document no.: ii - apdcl · every document, letter, progress report, ... c. 100% of all 33/11 kv...

533
ASSAM POWER DISTRIBUTION COMPANY LIMITED BIDDING DOCUMENT (FULL TURNKEY CONTRACT) FOR RURAL ELECTRIFICATION (REDB) WORKS Barpeta, Bongaigaon, Dhubri, Dibrugarh, Golaghat ,Hailakandi, jorhat, Kamrup, Kamrup (metro), Karbi Anglong, Kamrimganj, Kokrajhar, Morigaon, Nalbari, Dima- Hasao DISTRICTS OF ASSAM VOLUME-II (PMS, QUALITY ASSURANCE & EVALUATION MECHANISM, BID FORMS AND PRICE SCHEDULES) Section-I: PMS, Quality Assurance & Evaluation Mechanism (QAM), Documentation & PMA Section-II: Bid Forms Section-III: Price Schedules DOCUMENT NO.: II SPECIFICATION No.: I):APDCL/DDUGJY/II/XII/REDB 1)Package No. DDU/II/XII/REDB/BAR for Barpeta District. 2)Package No. DDU/II/XII/REDB/BNG for Bongaigaon District 3)Package No. DDU/II/XII/REDB/ DHB for Dhubri District 4)Package No. DDU/II/XII/REDB/ DIB for Dibrugarh District 5)Package No. DDU/II/XII/REDB/ GLT for Golaghat District 6)Package No. DDU/II/XII/REDB/ HKD for Hailakandi District 7)Package No. DDU/II/XII/REDB/ JRT for Jorhat District 8)Package No. DDU/II/XII/REDB/ KAM for Kamrup(r) District 9)Package No. DDU/II/XII/REDB/ KAM(M) for Kamrup (metro) District 10)Package No. DDU/II/XII/REDB/ KARBI for Karbianglong District 11)Package No. DDU/II/XII/REDB/ KMJ for Karimganj District 12)Package No. DDU/II/XII/REDB/ KOK for Kokrajhar District 13)Package No. DDU/II/XII/REDB/ MRG for Morigaon District 14)Package No. DDU/II/XII/REDB/ NAL for Nalbari District 15)Package No. DDU/II/XII/REDB/ DMH for Dima-Hasao District

Upload: volien

Post on 26-Apr-2018

219 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

ASSAM POWER DISTRIBUTION COMPANY LIMITEDBIDDING DOCUMENT

(FULL TURNKEY CONTRACT)FOR

RURAL ELECTRIFICATION(REDB) WORKS

Barpeta, Bongaigaon, Dhubri, Dibrugarh, Golaghat ,Hailakandi, jorhat, Kamrup,Kamrup (metro), Karbi Anglong, Kamrimganj, Kokrajhar, Morigaon, Nalbari, Dima-

Hasao DISTRICTS OF ASSAM

VOLUME-II(PMS, QUALITY ASSURANCE & EVALUATION MECHANISM, BID FORMS AND

PRICE SCHEDULES)

Section-I: PMS, Quality Assurance & Evaluation Mechanism (QAM),Documentation & PMA

Section-II: Bid FormsSection-III: Price Schedules

DOCUMENT NO.: II

SPECIFICATION No.:I):APDCL/DDUGJY/II/XII/REDB

1)Package No. DDU/II/XII/REDB/BAR for Barpeta District.2)Package No. DDU/II/XII/REDB/BNG for Bongaigaon District3)Package No. DDU/II/XII/REDB/ DHB for Dhubri District4)Package No. DDU/II/XII/REDB/ DIB for Dibrugarh District5)Package No. DDU/II/XII/REDB/ GLT for Golaghat District6)Package No. DDU/II/XII/REDB/ HKD for Hailakandi District7)Package No. DDU/II/XII/REDB/ JRT for Jorhat District8)Package No. DDU/II/XII/REDB/ KAM for Kamrup(r) District9)Package No. DDU/II/XII/REDB/ KAM(M) for Kamrup (metro)

District10)Package No. DDU/II/XII/REDB/ KARBI for Karbianglong District11)Package No. DDU/II/XII/REDB/ KMJ for Karimganj District12)Package No. DDU/II/XII/REDB/ KOK for Kokrajhar District13)Package No. DDU/II/XII/REDB/ MRG for Morigaon District14)Package No. DDU/II/XII/REDB/ NAL for Nalbari District15)Package No. DDU/II/XII/REDB/ DMH for Dima-Hasao District

Page 2: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

1

APDCL/DDUGJY/ II / XII/REDB Page 1

VOLUME-II: SECTION – I

PROJECT MANAGEMENT SYSTEM

(PMS),

QUALITY ASSURANCE &

EVALUATION MECHANISM

(QAM), DOCUMENTATION & PMA

Page 3: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

2

APDCL/DDUGJY/ II / XII/REDB Page 2

PROJECT MANAGEMENT SYSTEM, QUALITY ASSURANCE AND DOCUMENTATION

This section describes the project management system, quality assurance and documentationrequirements for the project.

1. Project Management System

1.1. General

The Contractor shall assign a project manager with the authority to make commitments and decisionsthat are binding on the Contractor. Employer will designate a project manager to coordinate allemployer project related activities. All communications between employer and the Contractor shall becoordinated through the project managers. The project managers shall also be assisting employer incommunicating project related information to other stake holders.

Bidder shall submit the manpower deployment plan along with the bids, describing the key roles ofeach person.

The role and responsibilities of contractor shall be as follows:

a) To prepare, maintain and update project detailed Work Execution Plan for successfulimplementation of project like approval of GTP, approval of sub-contractor, approval ofdrawings, supply of materials, mobilization of men, material and equipment etc. at site forsuccessful completion of works, Compile and up-load physical as well as financialprogresses, compile the progress of works at Employer level and to assist in forwarding it toall stake holders.

b) To actively participate with employer in resolving all issues relating to projectimplementation including ROW, Forest Clearances, Railway Crossings, and Payments tocontractors/vendors and policy matters.

c) To actively participate in monitoring, reviewing and analysing the physical, financial andquality assurances works’ progress of DDUGJY/IPDS works and also to take suitablemeasures on compliance of observations being raised during monitoring/review meetingswith employer.

d) To implement and maintain a dedicated centralized bank account for the project, uploadand up-date project wise physical progress in DDUGJY/IPDS web portal. Physical as well asfinancial progresses shall be uploaded in standard Bill of Material format of the contract.Also, to submit claims as per release DDUGJY/IPDS guidelines to Employer for release ofpayments/funds.

e) To oversee the progress and compliance of the Quality Assurance Mechanism as perDDUGJY/IPDS guidelines.

1.2. Project Schedule

Page 4: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

3

APDCL/DDUGJY/ II / XII/REDB Page 3

As per the schedule the bidder shall submit a preliminary implementation plan along with the bid. Thedetailed project implementation schedule shall be submitted by the contractor after the award foremployer’s approval, which shall include at least the following activities:

(a) Surveying of site.(b) Documents submission and approval schedule(c) Type Testing Schedule(d) Despatch Schedule(e) Installation & commissioning schedule(f) Training schedule, if any.

The project schedule shall include the estimated period for completion of project and its linkage withother activities.

1.3. Progress Report

A progress report shall be prepared by the Contractor each month against the activities listed in theproject schedule. The report shall be made available to employer on a monthly basis, e.g., the 10th ofeach month. The progress report shall include all the completed, ongoing and scheduled activities.

1.4. Transmittals

Every document, letter, progress report, change order, and any other written transmissions exchangedbetween the Contractor and employer shall be assigned a unique transmittal number. The Contractorshall maintain a correspondence index and assign transmittal numbers consecutively for all Contractordocuments. Employer will maintain a similar correspondence numbering scheme identifying documentsand correspondence that employer initiates.

2. Quality Assurance and Evaluation Mechanism

The contractor shall be solely responsible & accountable for assuring quality in DDUGJY/IPDS works.Accordingly, contractor shall formulate a comprehensive Quality Assurance (QA) Plan with an objectiveto build a quality infrastructure under DDUGJY/IPDS works. The QA Plan shall be integral part of thecontract agreement with contractor. Documentation with regard to Manufacturing Quality Plan (MQP)& Field Quality Plan (FQP) shall be maintained by bidder/Employer and kept in proper order forscrutiny during the course of project execution by Quality Monitors.

The internal quality assurance mechanism followed by EMPLOYER and the turnkey contractor shall betermed as level-zero of overall quality assurance plan of DDUGJY/IPDS works.

Quality checks under Level-Zero of QAM: Level-zero is of utmost importance. Under this level, theturnkey contractor & EMPLOYER shall strictly perform following QA checks during the course of projectexecution:

Page 5: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

4

APDCL/DDUGJY/ II / XII/REDB Page 4

a. 100% pre-dispatch inspections of all material as per MQP/ Drawings/ Technical Specifications& applicable national & international standards

b. 100% villages/town with all infrastructure are to be verified for quality as per MQP/Drawings/Technical Specifications and FQP

c. 100% of all 33/11 kV sub stations (New & Augmented) for quality of material as perMQP/Drawings/Technical Specifications and erection works in the field as per FQP

d. 100% verification of BPL connections

Vendor approval: EMPLOYER shall allow procurement of materials for DDUGJY/IPDS works onlyfrom the vendors approved by their Quality Assurance Departments. A manufacturer's facility may bevisited and the capability assessed suitably before accepting it as approved vendor.

Material Inspection: All major materials under the project shall both be inspected at manufacturerpremises before dispatch. Project Manager shall formulate list of materials to be inspected beforedispatch with contractors.

FQP for construction works: EMPLOYER shall approve a separate FQP prepared by contractor forconstruction works. The turnkey contractor shall adhere to this FQP while carrying out physical works.

FQP for testing & commissioning: Contractor shall prepare and Employer shall approve acomprehensive FQP for testing & commissioning of works under the project. The electrical system shallbe energized only after performing all tests as described in the FQP. Proper records in this regard,including tests on earth resistance, insulation resistance of 66/33/22/11 KV line & DistributionTransformer etc shall be maintained.

QA documentation: All QA checks conducted in the field as per FQP shall be properly documented &signed by the quality engineer of the turnkey contractor & countersigned by EMPLOYER'srepresentative. These documents shall be maintained in proper order & easily available at site forverification by Quality Monitors.

2.1. The contractor shall be solely responsible & accountable for assuring quality inDDUGJY/IPDS works. Accordingly, contractor shall formulate a comprehensive QualityAssurance (QA) and Inspection Plan with an objective to build Quality Infrastructure underDDUGJY/IPDS works. The QA and Inspection Plan shall be an integral Part of the contractagreement with turnkey contractor or equipment supplier/vendor and erection agency as thecase may be in case of partial turnkey and departmental execution of works. Documentationwith regard to Quality Assurance & Inspection Plan shall be maintained by contractor andkept in proper order for scrutiny during the course of project execution and for futurereference. The contractor has to ensure that the quality of material/equipment supplied atsite and field execution of works under the project is in accordance with Quality Assurance &Inspection Plan. The implementation of the scheme in the particular district shall bereviewed periodically during meeting of District Vigilance and Monitoring Committee

2.2. Nodal Agency (REC/PFC) shall also formulate an appropriate mechanism for third partyevaluation, both concurrent and post implementation of the scheme. The nodal agency willappoint agency for carrying out inspection on sample basis.

1. GENERAL

Page 6: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

5

APDCL/DDUGJY/ II / XII/REDB Page 5

1.1. To ensure that the equipment and services under the scope of this Contract whethermanufactured or performed within the Contractor’s Works or at his Sub-contractor’spremises or at the Employer’s site or at any other place of Work are in accordance with thespecifications, the Contractor shall adopt suitable quality assurance programme to controlsuch activities at all points necessary. Such programme shall be broadly outlined by thecontractor and finalized after discussions before the award of contract. The detailedprogramme shall be submitted by contractor after the award of contract and finallyaccepted by the Employer after discussions. A quality assurance programme of thecontractor shall generally cover the following:

a) His organization structure for the management and implementation of the proposed qualityassurance programme :

b) Documentation control system;

c) Qualification data for bidder’s key personnel;

d) The procedure for purchases of materials, parts components and selection of sub-Contractor’sservices including vendor analysis, source inspection, incoming raw material inspection,verification of material purchases etc.

e) System for shop manufacturing and site erection controls including process controls andfabrication and assembly control;

f) Control of non-conforming items and system for corrective actions;

g) Inspection and test procedure both for manufacture and field activities.

h) Control of calibration and testing of measuring instruments and field activities;

i) System for indication and appraisal of inspection status;

j) System for quality audits;

k) System for authorizing release of manufactured product to the Employer.

l) System for maintenance of records;

m) System for handling storage and delivery; and

n) A manufacturing quality plan detailing out the specific quality control measures andprocedures adopted for controlling the quality characteristics relevant to each item ofequipment furnished and/or services rendered.

o) A Field quality Plan covering field activities

1.2. The manufacturing & Field quality Plans shall be mutually discussed and approved by theEmployer after incorporating necessary corrections by the Contractor as may be required.

1.3. The Employer or his duly authorized representative reserves the right to carry out qualityaudit and quality surveillance of the system and procedure of the Contractor/his vendor’squality management and control activities.

1.4. The Contractor would be required to submit all the Quality Assurance documents asstipulated in the Quality Plan at the time of Employer’s Inspection of equipment/material.

2. TYPE & ACCEPTANCE TESTS

The following type, acceptance and routine tests and tests during manufacture shall be carried-out onthe material. For the purpose of this clause:

Page 7: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

6

APDCL/DDUGJY/ II / XII/REDB Page 6

2.1. Contractor shall supply the materials of type & design which has already been Type Tested.Contractor shall provide copy of such tests at site in support of type-tested materialssupplied under the contract. No extra payment or time shall be granted for type testing ofmaterials. In exceptional case to case basis, employer will decide to permit type testing ofmaterial at contractor’s cost.

2.2. Acceptance Tests shall mean those tests which are to be carried out on samples taken fromeach lot offered for pre-dispatch inspection, for the purposes of acceptance of that lot.

2.3. Routine Tests shall mean those tests, which are to be carried out on thematerial/equipment to check requirements which are likely to vary during production.

2.4. Tests during Manufacture shall mean those tests, which are to be carried out during theprocess of manufacture and end inspection by the Contractor to ensure the desired qualityof the end product to be supplied by him.

2.5. The norms and procedure of sampling for these tests will be as per the Quality AssuranceProgramme to be mutually agreed to by the Contractor and the Owner.

2.6. The standards and norms to which these tests will be carried out are listed against them.Where a particular test is a specific requirement of this Specification, the norms andprocedure of the tests shall be as per IS/IEC Standard this specification or as mutuallyagreed to between the Contractor and the Owner in the Quality Assurance Programme.

2.7. For all type test and acceptance tests, the acceptance values shall be the values specified inthis Specification, Approved Quality Plan or guaranteed by the Bidder, as applicable.

3. TYPE TESTING, INSPECTION, TESTING & INSPECTION CERTIFICATE

3.1. All equipment being supplied shall conform to type tests including additional typetests, if any as per technical specification and shall be subject to routine tests in accordancewith requirements stipulated under respective sections. Employer reserves the right towitness any or all the type tests. The Contractor shall intimate the Employer the detailedprogram about the tests at least three (3) weeks in advance in case of domestic supplies &six (6) weeks in advance in case of foreign supplies.

3.2. The reports for all type tests and additional type tests as per technical specification shall befurnished by the Contractor along with equipment/material drawings. The type testsconducted earlier should have either been conducted in accredited laboratory (accreditedbased on ISO/IEC Guide 25/17025 or EN 45001 by the national accreditation body of thecountry where laboratory is located) or witnessed by the representative(s) of Employer orUtility. The test-reports submitted shall be of the tests conducted within last 10 (ten) yearsprior to the date of bid opening. In case the test reports are of the test conducted earlier than10 (ten) years prior to the date of bid opening, the contractor shall repeat these test(s) at noextra cost to the Employer

3.3. In the event of any discrepancy in the test reports i.e. any test report not acceptable due toany design/manufacturing changes (including substitution of components) or due to non-compliance with the requirement stipulated in the Technical Specification or any/all additionaltype tests not carried out, same shall be carried out without any additional cost implication tothe Employer.

3.4. The Employer, his duly authorized representative and/or outside inspection agency acting onbehalf of the Employer shall have at all reasonable times free access to the Contractor’s/sub-

Page 8: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

7

APDCL/DDUGJY/ II / XII/REDB Page 7

vendors premises or Works and shall have the power at all reasonable times to inspect andexamine the materials and workmanship of the Works during its manufacture or erection ifpart of the Works is being manufactured or assembled at other premises or works, theContractor shall obtain for the Engineer and for his duly authorized representative permissionto inspect as if the works were manufactured or assembled on the Contractor’s own premisesor works. Inspection may be made at any stage of manufacture, dispatch or at site at theoption of the Employer and the equipment if found unsatisfactory due to bad workmanship orquality, material is liable to be rejected.

3.5. The Contractor shall give the Employer/Inspector ten (10) days written notice of any materialbeing ready for joint testing including contractor and Employer. Such tests shall be to theContractor’s account except for the expenses of the Inspector. The Employer/Inspector,unless witnessing of the tests is virtually waived, will attend such tests within thirty (30) daysof the date of which the equipment is notified as being ready for test /inspection, failingwhich the Contractor may proceed alone with the test which shall be deemed to have beenmade in the Inspector’s presence and he shall forthwith forward to the Inspector dulycertified copies of tests in triplicate.

