12:56:00:000 220.774 100.5 92.932 0.003 13.44 24.62019/02/10 12:57:00:000 220.774 100.4 93.077 0.003 13.44 24.92019/02/10 12:58:00:000 220.774 100.4 92.852 0.003 13.44 24.92019/02/10 12:59:00:000 220.316 100.4 92.852 0.003 13.44 24.62019/02/10 13:00:00:000 220.316 100.3 92.852 0.003 13.44 24.12019/02/10 13:01:00:000 220.098 100.4 92.711 0.003 13.44 24.12019/02/10 13:02:00:000 220.098 100.6 92.762 0.003 13.44 23.62019/02/10 13:03:00:000 220.392 100.4 92.826 0.003 13.44 23.62019/02/10 13:04:00:000 220.392 100.2 92.826 0.003 13.44 23.62019/02/10 13:05:00:000 219.733 100.4 92.826 0.003 13.44 23.42019/02/10 13:06:00:000 220.165 100.2 92.707 0.003 13.44 23.42019/02/10 13:07:00:000 220.035 100.4 92.674 0.003 13.44 23.42019/02/10 13:08:00:000 220.035 100.4 92.674 0.003 13.46 23.62019/02/10 13:09:00:000 220.035 100.4 92.754 0.003 13.46 23.62019/02/10 13:10:00:000 220.035 100.5 92.754 0.003 13.46 23.62019/02/10 13:11:00:000 220.378 100.5 92.875 0.003 13.45 23.62019/02/10 13:12:00:000 220.378 100.3 92.656 0.003 13.45 23.62019/02/10 13:13:00:000 220.378 100.3 92.813 0.003 13.45 23.42019/02/10 13:14:00:000 219.712 100.3 92.534 0.003 13.45 23.42019/02/10 13:15:00:000 219.712 100.3 92.706 0.003 13.45 23.92019/02/10 13:16:00:000 219.712 100.5 92.532 0.003 13.45 24.42019/02/10 13:17:00:000 219.712 100.6 92.751 0.003 13.45 24.42019/02/10 13:18:00:000 220.652 100.3 92.871 0.003 13.45 23.92019/02/10 13:19:00:000 220.582 100.6 92.871 0.003 13.45 23.92019/02/10 13:20:00:000 220.582 100.5 92.871 0.003 13.45 23.62019/02/10 13:21:00:000 220.582 100.1 92.871 0.003 13.45 23.62019/02/10 13:22:00:000 220.241 100.3 92.840 0.003 13.45 23.42019/02/10 13:23:00:000 220.241 100.3 92.840 0.003 13.45 23.02019/02/10 13:24:00:000 220.953 100.2 92.963 0.003 13.45 22.52019/02/10 13:25:00:000 220.662 100.3 92.963 0.003 13.45 22.12019/02/10 13:26:00:000 220.662 100.2 92.963 0.003 13.45 21.82019/02/10 13:27:00:000 220.662 100.1 92.963 0.003 13.45 21.82019/02/10 13:28:00:000 220.719 100.2 92.963 0.003 13.45 22.12019/02/10 13:29:00:000 220.719 100.3 92.881 0.003 13.45 22.12019/02/10 13:30:00:000 220.719 100.2 92.881 0.003 13.45 22.32019/02/10 13:31:00:000 220.023 100.0 92.881 0.003 13.45 22.32019/02/10 13:32:00:000 220.023 100.1 92.688 0.003 13.45 22.8

Page 49: Division of Environmental Permits Floor

2019/02/10 13:33:00:000 219.474 100.1 92.584 0.003 13.45 23.22019/02/10 13:34:00:000 220.173 100.4 92.861 0.003 13.45 23.42019/02/10 13:35:00:000 220.173 100.4 92.845 0.003 13.45 23.42019/02/10 13:36:00:000 220.602 100.3 92.845 0.003 13.45 23.42019/02/10 13:37:00:000 220.602 100.3 92.845 0.003 13.45 23.02019/02/10 13:38:00:000 220.185 100.2 92.845 0.003 13.45 23.02019/02/10 13:39:00:000 220.185 100.3 92.845 0.003 13.45 23.22019/02/10 13:40:00:000 220.185 100.1 92.775 0.003 13.45 23.22019/02/10 13:41:00:000 219.315 100.2 92.470 0.003 13.45 23.42019/02/10 13:42:00:000 219.315 100.2 92.596 0.003 13.45 24.12019/02/10 13:43:00:000 219.678 100.1 92.596 0.003 13.45 24.42019/02/10 13:44:00:000 218.927 100.1 92.367 0.003 13.45 24.42019/02/10 13:45:00:000 218.927 100.3 92.500 0.003 13.45 24.92019/02/10 13:46:00:000 219.373 100.5 92.635 0.003 13.45 24.92019/02/10 13:47:00:000 219.842 100.6 92.635 0.003 13.45 24.92019/02/10 13:48:00:000 219.842 100.5 92.635 0.003 13.45 24.92019/02/10 13:49:00:000 219.842 100.5 92.776 0.003 13.45 25.12019/02/10 13:50:00:000 220.451 100.5 92.833 0.003 13.45 24.62019/02/10 13:51:00:000 220.451 100.2 92.833 0.003 13.45 24.62019/02/10 13:52:00:000 220.110 100.2 92.661 0.003 13.45 24.12019/02/10 13:53:00:000 219.475 100.2 92.442 0.003 13.45 24.42019/02/10 13:54:00:000 218.957 100.2 92.442 0.003 13.45 24.42019/02/10 13:55:00:000 218.957 100.4 92.442 0.003 13.45 24.92019/02/10 13:56:00:000 218.957 100.5 92.442 0.003 13.45 24.92019/02/10 13:57:00:000 219.495 100.6 92.742 0.003 13.47 25.12019/02/10 13:58:00:000 219.990 100.5 92.742 0.003 13.47 25.32019/02/10 13:59:00:000 219.349 100.3 92.540 0.003 13.47 25.32019/02/10 14:00:00:000 219.349 100.3 92.269 0.003 13.45 25.72019/02/10 14:01:00:000 219.235 100.5 92.561 0.003 13.45 26.02019/02/10 14:02:00:000 219.781 100.5 92.682 0.003 13.45 25.82019/02/10 14:03:00:000 219.781 100.6 92.790 0.003 13.46 25.82019/02/10 14:04:00:000 220.174 100.4 92.790 0.003 13.46 25.12019/02/10 14:05:00:000 220.174 100.4 92.790 0.003 13.46 25.12019/02/10 14:06:00:000 220.174 100.2 92.790 0.003 13.46 24.42019/02/10 14:07:00:000 219.942 100.1 92.704 0.003 13.45 24.12019/02/10 14:08:00:000 219.552 100.2 92.704 0.003 13.45 24.12019/02/10 14:09:00:000 219.552 100.1 92.601 0.003 13.45 24.12019/02/10 14:10:00:000 219.552 100.1 92.601 0.003 13.45 24.42019/02/10 14:11:00:000 219.144 100.3 92.409 0.003 13.45 24.42019/02/10 14:12:00:000 219.491 100.3 92.606 0.003 13.47 24.92019/02/10 14:13:00:000 219.491 100.2 92.606 0.003 13.47 24.92019/02/10 14:14:00:000 218.956 100.2 92.296 0.003 13.47 24.92019/02/10 14:15:00:000 218.956 100.2 92.472 0.003 13.47 25.12019/02/10 14:16:00:000 219.279 100.3 92.472 0.003 13.46 25.32019/02/10 14:17:00:000 219.279 100.2 92.617 0.003 13.46 25.32019/02/10 14:18:00:000 219.279 100.4 92.528 0.003 13.46 25.12019/02/10 14:19:00:000 219.279 100.3 92.528 0.003 13.46 25.12019/02/10 14:20:00:000 219.279 100.6 92.528 0.003 13.46 25.12019/02/10 14:21:00:000 219.279 100.3 92.639 0.003 13.46 25.12019/02/10 14:22:00:000 219.279 100.6 92.553 0.003 13.46 25.12019/02/10 14:23:00:000 219.279 100.5 92.767 0.003 13.46 25.12019/02/10 14:24:00:000 219.279 100.3 92.614 0.003 13.46 25.12019/02/10 14:25:00:000 218.661 100.3 92.491 0.003 13.46 25.52019/02/10 14:26:00:000 218.661 100.6 92.377 0.003 13.46 25.52019/02/10 14:27:00:000 218.661 100.5 92.400 0.003 13.46 26.02019/02/10 14:28:00:000 218.661 100.6 92.521 0.003 13.46 26.42019/02/10 14:29:00:000 218.661 100.6 92.439 0.003 13.46 26.42019/02/10 14:30:00:000 219.167 100.7 92.658 0.003 13.46 26.42019/02/10 14:31:00:000 219.722 100.6 92.847 0.003 13.46 26.42019/02/10 14:32:00:000 219.722 100.3 92.779 0.003 13.46 26.22019/02/10 14:33:00:000 219.284 100.3 92.534 0.003 13.46 26.22019/02/10 14:34:00:000 219.284 100.4 92.534 0.003 13.46 26.22019/02/10 14:35:00:000 219.284 100.3 92.635 0.003 13.46 26.22019/02/10 14:36:00:000 219.284 100.3 92.552 0.003 13.46 25.82019/02/10 14:37:00:000 219.284 100.2 92.552 0.003 13.46 25.32019/02/10 14:38:00:000 218.573 100.3 92.319 0.003 13.46 25.72019/02/10 14:39:00:000 218.952 100.4 92.513 0.003 13.46 26.02019/02/10 14:40:00:000 218.952 100.5 92.488 0.003 13.46 26.02019/02/10 14:41:00:000 218.952 100.6 92.488 0.003 13.46 26.22019/02/10 14:42:00:000 218.211 100.3 92.593 0.003 13.46 26.42019/02/10 14:43:00:000 218.885 100.3 92.355 0.003 13.46 26.22019/02/10 14:44:00:000 218.885 100.4 92.463 0.003 13.46 26.22019/02/10 14:45:00:000 218.885 100.7 92.612 0.003 13.46 26.42019/02/10 14:46:00:000 219.403 100.4 92.612 0.003 13.46 26.22019/02/10 14:47:00:000 219.403 100.3 92.612 0.003 13.46 25.82019/02/10 14:48:00:000 219.066 100.3 92.455 0.003 13.46 25.82019/02/10 14:49:00:000 218.557 100.5 92.455 0.003 13.46 25.8

Page 50: Division of Environmental Permits Floor

2019/02/10 14:50:00:000 219.158 100.4 92.722 0.003 13.47 26.02019/02/10 14:51:00:000 219.158 100.3 92.570 0.003 13.47 26.02019/02/10 14:52:00:000 219.158 100.3 92.509 0.003 13.47 26.02019/02/10 14:53:00:000 218.523 100.1 92.316 0.003 13.47 26.02019/02/10 14:54:00:000 218.523 100.5 92.316 0.003 13.47 26.02019/02/10 14:55:00:000 218.925 100.4 92.465 0.003 13.47 26.22019/02/10 14:56:00:000 218.635 100.5 92.347 0.003 13.47 26.22019/02/10 14:57:00:000 218.635 100.4 92.388 0.003 13.47 26.72019/02/10 14:58:00:000 218.635 100.4 92.388 0.003 13.47 26.42019/02/10 14:59:00:000 218.635 100.3 92.258 0.003 13.46 26.42019/02/10 15:00:00:000 217.958 100.4 92.165 0.003 13.46 26.42019/02/10 15:01:00:000 218.554 100.6 92.342 0.003 13.46 26.72019/02/10 15:02:00:000 218.554 100.5 92.359 0.003 13.46 26.72019/02/10 15:03:00:000 218.554 100.3 92.359 0.003 13.47 26.92019/02/10 15:04:00:000 218.554 100.4 92.359 0.003 13.47 26.72019/02/10 15:05:00:000 218.246 100.5 92.298 0.003 13.47 26.92019/02/10 15:06:00:000 218.246 100.7 92.448 0.003 13.47 26.92019/02/10 15:07:00:000 218.687 100.7 92.448 0.003 13.47 26.92019/02/10 15:08:00:000 218.687 100.6 92.483 0.003 13.47 26.92019/02/10 15:09:00:000 218.687 100.5 92.305 0.003 13.47 26.72019/02/10 15:10:00:000 218.687 100.6 92.422 0.003 13.47 26.72019/02/10 15:11:00:000 218.687 100.5 92.422 0.003 13.47 26.72019/02/10 15:12:00:000 218.287 100.6 92.501 0.003 13.47 26.72019/02/10 15:13:00:000 218.925 100.7 92.501 0.003 13.47 26.72019/02/10 15:14:00:000 218.925 100.6 92.514 0.003 13.47 26.72019/02/10 15:15:00:000 219.398 100.4 92.599 0.003 13.47 26.72019/02/10 15:16:00:000 219.029 100.4 92.412 0.003 13.47 26.72019/02/10 15:17:00:000 218.702 100.3 92.412 0.003 13.47 26.92019/02/10 15:18:00:000 218.702 100.4 92.412 0.002 13.47 26.92019/02/10 15:19:00:000 218.702 100.3 92.412 0.002 13.47 26.92019/02/10 15:20:00:000 218.460 100.3 92.204 0.002 13.47 26.92019/02/10 15:21:00:000 218.460 100.4 92.422 0.002 13.47 27.22019/02/10 15:22:00:000 217.973 100.3 92.289 0.002 13.47 27.72019/02/10 15:23:00:000 217.973 100.4 92.289 0.002 13.47 27.72019/02/10 15:24:00:000 218.353 100.6 92.355 0.002 13.47 27.72019/02/10 15:25:00:000 218.353 100.5 92.355 0.002 13.47 27.72019/02/10 15:26:00:000 218.353 100.5 92.423 0.002 13.48 27.42019/02/10 15:27:00:000 218.353 100.4 92.346 0.002 13.48 27.42019/02/10 15:28:00:000 217.699 100.5 92.150 0.002 13.48 27.72019/02/10 15:29:00:000 218.031 100.5 92.344 0.002 13.48 27.72019/02/10 15:30:00:000 218.642 100.7 92.344 0.002 13.48 27.92019/02/10 15:31:00:000 218.642 100.4 92.438 0.002 13.48 27.92019/02/10 15:32:00:000 218.097 100.3 92.297 0.002 13.48 27.72019/02/10 15:33:00:000 218.097 100.2 92.131 0.002 13.48 27.72019/02/10 15:34:00:000 217.770 100.5 92.331 0.002 13.48 27.72019/02/10 15:35:00:000 218.036 100.5 92.280 0.002 13.48 27.72019/02/10 15:36:00:000 218.036 100.5 92.280 0.002 13.48 27.72019/02/10 15:37:00:000 218.036 100.6 92.176 0.002 13.48 27.92019/02/10 15:38:00:000 218.036 100.7 92.333 0.002 13.48 27.92019/02/10 15:39:00:000 218.644 100.5 92.443 0.002 13.48 28.12019/02/10 15:40:00:000 218.140 100.4 92.282 0.002 13.48 28.12019/02/10 15:41:00:000 218.140 100.6 92.126 0.002 13.48 28.12019/02/10 15:42:00:000 218.140 100.5 92.231 0.002 13.48 28.12019/02/10 15:43:00:000 218.054 100.6 92.231 0.002 13.48 28.12019/02/10 15:44:00:000 218.054 100.6 92.330 0.002 13.48 28.12019/02/10 15:45:00:000 218.170 100.6 92.330 0.002 13.48 28.12019/02/10 15:46:00:000 218.170 100.6 92.222 0.002 13.48 28.42019/02/10 15:47:00:000 218.353 100.5 92.379 0.002 13.48 28.42019/02/10 15:48:00:000 218.548 100.6 92.379 0.002 13.48 28.42019/02/10 15:49:00:000 218.548 100.4 92.379 0.002 13.48 28.62019/02/10 15:50:00:000 218.548 100.4 92.379 0.002 13.48 28.62019/02/10 15:51:00:000 218.548 100.2 92.379 0.002 13.48 28.62019/02/10 15:52:00:000 218.038 100.2 92.223 0.002 13.48 28.62019/02/10 15:53:00:000 218.038 100.4 92.325 0.002 13.48 28.62019/02/10 15:54:00:000 218.038 100.4 92.325 0.002 13.48 28.62019/02/10 15:55:00:000 218.266 100.3 92.251 0.002 13.48 28.62019/02/10 15:56:00:000 218.266 100.3 92.251 0.002 13.48 28.62019/02/10 15:57:00:000 217.851 100.3 92.251 0.002 13.48 28.62019/02/10 15:58:00:000 217.851 100.3 92.251 0.002 13.48 28.62019/02/10 15:59:00:000 218.251 100.4 92.190 0.002 13.48 28.62019/02/10 16:00:00:000 218.251 100.3 92.264 0.002 13.48 28.62019/02/10 16:01:00:000 217.934 100.3 92.264 0.002 13.48 28.62019/02/10 16:02:00:000 217.934 100.4 92.236 0.002 13.48 28.62019/02/10 16:03:00:000 217.934 99.9 92.037 0.002 13.49 28.62019/02/10 16:04:00:000 216.896 99.5 91.441 0.002 13.49 28.62019/02/10 16:05:00:000 216.688 100.1 91.643 0.002 13.51 28.82019/02/10 16:06:00:000 217.620 100.5 92.171 0.002 13.51 29.0

Page 51: Division of Environmental Permits Floor

2019/02/10 16:07:00:000 218.286 100.5 92.440 0.002 13.51 28.52019/02/10 16:08:00:000 218.286 100.3 92.212 0.002 13.47 28.52019/02/10 16:09:00:000 218.286 100.4 92.212 0.003 13.47 28.52019/02/10 16:10:00:000 218.286 100.3 92.302 0.003 13.47 28.52019/02/10 16:11:00:000 217.874 100.2 92.159 0.003 13.49 28.32019/02/10 16:12:00:000 217.874 100.3 92.159 0.003 13.49 28.32019/02/10 16:13:00:000 217.874 100.3 92.159 0.003 13.49 28.62019/02/10 16:14:00:000 217.874 100.1 92.159 0.003 13.49 28.62019/02/10 16:15:00:000 217.874 100.2 92.159 0.003 13.49 28.32019/02/10 16:16:00:000 217.874 100.3 92.203 0.003 13.49 28.32019/02/10 16:17:00:000 217.874 100.1 92.035 0.003 13.48 28.32019/02/10 16:18:00:000 217.874 100.3 92.035 0.003 13.48 28.32019/02/10 16:19:00:000 217.874 100.4 92.343 0.003 13.48 28.52019/02/10 16:20:00:000 218.182 100.3 92.279 0.003 13.48 28.12019/02/10 16:21:00:000 218.182 100.3 92.279 0.003 13.48 28.12019/02/10 16:22:00:000 218.182 100.2 92.204 0.003 13.49 28.32019/02/10 16:23:00:000 217.924 100.3 92.204 0.003 13.49 28.32019/02/10 16:24:00:000 217.924 100.1 92.204 0.003 13.49 28.32019/02/10 16:25:00:000 218.180 100.2 92.125 0.003 13.49 28.32019/02/10 16:26:00:000 218.180 100.2 92.254 0.003 13.49 28.32019/02/10 16:27:00:000 218.180 100.2 92.178 0.003 13.49 28.12019/02/10 16:28:00:000 218.180 100.2 92.247 0.003 13.48 28.12019/02/10 16:29:00:000 217.921 100.2 92.228 0.003 13.48 27.92019/02/10 16:30:00:000 218.434 100.2 92.228 0.003 13.48 27.92019/02/10 16:31:00:000 218.434 100.3 92.275 0.003 13.48 27.42019/02/10 16:32:00:000 218.434 100.3 92.408 0.003 13.48 27.42019/02/10 16:33:00:000 218.434 100.3 92.311 0.003 13.48 27.42019/02/10 16:34:00:000 218.434 100.1 92.344 0.003 13.48 27.42019/02/10 16:35:00:000 218.165 100.1 92.251 0.003 13.48 27.42019/02/10 16:36:00:000 218.165 100.2 92.251 0.003 13.48 27.2

AVERAGE: 219.21 100.36 92.54 0.00 13.47 25.72

Page 52: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-11 Base Load PM Data

Page 53: Division of Environmental Permits Floor

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

09:22 08:28 12:26 hh:mm

13:33 12:35 16:36 hh:mm

02/09/19 02/10/19 02/10/19 mm/dd/yy

Base Base Base % or w/DB --

1.012 0.984 1.012

0.7890 0.7240 0.7890

0.144 0.144 0.144 in

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

831.230 160.560 919.560 ft³

918.920 239.990 1010.230 ft³

87.690 79.430 90.670 85.930 ft³

243.00 224.75 243.50 237.08 min

45.58 53.58 56.00 51.72 °F

212.17 210.67 207.58 210.14 °F

29.28 29.39 29.29 29.32 in Hg

-1.30 -1.30 -1.30 -1.30 in H₂O

29.18 29.29 29.19 29.22 in Hg

0.45 0.45 0.45 0.45 in H₂O

29.41 29.52 29.42 29.45 in Hg

1.21 1.21 1.21 1.21 √(in H₂O)

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

146.60 131.20 148.40 142.07 g

11.80 16.40 10.82 13.01 g

158.69 147.87 159.51 155.35 ml

7.47 6.96 7.51 7.31 scf

90.8 79.0 92.0 87.3 dscf

2.6 2.2 2.6 2.5 dscm

7.60 8.09 7.54 7.75 %

100.00 99.43 93.77 97.73 %

7.60 8.09 7.54 7.75 %

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

4.4 4.4 4.4 4.4 %

13.5 13.5 13.5 13.5 %

0.0 0.0 0.0 0.0 ppm

82.1 82.1 82.1 82.1 %

29.24 29.24 29.24 29.24 lb/lb-mole

28.39 28.33 28.40 28.37 lb/lb-mole

1.682 1.682 1.682 1.682

8632.05 8632.49 8632.49 8632.34 dscf/MMBtu

165.1 165.1 165.1 165.1 %

Calculated Fuel Factor

Fuel F-Factor

Percent Excess Air

Oxygen Content

Carbon Monoxide Content

Nitrogen Content

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Calculated Stack Moisture

Saturated Stack Moisture

Reported Stack Moisture Content

Carbon Dioxide Content

Gas Analysis Data

Impinger Water Weight Gain

Silica Gel Weight Gain

Total Water Volume Collected

Standard Water Vapor Volume

Standard Meter Volume

Standard Metric Meter Volume

Absolute Stack Pressure

Average Orifice Pressure Drop

Absolute Meter Pressure

Avg Square Root Pitot Pressure

Moisture Content Data

Total Sampling Time

Average Meter Temperature

Average Stack Temperature

Barometric Pressure

Stack Static Pressure

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Initial Meter Volume

Final Meter Volume

Total Meter Volume

Stack Test Data

Run Start Time

Run Stop Time

Test Date

Meter Calibration Factor

Pitot Tube Coefficient

Project # sie-19-middletown.ny-comp#2

Historical Data

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

Average Nozzle Diameter

Load

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Results

Page 54: Division of Environmental Permits Floor

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

73.26 67.31 73.14 71.24 ft/sec

283.53 283.53 283.53 283.53 ft²

1,246,339 1,145,109 1,244,308 1,211,919 acfm

57,297 52,960 57,616 55,958 wkscfh

52,942,456 48,673,298 53,270,352 51,628,702 dscfh

106.0 108.6 106.6 107.1 %

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

4.15 4.74 3.53 4.14 mg --

4.57E-05 6.00E-05 3.84E-05 4.80E-05 g/dscf --

7.05E-04 9.25E-04 5.92E-04 7.41E-04 gr/dscf --

2.42 2.92 2.05 2.46 kg/hr --

5.33 6.43 4.51 5.42 lb/hr --

23.34 28.18 19.75 23.76 tpy --

0.0025 0.0032 0.0021 0.0026 lb/MMBtu 0.0073

1.07 1.36 1.26 1.23 mg --

1.17E-05 1.73E-05 1.37E-05 1.42E-05 g/dscf --

1.81E-04 2.66E-04 2.12E-04 2.20E-04 gr/dscf --

0.62 0.84 0.73 0.73 kg/hr --

1.37 1.85 1.61 1.61 lb/hr --

6.01 8.11 7.06 7.06 tpy --

0.0006 0.0009 0.0007 0.0008 lb/MMBtu --

1.88 2.17 1.57 1.87 mg --

2.07E-05 2.75E-05 1.71E-05 2.18E-05 g/dscf --

3.19E-04 4.25E-04 2.63E-04 3.36E-04 gr/dscf --

1.10 1.34 0.91 1.11 kg/hr --

2.42 2.95 2.00 2.46 lb/hr --

10.58 12.94 8.77 10.76 tpy --

0.0011 0.0015 0.0009 0.0012 lb/MMBtu --

1.20 1.20 0.70 1.03 mg --

1.32E-05 1.52E-05 7.61E-06 1.20E-05 g/dscf --

2.04E-04 2.34E-04 1.17E-04 1.85E-04 gr/dscf --

0.70 0.74 0.41 0.61 kg/hr --

1.54 1.63 0.89 1.36 lb/hr --

6.76 7.14 3.91 5.94 tpy --

0.0007 0.0008 0.0004 0.0006 lb/MMBtu --

11-PM-Base-1 11-PM-Base-2 11-PM-Base-3 Average Units Limits

0.53 0.50 0.53 0.52 ft³/min

208.16 207.34 207.13 207.54 µP

1.09 1.08 1.09 1.08

2.33 2.49 2.29 2.37

1.09 1.08 1.09 1.08

2.33 2.49 2.29 2.37

2700.22 2559.42 2743.40 2,667.68

1.00 1.00 1.00 1.00

0 0 0 0 points

Condensable PM₂.₅ Emission Rate

Cunningham Correction Factor

Recalculated D50-1 for CIV

Z

Recalculated Cunninham

Lower Limit Cut Diameter, CI (NRE<3162), D50LL

Reynolds Number

RM 201A Quality Control

No. Sampling Pts. Outside Dp

Cyclone Flow Rate

Stack Viscosity

Emission Rate Data

Stack Cross-Sectional Area

Actual Stack Flow Rate

Wet Standard Stack Flow Rate

Dry Standard Stack Flow Rate

Percent of Isokinetic Rate

Condensable PM₂.₅ Concentration

Filterable PM₂.₅ Mass

Filterable PM₂.₅ Concentration

Condensable PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Concentration

Filterable PM₁₀ Mass

Filterable PM₁₀ Concentration

Total PM₁₀/PM₂.₅ Emission Rate

Filterable PM₁₀ Emission Rate

Filterable PM₂.₅ Emission Rate

Average Stack Gas Velocity

Volumetric Flow Rate Data

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Results

Page 55: Division of Environmental Permits Floor

(mm/dd/yy)

°F

in Hg

indust. spec. scf

chk Subpart minutes

in

1 2 3

(mm/dd/yy) 02/09/19 02/10/19 02/10/19

Base Base Base % or w/DB

8632.05 8632.49 8632.49 dscf/MMBtu

from ACS samp-cp-0034 samp-cp-0030 samp-cp-0034

(Y) 1.012 0.984 1.012

(H@) 1.830 1.812 1.830 in H₂O

No No No

from ACS P-981/10 4187/10 P-981/10

(Cp) 0.7890 0.7240 0.7890

from ACS 3 3 3 must match cyc nozz tab (e.g. 3, 4, etc.)

(Dn) 0.144 0.144 0.144 in

from ACS samp-bh-0034 samp-hp-0143 samp-bh-0034

120.0 120.0 120.0 in

from list glass glass glass

from ACS samp-bh-0034 samp-bh-0034 samp-bh-0029

from ACS samp-cc-0001 samp-cc-0001 samp-cc-0001

Created with Isocalc-AHI v20190131

1600 W Tacoma Street

Broken Arrow, Oklahoma 74012

Cole McBride

(918) 307-8865

Unit Number

Operator DA

Standard Temperature

Standard Pressure

68

29.92

Pitot Identification

Number of Ports Used

Port Inside Diameter

Stack Shape

Base Run Number

Number of Ports Available

Test Equipment Information

Run

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE

Date for Preliminary Run 02/09/19

Company Name Air Hygiene International, Inc. (Tulsa, Oklahoma)

Test Information

Project # sie-19-middletown.ny-comp#2

Source Information

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

Fuel Type Gas, Natural

Required Sample Vol.

Run Duration

Testing Company Information

Pitot Tube Coefficient

Nozzle Number

Nozzle Diameter

Probe Number

Probe Length

(918) 307-9131

Address

City, State Zip

Project Manager

Phone Number

Fax Number

Sample Case / Oven Number

Impinger Case Number

(SS, Glass …. ) Liner Material

50

240

CTG-11

11-PM-Base

4

Test Date

Fuel F-Factor

Load

4

6.00

Circular

Meter Box Number

Meter Calibration Factor

Orifice Meter Coefficient

Non-Console Manometer Used

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Title Page

Page 56: Division of Environmental Permits Floor

(Lfw) 235.25 in

(Lnw) 7.25 in

(D) 228.00 in

(As) 283.53 ft²

(A) 1200.00 in

(AD) 5.26 diameters

(B) 1095.00 in

(BD) 4.80 diameters

Down Up Particulate Velocity

Stream Stream Points Points

2.00-4.99 0.50-1.24 24 16

5.00-5.99 1.25-1.49 20 16

6.00-6.99 1.50-1.74 16 12

7.00-7.99 1.75-1.99 12 12

>= 8.00 >=2.00 8 or 122 8 or 122

12 12

24 16 4 Ports by 3 Across

24 16 12 Pts Used 12 Required

Fraction Distance Distance

Traverse of from Including

Point Stack Inside Reference

Number Diameter Wall Length

in in

1 0.044 10 17 2/8

2 0.146 33 2/8 40 4/8

3 0.296 67 4/8 74 6/8

4

5

6

7

8

9

Traverse Point Locations

1 Check Minimum Number of Points for the Upstream

and Downstream conditions, then use the largest.

2 8 for Circular Stacks 12 to 24 inches

12 for Circular Stacks over 24 inches

Upstream Spec Number of Traverse Points Used

Downstream Spec

Traverse Pts Required

Distance Downstream

Diameters Downstream

Number of Traverse Points Required

Diameters to Minimum Number of1

Flow Disturbance Traverse Points

Distance to Near Wall of Stack

Diameter of Stack

Area of Stack

Distance from Port to Disturbances

Distance Upstream

Diameters Upstream

Stack Size Large (>24 inch diameter) Port ID (inches) 6.00

Circular Stack or Duct Diameter

Distance to Far Wall of Stack

Operator DA Ports Available 4

Stack Type

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 1 - SAMPLE AND VELOCITY TRAVERSES FOR CIRCULAR SOURCES

Plant Name CPV Valley Energy Center Date 02/09/19

Sampling Location CTG-11 Stack

Project #

Circular

Lnw

Lfw

D

B

A

Method 1 Trav

12 Point PM Trav (M201a ONLY)

Velocity

sie-19-middletown.ny-comp#1-CTG11-PM_BASE M1 - Circular

Page 57: Division of Environmental Permits Floor

x PreTest x PostTest 0.8177 A3541

(As) 283.53 ft²

(D) 228.00 in 08:14 Start 08:28 End

Traverse Velocity Null Zero Deg Stack Local

Point Head Angle Pressure Temp Velocity

(p) (Na) (0oa) (ts) (vs(l))

(Pb) 29.28 in Hg in H₂O deg in H₂O °F ft/sec

(Pstatic) -1.30 in H₂O A-1 1.50 0 0.00 205 76.82

(Ps) 29.18 in Hg A-2 1.60 0 0.00 208 79.52

A-3 1.50 0 0.00 208 76.99

B-1 1.20 0 0.00 208 68.86

B-2 1.20 0 0.00 208 68.86

(%CO2) 4.10 %vd B-3 1.20 0 0.00 206 68.76

(%O2) 13.60 %vd C-1 1.50 0 0.00 207 76.93

(ppmCO) 0.00 ppmvd C-2 1.50 0 0.00 210 77.11

(%N2) 82.30 %vd C-3 1.20 0 0.00 207 68.81

(Bws) 8.00 % D-1 1.90 0 0.00 212 86.91

(Md) 29.20 lb/lb-mole D-2 1.60 5 0.25 210 79.64

(Mw) 28.30 lb/lb-mole D-3 1.20 0 0.00 207 68.81

(vs) 72.20 ft/sec

(Qsd) 52,275,372 dscf/hr

(Qsd) 871,256 dscf/min

(Qaw) 1,228,319 acf/min

(Qsw) 56,821,056 ascf/hr

1.43 0 208

1.19

1.4

Thermocouple ID

Standard deviation of null angles =

Pressures

Barometric Pressure

Static Pressure

Carbon Dioxide Concentration

= Square roots of p

Avg Stack Dry Std Flow Rate

Avg Stack Wet Flow Rate

Avg Stack Wet Std Flow Rate

Stack Cross Section Schematic

40 CFR 60, Method 2G, Section 8.11.1 (but applies to all Method 2 type static pressure measurements): If a Type S probe is used for this measurement, position the probe at or between any traverse point(s) and rotate the probe until a null differential pressure reading is obtained. Disconnect the tubing from one of the pressure ports; read and record the ∆P. For pressure devices with one-directional scales, if a deflection in the positive direction is noted with the negative side disconnected, then the static pressure is positive. Likewise, if a deflection in the positive direction is noted with the positive side disconnected, then the static pressure is negative.

Average

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Results

Avg Stack Gas Velocity

Avg Stack Dry Std Flow Rate

Oxygen Concentration

Carbon Monoxide Concentration

Nitrogen Concentration

Stack Moisture Content

DA Ports Available 4

Stack Dimensions Velocity Traverse Data

Diameter of Stack

Run Number 11-PM-Base-V1

samp-bh-0034

Pitot Leak Check Pitot Coefficient

Absolute Stack Pressure

Stack Gas Composition

Estimated CompositionComposition Data:

Area of Stack

Run Time

METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE

Plant Name CPV Valley Energy Center Preliminary Run Date 02/09/19

Project # sie-19-middletown.ny-comp#2

Pitot Identification

Sampling Location CTG-11 Stack Stack Type Circular

Operator

sie-19-middletown.ny-comp#1-CTG11-PM_BASE M2 - Run (1)

Page 58: Division of Environmental Permits Floor

1.600 1.836

Date 02/09/19 09:22 13:33

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.4 13.5 0.0 82.1 165.1 YES

Date 02/10/19 08:28 12:35

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.4 13.5 0.0 82.1 165.1 YES

Date 02/10/19 12:26 16:36

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.4 13.5 0.0 82.1 165.1 YES

hh:mm lb/lb-mole

04:10 29.24 1.682

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Gas Analysis Data

Run Number 11-PM-Base-3 Run Start Time

hh:mm lb/lb-mole

04:07 29.24 1.682

Run Stop Time

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

Run Number 11-PM-Base-2 Run Start Time Run Stop Time

Gas Analysis Data

Dry Molecular Weight

(Md)

N₂ Conc.

CO₂ Conc.

O₂ Conc.

COConc.

Excess Air

Fuel Factor in

Range

hh:mm

04:11

CalculatedFuel Factor

(Fo)avg

1.682

SampleAnalysis

Time

lb/lb-mole

29.24

11-PM-Base-1 Run Start Time Run Stop Time

Gas Analysis Data

Fuel Type Min. Fuel Factor Max. Fuel FactorGas, Natural

METHOD 3a - DETERMINATION OF DRY MOLECULAR WEIGHT BY ANALYZER

02/09/19

Sampling Location CTG-11 Stack

Project #

Operator

sie-19-middletown.ny-comp#2 # of Ports Used

DA

1 (gas probe)

Plant Name CPV Valley Energy Center Preliminary Run Date

Run Number

sie-19-middletown.ny-comp#1-CTG11-PM_BASE M3a - Mol Wt

Page 59: Division of Environmental Permits Floor

Standard Result Difference Pass/Fail

(g) (g) (g) (± 0.5 g)

500 499.6 -0.4 Pass

500 499.6 -0.4 Pass

500 499.7 -0.3 Pass

Date 02/09/19 Start Time 09:22 Stop Time 13:33

(Y)

(Vm) 87.690 dcf (Pb) 29.28 in Hg

(ts)avg 212 °F (Pstatic) -1.30 in H₂O

(tm)avg 46 °F (H)avg 0.45 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 489.90 637.30 704.80 950.00

Initial Value (Vi),(Wi) 372.20 610.70 702.50 938.20

Net Value (Vn),(Wn) 117.7 26.6 2.3 11.8

(Wt) 158.40 g (Vwsg(std)) 7.469 scf

(Vm(std)) 90.797 dscf (Bws(svp)) 100.00 %

(Bws(calc)) 7.60 % (Bws) 7.60 %

Date 02/10/19 Start Time 08:28 Stop Time 12:35

(Y)

(Vm) 79.430 dcf (Pb) 29.39 in Hg

(ts)avg 211 °F (Pstatic) -1.30 in H₂O

(tm)avg 54 °F (H)avg 0.45 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 487.80 627.30 705.30 898.60

Initial Value (Vi),(Wi) 372.70 611.80 704.70 882.20

Net Value (Vn),(Wn) 115.1 15.5 0.6 16.4

(Wt) 147.60 g (Vwsg(std)) 6.959 scf

(Vm(std)) 79.019 dscf (Bws(svp)) 99.43 %

(Bws(calc)) 8.09 % (Bws) 8.09 %

Date 02/10/19 Start Time 12:26 Stop Time 16:36

(Y)

(Vm) 90.670 dcf (Pb) 29.29 in Hg

(ts)avg 208 °F (Pstatic) -1.30 in H₂O

(tm)avg 56 °F (H)avg 0.45 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 499.20 620.30 672.60 850.12

Initial Value (Vi),(Wi) 362.90 615.90 664.90 839.30

Net Value (Vn),(Wn) 136.3 4.4 7.7 10.8

(Wt) 159.22 g (Vwsg(std)) 7.507 scf

(Vm(std)) 92.019 dscf (Bws(svp)) 93.77 %

(Bws(calc)) 7.54 % (Bws) 7.54 %

Preliminary Date 02/09/19

Test Day 1

Test Day 2

02/09/19

02/10/19

Date

Scale Number SAMP-SC-0016

Scale Daily Calibration

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0034 Meter Cal Factor 1.012

Total Meter Volume Barometric Pressure

Calc Moisture Content Final Moisture Content

Moisture Content Data

Run Number 11-PM-Base-3

Results

Total Weight Water Vol Weighed

Std Meter Volume Sat. Moisture Content

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0030 Meter Cal Factor 0.984

Total Meter Volume Barometric Pressure

Moisture Content Data

Run Number 11-PM-Base-2

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Total Meter Volume Barometric Pressure

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Moisture Content Data

Run Number 11-PM-Base-1

Meter Box Number Meter Cal Factorsamp-cp-0034 1.012

Sampling Location CTG-11 Stack

Project #

DAOperator

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 4 - DETERMINATION OF MOISTURE CONTENT IN STACK GASES

Plant Name CPV Valley Energy Center Preliminary Run Date 02/09/19

sie-19-middletown.ny-comp#1-CTG11-PM_BASE M4 - Moisture

Page 60: Division of Environmental Permits Floor

(Cp) 0.7890 P-981/10

(ts) 212.2 °F

(tm) 45.6

(H@) 1.830 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.21 in H₂O

PASS Post 0.000 ft³/min@ 15.0 in Hg (Y) 1.012 (Bws) 7.60 %

Pitot Pre (+) 6.3 in H₂O for 30.0 sec (Md) 29.24 lb/lb-mole

Pre (-) 4.7 in H₂O for 30.0 sec (Dna) 0.1440 in (Qm) 0.75 acfm

Post (+) 5.3 in H₂O for 30.0 sec (Dni) 0.2146 in (K) 0.27

Post (-) 6.8 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.28 in Hg

Pre 0.144 0.144 0.144 PASS (Pstatic) -1.30 in H₂O

Post 0.144 0.144 0.144 PASS (Ps) 29.18 in Hg

(Pm) 29.41 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 09:22 End 13:33 Pre 372.2 610.7 702.5 938.2 ml

Post 489.9 637.3 704.8 950.0 ml

samp-cp-0034 samp-cp-0034 samp-cp-0034 samp-bh-0034 samp-bh-0034 samp-bh-0034 samp-cc-0001 1018 3135 samp-cp-0034

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 831.230 1.50 0.450 0.45 215 247 256 65 71 72 33 33 2.0 1.22 74.57 8.081 110.6 95.787

A-2 20.5 00:20:30 838.840 1.60 0.450 0.45 214 252 255 33 36 70 37 37 2.0 1.26 76.95 15.875 105.2 92.400

A-3 41.8 00:41:45 846.240 1.50 0.450 0.45 213 249 256 32 36 71 43 43 2.0 1.22 74.45 23.363 104.2 91.202

B-1 62.3 01:02:15 853.435 1.30 0.450 0.45 211 248 258 34 40 70 46 46 2.0 1.14 69.21 30.031 105.1 90.373

B-2 80.8 01:20:45 859.880 1.30 0.450 0.45 214 249 243 37 47 70 47 47 2.0 1.14 69.36 36.588 105.4 89.581

B-3 99.3 01:39:15 866.230 1.20 0.450 0.45 214 249 254 37 36 70 47 47 2.0 1.10 66.64 42.979 106.5 89.265

C-1 117.0 01:57:00 872.420 1.50 0.450 0.45 211 247 256 36 36 70 48 48 2.0 1.22 74.34 50.533 106.0 89.306

C-2 137.5 02:17:30 879.750 1.50 0.450 0.45 213 249 256 35 39 69 48 48 2.0 1.22 74.45 58.128 105.7 89.399

C-3 158.0 02:38:00 887.120 1.30 0.450 0.45 211 248 253 36 40 68 49 49 2.0 1.14 69.21 65.060 106.0 89.193

D-1 177.3 02:57:15 893.860 1.80 0.450 0.45 211 251 252 36 41 69 49 49 2.0 1.34 81.44 75.036 106.4 90.941

D-2 200.5 03:20:30 903.560 1.50 0.450 0.45 211 250 254 41 48 70 50 50 2.0 1.22 74.34 82.889 106.2 90.832

D-3 221.8 03:41:45 911.210 1.50 0.450 0.45 208 251 252 41 51 71 50 50 2.0 1.22 74.18 90.803 106.0 90.803

Last Pt 243.0 04:03:00 918.920

Final Val 243.0 04:03:00 918.920 Max Vac 2.0 90.803 106.0

1.46 0.45 212 249 254 39 43 70 46 46 1.21 73.26

Notes:

Identification Nos. samp-cp-0034

Nozzle Measurements

Meter Box Number

Meter Cal Factor

Average Meter Temp

Nozzle Number

Project # Run Number Average Stack Temp

Sampling Location Operator Pitot Coefficient / ID

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name Date Ideal Nozzle Diameter and IsoKinetic Factor SetupFilter #

18082927

0818-188

CPV Valley Energy Center

CTG-11 Stack

sie-19-middletown.ny-comp#2

02/09/19

DA

11-PM-Base-1

Stack Dry Molecular Weight

Estimated Orifice Flow Rate

Orifice Meter Coefficient

P to H Isokinetic Factor

Pressures

samp-cc-0001

samp-bh-0034

glass

PASS

Leak Checks

Square Root P

Stack Moisture Content

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Equipment

samp-cp-0034

3

120

samp-bh-0034

Absolute Meter Pressure

Run Time

Barometric Pressure

Stack Static Pressure

Barometer ID

SAMP-WE-0027

Scale ID

SAMP-SC-0016

Absolute Stack Pressure

Wash Volumes

Final Values

Average Values

46

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Isocalc - Run (1)

Page 61: Division of Environmental Permits Floor

(Cp) 0.7240 4187/10

(ts) 210.7 °F

(tm) 53.6

(H@) 1.812 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.21 in H₂O

PASS Post 0.000 ft³/min@ 15.0 in Hg (Y) 0.984 (Bws) 8.09 %

Pitot Pre (+) 6.3 in H₂O for 30.0 sec (Md) 29.24 lb/lb-mole

Pre (-) 5.2 in H₂O for 30.0 sec (Dna) 0.1440 in (Qm) 0.37 acfm

Post (+) 6.9 in H₂O for 30.0 sec (Dni) 0.1567 in (K) 0.23

Post (-) 7.2 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.39 in Hg

Pre 0.144 0.144 0.144 PASS (Pstatic) -1.30 in H₂O

Post 0.144 0.144 0.144 PASS (Ps) 29.29 in Hg

(Pm) 29.52 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 08:28 End 12:35 Pre 372.7 611.8 704.7 882.2 ml

Post 487.8 627.3 705.3 898.6 ml

samp-cp-0030 samp-cp-0030 samp-cp-0030 samp-hp-0143 samp-hp-0143 samp-bh-0034 samp-cc-0001 1035 3105 samp-cp-0030

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 160.560 1.50 0.450 0.45 215 254 250 58 65 68 47 47 2.0 1.22 68.36 6.611 108.0 79.241

A-2 18.8 00:18:45 167.120 1.60 0.450 0.45 217 254 247 51 50 68 47 47 2.0 1.26 70.71 13.927 109.9 81.832

A-3 38.3 00:38:15 174.380 1.50 0.450 0.45 215 255 249 40 47 72 48 48 2.0 1.22 68.36 20.640 109.8 81.385

B-1 57.0 00:57:00 181.055 1.30 0.450 0.45 210 246 238 39 46 75 50 50 2.0 1.14 63.40 26.806 111.9 81.416

B-2 74.0 01:14:00 187.210 1.30 0.450 0.45 213 256 249 39 39 76 52 52 2.0 1.14 63.55 32.145 110.5 79.392

B-3 91.0 01:31:00 192.560 1.20 0.450 0.45 206 242 250 33 41 78 54 54 2.0 1.10 60.73 37.006 109.3 77.549

C-1 107.3 01:47:15 197.450 1.50 0.450 0.45 210 258 256 31 34 81 55 55 2.0 1.22 68.11 43.732 109.4 78.007

C-2 126.0 02:06:00 204.230 1.50 0.450 0.45 209 254 250 32 34 79 56 56 2.0 1.22 68.06 50.287 109.0 78.080

C-3 144.8 02:24:45 210.850 1.50 0.450 0.45 203 254 249 34 35 79 57 57 2.0 1.22 67.75 57.175 109.3 78.594

D-1 163.5 02:43:30 217.820 1.70 0.450 0.45 213 225 225 35 36 85 59 59 2.0 1.30 72.67 65.454 109.7 79.626

D-2 184.8 03:04:45 226.230 1.50 0.450 0.45 210 254 248 45 51 84 59 59 2.0 1.22 68.11 72.670 109.7 79.769

D-3 204.8 03:24:45 233.560 1.50 0.450 0.45 207 256 246 45 51 85 59 59 2.0 1.22 67.95 79.000 108.6 79.000

Last Pt 224.8 03:44:45 239.990

Final Val 224.8 03:44:45 239.990 Max Vac 2.0 79.000 108.6

1.47 0.45 211 251 246 40 44 78 54 54 1.21 67.31

Notes:

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0030

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

Average Values

54

Final Values

Run Time

Wash Volumes

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0034 Stack Static Pressure

SAMP-SC-0016

samp-cc-0001 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Location CTG-11 Stack Operator DA 18010428

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/10/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Project # sie-19-middletown.ny-comp#2 Run Number 11-PM-Base-2 0818-188 Average Stack Temp

samp-cp-0030 Square Root PMeter Box Number

Sampling Equipment

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-hp-0143

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Isocalc - Run (2)

Page 62: Division of Environmental Permits Floor

(Cp) 0.7890 P-981/10

(ts) 207.6 °F

(tm) 56.0

(H@) 1.830 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.21 in H₂O

PASS Post 0.000 ft³/min@ 15.0 in Hg (Y) 1.012 (Bws) 7.54 %

Pitot Pre (+) 4.9 in H₂O for 30.0 sec (Md) 29.24 lb/lb-mole

Pre (-) 6.2 in H₂O for 30.0 sec (Dna) 0.1440 in (Qm) 0.35 acfm

Post (+) 7.1 in H₂O for 30.0 sec (Dni) 0.1451 in (K) 0.28

Post (-) 8.2 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.29 in Hg

Pre 0.144 0.144 0.144 PASS (Pstatic) -1.30 in H₂O

Post 0.144 0.144 0.144 PASS (Ps) 29.19 in Hg

(Pm) 29.42 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 12:26 End 16:36 Pre 362.9 615.9 664.9 839.3 ml

Post 499.2 620.3 672.6 850.1 ml

samp-cp-0034 samp-cp-0034 samp-cp-0034 samp-bh-0034 samp-bh-0034 samp-bh-0029 samp-cc-0001 1018 3135 samp-cp-0034

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 919.560 1.50 0.450 0.45 211 248 260 56 75 75 49 49 2.0 1.22 74.32 7.377 100.6 87.621

A-2 20.5 00:20:30 926.730 1.60 0.450 0.45 209 248 255 50 72 72 51 51 2.0 1.26 76.65 16.088 106.1 93.828

A-3 41.8 00:41:45 935.230 1.60 0.450 0.45 209 252 255 50 72 71 51 51 2.0 1.26 76.65 24.624 106.9 95.175

B-1 63.0 01:03:00 943.560 1.20 0.450 0.45 207 246 256 44 68 71 55 55 2.0 1.10 66.28 30.563 105.6 91.313

B-2 81.5 01:21:30 949.400 1.40 0.450 0.45 209 244 252 40 55 71 55 55 2.0 1.18 71.70 37.599 105.1 90.424

B-3 101.3 01:41:15 956.320 1.40 0.450 0.45 207 248 236 45 45 70 56 56 2.0 1.18 71.59 44.612 104.7 89.777

C-1 121.0 02:01:00 963.230 1.50 0.450 0.45 208 246 252 43 44 71 57 57 2.0 1.22 74.16 52.715 105.5 90.715

C-2 141.5 02:21:30 971.230 1.50 0.450 0.45 208 253 250 44 45 75 58 58 2.0 1.22 74.16 60.803 106.1 91.392

C-3 162.0 02:42:00 979.230 1.20 0.450 0.45 206 253 247 42 46 77 59 59 2.0 1.10 66.23 66.514 105.3 89.729

D-1 180.5 03:00:30 984.890 1.90 0.450 0.45 208 249 261 41 46 75 60 60 2.0 1.38 83.46 77.330 106.7 92.416

D-2 203.8 03:23:45 995.630 1.60 0.450 0.45 206 241 259 42 46 75 61 61 2.0 1.26 76.47 85.301 106.1 92.314

D-3 225.0 03:45:00 1003.560 1.20 0.450 0.45 203 235 255 41 50 74 60 60 2.0 1.10 66.08 92.018 106.6 92.018

Last Pt 243.5 04:03:30 1010.230

Final Val 243.5 04:03:30 1010.230 Max Vac 2.0 92.018 106.6

1.47 0.45 208 247 253 45 55 73 56 56 1.21 73.14

Notes:

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0034

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

Average Values

56

Final Values

Run Time

Wash Volumes

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0029 Stack Static Pressure

SAMP-SC-0016

samp-cc-0001 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Location CTG-11 Stack Operator DA 18082940

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/10/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Project # sie-19-middletown.ny-comp#2 Run Number 11-PM-Base-3 0818-188 Average Stack Temp

samp-cp-0034 Square Root PMeter Box Number

Sampling Equipment

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-bh-0034

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Isocalc - Run (3)

Page 63: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-11 Base Load

Opacity Data

Page 64: Division of Environmental Permits Floor
Page 65: Division of Environmental Permits Floor
Page 66: Division of Environmental Permits Floor
Page 67: Division of Environmental Permits Floor
Page 68: Division of Environmental Permits Floor
Page 69: Division of Environmental Permits Floor
Page 70: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-11 Base Load wDB

Unit Operating Data

Page 71: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 11 CTG-1 W/DB Run 3DCS Data - 20190209 - 0920-1800

Unit 11 GT Power Unit 11 GT PowerUnit 11 Total GT

Gas FlowUnit 11 HRSG DB Fuel Flow

Unit 11 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 11HAD00EU001 11MKA01EU902A 11MBP10CF910 11HHA10CF001 11HNE10CQ109 11MBL05CT1012019/02/09 13:48:00:000 222.422 100.5 93.636 6.734 12.98 18.32019/02/09 13:49:00:000 222.878 100.5 93.780 6.734 13.01 18.32019/02/09 13:50:00:000 222.878 100.5 93.593 6.734 12.97 18.32019/02/09 13:51:00:000 222.878 100.4 93.718 6.734 12.97 18.32019/02/09 13:52:00:000 222.878 100.3 93.718 6.749 12.99 18.12019/02/09 13:53:00:000 222.878 100.4 93.812 6.749 12.99 18.12019/02/09 13:54:00:000 222.878 100.4 93.812 6.749 13.00 17.92019/02/09 13:55:00:000 222.878 100.5 93.779 6.749 13.00 18.12019/02/09 13:56:00:000 223.384 100.4 93.759 6.749 13.00 18.12019/02/09 13:57:00:000 223.384 100.5 93.918 6.749 12.98 18.12019/02/09 13:58:00:000 222.879 100.4 93.814 6.762 12.98 18.12019/02/09 13:59:00:000 222.879 100.4 93.746 6.762 12.98 18.32019/02/09 14:00:00:000 222.879 100.4 93.603 6.762 12.98 18.32019/02/09 14:01:00:000 222.879 100.5 93.662 6.762 12.98 18.52019/02/09 14:02:00:000 222.416 100.3 93.662 6.762 12.98 18.52019/02/09 14:03:00:000 222.416 100.5 93.578 6.762 13.00 18.82019/02/09 14:04:00:000 222.416 100.3 93.578 6.778 13.00 18.82019/02/09 14:05:00:000 222.416 100.7 93.416 6.778 13.00 19.02019/02/09 14:06:00:000 222.416 100.6 93.505 6.778 13.00 18.82019/02/09 14:07:00:000 223.059 100.6 93.648 6.778 13.00 18.82019/02/09 14:08:00:000 223.059 100.6 93.648 6.778 13.00 19.02019/02/09 14:09:00:000 222.840 100.5 93.648 6.778 13.00 19.02019/02/09 14:10:00:000 222.840 100.4 93.648 6.778 13.00 18.82019/02/09 14:11:00:000 222.225 100.5 93.454 6.778 13.00 18.82019/02/09 14:12:00:000 222.562 100.6 93.569 6.778 13.00 18.82019/02/09 14:13:00:000 222.562 100.6 93.681 6.778 13.00 19.32019/02/09 14:14:00:000 222.847 100.5 93.681 6.778 13.00 19.02019/02/09 14:15:00:000 222.847 100.5 93.681 6.778 13.00 19.02019/02/09 14:16:00:000 222.847 100.5 93.681 6.778 13.00 18.52019/02/09 14:17:00:000 222.847 100.5 93.681 6.778 13.00 18.52019/02/09 14:18:00:000 222.847 100.5 93.681 6.778 13.00 18.52019/02/09 14:19:00:000 222.847 100.4 93.681 6.778 13.00 18.52019/02/09 14:20:00:000 222.847 100.4 93.681 6.778 13.00 18.32019/02/09 14:21:00:000 222.577 100.5 93.513 6.785 12.99 18.82019/02/09 14:22:00:000 222.577 100.4 93.513 6.785 12.99 18.82019/02/09 14:23:00:000 222.402 100.5 93.520 6.785 12.99 19.02019/02/09 14:24:00:000 222.402 100.6 93.563 6.785 12.99 19.02019/02/09 14:25:00:000 222.752 100.5 93.718 6.785 12.99 18.82019/02/09 14:26:00:000 222.752 100.5 93.558 6.785 13.01 18.82019/02/09 14:27:00:000 222.752 100.5 93.669 6.785 13.01 18.82019/02/09 14:28:00:000 222.752 100.4 93.669 6.785 13.00 18.82019/02/09 14:29:00:000 222.501 100.5 93.669 6.785 13.00 18.82019/02/09 14:30:00:000 222.501 100.7 93.732 6.785 13.00 19.02019/02/09 14:31:00:000 222.928 100.5 93.732 6.785 13.00 19.02019/02/09 14:32:00:000 222.928 100.5 93.732 6.785 13.00 18.82019/02/09 14:33:00:000 222.453 100.5 93.576 6.785 13.00 18.82019/02/09 14:34:00:000 222.453 100.4 93.576 6.789 12.98 19.02019/02/09 14:35:00:000 222.453 100.5 93.576 6.789 12.98 19.02019/02/09 14:36:00:000 222.453 100.5 93.576 6.789 12.99 19.32019/02/09 14:37:00:000 222.453 100.5 93.576 6.789 12.99 19.32019/02/09 14:38:00:000 222.737 100.5 93.576 6.789 12.99 19.32019/02/09 14:39:00:000 222.737 100.4 93.685 6.789 12.99 19.32019/02/09 14:40:00:000 222.737 100.5 93.685 6.789 12.99 19.02019/02/09 14:41:00:000 222.737 100.4 93.685 6.789 12.99 19.02019/02/09 14:42:00:000 222.737 100.3 93.657 6.789 12.99 18.82019/02/09 14:43:00:000 222.737 100.4 93.657 6.789 12.99 18.82019/02/09 14:44:00:000 222.737 100.4 93.657 6.789 12.99 18.82019/02/09 14:45:00:000 222.737 100.4 93.657 6.789 12.99 18.82019/02/09 14:46:00:000 222.737 100.4 93.657 6.789 12.99 18.52019/02/09 14:47:00:000 222.737 100.4 93.597 6.789 12.99 18.82019/02/09 14:48:00:000 222.241 100.4 93.397 6.789 12.99 18.82019/02/09 14:49:00:000 222.241 100.5 93.536 6.789 13.01 19.02019/02/09 14:50:00:000 222.582 100.5 93.755 6.789 13.01 19.02019/02/09 14:51:00:000 223.050 100.5 93.611 6.789 13.01 18.82019/02/09 14:52:00:000 222.455 100.3 93.442 6.789 12.99 18.82019/02/09 14:53:00:000 222.455 100.5 93.442 6.789 12.99 18.82019/02/09 14:54:00:000 222.455 100.4 93.590 6.789 12.99 19.0

Page 72: Division of Environmental Permits Floor

2019/02/09 14:55:00:000 222.455 100.4 93.590 6.789 12.99 19.02019/02/09 14:56:00:000 222.455 100.5 93.590 6.789 13.00 19.32019/02/09 14:57:00:000 222.455 100.5 93.590 6.789 13.00 19.32019/02/09 14:58:00:000 222.455 100.5 93.590 6.789 13.00 19.32019/02/09 14:59:00:000 222.455 100.4 93.590 6.789 13.00 19.32019/02/09 15:00:00:000 222.719 100.5 93.590 6.789 13.00 19.32019/02/09 15:01:00:000 222.719 100.4 93.590 6.789 13.00 19.02019/02/09 15:02:00:000 222.719 100.3 93.657 6.789 12.98 19.02019/02/09 15:03:00:000 222.719 100.5 93.657 6.789 12.98 18.52019/02/09 15:04:00:000 222.882 100.5 93.790 6.789 12.98 18.52019/02/09 15:05:00:000 222.882 100.5 93.697 6.789 12.98 18.52019/02/09 15:06:00:000 222.882 100.5 93.697 6.789 13.01 18.82019/02/09 15:07:00:000 222.281 100.0 93.358 6.789 13.01 18.82019/02/09 15:08:00:000 222.286 100.2 93.449 6.789 13.01 18.82019/02/09 15:09:00:000 222.864 100.6 93.590 6.789 13.01 18.82019/02/09 15:10:00:000 222.864 100.6 93.856 6.789 13.01 18.82019/02/09 15:11:00:000 223.055 100.6 93.677 6.789 13.01 18.82019/02/09 15:12:00:000 223.055 100.6 93.780 6.789 13.01 18.82019/02/09 15:13:00:000 223.055 100.6 93.731 6.789 12.99 18.82019/02/09 15:14:00:000 222.630 100.5 93.603 6.789 12.99 18.82019/02/09 15:15:00:000 222.236 100.6 93.517 6.789 12.99 18.82019/02/09 15:16:00:000 222.236 100.6 93.517 6.789 12.99 18.82019/02/09 15:17:00:000 222.593 100.7 93.570 6.792 12.99 19.02019/02/09 15:18:00:000 222.593 100.6 93.703 6.792 12.99 19.02019/02/09 15:19:00:000 222.937 100.6 93.657 6.792 13.01 18.82019/02/09 15:20:00:000 222.648 100.5 93.657 6.792 13.01 18.52019/02/09 15:21:00:000 222.648 100.6 93.587 6.792 12.98 18.52019/02/09 15:22:00:000 222.648 100.5 93.621 6.792 12.98 18.82019/02/09 15:23:00:000 222.648 100.6 93.621 6.792 12.98 18.82019/02/09 15:24:00:000 222.648 100.4 93.621 6.792 13.01 19.02019/02/09 15:25:00:000 222.349 100.5 93.499 6.792 13.01 19.02019/02/09 15:26:00:000 222.349 100.5 93.597 6.792 13.01 19.02019/02/09 15:27:00:000 222.652 100.5 93.597 6.792 13.00 19.32019/02/09 15:28:00:000 222.652 100.5 93.710 6.792 13.00 19.32019/02/09 15:29:00:000 222.652 100.5 93.558 6.792 13.00 19.32019/02/09 15:30:00:000 222.652 100.5 93.558 6.792 13.00 19.02019/02/09 15:31:00:000 222.387 100.5 93.656 6.792 13.00 19.02019/02/09 15:32:00:000 222.387 100.5 93.656 6.792 13.00 19.32019/02/09 15:33:00:000 222.874 100.5 93.656 6.792 13.00 19.02019/02/09 15:34:00:000 222.874 100.5 93.656 6.792 13.00 19.02019/02/09 15:35:00:000 222.420 100.5 93.534 6.792 13.00 19.02019/02/09 15:36:00:000 222.420 100.4 93.665 6.792 13.00 19.02019/02/09 15:37:00:000 222.807 100.5 93.665 6.792 13.00 19.02019/02/09 15:38:00:000 222.807 100.6 93.783 6.792 13.00 19.02019/02/09 15:39:00:000 222.807 100.6 93.691 6.792 13.00 19.02019/02/09 15:40:00:000 223.209 100.6 93.691 6.792 13.00 19.02019/02/09 15:41:00:000 223.209 100.4 93.775 6.792 13.00 19.02019/02/09 15:42:00:000 222.819 100.6 93.611 6.792 13.00 19.02019/02/09 15:43:00:000 223.241 100.6 93.922 6.792 13.00 19.02019/02/09 15:44:00:000 223.241 100.5 93.733 6.792 13.00 18.82019/02/09 15:45:00:000 223.241 100.6 93.828 6.792 13.00 18.82019/02/09 15:46:00:000 223.241 100.6 93.828 6.792 13.00 19.02019/02/09 15:47:00:000 222.838 100.6 93.746 6.792 13.00 19.32019/02/09 15:48:00:000 222.838 100.6 93.661 6.792 12.99 19.32019/02/09 15:49:00:000 222.838 100.6 93.728 6.792 12.99 19.52019/02/09 15:50:00:000 223.579 100.7 93.842 6.860 12.99 19.52019/02/09 15:51:00:000 223.214 100.7 93.713 6.860 12.99 19.52019/02/09 15:52:00:000 223.214 100.6 93.713 6.860 13.01 19.32019/02/09 15:53:00:000 222.877 100.6 93.788 6.860 13.01 19.02019/02/09 15:54:00:000 223.320 100.4 93.788 6.860 13.01 19.02019/02/09 15:55:00:000 222.756 100.6 93.788 6.860 12.99 19.02019/02/09 15:56:00:000 223.018 100.6 93.788 6.860 12.99 19.02019/02/09 15:57:00:000 223.018 100.5 93.788 6.860 12.99 19.02019/02/09 15:58:00:000 223.018 100.6 93.788 6.860 12.99 19.02019/02/09 15:59:00:000 223.018 100.5 93.788 6.860 12.99 19.02019/02/09 16:00:00:000 223.018 100.5 93.642 6.860 12.99 19.02019/02/09 16:01:00:000 223.018 100.6 93.775 6.860 12.99 19.32019/02/09 16:02:00:000 223.018 100.6 93.775 6.860 12.99 19.32019/02/09 16:03:00:000 223.018 100.6 93.742 6.860 12.99 19.32019/02/09 16:04:00:000 223.018 100.6 93.742 6.860 12.99 19.02019/02/09 16:05:00:000 223.018 100.4 93.810 6.860 12.99 19.02019/02/09 16:06:00:000 223.018 100.5 93.613 6.860 12.99 19.02019/02/09 16:07:00:000 223.018 100.5 93.875 6.860 12.99 19.32019/02/09 16:08:00:000 223.018 100.6 93.701 6.860 12.99 19.32019/02/09 16:09:00:000 223.126 100.6 93.747 6.865 12.99 19.32019/02/09 16:10:00:000 223.126 100.5 93.747 6.865 12.99 19.02019/02/09 16:11:00:000 223.126 100.6 93.747 6.865 12.99 19.3

Page 73: Division of Environmental Permits Floor

2019/02/09 16:12:00:000 222.954 100.6 93.747 6.865 13.00 19.32019/02/09 16:13:00:000 222.954 100.5 93.649 6.865 13.00 19.32019/02/09 16:14:00:000 222.954 100.5 93.649 6.865 12.98 19.32019/02/09 16:15:00:000 222.814 100.5 93.573 6.865 12.98 19.52019/02/09 16:16:00:000 222.814 100.5 93.662 6.865 12.98 19.52019/02/09 16:17:00:000 222.814 100.6 93.662 6.865 12.98 19.52019/02/09 16:18:00:000 222.814 100.6 93.662 6.865 12.98 19.52019/02/09 16:19:00:000 222.814 100.6 93.662 6.865 13.00 19.32019/02/09 16:20:00:000 222.814 100.7 93.734 6.865 13.00 19.52019/02/09 16:21:00:000 222.814 100.6 93.734 6.865 13.00 19.52019/02/09 16:22:00:000 222.814 100.6 93.734 6.865 13.00 19.32019/02/09 16:23:00:000 223.186 100.7 93.890 6.865 13.00 19.32019/02/09 16:24:00:000 223.186 100.6 93.890 6.865 13.00 19.02019/02/09 16:25:00:000 223.186 100.6 93.890 6.865 13.00 19.02019/02/09 16:26:00:000 223.186 100.6 93.786 6.865 12.99 19.02019/02/09 16:27:00:000 223.186 100.6 93.786 6.865 12.99 19.02019/02/09 16:28:00:000 223.186 100.7 93.845 6.865 12.99 19.02019/02/09 16:29:00:000 223.186 100.4 93.845 6.874 12.99 19.02019/02/09 16:30:00:000 223.186 100.7 93.845 6.874 12.99 18.82019/02/09 16:31:00:000 223.186 100.7 93.845 6.874 12.99 18.82019/02/09 16:32:00:000 223.186 100.6 93.792 6.874 12.99 18.82019/02/09 16:33:00:000 223.186 100.7 93.792 6.874 12.99 18.82019/02/09 16:34:00:000 223.186 100.6 93.792 6.874 12.99 18.82019/02/09 16:35:00:000 223.186 100.6 93.872 6.874 12.99 18.52019/02/09 16:36:00:000 223.186 100.6 93.758 6.874 12.99 18.52019/02/09 16:37:00:000 222.867 100.6 93.758 6.874 12.99 18.82019/02/09 16:38:00:000 222.867 100.7 93.663 6.874 12.99 18.82019/02/09 16:39:00:000 222.867 100.7 93.663 6.874 12.99 18.82019/02/09 16:40:00:000 222.867 100.6 93.782 6.874 12.99 18.82019/02/09 16:41:00:000 222.867 100.6 93.782 6.874 12.99 19.02019/02/09 16:42:00:000 223.271 100.6 93.782 6.874 12.99 19.02019/02/09 16:43:00:000 223.271 100.6 93.782 6.874 12.99 18.52019/02/09 16:44:00:000 223.103 100.6 93.782 6.874 12.99 18.52019/02/09 16:45:00:000 223.103 100.6 93.845 6.874 12.99 18.52019/02/09 16:46:00:000 223.103 100.6 93.845 6.874 12.99 18.52019/02/09 16:47:00:000 223.103 100.7 93.697 6.874 12.99 18.52019/02/09 16:48:00:000 223.103 100.7 93.797 6.874 12.99 18.52019/02/09 16:49:00:000 223.320 100.6 93.867 6.874 12.99 18.52019/02/09 16:50:00:000 223.320 100.6 93.727 6.874 12.99 18.52019/02/09 16:51:00:000 223.320 100.6 93.883 6.874 12.99 18.32019/02/09 16:52:00:000 223.320 100.5 93.883 6.874 12.99 18.32019/02/09 16:53:00:000 223.320 100.6 93.812 6.874 12.99 18.32019/02/09 16:54:00:000 223.320 100.6 93.868 6.874 12.99 18.32019/02/09 16:55:00:000 223.320 100.7 93.915 6.874 12.99 18.32019/02/09 16:56:00:000 223.320 100.6 93.915 6.874 12.99 18.12019/02/09 16:57:00:000 223.526 100.6 93.915 6.874 12.99 18.12019/02/09 16:58:00:000 223.526 100.6 93.915 6.874 12.99 18.12019/02/09 16:59:00:000 223.526 100.6 94.011 6.874 12.99 17.92019/02/09 17:00:00:000 223.526 100.6 93.885 6.874 12.98 17.92019/02/09 17:01:00:000 223.526 100.6 94.031 6.874 12.98 17.92019/02/09 17:02:00:000 223.526 100.6 93.861 6.874 12.98 17.92019/02/09 17:03:00:000 223.526 100.7 93.972 6.874 12.98 17.92019/02/09 17:04:00:000 223.526 100.6 93.972 6.874 12.98 17.92019/02/09 17:05:00:000 223.526 100.8 94.051 6.874 12.99 17.92019/02/09 17:06:00:000 223.939 100.7 94.051 6.874 12.99 17.92019/02/09 17:07:00:000 223.939 100.7 94.051 6.874 12.99 17.62019/02/09 17:08:00:000 223.939 100.6 94.099 6.874 12.99 17.62019/02/09 17:09:00:000 223.733 100.7 93.988 6.874 12.99 17.62019/02/09 17:10:00:000 223.733 100.6 93.988 6.874 12.99 17.62019/02/09 17:11:00:000 223.733 100.6 94.093 6.874 12.99 17.62019/02/09 17:12:00:000 223.733 100.7 94.016 6.874 12.99 17.62019/02/09 17:13:00:000 223.733 100.6 94.016 6.874 12.99 17.42019/02/09 17:14:00:000 223.733 100.6 94.016 6.874 12.99 17.42019/02/09 17:15:00:000 223.733 100.6 94.016 6.874 12.99 17.42019/02/09 17:16:00:000 224.036 100.6 94.062 6.874 12.99 17.42019/02/09 17:17:00:000 224.036 100.6 94.062 6.874 12.99 17.42019/02/09 17:18:00:000 223.720 100.6 94.062 6.874 12.99 17.42019/02/09 17:19:00:000 223.720 100.6 93.964 6.874 12.96 17.42019/02/09 17:20:00:000 223.720 100.6 94.059 6.874 12.96 17.42019/02/09 17:21:00:000 223.911 100.6 94.059 6.874 12.96 17.42019/02/09 17:22:00:000 223.911 100.7 94.009 6.874 12.97 17.22019/02/09 17:23:00:000 223.911 100.6 94.191 6.874 12.97 17.22019/02/09 17:24:00:000 223.911 100.6 94.133 6.874 12.99 17.22019/02/09 17:25:00:000 223.911 100.6 94.133 6.874 12.99 16.92019/02/09 17:26:00:000 223.911 100.6 94.133 6.874 12.99 16.92019/02/09 17:27:00:000 223.911 100.6 94.047 6.874 12.99 16.92019/02/09 17:28:00:000 223.911 100.7 94.047 6.874 12.99 16.9

Page 74: Division of Environmental Permits Floor

2019/02/09 17:29:00:000 224.028 100.6 94.093 6.874 12.99 17.22019/02/09 17:30:00:000 224.028 100.6 93.929 6.874 12.99 17.22019/02/09 17:31:00:000 223.698 100.6 94.051 6.874 12.99 17.22019/02/09 17:32:00:000 223.698 100.6 93.982 6.874 12.99 17.22019/02/09 17:33:00:000 223.784 100.6 94.115 6.874 12.99 17.22019/02/09 17:34:00:000 223.784 100.6 94.009 6.874 12.99 17.22019/02/09 17:35:00:000 223.784 100.5 94.009 6.874 12.99 17.22019/02/09 17:36:00:000 223.784 100.6 94.009 6.874 12.99 17.22019/02/09 17:37:00:000 223.784 100.6 94.009 6.874 12.99 17.22019/02/09 17:38:00:000 223.784 100.6 94.086 6.876 12.99 17.22019/02/09 17:39:00:000 223.784 100.7 94.086 6.876 12.99 17.22019/02/09 17:40:00:000 223.923 100.6 94.086 6.876 12.99 16.92019/02/09 17:41:00:000 223.923 100.7 94.086 6.876 12.98 16.92019/02/09 17:42:00:000 224.319 100.6 94.086 6.876 12.98 16.92019/02/09 17:43:00:000 224.319 100.7 94.172 6.876 12.98 16.92019/02/09 17:44:00:000 224.141 100.6 94.172 6.876 12.98 16.72019/02/09 17:45:00:000 224.141 100.8 94.308 6.876 12.98 16.72019/02/09 17:46:00:000 224.559 100.7 94.308 6.876 12.98 16.72019/02/09 17:47:00:000 224.559 100.7 94.308 6.876 12.96 16.72019/02/09 17:48:00:000 224.167 100.7 94.174 6.876 12.96 16.52019/02/09 17:49:00:000 224.167 100.7 94.340 6.876 12.96 16.52019/02/09 17:50:00:000 224.167 100.7 94.253 6.876 12.99 16.5

AVERAGE: 223.07 100.55 93.77 6.83 13.00 18.53

Page 75: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 11 CTG-1 WO/DB Run 1DCS Data - 20190209 - 0920-1800

Unit 11 GT Power Unit 11 GT PowerUnit 11 Total GT

Gas FlowUnit 11 HRSG DB Fuel Flow

Unit 11 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 11HAD00EU001 11MKA01EU902A 11MBP10CF910 11HHA10CF001 11HNE10CQ109 11MBL05CT1012019/02/09 09:22:00:000 225.408 100.2 94.591 0.002 13.40 11.12019/02/09 09:23:00:000 225.050 100.3 94.449 0.002 13.40 10.92019/02/09 09:24:00:000 225.446 100.2 94.702 0.002 13.40 11.12019/02/09 09:25:00:000 225.446 100.2 94.638 0.002 13.40 11.32019/02/09 09:26:00:000 225.446 100.2 94.638 0.002 13.40 11.12019/02/09 09:27:00:000 225.446 100.3 94.638 0.002 13.40 11.32019/02/09 09:28:00:000 225.674 100.1 94.638 0.002 13.40 11.32019/02/09 09:29:00:000 225.674 100.1 94.639 0.002 13.40 11.32019/02/09 09:30:00:000 225.409 100.2 94.639 0.002 13.40 11.62019/02/09 09:31:00:000 225.409 100.1 94.538 0.002 13.40 11.62019/02/09 09:32:00:000 225.409 100.4 94.538 0.002 13.40 11.62019/02/09 09:33:00:000 225.065 100.0 94.455 0.002 13.41 11.62019/02/09 09:34:00:000 225.065 100.1 94.455 0.002 13.41 11.62019/02/09 09:35:00:000 225.006 100.1 94.455 0.002 13.41 11.62019/02/09 09:36:00:000 225.006 100.3 94.455 0.002 13.41 11.62019/02/09 09:37:00:000 225.006 100.2 94.455 0.002 13.41 11.62019/02/09 09:38:00:000 225.006 100.2 94.455 0.002 13.41 11.82019/02/09 09:39:00:000 225.006 100.2 94.438 0.002 13.41 12.12019/02/09 09:40:00:000 224.836 100.2 94.438 0.002 13.41 12.12019/02/09 09:41:00:000 224.836 100.3 94.343 0.002 13.40 12.12019/02/09 09:42:00:000 224.836 100.2 94.427 0.002 13.40 12.32019/02/09 09:43:00:000 224.836 100.2 94.427 0.002 13.40 12.32019/02/09 09:44:00:000 224.836 100.3 94.427 0.002 13.41 12.32019/02/09 09:45:00:000 225.260 100.3 94.427 0.002 13.41 12.32019/02/09 09:46:00:000 225.260 100.4 94.427 0.002 13.41 12.32019/02/09 09:47:00:000 225.260 100.4 94.512 0.002 13.41 12.12019/02/09 09:48:00:000 225.260 100.2 94.631 0.002 13.41 12.12019/02/09 09:49:00:000 225.260 100.2 94.637 0.002 13.41 12.12019/02/09 09:50:00:000 225.260 100.2 94.501 0.002 13.40 12.12019/02/09 09:51:00:000 225.260 100.3 94.501 0.002 13.40 12.32019/02/09 09:52:00:000 225.260 100.2 94.572 0.002 13.40 12.32019/02/09 09:53:00:000 225.014 100.2 94.373 0.003 13.43 12.52019/02/09 09:54:00:000 225.014 100.2 94.440 0.003 13.43 12.52019/02/09 09:55:00:000 224.673 100.2 94.383 0.003 13.41 12.72019/02/09 09:56:00:000 224.673 100.2 94.383 0.003 13.41 12.72019/02/09 09:57:00:000 225.144 100.4 94.481 0.003 13.41 12.52019/02/09 09:58:00:000 225.144 100.3 94.560 0.003 13.39 12.52019/02/09 09:59:00:000 225.144 100.3 94.560 0.003 13.39 12.52019/02/09 10:00:00:000 225.144 100.3 94.501 0.003 13.39 12.32019/02/09 10:01:00:000 224.690 100.3 94.501 0.003 13.40 12.72019/02/09 10:02:00:000 224.690 100.3 94.354 0.003 13.40 12.92019/02/09 10:03:00:000 224.690 100.4 94.354 0.003 13.40 12.92019/02/09 10:04:00:000 224.690 100.3 94.474 0.003 13.40 12.92019/02/09 10:05:00:000 225.013 100.3 94.233 0.003 13.40 12.92019/02/09 10:06:00:000 224.431 100.1 94.397 0.003 13.40 13.22019/02/09 10:07:00:000 224.431 100.3 94.226 0.003 13.40 13.22019/02/09 10:08:00:000 224.431 100.3 94.226 0.003 13.40 13.22019/02/09 10:09:00:000 224.431 100.2 94.282 0.003 13.41 13.22019/02/09 10:10:00:000 224.431 100.2 94.282 0.003 13.41 12.92019/02/09 10:11:00:000 224.431 100.2 94.304 0.003 13.41 12.92019/02/09 10:12:00:000 224.431 100.2 94.304 0.003 13.41 13.22019/02/09 10:13:00:000 224.431 100.2 94.304 0.003 13.41 13.22019/02/09 10:14:00:000 224.693 100.2 94.404 0.003 13.41 13.42019/02/09 10:15:00:000 224.693 100.2 94.244 0.003 13.41 13.42019/02/09 10:16:00:000 224.693 100.3 94.356 0.003 13.41 13.42019/02/09 10:17:00:000 224.693 100.2 94.356 0.003 13.41 13.42019/02/09 10:18:00:000 224.693 100.2 94.356 0.003 13.41 13.42019/02/09 10:19:00:000 224.693 100.3 94.356 0.003 13.41 13.42019/02/09 10:20:00:000 224.693 100.4 94.408 0.003 13.41 13.02019/02/09 10:21:00:000 225.024 100.4 94.439 0.003 13.41 13.02019/02/09 10:22:00:000 225.024 100.3 94.439 0.003 13.41 13.02019/02/09 10:23:00:000 225.024 100.3 94.439 0.003 13.41 13.22019/02/09 10:24:00:000 224.495 100.3 94.280 0.003 13.41 13.22019/02/09 10:25:00:000 224.495 100.5 94.280 0.003 13.41 13.72019/02/09 10:26:00:000 224.495 100.5 94.280 0.003 13.41 13.72019/02/09 10:27:00:000 224.833 100.4 94.280 0.003 13.41 13.72019/02/09 10:28:00:000 224.584 100.4 94.280 0.003 13.40 13.7

Page 76: Division of Environmental Permits Floor

2019/02/09 10:29:00:000 224.584 100.4 94.280 0.003 13.40 13.92019/02/09 10:30:00:000 224.584 100.3 94.280 0.003 13.40 13.92019/02/09 10:31:00:000 224.584 100.3 94.280 0.003 13.40 13.92019/02/09 10:32:00:000 224.394 100.3 94.280 0.003 13.41 14.12019/02/09 10:33:00:000 224.394 100.4 94.266 0.003 13.41 14.12019/02/09 10:34:00:000 224.394 100.5 94.300 0.003 13.41 14.12019/02/09 10:35:00:000 224.891 100.5 94.300 0.003 13.41 14.12019/02/09 10:36:00:000 224.891 100.5 94.424 0.003 13.41 14.12019/02/09 10:37:00:000 224.891 100.4 94.255 0.003 13.40 13.92019/02/09 10:38:00:000 224.355 100.4 94.255 0.003 13.40 14.12019/02/09 10:39:00:000 224.355 100.4 94.192 0.003 13.40 14.42019/02/09 10:40:00:000 224.355 100.5 94.192 0.003 13.40 14.42019/02/09 10:41:00:000 224.355 100.4 94.290 0.003 13.40 14.42019/02/09 10:42:00:000 224.355 100.4 94.192 0.003 13.40 14.12019/02/09 10:43:00:000 224.355 100.4 94.192 0.003 13.40 14.12019/02/09 10:44:00:000 224.081 100.6 94.192 0.003 13.40 14.42019/02/09 10:45:00:000 224.081 100.4 94.232 0.003 13.41 14.42019/02/09 10:46:00:000 224.081 100.4 94.120 0.003 13.41 14.62019/02/09 10:47:00:000 224.081 100.4 94.029 0.003 13.41 14.62019/02/09 10:48:00:000 224.081 100.6 94.029 0.003 13.41 14.42019/02/09 10:49:00:000 224.081 100.5 94.168 0.003 13.41 14.42019/02/09 10:50:00:000 224.081 100.3 94.339 0.003 13.41 14.42019/02/09 10:51:00:000 224.269 100.3 94.220 0.003 13.41 14.12019/02/09 10:52:00:000 224.796 100.4 94.231 0.003 13.41 14.12019/02/09 10:53:00:000 224.226 100.3 94.376 0.003 13.41 14.42019/02/09 10:54:00:000 224.644 100.3 94.278 0.003 13.41 14.42019/02/09 10:55:00:000 224.644 100.4 94.322 0.003 13.41 14.12019/02/09 10:56:00:000 224.644 100.2 94.322 0.003 13.41 14.12019/02/09 10:57:00:000 224.644 100.4 94.159 0.003 13.41 14.12019/02/09 10:58:00:000 224.473 100.4 94.360 0.003 13.41 14.12019/02/09 10:59:00:000 224.473 100.3 94.208 0.003 13.41 14.12019/02/09 11:00:00:000 224.171 100.3 94.208 0.003 13.39 14.12019/02/09 11:01:00:000 224.171 100.2 94.190 0.003 13.39 14.12019/02/09 11:02:00:000 224.171 100.2 94.190 0.003 13.41 13.92019/02/09 11:03:00:000 224.171 100.2 94.190 0.003 13.41 13.92019/02/09 11:04:00:000 224.171 100.3 94.190 0.003 13.41 13.92019/02/09 11:05:00:000 224.171 100.3 94.190 0.003 13.41 14.42019/02/09 11:06:00:000 224.171 100.3 94.102 0.003 13.41 14.42019/02/09 11:07:00:000 224.371 100.3 94.175 0.003 13.41 14.42019/02/09 11:08:00:000 224.371 100.3 94.175 0.003 13.41 14.62019/02/09 11:09:00:000 224.051 100.3 94.175 0.003 13.41 14.82019/02/09 11:10:00:000 224.051 100.4 94.175 0.003 13.40 14.82019/02/09 11:11:00:000 224.332 100.4 94.175 0.003 13.40 14.82019/02/09 11:12:00:000 224.332 100.5 94.333 0.003 13.40 14.42019/02/09 11:13:00:000 224.632 100.5 94.333 0.003 13.40 14.42019/02/09 11:14:00:000 224.632 100.4 94.270 0.003 13.40 14.42019/02/09 11:15:00:000 224.171 100.6 94.193 0.003 13.40 14.42019/02/09 11:16:00:000 224.171 100.6 94.193 0.003 13.40 14.42019/02/09 11:17:00:000 224.455 100.4 94.076 0.003 13.40 14.62019/02/09 11:18:00:000 224.105 100.6 94.076 0.003 13.40 14.62019/02/09 11:19:00:000 224.105 100.4 94.076 0.003 13.40 14.92019/02/09 11:20:00:000 224.105 100.5 94.076 0.003 13.40 14.92019/02/09 11:21:00:000 224.105 100.5 94.135 0.003 13.41 14.92019/02/09 11:22:00:000 224.105 100.5 94.135 0.003 13.41 15.12019/02/09 11:23:00:000 224.105 100.5 94.135 0.003 13.41 15.12019/02/09 11:24:00:000 223.805 100.6 94.135 0.003 13.41 15.52019/02/09 11:25:00:000 224.152 100.5 94.135 0.003 13.41 15.52019/02/09 11:26:00:000 224.152 100.4 93.981 0.003 13.41 15.32019/02/09 11:27:00:000 223.970 100.6 94.159 0.003 13.41 15.32019/02/09 11:28:00:000 223.970 100.5 94.033 0.003 13.41 15.32019/02/09 11:29:00:000 224.272 100.5 94.220 0.003 13.41 15.32019/02/09 11:30:00:000 224.272 100.5 94.278 0.003 13.41 15.32019/02/09 11:31:00:000 224.272 100.5 94.332 0.003 13.41 15.12019/02/09 11:32:00:000 224.272 100.4 94.263 0.003 13.41 15.12019/02/09 11:33:00:000 224.272 100.4 94.159 0.003 13.41 15.12019/02/09 11:34:00:000 224.272 100.4 94.159 0.003 13.41 14.92019/02/09 11:35:00:000 224.272 100.5 94.234 0.003 13.41 14.92019/02/09 11:36:00:000 224.595 100.5 94.139 0.003 13.41 14.92019/02/09 11:37:00:000 224.251 100.4 94.139 0.003 13.40 15.12019/02/09 11:38:00:000 224.251 100.3 94.139 0.003 13.40 15.32019/02/09 11:39:00:000 223.730 100.4 94.019 0.003 13.40 15.52019/02/09 11:40:00:000 223.730 100.4 93.859 0.003 13.40 15.52019/02/09 11:41:00:000 223.730 100.4 93.979 0.003 13.41 15.72019/02/09 11:42:00:000 223.398 100.6 93.818 0.003 13.41 15.72019/02/09 11:43:00:000 223.398 100.7 93.989 0.003 13.41 15.72019/02/09 11:44:00:000 223.790 100.5 93.989 0.003 13.42 15.72019/02/09 11:45:00:000 223.790 100.5 94.089 0.003 13.42 15.7

Page 77: Division of Environmental Permits Floor

2019/02/09 11:46:00:000 223.790 100.5 93.931 0.003 13.42 16.02019/02/09 11:47:00:000 223.790 100.5 93.931 0.003 13.42 16.02019/02/09 11:48:00:000 223.790 100.4 94.108 0.003 13.42 16.22019/02/09 11:49:00:000 223.790 100.4 94.056 0.003 13.42 16.22019/02/09 11:50:00:000 223.239 100.6 93.919 0.003 13.41 16.02019/02/09 11:51:00:000 223.729 100.6 93.919 0.003 13.41 16.22019/02/09 11:52:00:000 223.729 100.6 94.095 0.003 13.41 16.22019/02/09 11:53:00:000 224.088 100.5 94.095 0.003 13.41 16.22019/02/09 11:54:00:000 224.088 100.5 94.095 0.003 13.41 16.02019/02/09 11:55:00:000 224.088 100.4 94.195 0.003 13.41 16.02019/02/09 11:56:00:000 223.815 100.4 94.091 0.003 13.41 15.72019/02/09 11:57:00:000 224.135 100.4 94.091 0.003 13.41 15.72019/02/09 11:58:00:000 224.135 100.5 94.091 0.003 13.41 15.72019/02/09 11:59:00:000 223.624 100.5 93.916 0.003 13.41 16.02019/02/09 12:00:00:000 223.624 100.5 94.008 0.003 13.41 16.02019/02/09 12:01:00:000 223.624 100.4 93.937 0.003 13.41 16.22019/02/09 12:02:00:000 223.624 100.5 93.937 0.003 13.41 16.22019/02/09 12:03:00:000 223.969 100.5 94.090 0.003 13.41 16.22019/02/09 12:04:00:000 223.969 100.5 94.013 0.003 13.41 16.02019/02/09 12:05:00:000 223.756 100.6 94.013 0.003 13.42 16.22019/02/09 12:06:00:000 223.756 100.4 94.013 0.003 13.42 16.02019/02/09 12:07:00:000 223.756 100.4 93.792 0.003 13.42 16.52019/02/09 12:08:00:000 223.039 100.4 93.837 0.003 13.41 16.52019/02/09 12:09:00:000 223.518 100.4 93.837 0.003 13.41 16.52019/02/09 12:10:00:000 223.518 100.7 93.837 0.003 13.41 16.52019/02/09 12:11:00:000 223.518 100.4 93.837 0.003 13.41 16.72019/02/09 12:12:00:000 223.004 100.5 93.760 0.003 13.42 17.22019/02/09 12:13:00:000 223.284 100.5 93.760 0.003 13.42 17.22019/02/09 12:14:00:000 223.284 100.6 93.841 0.003 13.42 17.22019/02/09 12:15:00:000 223.284 100.5 93.841 0.003 13.42 17.42019/02/09 12:16:00:000 223.284 100.5 93.971 0.003 13.42 17.22019/02/09 12:17:00:000 223.487 100.5 93.874 0.003 13.42 16.92019/02/09 12:18:00:000 223.487 100.6 93.874 0.003 13.42 16.92019/02/09 12:19:00:000 223.487 100.5 93.874 0.003 13.42 16.92019/02/09 12:20:00:000 223.487 100.6 93.874 0.003 13.42 16.72019/02/09 12:21:00:000 223.487 100.5 93.874 0.003 13.42 16.72019/02/09 12:22:00:000 223.487 100.4 93.874 0.003 13.42 16.72019/02/09 12:23:00:000 223.317 100.5 93.643 0.003 13.42 16.72019/02/09 12:24:00:000 223.317 100.4 93.780 0.003 13.42 16.72019/02/09 12:25:00:000 223.317 100.5 93.780 0.003 13.42 16.92019/02/09 12:26:00:000 222.797 100.4 93.780 0.003 13.42 16.92019/02/09 12:27:00:000 223.255 100.5 93.892 0.003 13.42 17.22019/02/09 12:28:00:000 223.255 100.5 93.761 0.003 13.42 17.22019/02/09 12:29:00:000 223.255 100.5 93.861 0.003 13.42 17.22019/02/09 12:30:00:000 223.255 100.6 93.773 0.003 13.42 17.62019/02/09 12:31:00:000 223.504 100.6 93.956 0.003 13.42 17.42019/02/09 12:32:00:000 223.504 100.6 93.926 0.003 13.42 17.42019/02/09 12:33:00:000 223.504 100.6 93.926 0.003 13.42 17.42019/02/09 12:34:00:000 223.504 100.5 93.926 0.003 13.42 17.22019/02/09 12:35:00:000 223.504 100.5 93.926 0.003 13.41 17.22019/02/09 12:36:00:000 223.504 100.5 93.858 0.003 13.41 17.22019/02/09 12:37:00:000 223.292 100.5 93.858 0.003 13.41 17.42019/02/09 12:38:00:000 223.292 100.5 93.729 0.003 13.41 17.62019/02/09 12:39:00:000 223.292 100.6 93.729 0.003 13.41 17.62019/02/09 12:40:00:000 222.841 100.5 93.824 0.003 13.41 17.92019/02/09 12:41:00:000 222.841 100.5 93.663 0.003 13.42 17.62019/02/09 12:42:00:000 223.167 100.5 93.759 0.003 13.42 17.62019/02/09 12:43:00:000 223.167 100.5 93.611 0.003 13.42 17.62019/02/09 12:44:00:000 223.039 100.4 93.735 0.003 13.42 17.92019/02/09 12:45:00:000 222.723 100.5 93.680 0.003 13.42 18.32019/02/09 12:46:00:000 222.723 100.4 93.680 0.003 13.42 18.32019/02/09 12:47:00:000 223.237 100.5 93.785 0.003 13.42 18.32019/02/09 12:48:00:000 223.237 100.6 93.785 0.003 13.42 18.12019/02/09 12:49:00:000 223.237 100.5 93.719 0.003 13.42 18.12019/02/09 12:50:00:000 223.237 100.6 93.719 0.003 13.42 17.82019/02/09 12:51:00:000 223.091 100.5 93.600 0.003 13.42 17.82019/02/09 12:52:00:000 223.091 100.5 93.797 0.003 13.42 17.82019/02/09 12:53:00:000 223.091 100.5 93.797 0.003 13.42 17.82019/02/09 12:54:00:000 223.091 100.3 93.760 0.003 13.42 17.62019/02/09 12:55:00:000 223.091 100.4 93.545 0.003 13.42 17.62019/02/09 12:56:00:000 222.682 100.5 93.545 0.003 13.42 17.92019/02/09 12:57:00:000 223.114 100.4 93.759 0.003 13.42 18.12019/02/09 12:58:00:000 223.114 100.4 93.759 0.003 13.43 17.92019/02/09 12:59:00:000 223.114 100.4 93.698 0.003 13.43 17.92019/02/09 13:00:00:000 222.870 100.6 93.698 0.003 13.43 18.12019/02/09 13:01:00:000 222.870 100.5 93.462 0.003 13.43 17.92019/02/09 13:02:00:000 222.870 100.4 93.716 0.003 13.42 18.1

Page 78: Division of Environmental Permits Floor

2019/02/09 13:03:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:04:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:05:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:06:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:07:00:000 222.870 100.5 93.716 0.003 13.42 18.12019/02/09 13:08:00:000 222.870 100.5 93.716 0.003 13.42 17.92019/02/09 13:09:00:000 222.870 100.5 93.532 0.003 13.42 18.32019/02/09 13:10:00:000 222.870 100.4 93.715 0.003 13.42 18.32019/02/09 13:11:00:000 222.870 100.4 93.715 0.003 13.42 18.32019/02/09 13:12:00:000 222.870 100.5 93.715 0.003 13.42 18.52019/02/09 13:13:00:000 222.870 100.6 93.715 0.003 13.42 18.52019/02/09 13:14:00:000 222.028 100.2 93.421 0.003 13.42 18.52019/02/09 13:15:00:000 221.397 100.0 93.214 0.003 13.42 18.52019/02/09 13:16:00:000 222.402 100.4 93.495 0.003 13.46 18.52019/02/09 13:17:00:000 222.963 100.6 93.801 0.003 13.46 18.52019/02/09 13:18:00:000 223.370 100.6 93.801 0.003 13.43 18.32019/02/09 13:19:00:000 222.890 100.4 93.838 0.003 13.43 18.12019/02/09 13:20:00:000 222.890 100.4 93.681 0.003 13.41 18.12019/02/09 13:21:00:000 222.890 100.4 93.681 0.003 13.41 17.92019/02/09 13:22:00:000 222.890 100.4 93.715 0.003 13.41 17.92019/02/09 13:23:00:000 222.890 100.4 93.715 0.003 13.41 17.92019/02/09 13:24:00:000 223.204 100.5 93.791 0.003 13.41 17.92019/02/09 13:25:00:000 222.853 100.5 93.713 0.003 13.42 17.92019/02/09 13:26:00:000 222.853 100.4 93.713 0.003 13.42 17.42019/02/09 13:27:00:000 222.853 100.6 93.713 0.003 13.42 17.62019/02/09 13:28:00:000 222.853 100.6 93.713 0.003 13.42 17.62019/02/09 13:29:00:000 223.184 100.5 93.713 0.003 13.42 17.62019/02/09 13:30:00:000 223.184 100.5 93.713 0.003 13.42 17.82019/02/09 13:31:00:000 222.784 100.5 93.713 0.003 13.42 17.82019/02/09 13:32:00:000 222.784 100.5 93.672 0.003 13.42 17.82019/02/09 13:33:00:000 222.784 100.4 93.672 0.003 13.42 17.8

AVERAGE: 223.99 100.40 94.09 0.00 13.41 15.20

Page 79: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-11 Base Load wDB

PM Data

Page 80: Division of Environmental Permits Floor

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

09:24 13:52 13:48 hh:mm

13:44 17:55 17:50 hh:mm

02/08/19 02/08/19 02/09/18 mm/dd/yy

Base w/db Base w/db Base w/db % or w/DB --

1.012 0.984 0.984

0.7890 0.7240 0.7240

0.142 0.144 0.144 in

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

743.580 984.260 66.510 ft³

826.665 1066.260 150.020 ft³

83.085 82.000 83.510 82.865 ft³

249.00 227.50 231.25 235.92 min

54.75 68.58 62.42 61.92 °F

192.75 191.08 197.58 193.81 °F

28.59 28.59 29.34 28.84 in Hg

-1.20 -1.20 -1.20 -1.20 in H₂O

28.50 28.50 29.25 28.75 in Hg

0.44 0.44 0.43 0.44 in H₂O

28.72 28.72 29.47 28.97 in Hg

1.20 1.19 1.20 1.20 √(in H₂O)

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

164.10 126.60 134.20 141.63 g

17.00 17.20 11.70 15.30 g

181.43 144.06 146.16 157.22 ml

8.54 6.78 6.88 7.40 scf

82.5 77.1 81.5 80.4 dscf

2.3 2.2 2.3 2.3 dscm

9.38 8.08 7.78 8.41 %

70.63 68.16 76.20 71.66 %

9.38 8.08 7.78 8.41 %

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

5.0 5.0 5.0 5.0 %

12.6 12.6 12.6 12.6 %

0.0 0.0 0.0 0.0 ppm

82.4 82.4 82.4 82.4 %

29.30 29.30 29.30 29.30 lb/lb-mole

28.24 28.39 28.42 28.35 lb/lb-mole

1.663 1.660 1.660 1.661

8632.05 8632.05 8632.05 8632.05 dscf/MMBtu

137.6 137.7 137.7 137.6 %

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Initial Meter Volume

Final Meter Volume

Total Meter Volume

Stack Test Data

Run Start Time

Run Stop Time

Test Date

Meter Calibration Factor

Pitot Tube Coefficient

Project # sie-19-middletown.ny-comp#2

Historical Data

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

Average Nozzle Diameter

Load

Absolute Stack Pressure

Average Orifice Pressure Drop

Absolute Meter Pressure

Avg Square Root Pitot Pressure

Moisture Content Data

Total Sampling Time

Average Meter Temperature

Average Stack Temperature

Barometric Pressure

Stack Static Pressure

Calculated Stack Moisture

Saturated Stack Moisture

Reported Stack Moisture Content

Carbon Dioxide Content

Gas Analysis Data

Impinger Water Weight Gain

Silica Gel Weight Gain

Total Water Volume Collected

Standard Water Vapor Volume

Standard Meter Volume

Standard Metric Meter Volume

Calculated Fuel Factor

Fuel F-Factor

Percent Excess Air

Oxygen Content

Carbon Monoxide Content

Nitrogen Content

Stack Dry Molecular Weight

Stack Wet Molecular Weight

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Results

Page 81: Division of Environmental Permits Floor

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

73.05 65.88 65.86 68.26 ft/sec

283.53 283.53 283.53 283.53 ft²

1,242,622 1,120,695 1,120,320 1,161,212 acfm

57,450 51,945 52,768 54,054 wkscfh

52,061,607 47,746,643 48,661,657 49,489,969 dscfh

100.9 106.9 109.0 105.6 %

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

5.25 4.43 11.23 6.97 mg --

6.36E-05 5.75E-05 1.38E-04 8.63E-05 g/dscf --

9.81E-04 8.87E-04 2.13E-03 1.33E-03 gr/dscf --

3.31 2.74 6.70 4.25 kg/hr --

7.30 6.05 14.78 9.37 lb/hr --

31.96 26.50 64.72 41.06 tpy --

0.0030 0.0028 0.0066 0.0041 lb/MMBtu 0.0073

1.27 1.66 7.36 3.43 mg --

1.53E-05 2.16E-05 9.03E-05 4.24E-05 g/dscf --

2.37E-04 3.33E-04 1.39E-03 6.54E-04 gr/dscf --

0.80 1.03 4.39 2.07 kg/hr --

1.76 2.27 9.68 4.57 lb/hr --

7.71 9.94 42.42 20.02 tpy --

0.0007 0.0010 0.0043 0.0020 lb/MMBtu --

1.98 1.47 2.97 2.14 mg --

2.40E-05 1.90E-05 3.64E-05 2.65E-05 g/dscf --

3.70E-04 2.94E-04 5.62E-04 4.09E-04 gr/dscf --

1.25 0.91 1.77 1.31 kg/hr --

2.75 2.00 3.91 2.89 lb/hr --

12.07 8.78 17.11 12.65 tpy --

0.0012 0.0009 0.0017 0.0013 lb/MMBtu --

2.00 1.30 0.90 1.40 mg --

2.42E-05 1.69E-05 1.10E-05 1.74E-05 g/dscf --

3.74E-04 2.60E-04 1.70E-04 2.68E-04 gr/dscf --

1.26 0.81 0.54 0.87 kg/hr --

2.78 1.77 1.18 1.91 lb/hr --

12.19 7.77 5.19 8.38 tpy --

0.0012 0.0008 0.0005 0.0008 lb/MMBtu --

11-PM-Base wDB-1 11-PM-Base wDB-2 11-PM-Base wDB-3 Average Units Limits

0.47 0.48 0.49 0.48 ft³/min

201.42 202.23 204.05 202.57 µP

1.08 1.08 1.08 1.08

2.55 2.53 2.47 2.51

1.08 1.08 1.08 1.08

2.55 2.53 2.47 2.51

2510.10 2534.30 2607.38 2,550.59

1.00 1.00 1.00 1.00

0 0 0 0 points

Average Stack Gas Velocity

Volumetric Flow Rate Data

Emission Rate Data

Stack Cross-Sectional Area

Actual Stack Flow Rate

Wet Standard Stack Flow Rate

Dry Standard Stack Flow Rate

Percent of Isokinetic Rate

Condensable PM₂.₅ Concentration

Filterable PM₂.₅ Mass

Filterable PM₂.₅ Concentration

Condensable PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Concentration

Filterable PM₁₀ Mass

Filterable PM₁₀ Concentration

Total PM₁₀/PM₂.₅ Emission Rate

Filterable PM₁₀ Emission Rate

Filterable PM₂.₅ Emission Rate

Reynolds Number

RM 201A Quality Control

No. Sampling Pts. Outside Dp

Cyclone Flow Rate

Stack Viscosity

Cunningham Correction Factor

Recalculated D50-1 for CIV

Z

Recalculated Cunninham

Lower Limit Cut Diameter, CI (NRE<3162), D50LL

Condensable PM₂.₅ Emission Rate

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Results

Page 82: Division of Environmental Permits Floor

(mm/dd/yy)

°F

in Hg

indust. spec. scf

chk Subpart minutes

in

1 2 3

(mm/dd/yy) 02/08/19 02/08/19 02/09/18

Base w/db Base w/db Base w/db % or w/DB

8632.05 8632.05 8632.05 dscf/MMBtu

from ACS samp-cp-0034 samp-cp-0030 samp-cp-0030

(Y) 1.012 0.984 0.984

(H@) 1.830 1.812 1.812 in H₂O

No No No

from ACS P-981/10 4187/10 4187/10

(Cp) 0.7890 0.7240 0.7240

from ACS 3 3 3 must match cyc nozz tab (e.g. 3, 4, etc.)

(Dn) 0.142 0.144 0.144 in

from ACS samp-hp-0144 samp-hp-0143 samp-ho-0143

120.0 120.0 120.0 in

from list glass glass glass

from ACS samp-bh-0034 samp-bh-0029 samp-bh-0034

from ACS Samp-cc-0001 Samp-cc-0001 Samp-cc-0001

Created with Isocalc-AHI v20190131

Load

4

6.00

Circular

Meter Box Number

Meter Calibration Factor

Orifice Meter Coefficient

Non-Console Manometer Used

50

240

CTG-11

11-PM-Base wDB

4

Test Date

Fuel F-Factor

(918) 307-9131

Address

City, State Zip

Project Manager

Phone Number

Fax Number

Sample Case / Oven Number

Impinger Case Number

(SS, Glass …. ) Liner Material

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE

Date for Preliminary Run 02/08/19

Company Name Air Hygiene International, Inc. (Tulsa, Oklahoma)

Test Information

Project # sie-19-middletown.ny-comp#2

Source Information

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

Fuel Type Gas, Natural

Required Sample Vol.

Run Duration

Testing Company Information

Pitot Tube Coefficient

Nozzle Number

Nozzle Diameter

Probe Number

Probe Length

1600 W Tacoma Street

Broken Arrow, Oklahoma 74012

Cole McBride

(918) 307-8865

Unit Number

Operator DA

Standard Temperature

Standard Pressure

68

29.92

Pitot Identification

Number of Ports Used

Port Inside Diameter

Stack Shape

Base Run Number

Number of Ports Available

Test Equipment Information

Run

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Title Page

Page 83: Division of Environmental Permits Floor

(Lfw) 235.25 in

(Lnw) 7.25 in

(D) 228.00 in

(As) 283.53 ft²

(A) 1200.00 in

(AD) 5.26 diameters

(B) 1095.00 in

(BD) 4.80 diameters

Down Up Particulate Velocity

Stream Stream Points Points

2.00-4.99 0.50-1.24 24 16

5.00-5.99 1.25-1.49 20 16

6.00-6.99 1.50-1.74 16 12

7.00-7.99 1.75-1.99 12 12

>= 8.00 >=2.00 8 or 122 8 or 122

12 12

24 16 4 Ports by 3 Across

24 16 12 Pts Used 12 Required

Fraction Distance Distance

Traverse of from Including

Point Stack Inside Reference

Number Diameter Wall Length

in in

1 0.044 10 17 2/8

2 0.146 33 2/8 40 4/8

3 0.296 67 4/8 74 6/8

4

5

6

7

8

9

Stack Type

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 1 - SAMPLE AND VELOCITY TRAVERSES FOR CIRCULAR SOURCES

Plant Name CPV Valley Energy Center Date 02/08/19

Sampling Location CTG-11 Stack

Project #

Circular

Stack Size Large (>24 inch diameter) Port ID (inches) 6.00

Circular Stack or Duct Diameter

Distance to Far Wall of Stack

Operator DA Ports Available 4

Distance Downstream

Diameters Downstream

Number of Traverse Points Required

Diameters to Minimum Number of1

Flow Disturbance Traverse Points

Distance to Near Wall of Stack

Diameter of Stack

Area of Stack

Distance from Port to Disturbances

Distance Upstream

Diameters Upstream

Traverse Point Locations

1 Check Minimum Number of Points for the Upstream

and Downstream conditions, then use the largest.

2 8 for Circular Stacks 12 to 24 inches

12 for Circular Stacks over 24 inches

Upstream Spec Number of Traverse Points Used

Downstream Spec

Traverse Pts Required

Lnw

Lfw

D

B

A

Method 1 Trav

12 Point PM Trav (M201a ONLY)

Velocity

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB M1 - Circular

Page 84: Division of Environmental Permits Floor

x PreTest x PostTest 0.8177 A3541

(As) 283.53 ft²

(D) 228.00 in 08:14 Start 08:33 End

Traverse Velocity Null Zero Deg Stack Local

Point Head Angle Pressure Temp Velocity

(p) (Na) (0oa) (ts) (vs(l))

(Pb) 28.53 in Hg in H₂O deg in H₂O °F ft/sec

(Pstatic) -1.20 in H₂O A-1 1.50 0 0.00 192 76.95

(Ps) 28.44 in Hg A-2 1.50 0 0.00 192 76.95

A-3 1.40 0 0.00 191 74.28

B-1 1.20 0 0.00 192 68.83

B-2 1.20 0 0.00 192 68.83

(%CO2) 4.90 %vd B-3 1.00 0 0.00 190 62.73

(%O2) 12.40 %vd C-1 1.50 0 0.00 195 77.13

(ppmCO) 0.00 ppmvd C-2 1.50 0 0.00 194 77.07

(%N2) 82.70 %vd C-3 1.10 0 0.00 192 65.90

(Bws) 8.00 % D-1 1.60 0 0.00 195 79.66

(Md) 29.28 lb/lb-mole D-2 1.60 0 0.00 193 79.54

(Mw) 28.38 lb/lb-mole D-3 1.40 0 0.00 193 74.40

(vs) 70.94 ft/sec

(Qsd) 51,233,450 dscf/hr

(Qsd) 853,891 dscf/min

(Qaw) 1,206,762 acf/min

(Qsw) 55,688,532 ascf/hr

1.38 0 193

1.17

0.0

METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE

Plant Name CPV Valley Energy Center Preliminary Run Date 02/08/19

Project # sie-19-middletown.ny-comp#2

Pitot Identification

Sampling Location CTG-11 Stack Stack Type Circular

Operator DA Ports Available 4

Stack Dimensions Velocity Traverse Data

Diameter of Stack

Run Number 11-PM-Base wDB-V1

samp-hp-0144

Pitot Leak Check Pitot Coefficient

Absolute Stack Pressure

Stack Gas Composition

Estimated CompositionComposition Data:

Area of Stack

Run Time

Average

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Results

Avg Stack Gas Velocity

Avg Stack Dry Std Flow Rate

Oxygen Concentration

Carbon Monoxide Concentration

Nitrogen Concentration

Stack Moisture Content

40 CFR 60, Method 2G, Section 8.11.1 (but applies to all Method 2 type static pressure measurements): If a Type S probe is used for this measurement, position the probe at or between any traverse point(s) and rotate the probe until a null differential pressure reading is obtained. Disconnect the tubing from one of the pressure ports; read and record the ∆P. For pressure devices with one-directional scales, if a deflection in the positive direction is noted with the negative side disconnected, then the static pressure is positive. Likewise, if a deflection in the positive direction is noted with the positive side disconnected, then the static pressure is negative.

Thermocouple ID

Standard deviation of null angles =

Pressures

Barometric Pressure

Static Pressure

Carbon Dioxide Concentration

= Square roots of p

Avg Stack Dry Std Flow Rate

Avg Stack Wet Flow Rate

Avg Stack Wet Std Flow Rate

Stack Cross Section Schematic

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB M2 - Run (1)

Page 85: Division of Environmental Permits Floor

1.600 1.836

Date 02/08/19 09:24 13:44

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

5.0 12.6 0.0 82.4 137.6 YES

Date 02/08/19 13:52 17:55

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

5.0 12.6 0.0 82.4 137.7 YES

Date 02/09/18 13:48 17:50

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

5.0 12.6 0.0 82.4 137.7 YES

11-PM-Base wDB-1 Run Start Time Run Stop Time

Gas Analysis Data

Fuel Type Min. Fuel Factor Max. Fuel FactorGas, Natural

METHOD 3a - DETERMINATION OF DRY MOLECULAR WEIGHT BY ANALYZER

02/08/19

Sampling Location CTG-11 Stack

Project #

Operator

sie-19-middletown.ny-comp#2 # of Ports Used

DA

1 (gas probe)

Plant Name CPV Valley Energy Center Preliminary Run Date

Run Number

Run Number 11-PM-Base wDB-2 Run Start Time Run Stop Time

Gas Analysis Data

Dry Molecular Weight

(Md)

N₂ Conc.

CO₂ Conc.

O₂ Conc.

COConc.

Excess Air

Fuel Factor in

Range

hh:mm

04:20

CalculatedFuel Factor

(Fo)avg

1.663

SampleAnalysis

Time

lb/lb-mole

29.30

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

Gas Analysis Data

Run Number 11-PM-Base wDB-3 Run Start Time

hh:mm lb/lb-mole

04:03 29.30 1.660

Run Stop Time

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

hh:mm lb/lb-mole

04:02 29.30 1.660

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB M3a - Mol Wt

Page 86: Division of Environmental Permits Floor

Standard Result Difference Pass/Fail

(g) (g) (g) (± 0.5 g)

500 499.7 -0.3 Pass

500 499.7 -0.3 Pass

500 499.6 -0.4 Pass

Date 02/08/19 Start Time 09:24 Stop Time 13:44

(Y)

(Vm) 83.085 dcf (Pb) 28.59 in Hg

(ts)avg 193 °F (Pstatic) -1.20 in H₂O

(tm)avg 55 °F (H)avg 0.44 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 504.80 623.80 710.90 937.90

Initial Value (Vi),(Wi) 370.90 609.00 695.50 920.90

Net Value (Vn),(Wn) 133.9 14.8 15.4 17.0

(Wt) 181.10 g (Vwsg(std)) 8.539 scf

(Vm(std)) 82.506 dscf (Bws(svp)) 70.63 %

(Bws(calc)) 9.38 % (Bws) 9.38 %

Date 02/08/19 Start Time 13:52 Stop Time 17:55

(Y)

(Vm) 82.000 dcf (Pb) 28.59 in Hg

(ts)avg 191 °F (Pstatic) -1.20 in H₂O

(tm)avg 69 °F (H)avg 0.44 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 476.70 615.80 665.50 828.50

Initial Value (Vi),(Wi) 362.30 614.00 655.10 811.30

Net Value (Vn),(Wn) 114.4 1.8 10.4 17.2

(Wt) 143.80 g (Vwsg(std)) 6.780 scf

(Vm(std)) 77.103 dscf (Bws(svp)) 68.16 %

(Bws(calc)) 8.08 % (Bws) 8.08 %

Date 02/09/18 Start Time 13:48 Stop Time 17:50

(Y)

(Vm) 83.510 dcf (Pb) 29.34 in Hg

(ts)avg 198 °F (Pstatic) -1.20 in H₂O

(tm)avg 62 °F (H)avg 0.43 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 497.80 617.10 664.80 839.50

Initial Value (Vi),(Wi) 363.80 616.60 665.10 827.80

Net Value (Vn),(Wn) 134.0 0.5 -0.3 11.7

(Wt) 145.90 g (Vwsg(std)) 6.879 scf

(Vm(std)) 81.530 dscf (Bws(svp)) 76.20 %

(Bws(calc)) 7.78 % (Bws) 7.78 %

Sampling Location CTG-11 Stack

Project #

DAOperator

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 4 - DETERMINATION OF MOISTURE CONTENT IN STACK GASES

Plant Name CPV Valley Energy Center Preliminary Run Date 02/08/19

Total Meter Volume Barometric Pressure

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Moisture Content Data

Run Number 11-PM-Base wDB-1

Meter Box Number Meter Cal Factorsamp-cp-0034 1.012

Meter Box Number samp-cp-0030 Meter Cal Factor 0.984

Total Meter Volume Barometric Pressure

Moisture Content Data

Run Number 11-PM-Base wDB-2

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Results

Total Weight Water Vol Weighed

Std Meter Volume Sat. Moisture Content

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0030 Meter Cal Factor 0.984

Total Meter Volume Barometric Pressure

Calc Moisture Content Final Moisture Content

Moisture Content Data

Run Number 11-PM-Base wDB-3

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Date

Scale Number SAMP-SC-0016

Scale Daily Calibration

Preliminary Date 02/08/19

Test Day 1

Test Day 2

02/08/19

02/09/19

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB M4 - Moisture

Page 87: Division of Environmental Permits Floor

(Cp) 0.7890 P-981/10

(ts) 192.8 °F

(tm) 54.8

(H@) 1.830 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.20 in H₂O

PASS Post 0.000 ft³/min@ 15.0 in Hg (Y) 1.012 (Bws) 9.38 %

Pitot Pre (+) 5.6 in H₂O for 30.0 sec (Md) 29.30 lb/lb-mole

Pre (-) 6.3 in H₂O for 30.0 sec (Dna) 0.1420 in (Qm) 0.75 acfm

Post (+) 5.2 in H₂O for 30.0 sec (Dni) 0.2097 in (K) 0.26

Post (-) 4.8 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 28.59 in Hg

Pre 0.142 0.142 0.142 PASS (Pstatic) -1.20 in H₂O

Post 0.142 0.142 0.142 PASS (Ps) 28.50 in Hg

(Pm) 28.72 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 09:24 End 13:44 Pre 370.9 609.0 695.5 920.9 ml

Post 504.8 623.8 710.9 937.9 ml

samp-cp-0034 samp-cp-0034 samp-cp-0034 samp-hp-0144 samp-hp-0144 samp-bh-0034 7711 1035 3105 samp-cp-0034

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 743.580 1.40 0.438 0.44 195 251 252 43 45 70 51 51 2.0 1.18 71.99 7.652 110.3 90.736

A-2 21.0 00:21:00 751.230 1.50 0.438 0.44 194 250 260 43 60 71 53 53 2.0 1.22 74.46 15.419 107.3 89.812

A-3 42.8 00:42:45 759.025 1.40 0.438 0.44 194 249 255 45 56 70 53 53 2.0 1.18 71.94 22.663 106.3 88.521

B-1 63.8 01:03:45 766.295 1.20 0.438 0.44 193 249 259 45 56 71 54 54 2.0 1.10 66.55 29.779 110.5 89.878

B-2 82.5 01:22:30 773.450 1.30 0.438 0.44 193 249 256 45 61 71 54 54 2.0 1.14 69.27 35.796 108.2 87.383

B-3 102.0 01:42:00 779.500 1.40 0.438 0.44 191 248 254 45 60 71 56 56 2.0 1.18 71.77 41.363 104.8 84.248

C-1 122.3 02:02:15 785.120 1.50 0.438 0.44 195 250 258 45 56 70 56 56 2.0 1.22 74.52 49.417 106.0 85.897

C-2 143.3 02:23:15 793.250 1.40 0.438 0.44 191 250 250 54 72 75 56 56 2.0 1.18 71.77 56.282 105.6 85.713

C-3 163.5 02:43:30 800.180 1.30 0.438 0.44 189 250 259 58 74 74 57 57 2.0 1.14 69.06 62.402 104.8 84.907

D-1 183.0 03:03:00 806.370 1.60 0.438 0.44 194 250 228 68 78 78 56 56 2.0 1.26 76.91 70.208 104.6 85.485

D-2 204.5 03:24:30 814.250 1.70 0.438 0.44 192 251 253 62 74 74 56 56 2.0 1.30 79.15 77.796 103.5 85.430

D-3 226.8 03:46:45 821.910 1.70 0.438 0.44 192 253 257 63 75 75 55 55 2.0 1.30 79.15 82.516 100.9 82.516

Last Pt 249.0 04:09:00 826.665

Final Val 249.0 04:09:00 826.665 Max Vac 2.0 82.516 100.9

1.45 0.44 193 250 253 51 64 73 55 55 1.20 73.05

Notes:

Wash Volumes

Final Values

Average Values

55

Absolute Meter Pressure

Run Time

Barometric Pressure

Stack Static Pressure

Barometer ID

SAMP-WE-0027

Scale ID

SAMP-SC-0016

Absolute Stack Pressure

Stack Dry Molecular Weight

Estimated Orifice Flow Rate

Orifice Meter Coefficient

P to H Isokinetic Factor

Pressures

Samp-cc-0001

samp-bh-0034

glass

PASS

Leak Checks

Square Root P

Stack Moisture Content

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Equipment

samp-cp-0034

3

120

samp-hp-0144

Project # Run Number Average Stack Temp

Sampling Location Operator Pitot Coefficient / ID

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name Date Ideal Nozzle Diameter and IsoKinetic Factor SetupFilter #

18082925

0818-188

CPV Valley Energy Center

CTG-11 Stack

sie-19-middletown.ny-comp#2

02/08/19

DA

11-PM-Base wDB-1

Average Meter Temp

Nozzle Number

Meter Box Number

Meter Cal Factor

Identification Nos. samp-cp-0034

Nozzle Measurements

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Isocalc - Run (1)

Page 88: Division of Environmental Permits Floor

(Cp) 0.7240 4187/10

(ts) 191.1 °F

(tm) 68.6

(H@) 1.812 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.19 in H₂O

PASS Post 0.000 ft³/min@ 15.0 in Hg (Y) 0.984 (Bws) 8.08 %

Pitot Pre (+) 6.2 in H₂O for 30.0 sec (Md) 29.30 lb/lb-mole

Pre (-) 6.5 in H₂O for 30.0 sec (Dna) 0.1440 in (Qm) 0.33 acfm

Post (+) 5.2 in H₂O for 30.0 sec (Dni) 0.1442 in (K) 0.24

Post (-) 6.2 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 28.59 in Hg

Pre 0.144 0.144 0.144 PASS (Pstatic) -1.20 in H₂O

Post 0.144 0.144 0.144 PASS (Ps) 28.50 in Hg

(Pm) 28.72 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 13:52 End 17:55 Pre 362.3 614.0 655.1 811.3 ml

Post 476.7 615.8 665.5 828.5 ml

samp-cp-0030 samp-cp-0030 samp-cp-0030 samp-hp-0143 samp-hp-0143 samp-bh-0029 1752 1018 3135 samp-cp-0030

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 984.260 1.30 0.438 0.44 194 257 252 65 80 81 56 56 2.0 1.14 63.44 6.492 110.9 76.725

A-2 19.3 00:19:15 991.000 1.40 0.438 0.44 192 253 254 62 80 80 68 68 2.0 1.18 65.74 13.175 108.3 76.368

A-3 39.3 00:39:15 998.100 1.40 0.438 0.44 190 256 246 62 80 80 69 69 2.0 1.18 65.64 19.799 107.0 76.023

B-1 59.3 00:59:15 1005.150 1.40 0.438 0.44 191 253 253 62 69 70 70 70 2.0 1.18 65.69 25.313 105.7 75.278

B-2 76.5 01:16:30 1011.030 1.40 0.438 0.44 191 257 254 57 64 71 71 71 2.0 1.18 65.69 31.079 105.7 75.419

B-3 93.8 01:33:45 1017.190 1.40 0.438 0.44 184 255 252 57 62 70 71 71 2.0 1.18 65.33 36.826 105.6 75.477

C-1 111.0 01:51:00 1023.330 1.40 0.438 0.44 193 250 234 60 64 69 71 71 2.0 1.18 65.79 43.210 105.5 75.472

C-2 130.3 02:10:15 1030.150 1.40 0.438 0.44 192 253 250 56 62 69 71 71 2.0 1.18 65.74 49.799 105.8 75.781

C-3 149.5 02:29:30 1037.190 1.40 0.438 0.44 191 253 228 52 56 70 71 71 2.0 1.18 65.69 56.122 105.6 75.661

D-1 168.8 02:48:45 1043.945 1.50 0.438 0.44 195 229 245 53 56 70 69 69 2.0 1.22 68.20 63.239 106.2 76.323

D-2 188.5 03:08:30 1051.520 1.50 0.438 0.44 193 232 252 60 65 70 68 68 2.0 1.22 68.10 70.280 106.4 76.777

D-3 208.3 03:28:15 1059.000 1.40 0.438 0.44 187 232 247 60 66 72 68 68 2.0 1.18 65.49 77.114 106.9 77.114

Last Pt 227.5 03:47:30 1066.260

Final Val 227.5 03:47:30 1066.260 Max Vac 2.0 77.114 106.9

1.41 0.44 191 248 247 59 67 73 69 69 1.19 65.88

Notes:

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-hp-0143

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

Project # sie-19-middletown.ny-comp#2 Run Number 11-PM-Base wDB-2 0818-188 Average Stack Temp

samp-cp-0030 Square Root PMeter Box Number

Sampling Equipment

Sampling Location CTG-11 Stack Operator DA 18082926

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/08/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0029 Stack Static Pressure

SAMP-SC-0016

Samp-cc-0001 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Run Time

Wash Volumes

Final Values

Average Values

69

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0030

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Isocalc - Run (2)

Page 89: Division of Environmental Permits Floor

(Cp) 0.7240 4187/10

(ts) 197.6 °F

(tm) 62.4

(H@) 1.812 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.20 in H₂O

PASS Post 0.000 ft³/min@ 15.0 in Hg (Y) 0.984 (Bws) 7.78 %

Pitot Pre (+) 6.3 in H₂O for 30.0 sec (Md) 29.30 lb/lb-mole

Pre (-) 5.7 in H₂O for 30.0 sec (Dna) 0.1440 in (Qm) 0.34 acfm

Post (+) 7.1 in H₂O for 30.0 sec (Dni) 0.1477 in (K) 0.24

Post (-) 6.0 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.34 in Hg

Pre 0.144 0.144 0.144 PASS (Pstatic) -1.20 in H₂O

Post 0.144 0.144 0.144 PASS (Ps) 29.25 in Hg

(Pm) 29.47 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 13:48 End 17:50 Pre 363.8 616.6 665.1 827.8 ml

Post 497.8 617.1 664.8 839.5 ml

samp-cp-0030 samp-cp-0030 samp-cp-0030 samp-ho-0143 samp-ho-0143 samp-bh-0034 Samp-cc-0001 1018 3135 samp-cp-0030

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 66.510 1.50 0.438 0.43 202 258 249 36 51 68 60 60 2.0 1.22 67.64 7.238 114.0 86.956