3.6. The Employer or Inspector shall, within fifteen (15) days from the date of inspection asdefined herein give notice in writing to the Contractor, of any objection to any drawings andall or any equipment and workmanship which in his opinion is not in accordance with theContract. The Contractor shall give due consideration to such objections and shall either makethe modifications that may be necessary to meet the said objections or shall confirm inwriting to the Employer/Inspector giving reasons therein, that no modifications are necessaryto comply with the Contract. If any modification is made on the equipment on the basis oftest results not in conformity with the contract, the modified equipment shall be subject tosame sequence of test again without any additional cost to Employer.

3.7. When the factory tests have been completed at the Contractor’s or Sub-Contractor’s works,the Employer/Inspector shall issue a certificate to this effect within fifteen (15) days aftercompletion of tests but if the tests are not witnessed by the Employer/Inspector, thecertificate shall be issued within fifteen (15) days of receipt of the Contractor’s Test certificateby the Engineer/Inspector. Failure of the Employer/Inspector to issue such a certificate shallnot prevent the Contractor from proceeding with the Works. The completion of these tests orthe issue of the certificate shall not bind the Employer to accept the equipment should, it, onfurther tests after erection, be found not to comply with the Contract. The equipment shall bedispatched to site only after approval of test reports and issuance of dispatch instruction bythe Employer.

3.8. In all cases where the Contract provides for tests whether at the premises or at the works ofthe Contractor or of any Sub-Contractor, the Contractor except where otherwise specifiedshall provide free of charge such items as labour, materials, electricity, fuel, water, stores,apparatus and instruments as may be reasonably demanded by the Employer/Inspector or hisauthorized representative to carry out effectively such tests of the equipment in accordancewith the Contract and shall give facilities to the Employer/Inspector or to his authorizedrepresentative to accomplish testing.

3.9. The inspection by Employer and issue of Inspection Certificate thereon shall in no way limitthe liabilities and responsibilities of the Contractor in respect of the agreed quality assuranceprogramme forming a part of the Contract.

3.10. The Employer will have the right of having at his own expenses any other test(s) ofreasonable nature carried out at Contractor’s premises or at site or in any other place in

Page 9: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

8

APDCL/DDUGJY/ II / XII/REDB Page 8

addition of aforesaid type and routine tests, to satisfy that the material comply with thespecification.

3.11. The Employer reserves the right for getting any field tests not specified in respective sectionsof the technical specification conducted on the completely assembled equipment at site. Thetesting equipment for these tests shall be provided by the Employer.

3.12. The Employer intends that type tests and additional type tests are conducted onPower/Distribution Transformers, Pin & Disc Insulators, 33 kV/11 kV LT AB cables,Conductors,66 kV / 33 kV &11 kV Vacuum circuit breaker, Battery Charger and energy meter.The price of conducting type tests and additional type tests shall be included in Bid price.

3.13. In case the contractor opts to procure these items from more than one manufacturer, thetype test shall be conducted in respect of all the manufactures. No type test / repeat type testcharges shall be paid by owner.

3.14. Purchaser reserves the right to witness any or all the type tests.

4. PRE-COMMISSIONING TESTS

On completion of erection of the equipment and before charging, each item of the equipment shall bethoroughly cleaned and then inspected jointly by the Employer and the contractor for correctness andcompleteness of installation and acceptability for charging, leading to initial pre-commissioning tests atSite. The list of pre-commissioning tests to be performed is given in respective chapters or as includedin the Contractor’s quality assurance programme.

5. COMMISSIONING TESTS

All required instrumentation and control equipment will be used during such tests and the contractorwill use all such measuring equipment and devices duly calibrated as far as practicable. However, theContractor, for the requirement of these tests, shall take immeasurable parameters into account in areasonable manner. The tests will be conducted at the specified load points and as near the specifiedcycle condition as practicable. The contractor will apply proper corrections in calculation, to take intoaccount conditions, which do not correspond to the specified conditions.

6. Any special equipment, tools and tackles required for the successful completion of the Commissioningtests shall be provided by the contractor, free of cost.

7. The specific tests to be conducted on equipment have been brought out in the respective chapters ofthe technical specification. However where the pre-commissioning tests have not been specifiedspecifically they shall be as per relevant IS code of practice or as mutually agreed.

8. The Contractor shall be responsible for obtaining statutory clearances from the concerned authoritiesfor commissioning and operation of the equipment including the Electrical Inspector. Necessary fee toperform these works shall be paid by Employer.

3. Documentation

3.1. GENERAL

3.1.1. To ensure that the proposed systems conform to the specific provisions and general intent

Page 10: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

9

APDCL/DDUGJY/ II / XII/REDB Page 9

of the Specification, the Contractor shall submit documentation describing the systems toemployer for review and approval. The contractor shall obtain approval of employer for therelevant document at each stage before proceeding for manufacturing, systemdevelopment, factory testing, site testing, training etc. The schedule forsubmission/approval of each document shall be finalised during the discussions beforeplacement of the contract, this schedule shall be in line to overall project schedule.

3.1.2. Each document shall be identified by a Contractor document number, the employerdocument number, and the employer purchase order number. Where a document is revisedfor any reason, each revision shall be indicated by a number, date, and description in arevision block along with an indication of official approval by the Contractor's projectmanager. Each revision of a document shall highlight all changes made since the previousrevision.

3.1.3. All technical description, specifications, literature, correspondence, prints, drawings,instruction manuals, test reports( both factory and at site), progress photographs, booklets,schedules and all supplementary data or documents furnished in compliance with therequirements of the Contract, shall become the property of the Employer and the costs shallbe considered as included in the Contract price.

3.1.4. The Contractor shall be responsible for any time delay, misinterpretation, error and conflictduring design, manufacturing, testing and erection of the Works resulting fromnon-compliance with the requirements of this Specification.

3.1.5. The Employer shall have the right to make copies of any documents, data, reports,information etc. supplied by the Contractor in connection with the Works. The Employershall not impart the information of these documents to any other manufacturer orcompetitor but he shall be free to use these for preparation of technical papers, reports etc.

3.1.6. All documentation shall be in English language.

3.2. REQUIREMENTS FOR SUBMISSION OF DOCUMENTS, INFORMATION ANDDATA BY THE CONTRACTOR

3.2.1. The Contractor shall submit to the Employer all documents in accordance with an approvedschedule of submissions and shall submit any further information (in the form of drawings,documents, manuals, literature, reports etc.) when asked by the Employer whilecommenting/approving any drawings/documents etc.

3.2.2. The documents which are subject to the approval of the Employer shall be identified by theContractor with the stamp "FOR APPROVAL". All other documents shall be submitted to theEmployer for information and shall be identified by the Contractor with the stamp "FORINFORMATION".

3.2.3. The sequence of submission of the documents shall be subject to the approval of theEmployer. The sequence of submissions of all documents shall be such that the necessaryinformation is available to enable the Employer to approve or comment the document.

3.2.4. The Contractor shall supply 4 hard copies of all drawings and documents.

3.2.5. In case a "SUBSEQUENT" revision of any document is made due to any reason whatsoever,a revision of the same, highlighting the changes shall be resubmitted for the Employer'sspecific approval/ information.

Page 11: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

10

APDCL/DDUGJY/ II / XII/REDB Page 10

3.3. DOCUMENTS FOR APPROVAL

3.3.1. The Employer shall be allowed fifteen (15) calendar days to approve the Contractor'ssubmissions. The submissions for approval, shall be returned to the Contractor marked inone of the following ways :

Category I: Approved

Category II: Approved with Comments.

Category III: Returned for correction.

Category IV : For information

3.3.2. The first notations "I" or "II" shall be deemed to permit the Contractor to proceed with thework shown on the document, except in the case of notation "II" the work shall be donesubject to the corrections indicated thereon and/or described in the letter of transmittal.The Contractor shall bear the full responsibility for proceeding with the Works prior toreceipt of the release in notation "I" from the Employer.

3.3.3. In case of notation "II", the Contractor shall include the alterations required & resubmit thedocument within fifteen (15) days from date of Employer's letter of transmittal.

3.3.4. In case of notation "III", the Contractor shall include the alterations required and resubmitthe document to the Employer, within fifteen (15) days, from date of letter of transmittal,so that such document can be returned with the notation "I" or "II".

3.3.5. It may also be noted that the approval/commenting by the Employer does not relieve theContractor of any of his contractual obligations and his responsibilities for correctness ofdimensions, materials, weights quantities or any other information contained therein, aswell as the conformity of designs with Indian Statutory Laws and the TechnicalSpecifications as may be applicable. The approval also does not limit the Employer's rightsunder the Contract.

3.3.6. The approved documents shall be considered as the working documents. However theTechnical Specification and connected documents shall prevail over these documents incase a decision is required on interpretation.

3.4. DOCUMENTS FOR INFORMATION

The Contractor shall not delay the Works pending the receipt by the Contractor of the comments ondocuments submitted to the Employer for information. However, the Employer shall have the right tocomment on all the documents submitted by the Contractor, when, in the opinion of the Employer thedocument does not comply with the Contract or otherwise. The Contractor shall satisfactorilydemonstrate that the information contained in the aforesaid document does meet the requirements ofthe Contract or revise the document in order that the information shall comply with the requirementsof the Contract.

3.5. BASIC REFERENCE DRAWINGS

3.5.1. The reference drawings are enclosed with the bid document, which forms a part of thespecification. The contractor shall develop a new layout in line with the specification and

Page 12: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

11

APDCL/DDUGJY/ II / XII/REDB Page 11

take the approval of the EMPLOYER. The contractor shall maintain the overall dimensions ofthe substation, buildings, bay length, bay width, phase to earth clearance, phase to phaseclearance and sectional clearances, clearances between buses, bus heights but may alterthe locations of equipment to obtain the statutory electrical clearances as required for thesubstation.

3.5.2. All drawings submitted by the Contractor including those submitted at the time of bid shallbe in sufficient detail to indicate the type, size, arrangement, material description, Bill ofMaterials, weight of each component, break-up for packing and shipment, dimensions,internal & the external connections, fixing arrangement required and any other informationspecifically requested in the specifications.

3.5.3. Each drawing submitted by the Contractor shall be clearly marked with the name of theEmployer, the unit designation, the specifications title, the specification number and thename of the Project. If standard catalogue pages are submitted, the applicable items shallbe indicated therein. All titles, noting, markings and writings on the drawing shall be inEnglish. All the dimensions should be in metric units.

3.5.4. Further work by the Contractor shall be in strict accordance with these drawings and nodeviation shall be permitted without the written approval of the Employer, if so required.

3.5.5. The review of these data by the Employer will cover only general conformance of the datato the specifications and documents interfaces with the equipment provided under thespecifications. This review by the Employer may not indicate a thorough review of alldimensions, quantities and details of the equipment, materials, any devices or itemsindicated or the accuracy of the information submitted. This review and/or approval by theEmployer shall not be considered by the Contractor, as limiting any of his responsibilitiesand liabilities for mistakes and deviations from the requirements, specified under thesespecifications and documents.

3.5.6. All manufacturing and fabrication work in connection with the equipment prior to theapproval of the drawings shall be at the Contractor’s risk. The Contractor may make anychanges in the design which are necessary to make the equipment conform to theprovisions and intent of the Contract and such changes will again be subject to approval bythe Employer. Approval of Contractor’s drawing or work by the Employer shall not relievethe contractor of any of his responsibilities and liabilities under the Contract.

3.5.7. All engineering data submitted by the Contractor after final process including review andapproval by the Employer shall form part of the Contract Document and the entire worksperformed under these specifications shall be performed in strict conformity, unlessotherwise expressly requested by the Employer in Writing.

3.6. PRE-DISPATCH INSPECTION:

Pre-dispatch inspection shall be performed on various materials at manufacturer’s work place for whichcontractor shall be required to raise requisition giving at least 10-day time. Depending on requirement,inspection shall be witnessed by representatives of Employer, TPIA and/or REC/PFC/MoP.

Page 13: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section IPMS, QAM & Documentation

12

APDCL/DDUGJY/ II / XII/REDB Page 12

The contractor shall ensure receipt of material at site within 21 days from date of receipt of dispatchinstructions.

The turnkey contractor shall ensure that pre-dispatch inspection for materials are intimated only whenthe material is completely ready for inspection. On due date of inspection, if it is found that materialsare not ready in required quantities, all expenditures incurred on deployment of various inspectingofficials along with a fine of Rs 50,000/- shall be recovered from the bills of the agency. 2nd suchsituation at same manufacturer/supplier shall result in rejection of name of manufacturer from list ofapproved vendors/sub-vendors. In case sub-standard materials (old component, re-cycled materials,re-used core material, re-used transformer coil material etc) offered for inspection and are noticedduring the inspection, materials shall be rejected and approval of sub-vendor shall also be cancelledfor all DDUGJY/IPDS projects.

4. Project Management Agency (PMA)

Employer shall appoint a Project Management Agency (PMA) to assist them in Project Planning andImplementation of the project as under:

4.1. Project Planning and Implementation:

4.1.1. Assisting Employer in preparation of detailed work implementation schedulein association with turnkey contractor.

4.1.2. Coordination & monitoring of project implementation activities.4.1.3. To monitor DPR wise monthly physical & financial progress of the scheme,

prepare a consolidated report & submit to utility for onward submission toNodal Agency.

4.1.4. Identification of anticipated bottlenecks in project implementation &preparation of remedial action plan in consultation with Employer &Contractor.

4.1.5. To assist Employer in addition of the created assets to their asset register.4.1.6. Recommend the claim of utility for fund release from Nodal Agency. The

recommendation is to be supported by a report on expenditure, progressand constraints if any for timely completion of project.

4.1.7. Submit a report to Nodal Agency, regarding Project Completion andexpenditure incurred along with recommendation in accordance with theguidelines.

4.1.8. To assist utility in supervision of flow of funds in dedicated bank account ofprojects.

4.2. Quality Monitoring:

4.2.1. To prepare a Quality Assurance (QA) Plan4.2.2. To carry out field quality inspection of ongoing/ completed works4.2.3. Joint inspection of material at site on sample basis i.e. 10% of major

materials (Poles, Conductor, Meters, Transformers, Cable etc).

Page 14: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

[Type text] Page 0

VOLUME-II: Section-II

Bid Forms (Bid Envelope)

Page 15: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

1

BID FORM : APDCL/DDUGJY/II/XII/REDB

BID Forms (Bid Envelope)

Bid Proposal Ref. No.:.............................. Date: ……….

To:

XXXXXXXX (Name of Employer)

XXXXXXXX (Address of Employer)

Name of Contract: Electrification works of XXXXXXXX (name of district) district in XXXXX

(Name of State) under Deendayal Upadhyaya Gram Jyoti Yojana (DDUGJY-

II).

(Specification No.:XXXXXXXXXXXXXXXXXXXXXX).

Dear Sir/ or Madam,

1.0 Having examined the Bidding Documents, including Amendment Nos. (Insert Numbers) ……… dated

........................ the receipt of which is hereby acknowledged, we the undersigned, offer to design,

manufacture, test, deliver, install and commission (including carrying out Trial operation, Performance &

Guarantee Test as per the provision of Technical Specification) the Facilities under the above-named

Project in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the

Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Bid

Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in Bid envelope i.e. Techno –

Commercial Part. Price Part i.e. Price is uploaded. We have submitted and uploaded on-line price bid

through e-mode to be opened subsequently.

2.0 Attachments to the Bid Form (Bid Envelope)

Page 16: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

2

BID FORM : APDCL/DDUGJY/II/XII/REDB

In line with the requirement of the Bidding Documents, we enclose herewith the following Attachments:

(a) Attachment 1: Bid Security, in a separate envelope, in the form of Bank Draft/Pay

Order/Bank Guarantee* for a sum of ................................................

(name of currency and amount in words and figures) initially valid for a

period of seven (07) months from the date set for opening of bids.

* delete whichever is not applicable.

(b) Attachment 2: A power of attorney duly authorized by a Notary Public indicating that the

person(s) signing the bid have the authority to sign the bid and thus that

the bid is binding upon us during the full period of its validity in

accordance with the ITB Clause 14.

(c) Attachment 3: The documentary evidence that we are eligible to bid in accordance with

ITB Clause 2. Further, in terms of ITB Clause 9.3 (c) & (e), the

qualification data has been furnished as per your format enclosed with

the bidding documents [Attachment-3(QR). * Further, the required Joint

Venture Agreement signed by us and our Partners has also been

furnished as per your format [Attachment-3(JV).

* Delete if not applicable

(d) Attachment 4: The documentary evidence establishing in accordance with ITB Clause 3,

Vol.-I of the Bidding Documents that the facilities offered by us are

eligible facilities and conform to the Bidding Documents has been

furnished as Attachment 4. A list of Special Tools & Tackles to be used by

us for erection, testing & Commissioning and to be handed over to

Employer, the cost of which is included in our Bid Price, is also enclosed

as per your format as Attachment 4A. A list of Special Tools & Tackles to

be brought by the contractor for erection, testing & Commissioning and

to be taken back after completion of work, whose cost in not included in

our bid price, is enclosed as per your format as Attachment 4B.

Page 17: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

3

BID FORM : APDCL/DDUGJY/II/XII/REDB

(e) Attachment 5: The details of all major items of services or supply which we propose

subletting in case of award, giving details of the name and nationality of

the proposed subcontractor/sub-vendor for each item.

(f) Attachment 6: The bidder has to declare that there will be no variation and deviations

from the requirements of the Conditions of Contract, Technical

Specification and Drawings (excluding critical provisions as mentioned at

clause 6.0 below) in your format enclosed with the Bidding Documents.

(g) Attachment 7: The details of Alternative Bids made by us indicating the complete

Technical Specifications and the deviation to contractual and commercial

conditions. [Not Applicable]

(h) Attachment 8: Manufacturer’s Authorisation Forms - registered/notarized

(i) Attachment 9: Work Completion Schedule.