A-2 19.3 00:19:15 73.890 1.50 0.438 0.43 201 254 251 41 47 68 62 62 2.0 1.22 67.59 14.185 111.7 85.205

A-3 38.5 00:38:30 81.000 1.30 0.438 0.43 200 256 248 42 50 68 62 62 2.0 1.14 62.87 20.390 111.8 83.454

B-1 56.5 00:56:30 87.350 1.20 0.438 0.43 199 255 251 40 50 73 62 62 2.0 1.10 60.36 25.803 110.6 80.907

B-2 73.8 01:13:45 92.890 1.50 0.438 0.43 198 255 249 40 50 72 62 62 2.0 1.22 67.44 32.672 110.0 81.240

B-3 93.0 01:33:00 99.920 1.50 0.438 0.43 196 255 249 41 48 75 62 62 2.0 1.22 67.33 39.521 109.6 81.418

C-1 112.3 01:52:15 106.930 1.40 0.438 0.43 197 254 252 39 43 74 62 62 2.0 1.18 65.10 46.526 110.2 81.819

C-2 131.5 02:11:30 114.100 1.60 0.438 0.43 198 255 253 39 48 76 63 63 2.0 1.26 69.65 53.655 109.1 81.630

C-3 152.0 02:32:00 121.410 1.40 0.438 0.43 198 254 251 40 46 76 63 63 2.0 1.18 65.15 60.394 109.1 81.554

D-1 171.3 02:51:15 128.320 1.40 0.438 0.43 190 255 251 39 46 74 63 63 2.0 1.18 64.75 67.132 108.8 81.279

D-2 191.0 03:11:00 135.230 1.50 0.438 0.43 197 255 251 39 41 72 64 64 2.0 1.22 67.38 74.598 108.9 81.564

D-3 211.5 03:31:30 142.900 1.40 0.438 0.43 195 255 250 39 42 72 64 64 2.0 1.18 65.00 81.528 109.0 81.528

Last Pt 231.3 03:51:15 150.020

Final Val 231.3 03:51:15 150.020 Max Vac 2.0 81.528 109.0

1.43 0.43 198 255 250 40 47 72 62 62 1.20 65.86

Notes:

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-ho-0143

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

Project # sie-19-middletown.ny-comp#2 Run Number 11-PM-Base wDB-3 0818-188 Average Stack Temp

samp-cp-0030 Square Root PMeter Box Number

Sampling Equipment

Sampling Location CTG-11 Stack Operator DA 18082928

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/09/18 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0034 Stack Static Pressure

SAMP-SC-0016

Samp-cc-0001 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Run Time

Wash Volumes

Final Values

Average Values

62

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0030

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Isocalc - Run (3)

Page 90: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-11 Base Load wDB

Opacity Data

Page 91: Division of Environmental Permits Floor
Page 92: Division of Environmental Permits Floor
Page 93: Division of Environmental Permits Floor
Page 94: Division of Environmental Permits Floor
Page 95: Division of Environmental Permits Floor
Page 96: Division of Environmental Permits Floor
Page 97: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-12 Base Load

Unit Operating Data

Page 98: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 12 CTG-2 WO/DB Run 1DCS Data - 20190209 - 0850-1740

Unit 12 GT Power Unit 12 GT PowerUnit 12 Total GT

Gas FlowUnit 12 HRSG DB Fuel Flow

Unit 12 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 12HAD00EU001 12MKA01EU902A 12MBP10CF910 12HHA10CF001 12HNE10CQ109 12MBL05CT1012019/02/09 08:57:00:000 224.509 99.5 94.893 0.004 13.50 10.72019/02/09 08:58:00:000 224.509 99.5 94.817 0.004 13.50 10.52019/02/09 08:59:00:000 224.509 99.4 94.764 0.004 13.50 10.22019/02/09 09:00:00:000 224.509 99.4 94.764 0.004 13.50 11.02019/02/09 09:01:00:000 224.509 99.4 94.809 0.004 13.50 11.02019/02/09 09:02:00:000 223.955 99.6 94.713 0.004 13.50 11.22019/02/09 09:03:00:000 224.411 99.5 94.740 0.004 13.50 11.42019/02/09 09:04:00:000 224.450 99.7 94.740 0.004 13.50 11.22019/02/09 09:05:00:000 224.450 99.7 94.841 0.004 13.50 11.42019/02/09 09:06:00:000 224.450 99.4 94.841 0.004 13.50 11.42019/02/09 09:07:00:000 224.450 99.7 94.877 0.004 13.51 11.42019/02/09 09:08:00:000 224.450 99.7 94.877 0.004 13.51 11.72019/02/09 09:09:00:000 224.450 99.6 94.877 0.004 13.51 11.72019/02/09 09:10:00:000 223.753 99.3 94.826 0.004 13.51 11.42019/02/09 09:11:00:000 223.753 99.6 94.540 0.004 13.51 12.32019/02/09 09:12:00:000 223.753 99.7 94.621 0.004 13.51 12.32019/02/09 09:13:00:000 224.311 99.6 94.783 0.004 13.51 12.12019/02/09 09:14:00:000 224.311 99.6 94.783 0.004 13.51 11.92019/02/09 09:15:00:000 223.913 99.4 94.711 0.004 13.51 11.72019/02/09 09:16:00:000 223.913 99.7 94.752 0.004 13.49 11.92019/02/09 09:17:00:000 223.913 99.6 94.584 0.004 20.94 12.12019/02/09 09:18:00:000 223.913 99.6 94.584 0.004 21.00 12.12019/02/09 09:19:00:000 223.913 99.7 94.647 0.004 0.71 12.52019/02/09 09:20:00:000 223.913 99.6 94.789 0.004 0.00 12.52019/02/09 09:21:00:000 224.181 99.7 94.647 0.004 0.00 12.12019/02/09 09:22:00:000 224.181 99.8 94.803 0.004 13.36 12.12019/02/09 09:23:00:000 224.565 99.7 94.803 0.004 13.47 12.12019/02/09 09:24:00:000 224.565 99.7 94.895 0.004 13.47 11.92019/02/09 09:25:00:000 224.565 99.6 94.857 0.004 13.49 11.92019/02/09 09:26:00:000 223.880 99.5 94.591 0.004 13.49 12.12019/02/09 09:27:00:000 223.880 99.8 94.591 0.004 13.49 13.02019/02/09 09:28:00:000 224.455 99.8 94.737 0.004 13.49 13.02019/02/09 09:29:00:000 224.455 99.6 94.808 0.004 13.52 13.02019/02/09 09:30:00:000 223.837 99.5 94.701 0.004 13.52 12.82019/02/09 09:31:00:000 223.837 99.7 94.547 0.004 13.49 12.82019/02/09 09:32:00:000 224.280 99.8 94.833 0.004 13.49 13.02019/02/09 09:33:00:000 224.280 99.7 94.683 0.004 13.50 12.82019/02/09 09:34:00:000 224.280 99.7 94.692 0.004 13.50 12.52019/02/09 09:35:00:000 224.280 99.7 94.692 0.004 13.50 12.32019/02/09 09:36:00:000 223.814 99.7 94.692 0.004 13.50 12.32019/02/09 09:37:00:000 222.968 99.7 94.464 0.004 13.50 13.32019/02/09 09:38:00:000 223.559 99.7 94.464 0.004 13.50 13.32019/02/09 09:39:00:000 223.559 99.9 94.717 0.004 13.50 13.32019/02/09 09:40:00:000 223.393 99.6 94.528 0.004 13.51 13.32019/02/09 09:41:00:000 223.393 99.7 94.562 0.004 13.51 13.52019/02/09 09:42:00:000 223.594 99.7 94.508 0.004 13.51 13.52019/02/09 09:43:00:000 223.594 99.7 94.508 0.004 13.51 13.52019/02/09 09:44:00:000 223.594 99.7 94.508 0.004 13.51 13.52019/02/09 09:45:00:000 223.594 99.8 94.597 0.004 13.51 13.82019/02/09 09:46:00:000 223.594 99.8 94.597 0.004 13.51 13.32019/02/09 09:47:00:000 223.944 99.8 94.597 0.004 13.51 13.32019/02/09 09:48:00:000 223.944 99.7 94.597 0.004 13.51 13.32019/02/09 09:49:00:000 223.542 99.5 94.573 0.004 13.51 13.52019/02/09 09:50:00:000 223.542 99.8 94.478 0.004 13.51 13.82019/02/09 09:51:00:000 224.197 99.9 94.696 0.004 13.51 14.02019/02/09 09:52:00:000 224.197 99.7 94.696 0.004 13.51 13.52019/02/09 09:53:00:000 223.882 99.7 94.565 0.004 13.51 13.52019/02/09 09:54:00:000 223.882 99.7 94.682 0.004 13.51 13.52019/02/09 09:55:00:000 224.394 99.7 94.682 0.004 13.51 13.32019/02/09 09:56:00:000 223.887 99.7 94.682 0.004 13.51 13.02019/02/09 09:57:00:000 223.887 99.7 94.682 0.004 13.51 12.82019/02/09 09:58:00:000 223.887 99.7 94.397 0.004 13.51 12.82019/02/09 09:59:00:000 223.575 99.7 94.484 0.004 13.51 13.52019/02/09 10:00:00:000 222.933 99.6 94.214 0.004 13.51 14.02019/02/09 10:01:00:000 222.933 99.7 94.385 0.004 13.51 14.42019/02/09 10:02:00:000 222.933 99.8 94.279 0.004 13.50 14.42019/02/09 10:03:00:000 223.324 99.9 94.279 0.004 13.50 14.42019/02/09 10:04:00:000 223.324 99.7 94.502 0.004 13.50 14.22019/02/09 10:05:00:000 223.692 99.8 94.576 0.004 13.52 14.02019/02/09 10:06:00:000 223.692 99.8 94.514 0.004 13.52 14.02019/02/09 10:07:00:000 223.692 99.6 94.592 0.004 13.52 13.3

Page 99: Division of Environmental Permits Floor

2019/02/09 10:08:00:000 223.349 99.7 94.335 0.004 13.52 13.32019/02/09 10:09:00:000 223.349 99.8 94.461 0.004 13.52 13.32019/02/09 10:10:00:000 223.349 99.6 94.509 0.004 13.52 13.32019/02/09 10:11:00:000 223.349 99.8 94.476 0.004 13.50 13.32019/02/09 10:12:00:000 223.349 99.9 94.435 0.004 13.50 13.52019/02/09 10:13:00:000 223.549 99.8 94.520 0.004 13.50 13.82019/02/09 10:14:00:000 223.549 99.6 94.520 0.004 13.50 14.02019/02/09 10:15:00:000 222.834 99.8 94.434 0.004 13.50 14.72019/02/09 10:16:00:000 223.369 99.8 94.582 0.004 13.52 14.72019/02/09 10:17:00:000 223.590 99.7 94.466 0.004 13.52 14.52019/02/09 10:18:00:000 223.590 99.9 94.466 0.004 13.52 14.22019/02/09 10:19:00:000 223.590 99.7 94.559 0.004 13.52 14.02019/02/09 10:20:00:000 223.590 99.9 94.570 0.004 13.49 13.82019/02/09 10:21:00:000 223.590 99.8 94.474 0.004 13.49 14.02019/02/09 10:22:00:000 223.590 99.9 94.474 0.004 13.51 14.22019/02/09 10:23:00:000 223.590 99.5 94.474 0.004 13.51 14.52019/02/09 10:24:00:000 222.685 99.6 94.033 0.004 13.51 15.42019/02/09 10:25:00:000 222.685 99.9 94.344 0.004 13.51 15.42019/02/09 10:26:00:000 223.537 100.0 94.486 0.004 13.51 15.12019/02/09 10:27:00:000 223.537 99.8 94.486 0.004 13.51 15.12019/02/09 10:28:00:000 223.092 99.8 94.256 0.004 13.51 15.42019/02/09 10:29:00:000 223.092 99.9 94.347 0.004 13.51 15.42019/02/09 10:30:00:000 223.092 99.8 94.347 0.004 13.51 15.62019/02/09 10:31:00:000 223.092 99.7 94.347 0.004 13.51 15.62019/02/09 10:32:00:000 223.092 99.7 94.220 0.004 13.51 15.42019/02/09 10:33:00:000 223.092 99.8 94.301 0.004 13.51 15.42019/02/09 10:34:00:000 222.904 99.8 94.031 0.004 13.51 15.42019/02/09 10:35:00:000 222.904 99.9 94.400 0.004 13.51 15.62019/02/09 10:36:00:000 222.904 99.8 94.099 0.004 13.51 15.62019/02/09 10:37:00:000 221.990 99.6 94.047 0.004 13.51 16.12019/02/09 10:38:00:000 222.653 100.0 94.240 0.004 13.51 16.12019/02/09 10:39:00:000 222.653 99.8 94.240 0.004 13.51 16.32019/02/09 10:40:00:000 222.653 99.8 94.098 0.004 13.51 16.32019/02/09 10:41:00:000 221.616 99.6 93.809 0.004 13.51 17.42019/02/09 10:42:00:000 222.438 100.0 93.990 0.004 13.51 18.22019/02/09 10:43:00:000 222.438 100.1 94.159 0.004 13.52 17.72019/02/09 10:44:00:000 222.911 99.8 94.159 0.004 13.52 17.02019/02/09 10:45:00:000 222.257 99.8 94.097 0.004 13.52 17.02019/02/09 10:46:00:000 222.257 99.7 93.779 0.004 13.52 17.22019/02/09 10:47:00:000 221.007 99.8 93.779 0.004 13.52 18.22019/02/09 10:48:00:000 222.468 100.1 94.158 0.004 13.52 18.22019/02/09 10:49:00:000 221.897 100.0 93.817 0.004 13.52 17.92019/02/09 10:50:00:000 222.273 100.1 94.080 0.004 13.52 17.72019/02/09 10:51:00:000 222.799 99.9 94.313 0.004 13.52 17.02019/02/09 10:52:00:000 222.799 99.7 94.151 0.004 13.52 16.32019/02/09 10:53:00:000 222.799 99.9 94.216 0.004 13.52 15.82019/02/09 10:54:00:000 223.112 99.9 94.425 0.004 13.52 15.12019/02/09 10:55:00:000 223.686 99.8 94.425 0.004 13.52 15.12019/02/09 10:56:00:000 223.282 99.7 94.425 0.004 13.51 14.92019/02/09 10:57:00:000 223.282 99.8 94.425 0.004 13.51 14.72019/02/09 10:58:00:000 223.282 99.8 94.425 0.004 13.51 14.72019/02/09 10:59:00:000 223.282 99.8 94.400 0.004 13.51 14.42019/02/09 11:00:00:000 223.534 99.8 94.573 0.004 13.51 14.42019/02/09 11:01:00:000 223.534 99.8 94.344 0.004 13.51 14.42019/02/09 11:02:00:000 223.288 99.9 94.435 0.004 13.51 14.72019/02/09 11:03:00:000 223.801 100.0 94.415 0.004 13.51 14.72019/02/09 11:04:00:000 223.801 99.8 94.522 0.004 13.52 14.72019/02/09 11:05:00:000 223.131 99.8 94.356 0.004 13.52 14.72019/02/09 11:06:00:000 223.131 99.8 94.356 0.004 13.50 14.92019/02/09 11:07:00:000 223.131 99.7 94.132 0.004 13.50 15.12019/02/09 11:08:00:000 223.131 100.0 94.410 0.004 13.50 15.42019/02/09 11:09:00:000 223.545 99.9 94.410 0.004 13.52 15.82019/02/09 11:10:00:000 223.545 99.9 94.410 0.004 13.52 15.42019/02/09 11:11:00:000 223.084 99.9 94.410 0.004 13.52 15.42019/02/09 11:12:00:000 223.754 100.0 94.410 0.004 13.50 15.12019/02/09 11:13:00:000 223.131 99.8 94.394 0.004 13.50 14.92019/02/09 11:14:00:000 223.131 99.8 94.394 0.004 13.50 14.92019/02/09 11:15:00:000 223.131 99.9 94.202 0.004 13.50 15.12019/02/09 11:16:00:000 223.131 99.9 94.418 0.004 13.52 14.92019/02/09 11:17:00:000 223.131 100.0 94.301 0.004 13.52 15.42019/02/09 11:18:00:000 223.764 100.1 94.419 0.004 13.52 15.42019/02/09 11:19:00:000 223.041 99.9 94.419 0.004 13.52 15.12019/02/09 11:20:00:000 223.041 99.8 94.147 0.004 13.50 15.12019/02/09 11:21:00:000 222.548 99.9 94.147 0.004 13.50 16.12019/02/09 11:22:00:000 222.548 99.9 94.147 0.004 13.50 16.62019/02/09 11:23:00:000 222.548 100.0 94.061 0.004 13.50 16.62019/02/09 11:24:00:000 223.307 100.1 94.420 0.004 13.53 16.12019/02/09 11:25:00:000 222.509 99.6 94.184 0.004 13.53 16.12019/02/09 11:26:00:000 222.075 99.9 93.981 0.004 13.50 16.32019/02/09 11:27:00:000 222.682 100.1 94.087 0.004 13.50 16.32019/02/09 11:28:00:000 222.682 99.8 94.207 0.004 13.51 16.1

Page 100: Division of Environmental Permits Floor

2019/02/09 11:29:00:000 222.682 99.9 93.890 0.004 13.51 16.32019/02/09 11:30:00:000 222.682 100.2 94.335 0.004 13.51 16.32019/02/09 11:31:00:000 223.514 100.1 94.335 0.004 13.51 16.32019/02/09 11:32:00:000 223.514 99.9 94.384 0.004 13.51 16.12019/02/09 11:33:00:000 223.258 99.8 94.384 0.004 13.53 15.82019/02/09 11:34:00:000 223.258 99.8 94.329 0.004 13.53 15.62019/02/09 11:35:00:000 223.258 99.9 94.329 0.004 13.50 15.62019/02/09 11:36:00:000 223.258 100.0 94.329 0.004 13.50 15.82019/02/09 11:37:00:000 223.258 99.8 94.273 0.004 13.50 15.62019/02/09 11:38:00:000 222.603 99.8 94.273 0.004 13.51 15.62019/02/09 11:39:00:000 222.225 99.9 94.048 0.004 13.51 16.62019/02/09 11:40:00:000 222.806 100.0 94.220 0.004 13.51 16.62019/02/09 11:41:00:000 222.806 99.9 94.242 0.004 13.51 16.82019/02/09 11:42:00:000 222.051 100.0 93.919 0.004 13.51 16.82019/02/09 11:43:00:000 222.051 100.1 93.919 0.004 13.51 17.02019/02/09 11:44:00:000 222.472 100.1 94.158 0.004 13.51 17.02019/02/09 11:45:00:000 222.472 100.0 94.097 0.004 13.51 17.22019/02/09 11:46:00:000 222.472 100.1 94.097 0.004 13.52 17.22019/02/09 11:47:00:000 223.001 100.0 94.179 0.004 13.52 17.02019/02/09 11:48:00:000 222.638 99.7 94.179 0.004 13.52 16.82019/02/09 11:49:00:000 221.974 99.9 93.992 0.004 13.52 17.72019/02/09 11:50:00:000 222.678 100.2 94.179 0.004 13.52 17.72019/02/09 11:51:00:000 222.678 100.2 94.179 0.004 13.52 17.42019/02/09 11:52:00:000 223.068 100.0 94.325 0.004 13.52 17.42019/02/09 11:53:00:000 223.068 100.0 94.325 0.004 13.52 16.82019/02/09 11:54:00:000 223.068 100.0 94.159 0.004 13.52 16.82019/02/09 11:55:00:000 223.068 100.0 94.298 0.004 13.52 16.12019/02/09 11:56:00:000 223.068 99.7 94.298 0.004 13.52 16.12019/02/09 11:57:00:000 223.068 99.8 94.163 0.004 13.51 15.82019/02/09 11:58:00:000 222.684 100.0 94.163 0.004 13.51 16.12019/02/09 11:59:00:000 222.684 99.8 94.163 0.004 13.51 16.32019/02/09 12:00:00:000 222.684 100.1 94.163 0.004 13.51 16.32019/02/09 12:01:00:000 223.322 100.1 94.330 0.004 13.51 16.32019/02/09 12:02:00:000 223.322 99.9 94.330 0.004 13.51 16.12019/02/09 12:03:00:000 222.586 99.9 94.106 0.004 13.51 16.12019/02/09 12:04:00:000 222.586 100.0 94.106 0.004 13.51 17.02019/02/09 12:05:00:000 222.586 99.9 94.106 0.004 13.51 17.42019/02/09 12:06:00:000 222.548 100.1 93.963 0.004 13.51 17.42019/02/09 12:07:00:000 222.548 100.1 94.158 0.004 13.51 17.72019/02/09 12:08:00:000 222.914 100.0 94.301 0.004 13.51 17.42019/02/09 12:09:00:000 222.914 99.9 94.237 0.004 13.51 17.22019/02/09 12:10:00:000 222.531 100.0 94.208 0.004 13.51 17.02019/02/09 12:11:00:000 222.531 100.0 94.049 0.004 13.51 17.02019/02/09 12:12:00:000 222.655 99.9 94.009 0.004 13.51 17.02019/02/09 12:13:00:000 222.655 99.9 94.092 0.004 13.51 17.02019/02/09 12:14:00:000 221.828 99.9 93.964 0.004 13.51 17.72019/02/09 12:15:00:000 221.828 100.0 93.796 0.004 13.51 18.42019/02/09 12:16:00:000 221.148 99.8 93.796 0.004 13.51 19.42019/02/09 12:17:00:000 221.802 100.2 93.681 0.004 13.51 19.82019/02/09 12:18:00:000 221.802 100.1 93.860 0.004 13.53 19.42019/02/09 12:19:00:000 221.802 99.8 93.860 0.004 13.53 19.42019/02/09 12:20:00:000 221.802 100.0 93.860 0.004 13.53 19.42019/02/09 12:21:00:000 222.177 100.0 93.860 0.004 13.52 19.12019/02/09 12:22:00:000 222.177 99.9 93.897 0.004 13.52 18.92019/02/09 12:23:00:000 222.390 100.1 94.120 0.004 13.52 18.62019/02/09 12:24:00:000 222.390 100.0 93.965 0.004 13.52 17.92019/02/09 12:25:00:000 222.390 100.0 94.051 0.004 13.52 17.92019/02/09 12:26:00:000 222.390 99.9 94.051 0.004 13.52 17.72019/02/09 12:27:00:000 222.390 99.9 93.852 0.004 13.52 17.42019/02/09 12:28:00:000 222.390 99.7 93.810 0.004 13.52 17.72019/02/09 12:29:00:000 221.827 99.9 93.810 0.004 13.52 18.42019/02/09 12:30:00:000 221.827 100.1 93.904 0.004 13.52 18.42019/02/09 12:31:00:000 222.345 99.9 93.943 0.004 13.52 18.42019/02/09 12:32:00:000 222.345 100.0 93.943 0.004 13.52 18.22019/02/09 12:33:00:000 222.345 100.0 94.015 0.004 13.52 17.92019/02/09 12:34:00:000 221.878 100.0 93.845 0.004 13.52 17.72019/02/09 12:35:00:000 221.878 100.0 94.118 0.004 13.52 17.72019/02/09 12:36:00:000 222.259 99.9 94.118 0.004 13.52 17.92019/02/09 12:37:00:000 222.259 99.8 93.965 0.004 13.52 17.92019/02/09 12:38:00:000 221.704 100.0 93.758 0.004 13.52 18.22019/02/09 12:39:00:000 221.994 99.9 93.690 0.004 13.52 18.62019/02/09 12:40:00:000 221.014 99.9 93.416 0.004 13.52 19.42019/02/09 12:41:00:000 221.014 100.2 93.552 0.004 13.51 19.82019/02/09 12:42:00:000 221.364 100.2 93.788 0.004 13.51 19.82019/02/09 12:43:00:000 221.988 100.0 93.788 0.004 13.51 19.62019/02/09 12:44:00:000 221.697 100.1 93.788 0.004 13.52 19.32019/02/09 12:45:00:000 221.697 100.2 93.940 0.004 13.52 19.62019/02/09 12:46:00:000 222.038 100.1 93.870 0.004 13.52 19.62019/02/09 12:47:00:000 222.038 99.9 93.818 0.004 13.52 19.12019/02/09 12:48:00:000 222.038 100.1 93.958 0.004 13.52 19.12019/02/09 12:49:00:000 222.038 100.0 93.978 0.004 13.52 18.9

Page 101: Division of Environmental Permits Floor

2019/02/09 12:50:00:000 222.038 99.9 93.853 0.004 13.52 18.62019/02/09 12:51:00:000 222.038 99.9 93.916 0.004 13.52 18.62019/02/09 12:52:00:000 222.038 100.0 93.916 0.004 13.52 18.42019/02/09 12:53:00:000 222.038 100.0 94.040 0.004 13.52 18.22019/02/09 12:54:00:000 222.419 100.0 94.040 0.004 13.52 17.92019/02/09 12:55:00:000 221.962 100.0 93.857 0.004 13.52 17.92019/02/09 12:56:00:000 221.962 100.0 93.993 0.004 13.52 18.22019/02/09 12:57:00:000 221.962 100.0 93.848 0.004 13.52 18.42019/02/09 12:58:00:000 221.962 99.8 93.859 0.004 13.51 18.42019/02/09 12:59:00:000 221.147 100.0 93.563 0.004 13.51 19.12019/02/09 13:00:00:000 221.761 100.1 93.852 0.004 13.51 19.12019/02/09 13:01:00:000 222.007 100.0 94.020 0.004 13.51 19.12019/02/09 13:02:00:000 222.007 99.9 93.876 0.004 13.53 18.92019/02/09 13:03:00:000 221.502 99.9 93.876 0.004 13.53 18.92019/02/09 13:04:00:000 221.502 99.9 93.876 0.004 13.53 18.92019/02/09 13:05:00:000 221.935 100.0 93.751 0.004 13.51 18.92019/02/09 13:06:00:000 221.472 99.9 93.751 0.004 13.51 19.12019/02/09 13:07:00:000 221.472 100.0 93.730 0.004 13.51 19.12019/02/09 13:08:00:000 221.472 100.0 93.918 0.004 13.53 18.92019/02/09 13:09:00:000 221.813 100.0 93.998 0.004 13.53 18.62019/02/09 13:10:00:000 221.813 100.1 93.737 0.004 13.53 18.6AVERAGE: 222.99 99.85 94.28 0.00 13.41 15.59

Page 102: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 12 CTG-2 WO/DB Run 2DCS Data - 20190210 - 0815-1700

Unit 12 GT Power Unit 12 GT PowerUnit 12 Total GT

Gas FlowUnit 12 HRSG DB Fuel Flow

Unit 12 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 12HAD00EU001 12MKA01EU902A 12MBP10CF910 12HHA10CF001 12HNE10CQ109 12MBL05CT1012019/02/10 08:22:00:000 226.799 100.2 95.305 0.004 13.47 10.52019/02/10 08:23:00:000 226.799 100.2 95.507 0.004 13.47 10.52019/02/10 08:24:00:000 226.292 100.1 95.349 0.004 13.48 10.52019/02/10 08:25:00:000 226.292 100.3 95.301 0.004 13.48 10.52019/02/10 08:26:00:000 226.521 100.1 95.340 0.004 13.48 10.72019/02/10 08:27:00:000 226.521 100.2 95.583 0.004 13.48 10.72019/02/10 08:28:00:000 226.521 100.1 95.489 0.004 13.48 10.72019/02/10 08:29:00:000 226.521 100.2 95.489 0.004 13.48 10.72019/02/10 08:30:00:000 226.749 100.0 95.489 0.004 13.48 11.02019/02/10 08:31:00:000 226.355 100.0 95.240 0.004 13.48 11.42019/02/10 08:32:00:000 226.355 100.3 95.371 0.004 13.48 11.42019/02/10 08:33:00:000 226.355 100.2 95.459 0.004 13.48 11.72019/02/10 08:34:00:000 226.099 100.1 95.285 0.004 13.48 12.12019/02/10 08:35:00:000 226.099 100.2 95.285 0.004 13.48 12.12019/02/10 08:36:00:000 226.099 100.2 95.423 0.004 13.48 12.12019/02/10 08:37:00:000 226.099 100.2 95.171 0.004 13.48 12.12019/02/10 08:38:00:000 226.099 100.2 95.168 0.004 13.48 11.92019/02/10 08:39:00:000 226.099 100.2 95.379 0.004 13.48 11.92019/02/10 08:40:00:000 226.099 100.0 95.256 0.004 13.48 11.92019/02/10 08:41:00:000 226.099 100.1 95.256 0.004 13.48 11.92019/02/10 08:42:00:000 226.567 100.3 95.442 0.004 13.48 11.72019/02/10 08:43:00:000 226.567 100.1 95.442 0.004 13.48 11.42019/02/10 08:44:00:000 226.135 100.1 95.287 0.004 13.48 11.22019/02/10 08:45:00:000 226.135 100.1 95.418 0.004 13.48 11.02019/02/10 08:46:00:000 226.371 100.1 95.283 0.004 13.48 11.02019/02/10 08:47:00:000 226.193 100.1 95.466 0.004 13.48 11.02019/02/10 08:48:00:000 226.193 100.2 95.166 0.004 13.48 11.02019/02/10 08:49:00:000 226.193 100.2 95.318 0.004 13.49 11.02019/02/10 08:50:00:000 226.193 100.1 95.394 0.004 13.49 11.22019/02/10 08:51:00:000 226.193 100.0 95.286 0.004 13.49 11.42019/02/10 08:52:00:000 225.922 100.1 95.286 0.004 13.49 11.42019/02/10 08:53:00:000 225.922 100.2 95.286 0.004 13.49 11.92019/02/10 08:54:00:000 226.128 100.1 95.286 0.004 13.48 11.92019/02/10 08:55:00:000 226.128 100.1 95.214 0.004 13.48 12.12019/02/10 08:56:00:000 226.128 100.0 95.125 0.004 13.48 12.32019/02/10 08:57:00:000 225.717 100.2 95.264 0.004 13.48 12.52019/02/10 08:58:00:000 225.717 100.1 95.264 0.004 13.48 12.82019/02/10 08:59:00:000 225.717 100.2 95.011 0.004 13.48 13.02019/02/10 09:00:00:000 225.717 100.1 95.222 0.004 13.48 13.02019/02/10 09:01:00:000 225.717 100.2 95.128 0.004 13.48 12.82019/02/10 09:02:00:000 225.717 100.1 95.128 0.004 13.51 12.82019/02/10 09:03:00:000 225.497 100.2 94.996 0.004 13.51 12.82019/02/10 09:04:00:000 225.497 100.2 95.153 0.004 13.49 12.82019/02/10 09:05:00:000 225.497 100.2 95.153 0.004 13.49 12.52019/02/10 09:06:00:000 225.726 100.2 95.153 0.004 13.49 12.52019/02/10 09:07:00:000 225.726 100.1 95.145 0.004 13.49 12.52019/02/10 09:08:00:000 225.726 100.1 95.145 0.004 13.49 12.82019/02/10 09:09:00:000 225.495 100.1 95.145 0.004 13.49 12.82019/02/10 09:10:00:000 225.495 100.0 94.993 0.004 13.49 12.82019/02/10 09:11:00:000 225.495 100.1 94.966 0.004 13.49 12.52019/02/10 09:12:00:000 225.495 100.3 95.214 0.004 13.49 12.52019/02/10 09:13:00:000 225.495 100.0 95.069 0.004 13.49 12.52019/02/10 09:14:00:000 225.495 100.2 95.131 0.004 13.49 12.82019/02/10 09:15:00:000 225.495 100.0 95.131 0.004 13.49 12.82019/02/10 09:16:00:000 225.495 100.0 94.914 0.004 13.49 12.82019/02/10 09:17:00:000 225.260 100.2 95.184 0.004 20.95 12.82019/02/10 09:18:00:000 225.260 100.2 95.029 0.004 21.01 12.82019/02/10 09:19:00:000 225.368 100.1 95.119 0.004 0.49 12.82019/02/10 09:20:00:000 225.368 100.1 95.110 0.004 0.00 12.82019/02/10 09:21:00:000 225.368 100.0 94.926 0.004 0.00 12.82019/02/10 09:22:00:000 225.368 100.1 94.926 0.004 13.35 12.52019/02/10 09:23:00:000 225.124 100.1 94.976 0.004 13.44 12.82019/02/10 09:24:00:000 225.570 100.2 94.976 0.004 13.48 13.02019/02/10 09:25:00:000 225.570 100.1 95.116 0.004 13.48 13.32019/02/10 09:26:00:000 225.570 99.9 94.865 0.004 13.48 13.32019/02/10 09:27:00:000 225.258 100.1 94.989 0.004 13.48 13.02019/02/10 09:28:00:000 225.258 100.1 94.892 0.004 13.48 12.82019/02/10 09:29:00:000 225.258 100.1 95.161 0.004 13.48 13.52019/02/10 09:30:00:000 224.816 100.0 94.888 0.004 13.50 13.52019/02/10 09:31:00:000 224.816 100.1 94.888 0.004 13.50 13.52019/02/10 09:32:00:000 224.816 100.1 94.714 0.004 13.50 13.8

Page 103: Division of Environmental Permits Floor

2019/02/10 09:33:00:000 224.816 100.0 94.855 0.004 13.50 14.22019/02/10 09:34:00:000 224.816 100.1 94.722 0.004 13.49 14.52019/02/10 09:35:00:000 224.596 100.1 94.790 0.004 13.49 14.72019/02/10 09:36:00:000 224.596 100.1 94.790 0.004 13.49 14.72019/02/10 09:37:00:000 225.119 100.2 94.975 0.004 13.49 14.72019/02/10 09:38:00:000 225.119 100.1 94.912 0.004 13.49 13.82019/02/10 09:39:00:000 225.119 99.9 94.912 0.004 13.50 13.82019/02/10 09:40:00:000 224.596 100.0 94.830 0.004 13.50 13.82019/02/10 09:41:00:000 224.596 100.1 94.830 0.004 13.50 14.72019/02/10 09:42:00:000 224.998 100.1 94.830 0.004 13.49 14.72019/02/10 09:43:00:000 224.998 100.0 94.961 0.004 13.49 14.72019/02/10 09:44:00:000 224.390 99.8 94.780 0.004 13.49 14.42019/02/10 09:45:00:000 224.390 99.9 94.597 0.004 13.49 14.22019/02/10 09:46:00:000 224.089 100.4 94.770 0.004 13.49 14.22019/02/10 09:47:00:000 224.966 100.2 94.880 0.004 13.49 14.92019/02/10 09:48:00:000 224.393 99.9 94.689 0.004 13.49 14.92019/02/10 09:49:00:000 223.705 100.0 94.419 0.004 13.50 14.92019/02/10 09:50:00:000 224.489 100.2 94.878 0.004 13.50 14.72019/02/10 09:51:00:000 224.489 100.2 94.720 0.004 13.50 14.72019/02/10 09:52:00:000 224.937 100.0 94.833 0.004 13.50 14.72019/02/10 09:53:00:000 224.421 100.1 94.677 0.004 13.50 14.72019/02/10 09:54:00:000 224.421 100.1 94.735 0.004 13.50 14.92019/02/10 09:55:00:000 224.421 100.0 94.735 0.004 13.50 15.62019/02/10 09:56:00:000 224.421 100.0 94.735 0.004 13.50 15.62019/02/10 09:57:00:000 224.421 99.9 94.633 0.004 13.50 15.82019/02/10 09:58:00:000 223.848 100.0 94.553 0.004 13.50 15.62019/02/10 09:59:00:000 223.848 100.1 94.553 0.004 13.50 15.42019/02/10 10:00:00:000 223.848 100.1 94.553 0.004 13.50 15.12019/02/10 10:01:00:000 223.848 100.0 94.498 0.004 13.50 15.12019/02/10 10:02:00:000 223.848 100.3 94.675 0.004 13.50 15.42019/02/10 10:03:00:000 223.848 99.9 94.604 0.004 13.50 15.62019/02/10 10:04:00:000 224.106 100.1 94.335 0.004 13.50 15.62019/02/10 10:05:00:000 224.106 100.1 94.545 0.004 13.50 16.62019/02/10 10:06:00:000 223.754 100.0 94.451 0.004 13.50 17.22019/02/10 10:07:00:000 223.754 100.2 94.451 0.004 13.50 17.22019/02/10 10:08:00:000 223.754 100.1 94.451 0.004 13.50 17.42019/02/10 10:09:00:000 223.311 100.1 94.451 0.004 13.50 17.42019/02/10 10:10:00:000 223.638 100.2 94.451 0.004 13.50 17.42019/02/10 10:11:00:000 223.638 100.1 94.451 0.004 13.50 17.42019/02/10 10:12:00:000 223.638 100.2 94.582 0.004 13.51 17.42019/02/10 10:13:00:000 223.943 100.2 94.477 0.004 13.51 17.42019/02/10 10:14:00:000 223.943 100.1 94.653 0.004 13.51 16.62019/02/10 10:15:00:000 223.943 100.0 94.537 0.004 13.51 15.82019/02/10 10:16:00:000 223.262 99.9 94.396 0.004 13.51 15.82019/02/10 10:17:00:000 223.262 100.0 94.180 0.004 13.51 16.32019/02/10 10:18:00:000 223.262 100.1 94.318 0.004 13.51 17.02019/02/10 10:19:00:000 223.549 100.0 94.421 0.004 13.51 17.02019/02/10 10:20:00:000 223.549 100.2 94.421 0.003 13.51 17.22019/02/10 10:21:00:000 223.549 100.1 94.421 0.003 13.51 17.42019/02/10 10:22:00:000 223.549 100.0 94.421 0.003 13.51 17.42019/02/10 10:23:00:000 223.549 100.1 94.421 0.003 13.51 17.22019/02/10 10:24:00:000 223.549 100.0 94.421 0.003 13.51 17.02019/02/10 10:25:00:000 223.549 100.0 94.266 0.003 13.51 17.42019/02/10 10:26:00:000 222.601 99.8 94.088 0.003 13.49 17.92019/02/10 10:27:00:000 222.601 100.1 93.986 0.003 13.49 17.92019/02/10 10:28:00:000 222.601 100.0 94.283 0.003 13.52 17.42019/02/10 10:29:00:000 223.111 99.9 94.074 0.003 13.52 17.42019/02/10 10:30:00:000 222.987 100.0 94.293 0.003 13.52 17.22019/02/10 10:31:00:000 222.282 99.7 93.872 0.003 13.52 17.02019/02/10 10:32:00:000 221.850 99.9 93.872 0.003 13.52 17.42019/02/10 10:33:00:000 221.396 100.1 93.804 0.003 13.51 18.42019/02/10 10:34:00:000 222.419 100.3 93.924 0.003 13.51 18.92019/02/10 10:35:00:000 222.419 100.3 94.171 0.003 13.51 19.42019/02/10 10:36:00:000 222.830 100.2 94.171 0.003 13.51 19.42019/02/10 10:37:00:000 222.830 100.1 94.171 0.003 13.52 19.62019/02/10 10:38:00:000 222.830 99.9 93.897 0.003 13.52 19.62019/02/10 10:39:00:000 222.369 100.0 94.086 0.003 13.52 19.42019/02/10 10:40:00:000 222.369 100.0 94.086 0.003 13.52 19.42019/02/10 10:41:00:000 221.532 99.9 93.897 0.003 13.52 19.42019/02/10 10:42:00:000 222.033 100.1 93.943 0.003 13.51 19.62019/02/10 10:43:00:000 222.033 100.0 93.943 0.003 13.51 19.62019/02/10 10:44:00:000 222.033 100.0 93.838 0.003 13.51 19.62019/02/10 10:45:00:000 222.033 99.9 93.741 0.003 13.51 19.42019/02/10 10:46:00:000 221.356 99.8 93.743 0.003 13.51 19.82019/02/10 10:47:00:000 221.356 100.1 93.634 0.003 13.51 20.72019/02/10 10:48:00:000 221.315 100.1 93.763 0.003 13.51 20.72019/02/10 10:49:00:000 221.315 99.9 93.763 0.003 13.52 20.72019/02/10 10:50:00:000 221.315 99.9 93.740 0.003 13.52 20.72019/02/10 10:51:00:000 221.315 100.1 93.555 0.003 13.52 20.52019/02/10 10:52:00:000 221.967 100.2 93.830 0.003 13.52 20.22019/02/10 10:53:00:000 221.967 100.1 93.943 0.003 13.52 20.2

Page 104: Division of Environmental Permits Floor

2019/02/10 10:54:00:000 221.967 100.0 93.923 0.003 13.52 19.82019/02/10 10:55:00:000 221.967 100.1 93.923 0.003 13.52 20.02019/02/10 10:56:00:000 222.637 100.2 94.069 0.003 13.52 20.02019/02/10 10:57:00:000 222.637 100.0 94.069 0.003 13.52 19.42019/02/10 10:58:00:000 222.002 100.0 94.069 0.003 13.52 19.42019/02/10 10:59:00:000 222.002 100.1 93.968 0.003 13.52 19.62019/02/10 11:00:00:000 222.002 100.0 93.899 0.003 13.52 19.82019/02/10 11:01:00:000 221.231 99.9 93.675 0.003 13.52 20.02019/02/10 11:02:00:000 221.798 100.1 93.852 0.003 13.52 20.02019/02/10 11:03:00:000 222.215 100.1 94.002 0.003 13.52 19.42019/02/10 11:04:00:000 222.215 100.1 94.002 0.003 13.52 19.42019/02/10 11:05:00:000 221.954 100.0 93.778 0.003 13.52 19.12019/02/10 11:06:00:000 221.954 100.0 93.797 0.003 13.52 19.82019/02/10 11:07:00:000 221.839 100.0 93.797 0.003 13.51 20.22019/02/10 11:08:00:000 221.839 100.0 93.976 0.003 13.51 20.22019/02/10 11:09:00:000 221.291 99.8 93.490 0.003 13.51 20.22019/02/10 11:10:00:000 221.291 100.2 93.827 0.003 13.51 20.22019/02/10 11:11:00:000 221.908 99.9 93.827 0.003 13.53 19.52019/02/10 11:12:00:000 221.051 99.7 93.449 0.003 13.53 19.52019/02/10 11:13:00:000 220.674 100.0 93.449 0.003 13.52 20.52019/02/10 11:14:00:000 220.908 100.2 93.620 0.003 13.52 20.52019/02/10 11:15:00:000 220.908 99.9 93.731 0.003 13.52 20.72019/02/10 11:16:00:000 220.908 99.9 93.445 0.003 13.52 21.02019/02/10 11:17:00:000 220.908 100.1 93.595 0.003 13.52 21.22019/02/10 11:18:00:000 221.860 100.0 93.852 0.003 13.52 20.22019/02/10 11:19:00:000 221.348 99.9 93.692 0.003 13.52 20.22019/02/10 11:20:00:000 221.348 100.0 93.692 0.003 13.52 20.52019/02/10 11:21:00:000 221.577 99.9 93.929 0.003 13.53 20.72019/02/10 11:22:00:000 221.577 99.9 93.791 0.003 13.53 20.72019/02/10 11:23:00:000 221.577 100.0 93.646 0.003 13.53 20.52019/02/10 11:24:00:000 220.759 99.8 93.646 0.003 13.53 20.72019/02/10 11:25:00:000 220.759 100.0 93.503 0.003 13.52 20.72019/02/10 11:26:00:000 220.295 99.8 93.347 0.003 13.52 21.62019/02/10 11:27:00:000 219.828 99.9 93.084 0.003 13.52 22.32019/02/10 11:28:00:000 220.298 100.1 93.329 0.003 13.52 22.32019/02/10 11:29:00:000 220.298 99.9 93.329 0.003 13.52 22.62019/02/10 11:30:00:000 219.962 99.9 93.329 0.003 13.52 22.32019/02/10 11:31:00:000 219.962 99.9 93.382 0.003 13.52 22.32019/02/10 11:32:00:000 219.962 100.1 93.268 0.003 13.52 22.32019/02/10 11:33:00:000 220.501 100.1 93.431 0.003 13.52 22.32019/02/10 11:34:00:000 220.905 100.1 93.499 0.003 13.53 21.72019/02/10 11:35:00:000 220.905 100.0 93.420 0.003 13.53 21.72019/02/10 11:36:00:000 221.139 100.0 93.475 0.003 13.53 21.72019/02/10 11:37:00:000 220.218 99.6 93.366 0.003 13.53 21.92019/02/10 11:38:00:000 220.218 99.9 93.261 0.003 13.51 22.62019/02/10 11:39:00:000 220.218 99.9 93.414 0.003 13.51 22.62019/02/10 11:40:00:000 220.674 99.9 93.366 0.003 13.54 22.62019/02/10 11:41:00:000 219.863 99.7 93.366 0.003 13.54 22.32019/02/10 11:42:00:000 219.863 99.8 93.135 0.003 13.52 22.32019/02/10 11:43:00:000 219.863 99.8 93.183 0.003 13.52 23.32019/02/10 11:44:00:000 219.863 100.1 93.183 0.003 13.52 23.32019/02/10 11:45:00:000 220.615 100.0 93.428 0.003 13.52 23.52019/02/10 11:46:00:000 220.615 100.1 93.428 0.003 13.52 23.52019/02/10 11:47:00:000 220.615 99.7 93.428 0.003 13.52 23.52019/02/10 11:48:00:000 219.495 99.7 93.321 0.003 13.52 22.82019/02/10 11:49:00:000 219.495 99.8 93.071 0.003 13.52 22.82019/02/10 11:50:00:000 220.517 100.2 93.342 0.003 13.52 22.62019/02/10 11:51:00:000 220.517 100.0 93.398 0.003 13.52 22.62019/02/10 11:52:00:000 219.888 99.5 93.125 0.003 13.52 21.92019/02/10 11:53:00:000 219.353 99.8 92.914 0.003 13.52 22.82019/02/10 11:54:00:000 219.353 100.1 93.217 0.003 13.52 23.52019/02/10 11:55:00:000 220.193 99.9 93.361 0.003 13.55 23.52019/02/10 11:56:00:000 220.193 99.8 93.361 0.003 13.55 23.52019/02/10 11:57:00:000 220.193 100.0 93.213 0.003 13.53 23.52019/02/10 11:58:00:000 219.850 99.7 93.251 0.003 13.53 23.32019/02/10 11:59:00:000 218.905 99.7 93.012 0.003 13.53 23.32019/02/10 12:00:00:000 218.905 99.9 92.906 0.003 13.53 23.32019/02/10 12:01:00:000 219.652 100.1 93.352 0.003 13.53 23.32019/02/10 12:02:00:000 220.034 99.9 93.286 0.003 13.53 23.32019/02/10 12:03:00:000 220.034 100.0 93.069 0.003 13.53 23.32019/02/10 12:04:00:000 219.735 99.5 93.204 0.003 13.53 23.52019/02/10 12:05:00:000 218.533 99.8 92.852 0.003 13.53 24.52019/02/10 12:06:00:000 219.361 100.1 93.139 0.003 13.53 24.52019/02/10 12:07:00:000 219.708 100.0 93.269 0.004 13.53 24.52019/02/10 12:08:00:000 219.708 99.5 93.006 0.004 13.53 24.52019/02/10 12:09:00:000 218.433 99.9 92.780 0.004 13.53 24.22019/02/10 12:10:00:000 220.050 100.1 93.144 0.004 13.53 24.22019/02/10 12:11:00:000 220.050 100.1 93.360 0.004 13.53 23.52019/02/10 12:12:00:000 220.657 100.0 93.360 0.004 13.53 23.02019/02/10 12:13:00:000 220.239 99.6 93.312 0.004 13.53 23.02019/02/10 12:14:00:000 219.426 99.7 92.946 0.004 13.53 23.0

Page 105: Division of Environmental Permits Floor

2019/02/10 12:15:00:000 219.426 100.0 93.144 0.004 13.53 23.32019/02/10 12:16:00:000 220.012 99.9 93.144 0.004 13.53 23.32019/02/10 12:17:00:000 220.012 99.8 93.250 0.004 13.53 23.02019/02/10 12:18:00:000 220.012 99.7 93.250 0.004 13.53 23.32019/02/10 12:19:00:000 220.012 99.9 93.250 0.004 13.53 23.32019/02/10 12:20:00:000 220.012 99.7 93.403 0.004 13.53 23.02019/02/10 12:21:00:000 219.148 99.5 93.047 0.004 13.53 23.02019/02/10 12:22:00:000 218.737 99.6 92.860 0.004 13.53 23.02019/02/10 12:23:00:000 218.737 100.0 92.860 0.004 13.53 23.52019/02/10 12:24:00:000 219.385 99.9 93.104 0.004 13.53 23.82019/02/10 12:25:00:000 220.041 99.9 93.235 0.004 13.53 23.52019/02/10 12:26:00:000 220.041 99.8 93.235 0.004 13.53 23.32019/02/10 12:27:00:000 220.041 99.7 93.235 0.004 13.53 23.02019/02/10 12:28:00:000 219.200 99.6 93.109 0.004 13.53 23.32019/02/10 12:29:00:000 218.857 99.6 92.939 0.004 13.53 23.32019/02/10 12:30:00:000 218.857 99.6 92.887 0.004 13.53 24.02019/02/10 12:31:00:000 218.736 99.8 92.887 0.004 13.53 24.02019/02/10 12:32:00:000 218.736 99.7 92.841 0.004 13.53 24.32019/02/10 12:33:00:000 218.434 99.7 92.604 0.004 13.53 24.32019/02/10 12:34:00:000 218.901 99.7 93.023 0.004 13.53 23.52019/02/10 12:35:00:000 218.901 99.7 93.004 0.004 13.53 23.02019/02/10 12:36:00:000 218.356 99.5 92.743 0.004 13.53 23.02019/02/10 12:37:00:000 218.356 99.6 92.894 0.004 13.53 22.82019/02/10 12:38:00:000 218.608 99.6 92.911 0.004 13.55 22.62019/02/10 12:39:00:000 218.608 99.7 92.827 0.004 13.55 22.32019/02/10 12:40:00:000 218.744 99.5 92.884 0.004 13.55 22.12019/02/10 12:41:00:000 218.744 99.7 92.667 0.004 13.53 21.62019/02/10 12:42:00:000 218.343 99.4 92.673 0.004 13.53 21.62019/02/10 12:43:00:000 217.939 99.8 92.774 0.004 13.53 21.62019/02/10 12:44:00:000 218.300 99.7 92.774 0.004 13.53 21.62019/02/10 12:45:00:000 218.300 99.6 92.774 0.004 13.53 22.62019/02/10 12:46:00:000 217.965 99.9 92.671 0.004 13.53 23.32019/02/10 12:47:00:000 218.841 99.9 92.842 0.004 13.53 23.3AVERAGE: 222.67 100.00 94.14 0.00 13.41 17.90

Page 106: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 12 CTG-2 WO/DB Run 3DCS Data - 20190210 - 0815-1700

Unit 12 GT Power Unit 12 GT PowerUnit 12 Total GT

Gas FlowUnit 12 HRSG DB Fuel Flow

Unit 12 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 12HAD00EU001 12MKA01EU902A 12MBP10CF910 12HHA10CF001 12HNE10CQ109 12MBL05CT1012019/02/10 12:52:00:000 218.695 99.7 92.803 0.004 13.54 22.62019/02/10 12:53:00:000 218.695 99.7 92.998 0.004 13.54 22.62019/02/10 12:54:00:000 218.695 99.5 92.773 0.004 13.54 22.62019/02/10 12:55:00:000 218.695 99.7 92.904 0.004 13.54 22.32019/02/10 12:56:00:000 218.695 99.6 92.904 0.004 13.54 22.12019/02/10 12:57:00:000 218.695 99.5 92.776 0.004 13.53 22.12019/02/10 12:58:00:000 218.695 99.5 92.660 0.004 13.53 21.92019/02/10 12:59:00:000 218.445 99.4 92.790 0.004 13.53 21.92019/02/10 13:00:00:000 218.445 99.4 92.586 0.004 13.53 21.92019/02/10 13:01:00:000 218.309 99.5 92.715 0.004 13.53 22.62019/02/10 13:02:00:000 218.059 99.5 92.715 0.004 13.54 22.62019/02/10 13:03:00:000 218.059 99.9 92.616 0.004 13.54 23.52019/02/10 13:04:00:000 218.351 99.7 92.732 0.004 13.54 23.52019/02/10 13:05:00:000 218.351 99.6 92.508 0.004 13.54 23.82019/02/10 13:06:00:000 217.887 99.7 92.554 0.004 13.54 24.42019/02/10 13:07:00:000 217.887 100.0 92.706 0.004 13.54 24.42019/02/10 13:08:00:000 218.342 99.7 92.779 0.004 13.54 24.22019/02/10 13:09:00:000 218.342 99.5 92.686 0.004 13.54 24.02019/02/10 13:10:00:000 217.371 99.6 92.547 0.004 13.54 24.42019/02/10 13:11:00:000 217.371 99.8 92.547 0.004 13.54 24.92019/02/10 13:12:00:000 218.055 99.9 92.722 0.004 13.54 24.92019/02/10 13:13:00:000 218.055 99.9 92.612 0.004 13.54 25.12019/02/10 13:14:00:000 218.055 99.9 92.773 0.004 13.54 25.12019/02/10 13:15:00:000 218.055 100.2 92.773 0.004 13.56 25.12019/02/10 13:16:00:000 219.148 100.2 93.115 0.004 13.56 25.42019/02/10 13:17:00:000 219.148 100.1 92.924 0.004 13.56 25.42019/02/10 13:18:00:000 219.148 99.7 93.006 0.004 13.54 25.42019/02/10 13:19:00:000 218.754 99.9 92.991 0.004 13.54 25.12019/02/10 13:20:00:000 219.275 99.8 92.991 0.004 13.54 24.92019/02/10 13:21:00:000 219.275 99.7 92.991 0.004 13.54 24.62019/02/10 13:22:00:000 218.830 99.6 92.854 0.004 13.54 24.62019/02/10 13:23:00:000 218.830 99.5 92.920 0.004 13.54 24.42019/02/10 13:24:00:000 218.066 99.6 92.715 0.004 13.54 25.12019/02/10 13:25:00:000 218.544 99.7 92.949 0.004 13.54 25.62019/02/10 13:26:00:000 218.965 99.8 92.859 0.004 13.54 25.62019/02/10 13:27:00:000 218.965 99.8 92.941 0.004 13.54 24.92019/02/10 13:28:00:000 219.375 99.7 92.973 0.004 13.54 24.92019/02/10 13:29:00:000 218.980 99.6 92.973 0.004 13.54 24.62019/02/10 13:30:00:000 218.980 99.7 92.973 0.004 13.54 24.22019/02/10 13:31:00:000 218.980 99.5 92.862 0.004 13.54 24.02019/02/10 13:32:00:000 218.300 99.5 92.862 0.004 13.54 24.02019/02/10 13:33:00:000 218.955 99.8 92.888 0.004 13.54 24.22019/02/10 13:34:00:000 218.955 99.5 92.888 0.004 13.54 24.22019/02/10 13:35:00:000 218.547 99.6 92.888 0.004 13.54 24.02019/02/10 13:36:00:000 218.891 99.7 92.888 0.004 13.54 24.02019/02/10 13:37:00:000 218.891 99.7 92.888 0.004 13.54 24.02019/02/10 13:38:00:000 219.205 99.6 92.823 0.004 13.54 24.02019/02/10 13:39:00:000 219.205 99.6 92.971 0.004 13.54 24.02019/02/10 13:40:00:000 218.757 99.6 92.856 0.004 13.54 24.22019/02/10 13:41:00:000 218.757 99.5 92.856 0.004 13.54 24.72019/02/10 13:42:00:000 218.047 99.6 92.725 0.004 13.54 25.42019/02/10 13:43:00:000 218.047 99.6 92.725 0.004 13.54 25.42019/02/10 13:44:00:000 218.047 99.5 92.575 0.004 13.54 25.42019/02/10 13:45:00:000 217.456 99.4 92.575 0.004 13.54 25.12019/02/10 13:46:00:000 217.301 100.1 92.647 0.004 13.54 25.82019/02/10 13:47:00:000 218.088 100.0 92.904 0.004 13.54 25.82019/02/10 13:48:00:000 218.553 100.0 92.904 0.004 13.54 25.62019/02/10 13:49:00:000 218.951 100.1 92.904 0.004 13.55 25.42019/02/10 13:50:00:000 218.951 99.9 92.951 0.004 13.55 25.42019/02/10 13:51:00:000 218.951 99.7 92.863 0.004 13.55 25.82019/02/10 13:52:00:000 218.514 99.6 92.654 0.004 13.53 25.82019/02/10 13:53:00:000 217.410 99.4 92.672 0.004 13.53 25.82019/02/10 13:54:00:000 217.410 99.6 92.484 0.004 13.53 26.32019/02/10 13:55:00:000 216.861 99.6 92.435 0.004 13.53 26.82019/02/10 13:56:00:000 218.044 100.3 92.872 0.004 13.55 27.42019/02/10 13:57:00:000 218.977 100.4 93.110 0.004 13.55 26.82019/02/10 13:58:00:000 219.351 99.9 93.110 0.004 13.57 26.32019/02/10 13:59:00:000 218.070 99.6 92.569 0.004 13.52 26.32019/02/10 14:00:00:000 217.850 99.8 92.539 0.004 13.52 26.52019/02/10 14:01:00:000 218.539 100.0 92.998 0.004 13.57 26.52019/02/10 14:02:00:000 218.539 99.8 92.804 0.004 13.57 26.3

Page 107: Division of Environmental Permits Floor

2019/02/10 14:03:00:000 218.729 99.8 92.860 0.004 13.54 26.32019/02/10 14:04:00:000 218.729 99.9 93.027 0.004 13.54 26.32019/02/10 14:05:00:000 218.074 99.7 92.750 0.004 13.54 26.12019/02/10 14:06:00:000 218.074 99.7 92.683 0.004 13.54 26.12019/02/10 14:07:00:000 218.074 99.8 92.795 0.004 13.54 26.32019/02/10 14:08:00:000 218.273 99.6 92.795 0.004 13.54 26.52019/02/10 14:09:00:000 218.117 99.9 92.750 0.004 13.55 26.82019/02/10 14:10:00:000 218.833 99.9 92.888 0.004 13.55 27.02019/02/10 14:11:00:000 218.335 99.7 92.888 0.004 13.55 26.82019/02/10 14:12:00:000 218.335 99.7 92.655 0.004 13.55 26.62019/02/10 14:13:00:000 218.335 99.8 92.828 0.004 13.55 26.32019/02/10 14:14:00:000 217.159 99.2 92.405 0.004 13.52 26.12019/02/10 14:15:00:000 217.159 99.6 92.405 0.004 13.52 25.82019/02/10 14:16:00:000 217.159 99.6 92.405 0.004 13.56 26.12019/02/10 14:17:00:000 217.159 99.8 92.440 0.004 13.56 26.32019/02/10 14:18:00:000 217.159 100.0 92.440 0.004 13.56 27.22019/02/10 14:19:00:000 217.159 100.0 92.610 0.004 13.56 27.22019/02/10 14:20:00:000 217.840 100.2 92.610 0.004 13.56 27.42019/02/10 14:21:00:000 217.840 100.0 92.718 0.004 13.56 27.72019/02/10 14:22:00:000 217.228 99.9 92.548 0.004 13.56 27.72019/02/10 14:23:00:000 217.228 100.1 92.499 0.004 13.56 27.92019/02/10 14:24:00:000 217.228 100.0 92.724 0.004 13.56 27.72019/02/10 14:25:00:000 217.228 99.8 92.474 0.004 13.56 27.72019/02/10 14:26:00:000 217.228 100.1 92.474 0.004 13.56 27.72019/02/10 14:27:00:000 217.228 99.9 92.538 0.004 13.56 27.42019/02/10 14:28:00:000 217.228 99.7 92.538 0.004 13.56 27.42019/02/10 14:29:00:000 216.601 100.0 92.448 0.004 13.54 27.72019/02/10 14:30:00:000 216.792 100.0 92.448 0.004 13.54 27.92019/02/10 14:31:00:000 217.315 100.2 92.502 0.004 13.57 28.22019/02/10 14:32:00:000 217.315 100.3 92.622 0.004 13.57 28.22019/02/10 14:33:00:000 217.797 100.2 92.674 0.004 13.57 28.22019/02/10 14:34:00:000 218.633 100.3 92.858 0.004 13.57 27.72019/02/10 14:35:00:000 218.633 99.8 92.835 0.004 13.57 27.22019/02/10 14:36:00:000 217.818 99.8 92.863 0.004 13.57 26.82019/02/10 14:37:00:000 217.818 99.6 92.672 0.004 13.57 26.82019/02/10 14:38:00:000 216.599 99.5 92.351 0.004 13.55 26.52019/02/10 14:39:00:000 216.599 99.8 92.351 0.004 13.55 27.42019/02/10 14:40:00:000 217.134 99.8 92.438 0.004 13.55 27.42019/02/10 14:41:00:000 216.413 99.8 92.471 0.004 13.55 27.72019/02/10 14:42:00:000 217.003 99.9 92.426 0.004 13.55 27.92019/02/10 14:43:00:000 217.003 100.3 92.620 0.004 13.57 28.22019/02/10 14:44:00:000 217.764 100.1 92.620 0.004 13.57 27.92019/02/10 14:45:00:000 217.204 99.9 92.478 0.004 13.57 27.92019/02/10 14:46:00:000 217.204 99.7 92.478 0.004 13.57 27.72019/02/10 14:47:00:000 216.828 99.8 92.343 0.004 13.57 27.72019/02/10 14:48:00:000 216.828 99.9 92.343 0.004 13.57 27.92019/02/10 14:49:00:000 216.828 99.9 92.343 0.004 13.57 28.22019/02/10 14:50:00:000 216.603 100.0 92.343 0.004 13.57 28.22019/02/10 14:51:00:000 216.603 99.8 92.443 0.004 13.57 28.42019/02/10 14:52:00:000 216.603 100.1 92.309 0.004 13.57 28.42019/02/10 14:53:00:000 216.890 100.1 92.422 0.004 13.57 28.42019/02/10 14:54:00:000 217.298 100.0 92.571 0.004 13.57 28.72019/02/10 14:55:00:000 217.298 100.3 92.571 0.004 13.57 28.72019/02/10 14:56:00:000 218.069 100.0 92.815 0.004 13.57 27.92019/02/10 14:57:00:000 218.069 99.7 92.731 0.004 13.57 27.22019/02/10 14:58:00:000 217.144 99.6 92.476 0.004 13.57 27.22019/02/10 14:59:00:000 217.144 99.6 92.347 0.004 13.57 27.02019/02/10 15:00:00:000 217.144 99.5 92.457 0.004 13.57 27.02019/02/10 15:01:00:000 216.787 99.6 92.490 0.004 13.57 26.82019/02/10 15:02:00:000 217.042 99.8 92.533 0.004 13.56 27.02019/02/10 15:03:00:000 217.042 99.8 92.533 0.004 13.56 27.02019/02/10 15:04:00:000 216.818 99.6 92.533 0.004 13.56 27.22019/02/10 15:05:00:000 217.228 99.8 92.385 0.004 13.56 27.02019/02/10 15:06:00:000 217.228 99.7 92.533 0.004 13.56 26.82019/02/10 15:07:00:000 217.009 99.6 92.354 0.004 13.56 27.02019/02/10 15:08:00:000 217.009 99.7 92.404 0.004 13.56 27.02019/02/10 15:09:00:000 217.009 99.8 92.404 0.004 13.56 27.22019/02/10 15:10:00:000 217.009 99.8 92.404 0.004 13.57 27.22019/02/10 15:11:00:000 217.009 99.7 92.404 0.004 13.57 27.22019/02/10 15:12:00:000 216.670 99.7 92.162 0.004 13.57 27.92019/02/10 15:13:00:000 217.032 100.1 92.324 0.004 13.57 27.92019/02/10 15:14:00:000 217.433 100.0 92.628 0.004 13.57 28.22019/02/10 15:15:00:000 217.433 100.0 92.628 0.004 13.57 28.22019/02/10 15:16:00:000 217.433 99.8 92.497 0.004 13.57 28.22019/02/10 15:17:00:000 216.671 99.8 92.275 0.004 13.56 28.72019/02/10 15:18:00:000 216.671 100.0 92.333 0.004 13.56 28.72019/02/10 15:19:00:000 217.013 99.9 92.429 0.004 13.56 28.72019/02/10 15:20:00:000 217.013 100.0 92.603 0.004 13.56 28.72019/02/10 15:21:00:000 217.335 100.0 92.603 0.004 13.56 28.72019/02/10 15:22:00:000 217.335 99.8 92.261 0.004 13.56 28.42019/02/10 15:23:00:000 216.788 99.7 92.262 0.004 13.56 28.2

Page 108: Division of Environmental Permits Floor

2019/02/10 15:24:00:000 216.788 99.9 92.334 0.004 13.57 28.22019/02/10 15:25:00:000 217.383 99.9 92.618 0.004 13.57 28.22019/02/10 15:26:00:000 217.383 99.9 92.460 0.004 13.57 28.42019/02/10 15:27:00:000 216.841 99.9 92.460 0.004 13.57 28.42019/02/10 15:28:00:000 216.841 99.8 92.440 0.004 13.57 28.72019/02/10 15:29:00:000 216.841 99.7 92.332 0.004 13.57 27.92019/02/10 15:30:00:000 216.841 99.8 92.424 0.004 13.57 27.92019/02/10 15:31:00:000 216.841 100.1 92.424 0.004 13.57 27.92019/02/10 15:32:00:000 217.322 99.8 92.424 0.004 13.57 28.22019/02/10 15:33:00:000 217.031 99.8 92.435 0.004 13.56 27.92019/02/10 15:34:00:000 217.031 99.8 92.435 0.004 13.56 27.92019/02/10 15:35:00:000 217.031 99.8 92.494 0.004 13.56 27.92019/02/10 15:36:00:000 217.242 99.7 92.494 0.004 13.56 27.92019/02/10 15:37:00:000 217.242 99.7 92.456 0.004 13.56 27.92019/02/10 15:38:00:000 216.388 99.7 92.165 0.004 13.56 28.22019/02/10 15:39:00:000 216.388 99.7 92.127 0.004 13.56 28.92019/02/10 15:40:00:000 216.388 99.9 92.286 0.004 13.58 29.32019/02/10 15:41:00:000 217.680 100.2 92.801 0.004 13.58 29.32019/02/10 15:42:00:000 217.680 100.0 92.781 0.004 13.58 29.32019/02/10 15:43:00:000 217.680 99.9 92.566 0.004 13.55 29.12019/02/10 15:44:00:000 217.680 99.8 92.342 0.004 13.55 28.42019/02/10 15:45:00:000 217.235 99.6 92.500 0.004 13.55 28.42019/02/10 15:46:00:000 216.780 99.6 92.253 0.004 13.55 28.42019/02/10 15:47:00:000 217.203 99.9 92.494 0.004 13.57 28.42019/02/10 15:48:00:000 217.203 99.7 92.434 0.004 13.57 28.42019/02/10 15:49:00:000 216.579 99.6 92.252 0.004 13.57 28.22019/02/10 15:50:00:000 216.579 99.7 92.252 0.004 13.57 28.42019/02/10 15:51:00:000 216.579 99.9 92.367 0.004 13.57 28.42019/02/10 15:52:00:000 216.579 99.9 92.367 0.004 13.57 28.42019/02/10 15:53:00:000 217.016 99.9 92.367 0.004 13.57 28.72019/02/10 15:54:00:000 217.016 100.0 92.604 0.004 13.57 28.92019/02/10 15:55:00:000 217.542 100.0 92.604 0.004 13.57 29.12019/02/10 15:56:00:000 217.060 99.8 92.402 0.004 13.57 29.32019/02/10 15:57:00:000 216.827 99.8 92.340 0.004 13.57 29.32019/02/10 15:58:00:000 216.827 100.0 92.340 0.004 13.57 29.32019/02/10 15:59:00:000 217.418 99.9 92.460 0.004 13.57 29.12019/02/10 16:00:00:000 217.418 99.8 92.460 0.004 13.57 29.12019/02/10 16:01:00:000 216.889 99.9 92.460 0.004 13.57 29.12019/02/10 16:02:00:000 217.232 99.7 92.460 0.004 13.57 28.92019/02/10 16:03:00:000 216.710 99.7 92.239 0.004 13.57 28.92019/02/10 16:04:00:000 216.710 99.5 92.279 0.004 13.57 29.12019/02/10 16:05:00:000 215.869 99.7 92.099 0.004 13.57 29.12019/02/10 16:06:00:000 216.772 100.0 92.332 0.004 13.57 29.12019/02/10 16:07:00:000 216.772 99.9 92.332 0.004 13.57 29.32019/02/10 16:08:00:000 217.349 99.8 92.493 0.004 13.57 29.52019/02/10 16:09:00:000 217.349 99.8 92.327 0.004 13.57 29.82019/02/10 16:10:00:000 216.974 99.8 92.327 0.004 13.57 29.52019/02/10 16:11:00:000 216.974 99.8 92.327 0.004 13.57 29.82019/02/10 16:12:00:000 216.974 99.9 92.327 0.004 13.57 29.82019/02/10 16:13:00:000 216.974 99.9 92.448 0.004 13.57 29.82019/02/10 16:14:00:000 216.974 99.9 92.448 0.004 13.57 29.32019/02/10 16:15:00:000 216.974 99.8 92.448 0.004 13.57 29.12019/02/10 16:16:00:000 216.974 99.7 92.489 0.004 13.57 29.12019/02/10 16:17:00:000 216.746 99.7 92.241 0.004 13.57 29.12019/02/10 16:18:00:000 216.746 99.7 92.284 0.004 13.57 29.32019/02/10 16:19:00:000 216.746 99.9 92.284 0.004 13.57 29.32019/02/10 16:20:00:000 216.746 99.9 92.481 0.004 13.57 29.32019/02/10 16:21:00:000 216.939 99.9 92.642 0.004 13.58 29.32019/02/10 16:22:00:000 217.365 100.0 92.537 0.004 13.58 29.32019/02/10 16:23:00:000 217.365 99.7 92.369 0.004 13.58 29.12019/02/10 16:24:00:000 216.986 99.7 92.294 0.004 13.56 29.12019/02/10 16:25:00:000 216.986 99.7 92.432 0.004 13.56 29.12019/02/10 16:26:00:000 217.227 99.7 92.432 0.004 13.56 29.12019/02/10 16:27:00:000 216.798 99.7 92.359 0.004 13.58 29.12019/02/10 16:28:00:000 216.798 99.7 92.359 0.004 13.58 29.12019/02/10 16:29:00:000 216.798 99.7 92.359 0.004 13.58 29.12019/02/10 16:30:00:000 217.233 99.7 92.359 0.004 13.57 28.92019/02/10 16:31:00:000 216.643 99.8 92.393 0.004 13.57 28.72019/02/10 16:32:00:000 217.069 99.8 92.393 0.004 13.57 28.72019/02/10 16:33:00:000 217.069 99.6 92.504 0.004 13.57 28.72019/02/10 16:34:00:000 217.069 99.7 92.343 0.004 13.57 28.72019/02/10 16:35:00:000 217.069 99.7 92.343 0.004 13.57 28.72019/02/10 16:36:00:000 216.642 99.7 92.243 0.004 13.57 28.72019/02/10 16:37:00:000 216.642 99.8 92.365 0.004 13.57 28.92019/02/10 16:38:00:000 217.017 99.6 92.365 0.004 13.57 28.92019/02/10 16:39:00:000 217.017 99.8 92.479 0.004 13.57 28.92019/02/10 16:40:00:000 217.017 99.7 92.436 0.004 13.57 28.72019/02/10 16:41:00:000 217.017 99.7 92.436 0.004 13.57 28.72019/02/10 16:42:00:000 217.017 99.6 92.337 0.004 13.57 28.72019/02/10 16:43:00:000 217.017 99.6 92.337 0.004 13.56 28.72019/02/10 16:44:00:000 217.017 99.7 92.337 0.004 13.56 28.7

Page 109: Division of Environmental Permits Floor

2019/02/10 16:45:00:000 217.017 99.6 92.446 0.004 13.56 28.42019/02/10 16:46:00:000 217.229 99.6 92.446 0.004 13.56 28.42019/02/10 16:47:00:000 217.229 99.5 92.317 0.004 13.56 28.42019/02/10 16:48:00:000 217.065 99.6 92.445 0.004 13.57 28.42019/02/10 16:49:00:000 217.065 99.5 92.383 0.004 13.57 28.42019/02/10 16:50:00:000 217.065 99.7 92.383 0.004 13.57 28.42019/02/10 16:51:00:000 217.065 99.7 92.383 0.004 13.57 28.42019/02/10 16:52:00:000 217.065 99.7 92.536 0.004 13.57 28.72019/02/10 16:53:00:000 217.065 99.6 92.440 0.004 13.57 28.92019/02/10 16:54:00:000 217.065 99.6 92.376 0.004 13.57 28.9AVERAGE: 217.54 99.79 92.56 0.00 13.56 27.13

Page 110: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-12 Base Load PM Data

Page 111: Division of Environmental Permits Floor

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

08:57 08:22 12:52 hh:mm

13:10 12:47 16:54 hh:mm

02/09/19 02/10/19 02/10/19 mm/dd/yy

Base Base Base % or w/DB --

1.017 0.893 1.017

0.7350 0.7290 0.7350

0.145 0.145 0.142 in

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

0.000 446.340 538.550 ft³

83.109 538.330 622.850 ft³

83.109 91.990 84.300 86.466 ft³

242.25 238.00 241.00 240.42 min

63.50 62.25 71.17 65.64 °F

210.75 210.92 204.42 208.69 °F

30.02 30.13 29.98 30.04 in Hg

-1.20 -1.20 -1.20 -1.20 in H₂O

29.93 30.04 29.89 29.96 in Hg

0.45 0.45 0.45 0.45 in H₂O

30.15 30.27 30.11 30.18 in Hg

1.24 1.23 1.24 1.23 √(in H₂O)

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

133.90 130.60 119.30 127.93 g

12.30 15.50 15.20 14.33 g

146.46 146.36 134.74 142.52 ml

6.89 6.89 6.34 6.71 scf

85.6 83.7 85.5 84.9 dscf

2.4 2.4 2.4 2.4 dscm

7.45 7.60 6.91 7.32 %

97.47 97.44 85.88 93.60 %

7.45 7.60 6.91 7.32 %

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

4.3 4.2 4.1 4.2 %

13.4 13.4 13.4 13.4 %

0.0 0.0 0.0 0.0 ppm

82.3 82.4 82.5 82.4 %

29.22 29.21 29.19 29.21 lb/lb-mole

28.39 28.36 28.42 28.39 lb/lb-mole

1.744 1.786 1.829 1.786

8632.05 8632.49 8632.49 8632.34 dscf/MMBtu

160.9 160.4 159.9 160.4 %

Calculated Fuel Factor

Fuel F-Factor

Percent Excess Air

Oxygen Content

Carbon Monoxide Content

Nitrogen Content

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Calculated Stack Moisture

Saturated Stack Moisture

Reported Stack Moisture Content

Carbon Dioxide Content

Gas Analysis Data

Impinger Water Weight Gain

Silica Gel Weight Gain

Total Water Volume Collected

Standard Water Vapor Volume

Standard Meter Volume

Standard Metric Meter Volume

Absolute Stack Pressure

Average Orifice Pressure Drop

Absolute Meter Pressure

Avg Square Root Pitot Pressure

Moisture Content Data

Total Sampling Time

Average Meter Temperature

Average Stack Temperature

Barometric Pressure

Stack Static Pressure

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Initial Meter Volume

Final Meter Volume

Total Meter Volume

Stack Test Data

Run Start Time

Run Stop Time

Test Date

Meter Calibration Factor

Pitot Tube Coefficient

Project # sie-19-middletown.ny-comp#2

Historical Data

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

Average Nozzle Diameter

Load

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Results

Page 112: Division of Environmental Permits Floor

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

68.97 67.96 68.86 68.60 ft/sec

283.53 283.53 283.53 283.53 ft²

1,173,258 1,156,061 1,171,486 1,166,935 acfm

55,436 54,810 55,805 55,350 wkscfh

51,305,315 50,643,478 51,950,960 51,299,918 dscfh

101.6 102.4 105.7 103.2 %

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

5.04 4.82 4.02 4.63 mg --

5.89E-05 5.76E-05 4.70E-05 5.45E-05 g/dscf --

9.09E-04 8.88E-04 7.25E-04 8.41E-04 gr/dscf --

3.02 2.92 2.44 2.79 kg/hr --

6.66 6.43 5.38 6.16 lb/hr --

29.18 28.15 23.57 26.96 tpy --

0.0031 0.0031 0.0025 0.0029 lb/MMBtu 0.0073

1.27 1.65 0.86 1.26 mg --

1.48E-05 1.97E-05 1.00E-05 1.48E-05 g/dscf --

2.29E-04 3.04E-04 1.54E-04 2.29E-04 gr/dscf --

0.76 1.00 0.52 0.76 kg/hr --

1.68 2.20 1.15 1.67 lb/hr --

7.34 9.64 5.02 7.33 tpy --

0.0008 0.0010 0.0005 0.0008 lb/MMBtu --

2.77 1.87 2.36 2.33 mg --

3.24E-05 2.23E-05 2.76E-05 2.74E-05 g/dscf --

5.00E-04 3.44E-04 4.26E-04 4.24E-04 gr/dscf --

1.66 1.13 1.43 1.41 kg/hr --

3.67 2.49 3.16 3.11 lb/hr --

16.05 10.91 13.85 13.61 tpy --

0.0017 0.0012 0.0015 0.0015 lb/MMBtu --

1.00 1.30 0.80 1.03 mg --

1.17E-05 1.55E-05 9.36E-06 1.22E-05 g/dscf --

1.80E-04 2.40E-04 1.44E-04 1.88E-04 gr/dscf --

0.60 0.79 0.49 0.62 kg/hr --

1.32 1.73 1.07 1.38 lb/hr --

5.79 7.59 4.69 6.02 tpy --

0.0006 0.0008 0.0005 0.0006 lb/MMBtu --

12-PM-Base-1 12-PM-Base-2 12-PM-Base-3 Average Units Limits

0.48 0.48 0.48 0.48 ft³/min

207.91 207.81 206.92 207.55 µP

1.08 1.08 1.08 1.08

2.53 2.55 2.53 2.54

1.08 1.08 1.08 1.08

2.53 2.55 2.53 2.54

2553.14 2543.59 2562.17 2,552.96

1.00 1.00 1.00 1.00

0 0 0 0 points

Condensable PM₂.₅ Emission Rate

Cunningham Correction Factor

Recalculated D50-1 for CIV

Z

Recalculated Cunninham

Lower Limit Cut Diameter, CI (NRE<3162), D50LL

Reynolds Number

RM 201A Quality Control

No. Sampling Pts. Outside Dp

Cyclone Flow Rate

Stack Viscosity

Emission Rate Data

Stack Cross-Sectional Area

Actual Stack Flow Rate

Wet Standard Stack Flow Rate

Dry Standard Stack Flow Rate

Percent of Isokinetic Rate

Condensable PM₂.₅ Concentration

Filterable PM₂.₅ Mass

Filterable PM₂.₅ Concentration

Condensable PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Concentration

Filterable PM₁₀ Mass

Filterable PM₁₀ Concentration

Total PM₁₀/PM₂.₅ Emission Rate

Filterable PM₁₀ Emission Rate

Filterable PM₂.₅ Emission Rate

Average Stack Gas Velocity

Volumetric Flow Rate Data

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Results

Page 113: Division of Environmental Permits Floor

(mm/dd/yy)

°F

in Hg

indust. spec. scf

chk Subpart minutes

in

1 2 3

(mm/dd/yy) 02/09/19 02/10/19 02/10/19

Base Base Base % or w/DB

8632.05 8632.49 8632.49 dscf/MMBtu

from ACS samp-cp-0025 samp-cp-0019 samp-cp-0025

(Y) 1.017 0.893 1.017

(H@) 1.820 1.838 1.820 in H₂O

No No No

from ACS 5272/10 P-983/10 5272/10

(Cp) 0.7350 0.7290 0.7350

from ACS 3 3 3 must match cyc nozz tab (e.g. 3, 4, etc.)

(Dn) 0.145 0.145 0.142 in

from ACS samp-hp-0149 samp-hp-0148 samp-hp-0149

120.0 120.0 120.0 in

from list glass glass glass

from ACS samp-bh-0035 samp-bh-0034 samp-bh-0035

from ACS samp-cc-0027 samp-cp-0012 samp-cc-0027

Created with Isocalc-AHI v20190131

1600 W Tacoma Street

Broken Arrow, Oklahoma 74012

Cole McBride

(918) 307-8865

Unit Number

Operator CM

Standard Temperature

Standard Pressure

68

29.92

Pitot Identification

Number of Ports Used

Port Inside Diameter

Stack Shape

Base Run Number

Number of Ports Available

Test Equipment Information

Run

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE

Date for Preliminary Run 02/09/09

Company Name Air Hygiene International, Inc. (Tulsa, Oklahoma)

Test Information

Project # sie-19-middletown.ny-comp#2

Source Information

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

Fuel Type Gas, Natural

Required Sample Vol.

Run Duration

Testing Company Information

Pitot Tube Coefficient

Nozzle Number

Nozzle Diameter

Probe Number

Probe Length

(918) 307-9131

Address

City, State Zip

Project Manager

Phone Number

Fax Number

Sample Case / Oven Number

Impinger Case Number

(SS, Glass …. ) Liner Material

50

240

CTG-12

12-PM-Base

4

Test Date

Fuel F-Factor

Load

4

6.00

Circular

Meter Box Number

Meter Calibration Factor

Orifice Meter Coefficient

Non-Console Manometer Used

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Title Page

Page 114: Division of Environmental Permits Floor

(Lfw) 235.25 in

(Lnw) 7.25 in

(D) 228.00 in

(As) 283.53 ft²

(A) 1200.00 in

(AD) 5.26 diameters

(B) 1095.00 in

(BD) 4.80 diameters

Down Up Particulate Velocity

Stream Stream Points Points

2.00-4.99 0.50-1.24 24 16

5.00-5.99 1.25-1.49 20 16

6.00-6.99 1.50-1.74 16 12

7.00-7.99 1.75-1.99 12 12

>= 8.00 >=2.00 8 or 122 8 or 122

12 12

24 16 4 Ports by 3 Across

24 16 12 Pts Used 12 Required

Fraction Distance Distance

Traverse of from Including

Point Stack Inside Reference

Number Diameter Wall Length

in in

1 0.044 10 17 2/8

2 0.146 33 2/8 40 4/8

3 0.296 67 4/8 74 6/8

4

5

6

7

8

9

Traverse Point Locations

1 Check Minimum Number of Points for the Upstream

and Downstream conditions, then use the largest.

2 8 for Circular Stacks 12 to 24 inches

12 for Circular Stacks over 24 inches

Upstream Spec Number of Traverse Points Used

Downstream Spec

Traverse Pts Required

Distance Downstream

Diameters Downstream

Number of Traverse Points Required

Diameters to Minimum Number of1

Flow Disturbance Traverse Points

Distance to Near Wall of Stack

Diameter of Stack

Area of Stack

Distance from Port to Disturbances

Distance Upstream

Diameters Upstream

Stack Size Large (>24 inch diameter) Port ID (inches) 6.00

Circular Stack or Duct Diameter

Distance to Far Wall of Stack

Operator CM Ports Available 4

Stack Type

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 1 - SAMPLE AND VELOCITY TRAVERSES FOR CIRCULAR SOURCES

Plant Name CPV Valley Energy Center Date 02/09/09

Sampling Location CTG-12 Stack

Project #

Circular

Lnw

Lfw

D

B

A

Method 1 Trav

12 Point PM Trav (M201a ONLY)

Velocity

sie-19-middletown.ny-comp#1-CTG12-PM_BASE M1 - Circular

Page 115: Division of Environmental Permits Floor

x PreTest x PostTest 0.7350 5272/10

(As) 283.53 ft²

(D) 228.00 in 08:29 Start 08:41 End

Traverse Velocity Null Zero Deg Stack Local

Point Head Angle Pressure Temp Velocity

(p) (Na) (0oa) (ts) (vs(l))

(Pb) 30.01 in Hg in H₂O deg in H₂O °F ft/sec

(Pstatic) -1.20 in H₂O A-1 1.80 0 0.00 212 75.09

(Ps) 29.92 in Hg A-2 1.70 -5 0.10 211 72.92

A-3 1.70 -5 0.10 210 72.87

B-1 1.40 -5 0.10 210 66.13

B-2 1.30 -5 0.10 210 63.72

(%CO2) 4.10 %vd B-3 1.30 0 0.00 209 63.68

(%O2) 13.60 %vd C-1 1.90 0 0.00 212 77.15

(ppmCO) 0.00 ppmvd C-2 1.60 -10 0.15 211 70.75

(%N2) 82.30 %vd C-3 1.20 0 0.00 210 61.22

(Bws) 8.00 % D-1 1.90 0 0.00 210 77.04

(Md) 29.20 lb/lb-mole D-2 1.80 -5 0.10 211 75.04

(Mw) 28.30 lb/lb-mole D-3 1.30 0 0.00 214 63.91

(vs) 69.96 ft/sec

(Qsd) 51,710,454 dscf/hr

(Qsd) 861,841 dscf/min

(Qaw) 1,190,130 acf/min

(Qsw) 56,207,015 ascf/hr

1.58 3 211

1.25

3.3

Thermocouple ID

Standard deviation of null angles =

Pressures

Barometric Pressure

Static Pressure

Carbon Dioxide Concentration

= Square roots of p

Avg Stack Dry Std Flow Rate

Avg Stack Wet Flow Rate

Avg Stack Wet Std Flow Rate

Stack Cross Section Schematic

40 CFR 60, Method 2G, Section 8.11.1 (but applies to all Method 2 type static pressure measurements): If a Type S probe is used for this measurement, position the probe at or between any traverse point(s) and rotate the probe until a null differential pressure reading is obtained. Disconnect the tubing from one of the pressure ports; read and record the ∆P. For pressure devices with one-directional scales, if a deflection in the positive direction is noted with the negative side disconnected, then the static pressure is positive. Likewise, if a deflection in the positive direction is noted with the positive side disconnected, then the static pressure is negative.

Average

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Results

Avg Stack Gas Velocity

Avg Stack Dry Std Flow Rate

Oxygen Concentration

Carbon Monoxide Concentration

Nitrogen Concentration

Stack Moisture Content

CM Ports Available 4

Stack Dimensions Velocity Traverse Data

Diameter of Stack

Run Number 12-PM-Base-V1

samp-hp-0149

Pitot Leak Check Pitot Coefficient

Absolute Stack Pressure

Stack Gas Composition

Estimated CompositionComposition Data:

Area of Stack

Run Time

METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE

Plant Name CPV Valley Energy Center Preliminary Run Date 02/09/09

Project # sie-19-middletown.ny-comp#2

Pitot Identification

Sampling Location CTG-12 Stack Stack Type Circular

Operator

sie-19-middletown.ny-comp#1-CTG12-PM_BASE M2 - Run (1)

Page 116: Division of Environmental Permits Floor

1.600 1.836

Date 02/09/19 08:57 13:10

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.3 13.4 0.0 82.3 160.9 YES

Date 02/10/19 08:22 12:47

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.2 13.4 0.0 82.4 160.4 YES

Date 02/10/19 12:52 16:54

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.1 13.4 0.0 82.5 159.9 YES

hh:mm lb/lb-mole

04:02 29.19 1.829

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Gas Analysis Data

Run Number 12-PM-Base-3 Run Start Time

hh:mm lb/lb-mole

04:25 29.21 1.786

Run Stop Time

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

Run Number 12-PM-Base-2 Run Start Time Run Stop Time

Gas Analysis Data

Dry Molecular Weight

(Md)

N₂ Conc.

CO₂ Conc.

O₂ Conc.

COConc.

Excess Air

Fuel Factor in

Range

hh:mm

04:13

CalculatedFuel Factor

(Fo)avg

1.744

SampleAnalysis

Time

lb/lb-mole

29.22

12-PM-Base-1 Run Start Time Run Stop Time

Gas Analysis Data

Fuel Type Min. Fuel Factor Max. Fuel FactorGas, Natural

METHOD 3a - DETERMINATION OF DRY MOLECULAR WEIGHT BY ANALYZER

02/09/09

Sampling Location CTG-12 Stack

Project #

Operator

sie-19-middletown.ny-comp#2 # of Ports Used

CM

1 (gas probe)

Plant Name CPV Valley Energy Center Preliminary Run Date

Run Number

sie-19-middletown.ny-comp#1-CTG12-PM_BASE M3a - Mol Wt

Page 117: Division of Environmental Permits Floor

Standard Result Difference Pass/Fail

(g) (g) (g) (± 0.5 g)

500 499.6 -0.4 Pass

500 499.6 -0.4 Pass

500 499.7 -0.3 Pass

Date 02/09/19 Start Time 08:57 Stop Time 13:10

(Y)

(Vm) 83.109 dcf (Pb) 30.02 in Hg

(ts)avg 211 °F (Pstatic) -1.20 in H₂O

(tm)avg 64 °F (H)avg 0.45 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 485.70 602.30 721.90 911.40

Initial Value (Vi),(Wi) 352.20 602.20 721.60 899.10

Net Value (Vn),(Wn) 133.5 0.1 0.3 12.3

(Wt) 146.20 g (Vwsg(std)) 6.893 scf

(Vm(std)) 85.628 dscf (Bws(svp)) 97.47 %

(Bws(calc)) 7.45 % (Bws) 7.45 %

Date 02/10/19 Start Time 08:22 Stop Time 12:47

(Y)

(Vm) 91.990 dcf (Pb) 30.13 in Hg

(ts)avg 211 °F (Pstatic) -1.20 in H₂O

(tm)avg 62 °F (H)avg 0.45 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 481.40 602.50 708.90 879.20

Initial Value (Vi),(Wi) 351.60 601.80 708.80 863.70

Net Value (Vn),(Wn) 129.8 0.7 0.1 15.5

(Wt) 146.10 g (Vwsg(std)) 6.889 scf

(Vm(std)) 83.726 dscf (Bws(svp)) 97.44 %

(Bws(calc)) 7.60 % (Bws) 7.60 %

Date 02/10/19 Start Time 12:52 Stop Time 16:54

(Y)

(Vm) 84.300 dcf (Pb) 29.98 in Hg

(ts)avg 204 °F (Pstatic) -1.20 in H₂O

(tm)avg 71 °F (H)avg 0.45 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 468.50 610.40 717.80 934.80

Initial Value (Vi),(Wi) 349.40 610.30 717.70 919.60

Net Value (Vn),(Wn) 119.1 0.1 0.1 15.2

(Wt) 134.50 g (Vwsg(std)) 6.342 scf

(Vm(std)) 85.487 dscf (Bws(svp)) 85.88 %

(Bws(calc)) 6.91 % (Bws) 6.91 %

Preliminary Date 02/09/09

Test Day 1

Test Day 2

02/09/19

02/10/19

Date

Scale Number SAMP-SC-0016

Scale Daily Calibration

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0025 Meter Cal Factor 1.017

Total Meter Volume Barometric Pressure

Calc Moisture Content Final Moisture Content

Moisture Content Data

Run Number 12-PM-Base-3

Results

Total Weight Water Vol Weighed

Std Meter Volume Sat. Moisture Content

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0019 Meter Cal Factor 0.893

Total Meter Volume Barometric Pressure

Moisture Content Data

Run Number 12-PM-Base-2

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Total Meter Volume Barometric Pressure

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Moisture Content Data

Run Number 12-PM-Base-1

Meter Box Number Meter Cal Factorsamp-cp-0025 1.017

Sampling Location CTG-12 Stack

Project #

CMOperator

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 4 - DETERMINATION OF MOISTURE CONTENT IN STACK GASES

Plant Name CPV Valley Energy Center Preliminary Run Date 02/09/09

sie-19-middletown.ny-comp#1-CTG12-PM_BASE M4 - Moisture

Page 118: Division of Environmental Permits Floor

(Cp) 0.7350 5272/10

(ts) 210.8 °F

(tm) 63.5

(H@) 1.820 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.24 in H₂O

PASS Post 0.000 ft³/min@ 10.0 in Hg (Y) 1.017 (Bws) 7.45 %

Pitot Pre (+) 4.2 in H₂O for 30.0 sec (Md) 29.22 lb/lb-mole

Pre (-) 4.5 in H₂O for 30.0 sec (Dna) 0.1453 in (Qm) 0.75 acfm

Post (+) 5.0 in H₂O for 30.0 sec (Dni) 0.2184 in (K) 0.25

Post (-) 4.6 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 30.02 in Hg

Pre 0.144 0.146 0.146 PASS (Pstatic) -1.20 in H₂O

Post 0.144 0.146 0.146 PASS (Ps) 29.93 in Hg

(Pm) 30.15 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 08:57 End 13:10 Pre 352.2 602.2 721.6 899.1 ml

Post 485.7 602.3 721.9 911.4 ml

samp-cp-0025 samp-cp-0025 samp-cp-0025 samp-hp-0149 samp-hp-0149 samp-bh-0035 samp-cc-0027 1008 7767 samp-cp-0025

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 0.000 1.70 0.451 0.45 212 247 254 43 39 68 58 58 2.0 1.30 72.86 7.580 96.3 85.410

A-2 21.5 00:21:30 7.280 1.70 0.451 0.45 211 254 248 43 44 75 60 60 2.0 1.30 72.80 15.317 97.3 86.292

A-3 43.0 00:43:00 14.739 1.60 0.451 0.45 210 255 253 43 46 80 62 62 2.0 1.26 70.58 22.696 98.1 86.243

B-1 63.8 01:03:45 21.880 1.40 0.451 0.45 210 246 225 43 44 76 62 62 2.0 1.18 66.02 29.598 100.7 86.647

B-2 82.8 01:22:45 28.560 1.30 0.451 0.45 210 254 255 43 44 75 62 62 2.0 1.14 63.62 36.066 102.5 86.505

B-3 101.0 01:41:00 34.820 1.30 0.451 0.45 209 251 238 44 45 74 64 64 2.0 1.14 63.57 42.699 104.1 86.741

C-1 119.3 01:59:15 41.264 1.80 0.451 0.45 212 254 250 40 47 74 64 64 2.0 1.34 74.97 50.312 102.3 86.287

C-2 141.3 02:21:15 48.660 1.60 0.451 0.45 211 254 247 40 46 73 65 65 2.0 1.26 70.63 57.668 102.0 86.235

C-3 162.0 02:42:00 55.820 1.20 0.451 0.45 210 251 252 41 47 74 65 65 2.0 1.10 61.12 63.553 102.3 85.532

D-1 180.0 03:00:00 61.549 1.80 0.451 0.45 211 253 256 44 50 75 66 66 2.0 1.34 74.91 71.778 102.0 86.081

D-2 202.0 03:22:00 69.570 1.70 0.451 0.45 212 254 248 45 50 75 67 67 2.0 1.30 72.86 79.618 101.7 86.297

D-3 223.5 03:43:30 77.230 1.30 0.451 0.45 211 253 248 45 50 75 67 67 2.0 1.14 63.67 85.635 101.6 85.635

Last Pt 242.3 04:02:15 83.109

Final Val 242.3 04:02:15 83.109 Max Vac 2.0 85.635 101.6

1.53 0.45 211 252 248 43 46 75 64 64 1.24 68.97

Notes:

Identification Nos. samp-cp-0025

Nozzle Measurements

Meter Box Number

Meter Cal Factor

Average Meter Temp

Nozzle Number

Project # Run Number Average Stack Temp

Sampling Location Operator Pitot Coefficient / ID

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name Date Ideal Nozzle Diameter and IsoKinetic Factor SetupFilter #

18082933

0818-188

CPV Valley Energy Center

CTG-12 Stack

sie-19-middletown.ny-comp#2

02/09/19

CM

12-PM-Base-1

Stack Dry Molecular Weight

Estimated Orifice Flow Rate

Orifice Meter Coefficient

P to H Isokinetic Factor

Pressures

samp-cc-0027

samp-bh-0035

glass

PASS

Leak Checks

Square Root P

Stack Moisture Content

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Equipment

samp-cp-0025

3

120

samp-hp-0149

Absolute Meter Pressure

Run Time

Barometric Pressure

Stack Static Pressure

Barometer ID

SAMP-WE-0027

Scale ID

SAMP-SC-0016

Absolute Stack Pressure

Wash Volumes

Final Values

Average Values

64

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Isocalc - Run (1)

Page 119: Division of Environmental Permits Floor

(Cp) 0.7290 P-983/10

(ts) 210.9 °F

(tm) 62.3

(H@) 1.838 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.23 in H₂O

PASS Post 0.001 ft³/min@ 14.0 in Hg (Y) 0.893 (Bws) 7.60 %

Pitot Pre (+) 4.2 in H₂O for 30.0 sec (Md) 29.21 lb/lb-mole

Pre (-) 4.6 in H₂O for 30.0 sec (Dna) 0.1453 in (Qm) 0.35 acfm

Post (+) 5.0 in H₂O for 30.0 sec (Dni) 0.1510 in (K) 0.25

Post (-) 4.0 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 30.13 in Hg

Pre 0.144 0.146 0.146 PASS (Pstatic) -1.20 in H₂O

Post 0.144 0.146 0.146 PASS (Ps) 30.04 in Hg

(Pm) 30.27 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 08:22 End 12:47 Pre 351.6 601.8 708.8 863.7 ml

Post 481.4 602.5 708.9 879.2 ml

samp-cp-0019 samp-cp-0019 samp-cp-0019 samp-hp-0148 samp-hp-0148 samp-bh-0034 samp-cp-0012 1030 7770 samp-cp-0019

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 446.340 1.70 0.451 0.45 220 240 246 37 43 68 52 52 2.0 1.30 72.60 7.919 103.2 88.694

A-2 21.3 00:21:15 454.870 1.70 0.451 0.45 217 237 246 42 49 68 55 55 2.0 1.30 72.44 15.783 102.7 88.384

A-3 42.5 00:42:30 463.390 1.50 0.451 0.45 213 241 248 47 55 70 57 57 2.0 1.22 67.84 23.221 104.7 88.425

B-1 62.5 01:02:30 471.480 1.40 0.451 0.45 211 239 249 46 57 70 58 58 2.0 1.18 65.45 29.993 105.8 87.857

B-2 81.3 01:21:15 478.860 1.20 0.451 0.45 212 240 242 45 56 70 59 59 2.0 1.10 60.64 35.644 106.0 86.125

B-3 98.5 01:38:30 485.030 1.30 0.451 0.45 210 238 244 42 54 69 60 60 2.0 1.14 63.02 41.604 105.7 84.994

C-1 116.5 01:56:30 491.550 1.80 0.451 0.45 210 240 250 35 50 68 62 62 2.0 1.34 74.15 49.299 104.0 84.868

C-2 138.3 02:18:15 500.000 1.60 0.451 0.45 208 243 246 41 56 71 67 67 2.0 1.26 69.81 56.343 103.1 84.470

C-3 158.8 02:38:45 507.810 1.20 0.451 0.45 206 241 245 40 55 71 67 67 2.0 1.10 60.37 61.728 102.8 83.236

D-1 176.5 02:56:30 513.780 1.80 0.451 0.45 211 242 249 47 52 68 69 69 2.0 1.34 74.21 69.940 102.5 83.964

D-2 198.3 03:18:15 522.920 1.60 0.451 0.45 208 238 243 47 56 71 70 70 2.0 1.26 69.81 77.052 102.1 83.833

D-3 218.8 03:38:45 530.850 1.40 0.451 0.45 205 244 244 46 58 72 71 71 2.0 1.18 65.15 83.748 102.4 83.748

Last Pt 238.0 03:58:00 538.330

Final Val 238.0 03:58:00 538.330 Max Vac 2.0 83.748 102.4

1.52 0.45 211 240 246 43 53 70 62 62 1.23 67.96

Notes:

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0019

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

Average Values

62

Final Values

Run Time

Wash Volumes

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0034 Stack Static Pressure

SAMP-SC-0016

samp-cp-0012 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Location CTG-12 Stack Operator CM 18082935

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/10/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Project # sie-19-middletown.ny-comp#2 Run Number 12-PM-Base-2 0818-188 Average Stack Temp

samp-cp-0019 Square Root PMeter Box Number

Sampling Equipment

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-hp-0148

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Isocalc - Run (2)

Page 120: Division of Environmental Permits Floor

(Cp) 0.7350 5272/10

(ts) 204.4 °F

(tm) 71.2

(H@) 1.820 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.24 in H₂O

PASS Post 0.000 ft³/min@ 12.0 in Hg (Y) 1.017 (Bws) 6.91 %

Pitot Pre (+) 4.7 in H₂O for 30.0 sec (Md) 29.19 lb/lb-mole

Pre (-) 4.2 in H₂O for 30.0 sec (Dna) 0.1420 in (Qm) 0.35 acfm

Post (+) 4.5 in H₂O for 30.0 sec (Dni) 0.1480 in (K) 0.24

Post (-) 4.3 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.98 in Hg

Pre 0.141 0.143 0.142 PASS (Pstatic) -1.20 in H₂O

Post 0.141 0.143 0.142 PASS (Ps) 29.89 in Hg

(Pm) 30.11 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 12:52 End 16:54 Pre 349.4 610.3 717.7 919.6 ml

Post 468.5 610.4 717.8 934.8 ml

samp-cp-0025 samp-cp-0025 samp-cp-0025 samp-hp-0149 samp-hp-0149 samp-bh-0035 samp-cc-0027 1008 7767 samp-cp-0025

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 538.550 1.80 0.451 0.45 206 229 240 45 56 68 70 70 2.0 1.34 74.64 8.517 109.1 95.466

A-2 21.5 00:21:30 546.930 1.70 0.451 0.45 204 241 242 47 52 69 71 71 2.0 1.30 72.43 16.206 107.1 92.441

A-3 42.3 00:42:15 554.510 1.60 0.451 0.45 204 240 241 48 53 69 71 71 2.0 1.26 70.27 23.733 107.5 91.513

B-1 62.5 01:02:30 561.930 1.40 0.451 0.45 203 242 243 47 52 69 71 71 2.0 1.18 65.68 30.357 107.8 89.767

B-2 81.5 01:21:30 568.460 1.30 0.451 0.45 204 243 243 47 48 70 71 71 2.0 1.14 63.34 36.768 108.8 88.832

B-3 99.8 01:39:45 574.780 1.30 0.451 0.45 203 238 240 45 45 69 71 71 2.0 1.14 63.29 42.590 108.1 86.986

C-1 118.0 01:58:00 580.520 1.80 0.451 0.45 206 244 245 50 52 70 72 72 2.0 1.34 74.64 49.860 105.6 85.831

C-2 140.0 02:20:00 587.700 1.60 0.451 0.45 204 241 243 55 55 71 71 71 2.0 1.26 70.27 56.464 104.1 84.652

C-3 160.8 02:40:45 594.210 1.30 0.451 0.45 205 242 240 58 59 72 72 72 2.0 1.14 63.39 62.883 104.8 84.428

D-1 179.5 02:59:30 600.550 1.80 0.451 0.45 204 244 237 56 57 71 71 71 2.0 1.34 74.53 71.627 105.3 85.668

D-2 201.5 03:21:30 609.170 1.50 0.451 0.45 205 244 243 58 60 72 71 71 2.0 1.22 68.09 78.799 105.6 85.736

D-3 221.5 03:41:30 616.240 1.40 0.451 0.45 205 232 238 59 61 72 72 72 2.0 1.18 65.78 85.492 105.7 85.492

Last Pt 241.0 04:01:00 622.850

Final Val 241.0 04:01:00 622.850 Max Vac 2.0 85.492 105.7

1.54 0.45 204 240 241 51 54 70 71 71 1.24 68.86

Notes:

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0025

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

Average Values

71

Final Values

Run Time

Wash Volumes

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0035 Stack Static Pressure

SAMP-SC-0016

samp-cc-0027 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Location CTG-12 Stack Operator CM 18082941

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/10/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Project # sie-19-middletown.ny-comp#2 Run Number 12-PM-Base-3 0818-188 Average Stack Temp

samp-cp-0025 Square Root PMeter Box Number

Sampling Equipment

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-hp-0149

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Isocalc - Run (3)

Page 121: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-12 Base Load

Opacity Data

Page 122: Division of Environmental Permits Floor
Page 123: Division of Environmental Permits Floor
Page 124: Division of Environmental Permits Floor
Page 125: Division of Environmental Permits Floor
Page 126: Division of Environmental Permits Floor
Page 127: Division of Environmental Permits Floor
Page 128: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-12 Base Load wDB

Unit Operating Data

Page 129: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 12 CTG-2 W/DB Run 1DCS Data - 20190208 - 0900-1750

Unit 12 GT Power Unit 12 GT PowerUnit 12 Total GT

Gas FlowUnit 12 HRSG DB Fuel Flow

Unit 12 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 12HAD00EU001 12MKA01EU902A 12MBP10CF910 12HHA10CF001 12HNE10CQ109 12MBL05CT1012019/02/08 09:02:00:000 208.713 97.7 89.953 9.821 12.57 34.92019/02/08 09:03:00:000 208.713 97.6 89.789 9.821 12.57 35.42019/02/08 09:04:00:000 208.224 97.7 89.789 9.821 12.57 35.92019/02/08 09:05:00:000 208.224 98.0 89.638 9.821 12.59 35.92019/02/08 09:06:00:000 208.224 98.1 89.736 9.821 12.59 36.32019/02/08 09:07:00:000 208.845 98.2 89.947 9.821 12.59 36.52019/02/08 09:08:00:000 208.845 98.1 90.019 9.821 12.59 36.52019/02/08 09:09:00:000 208.845 98.1 89.859 9.821 12.59 36.52019/02/08 09:10:00:000 208.845 98.0 90.036 9.821 12.59 36.52019/02/08 09:11:00:000 208.845 98.1 90.036 9.821 12.59 36.32019/02/08 09:12:00:000 209.298 98.0 89.960 9.821 12.56 36.12019/02/08 09:13:00:000 208.882 98.0 89.960 9.821 12.56 35.92019/02/08 09:14:00:000 208.882 98.0 89.960 9.821 12.59 35.92019/02/08 09:15:00:000 208.982 98.0 89.960 9.821 12.59 35.62019/02/08 09:16:00:000 208.982 98.0 89.960 9.821 12.58 35.62019/02/08 09:17:00:000 209.345 97.9 89.960 9.821 20.93 35.42019/02/08 09:18:00:000 209.111 97.8 89.960 9.821 21.02 35.42019/02/08 09:19:00:000 209.111 97.8 89.785 9.821 1.11 35.12019/02/08 09:20:00:000 209.111 97.6 89.946 9.821 0.02 35.12019/02/08 09:21:00:000 208.762 97.6 89.839 9.821 0.00 35.12019/02/08 09:22:00:000 208.762 97.7 89.839 9.821 12.51 35.12019/02/08 09:23:00:000 208.634 97.8 89.923 9.821 12.57 35.12019/02/08 09:24:00:000 208.878 97.8 89.864 9.821 12.57 35.12019/02/08 09:25:00:000 208.878 97.7 89.913 9.821 12.57 35.12019/02/08 09:26:00:000 208.494 97.7 89.823 9.821 12.57 35.12019/02/08 09:27:00:000 208.494 97.8 89.823 9.821 12.57 35.42019/02/08 09:28:00:000 208.494 97.8 89.823 9.821 12.57 35.62019/02/08 09:29:00:000 208.494 97.9 89.823 9.817 12.57 35.92019/02/08 09:30:00:000 208.494 98.0 89.974 9.817 12.57 36.12019/02/08 09:31:00:000 208.911 98.0 89.876 9.817 12.58 36.32019/02/08 09:32:00:000 208.911 98.0 89.876 9.817 12.58 36.32019/02/08 09:33:00:000 208.911 97.9 89.980 9.817 12.58 36.12019/02/08 09:34:00:000 208.911 97.9 89.855 9.817 12.58 35.92019/02/08 09:35:00:000 208.911 97.8 89.974 9.817 12.58 35.92019/02/08 09:36:00:000 208.911 97.9 89.837 9.817 12.58 35.92019/02/08 09:37:00:000 208.911 97.8 89.874 9.817 12.58 35.92019/02/08 09:38:00:000 208.911 97.7 89.874 9.826 12.58 35.62019/02/08 09:39:00:000 208.697 97.7 89.754 9.826 12.58 35.62019/02/08 09:40:00:000 208.697 97.8 89.927 9.826 12.59 35.62019/02/08 09:41:00:000 208.697 97.8 89.797 9.826 12.59 35.62019/02/08 09:42:00:000 208.697 98.0 89.797 9.826 12.59 35.62019/02/08 09:43:00:000 208.697 97.9 89.609 9.826 12.59 35.92019/02/08 09:44:00:000 208.697 97.8 89.764 9.826 12.59 35.92019/02/08 09:45:00:000 208.697 97.8 89.999 9.826 12.59 35.92019/02/08 09:46:00:000 208.697 97.9 89.822 9.826 12.57 35.92019/02/08 09:47:00:000 208.697 97.8 89.822 9.826 12.57 35.92019/02/08 09:48:00:000 208.697 97.6 89.822 9.826 12.57 35.92019/02/08 09:49:00:000 208.298 97.8 89.822 9.826 12.60 36.12019/02/08 09:50:00:000 208.298 97.8 89.822 9.826 12.60 36.12019/02/08 09:51:00:000 208.586 97.9 89.734 9.826 12.60 36.12019/02/08 09:52:00:000 208.586 97.7 89.840 9.826 12.56 36.12019/02/08 09:53:00:000 208.586 97.8 89.840 9.826 12.60 36.12019/02/08 09:54:00:000 208.586 97.8 89.803 9.826 12.60 36.12019/02/08 09:55:00:000 208.586 97.9 89.803 9.826 12.57 36.12019/02/08 09:56:00:000 208.248 97.9 89.697 9.817 12.57 36.12019/02/08 09:57:00:000 208.248 97.9 89.697 9.817 12.57 36.32019/02/08 09:58:00:000 208.248 98.0 89.697 9.817 12.60 36.62019/02/08 09:59:00:000 208.248 98.1 89.713 9.817 12.60 36.62019/02/08 10:00:00:000 208.248 97.9 89.713 9.817 12.60 36.82019/02/08 10:01:00:000 208.248 98.1 89.799 9.817 12.60 37.02019/02/08 10:02:00:000 208.248 98.0 89.799 9.817 12.60 37.02019/02/08 10:03:00:000 208.248 98.0 89.823 9.836 12.60 36.82019/02/08 10:04:00:000 208.481 97.9 89.615 9.836 12.58 36.82019/02/08 10:05:00:000 208.481 97.9 89.771 9.836 12.58 36.82019/02/08 10:06:00:000 208.481 98.1 89.771 9.816 12.58 36.82019/02/08 10:07:00:000 208.481 97.9 89.885 9.816 12.58 36.82019/02/08 10:08:00:000 208.481 98.0 89.726 9.816 12.58 36.82019/02/08 10:09:00:000 208.205 98.0 89.726 9.816 12.58 36.82019/02/08 10:10:00:000 208.205 98.0 89.726 9.816 12.58 36.82019/02/08 10:11:00:000 208.374 98.0 89.811 9.816 12.58 36.82019/02/08 10:12:00:000 208.374 98.0 89.656 9.816 12.58 37.0

Page 130: Division of Environmental Permits Floor

2019/02/08 10:13:00:000 208.069 98.0 89.791 9.816 12.58 37.02019/02/08 10:14:00:000 208.069 98.0 89.625 9.816 12.58 37.22019/02/08 10:15:00:000 208.069 98.1 89.706 9.829 12.58 37.22019/02/08 10:16:00:000 208.069 98.1 89.834 9.829 12.58 37.22019/02/08 10:17:00:000 208.069 98.2 89.743 9.829 12.58 37.22019/02/08 10:18:00:000 208.327 98.1 89.926 9.829 12.58 37.22019/02/08 10:19:00:000 208.327 98.1 89.726 9.829 12.58 37.22019/02/08 10:20:00:000 208.033 98.0 89.726 9.829 12.58 37.22019/02/08 10:21:00:000 208.033 98.1 89.873 9.829 12.58 37.42019/02/08 10:22:00:000 208.033 98.1 89.740 9.829 12.58 37.42019/02/08 10:23:00:000 208.033 98.1 89.740 9.829 12.58 37.72019/02/08 10:24:00:000 208.033 98.2 89.740 9.829 12.58 37.72019/02/08 10:25:00:000 208.033 98.2 89.740 9.829 12.58 37.92019/02/08 10:26:00:000 208.033 98.1 89.740 9.829 12.58 37.92019/02/08 10:27:00:000 208.033 98.2 89.740 9.822 12.58 38.22019/02/08 10:28:00:000 207.841 98.1 89.489 9.822 12.58 38.22019/02/08 10:29:00:000 207.841 98.4 89.794 9.822 12.58 38.42019/02/08 10:30:00:000 207.841 98.3 89.663 9.822 12.58 38.42019/02/08 10:31:00:000 207.841 98.2 89.663 9.822 12.58 38.42019/02/08 10:32:00:000 207.403 98.4 89.663 9.822 12.56 38.72019/02/08 10:33:00:000 208.042 98.2 89.807 9.822 12.60 38.92019/02/08 10:34:00:000 207.945 98.3 89.664 9.822 12.60 38.92019/02/08 10:35:00:000 207.561 98.2 89.664 9.822 12.58 39.12019/02/08 10:36:00:000 207.561 98.3 89.582 9.822 12.58 39.12019/02/08 10:37:00:000 207.561 98.4 89.582 9.822 12.58 39.32019/02/08 10:38:00:000 207.561 98.3 89.582 9.822 12.58 39.52019/02/08 10:39:00:000 207.561 98.3 89.582 9.822 12.58 39.52019/02/08 10:40:00:000 207.236 98.3 89.559 9.822 12.58 39.52019/02/08 10:41:00:000 207.236 98.3 89.797 9.822 12.60 39.52019/02/08 10:42:00:000 207.584 98.4 89.737 9.821 12.60 39.52019/02/08 10:43:00:000 207.584 98.3 89.630 9.821 12.60 39.82019/02/08 10:44:00:000 207.584 98.4 89.503 9.821 12.58 39.82019/02/08 10:45:00:000 207.223 98.3 89.552 9.821 12.58 40.02019/02/08 10:46:00:000 207.467 98.4 89.510 9.821 12.58 40.02019/02/08 10:47:00:000 207.467 98.3 89.632 9.855 12.60 40.32019/02/08 10:48:00:000 207.467 98.2 89.531 9.855 12.60 40.32019/02/08 10:49:00:000 207.467 98.2 89.531 9.855 12.57 40.02019/02/08 10:50:00:000 207.467 98.2 89.531 9.855 12.57 40.32019/02/08 10:51:00:000 207.467 98.2 89.531 9.855 12.57 40.32019/02/08 10:52:00:000 207.467 98.3 89.385 9.855 12.57 40.32019/02/08 10:53:00:000 207.206 98.2 89.462 9.855 12.60 40.52019/02/08 10:54:00:000 206.934 98.2 89.364 9.855 12.60 40.72019/02/08 10:55:00:000 206.934 98.3 89.364 9.855 12.60 41.02019/02/08 10:56:00:000 206.934 98.3 89.436 9.871 12.60 41.02019/02/08 10:57:00:000 206.934 98.4 89.361 9.871 12.60 41.02019/02/08 10:58:00:000 206.666 98.4 89.361 9.871 12.60 41.72019/02/08 10:59:00:000 206.666 98.4 89.263 9.871 12.57 41.72019/02/08 11:00:00:000 206.666 98.5 89.339 9.871 12.57 41.92019/02/08 11:01:00:000 206.879 98.5 89.451 9.871 12.60 42.12019/02/08 11:02:00:000 206.879 98.4 89.330 9.871 12.60 42.32019/02/08 11:03:00:000 206.879 98.5 89.294 9.855 12.60 42.32019/02/08 11:04:00:000 206.879 98.4 89.483 9.855 12.59 42.32019/02/08 11:05:00:000 206.879 98.4 89.360 9.855 12.59 42.32019/02/08 11:06:00:000 206.879 98.6 89.360 9.855 12.59 42.32019/02/08 11:07:00:000 206.638 98.4 89.434 9.855 12.59 42.32019/02/08 11:08:00:000 206.638 98.6 89.333 9.855 12.61 42.62019/02/08 11:09:00:000 206.638 98.5 89.333 9.855 12.61 42.62019/02/08 11:10:00:000 206.638 98.6 89.192 9.855 12.59 42.62019/02/08 11:11:00:000 206.566 98.6 89.350 9.855 12.59 42.32019/02/08 11:12:00:000 206.566 98.6 89.350 9.855 12.59 42.62019/02/08 11:13:00:000 206.870 98.7 89.350 9.855 12.59 42.62019/02/08 11:14:00:000 206.870 98.6 89.350 9.855 12.59 42.62019/02/08 11:15:00:000 206.870 98.6 89.350 9.855 12.61 42.62019/02/08 11:16:00:000 206.596 98.5 89.350 9.855 12.61 42.62019/02/08 11:17:00:000 206.596 98.6 89.350 9.855 12.57 42.82019/02/08 11:18:00:000 206.596 98.7 89.350 9.855 12.60 42.82019/02/08 11:19:00:000 206.941 98.6 89.263 9.855 12.60 42.82019/02/08 11:20:00:000 206.779 98.6 89.401 9.855 12.60 42.82019/02/08 11:21:00:000 206.779 98.6 89.277 9.855 12.60 42.82019/02/08 11:22:00:000 206.779 98.5 89.339 9.855 12.60 42.82019/02/08 11:23:00:000 206.779 98.5 89.372 9.855 12.60 42.82019/02/08 11:24:00:000 206.779 98.5 89.372 9.855 12.58 42.82019/02/08 11:25:00:000 206.530 98.6 89.253 9.842 12.58 42.82019/02/08 11:26:00:000 206.530 98.8 89.253 9.842 12.58 43.12019/02/08 11:27:00:000 206.789 98.9 89.220 9.842 12.58 43.12019/02/08 11:28:00:000 206.789 98.8 89.452 9.842 12.58 43.12019/02/08 11:29:00:000 206.789 98.7 89.371 10.177 12.60 43.12019/02/08 11:30:00:000 206.789 98.4 89.371 10.327 12.60 43.32019/02/08 11:31:00:000 206.789 98.6 89.265 10.327 12.55 43.52019/02/08 11:32:00:000 206.681 98.7 89.265 10.327 12.55 43.82019/02/08 11:33:00:000 205.999 98.6 89.265 10.350 12.55 43.8

Page 131: Division of Environmental Permits Floor

2019/02/08 11:34:00:000 206.370 98.7 89.290 10.350 12.55 44.02019/02/08 11:35:00:000 206.370 98.7 89.111 10.350 12.55 44.72019/02/08 11:36:00:000 206.028 98.9 89.168 10.350 12.55 44.72019/02/08 11:37:00:000 206.028 98.7 89.168 10.350 12.55 45.12019/02/08 11:38:00:000 206.028 99.0 89.020 10.350 12.55 45.92019/02/08 11:39:00:000 206.028 99.0 89.074 10.350 12.57 45.92019/02/08 11:40:00:000 206.028 99.0 89.074 10.350 12.57 46.62019/02/08 11:41:00:000 205.894 99.0 89.074 10.350 12.56 46.62019/02/08 11:42:00:000 205.894 99.0 89.074 10.342 12.56 46.62019/02/08 11:43:00:000 205.894 98.8 88.896 10.342 12.56 46.82019/02/08 11:44:00:000 204.804 98.9 88.652 10.342 12.53 47.92019/02/08 11:45:00:000 204.283 99.0 88.369 10.342 12.53 49.32019/02/08 11:46:00:000 203.886 99.4 88.558 10.342 12.58 50.72019/02/08 11:47:00:000 204.195 99.3 88.558 10.342 12.58 51.52019/02/08 11:48:00:000 203.238 99.0 88.205 10.342 12.58 53.12019/02/08 11:49:00:000 202.714 99.5 87.989 10.342 12.58 54.22019/02/08 11:50:00:000 202.714 99.5 88.162 10.342 12.58 54.72019/02/08 11:51:00:000 203.177 99.5 88.081 10.342 12.60 54.72019/02/08 11:52:00:000 203.177 99.6 88.215 10.342 12.60 54.92019/02/08 11:53:00:000 202.847 99.5 88.154 10.342 12.60 54.72019/02/08 11:54:00:000 202.203 99.3 88.024 10.342 12.60 54.72019/02/08 11:55:00:000 202.792 99.7 88.021 10.342 12.64 55.62019/02/08 11:56:00:000 202.792 99.8 88.021 10.331 12.64 55.62019/02/08 11:57:00:000 202.792 99.6 87.987 10.331 12.59 55.92019/02/08 11:58:00:000 202.493 99.4 87.774 10.331 12.59 56.62019/02/08 11:59:00:000 202.006 99.3 87.774 10.331 12.59 56.62019/02/08 12:00:00:000 201.142 99.6 87.614 10.331 12.59 57.52019/02/08 12:01:00:000 202.888 100.1 87.839 10.331 12.63 57.52019/02/08 12:02:00:000 203.290 99.7 88.179 10.331 12.63 57.52019/02/08 12:03:00:000 203.290 99.4 88.134 10.331 12.63 56.62019/02/08 12:04:00:000 202.216 99.5 87.719 10.331 12.58 57.02019/02/08 12:05:00:000 201.380 99.2 87.719 10.331 12.62 57.52019/02/08 12:06:00:000 201.993 99.7 87.719 10.331 12.62 58.02019/02/08 12:07:00:000 201.993 99.6 87.859 10.331 12.62 58.02019/02/08 12:08:00:000 201.579 99.7 87.689 10.331 12.60 58.02019/02/08 12:09:00:000 202.204 99.6 87.930 10.331 12.60 58.22019/02/08 12:10:00:000 202.204 99.6 87.863 10.331 12.64 58.02019/02/08 12:11:00:000 202.204 99.7 87.863 10.331 12.62 57.02019/02/08 12:12:00:000 202.204 99.4 87.863 10.331 12.62 57.02019/02/08 12:13:00:000 201.614 99.4 87.664 10.331 12.62 56.82019/02/08 12:14:00:000 202.052 99.6 87.916 10.331 12.62 56.82019/02/08 12:15:00:000 202.052 99.5 87.745 10.331 12.62 56.82019/02/08 12:16:00:000 202.052 99.5 87.745 10.331 12.62 56.82019/02/08 12:17:00:000 201.427 99.5 87.564 10.331 12.62 57.22019/02/08 12:18:00:000 201.427 99.5 87.719 10.331 12.62 57.52019/02/08 12:19:00:000 202.198 99.6 87.889 10.331 12.62 57.52019/02/08 12:20:00:000 202.198 99.5 87.889 10.331 12.62 57.22019/02/08 12:21:00:000 202.198 99.4 87.706 10.331 12.62 57.02019/02/08 12:22:00:000 201.953 99.5 87.795 10.331 12.62 57.02019/02/08 12:23:00:000 201.953 99.5 87.693 10.331 12.62 57.02019/02/08 12:24:00:000 201.953 99.8 87.900 10.337 12.65 57.52019/02/08 12:25:00:000 203.048 99.7 88.094 10.337 12.65 56.82019/02/08 12:26:00:000 201.773 99.1 87.910 10.337 12.61 56.82019/02/08 12:27:00:000 200.977 99.3 87.616 10.337 12.61 58.02019/02/08 12:28:00:000 200.977 99.4 87.524 10.337 12.61 58.02019/02/08 12:29:00:000 201.518 99.4 87.524 10.337 12.64 58.22019/02/08 12:30:00:000 201.518 99.6 87.886 10.337 12.64 58.42019/02/08 12:31:00:000 201.518 99.4 87.602 10.337 12.60 58.42019/02/08 12:32:00:000 201.363 99.5 87.602 10.337 12.60 58.72019/02/08 12:33:00:000 201.934 99.7 87.890 10.337 12.60 58.72019/02/08 12:34:00:000 202.376 99.6 87.998 10.337 12.65 58.42019/02/08 12:35:00:000 201.547 99.5 87.726 10.337 12.61 58.02019/02/08 12:36:00:000 202.575 99.6 88.017 10.337 12.61 57.22019/02/08 12:37:00:000 203.187 99.7 88.341 10.337 12.67 57.22019/02/08 12:38:00:000 203.187 99.4 88.174 10.337 12.60 56.62019/02/08 12:39:00:000 202.305 99.3 88.039 10.326 12.60 56.62019/02/08 12:40:00:000 202.305 99.3 87.983 10.326 12.62 56.42019/02/08 12:41:00:000 202.305 99.3 87.763 10.326 12.62 56.42019/02/08 12:42:00:000 202.305 99.3 87.967 10.326 12.62 56.42019/02/08 12:43:00:000 201.858 99.5 87.653 10.326 12.62 57.52019/02/08 12:44:00:000 201.858 99.6 87.819 10.337 12.65 58.02019/02/08 12:45:00:000 201.858 99.6 87.819 10.337 12.65 58.02019/02/08 12:46:00:000 201.858 99.4 87.858 10.337 12.63 58.92019/02/08 12:47:00:000 201.858 99.8 87.714 10.337 12.63 58.92019/02/08 12:48:00:000 202.855 100.0 88.232 10.337 12.63 58.42019/02/08 12:49:00:000 203.537 99.5 88.513 10.337 12.63 56.62019/02/08 12:50:00:000 203.537 99.3 88.266 10.337 12.59 55.42019/02/08 12:51:00:000 203.537 99.5 88.089 10.337 12.59 54.92019/02/08 12:52:00:000 202.389 99.4 87.851 10.337 12.59 55.62019/02/08 12:53:00:000 201.925 99.3 87.602 10.337 12.59 56.82019/02/08 12:54:00:000 201.925 99.9 87.946 10.337 12.63 57.5