(j) Attachment 10: Guarantee Declaration.

(k) Attachment 11: Information regarding ex-employees of Employer in our firm.

(l) Attachment 12: Bidder shall confirm that price adjustment for any material shall not be

preferred by him.

(m) Attachment 13: Declaration regarding Social Accountability

(n) Attachment 14: Integrity Pact, in a separate envelope( in inner envelope-1) , duly

signed on each page by the person signing the bid. For JV all partners to

sign.

Page 18: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

4

BID FORM : APDCL/DDUGJY/II/XII/REDB

(o) Attachment 15: Option for Interest bearing Initial Advance payment and Information for

E-payment, PF details and declaration regarding Micro/Small & Medium

Enterprises

(p) Attachment 16: Additional Information

(q) Attachment 17: Declaration for tax exemptions, reductions, allowances or benefits

(r) Attachment 18: Declaration

(s) Attachment 19: Bank Guarantee verification checklist

3.0 We are aware that, in line with Clause No. 27.1 (ITB), our online price bid is liable to be rejected in case

the same contains any deviation/omission from the contractual and commercial conditions and technical

Specifications other than those identified in this Bid Envelope.

3.1 We are aware that the Price Schedules do not generally give a full description of the Work to be

performed under each item and we shall be deemed to have read the technical specifications, scope of

works and other sections of the Bidding Documents and Drawings to ascertain the full scope of Work

included in each item while filling-in the rates and prices in price schedule quoted and uploaded in

e-procurement web-portal.

3.2 We declare that as specified in Clause 11.5, Section –II: ITB, Vol.-I of the Bidding Documents, prices

quoted by us in the Price Schedules shall be fixed and firm during the execution of Contract .

4.0 We confirm that except as otherwise specifically provided our Bid Prices quoted and uploaded in

e-procurement web portal include all taxes, duties, levies and charges as may be assessed on us, our

Sub-Contractor/Sub-Vendor or their employees by all municipal, state or national government

authorities in connection with the Facilities, in and outside of India in respect of this turnkey contract.

.

Page 19: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

5

BID FORM : APDCL/DDUGJY/II/XII/REDB

4.1 We confirm that we shall be entirely responsible for payment/ liability of all taxes, duties, cess, license

fees and other such levies legally payable/incurred until completion and taking-over of the project by

you. You will not be responsible for such taxes, duties, license fees and other levies. We further declare

and confirm that we shall hold you indemnified and harmless against any claims that may be made

against you in respect of all taxes, duties, license fees and other such levies in respect of this contract.

4.2 We understand that in case of award on us, if it is statutory requirement to make deductions /

recoveries towards any taxes, duties, levies, etc, the same shall be made by you from our contract price

and deposit the same with the relevant tax authorities.

4.3 We confirm and declare that the Quoted Price includes the total amount of Service Tax Payable by the

contractor and also by the Employer under Reverse Charge Mechanism, if any, under the Service Tax

Laws in respect of this Contract. We further understand and confirm that in case of award on us and if

you are liable to pay service tax under reverse charge mechanism, then you shall deduct such amount

from our Contract Price and you will deposit the same with the Service Tax Authority.

4.4 We confirm that we are registered / shall immediately get registered with the concerned Sales Tax

Authorities, in the state of Assam and produce the Relevant Registered Certificate and valid Sales Tax

Clearance Certificate / valid WC-2 (Composition Certificate) from time to time.

5.0 Construction of the Contract

5.1 We declare that we have studied Clause GCC 2.1 relating to mode of contracting for Domestic Bidders

and we are making this proposal with a stipulation that you shall award us one Turnkey Contract with

two distinct parts viz ‘Supply Part’ for supply of all equipment and materials including mandatory spares

and ‘Erection Part’ for providing all the services i.e. inland transportation for delivery at site, insurance,

unloading, storage, handling at site, installation, testing and commissioning including Trial operation in

respect of all the equipment supplied under the ‘Supply Part’ and other services specified in the Contract

Documents. We declare that the award of the contract with two distinct parts, will not, in any way,

dilute our responsibility for successful operation of plant/equipment and fulfilment of all obligations as

per Bidding Documents and that both parts of the Contract will have a cross-fall breach clause i.e. a

breach in one part will automatically be classified as a breach of the other part which will confer on you

the right to terminate the contract at our risk and cost.

6.0 We have read the provisions of following clauses and confirm that the specified stipulations of these

clauses are acceptable to us:

Page 20: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

6

BID FORM : APDCL/DDUGJY/II/XII/REDB

(a) ITB 13 Bid Security

(b) GCC 2.14 Governing Law

(c) GCC 8 Terms of Payment

(d) GCC 9.3 Performance Security

(e) GCC 10 Taxes and Duties

(f) GCC 21.2 Completion Time Guarantee

(g) GCC 22 Defect Liability

(h) GCC 23 Functional Guarantee

(i) GCC 25 Patent Indemnity

(j) GCC 26 Limitation of Liability

(k) GCC 38 Settlement of Disputes

(l) GCC 39 Arbitration

Further we understand that deviation taken in any of the above clauses by us may make our bid non-

responsive as per provision of bidding documents and be rejected by you.

7.0 We undertake, if our bid is accepted, to commence the work immediately upon your Notification of

Award to us, and to achieve the delivery of goods and related services within the time stated in the

Bidding Documents.

8.0 If our bid is accepted, we undertake to provide Performance Security (ies) in the form and amounts,

and within the time specified in the Bidding Documents.

9.0 We agree to abide by this bid for a period of six (06) months from the date fixed for opening of bids as

stipulated in the Bidding Documents, and it shall remain binding upon us and may be accepted by you

at any time before the expiration of that period.

10.0 Until a formal Contract is prepared and executed between us, this bid, together with your written

acceptance thereof in the form of your Notification of Award shall constitute a binding contract between

us.

Page 21: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

7

BID FORM : APDCL/DDUGJY/II/XII/REDB

11.0 We understand that you are not bound to accept the lowest or any bid you may receive.

*12.0 (For Joint Venture only) We, the partners of Joint Venture submitting this bid, do agree and confirm

that in case of Award of Contract on the Joint Venture, we shall be jointly and severally liable and

responsible for the execution of the Contract in accordance with Contract terms and conditions.

13.0 We, hereby, declare that only the persons or firms interested in this proposal as principals are named

here and that no other persons or firms other than those mentioned herein have any interest in this

proposal or in the Contract to be entered into, if the award is made on us, that this proposal is made

without any connection with any other person, firm or party likewise submitting a proposal is in all

respects for and in good faith, without collusion or fraud.

Dated this ____ day of ________20__

Thanking you, we remain,

Yours Sincerely,

For and on behalf of the [Name of the Bidder#]

(Signature)..................................

(Printed Name)............................

(Designation)...............................

(Common Seal)...........................

Date:

Place:

Business Address:

Country of Incorporation:

(State or Province to be indicated)

Name of the Principal Officer:

Page 22: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

8

BID FORM : APDCL/DDUGJY/II/XII/REDB

Address of the Principal Officer:

*Applicable in case of a bid from Joint Venture of firms.

#In case the bid is submitted by a Joint Venture, the name of the Joint Venture should be indicated

Note: Bidders may note that no prescribed proforma has been enclosed for:

(a) Attachment 2: Power of Attorney.

(For Attachments 2 Bidders may use their own proforma for furnishing the required information with the bid).

Page 23: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

9

BID FORM : APDCL/DDUGJY/II/XII/REDB

List of Attachments

Attachment-3(JV) ..................................................................................................................................... 10

Attachment-3 (QR) ................................................................................................................................... 11

Attachment-4 ........................................................................................................................................... 23

Attachment-4A ......................................................................................................................................... 24

Attachment-4B ......................................................................................................................................... 25

Attachment-5 ........................................................................................................................................... 26

Attachment-6 ........................................................................................................................................... 27

Attachment-8 ........................................................................................................................................... 28

Attachment-9 ........................................................................................................................................... 30

Attachment-10 ......................................................................................................................................... 32

Attachment-11 ......................................................................................................................................... 33

Attachment-12 ......................................................................................................................................... 34

Attachment-14 ......................................................................................................................................... 35

Attachment-15 ......................................................................................................................................... 42

Attachment-16 ......................................................................................................................................... 46

Attachment- 17 ........................................................................................................................................ 50

Attachment-18 ......................................................................................................................................... 51

Attachment-19 ......................................................................................................................................... 52

Page 24: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

10

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-3(JV)

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under

Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Joint Venture Agreement and Power of Attorney for Joint Venture*)

Bidder’s Name and Address: To: <Name and Address of Employer>

Dear Sir,

The Joint Venture Agreement (as per the proforma attached at no. 15 in Section-VI, Sample Forms and

Procedures, Conditions of Contract, Vol.-I of the Bidding Documents) and Power of Attorney for Joint Venture (as

per the proforma attached at no. 14 in Section-VI, Sample Forms and Procedures, Conditions of Contract, Vol.-I

of the Bidding Documents) are enclosed herewith.

* Applicable for Joint Venture.

Date:....................

(Signature)...................................................………..

Place:...................

(Printed Name)..........................................………….

(Designation)................…………..............................

(Common Seal).…………..........................................

Page 25: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

11

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-3 (QR)

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under

Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Qualifying Requirement Data)

Bidders Name & Address: To

<Name and Address of the Employer>

Dear Ladies and/or Gentlemen,

In support of the Qualification Requirements (QR) for bidders, stipulated in Annexure-A (BDS) of the Section - III

(BDS), Volume-I & additional information required as per ITB clause 9.3(c) of the Bidding Documents, we furnish

herewith our QR data/details/documents etc., along with other information, as follows (The QR stipulations have

been reproduced in italics for ready reference, however, in case of any discrepancy the QR as given in BDS shall

prevail).

* We have submitted bid as individual firm.

* We have submitted bid as joint venture of following firms:

(i) ..................................................................................................

(ii) ..................................................................................................

(iii) ..................................................................................................

(* Strike-off whichever is not applicable)

[For details regarding Qualification Requirements of a Joint Venture, please refer para 4.0 below.]

Page 26: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

12

BID FORM : APDCL/DDUGJY/II/XII/REDB

We are furnishing the following details/document in support of Qualifying requirement for the subject project.

A. Attached copies of original documents defining:

a) The constitution or legal status;

b) The principal place of business;

c) The place of incorporation (for bidders who are corporations); or the place of registration and

the nationality of the Owners (for applicants who are partnerships or individually-owned firms).

B. Attached original & copies of the following documents.

a) Written power of attorney of the signatory of the Bid to commit the bidder.

b)** Joint Venture Agreement

[** To be submitted only in case of Joint Ventures. Strike off in case of individual firms.]

1.0 Pre-qualification criteria – Part A:

1.01 Technical:

(I) Part I: Supply, Erection, Testing & Commissioning of New/Augmentation of existing

33/11KV substation1 and new/Augmentation of its incoming 33 and 11 KV Lines

The detailed criteria is mentioned at 1.01 (I) of Annexure-A to BDS at Volume-I : Section-III.

Format A: Format for the Bidder (Single Firm / Partner(s) in case of Joint Venture) for technical

experience in compliance to para 1.01 (I) {(i) or (ii) or (iii)} of Annexure-A to BDS

(Volume-I : Section-III) [In case of Joint Venture bidder, the QR data of each of the

partner (in support of meeting the requirement of para 1.01 (I) (iv) of Annexure-A to

BDS (Volume-I : Section-III)] is also is to furnished, as applicable, using this format.

The bidder (Single Firm / Partner(s) in case of Joint Venture) who is willing to qualify

1 Depending on the state practice to use 66 KV or 33 KV as sub-transmission voltage gradient

Page 27: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

13

BID FORM : APDCL/DDUGJY/II/XII/REDB

in compliance to para 1.01 (I) {(ii) or (iii)} of para 1.01 (I) (iv) of Annexure-A to BDS

(Volume-I : Section-III) shall fill below format for two or all three contracts.

A1. Name of Bidder/Lead Partner of JV/other partner(s) of JV

A2. Name of Contract (executed during the last 7 years as on the

originally scheduled date of bid opening):

A3.Contract Reference No. & Date of Award

A4 Name and Address of the Employer/Utility

by whom the Contract was awarded

e-mail ID

Telephone No.

Fax No.

____________________

____________________

____________________

A5(i)

(ii)

(iii)

(iv)

(v)

Name of electrical works of sub-station of 33/11 KV class and its

associated 33 KV/11KV lines successfully erected, tested and

commissioned

Transformer capacity successfully erected, tested and commissioned

for s/s of 33/11 KV (in KVA)

% of Transformer capacity executed w.r.t. transformer capacity

proposed in bid (in %)

Length of 33 KV and11KV line successfully erected, tested and

commissioned (in cKms)

% of 33 KV/11KV line executed w.r.t. 33 KV and 11KV line proposed

in bid (in %)

___________________

___________________

___________________

____________________

_____________________

A6(i) Date of successful execution of the Contract/Date of commissioning

No. of years the above referred electrical works is in successful

______________

______________ years

Page 28: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

14

BID FORM : APDCL/DDUGJY/II/XII/REDB

(ii) operation as on the date of bid opening

A7. Capacity in which the Contract was undertaken (Check One) Prime Contractor

Partner of JV

Subcontractor

(Tick whichever is applicable)

A8. Details/documentary evidence submitted in support of stated

experience/Contract

(Documentary evidence, such as copies of utility certificates etc., in support of its experience shall be attached

with the filled-up format for each experience/Contract)

(II) Part II: Supply, Erection, Testing and Commissioning of New of existing 11 KV & LT

Lines, New 11/0.4 KV Distribution Transformer substation and Single Phase Electricity

Connections including Service Line & Internal House wiring for BPL Households. (NOT

APPLICABLE)

(III) The detailed criteria is mentioned at 1.01 (II) of Annexure-A to BDS at Volume-I : Section-III.

Format B: Format for the Bidder (Single Firm / Partner(s) in case of Joint Venture) for technical

experience in compliance to para 1.01 (II) {(i) or (ii) or (iii)} of Annexure-A to BDS

(Volume-I : Section-III) [In case of Joint Venture bidder, the QR data of each of the

partner (in support of meeting the requirement of para 1.01 (II) (iv) of Annexure-A to

BDS (Volume-I : Section-III)] is also is to furnished, as applicable, using this format.

The bidder (Single Firm / Partner(s) in case of Joint Venture) who is willing to qualify

in compliance to para 1.01 (II) {(ii) or (iii)} of Annexure-A to BDS (Volume-I : Section-

III) shall fill below format for two or all three contracts.

A1. Name of Bidder/Lead Partner of JV/other partner(s) of JV

A2. Name of Contract (executed during the last 7 years as on the

originally scheduled date of bid opening):

A3.Contract Reference No. & Date of Award

Page 29: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

15

BID FORM : APDCL/DDUGJY/II/XII/REDB

A4 Name and Address of the Employer/Utility

by whom the Contract was awarded

e-mail ID

Telephone No.

Fax No.

____________________

____________________

____________________

A5(i)

(ii)

(iii)

(iv)

(v)

Name of electrical works of LT line or 11 KV or 22 KV class

successfully erected, tested and commissioned

Distribution transformer capacity successfully erected, tested and

commissioned for s/s of 33/11 KV or 66/11 KV (in KVA)

% of Distribution transformer capacity executed w.r.t. Distribution

transformer capacity proposed in bid (in %)

Length of LT line/11 KV/22 KV line successfully erected, tested and

commissioned (in cKms)

% of LT line/11 KV/22 KV line executed w.r.t. LT line/11 KV/22 KV

line proposed in bid (in %)

___________________

___________________

___________________

____________________

_____________________

A6(i)

(ii)

Date of successful execution of the Contract/Date of commissioning

No. of years the above referred electrical works is in successful

operation as on the date of bid opening

______________

______________ years

A7. Capacity in which the Contract was undertaken (Check One) Prime Contractor

Partner of JV

Subcontractor

(Tick whichever is applicable)

Page 30: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

16

BID FORM : APDCL/DDUGJY/II/XII/REDB

A8. Details/documentary evidence submitted in support of stated

experience/Contract

(Documentary evidence, such as copies of utility certificates etc., in support of its experience shall be attached

with the filled-up format for each experience/Contract)

(IV) Part III: Combined Part of Part-I & II above( Not applicable)

The detailed criteria is mentioned at 1.01 (III) of Annexure-A to BDS at Volume-I : Section-III.

Format C: Format for the Bidder (Single Firm / Partner(s) in case of Joint Venture) for technical

experience in compliance to para 1.01 (III) {(i) or (ii) or (iii)} of Annexure-A to BDS

(Volume-I : Section-III) [In case of Joint Venture bidder, the QR data of each of the

partner (in support of meeting the requirement of para 1.01 (III) (iv) of Annexure-A to

BDS (Volume-I : Section-III)] is also is to furnished, as applicable, using this format.

The bidder (Single Firm / Partner(s) in case of Joint Venture) who is willing to qualify

in compliance to para 1.01 (III) {(ii) or (iii)} above shall fill below format for two or all

three contracts.

A1. Name of Bidder/Lead Partner of JV/other partner(s) of JV

A2. Name of Contract (executed during the last 7 years as on the

originally scheduled date of bid opening):

A3.Contract Reference No. & Date of Award

A4 Name and Address of the Employer/Utility

by whom the Contract was awarded

e-mail ID

Telephone No.

Fax No.