Page 132: Division of Environmental Permits Floor

2019/02/08 12:55:00:000 202.932 99.5 88.158 10.320 12.63 56.82019/02/08 12:56:00:000 202.747 99.6 88.069 10.320 12.63 56.82019/02/08 12:57:00:000 202.747 99.5 88.069 10.320 12.63 56.12019/02/08 12:58:00:000 202.747 100.1 88.069 10.320 12.60 56.12019/02/08 12:59:00:000 203.487 99.3 88.167 10.320 12.60 55.12019/02/08 13:00:00:000 202.658 99.2 87.897 10.320 12.60 55.12019/02/08 13:01:00:000 202.043 99.3 87.654 10.333 12.65 56.62019/02/08 13:02:00:000 201.518 99.8 87.781 10.333 12.65 57.72019/02/08 13:03:00:000 202.412 99.7 88.013 10.333 12.65 57.72019/02/08 13:04:00:000 202.412 99.8 87.865 10.333 12.64 57.52019/02/08 13:05:00:000 202.412 99.7 87.990 10.333 12.59 56.82019/02/08 13:06:00:000 202.412 99.5 87.880 10.333 12.63 56.82019/02/08 13:07:00:000 202.412 99.3 87.880 10.333 12.63 56.42019/02/08 13:08:00:000 202.403 99.7 87.880 10.333 12.63 56.62019/02/08 13:09:00:000 202.403 99.7 87.880 10.333 12.63 56.82019/02/08 13:10:00:000 202.403 99.5 88.026 10.333 12.63 57.52019/02/08 13:11:00:000 202.403 99.8 87.840 10.333 12.62 57.52019/02/08 13:12:00:000 202.403 99.7 88.015 10.333 12.62 56.62019/02/08 13:13:00:000 202.403 99.6 88.015 10.333 12.62 56.62019/02/08 13:14:00:000 202.758 99.4 88.015 10.333 12.62 56.82019/02/08 13:15:00:000 202.214 99.6 87.970 10.333 12.62 56.8AVERAGE: 205.83 98.68 89.01 10.04 12.52 45.30

Page 133: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 12 CTG-2 W/DB Run 2DCS Data - 20190208 - 0900-1750

Unit 12 GT Power Unit 12 GT PowerUnit 12 Total GT

Gas FlowUnit 12 HRSG DB Fuel Flow

Unit 12 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 12HAD00EU001 12MKA01EU902A 12MBP10CF910 12HHA10CF001 12HNE10CQ109 12MBL05CT1012019/02/08 09:02:00:000 208.713 97.7 89.953 9.821 12.57 34.92019/02/08 09:03:00:000 208.713 97.6 89.789 9.821 12.57 35.42019/02/08 09:04:00:000 208.224 97.7 89.789 9.821 12.57 35.92019/02/08 09:05:00:000 208.224 98.0 89.638 9.821 12.59 35.92019/02/08 09:06:00:000 208.224 98.1 89.736 9.821 12.59 36.32019/02/08 09:07:00:000 208.845 98.2 89.947 9.821 12.59 36.52019/02/08 09:08:00:000 208.845 98.1 90.019 9.821 12.59 36.52019/02/08 09:09:00:000 208.845 98.1 89.859 9.821 12.59 36.52019/02/08 09:10:00:000 208.845 98.0 90.036 9.821 12.59 36.52019/02/08 09:11:00:000 208.845 98.1 90.036 9.821 12.59 36.32019/02/08 09:12:00:000 209.298 98.0 89.960 9.821 12.56 36.12019/02/08 09:13:00:000 208.882 98.0 89.960 9.821 12.56 35.92019/02/08 09:14:00:000 208.882 98.0 89.960 9.821 12.59 35.92019/02/08 09:15:00:000 208.982 98.0 89.960 9.821 12.59 35.62019/02/08 09:16:00:000 208.982 98.0 89.960 9.821 12.58 35.62019/02/08 09:17:00:000 209.345 97.9 89.960 9.821 20.93 35.42019/02/08 09:18:00:000 209.111 97.8 89.960 9.821 21.02 35.42019/02/08 09:19:00:000 209.111 97.8 89.785 9.821 1.11 35.12019/02/08 09:20:00:000 209.111 97.6 89.946 9.821 0.02 35.12019/02/08 09:21:00:000 208.762 97.6 89.839 9.821 0.00 35.12019/02/08 09:22:00:000 208.762 97.7 89.839 9.821 12.51 35.12019/02/08 09:23:00:000 208.634 97.8 89.923 9.821 12.57 35.12019/02/08 09:24:00:000 208.878 97.8 89.864 9.821 12.57 35.12019/02/08 09:25:00:000 208.878 97.7 89.913 9.821 12.57 35.12019/02/08 09:26:00:000 208.494 97.7 89.823 9.821 12.57 35.12019/02/08 09:27:00:000 208.494 97.8 89.823 9.821 12.57 35.42019/02/08 09:28:00:000 208.494 97.8 89.823 9.821 12.57 35.62019/02/08 09:29:00:000 208.494 97.9 89.823 9.817 12.57 35.92019/02/08 09:30:00:000 208.494 98.0 89.974 9.817 12.57 36.12019/02/08 09:31:00:000 208.911 98.0 89.876 9.817 12.58 36.32019/02/08 09:32:00:000 208.911 98.0 89.876 9.817 12.58 36.32019/02/08 09:33:00:000 208.911 97.9 89.980 9.817 12.58 36.12019/02/08 09:34:00:000 208.911 97.9 89.855 9.817 12.58 35.92019/02/08 09:35:00:000 208.911 97.8 89.974 9.817 12.58 35.92019/02/08 09:36:00:000 208.911 97.9 89.837 9.817 12.58 35.92019/02/08 09:37:00:000 208.911 97.8 89.874 9.817 12.58 35.92019/02/08 09:38:00:000 208.911 97.7 89.874 9.826 12.58 35.62019/02/08 09:39:00:000 208.697 97.7 89.754 9.826 12.58 35.62019/02/08 09:40:00:000 208.697 97.8 89.927 9.826 12.59 35.62019/02/08 09:41:00:000 208.697 97.8 89.797 9.826 12.59 35.62019/02/08 09:42:00:000 208.697 98.0 89.797 9.826 12.59 35.62019/02/08 09:43:00:000 208.697 97.9 89.609 9.826 12.59 35.92019/02/08 09:44:00:000 208.697 97.8 89.764 9.826 12.59 35.92019/02/08 09:45:00:000 208.697 97.8 89.999 9.826 12.59 35.92019/02/08 09:46:00:000 208.697 97.9 89.822 9.826 12.57 35.92019/02/08 09:47:00:000 208.697 97.8 89.822 9.826 12.57 35.92019/02/08 09:48:00:000 208.697 97.6 89.822 9.826 12.57 35.92019/02/08 09:49:00:000 208.298 97.8 89.822 9.826 12.60 36.12019/02/08 09:50:00:000 208.298 97.8 89.822 9.826 12.60 36.12019/02/08 09:51:00:000 208.586 97.9 89.734 9.826 12.60 36.12019/02/08 09:52:00:000 208.586 97.7 89.840 9.826 12.56 36.12019/02/08 09:53:00:000 208.586 97.8 89.840 9.826 12.60 36.12019/02/08 09:54:00:000 208.586 97.8 89.803 9.826 12.60 36.12019/02/08 09:55:00:000 208.586 97.9 89.803 9.826 12.57 36.12019/02/08 09:56:00:000 208.248 97.9 89.697 9.817 12.57 36.12019/02/08 09:57:00:000 208.248 97.9 89.697 9.817 12.57 36.32019/02/08 09:58:00:000 208.248 98.0 89.697 9.817 12.60 36.62019/02/08 09:59:00:000 208.248 98.1 89.713 9.817 12.60 36.62019/02/08 10:00:00:000 208.248 97.9 89.713 9.817 12.60 36.82019/02/08 10:01:00:000 208.248 98.1 89.799 9.817 12.60 37.02019/02/08 10:02:00:000 208.248 98.0 89.799 9.817 12.60 37.02019/02/08 10:03:00:000 208.248 98.0 89.823 9.836 12.60 36.82019/02/08 10:04:00:000 208.481 97.9 89.615 9.836 12.58 36.82019/02/08 10:05:00:000 208.481 97.9 89.771 9.836 12.58 36.82019/02/08 10:06:00:000 208.481 98.1 89.771 9.816 12.58 36.82019/02/08 10:07:00:000 208.481 97.9 89.885 9.816 12.58 36.82019/02/08 10:08:00:000 208.481 98.0 89.726 9.816 12.58 36.82019/02/08 10:09:00:000 208.205 98.0 89.726 9.816 12.58 36.82019/02/08 10:10:00:000 208.205 98.0 89.726 9.816 12.58 36.82019/02/08 10:11:00:000 208.374 98.0 89.811 9.816 12.58 36.82019/02/08 10:12:00:000 208.374 98.0 89.656 9.816 12.58 37.0

Page 134: Division of Environmental Permits Floor

2019/02/08 10:13:00:000 208.069 98.0 89.791 9.816 12.58 37.02019/02/08 10:14:00:000 208.069 98.0 89.625 9.816 12.58 37.22019/02/08 10:15:00:000 208.069 98.1 89.706 9.829 12.58 37.22019/02/08 10:16:00:000 208.069 98.1 89.834 9.829 12.58 37.22019/02/08 10:17:00:000 208.069 98.2 89.743 9.829 12.58 37.22019/02/08 10:18:00:000 208.327 98.1 89.926 9.829 12.58 37.22019/02/08 10:19:00:000 208.327 98.1 89.726 9.829 12.58 37.22019/02/08 10:20:00:000 208.033 98.0 89.726 9.829 12.58 37.22019/02/08 10:21:00:000 208.033 98.1 89.873 9.829 12.58 37.42019/02/08 10:22:00:000 208.033 98.1 89.740 9.829 12.58 37.42019/02/08 10:23:00:000 208.033 98.1 89.740 9.829 12.58 37.72019/02/08 10:24:00:000 208.033 98.2 89.740 9.829 12.58 37.72019/02/08 10:25:00:000 208.033 98.2 89.740 9.829 12.58 37.92019/02/08 10:26:00:000 208.033 98.1 89.740 9.829 12.58 37.92019/02/08 10:27:00:000 208.033 98.2 89.740 9.822 12.58 38.22019/02/08 10:28:00:000 207.841 98.1 89.489 9.822 12.58 38.22019/02/08 10:29:00:000 207.841 98.4 89.794 9.822 12.58 38.42019/02/08 10:30:00:000 207.841 98.3 89.663 9.822 12.58 38.42019/02/08 10:31:00:000 207.841 98.2 89.663 9.822 12.58 38.42019/02/08 10:32:00:000 207.403 98.4 89.663 9.822 12.56 38.72019/02/08 10:33:00:000 208.042 98.2 89.807 9.822 12.60 38.92019/02/08 10:34:00:000 207.945 98.3 89.664 9.822 12.60 38.92019/02/08 10:35:00:000 207.561 98.2 89.664 9.822 12.58 39.12019/02/08 10:36:00:000 207.561 98.3 89.582 9.822 12.58 39.12019/02/08 10:37:00:000 207.561 98.4 89.582 9.822 12.58 39.32019/02/08 10:38:00:000 207.561 98.3 89.582 9.822 12.58 39.52019/02/08 10:39:00:000 207.561 98.3 89.582 9.822 12.58 39.52019/02/08 10:40:00:000 207.236 98.3 89.559 9.822 12.58 39.52019/02/08 10:41:00:000 207.236 98.3 89.797 9.822 12.60 39.52019/02/08 10:42:00:000 207.584 98.4 89.737 9.821 12.60 39.52019/02/08 10:43:00:000 207.584 98.3 89.630 9.821 12.60 39.82019/02/08 10:44:00:000 207.584 98.4 89.503 9.821 12.58 39.82019/02/08 10:45:00:000 207.223 98.3 89.552 9.821 12.58 40.02019/02/08 10:46:00:000 207.467 98.4 89.510 9.821 12.58 40.02019/02/08 10:47:00:000 207.467 98.3 89.632 9.855 12.60 40.32019/02/08 10:48:00:000 207.467 98.2 89.531 9.855 12.60 40.32019/02/08 10:49:00:000 207.467 98.2 89.531 9.855 12.57 40.02019/02/08 10:50:00:000 207.467 98.2 89.531 9.855 12.57 40.32019/02/08 10:51:00:000 207.467 98.2 89.531 9.855 12.57 40.32019/02/08 10:52:00:000 207.467 98.3 89.385 9.855 12.57 40.32019/02/08 10:53:00:000 207.206 98.2 89.462 9.855 12.60 40.52019/02/08 10:54:00:000 206.934 98.2 89.364 9.855 12.60 40.72019/02/08 10:55:00:000 206.934 98.3 89.364 9.855 12.60 41.02019/02/08 10:56:00:000 206.934 98.3 89.436 9.871 12.60 41.02019/02/08 10:57:00:000 206.934 98.4 89.361 9.871 12.60 41.02019/02/08 10:58:00:000 206.666 98.4 89.361 9.871 12.60 41.72019/02/08 10:59:00:000 206.666 98.4 89.263 9.871 12.57 41.72019/02/08 11:00:00:000 206.666 98.5 89.339 9.871 12.57 41.92019/02/08 11:01:00:000 206.879 98.5 89.451 9.871 12.60 42.12019/02/08 11:02:00:000 206.879 98.4 89.330 9.871 12.60 42.32019/02/08 11:03:00:000 206.879 98.5 89.294 9.855 12.60 42.32019/02/08 11:04:00:000 206.879 98.4 89.483 9.855 12.59 42.32019/02/08 11:05:00:000 206.879 98.4 89.360 9.855 12.59 42.32019/02/08 11:06:00:000 206.879 98.6 89.360 9.855 12.59 42.32019/02/08 11:07:00:000 206.638 98.4 89.434 9.855 12.59 42.32019/02/08 11:08:00:000 206.638 98.6 89.333 9.855 12.61 42.62019/02/08 11:09:00:000 206.638 98.5 89.333 9.855 12.61 42.62019/02/08 11:10:00:000 206.638 98.6 89.192 9.855 12.59 42.62019/02/08 11:11:00:000 206.566 98.6 89.350 9.855 12.59 42.32019/02/08 11:12:00:000 206.566 98.6 89.350 9.855 12.59 42.62019/02/08 11:13:00:000 206.870 98.7 89.350 9.855 12.59 42.62019/02/08 11:14:00:000 206.870 98.6 89.350 9.855 12.59 42.62019/02/08 11:15:00:000 206.870 98.6 89.350 9.855 12.61 42.62019/02/08 11:16:00:000 206.596 98.5 89.350 9.855 12.61 42.62019/02/08 11:17:00:000 206.596 98.6 89.350 9.855 12.57 42.82019/02/08 11:18:00:000 206.596 98.7 89.350 9.855 12.60 42.82019/02/08 11:19:00:000 206.941 98.6 89.263 9.855 12.60 42.82019/02/08 11:20:00:000 206.779 98.6 89.401 9.855 12.60 42.82019/02/08 11:21:00:000 206.779 98.6 89.277 9.855 12.60 42.82019/02/08 11:22:00:000 206.779 98.5 89.339 9.855 12.60 42.82019/02/08 11:23:00:000 206.779 98.5 89.372 9.855 12.60 42.82019/02/08 11:24:00:000 206.779 98.5 89.372 9.855 12.58 42.82019/02/08 11:25:00:000 206.530 98.6 89.253 9.842 12.58 42.82019/02/08 11:26:00:000 206.530 98.8 89.253 9.842 12.58 43.12019/02/08 11:27:00:000 206.789 98.9 89.220 9.842 12.58 43.12019/02/08 11:28:00:000 206.789 98.8 89.452 9.842 12.58 43.12019/02/08 11:29:00:000 206.789 98.7 89.371 10.177 12.60 43.12019/02/08 11:30:00:000 206.789 98.4 89.371 10.327 12.60 43.32019/02/08 11:31:00:000 206.789 98.6 89.265 10.327 12.55 43.52019/02/08 11:32:00:000 206.681 98.7 89.265 10.327 12.55 43.82019/02/08 11:33:00:000 205.999 98.6 89.265 10.350 12.55 43.8

Page 135: Division of Environmental Permits Floor

2019/02/08 11:34:00:000 206.370 98.7 89.290 10.350 12.55 44.02019/02/08 11:35:00:000 206.370 98.7 89.111 10.350 12.55 44.72019/02/08 11:36:00:000 206.028 98.9 89.168 10.350 12.55 44.72019/02/08 11:37:00:000 206.028 98.7 89.168 10.350 12.55 45.12019/02/08 11:38:00:000 206.028 99.0 89.020 10.350 12.55 45.92019/02/08 11:39:00:000 206.028 99.0 89.074 10.350 12.57 45.92019/02/08 11:40:00:000 206.028 99.0 89.074 10.350 12.57 46.62019/02/08 11:41:00:000 205.894 99.0 89.074 10.350 12.56 46.62019/02/08 11:42:00:000 205.894 99.0 89.074 10.342 12.56 46.62019/02/08 11:43:00:000 205.894 98.8 88.896 10.342 12.56 46.82019/02/08 11:44:00:000 204.804 98.9 88.652 10.342 12.53 47.92019/02/08 11:45:00:000 204.283 99.0 88.369 10.342 12.53 49.32019/02/08 11:46:00:000 203.886 99.4 88.558 10.342 12.58 50.72019/02/08 11:47:00:000 204.195 99.3 88.558 10.342 12.58 51.52019/02/08 11:48:00:000 203.238 99.0 88.205 10.342 12.58 53.12019/02/08 11:49:00:000 202.714 99.5 87.989 10.342 12.58 54.22019/02/08 11:50:00:000 202.714 99.5 88.162 10.342 12.58 54.72019/02/08 11:51:00:000 203.177 99.5 88.081 10.342 12.60 54.72019/02/08 11:52:00:000 203.177 99.6 88.215 10.342 12.60 54.92019/02/08 11:53:00:000 202.847 99.5 88.154 10.342 12.60 54.72019/02/08 11:54:00:000 202.203 99.3 88.024 10.342 12.60 54.72019/02/08 11:55:00:000 202.792 99.7 88.021 10.342 12.64 55.62019/02/08 11:56:00:000 202.792 99.8 88.021 10.331 12.64 55.62019/02/08 11:57:00:000 202.792 99.6 87.987 10.331 12.59 55.92019/02/08 11:58:00:000 202.493 99.4 87.774 10.331 12.59 56.62019/02/08 11:59:00:000 202.006 99.3 87.774 10.331 12.59 56.62019/02/08 12:00:00:000 201.142 99.6 87.614 10.331 12.59 57.52019/02/08 12:01:00:000 202.888 100.1 87.839 10.331 12.63 57.52019/02/08 12:02:00:000 203.290 99.7 88.179 10.331 12.63 57.52019/02/08 12:03:00:000 203.290 99.4 88.134 10.331 12.63 56.62019/02/08 12:04:00:000 202.216 99.5 87.719 10.331 12.58 57.02019/02/08 12:05:00:000 201.380 99.2 87.719 10.331 12.62 57.52019/02/08 12:06:00:000 201.993 99.7 87.719 10.331 12.62 58.02019/02/08 12:07:00:000 201.993 99.6 87.859 10.331 12.62 58.02019/02/08 12:08:00:000 201.579 99.7 87.689 10.331 12.60 58.02019/02/08 12:09:00:000 202.204 99.6 87.930 10.331 12.60 58.22019/02/08 12:10:00:000 202.204 99.6 87.863 10.331 12.64 58.02019/02/08 12:11:00:000 202.204 99.7 87.863 10.331 12.62 57.02019/02/08 12:12:00:000 202.204 99.4 87.863 10.331 12.62 57.02019/02/08 12:13:00:000 201.614 99.4 87.664 10.331 12.62 56.82019/02/08 12:14:00:000 202.052 99.6 87.916 10.331 12.62 56.82019/02/08 12:15:00:000 202.052 99.5 87.745 10.331 12.62 56.82019/02/08 12:16:00:000 202.052 99.5 87.745 10.331 12.62 56.82019/02/08 12:17:00:000 201.427 99.5 87.564 10.331 12.62 57.22019/02/08 12:18:00:000 201.427 99.5 87.719 10.331 12.62 57.52019/02/08 12:19:00:000 202.198 99.6 87.889 10.331 12.62 57.52019/02/08 12:20:00:000 202.198 99.5 87.889 10.331 12.62 57.22019/02/08 12:21:00:000 202.198 99.4 87.706 10.331 12.62 57.02019/02/08 12:22:00:000 201.953 99.5 87.795 10.331 12.62 57.02019/02/08 12:23:00:000 201.953 99.5 87.693 10.331 12.62 57.02019/02/08 12:24:00:000 201.953 99.8 87.900 10.337 12.65 57.52019/02/08 12:25:00:000 203.048 99.7 88.094 10.337 12.65 56.82019/02/08 12:26:00:000 201.773 99.1 87.910 10.337 12.61 56.82019/02/08 12:27:00:000 200.977 99.3 87.616 10.337 12.61 58.02019/02/08 12:28:00:000 200.977 99.4 87.524 10.337 12.61 58.02019/02/08 12:29:00:000 201.518 99.4 87.524 10.337 12.64 58.22019/02/08 12:30:00:000 201.518 99.6 87.886 10.337 12.64 58.42019/02/08 12:31:00:000 201.518 99.4 87.602 10.337 12.60 58.42019/02/08 12:32:00:000 201.363 99.5 87.602 10.337 12.60 58.72019/02/08 12:33:00:000 201.934 99.7 87.890 10.337 12.60 58.72019/02/08 12:34:00:000 202.376 99.6 87.998 10.337 12.65 58.42019/02/08 12:35:00:000 201.547 99.5 87.726 10.337 12.61 58.02019/02/08 12:36:00:000 202.575 99.6 88.017 10.337 12.61 57.22019/02/08 12:37:00:000 203.187 99.7 88.341 10.337 12.67 57.22019/02/08 12:38:00:000 203.187 99.4 88.174 10.337 12.60 56.62019/02/08 12:39:00:000 202.305 99.3 88.039 10.326 12.60 56.62019/02/08 12:40:00:000 202.305 99.3 87.983 10.326 12.62 56.42019/02/08 12:41:00:000 202.305 99.3 87.763 10.326 12.62 56.42019/02/08 12:42:00:000 202.305 99.3 87.967 10.326 12.62 56.42019/02/08 12:43:00:000 201.858 99.5 87.653 10.326 12.62 57.52019/02/08 12:44:00:000 201.858 99.6 87.819 10.337 12.65 58.02019/02/08 12:45:00:000 201.858 99.6 87.819 10.337 12.65 58.02019/02/08 12:46:00:000 201.858 99.4 87.858 10.337 12.63 58.92019/02/08 12:47:00:000 201.858 99.8 87.714 10.337 12.63 58.92019/02/08 12:48:00:000 202.855 100.0 88.232 10.337 12.63 58.42019/02/08 12:49:00:000 203.537 99.5 88.513 10.337 12.63 56.62019/02/08 12:50:00:000 203.537 99.3 88.266 10.337 12.59 55.42019/02/08 12:51:00:000 203.537 99.5 88.089 10.337 12.59 54.92019/02/08 12:52:00:000 202.389 99.4 87.851 10.337 12.59 55.62019/02/08 12:53:00:000 201.925 99.3 87.602 10.337 12.59 56.82019/02/08 12:54:00:000 201.925 99.9 87.946 10.337 12.63 57.5

Page 136: Division of Environmental Permits Floor

2019/02/08 12:55:00:000 202.932 99.5 88.158 10.320 12.63 56.82019/02/08 12:56:00:000 202.747 99.6 88.069 10.320 12.63 56.82019/02/08 12:57:00:000 202.747 99.5 88.069 10.320 12.63 56.12019/02/08 12:58:00:000 202.747 100.1 88.069 10.320 12.60 56.12019/02/08 12:59:00:000 203.487 99.3 88.167 10.320 12.60 55.12019/02/08 13:00:00:000 202.658 99.2 87.897 10.320 12.60 55.12019/02/08 13:01:00:000 202.043 99.3 87.654 10.333 12.65 56.62019/02/08 13:02:00:000 201.518 99.8 87.781 10.333 12.65 57.72019/02/08 13:03:00:000 202.412 99.7 88.013 10.333 12.65 57.72019/02/08 13:04:00:000 202.412 99.8 87.865 10.333 12.64 57.52019/02/08 13:05:00:000 202.412 99.7 87.990 10.333 12.59 56.82019/02/08 13:06:00:000 202.412 99.5 87.880 10.333 12.63 56.82019/02/08 13:07:00:000 202.412 99.3 87.880 10.333 12.63 56.42019/02/08 13:08:00:000 202.403 99.7 87.880 10.333 12.63 56.62019/02/08 13:09:00:000 202.403 99.7 87.880 10.333 12.63 56.82019/02/08 13:10:00:000 202.403 99.5 88.026 10.333 12.63 57.52019/02/08 13:11:00:000 202.403 99.8 87.840 10.333 12.62 57.52019/02/08 13:12:00:000 202.403 99.7 88.015 10.333 12.62 56.62019/02/08 13:13:00:000 202.403 99.6 88.015 10.333 12.62 56.62019/02/08 13:14:00:000 202.758 99.4 88.015 10.333 12.62 56.82019/02/08 13:15:00:000 202.214 99.6 87.970 10.333 12.62 56.8AVERAGE: 205.83 98.68 89.01 10.04 12.52 45.30

Page 137: Division of Environmental Permits Floor

US1177 - CPV-Valley - Unit 12 CTG-2 W/DB Run 3DCS Data - 20190209 - 0850-1740

Unit 12 GT Power Unit 12 GT PowerUnit 12 Total GT

Gas FlowUnit 12 HRSG DB Fuel Flow

Unit 12 GT Exhaust O2

Ambient Temp.

MW % KPPH KPPH % °FDate / Time 12HAD00EU001 12MKA01EU902A 12MBP10CF910 12HHA10CF001 12HNE10CQ109 12MBL05CT1012019/02/09 13:28:00:000 221.398 99.8 93.886 6.195 12.94 18.42019/02/09 13:29:00:000 221.818 100.1 93.898 6.195 12.91 18.42019/02/09 13:30:00:000 221.818 99.8 93.601 6.195 12.91 18.62019/02/09 13:31:00:000 221.525 100.0 93.873 6.213 12.91 18.92019/02/09 13:32:00:000 221.525 100.1 93.936 6.213 12.91 19.12019/02/09 13:33:00:000 221.887 100.0 93.936 6.213 12.91 18.42019/02/09 13:34:00:000 222.178 99.9 93.947 6.213 12.91 18.42019/02/09 13:35:00:000 222.178 100.2 94.137 6.213 12.90 18.42019/02/09 13:36:00:000 222.178 99.8 93.889 6.230 12.90 18.42019/02/09 13:37:00:000 221.343 99.8 93.710 6.230 12.90 18.42019/02/09 13:38:00:000 221.805 99.9 93.928 6.230 12.90 18.62019/02/09 13:39:00:000 222.232 100.1 94.058 6.230 12.90 18.62019/02/09 13:40:00:000 222.232 100.0 93.971 6.230 12.90 18.42019/02/09 13:41:00:000 221.816 99.9 93.971 6.243 12.90 18.62019/02/09 13:42:00:000 221.816 100.0 93.977 6.243 12.90 18.62019/02/09 13:43:00:000 222.055 99.9 93.977 6.243 12.90 18.62019/02/09 13:44:00:000 222.055 99.9 93.921 6.243 12.90 18.42019/02/09 13:45:00:000 221.815 99.9 93.794 6.243 12.90 18.42019/02/09 13:46:00:000 221.815 99.8 93.794 6.243 12.91 19.12019/02/09 13:47:00:000 221.712 99.9 93.794 6.243 12.91 19.12019/02/09 13:48:00:000 221.712 99.8 93.697 6.243 12.91 19.42019/02/09 13:49:00:000 221.382 99.8 93.697 6.243 12.91 19.82019/02/09 13:50:00:000 221.382 100.1 93.894 6.243 12.88 19.82019/02/09 13:51:00:000 221.901 100.1 93.894 6.243 12.91 20.02019/02/09 13:52:00:000 221.901 99.9 93.894 6.243 12.91 19.42019/02/09 13:53:00:000 221.901 99.9 93.894 6.243 12.91 18.92019/02/09 13:54:00:000 221.901 99.8 93.894 6.243 12.91 18.92019/02/09 13:55:00:000 221.901 99.9 93.880 6.248 12.91 18.92019/02/09 13:56:00:000 221.901 99.9 93.880 6.248 12.91 18.92019/02/09 13:57:00:000 221.901 99.9 93.880 6.248 12.91 18.62019/02/09 13:58:00:000 221.901 99.9 93.880 6.248 12.90 18.62019/02/09 13:59:00:000 221.901 99.8 93.880 6.248 12.90 18.62019/02/09 14:00:00:000 221.901 99.8 93.736 6.248 12.90 19.12019/02/09 14:01:00:000 221.531 100.0 93.736 6.248 12.90 19.12019/02/09 14:02:00:000 221.531 99.9 93.882 6.248 12.90 19.42019/02/09 14:03:00:000 221.531 99.9 93.799 6.248 12.90 19.62019/02/09 14:04:00:000 220.646 99.7 93.369 6.248 12.90 20.52019/02/09 14:05:00:000 220.455 99.9 93.470 6.248 12.90 21.02019/02/09 14:06:00:000 221.174 100.0 93.626 6.248 12.90 21.02019/02/09 14:07:00:000 221.174 100.0 93.626 6.248 12.90 20.72019/02/09 14:08:00:000 221.174 100.0 93.626 6.248 12.90 20.52019/02/09 14:09:00:000 221.174 100.0 93.853 6.262 12.90 20.72019/02/09 14:10:00:000 221.174 99.8 93.592 6.262 12.90 20.72019/02/09 14:11:00:000 221.174 100.0 93.592 6.262 12.90 20.72019/02/09 14:12:00:000 221.174 100.1 93.842 6.262 12.90 20.72019/02/09 14:13:00:000 221.174 99.8 93.669 6.262 12.91 20.52019/02/09 14:14:00:000 221.174 100.1 93.558 6.262 12.91 20.72019/02/09 14:15:00:000 221.174 100.0 93.609 6.262 12.91 20.72019/02/09 14:16:00:000 221.174 100.2 93.801 6.262 12.90 20.22019/02/09 14:17:00:000 221.714 99.9 93.801 6.262 12.90 20.22019/02/09 14:18:00:000 221.714 99.9 93.801 6.259 12.90 20.02019/02/09 14:19:00:000 221.551 99.9 93.726 6.259 12.90 20.22019/02/09 14:20:00:000 221.202 99.9 93.726 6.259 12.90 20.22019/02/09 14:21:00:000 221.202 99.9 93.726 6.259 12.90 20.52019/02/09 14:22:00:000 221.740 100.0 93.915 6.259 12.90 20.02019/02/09 14:23:00:000 221.740 99.9 93.897 6.259 12.90 20.02019/02/09 14:24:00:000 221.538 99.9 93.803 6.259 12.90 19.82019/02/09 14:25:00:000 221.538 99.9 93.803 6.259 12.90 19.62019/02/09 14:26:00:000 221.538 99.9 93.803 6.259 12.90 19.62019/02/09 14:27:00:000 221.538 99.9 93.803 6.259 12.90 19.62019/02/09 14:28:00:000 221.538 99.9 93.771 6.259 12.90 19.62019/02/09 14:29:00:000 221.538 99.9 93.771 6.259 12.91 19.62019/02/09 14:30:00:000 221.538 100.0 93.771 6.259 12.91 19.62019/02/09 14:31:00:000 221.538 99.9 93.771 6.259 12.91 19.42019/02/09 14:32:00:000 221.190 99.9 93.646 6.259 12.91 19.62019/02/09 14:33:00:000 221.781 100.0 93.810 6.259 12.91 19.82019/02/09 14:34:00:000 221.781 99.8 94.040 6.259 12.90 19.82019/02/09 14:35:00:000 221.781 99.9 93.677 6.259 12.90 19.62019/02/09 14:36:00:000 221.581 100.1 93.845 6.259 12.90 19.42019/02/09 14:37:00:000 221.581 99.9 93.736 6.259 12.90 19.42019/02/09 14:38:00:000 221.581 99.9 93.736 6.259 12.90 19.6

Page 138: Division of Environmental Permits Floor

2019/02/09 14:39:00:000 221.334 99.9 93.736 6.259 12.90 19.82019/02/09 14:40:00:000 221.334 100.0 93.721 6.259 12.90 19.82019/02/09 14:41:00:000 221.623 100.0 93.823 6.259 12.90 20.02019/02/09 14:42:00:000 221.623 99.8 93.564 6.259 12.90 19.82019/02/09 14:43:00:000 221.623 100.0 93.732 6.259 12.90 20.02019/02/09 14:44:00:000 221.623 99.9 93.801 6.259 12.90 19.82019/02/09 14:45:00:000 221.623 99.9 93.801 6.259 12.90 19.82019/02/09 14:46:00:000 221.623 100.0 93.801 6.259 12.90 19.82019/02/09 14:47:00:000 221.623 99.7 93.723 6.259 12.93 19.82019/02/09 14:48:00:000 220.960 99.8 93.568 6.259 12.93 19.82019/02/09 14:49:00:000 221.137 100.0 93.836 6.259 12.90 19.82019/02/09 14:50:00:000 221.137 100.1 93.778 6.259 12.90 20.02019/02/09 14:51:00:000 221.313 99.8 93.751 6.259 12.92 19.52019/02/09 14:52:00:000 221.313 99.9 93.809 6.259 12.92 19.52019/02/09 14:53:00:000 221.789 100.0 93.910 6.259 12.92 19.52019/02/09 14:54:00:000 221.789 100.0 93.722 6.259 12.92 19.52019/02/09 14:55:00:000 221.510 99.6 93.722 6.259 12.92 19.52019/02/09 14:56:00:000 220.703 100.0 93.468 6.259 12.90 20.22019/02/09 14:57:00:000 221.318 100.0 93.714 6.259 12.90 20.22019/02/09 14:58:00:000 221.318 100.1 93.871 6.259 12.90 20.52019/02/09 14:59:00:000 221.318 99.9 93.666 6.259 12.90 20.52019/02/09 15:00:00:000 221.502 100.0 93.719 6.259 12.91 20.52019/02/09 15:01:00:000 221.502 100.0 93.797 6.259 12.91 20.02019/02/09 15:02:00:000 221.502 100.0 93.797 6.259 12.91 20.02019/02/09 15:03:00:000 221.792 99.9 93.797 6.259 12.91 19.82019/02/09 15:04:00:000 221.241 99.8 93.596 6.259 12.90 20.02019/02/09 15:05:00:000 221.241 99.9 93.767 6.259 12.90 20.52019/02/09 15:06:00:000 221.241 99.8 93.636 6.259 12.90 20.52019/02/09 15:07:00:000 220.311 99.3 93.172 6.259 12.90 20.52019/02/09 15:08:00:000 220.946 100.0 93.578 6.259 12.93 20.52019/02/09 15:09:00:000 221.764 100.0 93.738 6.259 12.93 20.52019/02/09 15:10:00:000 220.998 100.0 93.565 6.259 12.93 20.52019/02/09 15:11:00:000 220.998 100.0 93.499 6.259 12.90 20.72019/02/09 15:12:00:000 221.265 100.1 93.728 6.259 12.90 21.02019/02/09 15:13:00:000 221.265 100.0 93.619 6.259 12.90 21.22019/02/09 15:14:00:000 220.928 100.0 93.511 6.259 12.90 21.42019/02/09 15:15:00:000 220.928 100.2 93.677 6.259 12.90 21.22019/02/09 15:16:00:000 220.928 100.1 93.610 6.259 12.90 20.72019/02/09 15:17:00:000 221.154 100.1 93.610 6.259 12.90 20.72019/02/09 15:18:00:000 221.154 100.0 93.610 6.259 12.90 20.52019/02/09 15:19:00:000 220.614 100.1 93.455 6.259 12.90 20.72019/02/09 15:20:00:000 221.045 100.1 93.544 6.259 12.90 21.02019/02/09 15:21:00:000 221.045 100.0 93.724 6.259 12.90 21.22019/02/09 15:22:00:000 221.045 100.0 93.553 6.259 12.90 21.42019/02/09 15:23:00:000 221.045 100.3 93.552 6.259 12.90 21.22019/02/09 15:24:00:000 221.589 100.0 93.833 6.259 12.90 21.22019/02/09 15:25:00:000 220.963 99.9 93.676 6.259 12.90 21.02019/02/09 15:26:00:000 220.963 100.0 93.569 6.259 12.90 20.72019/02/09 15:27:00:000 221.550 100.1 93.715 6.259 12.90 20.72019/02/09 15:28:00:000 221.550 100.1 93.715 6.259 12.90 21.02019/02/09 15:29:00:000 221.550 99.6 93.458 6.259 12.90 21.02019/02/09 15:30:00:000 219.936 99.4 93.212 6.259 12.91 20.72019/02/09 15:31:00:000 221.141 100.0 93.823 6.259 12.96 20.52019/02/09 15:32:00:000 221.801 100.1 93.823 6.259 12.89 20.22019/02/09 15:33:00:000 221.801 100.0 93.823 6.259 12.89 20.22019/02/09 15:34:00:000 221.801 100.0 93.823 6.259 12.89 20.02019/02/09 15:35:00:000 221.003 99.9 93.687 6.259 12.89 20.02019/02/09 15:36:00:000 221.594 100.0 93.776 6.259 12.89 19.82019/02/09 15:37:00:000 221.594 99.9 93.776 6.259 12.92 19.82019/02/09 15:38:00:000 221.376 100.0 93.707 6.259 12.92 20.02019/02/09 15:39:00:000 221.376 99.9 93.707 6.259 12.92 20.22019/02/09 15:40:00:000 221.376 100.0 93.707 6.259 12.90 20.02019/02/09 15:41:00:000 221.376 100.1 93.707 6.259 12.90 20.02019/02/09 15:42:00:000 221.814 100.2 93.895 6.259 12.90 19.82019/02/09 15:43:00:000 221.814 99.9 93.852 6.259 12.90 19.82019/02/09 15:44:00:000 221.814 99.9 93.852 6.259 12.90 19.82019/02/09 15:45:00:000 221.343 100.0 93.821 6.259 12.90 19.52019/02/09 15:46:00:000 221.343 100.1 93.690 6.259 12.91 19.82019/02/09 15:47:00:000 221.925 100.0 93.895 6.259 12.91 20.22019/02/09 15:48:00:000 221.925 99.9 93.895 6.259 12.91 20.52019/02/09 15:49:00:000 221.513 99.9 93.680 6.259 12.91 20.72019/02/09 15:50:00:000 221.513 100.0 93.844 6.259 12.89 20.22019/02/09 15:51:00:000 221.513 100.0 93.844 6.259 12.89 20.22019/02/09 15:52:00:000 221.745 100.0 93.736 6.259 12.92 20.02019/02/09 15:53:00:000 221.745 100.1 94.008 6.259 12.92 19.82019/02/09 15:54:00:000 221.745 100.1 93.984 6.259 12.90 19.82019/02/09 15:55:00:000 222.104 100.0 93.830 6.259 12.90 19.82019/02/09 15:56:00:000 221.808 100.1 93.967 6.259 12.90 20.02019/02/09 15:57:00:000 221.808 100.2 93.901 6.261 12.90 20.02019/02/09 15:58:00:000 221.808 100.0 93.806 6.261 12.90 20.02019/02/09 15:59:00:000 222.309 100.1 94.001 6.261 12.90 19.8

Page 139: Division of Environmental Permits Floor

2019/02/09 16:00:00:000 221.867 100.1 93.758 6.261 12.90 19.82019/02/09 16:01:00:000 221.867 100.0 93.908 6.261 12.90 19.82019/02/09 16:02:00:000 221.867 100.0 93.832 6.261 12.90 19.82019/02/09 16:03:00:000 221.723 100.0 93.832 6.261 12.90 19.82019/02/09 16:04:00:000 221.723 100.1 93.832 6.261 12.90 20.02019/02/09 16:05:00:000 221.723 100.1 93.832 6.261 12.90 20.52019/02/09 16:06:00:000 221.723 100.1 93.993 6.261 12.91 20.52019/02/09 16:07:00:000 221.970 100.1 93.866 6.261 12.91 20.22019/02/09 16:08:00:000 221.970 100.0 93.832 6.261 12.91 20.02019/02/09 16:09:00:000 221.970 100.1 93.832 6.261 12.91 20.02019/02/09 16:10:00:000 221.801 100.1 93.982 6.261 12.91 20.02019/02/09 16:11:00:000 221.801 100.1 93.887 6.261 12.91 19.82019/02/09 16:12:00:000 221.801 100.1 93.963 6.261 12.90 19.82019/02/09 16:13:00:000 222.167 100.0 93.963 6.261 12.90 19.82019/02/09 16:14:00:000 221.786 100.0 93.846 6.261 12.90 19.82019/02/09 16:15:00:000 221.786 100.0 93.846 6.261 12.90 20.02019/02/09 16:16:00:000 221.635 100.1 93.846 6.261 12.90 20.02019/02/09 16:17:00:000 221.635 100.1 93.721 6.261 12.90 20.02019/02/09 16:18:00:000 221.830 100.1 93.875 6.261 12.90 19.82019/02/09 16:19:00:000 221.830 100.0 94.014 6.261 12.90 19.82019/02/09 16:20:00:000 221.830 100.1 93.901 6.261 12.90 19.62019/02/09 16:21:00:000 222.021 99.9 93.901 6.261 12.91 19.82019/02/09 16:22:00:000 221.631 100.1 93.845 6.261 12.91 19.62019/02/09 16:23:00:000 221.631 100.1 93.845 6.261 12.91 19.62019/02/09 16:24:00:000 222.000 99.9 93.948 6.261 12.91 19.62019/02/09 16:25:00:000 222.000 100.1 93.948 6.261 12.91 19.62019/02/09 16:26:00:000 221.584 100.0 93.954 6.261 12.91 19.62019/02/09 16:27:00:000 221.584 100.1 94.082 6.261 12.91 19.82019/02/09 16:28:00:000 222.108 100.1 93.927 6.261 12.91 19.82019/02/09 16:29:00:000 222.108 100.1 93.927 6.261 12.90 19.82019/02/09 16:30:00:000 221.986 100.0 93.927 6.261 12.90 19.62019/02/09 16:31:00:000 221.352 100.0 93.740 6.261 12.90 19.62019/02/09 16:32:00:000 221.950 100.1 93.879 6.261 12.90 19.82019/02/09 16:33:00:000 221.950 100.1 93.879 6.261 12.90 19.82019/02/09 16:34:00:000 221.579 100.0 93.936 6.268 12.91 19.82019/02/09 16:35:00:000 221.579 100.0 93.849 6.268 12.91 19.82019/02/09 16:36:00:000 221.579 100.0 93.966 6.268 12.91 20.02019/02/09 16:37:00:000 221.986 100.1 93.919 6.268 12.91 20.02019/02/09 16:38:00:000 221.544 100.1 93.866 6.268 12.91 20.02019/02/09 16:39:00:000 221.544 100.1 93.866 6.268 12.91 20.02019/02/09 16:40:00:000 222.025 100.1 93.915 6.268 12.91 20.02019/02/09 16:41:00:000 222.025 99.9 93.915 6.268 12.90 20.02019/02/09 16:42:00:000 221.586 100.0 93.915 6.268 12.90 19.82019/02/09 16:43:00:000 221.586 100.1 93.915 6.268 12.90 19.82019/02/09 16:44:00:000 221.848 100.1 93.915 6.268 12.90 19.82019/02/09 16:45:00:000 221.848 99.7 93.705 6.268 12.90 19.62019/02/09 16:46:00:000 220.600 99.8 93.487 6.268 12.90 19.42019/02/09 16:47:00:000 222.070 100.1 94.064 6.268 12.94 19.42019/02/09 16:48:00:000 222.070 100.2 94.064 6.268 12.94 19.12019/02/09 16:49:00:000 222.230 100.1 93.955 6.268 12.90 19.12019/02/09 16:50:00:000 222.230 100.0 93.955 6.268 12.90 19.12019/02/09 16:51:00:000 222.230 100.1 93.945 6.268 12.90 19.42019/02/09 16:52:00:000 221.865 100.0 93.945 6.268 12.90 19.42019/02/09 16:53:00:000 221.865 100.1 94.038 6.268 12.90 19.42019/02/09 16:54:00:000 222.294 100.1 93.932 6.268 12.90 19.42019/02/09 16:55:00:000 222.294 100.2 94.024 6.268 12.90 19.42019/02/09 16:56:00:000 222.012 100.1 94.024 6.268 12.90 19.42019/02/09 16:57:00:000 222.012 100.1 94.024 6.268 12.91 19.42019/02/09 16:58:00:000 222.012 100.2 93.933 6.268 12.91 19.42019/02/09 16:59:00:000 222.462 100.2 94.085 6.268 12.91 19.42019/02/09 17:00:00:000 222.235 100.0 93.986 6.268 12.90 19.42019/02/09 17:01:00:000 222.235 100.1 94.042 6.268 12.90 19.12019/02/09 17:02:00:000 222.235 100.1 94.042 6.268 12.90 19.12019/02/09 17:03:00:000 222.235 100.2 93.944 6.268 12.90 19.12019/02/09 17:04:00:000 222.235 100.2 94.032 6.268 12.90 18.92019/02/09 17:05:00:000 222.459 100.1 94.211 6.268 12.90 18.92019/02/09 17:06:00:000 222.459 100.0 93.936 6.268 12.90 18.92019/02/09 17:07:00:000 222.202 100.0 94.104 6.268 12.90 18.92019/02/09 17:08:00:000 222.202 100.1 94.009 6.268 12.90 18.92019/02/09 17:09:00:000 222.202 100.2 94.009 6.268 12.90 18.92019/02/09 17:10:00:000 222.202 100.0 94.009 6.268 12.90 18.92019/02/09 17:11:00:000 222.202 99.9 94.009 6.268 12.90 18.92019/02/09 17:12:00:000 221.807 100.0 93.800 6.268 12.90 18.92019/02/09 17:13:00:000 221.807 100.1 93.902 6.268 12.90 19.12019/02/09 17:14:00:000 222.219 100.3 94.085 6.268 12.90 19.42019/02/09 17:15:00:000 222.219 100.1 94.085 6.268 12.90 19.42019/02/09 17:16:00:000 222.219 100.1 94.097 6.268 12.90 19.42019/02/09 17:17:00:000 222.219 100.1 94.083 6.268 12.90 19.12019/02/09 17:18:00:000 222.219 100.1 94.083 6.268 12.90 19.12019/02/09 17:19:00:000 222.512 100.1 93.994 6.268 12.90 18.92019/02/09 17:20:00:000 222.512 100.1 93.999 6.268 12.90 18.9

Page 140: Division of Environmental Permits Floor

2019/02/09 17:21:00:000 222.208 100.1 93.999 6.268 12.90 18.92019/02/09 17:22:00:000 222.373 100.1 94.095 6.268 12.90 18.92019/02/09 17:23:00:000 222.373 100.0 93.982 6.268 12.90 18.62019/02/09 17:24:00:000 222.373 100.1 94.112 6.268 12.90 18.62019/02/09 17:25:00:000 222.373 100.1 94.112 6.268 12.90 18.92019/02/09 17:26:00:000 222.373 100.0 94.112 6.268 12.90 18.62019/02/09 17:27:00:000 222.373 100.0 94.112 6.268 12.90 18.62019/02/09 17:28:00:000 222.373 99.9 94.112 6.268 12.90 18.42019/02/09 17:29:00:000 222.373 100.0 94.112 6.268 12.90 18.42019/02/09 17:30:00:000 222.373 100.1 94.181 6.268 12.90 18.42019/02/09 17:31:00:000 222.373 100.1 94.181 6.268 12.90 18.42019/02/09 17:32:00:000 222.733 100.1 94.158 6.268 12.90 18.42019/02/09 17:33:00:000 222.295 100.1 94.158 6.268 12.90 18.22019/02/09 17:34:00:000 222.295 100.1 94.120 6.268 12.90 18.42019/02/09 17:35:00:000 222.938 100.2 94.192 6.268 12.90 18.2AVERAGE: 221.70 100.00 93.84 6.26 12.90 19.69

Page 141: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-12 Base Load wDB

PM Data

Page 142: Division of Environmental Permits Floor

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

09:02 13:20 13:28 hh:mm

13:15 17:40 17:35 hh:mm

02/08/19 02/08/19 02/08/19 mm/dd/yy

Base w/db Base w/db Base w/db % or w/DB --

1.017 0.893 0.893

0.7350 0.7290 0.7290

0.142 0.145 0.142 in

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

0.000 258.070 357.320 ft³

82.080 356.420 446.020 ft³

82.080 98.350 88.700 89.710 ft³

245.50 244.25 240.50 243.42 min

75.67 71.42 57.54 68.21 °F

191.08 192.08 196.25 193.14 °F

29.31 29.35 30.05 29.57 in Hg

-1.10 -1.10 -1.10 -1.10 in H₂O

29.23 29.27 29.97 29.49 in Hg

0.44 0.44 0.44 0.44 in H₂O

29.44 29.49 30.19 29.70 in Hg

1.18 1.20 1.19 1.19 √(in H₂O)

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

146.60 153.80 136.00 145.47 g

13.30 15.70 14.20 14.40 g

160.19 169.81 150.47 160.15 ml

7.54 7.99 7.08 7.54 scf

80.7 85.7 81.2 82.5 dscf

2.3 2.4 2.3 2.3 dscm

8.54 8.53 8.02 8.36 %

66.47 67.81 72.32 68.87 %

8.54 8.53 8.02 8.36 %

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

4.7 4.7 4.6 4.7 %

12.7 12.7 12.8 12.7 %

0.0 0.0 0.0 0.0 ppm

82.6 82.6 82.6 82.6 %

29.26 29.26 29.25 29.26 lb/lb-mole

28.30 28.30 28.35 28.31 lb/lb-mole

1.745 1.736 1.761 1.747

8632.05 8632.05 8632.05 8632.05 dscf/MMBtu

139.5 140.7 142.1 140.8 %

Calculated Fuel Factor

Fuel F-Factor

Percent Excess Air

Oxygen Content

Carbon Monoxide Content

Nitrogen Content

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Calculated Stack Moisture

Saturated Stack Moisture

Reported Stack Moisture Content

Carbon Dioxide Content

Gas Analysis Data

Impinger Water Weight Gain

Silica Gel Weight Gain

Total Water Volume Collected

Standard Water Vapor Volume

Standard Meter Volume

Standard Metric Meter Volume

Absolute Stack Pressure

Average Orifice Pressure Drop

Absolute Meter Pressure

Avg Square Root Pitot Pressure

Moisture Content Data

Total Sampling Time

Average Meter Temperature

Average Stack Temperature

Barometric Pressure

Stack Static Pressure

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Initial Meter Volume

Final Meter Volume

Total Meter Volume

Stack Test Data

Run Start Time

Run Stop Time

Test Date

Meter Calibration Factor

Pitot Tube Coefficient

Project # sie-19-middletown.ny-comp#2

Historical Data

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

Average Nozzle Diameter

Load

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Results

Page 143: Division of Environmental Permits Floor

METHOD 201A (FRONT) AND 202 (BACK) - RESULTS

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

65.77 66.25 65.05 65.69 ft/sec

283.53 283.53 283.53 283.53 ft²

1,118,793 1,126,988 1,106,536 1,117,439 acfm

53,180 53,561 53,505 53,416 wkscfh

48,636,278 48,992,010 49,215,157 48,947,815 dscfh

104.0 105.2 105.8 105.0 %

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

4.45 4.53 5.43 4.80 mg --

5.51E-05 5.28E-05 6.69E-05 5.83E-05 g/dscf --

8.51E-04 8.15E-04 1.03E-03 8.99E-04 gr/dscf --

2.68 2.59 3.29 2.85 kg/hr --

5.91 5.71 7.26 6.29 lb/hr --

25.90 24.99 31.78 27.56 tpy --

0.0027 0.0026 0.0033 0.0028 lb/MMBtu 0.0073

1.97 1.76 1.46 1.73 mg --

2.44E-05 2.05E-05 1.79E-05 2.10E-05 g/dscf --

3.77E-04 3.17E-04 2.77E-04 3.24E-04 gr/dscf --

1.19 1.01 0.88 1.03 kg/hr --

2.62 2.22 1.95 2.26 lb/hr --

11.47 9.71 8.53 9.90 tpy --

0.0012 0.0010 0.0009 0.0010 lb/MMBtu --

1.48 1.77 2.78 2.01 mg --

1.83E-05 2.06E-05 3.42E-05 2.44E-05 g/dscf --

2.83E-04 3.18E-04 5.27E-04 3.76E-04 gr/dscf --

0.89 1.01 1.68 1.19 kg/hr --

1.97 2.23 3.71 2.63 lb/hr --

8.61 9.76 16.23 11.53 tpy --

0.0009 0.0010 0.0017 0.0012 lb/MMBtu --

1.00 1.00 1.20 1.07 mg --

1.24E-05 1.17E-05 1.48E-05 1.29E-05 g/dscf --

1.91E-04 1.80E-04 2.28E-04 2.00E-04 gr/dscf --

0.60 0.57 0.73 0.63 kg/hr --

1.33 1.26 1.60 1.40 lb/hr --

5.82 5.52 7.02 6.12 tpy --

0.0006 0.0006 0.0007 0.0006 lb/MMBtu --

12-PM-Base wDB-1 12-PM-Base wDB-2 12-PM-Base wDB-3 Average Units Limits

0.45 0.48 0.46 0.46 ft³/min

201.86 202.13 203.63 202.54 µP

1.07 1.08 1.07 1.07

2.65 2.45 2.63 2.57

1.07 1.08 1.07 1.07

2.65 2.45 2.63 2.57

2466.75 2629.39 2503.20 2,533.12

1.00 1.00 1.00 1.00

0 0 0 0 points

Condensable PM₂.₅ Emission Rate

Cunningham Correction Factor

Recalculated D50-1 for CIV

Z

Recalculated Cunninham

Lower Limit Cut Diameter, CI (NRE<3162), D50LL

Reynolds Number

RM 201A Quality Control

No. Sampling Pts. Outside Dp

Cyclone Flow Rate

Stack Viscosity

Emission Rate Data

Stack Cross-Sectional Area

Actual Stack Flow Rate

Wet Standard Stack Flow Rate

Dry Standard Stack Flow Rate

Percent of Isokinetic Rate

Condensable PM₂.₅ Concentration

Filterable PM₂.₅ Mass

Filterable PM₂.₅ Concentration

Condensable PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Mass

Total PM₁₀/PM₂.₅ Concentration

Filterable PM₁₀ Mass

Filterable PM₁₀ Concentration

Total PM₁₀/PM₂.₅ Emission Rate

Filterable PM₁₀ Emission Rate

Filterable PM₂.₅ Emission Rate

Average Stack Gas Velocity

Volumetric Flow Rate Data

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Results

Page 144: Division of Environmental Permits Floor

(mm/dd/yy)

°F

in Hg

indust. spec. scf

chk Subpart minutes

in

1 2 3

(mm/dd/yy) 02/08/19 02/08/19 02/08/19

Base w/db Base w/db Base w/db % or w/DB

8632.05 8632.05 8632.05 dscf/MMBtu

from ACS samp-cp-0025 samp-cp-0019 samp-cp-0019

(Y) 1.017 0.893 0.893

(H@) 1.820 1.838 1.838 in H₂O

No No No

from ACS 5272/10 P-983/10 P-983/10

(Cp) 0.7350 0.7290 0.7290

from ACS 3 3 3 must match cyc nozz tab (e.g. 3, 4, etc.)

(Dn) 0.142 0.145 0.142 in

from ACS samp-hp-0149 samp-hp-148 samp-hp-148

120.0 120.0 120.0 in

from list glass glass glass

from ACS samp-bh-0032 samp-bh-0035 samp-bh-0032

from ACS samp-cc-0012 samp-cc-0027 samp-cc-0012

Created with Isocalc-AHI v20190131

1600 W Tacoma Street

Broken Arrow, Oklahoma 74012

Cole McBride

(918) 307-8865

Unit Number

Operator CM

Standard Temperature

Standard Pressure

68

29.92

Pitot Identification

Number of Ports Used

Port Inside Diameter

Stack Shape

Base Run Number

Number of Ports Available

Test Equipment Information

Run

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE

Date for Preliminary Run 02/08/19

Company Name Air Hygiene International, Inc. (Tulsa, Oklahoma)

Test Information

Project # sie-19-middletown.ny-comp#2

Source Information

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

Fuel Type Gas, Natural

Required Sample Vol.

Run Duration

Testing Company Information

Pitot Tube Coefficient

Nozzle Number

Nozzle Diameter

Probe Number

Probe Length

(918) 307-9131

Address

City, State Zip

Project Manager

Phone Number

Fax Number

Sample Case / Oven Number

Impinger Case Number

(SS, Glass …. ) Liner Material

50

240

CTG-12

12-PM-Base wDB

4

Test Date

Fuel F-Factor

Load

4

6.00

Circular

Meter Box Number

Meter Calibration Factor

Orifice Meter Coefficient

Non-Console Manometer Used

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Title Page

Page 145: Division of Environmental Permits Floor

(Lfw) 235.25 in

(Lnw) 7.25 in

(D) 228.00 in

(As) 283.53 ft²

(A) 1200.00 in

(AD) 5.26 diameters

(B) 1095.00 in

(BD) 4.80 diameters

Down Up Particulate Velocity

Stream Stream Points Points

2.00-4.99 0.50-1.24 24 16

5.00-5.99 1.25-1.49 20 16

6.00-6.99 1.50-1.74 16 12

7.00-7.99 1.75-1.99 12 12

>= 8.00 >=2.00 8 or 122 8 or 122

12 12

24 16 4 Ports by 3 Across

24 16 12 Pts Used 12 Required

Fraction Distance Distance

Traverse of from Including

Point Stack Inside Reference

Number Diameter Wall Length

in in

1 0.044 10 17 2/8

2 0.146 33 2/8 40 4/8

3 0.296 67 4/8 74 6/8

4

5

6

7

8

9

Traverse Point Locations

1 Check Minimum Number of Points for the Upstream

and Downstream conditions, then use the largest.

2 8 for Circular Stacks 12 to 24 inches

12 for Circular Stacks over 24 inches

Upstream Spec Number of Traverse Points Used

Downstream Spec

Traverse Pts Required

Distance Downstream

Diameters Downstream

Number of Traverse Points Required

Diameters to Minimum Number of1

Flow Disturbance Traverse Points

Distance to Near Wall of Stack

Diameter of Stack

Area of Stack

Distance from Port to Disturbances

Distance Upstream

Diameters Upstream

Stack Size Large (>24 inch diameter) Port ID (inches) 6.00

Circular Stack or Duct Diameter

Distance to Far Wall of Stack

Operator CM Ports Available 4

Stack Type

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 1 - SAMPLE AND VELOCITY TRAVERSES FOR CIRCULAR SOURCES

Plant Name CPV Valley Energy Center Date 02/08/19

Sampling Location CTG-12 Stack

Project #

Circular

Lnw

Lfw

D

B

A

Method 1 Trav

12 Point PM Trav (M201a ONLY)

Velocity

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB M1 - Circular

Page 146: Division of Environmental Permits Floor

x PreTest x PostTest 0.8232 4183

(As) 283.53 ft²

(D) 228.00 in 08:13 Start 08:23 End

Traverse Velocity Null Zero Deg Stack Local

Point Head Angle Pressure Temp Velocity

(p) (Na) (0oa) (ts) (vs(l))

(Pb) 29.31 in Hg in H₂O deg in H₂O °F ft/sec

(Pstatic) -1.10 in H₂O A-1 1.90 0 0.00 200 86.53

(Ps) 29.23 in Hg A-2 1.40 0 0.00 195 74.00

A-3 1.50 -5 0.10 194 76.53

B-1 1.10 0 0.00 194 65.54

B-2 1.20 -5 0.10 194 68.45

(%CO2) 4.90 %vd B-3 1.00 0 0.00 192 62.39

(%O2) 12.40 %vd C-1 1.70 0 0.00 200 81.85

(ppmCO) 0.00 ppmvd C-2 1.40 -10 0.20 198 74.17

(%N2) 82.70 %vd C-3 1.00 -5 0.10 195 62.54

(Bws) 8.00 % D-1 1.80 0 0.00 200 84.22

(Md) 29.28 lb/lb-mole D-2 1.50 -5 0.10 199 76.83

(Mw) 28.38 lb/lb-mole D-3 1.10 -5 0.10 199 65.79

(vs) 65.38 ft/sec

(Qsd) 48,225,330 dscf/hr

(Qsd) 803,756 dscf/min

(Qaw) 1,112,226 acf/min

(Qsw) 52,418,837 ascf/hr

1.38 3 197

1.17

3.3

Thermocouple ID

Standard deviation of null angles =

Pressures

Barometric Pressure

Static Pressure

Carbon Dioxide Concentration

= Square roots of p

Avg Stack Dry Std Flow Rate

Avg Stack Wet Flow Rate

Avg Stack Wet Std Flow Rate

Stack Cross Section Schematic

40 CFR 60, Method 2G, Section 8.11.1 (but applies to all Method 2 type static pressure measurements): If a Type S probe is used for this measurement, position the probe at or between any traverse point(s) and rotate the probe until a null differential pressure reading is obtained. Disconnect the tubing from one of the pressure ports; read and record the ∆P. For pressure devices with one-directional scales, if a deflection in the positive direction is noted with the negative side disconnected, then the static pressure is positive. Likewise, if a deflection in the positive direction is noted with the positive side disconnected, then the static pressure is negative.

Average

Stack Dry Molecular Weight

Stack Wet Molecular Weight

Results

Avg Stack Gas Velocity

Avg Stack Dry Std Flow Rate

Oxygen Concentration

Carbon Monoxide Concentration

Nitrogen Concentration

Stack Moisture Content

CM Ports Available 4

Stack Dimensions Velocity Traverse Data

Diameter of Stack

Run Number 12-PM-Base wDB-V1

samp-hp-0149

Pitot Leak Check Pitot Coefficient

Absolute Stack Pressure

Stack Gas Composition

Estimated CompositionComposition Data:

Area of Stack

Run Time

METHOD 2 - DETERMINATION OF STACK GAS VELOCITY AND VOLUMETRIC FLOW RATE

Plant Name CPV Valley Energy Center Preliminary Run Date 02/08/19

Project # sie-19-middletown.ny-comp#2

Pitot Identification

Sampling Location CTG-12 Stack Stack Type Circular

Operator

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB M2 - Run (1)

Page 147: Division of Environmental Permits Floor

1.600 1.836

Date 02/08/19 09:02 13:15

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.7 12.7 0.0 82.6 139.5 YES

Date 02/08/19 13:20 17:40

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.7 12.7 0.0 82.6 140.7 YES

Date 02/08/19 13:28 17:35

(%CO₂) (%O₂) (ppmCO) (%N₂) (%EA)avg

% % ppm % %

4.6 12.8 0.0 82.6 142.1 YES

hh:mm lb/lb-mole

04:07 29.25 1.761

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Gas Analysis Data

Run Number 12-PM-Base wDB-3 Run Start Time

hh:mm lb/lb-mole

04:20 29.26 1.736

Run Stop Time

SampleAnalysis

Time

CO₂ Conc.

O₂ Conc.

COConc.

N₂ Conc.

Dry Molecular Weight

CalculatedFuel Factor

Excess Air

Fuel Factor in

Range(Md) (Fo)avg

Run Number 12-PM-Base wDB-2 Run Start Time Run Stop Time

Gas Analysis Data

Dry Molecular Weight

(Md)

N₂ Conc.

CO₂ Conc.

O₂ Conc.

COConc.

Excess Air

Fuel Factor in

Range

hh:mm

04:13

CalculatedFuel Factor

(Fo)avg

1.745

SampleAnalysis

Time

lb/lb-mole

29.26

12-PM-Base wDB-1 Run Start Time Run Stop Time

Gas Analysis Data

Fuel Type Min. Fuel Factor Max. Fuel FactorGas, Natural

METHOD 3a - DETERMINATION OF DRY MOLECULAR WEIGHT BY ANALYZER

02/08/19

Sampling Location CTG-12 Stack

Project #

Operator

sie-19-middletown.ny-comp#2 # of Ports Used

CM

1 (gas probe)

Plant Name CPV Valley Energy Center Preliminary Run Date

Run Number

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB M3a - Mol Wt

Page 148: Division of Environmental Permits Floor

Standard Result Difference Pass/Fail

(g) (g) (g) (± 0.5 g)

500 499.7 -0.3 Pass

500 499.7 -0.3 Pass

Date 02/08/19 Start Time 09:02 Stop Time 13:15

(Y)

(Vm) 82.080 dcf (Pb) 29.31 in Hg

(ts)avg 191 °F (Pstatic) -1.10 in H₂O

(tm)avg 76 °F (H)avg 0.44 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 491.30 600.80 721.60 899.10

Initial Value (Vi),(Wi) 350.50 599.80 716.80 885.80

Net Value (Vn),(Wn) 140.8 1.0 4.8 13.3

(Wt) 159.90 g (Vwsg(std)) 7.539 scf

(Vm(std)) 80.692 dscf (Bws(svp)) 66.47 %

(Bws(calc)) 8.54 % (Bws) 8.54 %

Date 02/08/19 Start Time 13:20 Stop Time 17:40

(Y)

(Vm) 98.350 dcf (Pb) 29.35 in Hg

(ts)avg 192 °F (Pstatic) -1.10 in H₂O

(tm)avg 71 °F (H)avg 0.44 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 486.00 609.00 719.20 905.70

Initial Value (Vi),(Wi) 348.80 607.80 703.80 890.00

Net Value (Vn),(Wn) 137.2 1.2 15.4 15.7

(Wt) 169.50 g (Vwsg(std)) 7.992 scf

(Vm(std)) 85.694 dscf (Bws(svp)) 67.81 %

(Bws(calc)) 8.53 % (Bws) 8.53 %

Date 02/08/19 Start Time 13:28 Stop Time 17:35

(Y)

(Vm) 88.700 dcf (Pb) 30.05 in Hg

(ts)avg 196 °F (Pstatic) -1.10 in H₂O

(tm)avg 58 °F (H)avg 0.44 in H₂O

Impinger 1 Impinger 2 Impinger 3 Impinger 4 Impinger 5 Impinger 6 Impinger 7 Impinger 8

(g) (g) (g) (g)

Contents Dry Dry DI Water Sil Gel

Final Value (Vf),(Wf) 483.20 610.90 717.70 919.60

Initial Value (Vi),(Wi) 349.30 609.20 717.30 905.40

Net Value (Vn),(Wn) 133.9 1.7 0.4 14.2

(Wt) 150.20 g (Vwsg(std)) 7.082 scf

(Vm(std)) 81.248 dscf (Bws(svp)) 72.32 %

(Bws(calc)) 8.02 % (Bws) 8.02 %

Preliminary Date 02/08/19

Test Day 1 02/08/19

Date

Scale Number SAMP-SC-0016

Scale Daily Calibration

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0019 Meter Cal Factor 0.893

Total Meter Volume Barometric Pressure

Calc Moisture Content Final Moisture Content

Moisture Content Data

Run Number 12-PM-Base wDB-3

Results

Total Weight Water Vol Weighed

Std Meter Volume Sat. Moisture Content

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Meter Box Number samp-cp-0019 Meter Cal Factor 0.893

Total Meter Volume Barometric Pressure

Moisture Content Data

Run Number 12-PM-Base wDB-2

Std Meter Volume Sat. Moisture Content

Calc Moisture Content Final Moisture Content

Results

Total Weight Water Vol Weighed

Total Meter Volume Barometric Pressure

Average Stack Temp Stack Static Pressure

Average Meter Temp Avg Orifice Pressure

Moisture Content Data

Run Number 12-PM-Base wDB-1

Meter Box Number Meter Cal Factorsamp-cp-0025 1.017

Sampling Location CTG-12 Stack

Project #

CMOperator

sie-19-middletown.ny-comp#2 Ports Used 4

METHOD 4 - DETERMINATION OF MOISTURE CONTENT IN STACK GASES

Plant Name CPV Valley Energy Center Preliminary Run Date 02/08/19

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB M4 - Moisture

Page 149: Division of Environmental Permits Floor

(Cp) 0.7350 5272/10

(ts) 191.1 °F

(tm) 75.7

(H@) 1.820 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.18 in H₂O

PASS Post 0.000 ft³/min@ 9.0 in Hg (Y) 1.017 (Bws) 8.54 %

Pitot Pre (+) 4.2 in H₂O for 30.0 sec (Md) 29.26 lb/lb-mole

Pre (-) 4.6 in H₂O for 30.0 sec (Dna) 0.1420 in (Qm) 0.75 acfm

Post (+) 4.5 in H₂O for 30.0 sec (Dni) 0.2153 in (K) 0.24

Post (-) 5.2 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.31 in Hg

Pre 0.141 0.143 0.142 PASS (Pstatic) -1.10 in H₂O

Post 0.141 0.143 0.142 PASS (Ps) 29.23 in Hg

(Pm) 29.44 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 09:02 End 13:15 Pre 350.5 599.8 716.8 885.8 ml

Post 491.3 600.8 721.6 899.1 ml

samp-cp-0025 samp-cp-0025 samp-cp-0025 samp-hp-0149 samp-hp-0149 samp-bh-0032 samp-cc-0012 1030 7770 samp-cp-0025

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 0.000 1.70 0.447 0.44 191 254 252 45 49 68 71 71 2.0 1.30 72.68 8.474 103.8 88.530

A-2 23.5 00:23:30 8.545 1.50 0.447 0.44 192 254 256 45 62 69 74 74 2.0 1.22 68.33 16.033 104.0 86.036

A-3 45.8 00:45:45 16.210 1.40 0.447 0.44 189 241 237 47 53 69 76 76 2.0 1.18 65.86 23.127 104.2 84.426

B-1 67.3 01:07:15 23.430 1.20 0.447 0.44 191 256 250 50 58 71 76 76 2.0 1.10 61.07 28.658 104.4 82.529

B-2 85.3 01:25:15 29.060 1.20 0.447 0.44 192 256 252 55 62 73 76 76 2.0 1.10 61.11 34.160 104.5 81.223

B-3 103.3 01:43:15 34.660 1.10 0.447 0.44 192 256 255 53 63 73 76 76 2.0 1.05 58.51 39.220 104.5 79.904

C-1 120.5 02:00:30 39.810 1.70 0.447 0.44 192 229 258 57 39 71 76 76 2.0 1.30 72.74 47.185 104.3 81.148

C-2 142.8 02:22:45 47.917 1.40 0.447 0.44 191 241 250 59 42 72 76 76 2.0 1.18 65.96 54.019 104.6 81.360

C-3 163.0 02:43:00 54.873 1.10 0.447 0.44 190 254 248 48 58 74 77 77 2.0 1.05 58.42 59.380 104.8 80.540

D-1 181.0 03:01:00 60.340 1.70 0.447 0.44 191 256 256 54 63 74 77 77 2.0 1.30 72.68 66.911 103.6 80.523

D-2 204.0 03:24:00 68.020 1.50 0.447 0.44 191 255 245 53 69 76 77 77 2.0 1.22 68.27 74.109 103.5 80.682

D-3 225.5 03:45:30 75.360 1.30 0.447 0.44 191 255 253 54 69 76 76 76 2.0 1.14 63.56 80.712 104.0 80.712

Last Pt 245.5 04:05:30 82.080

Final Val 245.5 04:05:30 82.080 Max Vac 2.0 80.712 104.0

1.40 0.44 191 251 251 52 57 72 76 76 1.18 65.77

Notes:

Identification Nos. samp-cp-0025

Nozzle Measurements

Meter Box Number

Meter Cal Factor

Average Meter Temp

Nozzle Number

Project # Run Number Average Stack Temp

Sampling Location Operator Pitot Coefficient / ID

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name Date Ideal Nozzle Diameter and IsoKinetic Factor SetupFilter #

18082924

0818-188

CPV Valley Energy Center

CTG-12 Stack

sie-19-middletown.ny-comp#2

02/08/19

CM

12-PM-Base wDB-1

Stack Dry Molecular Weight

Estimated Orifice Flow Rate

Orifice Meter Coefficient

P to H Isokinetic Factor

Pressures

samp-cc-0012

samp-bh-0032

glass

PASS

Leak Checks

Square Root P

Stack Moisture Content

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Equipment

samp-cp-0025

3

120

samp-hp-0149

Absolute Meter Pressure

Run Time

Barometric Pressure

Stack Static Pressure

Barometer ID

SAMP-WE-0027

Scale ID

SAMP-SC-0016

Absolute Stack Pressure

Wash Volumes

Final Values

Average Values

76

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Isocalc - Run (1)

Page 150: Division of Environmental Permits Floor

(Cp) 0.7290 P-983/10

(ts) 192.1 °F

(tm) 71.4

(H@) 1.838 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.20 in H₂O

PASS Post 0.000 ft³/min@ 10.0 in Hg (Y) 0.893 (Bws) 8.53 %

Pitot Pre (+) 4.6 in H₂O for 30.0 sec (Md) 29.26 lb/lb-mole

Pre (-) 4.2 in H₂O for 30.0 sec (Dna) 0.1453 in (Qm) 0.33 acfm

Post (+) 3.9 in H₂O for 30.0 sec (Dni) 0.1432 in (K) 0.26

Post (-) 5.1 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 29.35 in Hg

Pre 0.144 0.146 0.146 PASS (Pstatic) -1.10 in H₂O

Post 0.144 0.146 0.146 PASS (Ps) 29.27 in Hg

(Pm) 29.49 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 13:20 End 17:40 Pre 348.8 607.8 703.8 890.0 ml

Post 486.0 609.0 719.2 905.7 ml

samp-cp-0019 samp-cp-0019 samp-cp-0019 samp-hp-148 samp-hp-148 samp-bh-0035 samp-cc-0027 1008 7767 samp-cp-0019

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 258.070 1.80 0.447 0.44 195 243 247 56 43 77 71 71 2.0 1.34 74.35 8.903 103.4 93.530

A-2 23.3 00:23:15 268.280 1.50 0.447 0.44 193 244 246 58 44 73 71 71 2.0 1.22 67.77 16.228 102.6 89.071

A-3 44.5 00:44:30 276.680 1.40 0.447 0.44 190 240 245 50 44 70 71 71 2.0 1.18 65.32 23.169 102.8 87.062

B-1 65.0 01:05:00 284.640 1.30 0.447 0.44 191 240 246 51 64 72 72 72 2.0 1.14 62.99 29.140 103.6 86.011

B-2 82.8 01:22:45 291.500 1.20 0.447 0.44 192 238 245 47 57 72 72 72 2.0 1.10 60.57 34.658 104.1 84.864

B-3 99.8 01:39:45 297.840 1.20 0.447 0.44 190 242 251 46 57 72 73 73 2.0 1.10 60.48 40.200 104.6 84.102

C-1 116.8 01:56:45 304.220 1.60 0.447 0.44 192 242 247 50 56 71 71 71 2.0 1.26 69.94 48.537 105.2 85.442

C-2 138.8 02:18:45 313.780 1.40 0.447 0.44 193 242 234 52 64 72 73 73 2.0 1.18 65.47 55.512 104.9 85.009

C-3 159.5 02:39:30 321.810 1.20 0.447 0.44 190 243 253 57 69 73 72 72 2.0 1.10 60.48 61.718 105.0 84.334

D-1 178.8 02:58:45 328.940 1.70 0.447 0.44 192 241 235 59 69 73 71 71 2.0 1.30 72.09 70.700 105.6 85.699

D-2 201.5 03:21:30 339.240 1.60 0.447 0.44 191 240 249 52 70 74 70 70 2.0 1.26 69.89 78.860 105.6 86.181

D-3 223.5 03:43:30 348.580 1.40 0.447 0.44 196 241 244 53 69 75 70 70 2.0 1.18 65.62 85.709 105.2 85.709

Last Pt 244.3 04:04:15 356.420

Final Val 244.3 04:04:15 356.420 Max Vac 2.0 85.709 105.2

1.44 0.44 192 241 245 53 59 73 71 71 1.20 66.25

Notes:

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0019

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

Average Values

71

Final Values

Run Time

Wash Volumes

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0035 Stack Static Pressure

SAMP-SC-0016

samp-cc-0027 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Location CTG-12 Stack Operator CM 18082932

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/08/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Project # sie-19-middletown.ny-comp#2 Run Number 12-PM-Base wDB-2 0818-188 Average Stack Temp

samp-cp-0019 Square Root PMeter Box Number

Sampling Equipment

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-hp-148

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Isocalc - Run (2)

Page 151: Division of Environmental Permits Floor

(Cp) 0.7290 P-983/10

(ts) 196.3 °F

(tm) 57.5

(H@) 1.838 in H₂O

Train Pre 0.000 ft³/min@ 15.0 in Hg (p1/2avg) 1.19 in H₂O

PASS Post 0.000 ft³/min@ 12.0 in Hg (Y) 0.893 (Bws) 8.02 %

Pitot Pre (+) 4.2 in H₂O for 30.0 sec (Md) 29.25 lb/lb-mole

Pre (-) 4.3 in H₂O for 30.0 sec (Dna) 0.1420 in (Qm) 0.35 acfm

Post (+) 5.1 in H₂O for 30.0 sec (Dni) 0.1515 in (K) 0.23

Post (-) 5.3 in H₂O for 30.0 sec in

in

ID: 3 (Pb) 30.05 in Hg

Pre 0.141 0.143 0.142 PASS (Pstatic) -1.10 in H₂O

Post 0.141 0.143 0.142 PASS (Ps) 29.97 in Hg

(Pm) 30.19 in Hg

Weights Imp 1 Imp 2 Imp 3 Imp 4 Imp 5 Imp 6 Imp 7 Imp 8

Start 13:28 End 17:35 Pre 349.3 609.2 717.3 905.4 ml

Post 483.2 610.9 717.7 919.6 ml

samp-cp-0019 samp-cp-0019 samp-cp-0019 samp-hp-148 samp-hp-148 samp-bh-0032 samp-cc-0012 1030 7770 samp-cp-0019

Dry Gas Desired Actual Impinger CPM Meter Meter Square Local Cumul. Cumul. Est-Run

Traverse Sampling Timer Meter Velocity Orifice Orifice Stack Probe Filter Exit Cond. Filter Inlet Outlet Pump Root Stack Meter Percent Meter

Point # Time Time Reading Head H H Temp Temp Temp Temp Temp Temp Temp Temp Vacuum P Velocity Volume IsoKinetic Volume

() (Vm) (p) (Hd) (Ha) (ts) (248±25°F) (248±25°F) (≤68°F) (≤85°F) (76.5±8.5°F) (tmi) (tmo) (p1/2) (vs)l (Vm)std (I) (Vm)std

min hh:mm:ss ft³ in H₂O in H₂O in H₂O °F °F °F °F °F °F °F °F in Hg √(in H₂O) ft/sec dscf % dscf

A-1 0.0 00:00:00 357.320 1.70 0.447 0.44 200 243 244 38 53 68 55 55 2.0 1.30 71.62 8.441 104.3 87.315

A-2 23.3 00:23:15 366.490 1.50 0.447 0.44 199 244 244 40 49 68 58 58 2.0 1.22 67.23 16.321 106.8 86.744

A-3 45.3 00:45:15 375.100 1.40 0.447 0.44 197 243 245 44 54 70 59 59 2.0 1.18 64.85 23.637 107.4 85.485

B-1 66.5 01:06:30 383.110 1.40 0.447 0.44 196 244 246 45 54 70 56 57 2.0 1.18 64.80 29.842 108.0 85.187

B-2 84.3 01:24:15 389.870 1.20 0.447 0.44 196 245 245 45 56 71 58 58 2.0 1.10 59.99 35.287 108.7 84.234

B-3 100.8 01:40:45 395.820 1.10 0.447 0.44 194 243 248 47 57 71 59 59 2.0 1.05 57.35 40.265 109.1 83.123

C-1 116.5 01:56:30 401.270 1.70 0.447 0.44 196 244 248 46 55 71 57 57 2.0 1.30 71.41 47.335 106.6 82.195

C-2 138.5 02:18:30 408.980 1.40 0.447 0.44 197 245 247 47 57 71 57 57 2.0 1.18 64.85 54.029 106.5 81.980

C-3 158.5 02:38:30 416.280 1.20 0.447 0.44 195 243 246 45 57 71 58 58 2.0 1.10 59.95 59.758 106.4 81.196

D-1 177.0 02:57:00 422.540 1.70 0.447 0.44 195 243 243 45 57 70 58 58 2.0 1.30 71.35 67.784 105.7 81.612

D-2 199.8 03:19:45 431.310 1.40 0.447 0.44 196 243 245 44 58 71 58 58 2.0 1.18 64.80 74.684 105.7 81.458

D-3 220.5 03:40:30 438.850 1.30 0.447 0.44 194 242 247 44 58 72 57 57 2.0 1.14 62.35 81.259 105.8 81.259

Last Pt 240.5 04:00:30 446.020

Final Val 240.5 04:00:30 446.020 Max Vac 2.0 81.259 105.8

1.42 0.44 196 244 246 44 55 70 58 58 1.19 65.05

Notes:

Meter Cal Factor

Nozzle Number

Identification Nos. samp-cp-0019

Nozzle Measurements Barometer ID

SAMP-WE-0027

Scale ID

Average Values

58

Final Values

Run Time

Wash Volumes

Absolute Meter Pressure

glass Barometric Pressure

samp-bh-0032 Stack Static Pressure

SAMP-SC-0016

samp-cc-0012 Absolute Stack Pressure

Liner Material

Sample Case / Oven Number

Impinger Case Number

Sampling Location CTG-12 Stack Operator CM 18082933

METHOD 201A (FRONT) AND 202 (BACK) SOURCE SAMPLING TITLE PAGE ISOKINETIC SAMPLING DATA

Plant Name CPV Valley Energy Center Date 02/08/19 Filter # Ideal Nozzle Diameter and IsoKinetic Factor Setup

Pitot Coefficient / ID

Project # sie-19-middletown.ny-comp#2 Run Number 12-PM-Base wDB-3 0818-188 Average Stack Temp

samp-cp-0019 Square Root PMeter Box Number

Sampling Equipment

Stack Moisture Content

Average Meter Temp

Leak Checks Orifice Meter Coefficient

samp-hp-148

120 Pressures

3 Stack Dry Molecular Weight

PASS

Estimated Orifice Flow Rate

P to H Isokinetic Factor

Average Nozzle Diameter

Suggested Nozzle Diameter

Probe Number

Probe Length

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Isocalc - Run (3)

Page 152: Division of Environmental Permits Floor

EMISSION DATA RECORDS

Unit #CTG-12 Base Load wDB

Opacity Data

Page 153: Division of Environmental Permits Floor
Page 154: Division of Environmental Permits Floor
Page 155: Division of Environmental Permits Floor
Page 156: Division of Environmental Permits Floor
Page 157: Division of Environmental Permits Floor
Page 158: Division of Environmental Permits Floor
Page 159: Division of Environmental Permits Floor

APPENDIX C

CALIBRATION GAS CERTIFICATIONS

Page 160: Division of Environmental Permits Floor

CALIBRATION GAS CERTIFICATIONS

Unit #CTG-11 Cylinder Certifications

Page 161: Division of Environmental Permits Floor

Version 02-B, Revised on 2015-05-27

This mixture is for laboratory use only, not for drug, household or other use.This mixture is certified in Mole % to be within ±2% of the actual number reported with a confidence of 95%.

This mixture was manufactured by scale; weights traceable to N.I.S.T. Certificate #822/266926-02.

Expiration Date:

Previous Certification Dates:

RBTGS-Shreveport-LAMFG Facility:

048388830EB0030162.20180703

Cylinder Number:Product ID Number:Cylinder Pressure:COA #Customer PO. NO.:Customer:

Certification Date: 07/03/201807/01/2026

1900 PSIG

Assay Laboratory: Red Ball TGS555 Craig Kennedy WayShreveport, LA 71107

800-551-8150

<0.1 PPM

EB0030162121026

Carbon Monoxide as Impurity

Total Oxides of Nitrogen as Impurity

<1.0 PPM

800-551-8150Fax (318-425-6309)

SpecificationBalance

<0.1 PPM

<0.1 PPM

Composing Material: Zero Ambient Nitrogen, Cert., Sz152

Tracking Number:Lot Number:

Balance

EB0030162.20180703-0

<0.5 PPM

<0.1 PPM

<1.0 PPM

<0.5 PPM

CERTIFICATE OF ANALYSIS

Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).

Analytical Chemist

<0.5 PPM

Anthony CyrInformation and Ordering

Red Ball Technical Gas ServicePGVP Vendor ID # G12018

Oxygen as Impurity

Carbon Dioxide as Impurity

<0.1 PPM

<0.1 PPM

Sulfur Dioxide as Impurity

<0.5 PPM

Accreditation #62754

Concentration

(Zero Ambient Nitrogen)

Total Hydrocarbons as Impurity

ComponentNitrogen

Page 162: Division of Environmental Permits Floor

Balance

Red Ball Technical Gas Service555 Craig Kennedy WayShreveport, LA 71107

800-551-8150Accreditation #62754 PGVP Vendor ID # G12018

EPA PROTOCOL GAS CERTIFICATE OF ANALYSISCylinder Number: CC721564 Certification Date: 09/18/2018Product ID Number: 124606 Expiration Date: 09/16/2026Cylinder Pressure: 1900 PSIG MFG Facility: - Shreveport - LACOA # CC721564.20180910-0 Lot Number: CC721564.20180910Customer PO. NO.: Tracking Number: 098508518Customer: Previous Certification Dates:

This calibration standard has been certified per the May 2012 EPA Traceability Protocol, Document EPA-600/R-12/531,using procedure G1.

Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).

Certified Concentration(s)Component Concentration Uncertainty Analytical Principle Assayed On

Carbon Dioxide 8.92 % ±0.08 % NDIR 09/17/2018

Oxygen 11.98 % ±0.06 % MPA 09/18/2018

NitrogenAnalytical Measurement Data Available Online.

Reference Standard(s)Serial Number Lot Expiration Type Balance Component Concentration Uncertainty(%) NIST Reference

EB0016197 EB0016197.20180205 05/13/2026 GMIS N2 CO2 15 % 0.76 101001

EB0034340 EB0034340.20170209 05/09/2026 GMIS N2 O2 20 % 0.5 071001

EB0087453 EB0087453.20170424 11/25/2025 GMIS N2 CO2 9.51 % 0.724 C1309410.01

Analytical Instrumentation SMART-CERTComponent Principle Make MPC Date

CO2 NDIR Thermo 09/06/2018

O2 MPA Thermo 08/30/2018

Serial

1162980025

1162980025

This is to certify the gases referenced have been calibrated/tested, and verified to meet the defined specifications. This calibration/test was performed using Gases or Scales that are traceable through National Institute of Standards and Technology (NIST) to the International System of Units (SI). The basis of compliance stated is a comparison of the

measurement parameters to the specified or required calibration/testing process. The expanded uncertainties use a coverage factor of k=2 to approximate the 95% confidence level of the measurement, unless otherwise noted. This calibration certificate

applies only to the item described and shall not be reproduced other than in full, without written approval from Red Ball Technical Gas Services. If not included, the uncertainty of calibrations are available upon request and were taken into account

when determining pass or fail. 

Amisha JewittAnalytical Chemist

Assay Laboratory: Red Ball TGSVersion 02-J, Revised on 2018-09-17

Model

410i

410i

Page 163: Division of Environmental Permits Floor

Balance

Red Ball Technical Gas Service555 Craig Kennedy WayShreveport, LA 71107

800-551-8150Accreditation #62754 PGVP Vendor ID # G12018

EPA PROTOCOL GAS CERTIFICATE OF ANALYSISCylinder Number: CC722516 Certification Date: 11/07/2018Product ID Number: 124605 Expiration Date: 11/05/2026Cylinder Pressure: 1900 PSIG MFG Facility: - Shreveport - LACOA # CC722516.20181102-0 Lot Number: CC722516.20181102Customer PO. NO.: Tracking Number: 098499274Customer: Previous Certification Dates:

This calibration standard has been certified per the May 2012 EPA Traceability Protocol, Document EPA-600/R-12/531,using procedure G1.

Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).

Certified Concentration(s)Component Concentration Uncertainty Analytical Principle Assayed On

Carbon Dioxide 18.9 % ±0.16 % NDIR 11/07/2018

Oxygen 21.0 % ±0.12 % MPA 11/07/2018

NitrogenAnalytical Measurement Data Available Online.

Reference Standard(s)Serial Number Lot Expiration Type Balance Component Concentration Uncertainty(%) NIST Reference

EB0004987 EB0004987.20180323 07/15/2026 GMIS N2 CO2 19.5 % 0.767 101001

EB0032246 EB0032246.20170209 08/05/2025 GMIS N2 O2 24 % 0.502 071001

Analytical Instrumentation SMART-CERTComponent Principle Make MPC Date

CO2 NDIR Thermo 10/24/2018

O2 MPA Thermo 11/06/2018

Serial

1162980025

1162980025

This is to certify the gases referenced have been calibrated/tested, and verified to meet the defined specifications. This calibration/test was performed using Gases or Scales that are traceable through National Institute of Standards and Technology (NIST) to the International System of Units (SI). The basis of compliance stated is a comparison of the

measurement parameters to the specified or required calibration/testing process. The expanded uncertainties use a coverage factor of k=2 to approximate the 95% confidence level of the measurement, unless otherwise noted. This calibration certificate

applies only to the item described and shall not be reproduced other than in full, without written approval from Red Ball Technical Gas Services. If not included, the uncertainty of calibrations are available upon request and were taken into account

when determining pass or fail. 

Amisha JewittAnalytical Chemist

Assay Laboratory: Red Ball TGSVersion 02-J, Revised on 2018-09-17

Model

410i

410i

Page 164: Division of Environmental Permits Floor

CALIBRATION GAS CERTIFICATIONS

Unit #CTG-12 Cylinder Certifications

Page 165: Division of Environmental Permits Floor

Version 02-B, Revised on 2015-05-27

This mixture is for laboratory use only, not for drug, household or other use.This mixture is certified in Mole % to be within ±2% of the actual number reported with a confidence of 95%.

This mixture was manufactured by scale; weights traceable to N.I.S.T. Certificate #822/266926-02.

Expiration Date:

Previous Certification Dates:

RBTGS-Shreveport-LAMFG Facility:

095496285EB0093392.20180925

Cylinder Number:Product ID Number:Cylinder Pressure:COA #Customer PO. NO.:Customer:

Certification Date: 09/25/201809/23/2026

1900 PSIG

Assay Laboratory: Red Ball TGS555 Craig Kennedy WayShreveport, LA 71107

800-551-8150

<0.1 PPM

EB0093392121026

Carbon Monoxide as Impurity

Total Oxides of Nitrogen as Impurity

<1.0 PPM

800-551-8150Fax (318-425-6309)

SpecificationBalance

<0.1 PPM

<0.1 PPM

Composing Material: Zero Ambient Nitrogen, Cert., Sz152

Tracking Number:Lot Number:

Balance

EB0093392.20180925-0

<0.5 PPM

<0.1 PPM

<1.0 PPM

<0.5 PPM

CERTIFICATE OF ANALYSIS

Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).

Assistant Operations Manager

<0.5 PPM

Anthony CyrInformation and Ordering

Red Ball Technical Gas ServicePGVP Vendor ID # G12018

Oxygen as Impurity

Carbon Dioxide as Impurity

<0.1 PPM

<0.1 PPM

Sulfur Dioxide as Impurity

<0.5 PPM

Accreditation #62754

Concentration

(Zero Ambient Nitrogen)

Total Hydrocarbons as Impurity

ComponentNitrogen

Page 166: Division of Environmental Permits Floor

Balance

Red Ball Technical Gas Service555 Craig Kennedy WayShreveport, LA 71107

800-551-8150Accreditation #62754 PGVP Vendor ID # G12018

EPA PROTOCOL GAS CERTIFICATE OF ANALYSISCylinder Number: CC722709 Certification Date: 11/27/2018Product ID Number: 124606 Expiration Date: 11/25/2026Cylinder Pressure: 1900 PSIG MFG Facility: - Shreveport - LACOA # CC722709.20181121-0 Lot Number: CC722709.20181121Customer PO. NO.: Tracking Number: 098499919Customer: Previous Certification Dates:

This calibration standard has been certified per the May 2012 EPA Traceability Protocol, Document EPA-600/R-12/531,using procedure G1.

Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).

Certified Concentration(s)Component Concentration Uncertainty Analytical Principle Assayed On

Carbon Dioxide 9.00 % ±0.05 % NDIR 11/27/2018

Oxygen 11.99 % ±0.08 % MPA 11/27/2018

NitrogenAnalytical Measurement Data Available Online.

Reference Standard(s)Serial Number Lot Expiration Type Balance Component Concentration Uncertainty(%) NIST Reference

EB0003672 EB0003672.20180118 07/21/2026 GMIS N2 O2 11.97 % 0.507 071001

EB0032246 EB0032246.20170209 08/05/2025 GMIS N2 O2 24 % 0.502 071001

EB0097768 EB0097768.20171018 02/06/2026 GMIS N2 CO2 24.8 % 0.398 C1309410.01

Analytical Instrumentation SMART-CERTComponent Principle Make MPC Date

CO2 NDIR Thermo 11/26/2018

O2 MPA Thermo 11/06/2018

Serial

1162980025

1162980025

This is to certify the gases referenced have been calibrated/tested, and verified to meet the defined specifications. This calibration/test was performed using Gases or Scales that are traceable through National Institute of Standards and Technology (NIST) to the International System of Units (SI). The basis of compliance stated is a comparison of the

measurement parameters to the specified or required calibration/testing process. The expanded uncertainties use a coverage factor of k=2 to approximate the 95% confidence level of the measurement, unless otherwise noted. This calibration certificate

applies only to the item described and shall not be reproduced other than in full, without written approval from Red Ball Technical Gas Services. If not included, the uncertainty of calibrations are available upon request and were taken into account

when determining pass or fail. 

Amisha JewittAnalytical Chemist

Assay Laboratory: Red Ball TGSVersion 02-J, Revised on 2018-09-17

Model

410i

410i

Page 167: Division of Environmental Permits Floor

Balance

Red Ball Technical Gas Service555 Craig Kennedy WayShreveport, LA 71107

800-551-8150Accreditation #62754 PGVP Vendor ID # G12018

EPA PROTOCOL GAS CERTIFICATE OF ANALYSISCylinder Number: EB0057286 Certification Date: 09/25/2018Product ID Number: 124605 Expiration Date: 09/23/2026Cylinder Pressure: 1900 PSIG MFG Facility: - Shreveport - LACOA # EB0057286.20180919-0 Lot Number: EB0057286.20180919Customer PO. NO.: Tracking Number: 074329340Customer: Previous Certification Dates:

This calibration standard has been certified per the May 2012 EPA Traceability Protocol, Document EPA-600/R-12/531,using procedure G1.

Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).

Certified Concentration(s)Component Concentration Uncertainty Analytical Principle Assayed On

Carbon Dioxide 18.7 % ±0.13 % NDIR 09/24/2018

Oxygen 21.0 % ±0.11 % MPA 09/25/2018

NitrogenAnalytical Measurement Data Available Online.

Reference Standard(s)Serial Number Lot Expiration Type Balance Component Concentration Uncertainty(%) NIST Reference

EB0004987 EB0004987.20180323 07/15/2026 GMIS N2 CO2 19.5 % 0.767 101001

EB0032246 EB0032246.20170209 08/05/2025 GMIS N2 O2 24 % 0.502 071001

EB0097768 EB0097768.20171018 02/06/2026 GMIS N2 CO2 24.8 % 0.398 C1309410.01

Analytical Instrumentation SMART-CERTComponent Principle Make MPC Date

CO2 NDIR Thermo 09/18/2018

O2 MPA Thermo 09/04/2018

Serial

1162980025

1162980025

This is to certify the gases referenced have been calibrated/tested, and verified to meet the defined specifications. This calibration/test was performed using Gases or Scales that are traceable through National Institute of Standards and Technology (NIST) to the International System of Units (SI). The basis of compliance stated is a comparison of the

measurement parameters to the specified or required calibration/testing process. The expanded uncertainties use a coverage factor of k=2 to approximate the 95% confidence level of the measurement, unless otherwise noted. This calibration certificate

applies only to the item described and shall not be reproduced other than in full, without written approval from Red Ball Technical Gas Services. If not included, the uncertainty of calibrations are available upon request and were taken into account

when determining pass or fail. 

Amisha JewittAnalytical Chemist

Assay Laboratory: Red Ball TGSVersion 02-J, Revised on 2018-09-17

Model

410i

410i

Page 168: Division of Environmental Permits Floor

APPENDIX D

QUALITY ASSURANCE AND QUALITY CONTROL DATA

Page 169: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1

QA/QC PROGRAM AIR HYGIENE ensures the quality and validity of its emission measurement and reporting procedures through a rigorous quality assurance (QA) program. The program is developed and administered by an internal QA team and encompasses six major areas:

1. Field Qualifications 2. QA reviews of reports, laboratory work, and field testing; 3. Equipment calibration and maintenance; 4. Chain-of-custody; 5. Training; and 6. Knowledge of current test methods

Field Qualifications Air Hygiene personnel are required to gain and maintain competence with testing methods and techniques according to their job titles and the roles they play during field testing events. Qualifications for each job description include: Staff Technician - An entry level position with responsibility to test on the stack by performing duties that include: keep trucks and trailers stocked and clean, travel to and from job site, be the “hands of the test” on the stack; stay on a stack during the sample test, set up and tear down equipment on-site, perform maintenance on equipment in the shop and on-site. Test Technician or Specialist - Acts as the “hands of the test” on the stack by performing duties that include: stay on a stack during the sample test, migrate to the testing trailer and learn the different analyzers and testing methods used on site, set up and tear down testing equipment on site, learn the system for testing from Testing Managers and Project Managers, travel to and from job site; including driving responsibilities under DOT requirements, follow directions of Testing Managers and Project Managers, learn the proper way to conduct on-site test of stationary stacks Test Manager or Engineer - Directs and coordinates all aspects of a successful test by performing the following duties personally or through subordinate supervisors including: operating analyzers and consoles during testing along with QA/QC procedures, supervise set up and tear down of equipment on site, writing, reviewing, and revising final test reports, working with the client or state personnel while on the job site, managing pre-test checklists and onsite testing procedures, diagnose and repair any problems that may arise with the equipment, safely operate a man lift and drive a truck with or without a trailer, act as crew leader in the field, write protocols and reports, maintain project log of services performed on the job, verify all equipment needed for a job was loaded on the trailer. Test Managers must hold at least one QSTI certificate. Project Manager - Directs and coordinates all aspects of a successful test by performing the following duties personally or through subordinate supervisors including: operating analyzers and consoles during testing along with QA/QC procedures, supervise set up and tear down of equipment on site, writing, reviewing, and revising final test reports, working with the client or state personnel while on the job site, managing pre-test checklists and onsite testing procedures, diagnose and repair any problems that may arise with the equipment, safely operate a man lift and drive a truck with or without a trailer, act as crew leader in the field, write protocols and reports, maintain project log of services performed on the job, verify all equipment needed for a job was loaded on the trailer. Project Managers typically hold QSTI certificates in Groups 1 through 4. QA Reviews Air Hygiene’s review procedure includes review of each source test report, along with laboratory and fieldwork, by the QA Team. The most important review is the one that takes place before a test program begins. The QA Team works closely with technical division personnel to prepare and review test protocols. Test protocol review includes selection of appropriate test procedures, evaluation of interferences or other restrictions that might preclude use of standard test procedures, and evaluation and/or development of alternate procedures. Equipment Calibration and Maintenance The equipment used to conduct the emission measurements is maintained according to the manufacturer’s instructions to ensure proper operation. In addition to the maintenance program, calibrations are carried out on each measurement device according to the schedule outlined by the Environmental Protection Agency. Quality control checks are also conducted in the field for each test program. In conformance with ASTM D7036 Section 15.3.15, all metering and monitoring equipment meets or exceeds the uncertainty criteria contained in the method language that pertains to that equipment.

Page 170: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1

Chain-of-Custody Air Hygiene maintains full chain-of-custody documentation on all samples and data sheets. In addition to normal documentation of changes between field sample custodians, laboratory personnel, and field test personnel, Air Hygiene documents every individual who handles any test component in the field (e.g., probe wash, impinger loading and recovery, filter loading and recovery, etc.). Samples are stored in a locked area to which only Air Hygiene personnel have access. Field data sheets are secured at Air Hygiene’s offices upon return from the field. Training Personnel’s training is essential to ensure quality testing. Air Hygiene has formal and informal training programs, which include:

1. Attendance at EPA-sponsored training courses 2. Enrollment in EPA correspondence courses 3 A requirement for all technicians to read and understand Air Hygiene’s QA manual 4. In-house training and QA meetings on a regular basis 5. Maintenance of training records

Knowledge of Current Test Methods With the constant updating of standard test methods and the wide variety of emerging test procedures, it is essential that any qualified source tester keep abreast of new developments. Air Hygiene subscribes to services, which provide updates on EPA reference methods, rules, and regulations. Additionally, source test personnel regularly attend and present papers at testing and emission-related seminars and conferences. Air Hygiene personnel maintain membership in the Air and Waste Management Association and the American Industrial Hygiene Association. Reproduction and Distribution Policy Reproducing portions of this test report may omit critical or substantial documentation or be taken out of context and due care must be exercised in this regard. Furthermore, this test report and its associated data shall not be reproduced in full or in part without the written consent of the customer.

Page 171: Division of Environmental Permits Floor

sie-19-middletown.ny-comp#1-PM-NG.v1

COMBUSTION TESTING QUALITY ASSURANCE ACTIVITIES In conformance with ASTM D7036 Section 15.3.11 and 13, all testing was performed without any real or apparent errors, with the exception of those that would be listed in Section 2.0 of this report. In addition, all testing was conducted according to the approved testing protocol, test methods, Air Hygiene Quality Manual, or ASTM D7036, with the exception of specifics noted in Section 2.0 of this report. A number of quality assurance activities were undertaken before, during, and after this testing project. This section of the report combined with the documentation in Appendix C describes each of those activities. Each instrument’s response was checked and adjusted in the field prior to the collection of data via multi-point calibration. The instrument’s linearity was checked by adjusting its zero and span responses to zero nitrogen and an upscale calibration gas in the range of the expected concentrations. The instrument response was then challenged with other calibration gases of known concentration and accepted as being linear if the response of the other calibration gases agreed within plus or minus two percent of the range of predicted values. NO2 to NO conversion was checked via direct connect with an EPA Protocol certified concentration of NO2 in a balance of air or nitrogen. Conversion was verified to be between 90 and 110 percent. After each test run, the analyzers were checked for zero and span drift. This allowed each test run to be bracketed by calibrations and documents the precision of the data just collected. The criterion for acceptable data is that the instrument drift is no more than three percent of the full-scale response. The quality assurance worksheets in the following pages summarize all multipoint calibration checks and zero to span checks performed during the tests. These worksheets (as prepared from the data records of Appendix A) show that no drifts in excess of three percent occurred in the zero to span checks following each test run. The sampling systems were leak checked by demonstrating that a vacuum greater than 10 in Hg could be held for at least one minute with a decline of less than one inch of Hg. A leak test was conducted after the sample system was set up and before the system was dismantled. This test was conducted to ensure that ambient air had not diluted the sample. Any leakage detected prior to the tests would be repaired and another leak check conducted before testing commenced. No leaks were found during the pre or post-test leak checks. The absence of leaks in the sampling system was also verified by a sampling system bias check. The sampling system’s integrity was tested by comparing the responses of the analyzers to the calibration gases introduced via two paths. The first path was directly into the analyzer and the second path via the sample system at the sample probe. Any difference in the instrument responses by these two methods was attributed to sampling system bias or leakage. The criterion for acceptance is agreement within five percent of the span of the analyzer. The control gases used to calibrate the instruments were analyzed and certified by the compressed gas vendors to plus or minus one percent accuracy for all gases. EPA Protocol No. 1 was used, where applicable to assign the concentration values traceable to the National Institute of Standards and Technology (NIST), Standard Reference Materials (SRM’s). The gas calibration sheets as prepared by the vendor are contained in Appendix C. Air Hygiene collected and reported the enclosed test data in accordance with the procedures and quality assurance activities described in this test report. Air Hygiene makes no warranty as to the suitability of the test methods. Air Hygiene also assumes no liability relating to the interpretation and use of the test data. INSTRUMENTAL ANALYSIS QUALITY ASSURANCE DATA Date: February 8-10, 2019 Company: CPV Valley, LLC Location: Middletown, NY Techs: CM / DA / BL / CM / ZVN / MJ

Sample System Leak Check

Date Sample System

Leak Rate (l/min)

February 8-10, 2019 1 0

Page 172: Division of Environmental Permits Floor

Accr

edit

ed A

ir E

mis

sion

Tes

ting

Bod

y

A2L

A h

as a

ccre

dite

d

AIR

HY

GIE

NE

IN

TE

RN

AT

ION

AL

, IN

C.

In re

cogn

ition

of t

he su

cces

sful

com

plet

ion

of th

e jo

int A

2LA

and

Sta

ck T

estin

g A

ccre

dita

tion

Cou

ncil (

STA

C)

eval

uatio

n pr

oces

s, th

is la

bora

tory

is a

ccre

dite

d to

per

form

test

ing

activ

ities

in c

ompl

ianc

e w

ith

AST

M D

7036

:200

4 - S

tand

ard

Pra

ctic

e fo

r Com

pete

nce

of A

ir Em

issio

n Te

stin

g Bo

die

s.

Pres

ente

d th

is 10

th d

ay o

f Oct

ober

201

7

__

____

____

____

____

____

_

Pr

esid

ent a

nd C

EO

For t

he A

ccre

dita

tion

Cou

ncil

Cer

tific

ate

Num

ber 3

796.

02

Val

id to

Aug

ust 3

1, 2

019

This

acc

redi

tatio

n pr

ogra

m is

not

incl

uded

und

er th

e A2

LA IL

AC M

utua

l Rec

ogni

tion

Arra

ngem

ent.

Am

eric

an

Ass

oc

iati

on

fo

r La

bo

rato

ry A

cc

red

ita

tio

n

Page 173: Division of Environmental Permits Floor

For t

he ty

pes o

f tes

ts to

whi

ch th

is ac

cred

itatio

n ap

plie

s, pl

ease

refe

r to

the

labo

rato

ry’s

Env

ironm

enta

l Sco

pe o

f Acc

redi

tatio

n.

Acc

redi

ted

Labo

rato

ry

A

2LA

ha

s acc

redi

ted

AIR

HYG

IEN

E IN

TERN

ATIO

NA

L, IN

C.

Brok

en A

rrow

, OK

for t

echn

ical

com

pete

nce

in th

e fie

ld o

f

Envi

ronm

enta

l Tes

ting

This

lab

ora

tory

is a

ccre

dite

d in

acc

ord

anc

e w

ith th

e re

cogn

ized

Inte

rnat

iona

l Sta

ndar

d IS

O/IE

C 1

7025

:200

5

Gen

era

l req

uire

men

ts fo

r the

com

pete

nce

of te

stin

g a

nd c

alib

ratio

n la

bora

torie

s . T

his l

abor

ator

y al

so m

eets

the

R219

Spec

ific

Requ

irem

ents

– T

NI F

ield

Sam

plin

g an

d M

easu

rem

ent O

rgan

izatio

n A

ccre

dita

tion

Prog

ram

. Thi

s acc

red

itatio

n d

emon

stra

tes t

echn

ical

com

pete

nce

for a

def

ined

scop

e an

d th

e op

erat

ion

of a

labo

rato

ry q

ualit

y m

anag

emen

t sy

stem

(ref

er to

join

t ISO

-ILA

C-IA

F C

omm

uniq

ué d

ated

8 J

anua

ry 2

009 )

.

Pres

ente

d th

is 10

th d

ay o

f Oct

ober

201

7

_

____

____

____

____

____

__

Pr

esid

ent a

nd C

EO

Fo

r the

Acc

red

itatio

n C

ounc

il

Cer

tific

ate

Num

ber 3

796.

01

V

alid

to A

ugus

t 31,

201

9

Page 174: Division of Environmental Permits Floor
Page 175: Division of Environmental Permits Floor
Page 176: Division of Environmental Permits Floor

���������� ������ ���� ����

��������������� �!"#�� �$��%�&�'��"�#���(��)��

��(��"�� *%�������"�(+,�"$�������%(�

��++���-��� ��(���+��(�������.���/���&#����"���&

'(��(��"��-�������(������(��

+����-�+(��"��(��������(����"�01�&23�45�!6)�75�3�

�����8�39�)�-����+��:��%"�

;9�(��(#�����9����+����-�����"��'(��(���.���/���&#

����"���-"��(�����"��"-���8�<7=

#"��%��-�"#��%���(���"-��%���+����-�+(��"�> ������+�"�

?"+(��"�@(��

ABCD�EFGGHIJ�KFGLHMCN OPQRSTRTUVRWXYSZCGLH[H\FLC�]CGH[H\FLHJM�H

�F]FHDF_DC�FL�`aZJbcDHFM\CaAdGFM\Ca\Jb

e\CGLacfc�dHMg�LfC�DFL�MFbC�FMI�RWXYS TReTUeYTRS

hijklim�noppl�q�nrost�uvivwop����xplyoi�h

pplz{�|}�����~l��srvi�o�h���pvi�o�h

��l�rvjo�{��i�������|p�rs���rjk��t{��vp�o�j{�h�{���

��������q���q�������l��srvi�oqv���pvi�o��l�

Page 177: Division of Environmental Permits Floor

QUALITY ASSURANCE AND QUALITY CONTROL DATA

Unit #CTG-11 Daily Analyzer Calibrations

Page 178: Division of Environmental Permits Floor

Calibration Date:Client: CPV Valley LLC

O2 Span (%) = 21.00

0.00 -0.03 -0.14 0.03 YES (%)

11.98 12.07 0.43 0.09 YES (%)

21.00 20.88 -0.57 0.12 YES (%)

Linearity = 1.003

CO2 Span (%) = 18.90

0.00 -0.07 -0.37 0.07 YES (%)

8.92 8.96 0.21 0.04 YES (%)

18.90 18.99 0.48 0.09 YES (%)

Linearity = 0.992

SERVOMEX 1440 (O₂ Analyzer) Linearity Plot

SERVOMEX 1440 (CO₂ Analyzer) Linearity Plot

AbsoluteConc.

(%)

SERVOMEX 1440 (O₂ Analyzer)

Pass (±2%,≤0.5%)

CertifiedConcentration

(%)

InstrumentResponse

(%)

InstrumentResponse

(%)

CalibrationError(%)

CalibrationError(%)

AbsoluteConc.

(%)

Pass (±2%,≤0.5%)

February 8, 2019 Location: CPV Valley Energy Center - Unit CTG-11

SERVOMEX 1440 (CO₂ Analyzer)

CertifiedConcentration

(%)

0.00

5.00

10.00

15.00

20.00

25.00

0.00 5.00 10.00 15.00 20.00 25.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0.00 5.00 10.00 15.00 20.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

sie-19-middletown.ny-comp#1-CTG11-gases App. D

Page 179: Division of Environmental Permits Floor

Calibration Date:Client: CPV Valley LLC

O2 Span (%) = 21.00

0.00 -0.01 -0.05 0.01 YES (%)

11.98 12.05 0.33 0.07 YES (%)

21.00 20.94 -0.29 0.06 YES (%)

Linearity = 1.002

CO2 Span (%) = 18.90

0.00 0.01 0.05 0.01 YES (%)

8.92 8.93 0.05 0.01 YES (%)

18.90 18.95 0.26 0.05 YES (%)

Linearity = 0.998

SERVOMEX 1440 (O₂ Analyzer) Linearity Plot

SERVOMEX 1440 (CO₂ Analyzer) Linearity Plot

AbsoluteConc.

(%)

SERVOMEX 1440 (O₂ Analyzer)

Pass (±2%,≤0.5%)

CertifiedConcentration

(%)

InstrumentResponse

(%)

InstrumentResponse

(%)

CalibrationError(%)

CalibrationError(%)

AbsoluteConc.

(%)

Pass (±2%,≤0.5%)

February 9, 2019 Location: CPV Valley Energy Center - Unit CTG-11

SERVOMEX 1440 (CO₂ Analyzer)

CertifiedConcentration

(%)

0.00

5.00

10.00

15.00

20.00

25.00

0.00 5.00 10.00 15.00 20.00 25.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0.00 5.00 10.00 15.00 20.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

sie-19-middletown.ny-comp#1-CTG11-gases App. D

Page 180: Division of Environmental Permits Floor

Calibration Date:Client: CPV Valley LLC

O2 Span (%) = 21.00

0.00 0.05 0.24 0.05 YES (%)

11.98 12.01 0.14 0.03 YES (%)

21.00 20.99 -0.05 0.01 YES (%)

Linearity = 1.003

CO2 Span (%) = 18.90

0.00 0.06 0.32 0.06 YES (%)

8.92 8.86 -0.32 0.06 YES (%)

18.90 18.88 -0.11 0.02 YES (%)

Linearity = 1.004

SERVOMEX 1440 (O₂ Analyzer)

February 10, 2019

SERVOMEX 1440 (O₂ Analyzer) Linearity Plot

SERVOMEX 1440 (CO₂ Analyzer) Linearity Plot

Pass (±2%,≤0.5%)

SERVOMEX 1440 (CO₂ Analyzer)

CertifiedConcentration

(%)

InstrumentResponse

(%)

CalibrationError(%)

AbsoluteConc.

(%)

InstrumentResponse

(%)

CalibrationError(%)

AbsoluteConc.

(%)

Pass (±2%,≤0.5%)

CertifiedConcentration

(%)

Location: CPV Valley Energy Center - Unit CTG-11

0.00

5.00

10.00

15.00

20.00

25.00

0.00 5.00 10.00 15.00 20.00 25.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0.00 5.00 10.00 15.00 20.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

sie-19-middletown.ny-comp#1-CTG11-gases App. D

Page 181: Division of Environmental Permits Floor

QUALITY ASSURANCE AND QUALITY CONTROL DATA

Unit #CTG-12 Daily Analyzer Calibrations

Page 182: Division of Environmental Permits Floor

Calibration Date:Client: CPV Valley LLC

O2 Span (%) = 21.00

0.00 0.02 0.10 0.02 YES (%)

11.99 12.02 0.14 0.03 YES (%)

21.00 21.05 0.24 0.05 YES (%)

Linearity = 0.999

CO2 Span (%) = 18.70

0.00 0.00 0.00 0.00 YES (%)

9.00 8.90 -0.53 0.10 YES (%)

18.70 18.67 -0.16 0.03 YES (%)

Linearity = 1.001

SERVOMEX 1440 (O₂ Analyzer) Linearity Plot

SERVOMEX 1440 (CO₂ Analyzer) Linearity Plot

AbsoluteConc.

(%)

SERVOMEX 1440 (O₂ Analyzer)

Pass (±2%,≤0.5%)

CertifiedConcentration

(%)

InstrumentResponse

(%)

InstrumentResponse

(%)

CalibrationError(%)

CalibrationError(%)

AbsoluteConc.

(%)

Pass (±2%,≤0.5%)

February 8, 2019 Location: CPV Valley Energy Center - Unit CTG-12

SERVOMEX 1440 (CO₂ Analyzer)

CertifiedConcentration

(%)

0.00

5.00

10.00

15.00

20.00

25.00

0.00 5.00 10.00 15.00 20.00 25.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0.00 5.00 10.00 15.00 20.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

sie-19-middletown.ny-comp#1-CTG12-gases App. D

Page 183: Division of Environmental Permits Floor

Calibration Date:Client: CPV Valley LLC

O2 Span (%) = 21.00

0.00 0.03 0.14 0.03 YES (%)

11.99 12.01 0.10 0.02 YES (%)

21.00 20.97 -0.14 0.03 YES (%)

Linearity = 1.003

CO2 Span (%) = 18.70

0.00 0.02 0.11 0.02 YES (%)

9.00 8.93 -0.37 0.07 YES (%)

18.70 18.64 -0.32 0.06 YES (%)

Linearity = 1.004

SERVOMEX 1440 (O₂ Analyzer) Linearity Plot

SERVOMEX 1440 (CO₂ Analyzer) Linearity Plot

AbsoluteConc.

(%)

SERVOMEX 1440 (O₂ Analyzer)

Pass (±2%,≤0.5%)

CertifiedConcentration

(%)

InstrumentResponse

(%)

InstrumentResponse

(%)

CalibrationError(%)

CalibrationError(%)

AbsoluteConc.

(%)

Pass (±2%,≤0.5%)

February 9, 2019 Location: CPV Valley Energy Center - Unit CTG-12

SERVOMEX 1440 (CO₂ Analyzer)

CertifiedConcentration

(%)

0.00

5.00

10.00

15.00

20.00

25.00

0.00 5.00 10.00 15.00 20.00 25.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0.00 5.00 10.00 15.00 20.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

sie-19-middletown.ny-comp#1-CTG12-gases App. D

Page 184: Division of Environmental Permits Floor

Calibration Date:Client: CPV Valley LLC

O2 Span (%) = 21.00

0.00 0.04 0.19 0.04 YES (%)

11.99 12.03 0.19 0.04 YES (%)

21.00 20.98 -0.10 0.02 YES (%)

Linearity = 1.003

CO2 Span (%) = 18.70

0.00 -0.02 -0.11 0.02 YES (%)

9.00 8.90 -0.53 0.10 YES (%)

18.70 18.87 0.91 0.17 YES (%)

Linearity = 0.990

SERVOMEX 1440 (O₂ Analyzer)

February 10, 2019

SERVOMEX 1440 (O₂ Analyzer) Linearity Plot

SERVOMEX 1440 (CO₂ Analyzer) Linearity Plot

Pass (±2%,≤0.5%)

SERVOMEX 1440 (CO₂ Analyzer)

CertifiedConcentration

(%)

InstrumentResponse

(%)

CalibrationError(%)

AbsoluteConc.

(%)

InstrumentResponse

(%)

CalibrationError(%)

AbsoluteConc.

(%)

Pass (±2%,≤0.5%)

CertifiedConcentration

(%)

Location: CPV Valley Energy Center - Unit CTG-12

0.00

5.00

10.00

15.00

20.00

25.00

0.00 5.00 10.00 15.00 20.00 25.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0.00 5.00 10.00 15.00 20.00

Ins

tru

me

nt

Re

sp

on

se

(%

)

Certified Concentrations (%)

sie-19-middletown.ny-comp#1-CTG12-gases App. D

Page 185: Division of Environmental Permits Floor

QUALITY ASSURANCE AND QUALITY CONTROL DATA

Unit #CTG-11 Summary PM Laboratory Analysis

Page 186: Division of Environmental Permits Floor

11-PM-Base-1

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

1 09:22

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.4000 49.0000

1.1000 42.0000

1.6000 26.0000

1.8000 351.0532

1.4000 166.9196

Analytical Data

Sample Leakage Evident

Sampling Location

Project #

Plant Name

SAMPLE ANALYTICAL DATA SHEET

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Sample Type Sample Number

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Inorganic Impinger Contents

Organic Impinger Contents

Filter Beaker

Nozzle Wash PM>10

Cyclone Wash 2.5<PM<10

Cyclone Exit to Front Half of Filter Wash (<2.5)

--

--

0.0388

Gravimetric Concentrations

Sample Portion

Filter0.3000

CPV Valley Energy Center

CTG-11 Stack

sie-19-middletown.ny-comp#2

NO

Run

Estimated Leak Volume

Inorganic Impinger Contents Maxxam

Organic Impinger Contents

Run Start Time

Blank and Titration Concentrations

Blank TypeConcentration

(mg/ml)

Blank Adjustment

(mg)

1.5794

0.7286

Adjusted Gain

(mg)

0.3000

1.3612

1.06680.0332

0.0206

1.0714

0.9286 0.4714

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Analytical - Run (1)

Page 187: Division of Environmental Permits Floor

11-PM-Base-2

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

2 08:28

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.4000 61.0000

1.4000 46.0000

1.9000 32.0000

1.9000 240.7222

1.3000 138.0880

Inorganic Impinger Contents 1.0714 0.8286

Organic Impinger Contents 0.9286 0.3714

Cyclone Wash 2.5<PM<10 0.0364 1.3636

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0253 1.8747

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0483 1.3517

Filter0.3000

--

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Analytical - Run (2)

Page 188: Division of Environmental Permits Floor

11-PM-Base-3

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

3 12:26

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

2.7000 67.0000

1.3000 46.0000

1.3000 39.0000

1.4000 220.6620

1.3000 150.2276

Inorganic Impinger Contents 1.0714 0.3286

Organic Impinger Contents 0.9286 0.3714

Cyclone Wash 2.5<PM<10 0.0364 1.2636

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0308 1.2692

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0530 2.6470

Filter0.3000

--

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Analytical - Run (3)

Page 189: Division of Environmental Permits Floor

11-PM-Base-FB

0.00 (mg)

Date Time

Final Tare Gain

(g) (g) (mg) (mg)

0.0015 0.0000 1.0714 1.5000

0.0013 0.0000 0.9286 1.3000Organic Impinger Contents

Inorganic Impinger Contents

Sample Portion

Gravimetric Concentrations

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

Actual Gain

max 2 mg total blank adjustment, proportioned

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG11-PM_BASE Analytical - FB (1)

Page 190: Division of Environmental Permits Floor

11-PM-Base wDB-1

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

1 09:24

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

2.5000 47.0000

1.3000 44.0000

1.7000 25.0000

2.1000 371.1133

1.9000 197.2686

Adjusted Gain

(mg)

0.3000

2.4628

1.26520.0348

0.0198

1.0714

0.9286 0.9714

Blank Adjustment

(mg)

1.6802

1.0286

Run Start Time

Blank and Titration Concentrations

Blank TypeConcentration

(mg/ml)

CPV Valley Energy Center

CTG-11 Stack

sie-19-middletown.ny-comp#2

NO

Run

Estimated Leak Volume

Inorganic Impinger Contents Maxxam

Organic Impinger Contents

Inorganic Impinger Contents

Organic Impinger Contents

Filter Beaker

Nozzle Wash PM>10

Cyclone Wash 2.5<PM<10

Cyclone Exit to Front Half of Filter Wash (<2.5)

--

--

0.0372

Gravimetric Concentrations

Sample Portion

Filter0.3000

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

SAMPLE ANALYTICAL DATA SHEET

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Sample Type Sample Number

Analytical Data

Sample Leakage Evident

Sampling Location

Project #

Plant Name

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Analytical - Run (1)

Page 191: Division of Environmental Permits Floor

11-PM-Base wDB-2

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

2 13:52

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

4.2000 56.0000

1.7000 47.0000

1.2000 40.0000

1.8000 341.0231

1.5000 227.6176

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

SAMPLE ANALYTICAL DATA SHEET

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0443 4.1557

Filter0.3000

--

Inorganic Impinger Contents 1.0714 0.7286

Organic Impinger Contents 0.9286 0.5714

Cyclone Wash 2.5<PM<10 0.0372 1.6628

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0316 1.1684

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Analytical - Run (2)

Page 192: Division of Environmental Permits Floor

11-PM-Base wDB-3

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

3 13:48

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

2.8000 60.0000

7.4000 51.0000

2.7000 39.0000

1.6000 250.7523

1.3000 182.0941

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

SAMPLE ANALYTICAL DATA SHEET

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0475 2.7525

Filter0.3000

--

Inorganic Impinger Contents 1.0714 0.5286

Organic Impinger Contents 0.9286 0.3714

Cyclone Wash 2.5<PM<10 0.0403 7.3597

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0308 2.6692

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Analytical - Run (3)

Page 193: Division of Environmental Permits Floor

11-PM-Base wDB-FB

0.00 (mg)

Date Time

Final Tare Gain

(g) (g) (mg) (mg)

0.0015 0.0000 1.0714 1.5000

0.0013 0.0000 0.9286 1.3000

SAMPLE ANALYTICAL DATA SHEET

Plant Name CPV Valley Energy Center

Sampling Location CTG-11 Stack

Actual Gain

max 2 mg total blank adjustment, proportioned

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Inorganic Impinger Contents

Sample Portion

Gravimetric Concentrations

Organic Impinger Contents

sie-19-middletown.ny-comp#1-CTG11-PM_BASE WDB Analytical - FB (1)

Page 194: Division of Environmental Permits Floor

QUALITY ASSURANCE AND QUALITY CONTROL DATA

Unit #CTG-12 Summary PM Laboratory Analysis

Page 195: Division of Environmental Permits Floor

12-PM-Base-1

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

1 08:57

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.7000 54.0000

1.3000 40.0000

2.5000 32.0000

1.6000 240.7222

1.4000 147.1927

Analytical Data

Sample Leakage Evident

Sampling Location

Project #

Plant Name

SAMPLE ANALYTICAL DATA SHEET

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Sample Type Sample Number

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Inorganic Impinger Contents

Organic Impinger Contents

Filter Beaker

Nozzle Wash PM>10

Cyclone Wash 2.5<PM<10

Cyclone Exit to Front Half of Filter Wash (<2.5)

--

--

0.0427

Gravimetric Concentrations

Sample Portion

Filter0.3000

CPV Valley Energy Center

CTG-12 Stack

sie-19-middletown.ny-comp#2

NO

Run

Estimated Leak Volume

Inorganic Impinger Contents Maxxam

Organic Impinger Contents

Run Start Time

Blank and Titration Concentrations

Blank TypeConcentration

(mg/ml)

Blank Adjustment

(mg)

2.4747

0.5286

Adjusted Gain

(mg)

0.3000

1.6573

1.26840.0316

0.0253

1.0714

0.9286 0.4714

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Analytical - Run (1)

Page 196: Division of Environmental Permits Floor

12-PM-Base-2

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

2 08:22

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

3.5000 59.0000

1.7000 62.0000

1.6000 40.0000

1.7000 210.6319

1.6000 145.6753

Inorganic Impinger Contents 1.0714 0.6286

Organic Impinger Contents 0.9286 0.6714

Cyclone Wash 2.5<PM<10 0.0490 1.6510

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0316 1.5684

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0467 3.4533

Filter0.3000

--

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Analytical - Run (2)

Page 197: Division of Environmental Permits Floor

12-PM-Base-3

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

3 12:52

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.6000 67.0000

0.9000 56.0000

2.1000 50.0000

1.6000 210.6319

1.2000 166.9196

Inorganic Impinger Contents 1.0714 0.5286

Organic Impinger Contents 0.9286 0.2714

Cyclone Wash 2.5<PM<10 0.0443 0.8557

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0396 2.0605

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0530 1.5470

Filter0.3000

--

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Analytical - Run (3)

Page 198: Division of Environmental Permits Floor

12-PM-Base-FB

0.00 (mg)

Date Time

Final Tare Gain

(g) (g) (mg) (mg)

0.0015 0.0000 1.0714 1.5000

0.0013 0.0000 0.9286 1.3000Organic Impinger Contents

Inorganic Impinger Contents

Sample Portion

Gravimetric Concentrations

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

Actual Gain

max 2 mg total blank adjustment, proportioned

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG12-PM_BASE Analytical - FB (1)

Page 199: Division of Environmental Permits Floor

12-PM-Base wDB-1

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

1 09:02

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.3000 35.0000

2.0000 38.0000

1.2000 26.0000

1.7000 240.7222

1.3000 144.1578

Analytical Data

Sample Leakage Evident

Sampling Location

Project #

Plant Name

SAMPLE ANALYTICAL DATA SHEET

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Sample Type Sample Number

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Inorganic Impinger Contents

Organic Impinger Contents

Filter Beaker

Nozzle Wash PM>10

Cyclone Wash 2.5<PM<10

Cyclone Exit to Front Half of Filter Wash (<2.5)

--

--

0.0277

Gravimetric Concentrations

Sample Portion

Filter0.3000

CPV Valley Energy Center

CTG-12 Stack

sie-19-middletown.ny-comp#2

NO

Run

Estimated Leak Volume

Inorganic Impinger Contents Maxxam

Organic Impinger Contents

Run Start Time

Blank and Titration Concentrations

Blank TypeConcentration

(mg/ml)

Blank Adjustment

(mg)

1.1794

0.6286

Adjusted Gain

(mg)

0.3000

1.2723

1.96990.0301

0.0206

1.0714

0.9286 0.3714

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Analytical - Run (1)

Page 200: Division of Environmental Permits Floor

12-PM-Base wDB-2

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

2 13:20

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.9000 53.0000

1.8000 51.0000

1.5000 41.0000

1.8000 310.9328

1.2000 212.4431

Inorganic Impinger Contents 1.0714 0.7286

Organic Impinger Contents 0.9286 0.2714

Cyclone Wash 2.5<PM<10 0.0403 1.7597

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0324 1.4676

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0419 1.8581

Filter0.3000

--

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Analytical - Run (2)

Page 201: Division of Environmental Permits Floor

12-PM-Base wDB-3

0.00 (mg)

Date Time

Weight Volume Mass

(g) (ml) (mg)

0.0020 250.0000 --

0.0003 250.7523 --

0.0003 242.7921 --

3 13:28

Final Tare Gain Volume

(g) (g) (mg) (ml)

--

--

1.7000 71.0000

1.5000 53.0000

2.5000 31.0000

2.0000 260.7823

1.2000 166.9196

Inorganic Impinger Contents 1.0714 0.9286

Organic Impinger Contents 0.9286 0.2714

Cyclone Wash 2.5<PM<10 0.0419 1.4581

Cyclone Exit to Front Half of Filter Wash (<2.5) 0.0245 2.4755

0.3000Filter Beaker --

Nozzle Wash PM>10 0.0562 1.6438

Filter0.3000

--

Start Time

Sample PortionBlank Adjustment Adjusted Gain

(mg) (mg)

Gravimetric Concentrations Run

Hexane Blank Weight of Solids 0.001236

Acetone Blank Weight of Solids 0.000791

DI Water Blank Weight of Solids 0.001196

Blank TypeConcentration

(mg/ml)

Blank and Titration Concentrations

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

Cyclone Wash 2.5<PM<10 Maxxam

Cyclone Exit to Front Half of Filter Wash (<2.5) Maxxam

Filter Maxxam

Nozzle Wash PM>10 Maxxam

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Analytical - Run (3)

Page 202: Division of Environmental Permits Floor

12-PM-Base wDB-FB

0.00 (mg)

Date Time

Final Tare Gain

(g) (g) (mg) (mg)

0.0015 0.0000 1.0714 1.5000

0.0013 0.0000 0.9286 1.3000Organic Impinger Contents

Inorganic Impinger Contents

Sample Portion

Gravimetric Concentrations

Sample Type Sample Number

Sample Leakage Evident NO Estimated Leak Volume

Plant Name CPV Valley Energy Center

Sampling Location CTG-12 Stack

Actual Gain

max 2 mg total blank adjustment, proportioned

Analytical Data Run

Project # sie-19-middletown.ny-comp#2

Inorganic Impinger Contents Maxxam

Organic Impinger Contents Maxxam

SAMPLE ANALYTICAL DATA SHEET

sie-19-middletown.ny-comp#1-CTG12-PM_BASE WDB Analytical - FB (1)

Page 203: Division of Environmental Permits Floor

QUALITY ASSURANCE AND QUALITY CONTROL DATA

Maxxam Laboratory Analysis Report

Page 204: Division of Environmental Permits Floor

Prepared for: Air Hygiene International Inc  

Project: SIE‐19‐MIDDLETOWN.NY‐COMP#2   

  

Analytical Data Package    

Analysis: Method 201A, Method 202  

   

Maxxam Job #: B937745  

  

Maxxam Analytics International 6740 Campobello Rd. 