____________________

____________________

____________________

Page 31: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

17

BID FORM : APDCL/DDUGJY/II/XII/REDB

A5(i)

(ii)

(iii)

(iv)

(v)

Name of electrical works of 33/11 KV or 66/11 KV class substation

and its associated 33 KV/66 KV lines successfully erected, tested and

commissioned

Transformer capacity successfully erected, tested and commissioned

for 33/11 KV or 66/11 KV s/s(in KVA)

% of Transformer capacity executed w.r.t. transformer capacity

proposed in bid (in %)

Length of 33 KV/66KV line successfully erected, tested and

commissioned (in cKms)

% of 33 KV/66KV line executed w.r.t. 33 KV/66KV line proposed in

bid (in %)

___________________

___________________

___________________

____________________

_____________________

A6(i)

(ii)

(iii)

(iv)

(v)

Name of electrical works of LT line or 11 KV or 22 KV class

successfully erected, tested and commissioned

Distribution transformer capacity successfully erected, tested and

commissioned (in KVA)

% of Distribution transformer capacity executed w.r.t. Distribution

transformer capacity proposed in bid (in %)

Length of LT line/11 KV/22 KV line successfully erected, tested and

commissioned (in Kms)

% of LT line/11 KV/22 KV line executed w.r.t. 11 KV/22 KV line

proposed in bid (in %)

___________________

___________________

___________________

____________________

A7(i)

(ii)

Date of successful execution of the Contract/Date of commissioning

No. of years the above referred electrical works is in successful

operation as on the date of bid opening

______________

______________ years

Page 32: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

18

BID FORM : APDCL/DDUGJY/II/XII/REDB

A8. Capacity in which the Contract was undertaken (Check One) Prime Contractor

Partner of JV

Subcontractor

(Tick whichever is applicable)

A9. Details/documentary evidence submitted in support of stated

experience/Contract

(Documentary evidence, such as copies of utility certificates etc., in support of its experience shall be attached

with the filled-up format for each experience/Contract)

1.01.1 The bidder should possess "A Class” or “Class-I” license issued by the Electrical inspectorate of

Govt of Assam /Central Inspectorial organization of Govt. of India/ other state Govt. In case bid

submitted joint venture firm, any of partner should possess "A Class” or “Class-I” electrical license

as stated above.

1.02 Commercial

The detailed criteria is mentioned at 1.02 of Annexure-A to BDS at Volume-I : Section-III.

Format C: Format for the Bidder (Single Firm / Partner(s) in case of Joint Venture) for commercial

experience in compliance to para 1.02.1 (i) of Annexure-A to BDS at Volume-I :

Section-III [In case of Joint Venture bidder, the QR data of each of the partner (in

support of meeting the requirement of para 1.02.5 of Annexure-A to BDS at Volume-I :

Section-III] is also is to furnished, as applicable, using this format. The bidder (Single

Firm / Partner(s) in case of Joint Venture) who is willing to qualify in compliance to

para 1.02.1 {(ii) or (iii)} of Annexure-A to BDS at Volume-I : Section-III shall fill below

format for two or all three contracts.

A1. Name of Bidder/Lead Partner of JV/other partner(s) of JV

A2. Name of Contract (executed during the last 5 years up to

31.03.2013):

A3.Contract Reference No. & Date of Award

A4 Name and Address of the Employer/Utility

Page 33: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

19

BID FORM : APDCL/DDUGJY/II/XII/REDB

by whom the Contract was awarded

e-mail ID

Telephone No.

Fax No.

____________________

____________________

____________________

A5(i)

(ii)

(iii)

Name of completed work of project execution in electrical

Transmission or sub-transmission & distribution sector

Cost of the project

% of cost w.r.t. estimated cost of this bid (in %)

___________________

___________________

A6(i) Date of successful execution of the Contract/Date of commissioning

______________

A7. Capacity in which the Contract was undertaken (Check One) ○Prime Contractor

Partner of JV

Subcontractor

(Tick whichever is applicable)

A8. Details/documentary evidence submitted in support of stated

experience/Contract

(Documentary evidence, such as copies of utility certificates etc., in support of its experience shall be attached

with the filled-up format for each experience/Contract)

Format D: Format for the Bidder (Single Firm / Partner(s) in case of Joint Venture) for commercial

experience in compliance to para 1.02.2, 1.02.3 & 1.02.4 of Annexure-A to BDS at

Volume-I : Section-III [In case of Joint Venture bidder, the QR data of each of the

partner (in support of meeting the requirement of para 1.02.5 of Annexure-A to BDS at

Volume-I : Section-III] is also to furnished, as applicable, using this format.

A1. Name of Bidder/Lead Partner of JV/other partner(s) of JV

A2. Net-worth in last three years

Page 34: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

20

BID FORM : APDCL/DDUGJY/II/XII/REDB

1. Financial Year 2013-14

2. Financial Year 2014-15

3. Financial Year 2015-16

: Rs. ----- lakhs

: Rs. ----- lakhs

: Rs. ----- lakhs

A3.Minimum Average Annual Turnover (MAAT)

1. Financial Year 2011-12

2. Financial Year 2012-13

3. Financial Year 2013-14

4. Financial Year 2014-15

5. Financial Year 2015-16

: Rs. ----- lakhs

: Rs. ----- lakhs

: Rs. ----- lakhs

: Rs. ----- lakhs

: Rs. ----- lakhs

A4 liquid assets (LA) and/ or evidence of access to or availability of

credit facilities

: Rs. ----- lakhs

A4. Details/documentary evidence submitted in support of stated

experience/Contract

(Documentary evidence, such as copies of utility certificates etc., in support of its experience shall be attached

with the filled-up format for each experience/Contract)

1.02.1 Failure to comply with this requirement will result in rejection of the joint venture’s bid. Sub

contractors’ experience and resources shall not be taken into account in determining the bidder’s

compliance with qualifying criteria.

1.02.2 One of the partners shall be nominated as lead partner, and the lead partner shall be authorized to

incur liabilities and receive instruction for and on behalf of any and all partners of the joint venture

and the entire execution of the contract including receipt of payment shall be done exclusively

through the lead partner. This authorization shall be evidenced by submitting a power of attorney

signed by legally authorized signatories of all the partners as per proforma in section “Annexure” of

Special Conditions of Contract-Vol.-IA. .

Page 35: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

21

BID FORM : APDCL/DDUGJY/II/XII/REDB

1.02.3 All partner of the joint venture shall be liable jointly and severally for the execution of the contract

in accordance with the contract terms and a copy of the agreement entered into by the joint

venture partners having such a provision shall be submitted with the bid.

2.0 Pre-qualification criteria – Part B:

The Bidder shall also furnish following documents/details with its bid:

2.01.1 A certificate from banker (as per format) indicating various fund based/non fund based limits

sanctioned to the bidder and the extent of utilization as on date Such certificate should have been

issued not earlier than three months prior to the date of bid opening. Wherever necessary

Employer may make queries with the Bidders’ bankers.

2.01.2 The complete annual reports together with Audited statement of accounts of the company for last

five years of its own (separate) immediately preceding the date of submission of bid.

2.01.3 Note:

2.01.3.1 In the event the bidder is not able to furnish the information of its own (i.e.

separate), being a subsidiary company and its accounts are being consolidated with

its group/holding/parent company, the bidder should submit the audited balance

sheets, income statements, other information pertaining to it only (not of its

group/Holding/Parent Company) duly certified by any one of the authority [(i)

Statutory Auditor of the bidder /(ii) Company Secretary of the bidder or (iii) A

certified Public Accountant] certifying that such information/documents are based on

the audited accounts as the case may be.

2.01.3.2 Similarly, if the bidder happens to be a Group/Holding/Parent Company, the bidder

should submit the above documents/information of its own (i.e. exclusive of its

subsidiaries) duly certified by any one of the authority mentioned in Note - 2.01.3.1

above certifying that these information/ documents are based on the audited

accounts, as the case may be.

2.01.4 Litigation History:

2.01.4.1 The bidder should provide detailed information on any litigation or arbitration arising

out of contracts completed or under execution by it over the last five years. A

Page 36: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

22

BID FORM : APDCL/DDUGJY/II/XII/REDB

consistent history of awards involving litigation against the Bidder or any partner of JV

may result in rejection of Bid.

2.01.4.2 Notwithstanding anything stated hereinabove, the Employer reserves the right to

assess the capacity and capability of the bidder, should the circumstances warrant

such assessment in an overall interest of the Employer. The Employer reserves the

right to waive minor deviations if they do not materially affect the capability of the

Bidder to perform the contract.

2.01.4.2.1 In order to assess the financial capacity and capability of the bidder, thebidder ,either Single or JV(or each of JV partner) has to furnish adeclaration stating the quantum of work at hand till 31/3/2016 and thevalue of total work in Central / State Government department/ StatePower utility/CPSU etc. duly certified by the Govt.Department/organizations. An amount of 30% of the said value will bededucted from available MAAT for evaluating capacity of the bidder. Incase the information submitted is found to be not true, the bidder will beconsidered as non responsive. Submission of the declaration ismandatory in Techno-commercial bid as enclosure to Certificate of theAuditor(CA).Wherever there is no work at hand, a NIL declaration has tobe submitted.

Page 37: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

23

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-4

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under Deendayal

Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Form of Certificate of Origin and Eligibility)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

We hereby certify that equipment and materials to be supplied are produced in

..................................................................................................., an eligible source count ry.

We hereby certify that our company is incorporated and registered in

...................................................................................................., an eligible source country.

Date:.................... (Signature)...................................................………..

Place:................... (Printed Name)..........................................………….

(Designation)................…………..............................

(Common Seal).…………..........................................

Page 38: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

24

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-4A

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under Deendayal

Upadhyay Gram Jyoti Yojana (DDUGJY-II-II)

(List of Special Maintenance Tools & Tackles)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We are furnishing below the list of special maintenance tools & tackles for various equipment under the subject

project. The prices for these tools & tackles are included in our lumpsum bid price. We further confirm that the

list of special maintenance tools & tackles includes all the items specifically identified in your bidding documents

as brought out below:

------------------------------------------------------------------------------------------------------------------

S.No. For Equipment Item Description Unit Quantity

------------------------------------------------------------------------------------------------------------------

------------------------------------------------------------------------------------------------------------------

Notwithstanding what is stated above, we further confirm that any additional special maintenance tools and

tackles, required for the equipment under this project shall be furnished by us at no extra cost to the employer.

Date:....................

(Signature)...................................................……………..

Place:................... (Printed Name)..........................................………………

(Designation)................…………............................……..

(Common Seal).…………........................................……..

Page 39: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

25

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-4B

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under Deendayal

Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(List of Special Maintenance Tools & Tackles)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We are furnishing below the list of special maintenance tools & tackles for various equipment under the subject

Project. The prices for these tools & tackles which are to be taken back after the completion of the work by us

are not included in our lumpsum bid price. We further confirm that the list of special maintenance tools & tackles

includes all the items specifically identified in your bidding documents as brought out below:

(a) .............................

(b) .............................

Date:....................

(Signature)...................................................……………..

Place:...................

(Printed Name)..........................................………………

(Designation)................…………............................……..

(Common Seal).…………........................................……..

Page 40: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

26

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-5

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under

Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Bought-out & Sub-contracted Items)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

1.0 We hereby furnish the details of the items/ sub-assemblies, we propose to buy for the purpose of furnishing and

installation of the subject Project:

Sl.

No.

Item Description Quantity proposed to be

bought/sub-contracted

Details of the proposed sub-

contractor/sub-vendor

Name Nationality

1.

2.

3.

4.

5.

6.

2.0 We hereby declare that, we would not subcontract the erection portion of the contract without the

prior approval of Employer.

Date:.................... (Signature)...............................................

Place:................... (Printed Name).......................................…

(Designation)......…................................….

(Common Seal).….………..........................

Page 41: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

27

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-6

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State) under

Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Alternative, Deviations and Exceptions to the Provisions)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

The bidder shall itemize any deviation from the Specifications included in his bid. Each item shall be listed

(separate sheets may be used and enclosed with this Attachment) with the following information:

Sl. No. Reference clause in the

Specifications

Deviation Cost of withdrawal of the

deviation

The above deviations and variations are exhaustive. We confirm that we shall withdraw the deviations proposed

by us at the cost of withdrawal indicated in this attachment, failing which our bid may be rejected and Bid

Security forfeited.

Except for the above deviations and variations, the entire work shall be performed as per your specifications and

documents. Further, we agree that any deviations, conditionality or reservation introduced in this Attachment-6

and/or in the Bid form, Price schedules & Technical Data Sheets and covering letter, or in any other part of the

bid will be reviewed to conduct a determination of the substantial responsiveness of the bid.

Date:.................... (Signature)...............................................

Place:................... (Printed Name)...................................…

(Designation).............……........................

(Common Seal)..................................……

Page 42: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

28

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-8

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Manufacturer’s Authorization Form)

(On Manufacturer’s Letterhead, see Clause 9.3(c) of the ITB)

To: [Insert: name of Employer]

Dear Ladies and/or Gentlemen,

WE [insert: name of Manufacturer] who are established and reputable manufacturers of [insert: name

and/or description of the plant & equipment] having production facilities at [insert: address of factory]

do hereby authorize [insert: name & address of Bidder] (hereinafter, the “Bidder”) to submit a bid, and

subsequently negotiate and sign the Contract with you against IFB [insert: title and reference number of

Invitation for Bids] including the above plant & equipment or other goods produced by us.

We hereby extend our full guarantee and warranty for the above specified plant & equipment materials or other

goods offered supporting the supply, installation and achieving of Operational Acceptance of the plant by the

Bidder against these Bidding Documents, and duly authorize said Bidder to act on our behalf in fulfilling these

guarantee and warranty obligations. We also hereby declare that we and ……………, [insert: name of the

Bidder] have entered into a formal relationship in which, during the duration of the Contract (including warranty

/ defects liability) we, the Manufacturer or Producer, will make our technical and engineering staff fully available

to the technical and engineering staff of the successful Bidder to assist that Bidder, on a reasonable and best

effort basis, in the performance of all its obligations to the Purchaser under the Contract.

For and on behalf of the Manufacturer

Signed: _______________________________________________________________

Date: __________________________________

Page 43: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

29

BID FORM : APDCL/DDUGJY/II/XII/REDB

In the capacity of [insert: title of position or other appropriate designation] and this should be signed by

a person having the power of attorney to legal bind the manufacturer.

Date:....................

Place:................... (Signature)........................................….........………..

(Printed Name)...........................................………….

(Designation)................…………................................

(Common Seal).…………..........…...….......................

Note 1. The letter of Undertaking should be on the letterhead of the Manufacturer and should be signed by a

person competent and having Power of Attorney to legally bind the Manufacturer. It shall be included

by the bidder in its bid.

2. Above undertaking shall be registered or notarized so as to be legally enforceable.

Page 44: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

30

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-9

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Work Completion Schedule)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We hereby declare that the following Work Completion Schedule shall be followed by

us in furnishing and installation of the subject Project for the period commencing from

the effective date of Contract to us:

Sl.No.

Description of WorkPeriod in months from the effective dateof Contract

1. Detailed Engineering and drawing submission

a) commencement

b) completion

2. Procurement of equipment/ components & assembly

a) commencement

b) completion

3. Type Tests

a) commencement

b) completion

4. Manufacturing

a) commencement

b) completion

5. Shipments & Delivery

a) commencement

b) completion

6. Establishment of site office

Page 45: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

31

BID FORM : APDCL/DDUGJY/II/XII/REDB

Sl.No.

Description of WorkPeriod in months from the effective dateof Contract

7. Installation at Site

a) commencement

b) completion

8. Testing & Pre-commissioning

a) commencement

b) completion

9. Trial Operation

a) commencement

b) completion

Date:.................... (Signature)...........….......................................………..

Place:................... (Printed Name)....…....................................………….

(Designation)......….........…………..............................

(Common Seal).…..………..........................................

Note: Bidders to enclose a detailed network covering all the activities to be undertaken for completion of the

project indicating key dates for various milestones for each phase constituent-wise.

Page 46: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

32

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-10

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Guarantee Declaration)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We hereby declare that this Attachment of “Guarantee Declaration” is furnished by us in Packet-I of InnerEnvelope-2 of bid envelope.

Date:....................

(Signature)................….................................………..

Place:...................

(Printed Name)...........................................………….

(Designation).............….…………..............................

(Common Seal).……….…..........................................

Page 47: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

33

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-11

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Information regarding Ex-employees of XXXXX (Name of Employer) in our Organisation)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We hereby furnish the details of ex-employees of XXXXX (Name of Employer) who had retired/ resigned at

the level of XXXXXX (Define suitable post) from XXXXX (Name of Employer)and subsequently have been

employed by us:

__________________________________________________________________________

Sl. Name of the person Date of Retirement/ Date of joining and

No. with designation in resignation from designation in our

XXXXX (Name of XXXXX (Name of Organisation

Employer) Employer)

_________________________________________________________________________

1. ...................... ................................. ...............................

2. ...................... ................................. ...............................

3. ...................... ................................. ...............................

___________________________________________________________________________

Date:.................... (Signature)........................................….........………..

Place:................... (Printed Name)...........................................………….

(Designation)................…………................................

(Common Seal).…………..........…...….......................

Note: The information in similar format should be furnished for each partner of joint venture in case of joint

venture bid.

Page 48: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

34

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-12

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We hereby furnish the details of Price Adjustments:

Name of Material Variation*

ACSR conductor No Variation

Power / Station / Distribution

Transformer ( Copper / Aluminium

wound)No Variation.

Cables No Variation.

We confirm that Price Adjustment shall not be preferred by us.

Date:....................

(Signature)........................................….........………..

Place:...................

(Printed Name)...........................................………….

(Designation)................…………................................

(Common Seal).…………..........…...…......................