Mississauga, Ontario, Canada L5N 2L8 

1‐800‐668‐0639 www.maxxam.ca 

Page 205: Division of Environmental Permits Floor

I hereby certify that to the best of my knowledge all analytical data presented in this report:        Has been checked for completeness.  Is accurate, legible and error free.  Has been conducted in accordance with approved SOP’s and that all deviations are clearly listed 

in the Case Narrative.  This report has been generated in .pdf format. 

   

  Review Performed By:               

Maxxam Analytics International 6740 Campobello Rd. 

Mississauga, Ontario, Canada L5N 2L8 

1‐800‐668‐0639 www.maxxamanalytics.com 

Maxxam Analytics Inc Page 2 of 45

Page 206: Division of Environmental Permits Floor

Glossary of Terms  

MDL represents the Minimum Detection Limit below which the laboratory cannot confirm the presence of the analyte to the 95% confidence level. 

RDL represents the Reportable Detection Limit and is usually set at a value equivalent to the lowest calibration standard 

Acceptance Criteria are values used by the laboratory to determine that a process is in control. 

Accuracy is the degree of agreement of a measured value with the true or expected value. 

Calibration Standards are a set of solutions containing the analytes of interest at a specified concentration. 

Calibration Verification Standard consists of a calibration standard solution of intermediate concentration (mid‐point initial calibration level) used to access whether the initial calibration is still valid 

Certified Reference Material is a stable homogenous material that is certified by 

repetitive analysis from a supplier who is certified to generate said materials.  Internal Standard a deuterated or 13C‐labelled analyte that is added to a 

sample extract prior to instrumental analysis to compensate for injection variablity. 

Isomer is a member of a group of compounds that differ from each other only in the locations of a specific number of common substituent atoms or groups of atoms on the parent compound. 

Method Blank is a laboratory control sample using reagents that are known to be free of contamination. 

Precision is the degree of agreement between the data generated from repetitive measurements under specific conditions. 

Quality Assurance is a system of activities whose purpose is to provide the producer or user of a product with the assurance that the product meets a defined standard of quality. 

Quality Control is the overall system of activities whose purpose is to control the quality of a product so that it meets the needs of the end user. 

RSD is the relative standard deviation. 

Blank Spike is a laboratory control sample that has been fortified with native analytes of interest. 

Window Defining Mixture is a solution containing only the earliest and latest eluting congeners within each homologous group of target analytes on a specified GC column. 

RPD or Relative Percent Difference. A measure used to compare duplicate sample analysis. 

EMPC/NDR – Peak detected does not meet ratio criteria and has resulted in a higher detection limit. 

Maxxam Analytics Inc Page 3 of 45

Page 207: Division of Environmental Permits Floor

   

                                      

1.0 Project Narrative                           

Maxxam Analytics International 

6740 Campobello Rd. Mississauga, 

Ontario, Canada 

L5N 2L8 

1‐800‐668‐0639 

www.maxxamanalytics.com 

Maxxam Analytics Inc Page 4 of 45

Page 208: Division of Environmental Permits Floor

PROJECT NARRATIVE

Maxxam Analytics

Client Project #: SIE‐19‐MIDDLETOWN.NY‐COMP#2

Client:    Air Hygiene International Inc

Client Project: SIE‐19‐MIDDLETOWN.NY‐COMP#2  

I. SAMPLE RECEIPT/ANALYSIS

a) Sample Listing

Maxxam Client Date Date Date Date

ID Sample ID Sampled Received Prepped Run

<2.5um Particulates in Rinse

IYU734 M201A‐ U1‐ BASE‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU735 M201A‐ U1‐ BASE‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU736 M201A‐ U1‐ BASE‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU737 M201A‐ U1‐ BASE WDB‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU738 M201A‐ U1‐ BASE WDB‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU739 M201A‐ U1‐ BASE WDB‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU740 M201A‐ U2‐ BASE‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU741 M201A‐ U2‐ BASE‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU742 M201A‐ U2‐ BASE‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU743 M201A‐ U2‐ BASE WDB‐ R1 2019/02/08 2019/02/11 2019/02/13 2019/02/15

IYU744 M201A‐ U2‐ BASE WDB‐ R2 2019/02/08 2019/02/11 2019/02/13 2019/02/15

IYU745 M201A‐ U2‐ BASE WDB‐ R3 2019/02/08 2019/02/11 2019/02/13 2019/02/15

>10um Particulates in Rinse 

IYU734 M201A‐ U1‐ BASE‐ R1 2019/02/11 2019/02/15 2019/02/15

IYU735 M201A‐ U1‐ BASE‐ R2 2019/02/11 2019/02/15 2019/02/15

IYU736 M201A‐ U1‐ BASE‐ R3 2019/02/11 2019/02/15 2019/02/15

IYU737 M201A‐ U1‐ BASE WDB‐ R1 2019/02/11 2019/02/15 2019/02/15

IYU738 M201A‐ U1‐ BASE WDB‐ R2 2019/02/11 2019/02/15 2019/02/15

IYU739 M201A‐ U1‐ BASE WDB‐ R3 2019/02/11 2019/02/15 2019/02/15

IYU740 M201A‐ U2‐ BASE‐ R1 2019/02/11 2019/02/15 2019/02/15

IYU741 M201A‐ U2‐ BASE‐ R2 2019/02/11 2019/02/15 2019/02/15

IYU742 M201A‐ U2‐ BASE‐ R3 2019/02/11 2019/02/15 2019/02/15

IYU743 M201A‐ U2‐ BASE WDB‐ R1 2019/02/08 2019/02/11 2019/02/15 2019/02/15

IYU744 M201A‐ U2‐ BASE WDB‐ R2 2019/02/08 2019/02/11 2019/02/15 2019/02/15

IYU745 M201A‐ U2‐ BASE WDB‐ R3 2019/02/08 2019/02/11 2019/02/15 2019/02/15

2.5 um Particulates on Filter

IYU698 M201A‐ BLANK 2019/02/11 N/A 2019/02/14

IYU734 M201A‐ U1‐ BASE‐ R1 2019/02/11 N/A 2019/02/14

IYU735 M201A‐ U1‐ BASE‐ R2 2019/02/11 N/A 2019/02/14

IYU736 M201A‐ U1‐ BASE‐ R3 2019/02/11 N/A 2019/02/14

IYU737 M201A‐ U1‐ BASE WDB‐ R1 2019/02/11 N/A 2019/02/14

IYU738 M201A‐ U1‐ BASE WDB‐ R2 2019/02/11 N/A 2019/02/14

IYU739 M201A‐ U1‐ BASE WDB‐ R3 2019/02/11 N/A 2019/02/14

IYU740 M201A‐ U2‐ BASE‐ R1 2019/02/11 N/A 2019/02/14

IYU741 M201A‐ U2‐ BASE‐ R2 2019/02/11 N/A 2019/02/14

IYU742 M201A‐ U2‐ BASE‐ R3 2019/02/11 N/A 2019/02/14

IYU743 M201A‐ U2‐ BASE WDB‐ R1 2019/02/08 2019/02/11 N/A 2019/02/14

IYU744 M201A‐ U2‐ BASE WDB‐ R2 2019/02/08 2019/02/11 N/A 2019/02/14

IYU745 M201A‐ U2‐ BASE WDB‐ R3 2019/02/08 2019/02/11 N/A 2019/02/14

2.5‐10um Particulates in Rinse

IYU734 M201A‐ U1‐ BASE‐ R1 2019/02/11 2019/02/15 2019/02/15

IYU735 M201A‐ U1‐ BASE‐ R2 2019/02/11 2019/02/15 2019/02/15

IYU736 M201A‐ U1‐ BASE‐ R3 2019/02/11 2019/02/15 2019/02/15

IYU737 M201A‐ U1‐ BASE WDB‐ R1 2019/02/11 2019/02/15 2019/02/15

IYU738 M201A‐ U1‐ BASE WDB‐ R2 2019/02/11 2019/02/15 2019/02/15

IYU739 M201A‐ U1‐ BASE WDB‐ R3 2019/02/11 2019/02/15 2019/02/15

IYU740 M201A‐ U2‐ BASE‐ R1 2019/02/11 2019/02/15 2019/02/15

IYU741 M201A‐ U2‐ BASE‐ R2 2019/02/11 2019/02/15 2019/02/15

IYU742 M201A‐ U2‐ BASE‐ R3 2019/02/11 2019/02/15 2019/02/15

IYU743 M201A‐ U2‐ BASE WDB‐ R1 2019/02/08 2019/02/11 2019/02/15 2019/02/15

IYU744 M201A‐ U2‐ BASE WDB‐ R2 2019/02/08 2019/02/11 2019/02/15 2019/02/15

IYU745 M201A‐ U2‐ BASE WDB‐ R3 2019/02/08 2019/02/11 2019/02/15 2019/02/15

Extractable Condensables (M202)

IYU372 M202‐ HEXANE BLANK 2019/02/11 2019/02/13 2019/02/15

IYU373 M202‐ FB 2019/02/11 2019/02/13 2019/02/15

IYU374 M202‐ U1‐ BASE‐ R1 2019/02/11 2019/02/13 2019/02/15

Maxxam Analytics Inc Page 5 of 45

Page 209: Division of Environmental Permits Floor

IYU375 M202‐ U1‐ BASE‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU376 M202‐ U1‐ BASE‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU377 M202‐ U1‐ BASE WDB‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU378 M202‐ U1‐ BASE WDB‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU379 M202‐ U1‐ BASE WDB‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU691 M202‐ U2‐ BASE‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU692 M202‐ U2‐ BASE‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU693 M202‐ U2‐ BASE‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU694 M202‐ U2‐ BASE WDB‐ R1 2019/02/08 2019/02/11 2019/02/13 2019/02/15

IYU695 M202‐ U2‐ BASE WDB‐ R2 2019/02/08 2019/02/11 2019/02/13 2019/02/15

IYU696 M202‐ U2‐ BASE WDB‐ R3 2019/02/08 2019/02/11 2019/02/13 2019/02/15

Non Extractable Condensibles (M202)

IYU371 M202‐ DI WATER BLANK 2019/02/11 2019/02/13 2019/02/15

IYU373 M202‐ FB 2019/02/11 2019/02/13 2019/02/15

IYU374 M202‐ U1‐ BASE‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU375 M202‐ U1‐ BASE‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU376 M202‐ U1‐ BASE‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU377 M202‐ U1‐ BASE WDB‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU378 M202‐ U1‐ BASE WDB‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU379 M202‐ U1‐ BASE WDB‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU691 M202‐ U2‐ BASE‐ R1 2019/02/11 2019/02/13 2019/02/15

IYU692 M202‐ U2‐ BASE‐ R2 2019/02/11 2019/02/13 2019/02/15

IYU693 M202‐ U2‐ BASE‐ R3 2019/02/11 2019/02/13 2019/02/15

IYU694 M202‐ U2‐ BASE WDB‐ R1 2019/02/08 2019/02/11 2019/02/13 2019/02/15

IYU695 M202‐ U2‐ BASE WDB‐ R2 2019/02/08 2019/02/11 2019/02/13 2019/02/15

IYU696 M202‐ U2‐ BASE WDB‐ R3 2019/02/08 2019/02/11 2019/02/13 2019/02/15

Particulates/Acetone Rinse (M5/315/M201)

IYU698 M201A‐ BLANK 2019/02/11 2019/02/13 2019/02/15

b) Shipping Problems: none encountered

c) Documentation Problems: none encountered

II. SAMPLE PREP:

No problems encountered

III. SAMPLE ANALYSIS:

See also comments within the appropriate Certificate of Analysis

a) Hold Times: all within recommended hold times

b) Instrument Calibration: all within control limits

c) Quality Control: All applicable QC meets control criteria, except where otherwise noted.

d) All analytes requiring manual intergration(s) are noted on the sample chromatograms

2019/02/19

  Julian Tong ‐ Project Manager Assistant Date

Run Date is defined as the date of injection of the last calibration standard (12 hours or less) prior to the samples 

analyzed within that run sequence.  Therefore the time of calibration injection that defines the run date is always 

within 12 hours of the time of sample injection.

I certify that this data package is in compliance with the terms and conditions of the contract, both technically and for 

other than the conditions detailed above.

In addition, I certify, that to the best of my knowledge and belief, the data as reported are true and accurate.  Release 

of the data contained in this data package has been authorized by the cognizant laboratory official or his/her designee, 

as verified by this signature.

Maxxam Analytics Inc Page 6 of 45

Page 210: Division of Environmental Permits Floor

2.0 Summary Report           

     

 Maxxam Analytics International 

6740 Campobello Rd. Mississauga, Ontario, Canada 

L5N 2L8 1‐800‐668‐0639 

www.maxxamanalytics.com Maxxam Analytics Inc Page 7 of 45

Page 211: Division of Environmental Permits Floor

MAXXAM JOB #: B937745Received: 2019/02/11, 15:45

CERTIFICATE OF ANALYSIS

Your Project #: SIE-19-MIDDLETOWN.NY-COMP#2

Report Date: 2019/02/19Report #: R5599244

Version: 2 - Final

Attention: Data Reports

Air Hygiene International Inc1600 West Tacoma StreetBroken Arrow, OKUSA 74012

Sample Matrix: Stack Sampling Train# Samples Received: 28

Analyses QuantityDateExtracted

DateAnalyzed Laboratory Method Reference

Extractable Condensables (M202) 14 2019/02/13 2019/02/15 BRL SOP-00118 EPA 202 m

Non Extractable Condensibles (M202) 14 2019/02/13 2019/02/15 BRL SOP-00118 / BRL SOP-00109

EPA 202 m

>10um Particulates in Rinse 12 2019/02/15 2019/02/15 BRL SOP-00109 EPA M201A

2.5-10um Particulates in Rinse 12 2019/02/15 2019/02/15 BRL SOP-00109 EPA M201A

2.5 um Particulates on Filter 13 N/A 2019/02/14 BRL SOP-00109 EPA M201A

<2.5um Particulates in Rinse 12 2019/02/13 2019/02/15 BRL SOP-00109 EPA M201A

Particulates/Acetone Rinse (M5/315/M201) 1 2019/02/13 2019/02/15 BRL SOP-00109 EPA 5/315 m

Final Volume of Acetone Probe Rinse 13 N/A 2019/02/15 BRL SOP-00109

Weight of Solvent from Impingers 14 N/A 2019/02/19

Weight of Water from Impingers 14 N/A 2019/02/15

Remarks:

Maxxam Analytics' laboratories are accredited to ISO/IEC 17025:2005 for specific parameters on scopes of accreditation. Unless otherwise noted,procedures used by Maxxam are based upon recognized Provincial, Federal or US method compendia such as CCME, MDDELCC, EPA, APHA.

All work recorded herein has been done in accordance with procedures and practices ordinarily exercised by professionals in Maxxam’s profession usingaccepted testing methodologies, quality assurance and quality control procedures (except where otherwise agreed by the client and Maxxam in writing). Alldata is in statistical control and has met quality control and method performance criteria unless otherwise noted. All method blanks are reported; unlessindicated otherwise, associated sample data are not blank corrected. Where applicable, unless otherwise noted, Measurement Uncertainty has not beenaccounted for when stating conformity to the referenced standard.

Maxxam Analytics' liability is limited to the actual cost of the requested analyses, unless otherwise agreed in writing. There is no other warranty expressedor implied. Maxxam has been retained to provide analysis of samples provided by the Client using the testing methodology referenced in this report.Interpretation and use of test results are the sole responsibility of the Client and are not within the scope of services provided by Maxxam, unless otherwiseagreed in writing. Maxxam is not responsible for the accuracy or any data impacts, that result from the information provided by the customer or theiragent.

Solid sample results, except biota, are based on dry weight unless otherwise indicated. Organic analyses are not recovery corrected except for isotopedilution methods.Results relate to samples tested. When sampling is not conducted by Maxxam, results relate to the supplied samples tested.This Certificate shall not be reproduced except in full, without the written approval of the laboratory.Reference Method suffix “m” indicates test methods incorporate validated modifications from specific reference methods to improve performance.

* RPDs calculated using raw data. The rounding of final results may result in the apparent difference.

Page 1 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 8 of 45

Page 212: Division of Environmental Permits Floor

MAXXAM JOB #: B937745Received: 2019/02/11, 15:45

CERTIFICATE OF ANALYSIS

Your Project #: SIE-19-MIDDLETOWN.NY-COMP#2

Report Date: 2019/02/19Report #: R5599244

Version: 2 - Final

Attention: Data Reports

Air Hygiene International Inc1600 West Tacoma StreetBroken Arrow, OKUSA 74012

Encryption Key

Please direct all questions regarding this Certificate of Analysis to your Project Manager.Clayton Johnson, Project Manager - Air Toxics, Source EvaluationEmail: [email protected]# (905)817-5769==================================================================== Maxxam has procedures in place to guard against improper use of the electronic signature and have the required "signatories", as per section 5.10.2 of ISO/IEC 17025:2005(E), signing the reports. For Service Group specific validation please refer to the Validation Signature Page.

Total Cover Pages : 2Page 2 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 9 of 45

Page 213: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

EPA M201A - PARTICULATES (STACK SAMPLING TRAIN)

Maxxam ID IYU736 IYU737 IYU738

Sampling Date

UNITSM201A- U1- BASE-

R3M201A- U1- BASE

WDB- R1M201A- U1- BASE

WDB- R2RDL QC Batch

> 10 Particulate Weight in Acetone Rinse mg 2.7 2.5 4.2 0.5 5972676

< 2.5 Particulate Weight in Acetone Rinse mg 1.3 1.7 1.2 0.5 5972674

2.5 - 10 Particulate Weight in Acetone Rinse mg 1.3 1.3 1.7 0.5 5972675

< 2.5 Particulate Weight on Filter mg (-1.10000) ND (-0.30000) ND (-1.10000) ND (1) 0.30 5975069

Acetone Rinse Volume (10) ml 67 47 56 1 5972677

Acetone Rinse Volume (2.5 - 10) ml 46 44 47 1 5972677

Acetone Rinse Volume (2.5) ml 39 25 40 1 5972677

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

(1) Negative weight observed

LFT Loose filter material in the petri dishDE Edges of the filter are frayed

Maxxam ID IYU698 IYU734 IYU735

Sampling Date

UNITS M201A- BLANKM201A- U1- BASE-

R1M201A- U1- BASE-

R2RDL QC Batch

> 10 Particulate Weight in Acetone Rinse mg N/A 1.4 1.4 0.5 5972676

< 2.5 Particulate Weight in Acetone Rinse mg N/A 1.6 1.9 0.5 5972674

2.5 - 10 Particulate Weight in Acetone Rinse mg N/A 1.1 1.4 0.5 5972675

< 2.5 Particulate Weight on Filter mg (0.10000) ND (-0.50000) ND (-0.20000) ND 0.30 5975069

Acetone Rinse Volume (10) ml N/A 49 61 1 5972677

Acetone Rinse Volume (2.5 - 10) ml N/A 42 46 1 5972677

Acetone Rinse Volume (2.5) ml N/A 26 32 1 5972677

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

N/A = Not Applicable

Page 3 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 10 of 45

Page 214: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

EPA M201A - PARTICULATES (STACK SAMPLING TRAIN)

Maxxam ID IYU742 IYU743 IYU744

Sampling Date 2019/02/08 2019/02/08

UNITSM201A- U2- BASE-

R3M201A- U2- BASE

WDB- R1M201A- U2- BASE

WDB- R2RDL QC Batch

> 10 Particulate Weight in Acetone Rinse mg 1.6 1.3 1.9 0.5 5972676

< 2.5 Particulate Weight in Acetone Rinse mg 2.1 1.2 1.5 0.5 5972674

2.5 - 10 Particulate Weight in Acetone Rinse mg 0.9 2.0 1.8 0.5 5972675

< 2.5 Particulate Weight on Filter mg (-0.40000) ND (-0.20000) ND (0.10000) ND 0.30 5975069

Acetone Rinse Volume (10) ml 67 35 53 1 5972677

Acetone Rinse Volume (2.5 - 10) ml 56 38 51 1 5972677

Acetone Rinse Volume (2.5) ml 50 26 41 1 5972677

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

Maxxam ID IYU739 IYU740 IYU741

Sampling Date

UNITSM201A- U1- BASE

WDB- R3M201A- U2- BASE-

R1M201A- U2- BASE-

R2RDL QC Batch

> 10 Particulate Weight in Acetone Rinse mg 2.8 1.7 3.5 0.5 5972676

< 2.5 Particulate Weight in Acetone Rinse mg 2.7 2.5 1.6 0.5 5972674

2.5 - 10 Particulate Weight in Acetone Rinse mg 7.4 1.3 1.7 0.5 5972675

< 2.5 Particulate Weight on Filter mg (-0.50000) ND (-1.30000) ND (1) (-0.60000) ND (2) 0.30 5975069

Acetone Rinse Volume (10) ml 60 54 59 1 5972677

Acetone Rinse Volume (2.5 - 10) ml 51 40 62 1 5972677

Acetone Rinse Volume (2.5) ml 39 32 40 1 5972677

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

(1) Negative weight observed

LFT Loose filter material in the petri dish

(2) LFT Loose filter material in the petri dishDE Edges of the filter are frayed

Page 4 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 11 of 45

Page 215: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

EPA M201A - PARTICULATES (STACK SAMPLING TRAIN)

Maxxam ID IYU745

Sampling Date 2019/02/08

UNITSM201A- U2- BASE

WDB- R3RDL QC Batch

> 10 Particulate Weight in Acetone Rinse mg 1.7 0.5 5972676

< 2.5 Particulate Weight in Acetone Rinse mg 2.5 0.5 5972674

2.5 - 10 Particulate Weight in Acetone Rinse mg 1.5 0.5 5972675

< 2.5 Particulate Weight on Filter mg (-0.20000) ND 0.30 5975069

Acetone Rinse Volume (10) ml 71 1 5972677

Acetone Rinse Volume (2.5 - 10) ml 53 1 5972677

Acetone Rinse Volume (2.5) ml 31 1 5972677

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

Page 5 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 12 of 45

Page 216: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

EPA M202 CONDENSIBLE PM (STACK SAMPLING TRAIN)

Maxxam ID IYU379 IYU691 IYU692 IYU693

Sampling Date

UNITSM202- U1- BASE WDB-

R3M202- U2- BASE-

R1M202- U2- BASE-

R2M202- U2- BASE-

R3RDL QC Batch

Weight g 250 240 210 210 0.1 5973794

Weight of Solvent g 120 97 96 110 0.1 5973791

Miscellaneous Parameters

Inorganic Condensibles mg 1.6 1.6 1.7 1.6 0.5 5973792

Organic Condensibles mg 1.3 1.4 1.6 1.2 1.0 5973788

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

Maxxam ID IYU375 IYU376 IYU377 IYU378

Sampling Date

UNITSM202- U1- BASE-

R2M202- U1- BASE-

R3M202- U1- BASE WDB-

R1M202- U1- BASE WDB-

R2RDL QC Batch

Weight g 240 220 370 340 0.1 5973794

Weight of Solvent g 91 99 130 150 0.1 5973791

Miscellaneous Parameters

Inorganic Condensibles mg 1.9 1.4 2.1 1.8 0.5 5973792

Organic Condensibles mg 1.3 1.3 1.9 1.5 1.0 5973788

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

Maxxam ID IYU371 IYU372 IYU373 IYU374

Sampling Date

UNITSM202- DI WATER

BLANKM202- HEXANE

BLANKM202- FB

M202- U1- BASE-R1

RDL QC Batch

Weight g 250 N/A 230 350 0.1 5973794

Weight of Solvent g N/A 160 99 110 0.1 5973791

Miscellaneous Parameters

Inorganic Condensibles mg (0.30000) ND N/A 1.5 1.8 0.5 5973792

Organic Condensibles mg N/A (0.30000) ND 1.3 1.4 1.0 5973788

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

N/A = Not Applicable

Page 6 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 13 of 45

Page 217: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

EPA M202 CONDENSIBLE PM (STACK SAMPLING TRAIN)

Maxxam ID IYU694 IYU695 IYU696

Sampling Date 2019/02/08 2019/02/08 2019/02/08

UNITSM202- U2- BASE WDB-

R1M202- U2- BASE WDB-

R2M202- U2- BASE WDB-

R3RDL QC Batch

Weight g 240 310 260 0.1 5973794

Weight of Solvent g 95 140 110 0.1 5973791

Miscellaneous Parameters

Inorganic Condensibles mg 1.7 1.8 2.0 0.5 5973792

Organic Condensibles mg 1.3 1.2 1.2 1.0 5973788

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

Page 7 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 14 of 45

Page 218: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

EPA M5 PARTICULATE MATTER (PM)

Maxxam ID IYU698

Sampling Date

UNITS M201A- BLANK RDL QC Batch

Acetone Rinse Particulate Weight in Acetone Rinse mg 2.0 0.5 5972673

Acetone Rinse Volume ml 250 1 5972677

RDL = Reportable Detection Limit

QC Batch = Quality Control Batch

Page 8 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 15 of 45

Page 219: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

TEST SUMMARY

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU371 Collected:Sample ID: M202- DI WATER BLANK

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU372 Collected:Sample ID: M202- HEXANE BLANK

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU373 Collected:Sample ID: M202- FB

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU374 Collected:Sample ID: M202- U1- BASE- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU375 Collected:Sample ID: M202- U1- BASE- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU376 Collected:Sample ID: M202- U1- BASE- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Page 9 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 16 of 45

Page 220: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

TEST SUMMARY

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU376 Collected:Sample ID: M202- U1- BASE- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU377 Collected:Sample ID: M202- U1- BASE WDB- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU378 Collected:Sample ID: M202- U1- BASE WDB- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU379 Collected:Sample ID: M202- U1- BASE WDB- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU691 Collected:Sample ID: M202- U2- BASE- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Page 10 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 17 of 45

Page 221: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

TEST SUMMARY

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU692 Collected:Sample ID: M202- U2- BASE- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU693 Collected:Sample ID: M202- U2- BASE- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU694 Collected: 2019/02/08Sample ID: M202- U2- BASE WDB- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU695 Collected: 2019/02/08Sample ID: M202- U2- BASE WDB- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU696 Collected: 2019/02/08Sample ID: M202- U2- BASE WDB- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Extractable Condensables (M202) BAL 5973788 2019/02/13 2019/02/15 Farag Farag

Non Extractable Condensibles (M202) BAL 5973792 2019/02/13 2019/02/15 Farag Farag

Weight of Solvent from Impingers 5973791 N/A 2019/02/19 Farag Farag

Weight of Water from Impingers 5973794 N/A 2019/02/15 Farag Farag

Page 11 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 18 of 45

Page 222: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

TEST SUMMARY

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU698 Collected:Sample ID: M201A- BLANK

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

Particulates/Acetone Rinse (M5/315/M201) BAL 5972673 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU734 Collected:Sample ID: M201A- U1- BASE- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU735 Collected:Sample ID: M201A- U1- BASE- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU736 Collected:Sample ID: M201A- U1- BASE- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU737 Collected:Sample ID: M201A- U1- BASE WDB- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Page 12 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 19 of 45

Page 223: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

TEST SUMMARY

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU738 Collected:Sample ID: M201A- U1- BASE WDB- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU739 Collected:Sample ID: M201A- U1- BASE WDB- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU740 Collected:Sample ID: M201A- U2- BASE- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU741 Collected:Sample ID: M201A- U2- BASE- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU742 Collected:Sample ID: M201A- U2- BASE- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Page 13 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 20 of 45

Page 224: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

TEST SUMMARY

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU742 Collected:Sample ID: M201A- U2- BASE- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU743 Collected: 2019/02/08Sample ID: M201A- U2- BASE WDB- R1

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU744 Collected: 2019/02/08Sample ID: M201A- U2- BASE WDB- R2

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Test Description Instrumentation Batch Extracted Date Analyzed Analyst

Maxxam ID: IYU745 Collected: 2019/02/08Sample ID: M201A- U2- BASE WDB- R3

Matrix: Stack Sampling TrainShipped:

Received: 2019/02/11

>10um Particulates in Rinse BAL 5972676 2019/02/15 2019/02/15 Farag Farag

2.5-10um Particulates in Rinse BAL 5972675 2019/02/15 2019/02/15 Farag Farag

2.5 um Particulates on Filter BAL 5975069 N/A 2019/02/14 Brenda Moore

<2.5um Particulates in Rinse BAL 5972674 2019/02/13 2019/02/15 Farag Farag

Final Volume of Acetone Probe Rinse 5972677 N/A 2019/02/15 Farag Farag

Page 14 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 21 of 45

Page 225: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

GENERAL COMMENTS

All water samples were received in plastic bottles, transferred into amber glass bottles for oven evaporation

Sample IYU371 [M202- DI WATER BLANK] : INORGANIC EXTRACTION : No material found in Teflon dish.

Sample IYU372 [M202- HEXANE BLANK] : ORGANIC EXTRACTION : No material noticed in the vial.

Sample IYU373 [M202- FB] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU374 [M202- U1- BASE- R1] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU375 [M202- U1- BASE- R2] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU376 [M202- U1- BASE- R3] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU377 [M202- U1- BASE WDB- R1] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU378 [M202- U1- BASE WDB- R2] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU379 [M202- U1- BASE WDB- R3] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU691 [M202- U2- BASE- R1] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU692 [M202- U2- BASE- R2] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU693 [M202- U2- BASE- R3] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU694 [M202- U2- BASE WDB- R1] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU695 [M202- U2- BASE WDB- R2] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU696 [M202- U2- BASE WDB- R3] : ORGANIC EXTRACTION : Oily material found in vial.INORGANIC EXTRACTION : Whitish residue found in Teflon dish.

Sample IYU698 [M201A- BLANK] : Acetone fraction: Observed traces of oily residue

Sample IYU734 [M201A- U1- BASE- R1] : Acetone fraction: Observed traces of oily residue

Sample IYU735 [M201A- U1- BASE- R2] : Acetone fraction: Observed traces of oily residue

Sample IYU736 [M201A- U1- BASE- R3] : Acetone fraction: Observed traces of oily residue

Sample IYU737 [M201A- U1- BASE WDB- R1] : Acetone fraction: Observed traces of oily residue

Sample IYU738 [M201A- U1- BASE WDB- R2] : Acetone fraction: Observed traces of oily residue

Page 15 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 22 of 45

Page 226: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

Sample IYU739 [M201A- U1- BASE WDB- R3] : Acetone fraction: Observed traces of oily residue

Sample IYU740 [M201A- U2- BASE- R1] : Acetone fraction: Observed traces of oily residue

Sample IYU741 [M201A- U2- BASE- R2] : Acetone fraction: Observed traces of oily residue

Sample IYU742 [M201A- U2- BASE- R3] : Acetone fraction: Observed traces of oily residue

Sample IYU743 [M201A- U2- BASE WDB- R1] : Acetone fraction: Observed traces of oily residue

Sample IYU744 [M201A- U2- BASE WDB- R2] : Acetone fraction: Observed traces of oily residue

Sample IYU745 [M201A- U2- BASE WDB- R3] : Acetone fraction: Observed traces of oily residue

Results relate only to the items tested.

Page 16 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 23 of 45

Page 227: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

QUALITY ASSURANCE REPORT

QA/QCBatch Init QC Type Parameter Date Analyzed Value % Recovery UNITS QC Limits

5972673 FF Method Blank Acetone Rinse Particulate Weight in AcetoneRinse

2019/02/15 (0.20000) ND,RDL=0.5

mg

5972674 FF Method Blank < 2.5 Particulate Weight in Acetone Rinse 2019/02/15 (0.20000) ND,RDL=0.5

mg

5972675 FF Method Blank 2.5 - 10 Particulate Weight in Acetone Rinse 2019/02/15 (0.20000) ND,RDL=0.5

mg

5972676 FF Method Blank > 10 Particulate Weight in Acetone Rinse 2019/02/15 (0.20000) ND,RDL=0.5

mg

5973788 FF Spiked Blank Organic Condensibles 2019/02/15 94 % 70 - 130

5973788 FF Method Blank Organic Condensibles 2019/02/15 (0.20000) ND,RDL=1.0

mg

5973792 FF Method Blank Inorganic Condensibles 2019/02/15 (0) ND,RDL=0.5

mg

Spiked Blank: A blank matrix sample to which a known amount of the analyte, usually from a second source, has been added. Used to evaluate method accuracy.

Method Blank: A blank matrix containing all reagents used in the analytical procedure. Used to identify laboratory contamination.

Page 17 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.ca

Maxxam Analytics Inc Page 24 of 45

Page 228: Division of Environmental Permits Floor

Maxxam Job #: B937745Report Date: 2019/02/19

Air Hygiene International IncClient Project #: SIE-19-MIDDLETOWN.NY-COMP#2

VALIDATION SIGNATURE PAGE

The analytical data and all QC contained in this report were reviewed and validated by the following individual(s).

Brenda Moore, Team Lead, Inorganic

Frank Mo, B.Sc., Inorganic Lab. Manager

Maxxam has procedures in place to guard against improper use of the electronic signature and have the required "signatories", as per section 5.10.2 of ISO/IEC17025:2005(E), signing the reports. For Service Group specific validation please refer to the Validation Signature Page.

Page 18 of 18

Maxxam Analytics International Corporation o/a Maxxam Analytics 6740 Campobello Road, Mississauga, Ontario, L5N 2L8 Tel: (905) 817-5700 Toll-Free: 800-563-6266 Fax: (905) 817-5777 www.maxxam.caMaxxam Analytics Inc Page 25 of 45

Page 229: Division of Environmental Permits Floor

3.0 Sample Custody            

 Maxxam Analytics International 

6740 Campobello Rd. Mississauga, Ontario, Canada 

L5N 2L8 1‐800‐668‐0639 

www.maxxamanalytics.com 

Maxxam Analytics Inc Page 26 of 45

Page 230: Division of Environmental Permits Floor

Pag

e 1

of

4

Maxxam Analytics Inc Page 27 of 45

Page 231: Division of Environmental Permits Floor

Pag

e 2

of

4

Maxxam Analytics Inc Page 28 of 45

Page 232: Division of Environmental Permits Floor

Pag

e 3

of

4

Maxxam Analytics Inc Page 29 of 45

Page 233: Division of Environmental Permits Floor

Pag

e 4

of

4

Maxxam Analytics Inc Page 30 of 45

Page 234: Division of Environmental Permits Floor

4.0 Sample Chromatograms

Maxxam Analytics International

6740 Campobello Rd Mississauga, Ontario, Canada

L5N 2L8 1-800-668-0639

www.maxxamanalytics.com

Maxxam Analytics Inc Page 31 of 45

Page 235: Division of Environmental Permits Floor

Method 201A – Determination of PM10 Emissions 

       

           

 Maxxam Analytics International 

6740 Campobello Rd. Mississauga, Ontario, Canada 

L5N 2L8 1‐800‐668‐0639 

www.maxxamanalytics.com 

Maxxam Analytics Inc Page 32 of 45

Page 236: Division of Environmental Permits Floor

Client ID

Maxxam Job #

startMaxxam Sample ID's IYU698-01R

Analytical Worksheet(s) Filters 5975069 5972676Solvent Rinse 5972673 5972677

Solvent Volumes 59726745972675

Analysis

Analyst ID

Actions: *Impacted Sample ID's

Bottle discrepancies No

Filters damaged Yes

Solvent rinse anomalies No

Water impinger anomalies N/A

Filter blank submitted No

Solvent blank submitted No

Water blank submitted N/A

Other

See data sheets for any anomalies of samples

Inorganic Analysis Action / Comment Form

Comments

Particulates

B Moore / F Farag

Air Hygiene

B937745

Maxxam AnalyticsInorganic AirData Package B937745 M201A Air Hygiene CAM FCD-00813/08Maxxam Analytics Inc Page 33 of 45

Page 237: Division of Environmental Permits Floor

FilterParticulate Weight Log

0.0005 MAXXAMJob # Metals No supplier Pall N/A

Client Filter Blank Submitted No p/n 61631 N/AAnalysis Date of Dessication 2019/02/13 lot # T83173 N/A Type

Balance ID Time of Dessication 11:32 AM M5Condition

DE Edges of filter frayed FT Filter torn FCL Filter contains liquid after dessicatioLPC Loose particulate material in filter containe LFT Loose filter materia

Increment 1 Analyst B Moore B Moore B MooreWeighing Date 2019/02/14 2019/02/15

Weighing Time 11:38 AM 11:32 AM Temperature (ºC) 21 21

Humidity (%) 37 42

Worksheet # # Maxxam # Filter Condition Filter ID # Pre

Weight Weight

#1 Weight

#2 Weight

#3 Weight

#4 Weight

#5 Weight

#6 Weight

#7 Final

Weight Particulate RDL

gm gm gm gm gm gm gm gm gm mg mg

5975069 1 IYU698-01R NORMAL 18010429 0.11235 0.1125 0.1125 0.1125 0.1 0.35975069 2 IYU734-01R NORMAL 18082927 0.11390 0.1134 0.1134 0.1134 -0.5 0.35975069 3 IYU735-01R NORMAL 18010428 0.11300 0.1128 0.1128 0.1128 -0.2 0.35975069 4 IYU736-01R NORMAL 18082940 0.11395 0.1129 0.1129 0.1129 -1.1 0.35975069 5 IYU737-01R NORMAL 18082925 0.11430 0.1140 0.1140 0.1140 -0.3 0.35975069 6 IYU738-01R *DE**LFT* 18082926 0.11175 0.1105 0.1106 0.1106 -1.1 0.35975069 7 IYU739-01R NORMAL 18082928 0.11415 0.1137 0.1136 0.1136 -0.5 0.35975069 8 IYU740-01R LFT 18082933 0.11395 0.1125 0.1127 0.1127 -1.3 0.35975069 9 IYU741-01R *DE**LFT* 18082935 0.11395 0.1132 0.1133 0.1133 -0.6 0.35975069 10 IYU742-01R NORMAL 18082941 0.11240 0.1120 0.1120 0.1120 -0.4 0.3

zero 0.0000 0.0000 0.00000.3000 gm 0.3000 0.2999 0.3000

5975069 11 IYU743-01R NORMAL 18082924 0.11150 0.1112 0.1113 0.1113 -0.2 0.35975069 12 IYU744-01R NORMAL 18082932 0.11210 0.1121 0.1122 0.1122 0.1 0.35975069 13 IYU745-01R NORMAL 18082934 0.11340 0.1132 0.1132 0.1132 -0.2 0.3

14151617181920

zero 0.0000 0.0000 0.00000.3000 gm 0.3000 0.3000 0.3000

21222324252627282930

zero0.3000 gm

31323334353637383940

zero0.3000 gm

Filters are placed in a dessicator for 24 hours minimum prior to beginning weighing cycle. Filters are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of >50 %.

Dickson THDX S/N 6213019220-BALANAL4

Particulate Weight on Filter

B937745Air Hygiene

Maxxam AnalyticsCAM FCD-00813/08FILTERPage 2of 6

Maxxam Analytics Inc Page 34 of 45

Page 238: Division of Environmental Permits Floor

SolventParticulate Weight Log

0.0005 MAXXAMJob # Metals No Solvent

Client Reagent Blank Submitted Yes Lab SupplierAnalysis Date of Dessication 2019/02/13 lot #

Test Code Time of Dessication 3:30 PMBalance ID

Condition

Analyst F Farag F Farag F Farag reagentWeighing Date 2019/02/13 2019/02/14 2019/02/15 blankWeighing Time 12:04 PM 3:41 PM 8:24 AM correction

Temperature (ºC) 22 22 22 IYU698-02RHumidity (%) 41 40 41 2.0

Worksheet # # Maxxam # Bottle Full

Bottle Empty

Solvent Volume Vial ID Pre

Weight Weight

#1 Weight

#2 Weight

#3 Weight

#4 Weight

#5 Weight

#6 Weight

#7 Final

Weight Particulate RDL

gm gm mL gm gm gm gm gm gm gm gm gm mg mg

5972673 1 Blank 252.9 174.4 99.4 K45 25.1578 25.1579 25.1580 25.1580 0.25972673 2 IYU698-02R 230.1 34.4 247.7 K46 24.8638 24.8654 24.8658 Traces of oily residue  24.8658 2.0 0.5

34567891011

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

12131415161718192021

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

22 Blank23242526272829303132

zero zero

100.0 gm 0.3000 gm

33343536373839404142

zero zero

100.0 gm 0.3000 gm

Unusual residue appearance is noted in the appropriate cell.Vials are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of >50%. The residue appearance is noted.

PARTACE-TR (as per M5)220-BALANAL5

Dickson THDX S/N 6213019

B937745 AcetoneAir Hygiene Caledon

Particulate Weight in Acetone Rinse 103158

Maxxam AnalyticsCAM FCD-00813/08SOLVENTPage 3 of 6

Maxxam Analytics Inc Page 35 of 45

Page 239: Division of Environmental Permits Floor

SolventParticulate Weight Log

0.0005 MAXXAMJob # Metals No Solvent

Client Reagent Blank Submitted No Lab SupplierAnalysis Date of Dessication lot #

Test Code Time of DessicationBalance ID

Condition

Analyst F Farag F Farag F Farag reagentWeighing Date 2019/02/13 2019/02/14 2019/02/15 blankWeighing Time 12:07 PM 3:43 PM 8:25 AM correction

Temperature (ºC) 22 22 22 N/AHumidity (%) 41 40 41

Worksheet # # Maxxam # Bottle Full

Bottle Empty

Solvent Volume Vial ID Pre

Weight Weight

#1 Weight

#2 Weight

#3 Weight

#4 Weight

#5 Weight

#6 Weight

#7 Final

Weight Particulate RDL

gm gm mL gm gm gm gm gm gm gm gm gm mg mg

5972674 1 Blank 252.9 174.4 99.4 K45 25.1578 25.1579 25.1580 25.1580 0.2 0.55972674 2 N/A5972674 3 IYU734-02R 55.0 34.3 26.2 K47 24.7231 24.7245 24.7247 Traces of oily residue  24.7247 1.6 0.55972674 4 IYU735-02R 59.4 34.1 32.0 K48 25.1468 25.1490 25.1487 Traces of oily residue  25.1487 1.9 0.55972674 5 IYU736-02R 64.7 34.3 38.5 K49 24.9601 24.9609 24.9614 Traces of oily residue  24.9614 1.3 0.55972674 6 IYU737-02R 53.7 34.3 24.6 K50 24.8031 24.8043 24.8048 Traces of oily residue  24.8048 1.7 0.55972674 7 IYU738-02R 65.7 34.4 39.6 K51 25.1397 25.1410 25.1409 Traces of oily residue  25.1409 1.2 0.55972674 8 IYU739-02R 64.7 34.2 38.6 K52 25.1544 25.1570 25.1571 Traces of oily residue  25.1571 2.7 0.55972674 9 IYU740-02R 59.8 34.4 32.2 K53 24.8540 24.8563 24.8565 Traces of oily residue  24.8565 2.5 0.55972674 10 IYU741-02R 66.1 34.6 39.9 K54 24.7898 24.7914 24.7914 Traces of oily residue  24.7914 1.6 0.55972674 11 IYU742-02R 73.3 34.2 49.5 K55 24.8186 24.8209 24.8207 Traces of oily residue  24.8207 2.1 0.5

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

5972674 12 IYU743-02R 54.4 34.2 25.6 K56 24.8783 24.8794 24.8795 Traces of oily residue  24.8795 1.2 0.55972674 13 IYU744-02R 67.1 34.5 41.3 K57 25.2269 25.2282 25.2284 Traces of oily residue  25.2284 1.5 0.55972674 14 IYU745-02R 58.8 34.2 31.1 K58 24.7073 24.7094 24.7098 Traces of oily residue  24.7098 2.5 0.5

15161718192021

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

22 Blank23242526272829303132

zero zero

100.0 gm 0.3000 gm

33343536373839404142

zero zero

100.0 gm 0.3000 gm

Unusual residue appearance is noted in the appropriate cell.Vials are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of >50%. The residue appearance is noted.

Dickson THDX S/N 6213019220-BALANAL5

AcetoneCaledon103158

PARTACE-TR (as per M5)Particulate Weight in Acetone Rinse

B937745Air Hygiene

Maxxam AnalyticsCAM FCD-00813/08P2.5-TRPage 4 of 6

Maxxam Analytics Inc Page 36 of 45

Page 240: Division of Environmental Permits Floor

SolventParticulate Weight Log

0.0005 MAXXAMJob # Metals No Solvent

Client Reagent Blank Submitted No Lab SupplierAnalysis Date of Dessication 2019/02/13 lot #

Test Code Time of Dessication 3:30 PMBalance ID

Condition

Analyst F Farag F Farag F Farag reagentWeighing Date 2019/02/13 2019/02/14 2019/02/15 blankWeighing Time 12:07 PM 3:58 PM 8:48 AM correction

Temperature (ºC) 22 22 22 N/AHumidity (%) 41 40 41

Worksheet # # Maxxam # Bottle Full

Bottle Empty

Solvent Volume Vial ID Pre

Weight Weight

#1 Weight

#2 Weight

#3 Weight

#4 Weight

#5 Weight

#6 Weight

#7 Final

Weight Particulate RDL

gm gm mL gm gm gm gm gm gm gm gm gm mg mg

5972675 1 Blank 252.9 174.4 99.4 K45 25.1578 25.1579 25.1580 25.1580 0.2 0.55972675 2 N/A5972675 3 IYU734-03R 67.3 34.4 41.6 K59 25.3398 25.3404 25.3409 Traces of oily residue  25.3409 1.1 0.55972675 4 IYU735-03R 70.5 34.3 45.8 K60 25.0331 25.0343 25.0345 Traces of oily residue  25.0345 1.4 0.55972675 5 IYU736-03R 71.0 34.4 46.3 K61 25.2843 25.2860 25.2856 Traces of oily residue  25.2856 1.3 0.55972675 6 IYU737-03R 68.7 34.1 43.8 K62 25.0161 25.0171 25.0174 Traces of oily residue  25.0174 1.3 0.55972675 7 IYU738-03R 71.7 34.3 47.3 K63 24.6407 24.6422 24.6424 Traces of oily residue  24.6424 1.7 0.55972675 8 IYU739-03R 74.6 34.2 51.1 K64 24.8009 24.8086 24.8083 Traces of oily residue  24.8083 7.4 0.55972675 9 IYU740-03R 66.1 34.2 40.4 K65 24.9597 24.9612 24.9610 Traces of oily residue  24.9610 1.3 0.55972675 10 IYU741-03R 83.2 34.2 62.0 K66 24.9245 24.9258 24.9262 Traces of oily residue  24.9262 1.7 0.55972675 11 IYU742-03R 78.2 34.3 55.6 K67 25.0878 25.0882 25.0887 Traces of oily residue  25.0887 0.9 0.5

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

5972675 12 IYU743-03R 64.6 34.3 38.4 K68 25.1347 25.1365 25.1367 Traces of oily residue  25.1367 2.0 0.55972675 13 IYU744-03R 74.9 34.5 51.1 K69 24.9910 24.9930 24.9928 Traces of oily residue  24.9928 1.8 0.55972675 14 IYU745-03R 76.4 34.3 53.3 K70 24.7803 24.7820 24.7818 Traces of oily residue  24.7818 1.5 0.5

15161718192021

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

22 Blank23242526272829303132

zero zero

100.0 gm 0.3000 gm

33343536373839404142

zero zero

100.0 gm 0.3000 gm

Unusual residue appearance is noted in the appropriate cell.Vials are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of >50%. The residue appearance is noted.

PARTACE-TR (as per M5)220-BALANAL5

Dickson THDX S/N 6213019

B937745 AcetoneAir Hygiene Caledon

Particulate Weight in Acetone Rinse 103158

Maxxam AnalyticsCAM FCD-00813/08P2.5-10-TRPage 5 of 6

Maxxam Analytics Inc Page 37 of 45

Page 241: Division of Environmental Permits Floor

SolventParticulate Weight Log

0.0005 MAXXAMJob # Metals No Solvent

Client Reagent Blank Submitted No Lab SupplierAnalysis Date of Dessication 2019/02/13 lot #

Test Code Time of Dessication 3:30 PMBalance ID

Condition

Analyst F Farag F Farag F Farag reagentWeighing Date 2019/02/13 2019/02/14 2019/02/15 blankWeighing Time 12:18 PM 4:04 PM 8:57 AM correction

Temperature (ºC) 22 22 22 N/AHumidity (%) 41 40 41

Worksheet # # Maxxam # Bottle Full

Bottle Empty

Solvent Volume Vial ID Pre

Weight Weight

#1 Weight

#2 Weight

#3 Weight

#4 Weight

#5 Weight

#6 Weight

#7 Final

Weight Particulate RDL

gm gm mL gm gm gm gm gm gm gm gm gm mg mg

5972676 1 Blank 252.9 174.4 99.4 K45 25.1578 25.1579 25.1580 25.1580 0.2 0.55972676 2 N/A5972676 3 IYU734-04R 72.7 34.1 48.9 K71 24.9752 24.9765 24.9766 Traces of oily residue  24.9766 1.4 0.55972676 4 IYU735-04R 82.7 34.3 61.3 K72 24.9209 24.9224 24.9223 Traces of oily residue  24.9223 1.4 0.55972676 5 IYU736-04R 86.8 34.3 66.5 L1 25.1480 25.1503 25.1507 Traces of oily residue  25.1507 2.7 0.55972676 6 IYU737-04R 71.2 34.3 46.7 L2 25.2247 25.2272 25.2272 Traces of oily residue  25.2272 2.5 0.55972676 7 IYU738-04R 78.4 34.2 55.9 L3 25.5390 25.5430 25.5432 Traces of oily residue  25.5432 4.2 0.55972676 8 IYU739-04R 81.2 34.1 59.6 L4 25.2518 25.2542 25.2546 Traces of oily residue  25.2546 2.8 0.55972676 9 IYU740-04R 76.5 34.2 53.5 L5 25.1190 25.1208 25.1207 Traces of oily residue  25.1207 1.7 0.55972676 10 IYU741-04R 81.0 34.4 59.0 L6 25.2602 25.2632 25.2637 Traces of oily residue  25.2637 3.5 0.55972676 11 IYU742-04R 87.4 34.3 67.2 L7 25.3101 25.3121 25.3117 Traces of oily residue  25.3117 1.6 0.5

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

5972676 12 IYU743-04R 62.0 34.3 35.1 L8 24.7951 24.7967 24.7964 Traces of oily residue  24.7964 1.3 0.55972676 13 IYU744-04R 76.2 34.5 52.8 L9 25.0963 25.0979 25.0982 Traces of oily residue  25.0982 1.9 0.55972676 14 IYU745-04R 90.3 34.2 71.0 L10 25.1046 25.1065 25.1063 Traces of oily residue  25.1063 1.7 0.5

15161718192021

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 gm 0.2998 0.2998 0.2998

22 Blank23242526272829303132

zero zero

100.0 gm 0.3000 gm

33343536373839404142

zero zero

100.0 gm 0.3000 gm

Unusual residue appearance is noted in the appropriate cell.Vials are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of >50%. The residue appearance is noted.

PARTACE-TR (as per M5)220-BALANAL5

Dickson THDX S/N 6213019

B937745 AcetoneAir Hygiene Caledon

Particulate Weight in Acetone Rinse 103158

Maxxam AnalyticsCAM FCD-00813/08P10-TRPage 6 of 6

Maxxam Analytics Inc Page 38 of 45

Page 242: Division of Environmental Permits Floor

Method 202 – Determination of Condensible Particulate Emissions from Stationary Sources  

       

           

 Maxxam Analytics International 

6740 Campobello Rd. Mississauga, Ontario, Canada 

L5N 2L8 1‐800‐668‐0639 

www.maxxamanalytics.com 

Maxxam Analytics Inc Page 39 of 45

Page 243: Division of Environmental Permits Floor

Weight of Solvent (Method-202)

Client ID

Maxxam Job #

Analytical Worksheet(s) - solventAnalytical Worksheet(s) - water

Analysis

Analyst ID - solventAnalyst ID - water

No

No

No

Yes

Yes

No

No

* Please note any action or anomalies impacting this set of samples

GENERAL COMMENTS:

Not ApplicableOther

No anomalies were noted in this submission.

No anomalies were noted in this submission.

ACTIONS

Bottle discrepancies

Solvent rinse anomalies

Water impinger anomalies

*COMMENTS

No discrepancies were noted regarding bottles used for samples.

Not Applicable

Not Applicable

Filter anomalies No anomalies were noted in this submission.

Solvent blank submitted

Water blank submitted

METHOD-202 ANALYSIS ACTION/COMMENT FORM

Air Hygiene

B937745

F Farag

Method 202

F Farag

59737885973792

Maxxam AnalyticsInorganic AirData PackagePage 1 of 5

B937745 M202 Air HygieneCAM FCD-00847/5

Maxxam Analytics Inc Page 40 of 45

Page 244: Division of Environmental Permits Floor

Weight of Solvent (Method-202)

0.0005 MAXXAM

Job # Solvent Blank Submitted Yes SolventClient Date of Dessication 2019/02/15 Lab Supplier

Analysis Time of Dessication 12:15 PM lot #Balance ID Date/Time of Extraction 2019/02/15 11:34 AM

Condition Spike ID 21

Spike MeanStd. Deviation Date PreparedSpike Range Min: 79.2 Max: 107.8 Date Expired

Analyst F Farag F Farag F Farag

Weighing Date 2019/02/15 2019/02/16 2019/02/17

Weighing Time 10:21 AM 12:30 PM 1:02 PM Temperature (ºC) 21.7 21.7 21.7

Humidity (%) 25 25 25

Pre Weight

Weight #1

Weight #2

Weight #3

Weight #4

Weight #5

Weight #6

Weight #7

Final Weight

RDL

g g g g g g g g g mg

5973788 1 Blank 200 ml 11.7835 11.7836 11.7837 11.7837 1.05973788 2 Spike 200 ml 11.8066 11.8440 11.8441 11.8441 93.7 % 1.05973788 3 Spike:D1 200 ml N/A N/A N/A ##### ## 1.0

5973788 4 IYU372-01R N/A 442.3 284.2 158 11.8296 11.8302 11.8299 11.8299 1.05973788 5 IYU373-02R Oily 385.1 286.3 99 11.7872 11.7884 11.7885 11.7885 1.05973788 6 IYU374-02R Oily 389.7 281.8 108 11.8210 11.8226 11.8224 11.8224 1.05973788 7 IYU375-02R Oily 374.4 283.5 91 11.8406 11.8418 11.8419 11.8419 1.05973788 8 IYU376-02R Oily 383.3 284.7 99 11.8009 11.8021 11.8022 11.8022 1.05973788 9 IYU377-02R Oily 410.7 283.8 127 11.8241 11.8261 11.8260 11.8260 1.05973788 10 IYU378-02R Oily 427.3 281.0 146 11.8129 11.8143 11.8144 11.8144 1.05973788 11 IYU379-02R Oily 404.8 287.0 118 11.8050 11.8063 11.8063 11.8063 1.05973788 12 IYU691-02R Oily 378.5 281.6 97 11.8126 11.8136 11.8140 11.8140 1.05973788 13 IYU692-02R Oily 382.5 286.1 96 11.7755 11.7768 11.7771 11.7771 1.0

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 0.2998 0.2998 0.2998

5973788 14 IYU693-02R Oily 397.4 286.0 111 11.7872 11.7883 11.7884 11.7884 1.05973788 15 IYU694-02R Oily 376.8 281.5 95 11.7465 11.7479 11.7478 11.7478 1.05973788 16 IYU695-02R Oily 416.7 281.1 136 11.8162 11.8175 11.8174 11.8174 1.05973788 17 IYU696-02R Oily 389.0 280.7 108 11.7902 11.7913 11.7914 11.7914 1.0

181920212223

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 0.2998 0.2998 0.2998

NOTE: Vials are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of 50 %Appearance of residue is noted in the Residue column (Oily residues, color of residues etc.)