Page 49: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

35

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-14

(PRE-CONTRACT INTEGRITY PACT)

General

This pre-bid pre-contract Agreement (hereinafter called the Integrity Pact) is made on -- day of the --- mon th

of -------, between, on one hand, the ………………….. (Name of Owner) acting through Shri…… (Name and

designation of Project Manager) (hereinafter called the "BUYER", which expression shall mean and include,

unless the context otherwise requires, his successors in office and assigns) of the First Part and M/s…….. (Name

of Bidder) represented by Shri ,Chief Executive Officer (hereinafter called the "BIDDER/Seller" which

expression shall mean and include, unless the context otherwise requires, his successors and permitted assigns)

of the Second Part.

WHEREAS the BUYER proposes to procure (Name of the Stores/Equipment/Item) and the BIDDER/Seller is

willing to offer/has offered the stores and

WHEREAS the BIDDER is a private company/public company/Government

undertaking/partnership/registered export agency, constituted in accordance with the relevant law in the

matter and the BUYER is a PSU/Utility/Department of State Govt. performing its functions on behalf of the

……………… (Name of owner).

NOW, THEREFORE,

To avoid all forms of corruption by following a system that is fair, transparent and free from any

influence/prejudiced dealings prior to, during and subsequent to the currency of the contract to be entered into

with a view to:-

Enabling the BUYER to obtain the desired said stores/equipment at a competitive price in conformity with the

defined specifications by avoiding the high cost and the distortionary impact of corruption on public procurement,

and

Enabling BIDDERs to abstain from bribing or indulging in any corrupt practice in order to secure the contract by

providing assurance to them that their competitors will also abstain from bribing and other corrupt practices and

the BUYER will commit to prevent corruption, in any form, by its officials by following transparent procedures.

The parties hereto hereby agree to enter into this Integrity Pact and agree as follows:

1.0 Commitments of the BUYER

1.1 The BUYER undertakes that no official of the BUYER, connected directly or indirectly with the contract,

will demand, take a promise for or accept, directly or through intermediaries, any bribe, consideration,

gift, reward, favour or any material or immaterial benefit or any other advantage from the BIDDER,

either for themselves or for any person, organization or third party related to the contract in exchange

for an advantage in the bidding process, bid evaluation, contracting or implementation process related

to the contract.

Page 50: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

36

BID FORM : APDCL/DDUGJY/II/XII/REDB

1.2 The BUYER will, during the pre-contract stage, treat all BIDDERs alike and will provide to all BIDDERs

the same information and will not provide any such information to any particular BIDDER which could

afford an advantage to that particular BIDDER in comparison to other BIDDERs.

1.3 All the officials of the BUYER will report to the appropriate Government office any attempted or

completed breaches of the above commitments as well as any substantial suspicion of such a breach

2.0 In case any such preceding misconduct on the par t of such official (s) is reported by the BIDDER to the

BUYER with full and verifiable facts and the same is primafacie found to be correct by the BUYER, necessary

disciplinary proceedings, or any other action as deemed fit, including criminal proceedings may be initiated

by the BUYER and such a person shall be debarred from further dealings related to the contract process. In

such a case while an enquiry is being conducted by the BUYER the proceedings under the contract would not

be stalled.

Commitments of BIDDERs

3.0 The BIDDER commits itself to take all measures necessary to prevent corrupt practices, unfair means and

illegal activities during any stage of its bid or during any pre-contract or post-contract stage in order to

secure the contract or in furtherance to secure it and in particular commit itself to the following:-

3.1 The BIDDER will not offer, directly or through intermediaries, any bribe, gift, consideration, reward, favour,

any material or immaterial benefit or other advantage, commission, fees, brokerage or inducement to any

official of the BUYER, connected directly or indirectly with the bidding process, or to any person,

organisation or third party related to the contract i n exchange for any advantage in the b i d d i n g ,

evaluation, contracting and implementation of the contract.

3.2 The BIDDER further undertakes that it has not given, offered or promised to give, directly or indirectly any

bribe, gift, consideration, reward, favour, any material or immaterial benefit or other advantage,

commission, fees, brokerage or inducement to any official of the BUYER or otherwise in procuring the

Contract or for bearing to door having done any act in relation to the obtaining or execution of the contract

or any other contract with the Government for showing or for bearing to show favour or disfavour to any

person in relation to the contract or any other contract with Government.

3.3 BIDDERs shall disclose the name and address of agents a n d representatives and Indian BIDDERs

shall disclose their foreign principals or associates.

3.4 BIDDERs shall disclose the payments to be made by them to agents/brokersor any other intermediary, in

connection with this bid/contract.

3.5 The BIDDER further confirms and declares to the BUYER that the BIDDER is the original

manufacturer/integrator/authorised government sponsored export entity of the defence stores and has not

engaged any individual or firm or company whether Indian or foreign to intercede, facilitate or in any way

to recommend to the BUYER or any of its functionaries, whether officially or unofficially to the award of the

contract to the BIDDER, nor has any amount been paid, promised or intended to be paid to any such

individual, firm or company in respect of any such intercession, facilitation or recommendation.

Page 51: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

37

BID FORM : APDCL/DDUGJY/II/XII/REDB

3.6 The BIDDER, either while presenting the bid or during pre-contract negotiations or before signing the

contract, shall disclose any payments he has made, is committed to or intends to make to officials of the

BUYER or their family members, agents, brokers or any other intermediaries in connection with

the contract and the details of services agreed upon for such payments.

3.7 The BIDDER will not collude with other parties interested in the contract to impair the transparency,

fairness and progress of the bidding process, bid evaluation, contracting and implementation of the

contract.

3.8 The BIDDER will not accept any advantage in exchange for any corrupt practice, unfair means and illegal

activities.

3.9 The BIDDER shall not use improperly, for purposes of competition or personal gain, or pass on to others, any

information provided by the BUYER as part of the business relationship, regarding plans, technical proposals

and business details, including information contained in any electronic data carrier. The BIDDER also

undertakes to exercise due and adequate care lest any such information is divulged.

3.10 The BIDDER commits to refrain from giving any complaint directly or through any other manner without

supporting it with full and verifiable facts.

3.11 The BIDDER shall not instigate or cause to instigate any third person to commit any of the actions

mentioned above.

3.12 If the BIDDER or any employee of the BIDDER or any person acting on behalf of the BIDDER, either directly

or indirectly, is a relative of any of the officers of the BUYER, or alternatively, if any relative of an officer of

the BUYER has financial interest/stake in the BIDDER's firm, the same shall be disclosed by the BIDDER at

the time of filing of tender.

The term 'relative' for this purpose would be as defined in Section 6 of the Companies Act1956.

3.13 The BIDDER shall not lend to or borrow any money from or enter into any monetary dealings or

transactions, directly or indirectly, with any employee of the BUYER.

4. Previous Transgression

4.1 The BIDDER declares that no previous transgression occurred in the last three years immediately before

signing of this Integrity Pact, with any other company in any country in respect of any corrupt practices

envisaged hereunder or with any Public Sector Enterprise in India or any Government Department in India

that could justify BIDDER’s exclusion from the tender process.

4.2 The BIDDER agrees that if it makes incorrect statement on this subject, BIDDER can be disqualified from the

tender process or the contract, if already awarded, can be terminated for such reason.

5. Earnest Money (Security Deposit)

5.1 While submitting commercial bid, the BIDDER shall deposit an amount………. (to be specified in RFP) as

Earnest Money/Security Deposit, with the BUYER through any of the following instruments:

Page 52: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

38

BID FORM : APDCL/DDUGJY/II/XII/REDB

(i) Bank Draft or a Pay Order in favour of

(ii) A confirmed guarantee by an Indian Nationalised Bank, promising payment of the guaranteed sum to

the BUYER on demand within three working days without any demur whatsoever and without seeking

any reasons whatsoever. The demand for payment by the BUYER shall be treated as conclusive proof of

payment.

(iii) Any other mode or through any other instrument (to be specified in the RFP).

5.2 The Earnest Money/Security Deposit shall be valid up to a period of….. years or the complete conclusion of

the contractual obligations to the complete satisfaction of both the BIDDER and the BUYER, including

warranty period, whichever is later.

5.3 In case of the successful BIDDER a clause would also be incorporated in the Article pertaining to

Performance Bond for the Supply Part that the provisions of Sanctions for Violation shall be applicable for

forfeiture of Performance Bond in case of a decision by the BUYER to forfeit the same without assigning any

reason for imposing sanction for violation of this Pact.

5.4 No interest shall be payable by the BUYER to the BIDDER on Earnest Money/Security Deposit for the period

of its currency.

6. Sanctions for Violations

6.1 Any breach of the aforesaid provisions by the BIDDER or anyone employed by it or acting on its behalf

(whether with or without the knowledge of the BIDDER) shall entitle the BUYER to take all or any one of the

following actions, wherever required:-

(i) To immediately call off the pre contract negotiations without assigning any reason or giving any

compensation to the BIDDER. However, the proceedings with the other BIDDER(s) would continue.

(ii) The Earnest Money Deposit (in pre-contract stage) and/or Security Deposit/Performance Bond (after the

contract is signed) shall stand forfeited either fully or partially, as decided by the BUYER and the BUYER

shall not be required to assign any reason therefore.

(iii) To immediately cancel the contract, if already signed, without giving any compensation to the

BIDDER.

(iv) To recover all sums already paid by the BUYER, and in case of an Indian BIDDER with interest thereon

at 2% higher than the prevailing Prime Lending Rate of State Bank of India, while in case of a BIDDER

from a country other than India with interest thereon at 2% higher than the UBOR. If any outstanding

payment is due to the BIDDER from the BUYER in connection with any other contract for any other

stores, such outstanding payment could also be utilized to recover the aforesaid sum and interest.

(v) To encash the advance bank guarantee and performance bond/warranty bond, if furnished by the

BIDDER, in order to recover the payments, already made by the BUYER, along with interest.

Page 53: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

39

BID FORM : APDCL/DDUGJY/II/XII/REDB

(vi) To cancel all or any other Contracts with the BIDDER. The BIDDER shall be liable to pay

compensation for any loss 'or damage to the BUYER resulting from such cancellation/rescission and the

BUYER shall be entitled to deduct the amount so payable from the money(s) due to the BIDDER

(vii) To debar the BIDDER from participating in future bidding processes of the Government of India for

a minimum period of five years, which may be further extended at the discretion of the BUYER.

(viii) To recover all sums paid in violation of this Pact by BIDDER(s) to any middleman or agent or broker

with a view to securing the contract.

(ix) In cases where irrevocable Letters of Credit have been received in respect of any contract signed by the

BUYER with the BIDDER, the same shall not be opened.

(X) Forfeiture of Performance Bond in case of a decision by the BUYER to forfeit the same without assigning

any reason for imposing sanction for violation of this Pact.

6.2 The BUYER will be entitled to take all or any of the actions mentioned at para 6.1(i) to (x) of this Pact also

on the Commission by the BIDDER or anyone employed by it or acting on its behalf (whether with or

without the knowledge of the BIDDER), of an offence as defined in Chapter IX of the Indian Penal code,

1860 or Prevention of Corruption Act, 1988 or any other statute enacted for prevention of corruption.

6.3 The decision of the BUYER to the effect that a breach of the provisions of this Pact has been committed by

the BIDDER shall be final and conclusive on the BIDDER. However, the BIDDER can approach the

Independent Monitor(s) appointed for the purposes of this Pact.

7. Fall Clause

7.1 The BIDDER undertakes that it has not supplied/is not supplying similar product/systems or subsystems at a

price lower than that offered in the present bid in respect of any other Ministry/Department of the

Government of India or PSU and if it is found at any stage that similar product/systems or sub systems was

supplied by the BIDDER to any other Ministry/Department of the Government of India or a PSU at a lower

price, then that very price, with due allowance for elapsed time, will be applicable to the present case and

the difference in the cost would be refunded by the BIDDER to the BUYER, if the contract has already been

concluded.

8. Independent Monitors

8.1 The BUYER has appointed Independent Monitors (hereinafter referred to as Monitors) for this Pact in

consultation with the Central Vigilance to as Monitors) for this Pact in consultation with the Central Vigilance

Commission (Names and Addresses of the Monitors to be given).

8.2 The task of the Monitors shall be to review independently andobjectively, whether and to what

extent the parties comply with the obligations under this Pact.

8.3 The Monitors shall not be subject to instructions by the representatives of the parties and perform their

functions neutrally and independently.

Page 54: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

40

BID FORM : APDCL/DDUGJY/II/XII/REDB

8.4 Both the parties accept that the Monitors have the right to access all the documents relating to the

project/procurement, including minutes of meetings.

8.5 As soon as the Monitor notices, or has reason to believe, a violation of this Pact, he will so inform the

Authority designated by the BUYER.

8.6 The BIDDER(s) accepts that the Monitor has the right to access without restriction to all Project

documentation of the BUYER including that provided by the BIDDER. The BIDDER will also grant the

Monitor, upon his request and demonstration of a valid interest, unrestricted and unconditionalaccess to his

project documentation. The same is applicable to Subcontractors. The Monitor shall be under contractual

obligation to treat the information and documents of the BIDDER/Subcontractor(s) with confidentiality.

8.7 The BUYER will provide to the Monitor sufficient information about all meetings among the parties related to

the Project provided such meetings could have an impact on the contractual relations between the parties.

The parties will offer to the Monitor the option to participate in such meetings.

8.8 The Monitor will submit a written report to the designated Authority of BUYER/Secretary in the Department/

within 8 to 10 weeks from the date of reference or intimation to him by the BUYER / BIDDER and, should

the occasion arise, submit proposals for correcting problematic situations.

9. Facilitation of Investigation

In case of any allegation of violation of any provisions of this Pact or payment of commission, the BUYER or its

agencies shall be entitled to examine all the documents including the Books of Accounts of the BIDDER and the

BIDDER shall provide necessary information and documents in English and shall extend all possible help

for the purpose of such examination.

10. Law and Place of Jurisdiction

This Pact is subject to Indian Law. The place of performance and jurisdiction is the seat of the BUYER.

11. Other Legal Actions

The actions stipulated in this Integrity Pact are without prejudice to any other legal action that may follow in

accordance with the provisions of the extant law in force relating to any civil or criminal proceedings

12. Validity

12.1 The validity of this Integrity Pact shall be from date of its signing and extend upto 5 years or the complete

execution of the contract to the satisfaction of both the BUYER and the BIDDER/Seller, including warranty

period, whichever is later. In case BIDDER is unsuccessful, this Integrity Pact shall expire after six months

from the date of the signing of the contract.

12.2 Should one or several provisions of this Pact turn out to be invalid; theremainder of this Pact shall remain

valid. In this case, the parties will strive to come to an agreement to their original intentions.

13. The parties hereby sign this Integrity Pact at ……………on…………………..

Page 55: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

41

BID FORM : APDCL/DDUGJY/II/XII/REDB

BUYER BIDDER

Name of the Officer CHIEF EXECUTIVE OFFICER

Designation

Deptt./PSU

Witness Witness

1……………………….. 2……………………………….

2………………………. 3………………………………..

* Provisions of these clauses would need to be amended/ deleted in line with the policy of the BUYER in regard

to involvement of Indian agents of foreign suppliers

Page 56: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

42

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-15

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Option for Initial Advance (either Interest Bearing Initial Advance or No Initial Advance) and

Information for E-payment, PF details and declaration regarding Micro/Small & Medium

Enterprises)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

I. We have read the provisions in the Bidding Documents regarding furnishing the option for advance

payment. Accordingly, as per ITB Clause 9.3 as provided in Section BDS, Section III, Vol.-I of the Bidding

Documents, we hereby confirm to opt the following:

Interest Bearing Initial Advance

Supply Portion : Yes* [ ] No* [ ]

Installation Portion : Yes^ [ ] No^ [ ]

(*^ tick ONLY ONE of the selected options)

II. We are furnishing the following details of Statutory Registration Numbers and details of Bank for electronic

payment.

1. Name of the Supplier/ Contractor in whose

favour payment is to be made

2. Address with PIN Code and State Registered Office:

Page 57: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

43

BID FORM : APDCL/DDUGJY/II/XII/REDB

Branch Office:

Correspondence Address:

3. Status – Company/others

[Declaration of Micro/ Small/ Medium Enterprise

under Micro/ Small & Medium Enterprises

Development Act 2006, if applicable]

4. Permanent Account (PAN) No.

5. Central Sales Tax (CST) No.

6. State Sales Tax No.

7. Work Contract Tax No.

8. Service Tax Registration No.

9. PF Registration No. of the Company

10. PF Regional Office covered (with Address)

11. Name of Contact Person

12. Telephone No(s). Landline(s):

Page 58: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

44

BID FORM : APDCL/DDUGJY/II/XII/REDB

Email

Mobile(s):

Email ID :

13. Bank Details for Electronic Payment Name of the Bank:

Address of Branch:

Account No.:

Type of Account:

[ ] Saving

[ ] Current

14. 9 digit MICR code printed at bottom in middle,

next to cheque no.

15. IFSC (for RTGS)/NEFT Code (to be obtained

from the Bank)

Sample Cancelled Cheque to be enclosed

We hereby declare that the above information is true and correct and we agree that the payment on account of

this Contract, in the event of award, be made in the above account maintained in the above mentioned Bank.

Page 59: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

45

BID FORM : APDCL/DDUGJY/II/XII/REDB

Date:....................

(Signature)................….................................………..

Place:...................

(Printed Name)...........................................………….

(Designation).............….…………..............................

(Common Seal).……….…..........................................