Hexane

Fisher

185340

COMMENTS:

Vial #MOGC202#

Solvent Spike

Worksheet # # Maxxam #

93.48

Solvent Weight Before

g

Solvent Weight After

g

Residue Appearance

Solvent Weight

g

4.76

1.31.4

B937745Air Hygiene

Fisher S/N 170291073

Condensibles220-BALANAL5

Residue mg

0.2

0.31.31.41.31.31.91.5

1.6

1.21.31.21.2

Acetone

Caledon

103158

V-1

Acetone

2019/01/09

2019/07/09

Maxxam AnalyticsInorganic AirCON202E-TRPage 2 of 5

B937745 M202 Air HygieneCAM FCD-00847/5

Maxxam Analytics Inc Page 41 of 45

Page 245: Division of Environmental Permits Floor

Weight of Solvent (Method-202)

0.0005 MAXXAM

Job # Water Blank Submitted YesClient Date of Dessication 2019/02/16

Analysis Time of Dessication 9:30 AM

Balance ID 2019/02/15 1:45 PM

Condition

Analyst F Farag F Farag F Farag

Weighing Date 2019/02/15 2019/02/17 2019/02/18

Weighing Time 10:43 AM 1:22 PM 2:59 PM Temperature (ºC) 21.7 21.7 21.5

Humidity (%) 25 25 25

Not Applicable

Pre Weight

Final Weight

Non Extractable

Condensibles

RDL

g g mg mg

5973792 1 Blank 200 ml No 0 2.2512 2.2513 2.2512 2.2512 0.0 0.5Spike 200 ml

Spike:D1 200 ml

5973792 2 IYU371-01R N/A 287.3 37.6 250 No 0 2.4047 2.4048 2.4050 2.4050 0.3 0.55973792 3 IYU373-01R Whitish 283.8 59.1 225 No 0 2.2874 2.2888 2.2889 2.2889 1.5 0.55973792 4 IYU374-01R Whitish 408.0 58.7 349 No 0 2.2900 2.2915 2.2918 2.2918 1.8 0.55973792 5 IYU375-01R Whitish 295.5 57.6 238 No 0 2.2812 2.2829 2.2831 2.2831 1.9 0.55973792 6 IYU376-01R Whitish 278.8 58.8 220 No 0 2.2308 2.2320 2.2322 2.2322 1.4 0.55973792 7 IYU377-01R Whitish 425.1 57.4 368 No 0 2.2940 2.2963 2.2961 2.2961 2.1 0.55973792 8 IYU378-01R Whitish 398.7 58.8 340 No 0 2.3814 2.3834 2.3832 2.3832 1.8 0.55973792 9 IYU379-01R Whitish 312.5 58.7 254 No 0 2.3115 2.3130 2.3131 2.3131 1.6 0.55973792 10 IYU691-01R Whitish 295.8 58.9 237 No 0 2.2391 2.2408 2.2407 2.2407 1.6 0.55973792 11 IYU692-01R Whitish 272.7 58.9 214 No 0 2.2432 2.2449 2.2449 2.2449 1.7 0.5

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 0.2998 0.2998 0.2998

5973792 12 IYU693-01R Whitish 271.6 58.6 213 No 0 2.3456 2.3472 2.3472 2.3472 1.6 0.55973792 13 IYU694-01R Whitish 300.0 58.7 241 No 0 2.2594 2.2610 2.2611 2.2611 1.7 0.55973792 14 IYU695-01R Whitish 364.5 58.6 306 No 0 2.2942 2.2961 2.2960 2.2960 1.8 0.55973792 15 IYU696-01R Whitish 321.5 58.8 263 No 0 2.3573 2.3594 2.3593 2.3593 2.0 0.5

161718192021

zero 0.0 0.0 zero 0.0000 0.0000 0.0000100.0 gm 100.0 100.0 0.3000 0.2998 0.2998 0.2998

NOTE: Vials are not to be exposed to lab atmosphere for > 2 minutes at a relative humidity of 50 %.Appearance of residue is noted in the Residue column (Oily residues, color of residues etc.)

Residue Appearance

Water Weight

g

Water Weight Before

g

Water Weight After

g

Worksheet # # Maxxam #

COMMENTS:

Not Applicable

Not Applicable

Not ApplicableNon-Extractable Condensibles220-BALANAL5

Fisher S/N 170291073Date/Time of Transfer

B937745Air Hygiene

NH4OH Supplier

Neu

traliz

atio

n R

equi

red

Not ApplicableNormailty

6th Weight after 6hrs of 5th wt.

g

1st Weight after 24hrs desiccation

g

2nd Weight after 6hrs of 1st wt.

g

5th Weight after 6hrs of 4th wt.

g

4th Weight after 6hrs of 3rd wt.

g

3rd Weight after 24hrs desiccation

g

p/nlot #

Volume of 0.1 N NH4OH

used ml

Maxxam AnalyticsInorganic AirCOND202-TRPage 3 of 5

B937745 M202 Air HygieneCAM FCD-00847/5

Maxxam Analytics Inc Page 42 of 45

Page 246: Division of Environmental Permits Floor

Weight of Solvent (Method-202)

MAXXAM

Job #

Client

Analysis

Balance ID

Solvent Weight RDL

g g

5973791 1 IYU372-01R 158 0.1

5973791 2 IYU373-02R 99 0.1

5973791 3 IYU374-02R 108 0.1

5973791 4 IYU375-02R 91 0.1

5973791 5 IYU376-02R 99 0.1

5973791 6 IYU377-02R 127 0.1

5973791 7 IYU378-02R 146 0.1

5973791 8 IYU379-02R 118 0.1

5973791 9 IYU691-02R 97 0.1

5973791 10 IYU692-02R 96 0.1

5973791 11 IYU693-02R 111 0.1

5973791 12 IYU694-02R 95 0.1

5973791 13 IYU695-02R 136 0.1

5973791 14 IYU696-02R 108 0.1

15

16

17

18

19

20

B937745

Air Hygiene

Worksheet # Maxxam ##

Weight of Solvent

220-BALANAL10

Maxxam AnalyticsInorganic AirWSOLV-TRPage 4 of 5

B937745 M202 Air HygieneCAM FCD-00847/5

Maxxam Analytics Inc Page 43 of 45

Page 247: Division of Environmental Permits Floor

Weight of Solvent (Method-202)

MAXXAM

Job #

Client

Analysis

Balance ID

Water Weight RDL

g g

5973794 1 IYU371-01R 250 0.1

5973794 2 IYU373-01R 225 0.1

5973794 3 IYU374-01R 349 0.1

5973794 4 IYU375-01R 238 0.1

5973794 5 IYU376-01R 220 0.1

5973794 6 IYU377-01R 368 0.1

5973794 7 IYU378-01R 340 0.1

5973794 8 IYU379-01R 254 0.1

5973794 9 IYU691-01R 237 0.1

5973794 10 IYU692-01R 214 0.1

5973794 11 IYU693-01R 213 0.1

5973794 12 IYU694-01R 241 0.1

5973794 13 IYU695-01R 306 0.1

5973794 14 IYU696-01R 263 0.1

15

16

17

18

19

20

B937745

Air Hygiene

Worksheet # # Maxxam #

Weight

220-BALANAL10

Maxxam AnalyticsInorganic AirWWATER-TRPage 5 of 5

B937745 M202 Air HygieneCAM FCD-00847/5

Maxxam Analytics Inc Page 44 of 45

Page 248: Division of Environmental Permits Floor

This is the last page of the report and is intentionally left blank 

      

        

 Maxxam Analytics International  

6740 Campobello Rd. Mississauga, Ontario, Canada 

L5N 2L8 1‐800‐668‐0639 

www.maxxamanalytics.com Maxxam Analytics Inc Page 45 of 45

Page 249: Division of Environmental Permits Floor

APPENDIX E

FUEL ANALYSIS RECORDS

Page 250: Division of Environmental Permits Floor

Client: CPV Valley LLCLocation: CPV Valley Energy Center

Date:Project #: sie-19-middletown.ny-comp#1

Natural Gas - Fuel Analysis

Mole (%)Molecular1

Weight(lb/lb-mole)

Lbs Component per Lb-Mole

of Gas

Wt. % of Component

Ideal Gross1,3

Heating Value

(Btu/ft3)

Fuel Heat Value [HHV]

(Btu/SCF)

Ideal Net1,3

Heating Value

(Btu/ft3)

Fuel Heat Value [LHV] (Btu/SCF)

Methane CH4 97.784 16.0430 15.69 95.90 994.85 972.80 895.75 875.90

Ethane C2H6 1.862 30.0700 0.56 3.42 1,743.15 32.46 1,594.41 29.69

Propane C3H8 0.047 44.0970 0.02 0.13 2,478.35 1.16 2,280.17 1.07

iso-Butane iC4H10 0.000 58.1230 0.00 0.00 3,203.11 0.00 2,955.38 0.00

n-Butane nC4H10 0.000 58.1230 0.00 0.00 3,213.35 0.00 2,965.62 0.00

Iso-Pentane iC5H12 0.000 72.1500 0.00 0.00 3,940.87 0.00 3,643.50 0.00

n-Pentane nC5H12 0.000 72.1500 0.00 0.00 3,948.75 0.00 3,648.32 0.00

Hexanes C6H14 0.000 86.1770 0.00 0.00 4,684.54 0.00 4,337.82 0.00

Heptanes C7H16 0.000 100.2040 0.00 0.00 5,419.94 0.00 5,023.77 0.00

Octanes C8H18 0.000 114.2310 0.00 0.00 6,155.14 0.00 5,709.23 0.00

Carbon Dioxide CO2 0.029 44.0100 0.01 0.08 0.00 0.00 0.00 0.00

Nitrogen N2 0.278 28.0134 0.08 0.48 0.00 0.00 0.00 0.00

Hydrogen Sulfide H2S 0.000 34.0800 0.00 0.00 627.54 0.00 578.00 0.00

Oxygen O2 0.000 31.9988 0.00 0.00 0.00 0.00 0.00 0.00

Helium He 0.000 4.0026 0.00 0.00 0.00 0.00 0.00 0.00

Hydrogen H2 0.000 2.0159 0.00 0.00 319.34 0.00 269.82 0.00

100.000 16.36 100.00 dry 1,006.42 dry 906.66

wet2,5 983.22 wet2,5 885.76

Component Wt%

Molecular Weight of gas = 16.359 lb/lb-mole carbon 74.65

Btu per lb. of gas4 = 23,700.074 gross (HHV) oxygen 0.06

Btu per lb. of gas4 = 21,350.905 net (LHV) hydrogen 24.81

Density of fuel gas2 = 0.0425 lb/cu. ft nitrogen 0.48

Wt % VOC in fuel gas = 0.13 % helium 0.00

Specific Gravity1 = 0.5648 sulfur 0.00

Total 100.00

8,632.05

F-Factor Calculation:

F-Factor = 1,000,000*((3.64*%H)+(1.53*%C)+(0.57*%S)+(0.14*%N)-(0.46*%O))/GCV

GCV = Gross Btu per lb. of gas (HHV)

%H, %C, %S, %N, & %O are percent weight values calculated from fuel analysis and have units of (scf/lb)/%

Density of natural gas based on specific gravity multiplied by density of air at 68 deg F and 14.696 psia.

References:1 ASTM D 35882 Civil Engineering Reference Manual, 7th ed. - Michael R. Lindeburg3 Mark's Standard Handbook for Mechanical Engineers, 10th ed. - Eugene A. Avallone, Theodore Baumeister III4 Introduction to Fluid Mechanics, 3rd ed. - William S. Janna5 GPA Reference Bulletin 181-86, revised 1986, reprinted 1995

February 9, 2019

Standardized to 68 deg F and 14.696 psia - EPA Standards

F-Factor (SCF dry exhaust per MMBtu [HHV]) =

(Based on EPA RM-19) at 68 deg F and 14.696 psia

Characteristics of Fuel Gas

Gas Component

Totals

sie-19-middletown.ny-comp#1-CTG11-gases App. E

Page 251: Division of Environmental Permits Floor

Client: CPV Valley LLCLocation: CPV Valley Energy Center

Date:Project #: sie-19-middletown.ny-comp#1

Natural Gas - Fuel Analysis

Mole (%)Molecular1

Weight(lb/lb-mole)

Lbs Component per Lb-Mole

of Gas

Wt. % of Component

Ideal Gross1,3

Heating Value

(Btu/ft3)

Fuel Heat Value [HHV]

(Btu/SCF)

Ideal Net1,3

Heating Value

(Btu/ft3)

Fuel Heat Value [LHV] (Btu/SCF)

Methane CH4 97.744 16.0430 15.68 95.83 994.85 972.40 895.75 875.55

Ethane C2H6 1.859 30.0700 0.56 3.42 1,743.15 32.41 1,594.41 29.64

Propane C3H8 0.045 44.0970 0.02 0.12 2,478.35 1.12 2,280.17 1.03

iso-Butane iC4H10 0.000 58.1230 0.00 0.00 3,203.11 0.00 2,955.38 0.00

n-Butane nC4H10 0.000 58.1230 0.00 0.00 3,213.35 0.00 2,965.62 0.00

Iso-Pentane iC5H12 0.000 72.1500 0.00 0.00 3,940.87 0.00 3,643.50 0.00

n-Pentane nC5H12 0.000 72.1500 0.00 0.00 3,948.75 0.00 3,648.32 0.00

Hexanes C6H14 0.000 86.1770 0.00 0.00 4,684.54 0.00 4,337.82 0.00

Heptanes C7H16 0.000 100.2040 0.00 0.00 5,419.94 0.00 5,023.77 0.00

Octanes C8H18 0.000 114.2310 0.00 0.00 6,155.14 0.00 5,709.23 0.00

Carbon Dioxide CO2 0.028 44.0100 0.01 0.08 0.00 0.00 0.00 0.00

Nitrogen N2 0.324 28.0134 0.09 0.55 0.00 0.00 0.00 0.00

Hydrogen Sulfide H2S 0.000 34.0800 0.00 0.00 627.54 0.00 578.00 0.00

Oxygen O2 0.000 31.9988 0.00 0.00 0.00 0.00 0.00 0.00

Helium He 0.000 4.0026 0.00 0.00 0.00 0.00 0.00 0.00

Hydrogen H2 0.000 2.0159 0.00 0.00 319.34 0.00 269.82 0.00

100.000 16.36 100.00 dry 1,005.92 dry 906.21

wet2,5 982.73 wet2,5 885.32

Component Wt%

Molecular Weight of gas = 16.363 lb/lb-mole carbon 74.60

Btu per lb. of gas4 = 23,682.159 gross (HHV) oxygen 0.05

Btu per lb. of gas4 = 21,334.731 net (LHV) hydrogen 24.79

Density of fuel gas2 = 0.0425 lb/cu. ft nitrogen 0.55

Wt % VOC in fuel gas = 0.12 % helium 0.00

Specific Gravity1 = 0.5650 sulfur 0.00

Total 100.00

8,632.49

F-Factor Calculation:

F-Factor = 1,000,000*((3.64*%H)+(1.53*%C)+(0.57*%S)+(0.14*%N)-(0.46*%O))/GCV

GCV = Gross Btu per lb. of gas (HHV)

%H, %C, %S, %N, & %O are percent weight values calculated from fuel analysis and have units of (scf/lb)/%

Density of natural gas based on specific gravity multiplied by density of air at 68 deg F and 14.696 psia.

References:1 ASTM D 35882 Civil Engineering Reference Manual, 7th ed. - Michael R. Lindeburg3 Mark's Standard Handbook for Mechanical Engineers, 10th ed. - Eugene A. Avallone, Theodore Baumeister III4 Introduction to Fluid Mechanics, 3rd ed. - William S. Janna5 GPA Reference Bulletin 181-86, revised 1986, reprinted 1995

February 10, 2019

Standardized to 68 deg F and 14.696 psia - EPA Standards

Gas Component

Characteristics of Fuel Gas

Totals

F-Factor (SCF dry exhaust per MMBtu [HHV]) =

(Based on EPA RM-19) at 68 deg F and 14.696 psia

sie-19-middletown.ny-comp#1-CTG11-gases App. E

Page 252: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

No Results AvailableNumber: 1030-19020581-001A

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample A Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotMethod: GPA-2261M Sample Date: 02/08/2019Cylinder No: 4030-004769 Sample Conditions:500 psig

The above-mentioned sample could not be analyzed properly by our laboratory personnel due to:

No sample; bad valve.

We regret that an analysis could not be performed and recommend that another sample be collected, if appropriate. Please contact us if we can be of any assistance in this matter.

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 1 of 9

Page 253: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

No Results AvailableNumber: 1030-19020581-001A

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample A Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotMethod: ASTM D-5504 Sample Date: 02/08/2019Cylinder No: 4030-004769 Sample Conditions:500 psig

The above-mentioned sample could not be analyzed properly by our laboratory personnel due to:

No sample; bad valve.

We regret that an analysis could not be performed and recommend that another sample be collected, if appropriate. Please contact us if we can be of any assistance in this matter.

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 2 of 9

Page 254: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

No Results AvailableNumber: 1030-19020581-001B

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample A Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotMethod: GPA-2261M Sample Date: 02/08/2019Cylinder No: 1030-07124 Sample Conditions:500 psig

The above-mentioned sample could not be analyzed properly by our laboratory personnel due to:

No sample; valves were in good working condition.

We regret that an analysis could not be performed and recommend that another sample be collected, if appropriate. Please contact us if we can be of any assistance in this matter.

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 3 of 9

Page 255: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

No Results AvailableNumber: 1030-19020581-001B

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample A Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotMethod: ASTM D-5504 Sample Date: 02/08/2019Cylinder No: 1030-07124 Sample Conditions:500 psig

The above-mentioned sample could not be analyzed properly by our laboratory personnel due to:

No sample; valves were in good working condition.

We regret that an analysis could not be performed and recommend that another sample be collected, if appropriate. Please contact us if we can be of any assistance in this matter.

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 4 of 9

Page 256: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

Certificate of AnalysisNumber: 1030-19020581-002A

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample B Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotCylinder No: 1030-07768 Sample Date: 02/09/2019Analyzed: 02/15/2019 14:32:00 by PW Sample Conditions:500 psig

Method: GPA-2261M

Analytical Data

Components Mol. % Wt. % GPM at14.696 psia

Nitrogen 0.278 0.476Methane 97.784 95.896Carbon Dioxide 0.029 0.078Ethane 1.862 3.423 0.498Propane 0.047 0.127 0.013Iso-butane NIL NIL NILn-Butane NIL NIL NILIso-pentane NIL NIL NILn-Pentane NIL NIL NILHexanes Plus NIL NIL NIL

100.000 100.000 0.511

GPM TOTAL C2+ 0.511GPM TOTAL C3+ 0.013GPM TOTAL iC5+ 0.000

Calculated Physical Properties TotalRelative Density Real Gas 0.5658Calculated Molecular Weight 16.36Compressibility Factor 0.9979GPA 2172 Calculation:Calculated Gross BTU per ft³ @ 14.696 psia & 60°FReal Gas Dry BTU 1024Water Sat. Gas Base BTU 1006

Comments: Gross Dry BTU at 29.92 "Hg and 68 °F = 1006 per cubic foot (ASTM D1826). Gross Saturated BTU at 29.92 "Hgand 68 °F = 983 per cubic foot (ASTM D1826).

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 5 of 9

Page 257: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

Certificate of AnalysisNumber: 1030-19020581-002A

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample B Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotCylinder No: 1030-07768 Sample Date: 02/09/2019Analyzed: 02/18/2019 by TB Sample Conditions:500 psig

Method: ASTM D-5504

Sulfur Analysis

SULFIDES ppmw MERCAPTANS ppmw DISULFIDES ppmw

Hydrogen ND Methyl ND Carbon NDCarbonyl 0.1 Ethyl ND Dimethyl NDDimethyl 0.1 Isopropyl ND Methyl Ethyl NDMethyl Ethyl ND n-Propyl ND Diethyl NDDiethyl ND Isobutyl ND Di-iso-Propyl NDDi-iso-Propyl ND sec-Butyl ND Di-n-Propyl NDDi-n-Propyl ND tert-Butyl ND Di-iso-Butyl NDDi-iso-Butyl ND n-Butyl ND Di-sec-Butyl NDDi-sec-Butyl ND Isoamyl ND Di-tert-Butyl NDDi-tert-Butyl ND pri-Amyl ND Di-n-Butyl NDDi-n-Butyl ND n-Amyl ND

OTHER ppmw OTHER ppmw OTHER ppmw

Misc. Sulfurs ND Thiophene ND Thiophane NDSulfur Dioxide ND

Comments: Detection limit = 0.1 ppmwTotal Sulfur detected = <0.030 grains/100 std. cubic ft @ 68 °FND = Not Detected

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 6 of 9

Page 258: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

Certificate of AnalysisNumber: 1030-19020581-003A

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample C Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotCylinder No: 1030-03223 Sample Date: 02/10/2019Analyzed: 02/15/2019 14:46:00 by PW Sample Conditions:500 psig

Method: GPA-2261M

Analytical Data

Components Mol. % Wt. % GPM at14.696 psia

Nitrogen 0.324 0.555Methane 97.744 95.833Carbon Dioxide 0.028 0.075Ethane 1.859 3.416 0.497Propane 0.045 0.121 0.012Iso-butane NIL NIL NILn-Butane NIL NIL NILIso-pentane NIL NIL NILn-Pentane NIL NIL NILHexanes Plus NIL NIL NIL

100.000 100.000 0.509

GPM TOTAL C2+ 0.509GPM TOTAL C3+ 0.012GPM TOTAL iC5+ 0.000

Calculated Physical Properties TotalRelative Density Real Gas 0.5659Calculated Molecular Weight 16.36Compressibility Factor 0.9979GPA 2172 Calculation:Calculated Gross BTU per ft³ @ 14.696 psia & 60°FReal Gas Dry BTU 1023Water Sat. Gas Base BTU 1006

Comments: Gross Dry BTU at 29.92 "Hg and 68 °F = 1006 per cubic foot (ASTM D1826). Gross Saturated BTU at 29.92 "Hgand 68 °F = 983 per cubic foot (ASTM D1826).

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 7 of 9

Page 259: Division of Environmental Permits Floor

Houston Laboratories8820 Interchange Drive

Houston, TX 77054Phone 713-660-0901

Certificate of AnalysisNumber: 1030-19020581-003A

Feb. 18, 2019Air Hygiene International, Inc.1600 West Tacoma StreetBroken Arrow, OK 74012

Station Name: Fuel Sample C Sampled By: N/AStation Number:sie-19-middletown.ny-comp#2 Sample Of: Gas SpotCylinder No: 1030-03223 Sample Date: 02/10/2019Analyzed: 02/18/2019 by TB Sample Conditions:500 psig

Method: ASTM D-5504

Sulfur Analysis

SULFIDES ppmw MERCAPTANS ppmw DISULFIDES ppmw

Hydrogen ND Methyl ND Carbon NDCarbonyl ND Ethyl ND Dimethyl NDDimethyl ND Isopropyl ND Methyl Ethyl NDMethyl Ethyl ND n-Propyl ND Diethyl NDDiethyl ND Isobutyl ND Di-iso-Propyl NDDi-iso-Propyl ND sec-Butyl ND Di-n-Propyl NDDi-n-Propyl ND tert-Butyl ND Di-iso-Butyl NDDi-iso-Butyl ND n-Butyl ND Di-sec-Butyl NDDi-sec-Butyl ND Isoamyl ND Di-tert-Butyl NDDi-tert-Butyl ND pri-Amyl ND Di-n-Butyl NDDi-n-Butyl ND n-Amyl ND

OTHER ppmw OTHER ppmw OTHER ppmw

Misc. Sulfurs ND Thiophene ND Thiophane NDSulfur Dioxide ND

Comments: Detection limit = 0.1 ppmwTotal Sulfur detected = <0.030 grains/100 std. cubic ft @ 68 °FND = Not Detected

Hydrocarbon Laboratory Manager

Quality Assurance: The above analyses are performed in accordance with ASTM, UOP, GPA guidelines for qualityassurance, unless otherwise stated.

Page 8 of 9

Page 260: Division of Environmental Permits Floor

Page 9 of 9

Page 261: Division of Environmental Permits Floor

APPENDIX F

EQUIPMENT CALIBRATION RECORDS

Page 262: Division of Environmental Permits Floor

Filename:Make: Date: 01/25/19

Model #: Barometric Pressure: 29.43 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.88 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

17.00 773.750 779.640 5.890 73.0 73.012.00 779.640 785.610 5.970 74.0 74.010.00 785.610 792.340 6.730 75.0 75.010.00 792.340 801.060 8.720 76.0 76.010.00 801.060 812.920 11.860 77.0 77.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

74.0 74.0 140 0.2353 16.0 70.6 70.8 70.775.0 75.0 148 0.3368 16.0 70.8 71.0 70.976.0 76.0 155 0.4555 16.0 70.9 70.9 70.978.0 78.0 163 0.5955 16.0 71.0 71.2 71.179.0 79.0 173 0.8121 16.0 71.2 71.2 71.2

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

5.736 162.45 5.110 144.7 5.2245.808 164.47 5.162 146.2 5.2796.542 185.28 5.818 164.8 5.9508.470 239.87 7.605 215.4 7.780

11.544 326.94 10.370 293.7 10.611

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)-0.002 0.891 2.000 50.79 0.162-0.004 0.889 1.861 47.26 0.023-0.004 0.889 1.773 45.03 -0.0650.005 0.898 1.787 45.40 -0.0500.005 0.898 1.767 44.89 -0.070

AVERAGE: 0.893 1.838 46.67 PASSED

SIGNATURE: DATE:

1.90

DRY GAS METER READINGS

(in. H2O)0.33

∆H

Apex

samp-cp-0019

Volume

1103025XC-522

ORIFICE

01/25/19

CALIBRATION FACTOR∆H@

Craig McCarty 01/25/19

1.10

Time

0.63

Y

DRY GAS METERCALIBRATION FACTOR

ORIFICERESULTS

DRY GAS METER

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test Calibration

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0019 Calibration 1-25-19.xls]Original (5 point)

Air Hygiene Assett ID:

3.50

Initial Temperature

Final Temperature Ambient Temperature

Notes:

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/-0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

SAMP-CP-0019 Calibration 1-25-19 Original (5 point)

Page 263: Division of Environmental Permits Floor

Filename:Make: Date: 01/25/19

Model #: Barometric Pressure: 29.53 (in. Hg)Serial #: Temperature (ASTM cal): 70.20 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error101.00 0.50 603.00 0.50 1203.00 0.25101.00 0.50 603.00 0.50 1203.00 0.25101.00 0.50 603.00 0.50 1203.00 0.25101.00 0.50 603.00 0.50 1203.00 0.25101.00 0.50 603.00 0.50 1203.00 0.25

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

70.20 (°F)Reading (±°F)

71.0 0.8071.0 0.80

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

yesyes

01/25/19 01/25/19Craig McCarty

Aux.

Responded to heating/cooling withthe anticipated outcome?

samp-cp-0019

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0019 Calibration 1-25-19.xls]Original (5 point)

Apex

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID:

XC-522

ProbeFilterDryer

1103025

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test CalibrationAir Hygiene Assett ID:

Thermocouple

DGM InDGM Out

Thermocouple

Stack

samp-tc-0003

Standard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0019 Calibration 1-25-19 Original (5 point)

Page 264: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.53

Temps(°F)

Ref 70.00Read 71.00

±°F 1.00Ref 70.00

Read 71.00±°F 1.00Ref 70.00

Read 70.00±°F 0.00Ref 70.00

Read 70.00±°F 0.00Ref 70.00

Read 70.00±°F 0.00Ref 70.00

Read 70.00±°F 0.00

Note: Calibrated against Reference Thermometer ID: a070717

yesyes

CPMExit

Responded to heating/cooling withthe anticipated outcome?

Thermocouple

StackProbeFilterCond.

yesyesyesyes

01/25/19

Craig McCarty 01/25/19

Craig McCarty01/25/19

Craig McCarty

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEET

01/25/19

01/25/19

01/25/19

01/25/19

Craig McCarty 01/25/19

Craig McCarty 01/25/19

01/25/19

Thermo-couples

01/25/19

EPA Reference MethodMetering System Pre-Test Calibration

Air Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0019 Calibration 1-25-19.xls]Original (5 point)

DateSignature

Craig McCarty 01/25/19

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0019 Calibration 1-25-19 Original (5 point)

Page 265: Division of Environmental Permits Floor

Filename:Make: Date: 02/19/19

Model #: Barometric Pressure: 29.26 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.80 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

10.00 642.030 650.710 8.680 70.0 70.010.00 650.710 659.390 8.680 71.0 71.010.00 659.390 668.070 8.680 73.0 73.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

71.0 71.0 163 0.5955 16.0 69.8 69.7 69.873.0 73.0 163 0.5955 16.0 69.7 69.9 69.8

163 0.5955 16.0 69.9

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

8.485 240.31 7.570 214.4 7.7708.462 239.63 7.570 214.4 7.7708.446 239.18 7.569 214.4 7.771

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)-0.002 0.892 1.815 46.10 0.0040.000 0.895 1.810 45.98 -0.0010.002 0.896 1.807 45.90 -0.004

AVERAGE: 0.894 1.811 45.99 PASSED

LAST 5-PT: 0.893 1.838 5-PT Date:% DIFF: 0.1% 1.5% 01/25/19

Notes:

SIGNATURE: DATE:

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0019

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0019 Calibration 1-25-19.xls]2-19-19 (3 point)

ApexXC-5221103025

DRY GAS METER READINGS

∆H TimeVolume Initial Temperature

(in. H2O)1.901.901.90

Final Temperature Ambient Temperature

RESULTSDRY GAS METER ORIFICE

DRY GAS METER ORIFICECALIBRATION FACTOR CALIBRATION FACTOR

Y ∆H@

PASSED

Craig McCarty 02/19/19 02/19/19

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/- 0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

40 CFR - CHAPTER I - PART 60Appendix A, Method 5 10.3.2 Calibration After UseAfter each field use, the calibration of the metering system shall be checked by performing three calibration runs at a single, intermediate orifice setting (based on the previous field test)....Calculate the average value of the DGM calibration factor. If the value has changed by more than 5 percent, recalibrate the meter over the full range of orifice settings, as detailed in Section 10.3.1.

10.3.3 Acceptable Variation in Calibration If the DGM coefficient values obtained before and after a test series differ by more than 5 percent, the test series shall either be voided, or calculations for the test series shall be performed using whichever meter coefficient value (i.e., before or after) gives the lower value of total sample volume.

SAMP-CP-0019 Calibration 1-25-19 2-19-19 (3 point)

Page 266: Division of Environmental Permits Floor

Filename:Make: Date: 02/19/19

Model #: Barometric Pressure: 29.26 (in. Hg)Serial #: Temperature (ASTM cal): 69.80 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

69.80 (°F)Reading (±°F)

70.0 0.2070.0 0.20

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0019

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0019 Calibration 1-25-19.xls]2-19-19 (3 point)

ApexXC-5221103025

Thermocouple

StackProbeFilterDryerAux.

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID: samp-tc-0003

ThermocoupleResponded to heating/cooling with

the anticipated outcome?DGM In yes

DGM Out yes

Craig McCarty 02/19/19 02/19/19

Standard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0019 Calibration 1-25-19 2-19-19 (3 point)

Page 267: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.26

Temps(°F)

Ref 69.80Read 70.00

±°F 0.20Ref 69.80

Read 70.00±°F 0.20Ref 69.80

Read 70.00±°F 0.20Ref 69.80

Read 70.00±°F 0.20Ref 69.80

Read 70.00±°F 0.20Ref 69.80

Read 70.00±°F 0.20

Note: Calibrated against Reference Thermometer ID: a070717

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0019 Calibration 1-25-19.xls]2-19-19 (3 point)

Thermo-couples

Signature Date

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

ThermocoupleResponded to heating/cooling with

the anticipated outcome?Stack yesProbe yesFilter yesCond. yesCPM yesExit yes

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0019 Calibration 1-25-19 2-19-19 (3 point)

Page 268: Division of Environmental Permits Floor

Filename:Make: Date: 06/06/18

Model #: Barometric Pressure: 29.23 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.79 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

17.00 0.001 5.141 5.140 72.0 72.012.00 5.141 10.330 5.189 72.0 72.010.00 10.330 16.222 5.892 74.0 74.010.00 16.222 23.904 7.682 77.0 77.010.00 23.904 34.397 10.493 78.0 78.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

72.0 72.0 140 0.2353 16.0 71.8 71.8 71.874.0 74.0 148 0.3368 16.0 71.8 72.1 72.076.0 76.0 155 0.4555 16.0 72.1 72.5 72.378.0 78.0 163 0.5955 16.0 72.5 73.3 72.980.0 80.0 173 0.8121 16.0 73.3 73.4 73.4

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

4.986 141.19 5.070 143.6 5.2295.027 142.38 5.122 145.1 5.2845.694 161.26 5.771 163.4 5.9587.404 209.69 7.540 213.5 7.793

10.126 286.77 10.279 291.1 10.632

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)

0.000 1.017 1.901 48.28 0.0800.002 1.019 1.823 46.29 0.002-0.003 1.013 1.791 45.50 -0.0290.002 1.018 1.804 45.82 -0.016-0.001 1.015 1.783 45.30 -0.037

AVERAGE: 1.017 1.820 46.24 PASSED

SIGNATURE: DATE:

1.90

DRY GAS METER READINGS

(in. H2O)0.31

∆H

apex

samp-cp-0025

Volume

1604005XC-522D

ORIFICE

06/06/18

CALIBRATION FACTOR∆H@

Craig McCarty 06/06/18

1.10

Time

0.61

Y

DRY GAS METERCALIBRATION FACTOR

ORIFICERESULTS

DRY GAS METER

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test Calibration

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0025 Calibration 6-6-18.xls]Original (5 point)

Air Hygiene Assett ID:

3.50

Initial Temperature

Final Temperature Ambient Temperature

Notes:

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/-0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

SAMP-CP-0025 Calibration 6-6-18 Original (5 point)

Page 269: Division of Environmental Permits Floor

Filename:Make: Date: 06/06/18

Model #: Barometric Pressure: 29.23 (in. Hg)Serial #: Temperature (ASTM cal): 72.00 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error100.00 0.00 601.00 0.17 1202.00 0.17100.00 0.00 601.00 0.17 1202.00 0.17100.00 0.00 601.00 0.17 1202.00 0.17100.00 0.00 601.00 0.17 1202.00 0.17100.00 0.00 601.00 0.17 1202.00 0.17

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

72.00 (°F)Reading (±°F)

72.0 0.0072.0 0.00

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

yesyes

06/06/18 06/06/18Craig McCarty

Aux.

Responded to heating/cooling withthe anticipated outcome?

samp-cp-0025

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0025 Calibration 6-6-18.xls]Original (5 point)

apex

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID:

XC-522D

ProbeFilterDryer

1604005

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test CalibrationAir Hygiene Assett ID:

Thermocouple

DGM InDGM Out

Thermocouple

Stack

samp-tc-0003

Standard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0025 Calibration 6-6-18 Original (5 point)

Page 270: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.21

Temps(°F)

Ref 72.00Read 72.00

±°F 0.00Ref 72.00

Read 71.00±°F 1.00Ref 72.00

Read 72.00±°F 0.00Ref 72.00

Read 71.00±°F 1.00Ref 72.00

Read 71.00±°F 1.00Ref 72.00

Read 72.00±°F 0.00

Note: Calibrated against Reference Thermometer ID: a070717

yesyes

CPMExit

Responded to heating/cooling withthe anticipated outcome?

Thermocouple

StackProbeFilterCond.

yesyesyesyes

06/06/18

Craig McCarty 06/06/18

Craig McCarty06/06/18

Craig McCarty

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEET

06/06/18

06/06/18

06/06/18

06/06/18

Craig McCarty 06/06/18

Craig McCarty 06/06/18

06/06/18

Thermo-couples

06/06/18

EPA Reference MethodMetering System Pre-Test Calibration

Air Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0025 Calibration 6-6-18.xls]Original (5 point)

DateSignature

Craig McCarty 06/06/18

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0025 Calibration 6-6-18 Original (5 point)

Page 271: Division of Environmental Permits Floor

Filename:Make: Date: 02/19/19

Model #: Barometric Pressure: 29.46 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.90 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

10.00 0.001 7.576 7.575 70.0 70.010.00 7.576 15.184 7.608 73.0 73.010.00 15.184 22.815 7.631 74.0 74.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

73.0 73.0 163 0.5955 16.0 68.5 68.9 68.774.0 74.0 163 0.5955 16.0 68.9 69.2 69.176.0 76.0 163 0.5955 16.0 69.2 69.4 69.3

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

7.442 210.75 7.630 216.1 7.7627.446 210.87 7.627 216.0 7.7657.448 210.91 7.625 216.0 7.767

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)

0.001 1.025 1.796 45.61 0.0050.000 1.024 1.790 45.47 0.000-0.001 1.024 1.786 45.37 -0.005

AVERAGE: 1.025 1.791 45.48 PASSED

LAST 5-PT: 1.017 1.820 5-PT Date:% DIFF: 0.8% 1.7% 06/06/18

Notes:

SIGNATURE: DATE:

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0025

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0025 Calibration 6-6-18.xls]2-19-19 (3 point)

apexXC-522D1604005

DRY GAS METER READINGS

∆H TimeVolume Initial Temperature

(in. H2O)1.901.901.90

Final Temperature Ambient Temperature

RESULTSDRY GAS METER ORIFICE

DRY GAS METER ORIFICECALIBRATION FACTOR CALIBRATION FACTOR

Y ∆H@

PASSED

Craig McCarty 02/19/19 02/19/19

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/- 0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

40 CFR - CHAPTER I - PART 60Appendix A, Method 5 10.3.2 Calibration After UseAfter each field use, the calibration of the metering system shall be checked by performing three calibration runs at a single, intermediate orifice setting (based on the previous field test)....Calculate the average value of the DGM calibration factor. If the value has changed by more than 5 percent, recalibrate the meter over the full range of orifice settings, as detailed in Section 10.3.1.

10.3.3 Acceptable Variation in Calibration If the DGM coefficient values obtained before and after a test series differ by more than 5 percent, the test series shall either be voided, or calculations for the test series shall be performed using whichever meter coefficient value (i.e., before or after) gives the lower value of total sample volume.

SAMP-CP-0025 Calibration 6-6-18 2-19-19 (3 point)

Page 272: Division of Environmental Permits Floor

Filename:Make: Date: 02/19/19

Model #: Barometric Pressure: 29.45 (in. Hg)Serial #: Temperature (ASTM cal): 68.20 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25101.00 0.50 602.00 0.33 1203.00 0.25

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

68.20 (°F)Reading (±°F)

68.0 0.2068.0 0.20

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0025

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0025 Calibration 6-6-18.xls]2-19-19 (3 point)

apexXC-522D1604005

Thermocouple

StackProbeFilterDryerAux.

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID: samp-tc-0003

ThermocoupleResponded to heating/cooling with

the anticipated outcome?DGM In

DGM Out

Craig McCarty 02/19/19 02/19/19

Standard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0025 Calibration 6-6-18 2-19-19 (3 point)

Page 273: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.45

Temps(°F)

Ref 68.20Read 68.00

±°F 0.20Ref 68.20

Read 69.00±°F 0.80Ref 68.20

Read 69.00±°F 0.80Ref 68.20

Read 68.00±°F 0.20Ref 68.20

Read 68.00±°F 0.20Ref 68.20

Read 69.00±°F 0.80

Note: Calibrated against Reference Thermometer ID: a070717

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0025 Calibration 6-6-18.xls]2-19-19 (3 point)

Thermo-couples

Signature Date

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

Craig McCarty 02/19/19 02/19/19

ThermocoupleResponded to heating/cooling with

the anticipated outcome?Stack yesProbe yesFilter yesCond. yesCPM yesExit yes

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0025 Calibration 6-6-18 2-19-19 (3 point)

Page 274: Division of Environmental Permits Floor

Filename:Make: Date: 07/09/18

Model #: Barometric Pressure: 29.36 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.85 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

17.00 523.220 528.570 5.350 79.0 79.012.00 528.570 533.970 5.400 79.0 79.010.00 533.970 540.100 6.130 80.0 80.010.00 540.100 548.090 7.990 81.0 81.010.00 548.090 559.080 10.990 82.0 82.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

79.0 79.0 140 0.2353 16.0 74.1 74.1 74.180.0 80.0 148 0.3368 16.0 74.1 74.2 74.281.0 81.0 155 0.4555 16.0 74.2 74.3 74.382.0 82.0 163 0.5955 16.0 74.3 74.4 74.484.0 84.0 173 0.8121 16.0 74.4 74.5 74.5

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

5.145 145.70 5.082 143.9 5.2415.192 147.04 5.134 145.4 5.2955.890 166.80 5.786 163.9 5.9687.678 217.45 7.564 214.2 7.804

10.574 299.46 10.314 292.1 10.643

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)

0.004 0.988 1.876 47.64 0.0640.005 0.989 1.859 47.22 0.047-0.002 0.982 1.772 45.00 -0.0400.001 0.985 1.788 45.40 -0.025-0.009 0.975 1.766 44.86 -0.046

AVERAGE: 0.984 1.812 46.03 PASSED

SIGNATURE: DATE:

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test Calibration

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0030 Calibration 7-9-18.xls]Original (5 point)

Air Hygiene Assett ID:

3.50

Initial Temperature

Final Temperature Ambient Temperature

DRY GAS METER

1.10

Time

0.63

Y

DRY GAS METERCALIBRATION FACTOR

ORIFICERESULTS

ORIFICE

07/09/18

CALIBRATION FACTOR∆H@

Craig McCarty 07/09/18

DRY GAS METER READINGS

(in. H2O)0.31

∆H

apex

samp-cp-0030

Volume

1706010522

1.90

Notes:

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/-0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

SAMP-CP-0030 Calibration 7-9-18 Original (5 point)

Page 275: Division of Environmental Permits Floor

Filename:Make: Date: 07/09/18

Model #: Barometric Pressure: 29.36 (in. Hg)Serial #: Temperature (ASTM cal): 74.30 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error100.00 0.00 602.00 0.33 1205.00 0.42100.00 0.00 602.00 0.33 1205.00 0.42100.00 0.00 602.00 0.33 1205.00 0.42100.00 0.00 602.00 0.33 1205.00 0.42100.00 0.00 602.00 0.33 1205.00 0.42

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

74.30 (°F)Reading (±°F)

74.0 0.3074.0 0.30

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

Thermocouple

DGM InDGM Out

Thermocouple

Stack

samp-tc-0003

522

ProbeFilterDryer

1706010

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test CalibrationAir Hygiene Assett ID:

Aux.

Responded to heating/cooling withthe anticipated outcome?

samp-cp-0030

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0030 Calibration 7-9-18.xls]Original (5 point)

apex

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID:

yesyes

07/09/18 07/09/18Craig McCartyStandard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0030 Calibration 7-9-18 Original (5 point)

Page 276: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.36

Temps(°F)

Ref 74.20Read 74.00

±°F 0.20Ref 74.20

Read 74.00±°F 0.20Ref 74.20

Read 74.00±°F 0.20Ref 74.20

Read 74.00±°F 0.20Ref 74.20

Read 74.00±°F 0.20Ref 74.20

Read 74.00±°F 0.20

Note: Calibrated against Reference Thermometer ID: a070717

07/09/18

EPA Reference MethodMetering System Pre-Test Calibration

Air Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0030 Calibration 7-9-18.xls]Original (5 point)

DateSignature

Craig McCarty 07/09/18

Thermo-couples

07/09/18

07/09/18

Craig McCarty 07/09/18

Craig McCarty 07/09/18

07/09/18

07/09/18

07/09/18

Craig McCarty

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEET

07/09/18

yesyesyesyes

07/09/18

Craig McCarty 07/09/18

Craig McCarty

yesyes

CPMExit

Responded to heating/cooling withthe anticipated outcome?

Thermocouple

StackProbeFilterCond.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0030 Calibration 7-9-18 Original (5 point)

Page 277: Division of Environmental Permits Floor

Filename:Make: Date: 02/18/19

Model #: Barometric Pressure: 29.58 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.95 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

10.00 267.150 275.080 7.930 72.0 72.010.00 275.080 283.050 7.970 74.0 74.010.00 283.050 291.010 7.960 75.0 75.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

74.0 74.0 163 0.5955 16.0 68.5 68.7 68.675.0 75.0 163 0.5955 16.0 68.7 69.0 68.976.0 76.0 163 0.5955 16.0 69.0 69.5 69.3

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

7.800 220.89 7.662 217.0 7.7627.817 221.38 7.660 216.9 7.7637.793 220.69 7.657 216.8 7.766

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)

0.001 0.982 1.783 45.29 0.003-0.002 0.980 1.779 45.19 -0.0010.001 0.983 1.777 45.14 -0.003

AVERAGE: 0.982 1.780 45.20 PASSED

LAST 5-PT: 0.984 1.812 5-PT Date:% DIFF: 0.2% 1.8% 07/09/18

Notes:

SIGNATURE: DATE:

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0030

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0030 Calibration 7-9-18.xls]2-18-19 (3 point)

apex5221706010

DRY GAS METER READINGS

∆H TimeVolume Initial Temperature

(in. H2O)1.901.901.90

Final Temperature Ambient Temperature

RESULTSDRY GAS METER ORIFICE

DRY GAS METER ORIFICECALIBRATION FACTOR CALIBRATION FACTOR

Y ∆H@

PASSED

Craig McCarty 02/18/19 02/18/19

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/- 0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

40 CFR - CHAPTER I - PART 60Appendix A, Method 5 10.3.2 Calibration After UseAfter each field use, the calibration of the metering system shall be checked by performing three calibration runs at a single, intermediate orifice setting (based on the previous field test)....Calculate the average value of the DGM calibration factor. If the value has changed by more than 5 percent, recalibrate the meter over the full range of orifice settings, as detailed in Section 10.3.1.

10.3.3 Acceptable Variation in Calibration If the DGM coefficient values obtained before and after a test series differ by more than 5 percent, the test series shall either be voided, or calculations for the test series shall be performed using whichever meter coefficient value (i.e., before or after) gives the lower value of total sample volume.

SAMP-CP-0030 Calibration 7-9-18 2-18-19 (3 point)

Page 278: Division of Environmental Permits Floor

Filename:Make: Date: 02/18/19

Model #: Barometric Pressure: 29.58 (in. Hg)Serial #: Temperature (ASTM cal): 69.10 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error101.00 0.50 603.00 0.50 1206.00 0.50101.00 0.50 603.00 0.50 1206.00 0.50101.00 0.50 603.00 0.50 1206.00 0.50101.00 0.50 603.00 0.50 1206.00 0.50101.00 0.50 603.00 0.50 1206.00 0.50

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

69.10 (°F)Reading (±°F)

70.0 0.9070.0 0.90

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0030

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0030 Calibration 7-9-18.xls]2-18-19 (3 point)

apex5221706010

Thermocouple

StackProbeFilterDryerAux.

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID: samp-tc-0003

ThermocoupleResponded to heating/cooling with

the anticipated outcome?DGM In

DGM Out

Craig McCarty 02/18/19 02/18/19

Standard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0030 Calibration 7-9-18 2-18-19 (3 point)

Page 279: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.58

Temps(°F)

Ref 69.80Read 70.00

±°F 0.20Ref 69.80

Read 71.00±°F 1.20Ref 69.80

Read 71.00±°F 1.20Ref 69.80

Read 70.00±°F 0.20Ref 69.80

Read 70.00±°F 0.20Ref 69.80

Read 71.00±°F 1.20

Note: Calibrated against Reference Thermometer ID: a070717

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0030 Calibration 7-9-18.xls]2-18-19 (3 point)

Thermo-couples

Signature Date

Craig McCarty 02/18/19 02/18/19

Craig McCarty 02/18/19 02/18/19

Craig McCarty 02/18/19 02/18/19

Craig McCarty 02/18/19 02/18/19

Craig McCarty 02/18/19 02/18/19

Craig McCarty 02/18/19 02/18/19

ThermocoupleResponded to heating/cooling with

the anticipated outcome?Stack yesProbe yesFilter yesCond. yesCPM yesExit yes

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0030 Calibration 7-9-18 2-18-19 (3 point)

Page 280: Division of Environmental Permits Floor

Filename:Make: Date: 06/13/18

Model #: Barometric Pressure: 29.16 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.75 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

17.00 646.000 651.150 5.150 73.0 73.012.00 651.150 656.350 5.200 75.0 75.010.00 656.350 662.270 5.920 76.0 76.010.00 662.270 670.030 7.760 77.0 77.010.00 670.030 680.650 10.620 80.0 80.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

75.0 75.0 140 0.2353 16.0 74.0 73.8 73.976.0 76.0 148 0.3368 16.0 73.7 73.7 73.777.0 77.0 155 0.4555 16.0 73.7 73.6 73.778.0 78.0 163 0.5955 16.0 73.7 73.6 73.782.0 82.0 173 0.8121 16.0 73.5 73.6 73.6

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

4.965 140.60 5.048 143.0 5.2405.003 141.68 5.101 144.5 5.2935.692 161.19 5.750 162.8 5.9657.462 211.32 7.517 212.9 7.799

10.187 288.48 10.252 290.3 10.634

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)

0.005 1.017 1.906 48.40 0.0760.008 1.020 1.854 47.10 0.025-0.002 1.010 1.795 45.60 -0.034-0.005 1.007 1.811 45.99 -0.019-0.006 1.006 1.782 45.25 -0.048

AVERAGE: 1.012 1.830 46.47 PASSED

SIGNATURE: DATE:

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test Calibration

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0034 Calibration 6-13-18.xls]Original (5 point)

Air Hygiene Assett ID:

3.50

Initial Temperature

Final Temperature Ambient Temperature

DRY GAS METER

1.10

Time

0.62

Y

DRY GAS METERCALIBRATION FACTOR

ORIFICERESULTS

ORIFICE

06/13/18

CALIBRATION FACTOR∆H@

Craig McCarty 06/13/18

DRY GAS METER READINGS

(in. H2O)0.31

∆H

apex

samp-cp-0034

Volume

1804005xc-522

1.90

Notes:

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/-0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

SAMP-CP-0034 Calibration 6-13-18 Original (5 point)

Page 281: Division of Environmental Permits Floor

Filename:Make: Date: 06/13/18

Model #: Barometric Pressure: 29.16 (in. Hg)Serial #: Temperature (ASTM cal): 73.90 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error100.00 0.00 600.00 0.00 1200.00 0.00100.00 0.00 600.00 0.00 1200.00 0.00100.00 0.00 600.00 0.00 1200.00 0.00100.00 0.00 600.00 0.00 1200.00 0.00100.00 0.00 600.00 0.00 1200.00 0.00

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

73.90 (°F)Reading (±°F)

73.0 0.9073.0 0.90

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

Thermocouple

DGM InDGM Out

Thermocouple

Stack

samp-tc-0003

xc-522

ProbeFilterDryer

1804005

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Pre-Test CalibrationAir Hygiene Assett ID:

Aux.

Responded to heating/cooling withthe anticipated outcome?

samp-cp-0034

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0034 Calibration 6-13-18.xls]Original (5 point)

apex

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID:

yesyes

06/13/18 06/13/18Craig McCartyStandard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0034 Calibration 6-13-18 Original (5 point)

Page 282: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.16

Temps(°F)

Ref 74.00Read 73.00

±°F 1.00Ref 74.00

Read 73.00±°F 1.00Ref 74.00

Read 74.00±°F 0.00Ref 74.00

Read 74.00±°F 0.00Ref 74.00

Read 74.00±°F 0.00Ref 74.00

Read 73.00±°F 1.00

Note: Calibrated against Reference Thermometer ID: a070717

06/13/18

EPA Reference MethodMetering System Pre-Test Calibration

Air Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0034 Calibration 6-13-18.xls]Original (5 point)

DateSignature

Craig McCarty 06/13/18

Thermo-couples

06/13/18

06/13/18

Craig McCarty 06/13/18

Craig McCarty 06/13/18

06/13/18

06/13/18

06/13/18

Craig McCarty

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEET

06/13/18

yesyesyesyes

06/13/18

Craig McCarty 06/13/18

Craig McCarty

yesyes

CPMExit

Responded to heating/cooling withthe anticipated outcome?

Thermocouple

StackProbeFilterCond.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0034 Calibration 6-13-18 Original (5 point)

Page 283: Division of Environmental Permits Floor

Filename:Make: Date: 02/20/19

Model #: Barometric Pressure: 29.04 (in. Hg)Serial #: Theoretical Critical Vacuum: 13.70 (in. Hg)

Initial Final Total Inlet Outlet(min) (ft³) (ft³) (ft³) (°F) (°F)

10.00 27.250 34.900 7.650 69.0 69.010.00 34.900 42.570 7.670 71.0 71.010.00 42.570 50.280 7.710 73.0 73.0

Orifice K' Orifice ActualInlet Outlet Serial# Coefficient Vacuum Initial Final Average(°F) (°F) (number) (see above) (in. Hg) (°F) (°F) (°F)

71.0 71.0 163 0.5955 16.0 69.2 69.2 69.273.0 73.0 163 0.5955 16.0 69.2 69.3 69.375.0 75.0 163 0.5955 16.0 69.3 69.6 69.5

VOLUME VOLUME VOLUME VOLUME VOLUMECORRECTED CORRECTED CORRECTED CORRECTED NOMINAL

Vm(std) Vm(std) Vcr(std) Vcr(std) Vcr(ft³) (liters) (ft³) (liters) (ft³)

7.430 210.41 7.517 212.9 7.7667.421 210.16 7.517 212.9 7.7667.432 210.47 7.516 212.8 7.768

Variation Value Value Value Variation(number) (number) (in. H2O) (mm H2O) (in. H2O)

0.000 1.012 1.829 46.45 0.0070.001 1.013 1.822 46.28 0.000-0.001 1.011 1.816 46.12 -0.006

AVERAGE: 1.012 1.822 46.28 PASSED

LAST 5-PT: 1.012 1.830 5-PT Date:% DIFF: 0.0% 0.4% 06/13/18

Notes:

SIGNATURE: DATE:

METERING SYSTEM DRY GAS METER CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0034

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0034 Calibration 6-13-18.xls]2-20-19 (3 point)

apex5221804005

DRY GAS METER READINGS

∆H TimeVolume Initial Temperature

(in. H2O)1.901.901.90

Final Temperature Ambient Temperature

RESULTSDRY GAS METER ORIFICE

DRY GAS METER ORIFICECALIBRATION FACTOR CALIBRATION FACTOR

Y ∆H@

PASSED

Craig McCarty 02/20/19 02/20/19

For Calibration Factor Y, the ratio of the reading of the calibration meter to the dry gas meter,acceptable tolerance of individual values from the average is +/- 0.02. For Orifice Calibration Factor dH@, the orifice differential pressure in inches of H20 that equates to 0.75 cfm of air at 68 oF and 29.92 inches of Hg, acceptable tolerance of individual values from the average is +/- 0.2. For valid test results, the Actual Vacuum should be 1 to 2 in. Hg greater than the Theoretical Critical Vacuum shown above. The Critical Orifice Coefficient, K', must be entered in English units, (ft)^3*(deg R)^0.5/((in.Hg)*(min)).

40 CFR - CHAPTER I - PART 60Appendix A, Method 5 10.3.2 Calibration After UseAfter each field use, the calibration of the metering system shall be checked by performing three calibration runs at a single, intermediate orifice setting (based on the previous field test)....Calculate the average value of the DGM calibration factor. If the value has changed by more than 5 percent, recalibrate the meter over the full range of orifice settings, as detailed in Section 10.3.1.

10.3.3 Acceptable Variation in Calibration If the DGM coefficient values obtained before and after a test series differ by more than 5 percent, the test series shall either be voided, or calculations for the test series shall be performed using whichever meter coefficient value (i.e., before or after) gives the lower value of total sample volume.

SAMP-CP-0034 Calibration 6-13-18 2-20-19 (3 point)

Page 284: Division of Environmental Permits Floor

Filename:Make: Date: 02/20/19

Model #: Barometric Pressure: 29.04 (in. Hg)Serial #: Temperature (ASTM cal): 69.00 (°F)

100 (°F) 600 (°F) 1200 (°F)Reading % Error Reading % Error Reading % Error100.00 0.00 600.00 0.00 1200.00 0.00100.00 0.00 600.00 0.00 1200.00 0.00100.00 0.00 600.00 0.00 1201.00 0.08100.00 0.00 600.00 0.00 1200.00 0.00101.00 0.50 601.00 0.17 1201.00 0.08

Direct temperature output calibrated to ASTM and IPTS standards as outlined in ALTEK Data Sheet 22.

69.00 (°F)Reading (±°F)

68.0 1.0068.0 1.00

Note: Calibrated against Reference Thermometer ID: a070717

SIGNATURE: DATE:

METERING SYSTEM THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID: samp-cp-0034

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0034 Calibration 6-13-18.xls]2-20-19 (3 point)

apex5221804005

Thermocouple

StackProbeFilterDryerAux.

Note: Calibrated against an ALTEK Thermocouple Source Series 22, ID: samp-tc-0003

ThermocoupleResponded to heating/cooling with

the anticipated outcome?DGM In yes

DGM Out yes

Craig McCarty 02/20/19 02/20/19

Standard for Calibration of Console Thermocouple Systems

40 CFR, Part 60Appendix A, Method 5 10.3.2 The temperature data recorded in the field shall be considered valid. If, during calibration, the absolute temperature measured with the sensor being calibrated and the reference sensor agree within 1.5 percent, the temperature data taken in the field shall be considered valid.

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of thethermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

SAMP-CP-0034 Calibration 6-13-18 2-20-19 (3 point)

Page 285: Division of Environmental Permits Floor

Probe: samp-hp-0086 Hotbox: samp-bh-0012 Gooseneck: samp-ad-0028

Filename:Barometric Pressure: 29.16

Temps(°F)

Ref 69.20Read 70.00

±°F 0.80Ref 69.20

Read 70.00±°F 0.80Ref 69.20

Read 70.00±°F 0.80Ref 69.20

Read 69.00±°F 0.20Ref 69.20

Read 69.00±°F 0.20Ref 69.20

Read 70.00±°F 0.80

Note: Calibrated against Reference Thermometer ID: a070717

PROBE (STACK), HOTBOX (FILTER), AND GOOSENECK (EXIT) THERMOCOUPLE CALIBRATION SHEETEPA Reference Method

Metering System Post-Test CalibrationAir Hygiene Assett ID(s):

Z:\QAQC\Calibrations\PM-Equipment\M-5 Consoles\Calibration Sheet v4.1\Current\[SAMP-CP-0034 Calibration 6-13-18.xls]2-20-19 (3 point)

Thermo-couples

Signature Date

Craig McCarty 02/20/19 02/20/19

Craig McCarty 02/20/19 02/20/19

Craig McCarty 02/20/19 02/20/19

Craig McCarty 02/20/19 02/20/19

Craig McCarty 02/20/19 02/20/19

Craig McCarty 02/20/19 02/20/19

ThermocoupleResponded to heating/cooling with

the anticipated outcome?Stack yesProbe yesFilter yesCond. yesCPM yesExit yes

Standard for Calibration of Individual Thermocouples

EMC, ALT-011: After each test run series, check the accuracy (and, hence, the calibration) of each thermocouple system at ambient temperature, or any other temperature, within the range specified by the manufacturer, using a reference thermometer (either ASTM reference thermometer or a thermometer that has been calibrated against an ASTM reference thermometer). The temperatures of the thermocouple and reference thermometers shall agree to within ±2°F.

Check the continuity of the thermocouple by subjecting it to a change in the temperature (e.g.., removing it from the stack or touching an ice cube). This step will also check for loose connections and reversed connections (noted by a wrong change in the temperature).

Stack

Filter

Exit

Probe

Cond.

CPM

SAMP-CP-0034 Calibration 6-13-18 2-20-19 (3 point)

Page 286: Division of Environmental Permits Floor
Page 287: Division of Environmental Permits Floor
Page 288: Division of Environmental Permits Floor
Page 289: Division of Environmental Permits Floor
Page 290: Division of Environmental Permits Floor
Page 291: Division of Environmental Permits Floor
Page 292: Division of Environmental Permits Floor

Filename:Make: ISO 17025 Weight ID

Model #: Scout Pro SP2001-US ISO S/N 1000128090Serial #: ISO Cal Due

Field Weight #:Trailer #:

must be <0.5

must be <0.5

must be <0.5

0.10

ISO 17025 Certfified Weight(g)

500.00

ISO 17025 Certfified Weight Field Balance Weight

± g

0.00

Field Balance Weight(g)

500.00

7126210013

John Bengs

8/16/2018

(date)

John Bengs 07/02/18

(signature) (date)

07/02/18

± g(g) (g)

sc-0016213

500.00 500.10

LABS-WT-0005Z:\QAQC\Calibrations\Field Balance Weights\2018\[samp-sc-0016_213.xlsm]BalanceOhaus

Field Balance Weight VerficationAnnual 500g Field Balance Stock Weight vs. 500g ISO 17025 Traceable Weight

Air Hygiene Asset ID: samp-sc-0016

Note: Calibrated against ISO 17025 Certified weight LABS-WT-0005

(signature) (date)

(signature)

500.10 500.10 0.00

John Bengs 07/02/18

ISO 17025 Certfified Weight Field Balance Weight± g

(g) (g)

EPA Method 4 - Section 10.3, EPA Method 5 - Section 10.7, EPA Method 202 - Section 10.3: Field Balance Calibration Check. Check the calibration of the balance used to weigh impingers with a weight that is at least 500g or within 50g of a loaded impinger. The weight must be ASTM E617-13 "Standard Specification for Laboratory Weights and Precision Mass Standards" Class 6 (or better). Daily before used, the field balance must meausure within ±0.5g of the certified mass. If the daily balance calibration check fails, perform corrective measures and repeat the check before using balance.

ISO 17025 Certified 500g Weight is certified annually. Certified weight is used to verify Class 6 or better weight that accompanies each field balance on the balance it will be used. Acceptance critieria is certified weight must be within ±0.5g of Class 6 or better weight.

samp-sc-0016_213Balance

Page 293: Division of Environmental Permits Floor

Filename:Make: ISO 17025 Weather Station ID

Model #: ISO 17025 S/NSerial #: ISO 17025 Cal Due

ASTM Temp Thermo. ASTM Barometer Barometric(deg F) (±1.5°) (deg F) (in. Hg) (±0.1 in Hg) (in. Hg)

01/02/19

ASTM Temp Thermo. ASTM Barometer Barometric(deg F) (±1.5°) (deg F) (in. Hg) (±0.1 in Hg) (in. Hg)

01/02/19

ASTM Temp Thermo. ASTM Barometer Barometric(deg F) (±1.5°) (deg F) (in. Hg) (±0.1 in Hg) (in. Hg)

01/02/19

ASTM Temp Thermo. ASTM Barometer Barometric(+C9:I39deg F) (±1.5 (deg F) (in. Hg) (±0.1 in Hg) (in. Hg)

01/02/19(date)

Time

13:53

(date)

Time

14:08

0.01

0.01

Miguel J

± in. Hg

4000704981

± deg F

± in. Hg

Miguel J0.0271.80 73.00 1.20 29.35

A0263348/3/2019

± deg F

.SAMP-WE-0033Z:\QAQC\Calibrations\Weather Stations\2019\[SAMP-WE-0027_213.xlsm]112013Kestrel

WEATHER STATION CALIBRATION SHEETTemperature, Barometric Pressure, and Relative Humidity Periodic Calibration

Air Hygiene Asset ID: samp-we-0027

Note: Verified against ISO 17025 Traceable Barometer and Thermometer (SAMP-WE-0033).

(signature)

73.00 0.70 29.35 29.34

(signature)

72.30

± deg F ± in. Hg

Miguel J0.01

(date)

Time

14:38

29.35

(signature)

± in. Hg

72.30 72.90 0.60 29.36

(date)

Time

14:23

Miguel J

29.37

(signature)

± deg F

29.3572.10 73.30 1.20 29.36

SAMP-WE-0027_213112013

Page 294: Division of Environmental Permits Floor

this page intentionally left blank end of report