Page 60: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

46

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-16

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Additional Information)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

In support of the additional information required as per ITB Sub-Clause 9.3 (p) of the

Bidding Documents, we furnish herewith our data/details/documents etc., alongwith

other information, as follows (the stipulations have been reproduced in italics for

ready reference):

1.0 The Bidder shall furnish

A certificate from their Banker(s) (as per prescribed formats in Form 16, Volume-I:Section-VI: Sample

Forms and Procedures) indicating various fund based/non fund based limits sanctioned to the Bidder

and the extent of utilization as on date. Such certificate should have been issued not earlier than three

months prior to the date of bid opening. Wherever necessary the Employer may make queries with the

Bidders’ Bankers.[Reference ITB clause 9.3(p)(i)]

1.1 In accordance with 1.0, certificate(s) from banker as per requisite format, indicating various fund

based/non fund based limits sanctioned to the bidder or each member of the joint venture and the

extent of utilization as on date is/are enclosed, as per the following details:

Name of the Bidder/partner of Joint Venture

Name of the Banker by whom certificate issued

Date of certificate (should not be earlier than 3 months prior to date of

bid opening)

Whether fund based/non fund based limits are indicated in the certificate

Whether extent of utilization is indicated in the certificate

Page 61: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

47

BID FORM : APDCL/DDUGJY/II/XII/REDB

1.2 The Bidder should accordingly also provide the following information/documents (In case of JV

bidders, information should be provided separately for all the Partners of JV in the given

format):

(i) Details of Banker:

Name of Banker

Address of Banker _____________________________

_____________________________

_____________________________

Telephone No. _____________________________

Contact Name and Title _____________________________

Fax No. _____________________________

E-mail ID _____________________________

(ii) As per para 1.0, Authorization Letter(s) from the bidder (in case of JV bidder, from all the

partners) addressed to the Banker(s), authorizing XXXXX (Name of Employer) to seek

queries about the bidder with the Banker(s) and advising the Banker(s) to reply the same

promptly, is/are enclosed as per following details:

Sl. No. Letter Ref. Date Addressed to

(name of the Bank)

2.0 Litigation History

The bidder should provide detailed information on any litigation or arbitrationarising out of contracts completed or under execution by it over the last fiveyears. A consistent history of awards involving litigation against the Bidder or

Page 62: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

48

BID FORM : APDCL/DDUGJY/II/XII/REDB

any partner of JV may result in rejection of Bid. [Reference ITB clause9.3(p)(ii)]

2.1 Details of litigation history resulting from Contracts completed or under execution by the bidder over thelast five years

Year Name of client, cause of

litigation/arbitration and

matter in dispute

Details of

Contract and

date

Award for or

against the

bidder

Disputed

amount

3.0 OTHER INFORMATION

3.1 Current Contract Commitments of works in progress

Bidders (individual firms or each partners of JV) should provide information on their current

commitments on all contracts that have been awarded, or for which a letter of intent or acceptance has

been received, or for contracts approaching completion, but for which an unqualified, full completion

certificate has yet to be issued.

Details of Contract Value of outstanding work (Rs.) Estimated completion date

Page 63: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

49

BID FORM : APDCL/DDUGJY/II/XII/REDB

3.2 Financial Data :

(In Rs. Millions)

Actual

(previous five years)

Projection for next five

years

1. Total Assets

2. Current Assets

3. Total Liability

4. Current Liability

5. Profit before taxes

6. Profit after taxes

4. The information/documentation in support of Bidder’s design infrastructure and erection facilities and

capacity and procedures including quality control related to the work, are enclosed at _______ herewith.

5. The CV and experience details of a project manager with 15 years experience in executing such contract

of comparable nature including not less than five years as manager and the CVs of other employees to

be deputed for the subject work, are enclosed at ____ herewith.

Date:.................... (Signature) ……….....................................

Place:................... (Printed Name) ......................................….

(Designation) ....…..........................................

(Common Seal) …..........................................

Page 64: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

50

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment- 17

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Declaration for tax exemptions, reductions, allowances or benefits)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sirs,

1. We confirm that we are solely responsible for obtaining following tax exemptions, reductions,

allowances or benefits in respect of supplies under the subject Project, in case of award. We further

confirm that we have considered the same in our bid thereby passing on the benefit to XXXXX (Name

of Employer) while quoting our prices. In case of our failure to receive such benefits, partly or fully,

for any reason whatsoever, the Employer will not compensate us.

2. We are furnishing the following information required by the Employer for issue of requisite certificate if

and as permitted in terms of the applicable Govt. of India policies/procedures(in case of award):

Applicable Act,

Notification No. and

Clause Ref. No.

Sl. No. Description of item on

which applicable

Country of origin Remarks, if any

(The requirements listed above are as per current Notification of Govt. of India indicated above. These

may be modified, if necessary, in terms of the Notifications.)

Date:.................... Signature)...................................................……….…….

Place:................... (Printed Name)..........................................……………...

(Designation)................………............................……….

(Common Seal).………........................................………

Page 65: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

51

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-18

Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of State)

under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Declaration)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

Dear Sir,

We confirm that Bid Form have been filled up by us as per the provisions of the Instruction to Bidders. We have

also uploaded price bid electronically as per the provisions of the Instruction to Bidders. Further, we have noted

that the same shall be evaluated as per the provisions of the Bidding Documents.

Further, we hereby confirm that except as mentioned in the Attachment – 6 (Alternative, Deviations and

Exceptions to the Provisions) hereof and/or the Covering Letter, forming part of our Bid Envelope:

(i) there are no discrepancies/inconsistencies and deviations/omissions/ reservations to the Bidding

Documents, in the price bid;

(ii) the description of items and the unit thereof in the price schedules are in conformity with those indicated

in the price schedule of the Bidding Documents without any deviation to the specified scope of work.

We also confirm that in case any discrepancies/ inconsistencies and deviations/ omissions/ reservations, as

referred to in para (i) and (ii) above, is observed in the online price bid, the same shall be deemed as

withdrawn/rectified without any financial implication, whatsoever to XXXXX (Name of Employer). However, in

case of any arithmetical errors, the same shall be governed as per the provision of ITB Sub-Clause 27.2 read in

conjunction with BDS.

Date:.................... (Signature)...................................................………..

Place:................... (Printed Name)..........................................………….

(Designation)................…………..............................

(Common Seal).…………..........................................

Page 66: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Volume-II : Section-IIBid Forms (Bid Envelope)

52

BID FORM : APDCL/DDUGJY/II/XII/REDB

Attachment-19

Rural Electrification works of XXXXXXXX (name of district) district in XXXXX (Name of

State) under Deendayal Upadhyay Gram Jyoti Yojana (DDUGJY-II)

(Bank Guarantee verification Check list)

Bidder’s Name and Address: To: XXXXX (Name and Address of Employer)

S. No. Checklist Yes No

1 Does the bank guarantee compare verbatim with standard proforma for

BG?

2(a) Has the executing Officer of BG indicated his name designation & Power of

Attorney No. / Signing power Number etc. on BG?

2(b) Is each page of BG duly Signed/ initialled by the executants and last page

is signed with full particulars as required in the standard proforma of BG

and under the seal of the bank?

2(c) Does the last page of the BG carry the signatures of two witnesses

alongside the signature of the executing Bank Manager?

3(a) Is the BG on non-judicial stamp paper of appropriate value?

3(b) Is the date of sale of non-judicial stamp paper shown on the BG and the

stamp paper is issued not more than Six months prior to the date of

execution of BG?

4(a) Are the factual details such as Bid specification No., LOA No. contract price,

etc, correct?

4(b) Whether Overwriting /cutting, if any on the BG, authenticated under

signature & seal of executants?

5 Is the amount and validity of BG is inline with contract provisions?

6 Whether the BG has been issued by a Nationalized bank / Non-

Nationalized Bank acceptable to Buyer /Scheduled Bank in India (the

applicability of the bank should be in line with the provisions of bidding

documents)?

Date:.................... (Signature)...................................................………..

Place:................... (Printed Name)..........................................………….

(Designation)................…………..............................

(Common Seal).…………..........................................

Page 67: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

VOLUME-II: SECTION – III

Price Schedules

Price Schedule-1: Ex-works Supply of Materials

Price Schedule-2: Local Transportation, Insurance

and other incidental services

Price Schedule-3: Installation/Erection Charges

Price Schedule-4: Summary of Taxes and Duties

Price Schedule-5: Grand Summary

Page 68: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution
Page 69: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT New S/S,2x5 MVA at

UttarBarpeta

(Barpeta)

New S/S,2x5 MVA atGobardhana

(Barpeta)

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 1 22 Boundary wall inculing Gate R/Mt 220 220 4403 Construction of Assam Type control room building with best

quality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120 240

4 Water supply: Deep well with 1 HP motor- Pump,Overhead waterresurvior capacity 2x500 Ltr over the GI staging with necesssarypipeline with connection,stand & power connection appliances.

set 1 1 2

5 Approach road , 4.0 Mtr width Mtr 50 50 1006 Drainage System Mtr 100 100 2007 Foundation of Pad for 33/11KV power transformer No 2 2 48 Foundation of Pad for 33/.433 KV power transformer No 1 1 29 Const. of Cable Trenches as per specification with following sizes

: -

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Barpeta Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Barpeta District under DDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BAR

Page 1 of 31

9 Const. of Cable Trenches as per specification with following sizes: -

(a) Width 600mm x Depth . RM 150 150 30010 Gravelling of switch yard, depth 22.5 Cm with crushed stone

size 40 mmSq

Mtr.1200 1200 2400

11 Earth Filling CM 3900 2000 590012 Sign Board, size: 4 feetx3 feet No 1 1 2

EQUIPMENT & MATERIALS FOR CONSTRUTION OFSWITCHYARD13(a) 33/11KV 5 MVA Power Transformer Nos. 2 2 4

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB,Siemens, Schneider make

Nos. 3 3 6

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 2 2 4

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1 1 218 33KV , 10 KA Lightning Arrester with chagre monitor and GI

mounting(set of 3 units) Station TypeSet 3 3 6

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1 2

20 33 KV ,1250 Amp Isolator with earth blade Set 2 2 421 33 KV ,1250 Amp Isolator without earth blade Set 6 6 1222 33KV Transformer Panels preferably CG,ABB,Siemens,Schneider

makeNos. 2 2 4

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 1 1 2

24 33 KV Potential Transformer Set 1 1 225 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG,

ABB, Siemens, Schneider makeNo. 6 6 12

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4 8

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 2 2 4

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Boxand GI Structure

Set 2 2 4

Page 1 of 31

Page 70: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT New S/S,2x5 MVA at

UttarBarpeta

(Barpeta)

New S/S,2x5 MVA atGobardhana

(Barpeta)

TotalQuantity

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4 8

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4 8

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 9 9 18

37 11 KV Out door Potential Transformer Set 2 2 438 11 KV LA Line Type (set of 3 units) Set 4 4 839 11 KV LA Station Type (set of 3 units) Set 2 2 441 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 242 Battery charger etc. No. 1 1 249 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4700 4700 940050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 3400 3400 680051 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,

PVC insulated and PVC sheathed cableMtr 100 100 200

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 15 3054 33 KV Gantry Structure Extension Set ext. at PSS 155 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 256 Distrbutiob Box Nos. 1 1 257 LTACDB ,DCDB Etc. Set 1 1 258 Earthing & Grounding conductor as per Approved Electrical

Layout for each sub-station witha 75 x8 mm MS flat for ground mat MT 3 3 6b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 2c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 2

Page 2 of 31

c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 2d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.4059 40 mm dia,3000 mm length GI Earth Pipe No 25 25 5060 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.8061 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of

3 nos.30 30 60

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 108

63 Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1 2

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1 2

65 Substation Tools and Plants like megger, earth tester, Multimeter,Tong tester, Box-spanners, D-spanners, screw drivers, earthingrods, earth mat etc as required as per scope of work.

Set 1 1 2

66 New 33&11 KV Line LILO fromBarpeta

Feeder/ GSS

Bpt.Rd SS

a 33 KV Line Km 17 18 35b 11 KV Line Km 8 12 20c 33 KV Rly-Xing No 1 1g 33 KV Gantry Structure (Exiention) No 1 1

Page 2 of 31

Page 71: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 35.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 7002 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 2803 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 6304 Jam Clamp of GI Flat 65x6 mm Pair 18205 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 4206 33 KV Polymeric Pin Insulator No. 33607 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 16808 Tension Clamp for Wolf Conductor No. 8409 AAA Wolf Conductor (19/3.40 mm) Km. 115.50

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 350

11 Guy Insulator (HT) No. 70012 Stay Wire 7/4.0 mm Kg 2800

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 2100

14 Jointing Sleeve for Wolf No. 105

Rural Electrification works in Barpeta Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Barpeta District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BAR

Page 3 of 31

14 Jointing Sleeve for Wolf No. 10515 PG Clamp for Wolf (Alcon 80) No. 84016 Al. Binding Wire (10 SWG.) Kg 21017 GI Nuts & Bolts (assorted) Kg 280018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 140019 33 KV Danger Plate (1.6 mm thick) No. 70020 Barbed Wire Kg 140021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 70022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 700A1 33 KV Overhead Line Crossing - Line to line / Road: Set 351 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 702 GI wire 8 SWG for cross lacing as per T.S Kg. 3503 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 7004 GI 'I' Hook No. 1405 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 70B New 11 kV Line Ckt. Km. 20.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 4002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 2403 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 1604 Composite Polymeric 11 kV Pin Insulator No. 9605 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 4806 Tension Clamp for Raccoon No. 4807 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 66.00

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 200

9 HT Guy Insulator No. 20010 GI Stay wire 7/3.15 mm Kg. 1600

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 800

12 GI wire 6 SWG for Earthing Kg. 200

Page 3 of 31

Page 72: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 413 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8014 Jointing Sleeve for Raccoon No. 6015 PG Clamp for Raccoon No. 48016 AI. Binding Wire (10 SWG.) Kg. 10017 Pole Clamp of GI flat (50x6) mm No. 32018 GI Barbed Wire for anticlimbing device Kg. 80019 11 KV Danger Plate (1.6 mm thick) No. 40020 GI Nuts & Bolts with GI washer (Assorted) Kg. 600B1 11 KV Overhead Line Crossing - Line to line / Road: Set 201 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 402 GI wire 8 SWG for cross lacing as per T.S Kg. 2003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 4004 GI 'I' Hook No. 805 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 40

Page 4 of 31Page 4 of 31

Page 73: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A 33/11 KV Substation Works -

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservatortank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthingstrips {(with braided conductor on bushing end), isolating link, isolationwith insulators, Vent explosion plug, control wiring between sensingequipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 4.00

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Barpeta Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BAR

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 31

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservatortank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthingstrips {(with braided conductor on bushing end), isolating link, isolationwith insulators, Vent explosion plug, control wiring between sensingequipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 4.00

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 2.00

3.00

Extention of 33 or 11 KV Bus Bar with 4 Four Nos 9.75 meter long PSC Pole,

Channel, cross arm, back clamps, insulator with hardware etc all complete

as per technical specifications, scope of works and approved drawings.

Set 1.00

Page 5 of 31

Page 74: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication asper IS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of worksand approved drawings..

MT 30.00

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 6.00

Page 6 of 31

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 6.00

6.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 2.00

7.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4.00

8.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 2.00

Page 6 of 31

Page 75: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 4.00

10.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 4.00

11.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 12.00

Page 7 of 31

11.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 12.00

12.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

6.00

13.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

2.00

14.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

2.00

15.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per

technical specifications, approved drawings and scope of the works.

No 12.00

16.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 4.00

Page 7 of 31

Page 76: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

17.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 8.00

18.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4.00

19.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

8.00

20.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 4.00

Page 8 of 31

20.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 4.00

21.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 8.00

22.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(With Earth Blade)

Set 8.00

23.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 18.00

24.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

4.00

Page 8 of 31

Page 77: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

25.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm(200 sqmm Al. Area) - Panther

Km 0.80

26.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including their terminationmaterials like glands, lugs, tagging etc. as per technical specifications,approved drawings and scope of the work.

Mtr 200.00

27.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 6800.00

28.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 9400.00

Page 9 of 31

28.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 9400.00

29.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 6.00

30.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 2.00

31.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 2.00

32.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.40

33.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,

RCC cover, placed on GI frame, bantonide powder and other accessories

complete as per technical specification. (for Power Transformer Neutral,

Station Transformer Neutral and Lightening Arresters direct earthing)

No 50.00

Page 9 of 31

Page 78: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

34.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 2.00

35.00

Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 2.00

Page 10 of 31

35.00

Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 2.00

36.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

60.00

37.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

108.00

38.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 2.00

39.00

110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification

for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per

technical specifications, approved drawings and scope of works.

Set 2.00

40.00

External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 2.00

41.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 2.00

Page 10 of 31

Page 79: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

42.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 2.00

43.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 2.00

B New 33 KV Lines

1.00

12 M long steel Tubular poles with welded steel base plate of Designation

540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as

per technical specification, approved drawings and scope of work.

No 700.00

Page 11 of 31

1.00

12 M long steel Tubular poles with welded steel base plate of Designation

540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as

per technical specification, approved drawings and scope of work.

No 700.00

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 28.16

3.00 GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 2.80

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete

as per technical specification, approved drawings and scope of work.

Set 2800.00

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 700.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.40

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas

per technical specification, approved drawings and scope of workSet 1680.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 3360.00

Page 11 of 31

Page 80: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 115.50

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 35.00

11.00

33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

Set 1.00

Page 12 of 31

11.00

33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

Set 1.00

C New 11 KV Lines

1.008.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 400.00

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials shown in BOQ for over headstructures as per technical specification, approved drawings and scope ofwork.

MT 9.09

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.60

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 200.00

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas

per technical specification, approved drawings and scope of work.Set 480.00

Page 12 of 31

Page 81: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 960.00

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 80.00

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.20

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

Page 13 of 31

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 20.00

Total Ex-works

Page 13 of 31

Page 82: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9New 33/11 KV Substation Works (Excluding civil works)

A. 33/11 KV Substation Works -

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 4.00

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Barpeta Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BAR

Page 14 of 31

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 4.00

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 2.00

3.00Extention of 33 or 11 KV Bus Bar with 4 (four)Nos 9.75 meter long PSC Pole, Channel,cross arm, back clamps, insulator with hardware etc all complete as per technicalspecifications, scope of works and approved drawings.

Set 1.00

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 30.00

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 6.00

Page 14 of 31

Page 83: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

6.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Set 2.00

7.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 4.00

8.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 2.00

Page 15 of 31

8.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 2.00

9.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 4.00

10.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 4.00

11.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 12.00

12.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

6.00

13.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

2.00

14.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2.00

Page 15 of 31

Page 84: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

15.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 12.00

16.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 4.00

17.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 8.00

18.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

4.00

Page 16 of 31

18.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

4.00

19.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

8.00

20.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 4.00

21.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories complete

for feeder breaker protection as per technical specifications, approved drawings and

scope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 8.00

22.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 8.00

23.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 18.00

Page 16 of 31

Page 85: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

24.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

4.00

25.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware

fittings, hardware, T-claimp etc as per technical specifications, approved drawings and

scope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.80

26.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVC

sheathed LT Power Cables including their termination materials like glands, lugs, tagging

etc. as per technical specifications, approved drawings and scope of the work.

Mtr 200.00

27.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 6800.00

Page 17 of 31

27.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 6800.00

28.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 9400.00

29.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 6.00

30.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 2.00

31.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 2.00

32.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.40

33.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 50.00

34.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 2.00

Page 17 of 31

Page 86: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

35.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 2.00

36.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

60.00

37.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.

Set ofthree

108.00

38.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 2.00

Page 18 of 31

38.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 2.00

39.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 2.00

40.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 2.00

41.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 2.00

42.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 2.00

43.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 2.00

B New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 700.00

Page 18 of 31

Page 87: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 28.16

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 2.80

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 2800.00

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 700.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.40

Page 19 of 31

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.40

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 1680.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 3360.00

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 115.50

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 35.00

11.00

33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos (INCLUDINGONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 km each) USING 150MM DIA CIPIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT,OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 33 KV LIGHTENING ARRESTORSTATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK including Wayleave/ Supervision Charges payable to Railway Department on actual basis.

set 1.00

C New 11 KV Lines

Page 19 of 31

Page 88: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 400.00

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 9.09

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.60

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nos

turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI stranded

wire etc as required as per technical specification, approved drawings and scope of work.

Set 200.00

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 480.00

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 960.00

Page 20 of 31

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 960.00

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 80.00

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.20

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 20.00

Total

Page 20 of 31

Page 89: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PERS/S

2.00

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 5900.00

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BAR

(Schedule of rates and prices)Rural Electrification works in Barpeta Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian RupeesBidder's Name & Address:

Page 21 of 31

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 5900.00

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 2400.00

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 4.00

5.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 2.00

6.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 6.00

Page 21 of 31

Page 90: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

7.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 12.00

8.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 30.00

9.00

Fabrication and Erection of Gantry structures using PSC Pole, GI channel, GIangle and GI flat of various sizes including GI nuts & bolts, etc as required asper soil & site requirment and as per Technical Specification, approved Drawing& Scope of works

Set 1.00

10.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 440.00

Page 22 of 31

10.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 440.00

Page 22 of 31

Page 91: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

11.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 240.00

12.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 300.00

Page 23 of 31

12.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 300.00

13.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 200.00

14.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 100.00

15.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 2.00

A (Ib) Substation Electrical works

Page 23 of 31

Page 92: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 4.00

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 2.00

33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 6.00

Page 24 of 31

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 6.00

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

6.00

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 2.00

Page 24 of 31

Page 93: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 4.00

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 16.00

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

8.00

Page 25 of 31

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

8.00

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2.00

11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 12.00

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 12.00

Page 25 of 31

Page 94: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 4.00

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 8.00

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

12.00

Page 26 of 31

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

12.00

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 26.00

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

4.00

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.80

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 200.00

Page 26 of 31

Page 95: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 6.00

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 2.00

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 2.00

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.40

Page 27 of 31

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.40

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 50.00

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 2.00

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 2.00

Page 27 of 31

Page 96: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 2.00

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 2.00

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 2.00

Page 28 of 31

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 2.00

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 2.00

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 35.00

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 210.00

Page 28 of 31

Page 97: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 490.00

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 28.16

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 2800.00

Page 29 of 31

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 2800.00

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 3360.00

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 1680.00

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

35.00

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 700.00

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 35.00

Page 29 of 31

Page 98: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

11.00

Erection of 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4 Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 km each)USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MMHDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLE CABLEJOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.),LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GI WIRES, CABLEMARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK includingWay leave/ Supervision Charges payable to Railway Department on actual basis.

Set 1.00

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 20.00

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 120.00

Page 30 of 31

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 120.00

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 280.00

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 9.09

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 80.00

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 200.00

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 960.00

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 480.00

Page 30 of 31

Page 99: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

20.00

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 20.00

Total

Page 31 of 31Page 31 of 31

Page 100: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT

New S/S,2x5 MVA at

UttarBarpeta

(Barpeta)

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 12 Boundary wall inculing Gate R/Mt 220 220

3Construction of Assam Type control room building with bestquality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120

4Water supply: Deep well with 1 HP motor- Pump,Overhead waterresurvior capacity 2x500 Ltr over the GI staging with necesssarypipeline with connection,stand & power connection appliances.

set 1 1

5 Approach road , 4.0 Mtr width Mtr 50 506 Drainage System Mtr 100 1007 Foundation of Pad for 33/11KV power transformer No 1 18 Foundation of Pad for 33/.433 KV power transformer No 1 1

9 Const. of Cable Trenches as per specification with following sizes: -

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Bongaigaon Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Bongaigaon District under DDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BNG

Page 1 of 30

9 Const. of Cable Trenches as per specification with following sizes: -

(a) Width 600mm x Depth . RM 150 150

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

SqMtr.

1200 1200

11 Earth Filling CM12 Sign Board, size: 4 feetx3 feet No 1 1

13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB,Siemens, Schneider make

Nos. 2 2

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 1 1

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Station Type

Set 2 2

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1

20 33 KV ,1250 Amp Isolator with earth blade Set 2 221 33 KV ,1250 Amp Isolator without earth blade Set 5 5

22 33KV Transformer Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 1 1

24 33 KV Potential Transformer Set 1 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG,ABB, Siemens, Schneider make

No. 5 5

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 1 1

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Boxand GI Structure

Set 1 1

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

Page 1 of 30

Page 101: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT

New S/S,2x5 MVA at

UttarBarpeta

(Barpeta)

TotalQuantity

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 8 8

37 11 KV Out door Potential Transformer Set 2 238 11 KV LA Line Type (set of 3 units) Set 4 439 11 KV LA Station Type (set of 3 units) Set 1 141 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 142 Battery charger etc. No. 1 149 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4100 410050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800 2800

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,PVC insulated and PVC sheathed cable

Mtr 100 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 1554 33 KV Gantry Structure Extension Set ext. at PSS 155 Station service transformer, 33/.433KV,100 KVA Nos. 1 156 Distrbutiob Box Nos. 1 157 LTACDB ,DCDB Etc. Set 1 1

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3b 50 x 6 mm Galvanized GS flat (risers) MT 1 1c 25 x 6 mm Galvanized GI flat (risers) MT 1 1

Page 2 of 30

c 25 x 6 mm Galvanized GI flat (risers) MT 1 1d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.259 40 mm dia,3000 mm length GI Earth Pipe No 25 2560 ACSR Panther Conductor for Bus bar Km 0.4 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1

65Substation Tools and Plants like megger, earth tester, Multimeter,Tong tester, Box-spanners, D-spanners, screw drivers, earthingrods, earth mat etc as required as per scope of work.

Set 1 1

66 New 33&11 KV Line Manikpur SS

a 33 KV Line Km 11 11b 11 KV Line Km 11 11e 33 KV NH-Xing No 1 1

Page 2 of 30

Page 102: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 11.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 2202 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 883 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 1984 Jam Clamp of GI Flat 65x6 mm Pair 5725 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 1326 33 KV Polymeric Pin Insulator No. 10567 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 5288 Tension Clamp for Wolf Conductor No. 2649 AAA Wolf Conductor (19/3.40 mm) Km. 36.30

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 110

11 Guy Insulator (HT) No. 22012 Stay Wire 7/4.0 mm Kg 880

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 660

14 Jointing Sleeve for Wolf No. 33

Rural Electrification works in Bongaigaon Project in Assam under DDUGJY Phase-II (REDB works)

For New S/S, 1x5 MVA at Daigagaon (Bongaigaon)

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BNG

Page 3 of 30

14 Jointing Sleeve for Wolf No. 3315 PG Clamp for Wolf (Alcon 80) No. 26416 Al. Binding Wire (10 SWG.) Kg 6617 GI Nuts & Bolts (assorted) Kg 88018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 44019 33 KV Danger Plate (1.6 mm thick) No. 22020 Barbed Wire Kg 44021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 22024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 220A1 33 KV Overhead Line Crossing - Line to line / Road: Set 111 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 222 GI wire 8 SWG for cross lacing as per T.S Kg. 1103 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2204 GI 'I' Hook No. 445 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 22B New 11 kV Line Ckt. Km. 11.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 2202 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 1323 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 884 Composite Polymeric 11 kV Pin Insulator No. 5285 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 2646 Tension Clamp for Raccoon No. 2647 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 36.30

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 110

9 HT Guy Insulator No. 11010 GI Stay wire 7/3.15 mm Kg. 880

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 440

12 GI wire 6 SWG for Earthing Kg. 11013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 4414 Jointing Sleeve for Raccoon No. 33

Page 3 of 30

Page 103: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

15 PG Clamp for Raccoon No. 26416 AI. Binding Wire (10 SWG.) Kg. 5517 Pole Clamp of GI flat (50x6) mm No. 17618 GI Barbed Wire for anticlimbing device Kg. 44019 11 KV Danger Plate (1.6 mm thick) No. 22020 GI Nuts & Bolts with GI washer (Assorted) Kg. 330B1 11 KV Overhead Line Crossing - Line to line / Road: Set 111 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 222 GI wire 8 SWG for cross lacing as per T.S Kg. 1103 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2204 GI 'I' Hook No. 445 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 22

Page 4 of 30Page 4 of 30

Page 104: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

A. 33/11 KV Substation Works -

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 1

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Bongaigaon Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BNG

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 1

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 1

3.00Extention of 33 or 11 KV Bus Bar with 2 (Two)-Nos SP-76 MS Pole,Channel, cross arm, back clamps, insulator with hardware etc all completeas per technical specifications, scope of works and approved drawings.

Set 1

Page 5 of 30

Page 105: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication asper IS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of worksand approved drawings..

MT 15

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 2

Page 6 of 30

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 2

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

Page 6 of 30

Page 106: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector EnergyMeter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 5

Page 7 of 30

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

2

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as pertechnical specifications, approved drawings and scope of the works.

No 5

Page 7 of 30

Page 107: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

Page 8 of 30

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector EnergyMeter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(With Earth Blade)

Set 4

Page 8 of 30

Page 108: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2.0

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200mm² Al. Area) - Panther

Km 0.4

Page 9 of 30

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200mm² Al. Area) - Panther

Km 0.4

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including their terminationmaterials like glands, lugs, tagging etc. as per technical specifications,approved drawings and scope of the work.

Mtr 100

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 2800

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 3.00

41.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 1.00

42.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 1.00

Page 9 of 30

Page 109: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

43.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.20

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,RCC cover, placed on GI frame, bantonide powder and other accessoriescomplete as per technical specification. (for Power Transformer Neutral,Station Transformer Neutral and Lightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 1

Page 10 of 30

46.00

Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 1

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 1

Page 10 of 30

Page 110: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

51.00

External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 1

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

New 33 KV Lines

Page 11 of 30

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line asper technical specification, approved drawings and scope of work.

No 220

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 8.840

3.00 GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 0.880

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire completeas per technical specification, approved drawings and scope of work.

Set 880

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 220

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.440

New 33 KV Lines

Page 11 of 30

Page 111: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsasper technical specification, approved drawings and scope of work

Set 528.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 1056

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 36

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 11

C New 11 KV Lines

Page 12 of 30

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 220.00

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials shown in BOQ for over headstructures as per technical specification, approved drawings and scope ofwork.

MT 4.99

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.33

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 110

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsasper technical specification, approved drawings and scope of work.

Set 264

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 528

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 44

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.11

New 11 KV Lines

Page 12 of 30

Page 112: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1.00 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 36.30

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 11

Total Ex-works

Page 13 of 30Page 13 of 30

Page 113: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1.00 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

New 33/11 KV Substation Works (Excluding civil works)A. 33/11 KV Substation Works -

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Bongaigaon Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BNG

Page 14 of 30

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 1

3.00Extention of 33 or 11 KV Bus Bar with 2 (Two)-Nos SP-76 MS Pole, Channel, cross arm,back clamps, insulator with hardware etc all complete as per technical specifications,scope of works and approved drawings.

Set 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15.00

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 2

Page 14 of 30

Page 114: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Set 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 15 of 30

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

2

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

Page 15 of 30

Page 115: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

Page 16 of 30

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 8

Page 16 of 30

Page 116: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

36.00ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.40

37.003.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 100

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 2800

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4100

Page 17 of 30

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3.00

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1.00

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1.00

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

Page 17 of 30

Page 117: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 1

47.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

Page 18 of 30

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 1

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B. New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 220

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 8.84

Page 18 of 30

Page 118: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 0.88

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 880

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 220.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.44

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 528

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 1056

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 36.30

Page 19 of 30

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 36.30

10.00Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 11

C New 11 KV Lines

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 220

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 4.99

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.33

4.00Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 110

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 264

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 528

Page 19 of 30

Page 119: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 44

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.11

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 36.30

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 11.00

Total

Page 20 of 30Page 20 of 30

Page 120: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @1.00 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A 33/11 KV Grid Substation worksA-I 33/11 KV Grid Substation works -

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soilprofile and necessary soil parameters of sub-station site & recommendations ofsoil mechanic engineer regarding foundation depth of defferent type of footingswith size including contour survey etc. as per Technical Specification.

PERS/S

1

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 1200

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/BNG

(Schedule of rates and prices)Rural Electrification works in Bongaigaon Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian Rupees

Page 21 of 30

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 1200

5.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 1

7.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 2

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 5

Page 21 of 30

Page 121: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and asper Technical Specification, approved Drawing & Scope of works

MT 15.00

11.00

Fabrication and Erection of Gantry structures using PSC Pole, GI channel, GIangle and GI flat of various sizes including GI nuts & bolts, etc as required asper soil & site requirment and as per Technical Specification, approved Drawing& Scope of works

Set 1

12.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

Page 22 of 30

12.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

13.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 120

14.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 150

Page 22 of 30

Page 122: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

15.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 100

16.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

17.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

B (Ib) Substation Electrical works

Page 23 of 30

17.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

B (Ib) Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 1

2.00Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,aluminium would outdoor type Distribution Transformer (Station Transformer) asper Technical Specification, approved Drawing & Scope of works

Set 1

33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 2

Page 23 of 30

Page 123: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

2

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 1

Page 24 of 30

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 1

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 7

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set of three 3

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

1

11KV Yard

Page 24 of 30

Page 124: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 5

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 5

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

Page 25 of 30

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

5

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 12

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set of three 2

Page 25 of 30

Page 125: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.40

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100.0

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 3.00

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1.00

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1.00

Page 26 of 30

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1.00

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.20

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 25.0

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 1

Page 26 of 30

Page 126: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 1

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 1

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with fullwave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDBas per approved drawings, technical specifications and scope of the work

Set 1

Page 27 of 30

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with fullwave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDBas per approved drawings, technical specifications and scope of the work

Set 1

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 1

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 1

A Erection, testing and Commissioning of New 33 KV lines:

1.00Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 11

Page 27 of 30

Page 127: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 66.00

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 154

Page 28 of 30

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 154

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 9

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 880

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 1056

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 528

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

11

Page 28 of 30

Page 128: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 220

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 11

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 11

2.01

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 66

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 154.00

Page 29 of 30

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 154.00

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channelcross arm, angle, flats and all other GI materials for over head structures.

MT 4.99

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 44

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 110.00

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 528

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 264

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

11

Page 29 of 30

Page 129: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam Value AddedTax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 11

11.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

20.00

12.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 20.00

Page 30 of 30

12.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 20.00

Total

Page 30 of 30

Page 130: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT

NewS/S,1x5MVA atPanbari(Dhubri)

Augmentationof Bisandoi

(Golokganj) atDhubri

(2x2.5) to(1x5+1x2.5)

Augmentation of

Mahamayaat Dhubri(1x2.5 to

2x2.5)

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 1 22 Boundary wall inculing Gate R/Mt 220 220 440

3Construction of Assam Type control room building with bestquality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120 240

4Water supply: Deep well with 1 HP motor- Pump,Overhead waterresurvior capacity 2x500 Ltr over the GI staging with necesssarypipeline with connection,stand & power connection appliances.

set 1 1 2

5 Approach road , 4.0 Mtr width Mtr 50 50 1006 Drainage System Mtr 100 100 2007 Foundation of Pad for 33/11KV power transformer No 1 18 Foundation of Pad for 33/.433 KV power transformer No 1 1 2

9 Const. of Cable Trenches as per specification with following sizes: -

(a) Width 600mm x Depth . RM 150 100 10 260

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

SqMtr.

1200 1200 400 2800

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Dhubri Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Dhubri District under DDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DHB

Page 1 of 33

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

SqMtr.

1200 1200 400 2800

11 Earth Filling CM 1000 100012 Sign Board, size: 4 feetx3 feet No 1 1 1 3

EQUIPMENT & MATERIALS FOR CONSTRUTION OFSWITCHYARD

13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1 213(b) 33/11KV 2.5 MVA Power Transformer Nos. 1 1

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB,Siemens, Schneider make

Nos. 2 2 1 5

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 1 2 1 4

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Station Type

Set 2 3 1 6

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1

20 33 KV ,1250 Amp Isolator with earth blade Set 2 1 321 33 KV ,1250 Amp Isolator without earth blade Set 5 3 1 9

22 33KV Transformer Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 2 1 4

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 1 1

24 33 KV Potential Transformer Set 1 1 2

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferablyCG, ABB, Siemens, Schneider make

No. 5 5

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 1 1

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Boxand GI Structure

Set 1 1

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4

Page 1 of 33

Page 131: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT

NewS/S,1x5MVA atPanbari(Dhubri)

Augmentationof Bisandoi

(Golokganj) atDhubri

(2x2.5) to(1x5+1x2.5)

Augmentation of

Mahamayaat Dhubri(1x2.5 to

2x2.5)

TotalQuantity

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 8 8

32 11 KV Gang Operated Switch (Line) Nos. 5 5

33 11 KV indoor VCB Panel for Transformer preferably CG, ABB,Siemens, Schneider make

Set 2 2

34 11 KV indoor VCB Panel for Feeder preferablyCG,ABB,Siemens,Schneider make

Set 4 4

35 12 KV indoor VCB Panel for Bus-cuplar preferablyCG,ABB,Siemens,Schneider make

Set 1 1

36 11 KV In door Potential Transformer Set 2 237 11 KV Out door Potential Transformer Set 2 238 11 KV LA Line Type (set of 3 units) Set 4 4 839 11 KV LA Station Type (set of 3 units) Set 1 2 341 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 242 Battery charger etc. No. 1 1 243 11 KV XLPE Cable 1x300Sq.mm Mtr 400 40044 11 KV XLPE Cable 1x300 Sq mm Terminate Box(outdoor) No 8 845 11 KV XLPE Cable 1x300 Sq mm Terminate Box(indoor) No 8 846 11 KV XLPE Cable 1x185 Sq.mm for 5 feeder Mtr 800 80047 11 KV XLPE Cable 1x185 Sq mm Terminate Box(outdoor) No 16 1648 11 KV XLPE Cable 1x185 Sq mm Terminate Box(indoor) No 16 1649 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4100 1000 800 5900.050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800 1500 600 4900

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,PVC insulated and PVC sheathed cable

Mtr 100 100 200.0

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 1555 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 256 Distrbutiob Box Nos. 1 1 2

Page 2 of 33

56 Distrbutiob Box Nos. 1 1 257 LTACDB ,DCDB Etc. Set 1 1 2

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3 6b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 2c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 2d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 060 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.8

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30 60

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 108

Page 2 of 33

Page 132: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 4.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 802 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 323 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 724 Jam Clamp of GI Flat 65x6 mm Pair 2085 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 486 33 KV Polymeric Pin Insulator No. 3847 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 1928 Tension Clamp for Wolf Conductor No. 969 AAA Wolf Conductor (19/3.40 mm) Km. 13.20

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 40

11 Guy Insulator (HT) No. 8012 Stay Wire 7/4.0 mm Kg 320

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 240

14 Jointing Sleeve for Wolf No. 12

Rural Electrification works in Dhubri Project in Assam under DDUGJY Phase-II (REDB works)

For New S/S,1x5 MVA at Panbari (Dhubri)

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DHB

Page 3 of 33

14 Jointing Sleeve for Wolf No. 1215 PG Clamp for Wolf (Alcon 80) No. 9616 Al. Binding Wire (10 SWG.) Kg 2417 GI Nuts & Bolts (assorted) Kg 32018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 16019 33 KV Danger Plate (1.6 mm thick) No. 8020 Barbed Wire Kg 16021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 80A1 33 KV Overhead Line Crossing - Line to line / Road: Set 41 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 82 GI wire 8 SWG for cross lacing as per T.S Kg. 403 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 804 GI 'I' Hook No. 16.005 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8B New 11 kV Line Ckt. Km. 61 PSC Pole, 8.5 Mt. long 550 Kg. No. 1202 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 723 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 484 Composite Polymeric 11 kV Pin Insulator No. 2885 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 144.006 Tension Clamp for Raccoon No. 1447 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 20

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 60

9 HT Guy Insulator No. 6010 GI Stay wire 7/3.15 mm Kg. 480

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 240

12 GI wire 6 SWG for Earthing Kg. 60

Page 3 of 33

Page 133: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

13 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 2414 Jointing Sleeve for Raccoon No. 1815 PG Clamp for Raccoon No. 14416 AI. Binding Wire (10 SWG.) Kg. 3017 Pole Clamp of GI flat (50x6) mm No. 9618 GI Barbed Wire for anticlimbing device Kg. 24019 11 KV Danger Plate (1.6 mm thick) No. 12020 GI Nuts & Bolts with GI washer (Assorted) Kg. 180B1 11 KV Overhead Line Crossing - Line to line / Road: Set 61 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 122 GI wire 8 SWG for cross lacing as per T.S Kg. 603 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 1204 GI 'I' Hook No. 245 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 12

Page 4 of 33Page 4 of 33

Page 134: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works -

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 1

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Dhubri Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DHB

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 33

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 1

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 2

2

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 2

Page 5 of 33

Page 135: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

3

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication asper IS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of worksand approved drawings..

MT 15

4

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 5

Page 6 of 33

4

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 5

5

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 1

6

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4

7

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

Page 6 of 33

Page 136: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

8

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector EnergyMeter

No 4

9

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 3

10

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 9

Page 7 of 33

10

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 9

1136 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

6

1236 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

13

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2

14

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as pertechnical specifications, approved drawings and scope of the works.

No 5

Page 7 of 33

Page 137: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

15

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 1

16

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 4

179kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

Page 8 of 33

179kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

189kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

8

19

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector EnergyMeter

No 1

20

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

21

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(With Earth Blade)

Set 4

Page 8 of 33

Page 138: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

22

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 8

23

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2.0

24

12kV, 800A, 25kA for 3 sec, 3-Phase, 3 Pin type, Horizonal/VerticalMounting type (as desired by DISCOM), Gang Operated, AB Switch, alongwith support insulators, Base Channel, down pipe, Arching Horns etc. and allcomplete accessories as per technical specifications, scope of works andapproved drawings

Set 5.0

Page 9 of 33

24

12kV, 800A, 25kA for 3 sec, 3-Phase, 3 Pin type, Horizonal/VerticalMounting type (as desired by DISCOM), Gang Operated, AB Switch, alongwith support insulators, Base Channel, down pipe, Arching Horns etc. and allcomplete accessories as per technical specifications, scope of works andapproved drawings

Set 5.0

25

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuitbreaker along with 12 kV, 1-Phase, 600-300/5-5-5 3 Nos indoor typeCurrent Transformer, indoor mounting type control panel for Transformerbreaker, and required accessories, bi-metallic clamps, A-meter, volt-meter,3-phase electronic energy meter, Relay & accessories complete fortransformer breaker protection as per technical specifications, approveddrawings and scope of works.

No 2

26

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuitbreaker along with 12 kV, 1-Phase, 300-150/5-5 3 Nos indoor type CurrentTransformer, indoor mounting type control panel for Feeder protection,and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phaseelectronic energy meter, Relay & accessories complete for feeder breakerprotection as per technical specifications, approved drawings and scope ofworks.

No 4

27

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuitbreaker along with 12 kV, 1-Phase, 600-300/5-5 3 Nos indoor type CurrentTransformer, indoor mounting type control panel for Bus coupler, andrequired accessories, bi-metallic clamps, A-meter, volt-meter, 3-phaseelectronic energy meter, Relay & accessories complete as per specificationsfor bus coupler protection

No 1

Page 9 of 33

Page 139: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

2812 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core Indoor type PotentialTransformer along with required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set 2

29

Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etcas required as per technical specifications, approved drawings and scope ofthe works. 1Cx 300 sqmm size

Mtr 400

30

Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etcas required as per technical specifications, approved drawings and scope ofthe works. 1Cx 185sqmm size

Mtr 800

31

Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc. asper technical specifications, approved drawings and scope of the works. 1Cx300 sqmm size

Set 8

Page 10 of 33

31

Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc. asper technical specifications, approved drawings and scope of the works. 1Cx300 sqmm size

Set 8

32

Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc. asper technical specifications, approved drawings and scope of the works. 1Cx185sqmm size

Set 16

33

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00mm (200 mm² Al. Area) - Panther

Km 1

34

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including their terminationmaterials like glands, lugs, tagging etc. as per technical specifications,approved drawings and scope of the work.

Mtr 200

35

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 4900

36

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 5900

Page 10 of 33

Page 140: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

37Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 6

38Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 2

39Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 2

40Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0

41

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,RCC cover, placed on GI frame, bantonide powder and other accessoriescomplete as per technical specification. (for Power Transformer Neutral,Station Transformer Neutral and Lightening Arresters direct earthing)

No 50

Page 11 of 33

41

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,RCC cover, placed on GI frame, bantonide powder and other accessoriescomplete as per technical specification. (for Power Transformer Neutral,Station Transformer Neutral and Lightening Arresters direct earthing)

No 50

42

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 2

43

Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 2

4433 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

60

4511 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

108

Page 11 of 33

Page 141: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

46

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 2

47110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 2

48

External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 3

Page 12 of 33

48

External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 3

49 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 3

50

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 2

51

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 2

B. New 33 KV Lines

112 M long steel Tubular poles with welded steel base plate of Designation540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line asper technical specification, approved drawings and scope of work.

No 80

2

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 3.23

Page 12 of 33

Page 142: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

3 GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 0.32

4

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire completeas per technical specification, approved drawings and scope of work.

Set 320

5100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 80

6 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.16

733 KV polymer Disc insulator 70 KN along with suitable hardware fittingsasper technical specification, approved drawings and scope of work

Set 192

Page 13 of 33

733 KV polymer Disc insulator 70 KN along with suitable hardware fittingsasper technical specification, approved drawings and scope of work

Set 192

8 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 384

9

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 13.2

10

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 4.00

C New 11 KV Lines

18.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 120

2

Galvanized pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials shown in BOQ for over headstructures as per technical specification, approved drawings and scope ofwork.

MT 2.73

3 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.18

Page 13 of 33

Page 143: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 60

5Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsasper technical specification, approved drawings and scope of work.

Set 144

6 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 288

7100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 24

Page 14 of 33

7100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 24

8 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.06

9

AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 19.8

10

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 6

Total Ex-works

Page 14 of 33

Page 144: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

New 33/11 KV Substation Works (Excluding civil works)A. 33/11 KV Substation Works -

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Dhubri Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DHB

Page 15 of 33

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 2

2100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 2

Page 15 of 33

Page 145: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

3

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15

4

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

Nos 5

5

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Sets 1

Page 16 of 33

5

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Sets 1

6

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Sets 4

7

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

8

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 4

9

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 3

Page 16 of 33

Page 146: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

10

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 9

1136 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

6

1236 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

13

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

14

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

Page 17 of 33

14

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

15

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

16

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

179kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

189kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

8

19

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 17 of 33

Page 147: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

20

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

21

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

22

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 8

23

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2.0

Page 18 of 33

23

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2.0

24

12kV, 800A, 25kA for 3 sec, 3-Phase, 3 Pin type, Horizonal/Vertical Mounting type (asdesired by DISCOM), Gang Operated, AB Switch, along with support insulators, BaseChannel, down pipe, Arching Horns etc. and all complete accessories as per technicalspecifications, scope of works and approved drawings

Set 5.0

25

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 600-300/5-5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Transformer breaker, and required accessories, bi-metallic clamps, A-meter, volt-meter,3-phase electronic energy meter, Relay &accessories complete for transformer breaker protection as per technical specifications,approved drawings and scope of works.

No 2

26

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 300-150/5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Feeder protection, and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay &accessories complete for feeder breaker protection as per technical specifications,approved drawings and scope of works.

No 4

27

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 600-300/5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Bus coupler, and required accessories, bi-metallicclamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay & accessoriescomplete as per specifications for bus coupler protection

No 1

2812 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core Indoor type Potential Transformeralong with required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set 2

Page 18 of 33

Page 148: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

29Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,including their termination materials like glands, lugs, tagging etc as required as pertechnical specifications, approved drawings and scope of the works. 1Cx 300 sqmm size

Mtr 400

30Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,including their termination materials like glands, lugs, tagging etc as required as pertechnical specifications, approved drawings and scope of the works. 1Cx 185sqmm size

Mtr 800

31Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 300 sqmm size

Set 8

32Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 185sqmm size

Set 16

33ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 1

Page 19 of 33

33ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 1

343.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 200

354 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4900

367 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 5900

37Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 6

38Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 2

39Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 2

40Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0

Page 19 of 33

Page 149: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

41

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 50

42

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 2

43

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 2

44 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

60

Page 20 of 33

44 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

60

4511 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.Set ofthree

108

46

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 2

47110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 2

48

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 3

49 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 3

50

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 2

51

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 2

B. New 33 KV Lines

Page 20 of 33

Page 150: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

112 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 80

2

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 3.23

3 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 0.32

4

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 320

5100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 80

Page 21 of 33

5100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 80

6 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.16

7 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 192

8 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 384

9

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 13.2

10Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 4.00

C New 11 KV Lines

18.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 120

2Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 2.73

3 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.18

Page 21 of 33

Page 151: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

4Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 60

5 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 144

6 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 288

7100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 24

8 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.06

9

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 19.8

Page 22 of 33

9

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 19.8

10

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 6

Page 22 of 33

Page 152: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A 33/11 KV Grid Substation worksA-I 33/11 KV Grid Substation works -

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soilprofile and necessary soil parameters of sub-station site & recommendations ofsoil mechanic engineer regarding foundation depth of defferent type of footingswith size including contour survey etc. as per Technical Specification.

PERS/S

2

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DHB

(Schedule of rates and prices)Rural Electrification works in Dhubri Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian Rupees

Page 23 of 33

1.00

Detail sub-soil investigation report about specific information about the soilprofile and necessary soil parameters of sub-station site & recommendations ofsoil mechanic engineer regarding foundation depth of defferent type of footingswith size including contour survey etc. as per Technical Specification.

PERS/S

2

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 1000

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 2800

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works: 2.5 MVA with offload / on load tap changer

No 1

5.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 2

6.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 2

Page 23 of 33

Page 153: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 5

8.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 5

9.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and asper Technical Specification, approved Drawing & Scope of works

MT 15.0

Page 24 of 33

9.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and asper Technical Specification, approved Drawing & Scope of works

MT 15.0

10.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 440

Page 24 of 33

Page 154: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

11.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 240

12.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 260

Page 25 of 33

12.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 260

13.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 200

14.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 100

15.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 2

B (Ib) Substation Electrical works

Page 25 of 33

Page 155: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 2.5 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 1

2.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 2

Page 26 of 33

2.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 2

3.00Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,aluminium would outdoor type Distribution Transformer (Station Transformer) asper Technical Specification, approved Drawing & Scope of works

Set 2

33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 5

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

5

Page 26 of 33

Page 156: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 4

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 12

Page 27 of 33

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 4

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 12

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

7

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 5

Page 27 of 33

Page 157: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 5

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

Page 28 of 33

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

11

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 12

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

Page 28 of 33

Page 158: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

8.00

Design, construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Transformer Protection Breaker Panel along with 12 kV, 1-Phase, 25kAfor 3 seconds, 600- 300/5-5-5 A and 300-150/5-5, indoor type CurrentTransformer along with control and relay panel consisting of A-meter, volt-meter,Relay &amp; accessories complete cabling between VCB and indoor control paneland required accessories complete as per approved drawings, technicalspecifications and scope of the work,

NO 2

9.00

Design,construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Feeder Protection Breaker Panel along with 12 kV, 1-Phase, 25kA for 3seconds, 600- 300/5-5-5 A and 300-150/5-5, indoor type Current Transformeralong with control and relay panel consisting of A-meter, volt-meter, Relay&amp; accessories complete cabling between VCB and indoor control panel andrequired accessories complete as per approved drawings, technical specificationsand scope of the work,

No 4

10.00

Design, construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Bus Coupler Panel along with 12 kV, 1-Phase, 25kA for 3 seconds, 600-300/5-5-5 A and 300-150/5-5, indoor type Current Transformer along withcontrol and relay panel consisting of A-meter, volt-meter, Relay &; accessoriescomplete cabling between VCB and indoor control panel and required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

NO 1

Page 29 of 33

9.00

Design,construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Feeder Protection Breaker Panel along with 12 kV, 1-Phase, 25kA for 3seconds, 600- 300/5-5-5 A and 300-150/5-5, indoor type Current Transformeralong with control and relay panel consisting of A-meter, volt-meter, Relay&amp; accessories complete cabling between VCB and indoor control panel andrequired accessories complete as per approved drawings, technical specificationsand scope of the work,

No 4

10.00

Design, construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Bus Coupler Panel along with 12 kV, 1-Phase, 25kA for 3 seconds, 600-300/5-5-5 A and 300-150/5-5, indoor type Current Transformer along withcontrol and relay panel consisting of A-meter, volt-meter, Relay &; accessoriescomplete cabling between VCB and indoor control panel and required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

NO 1

11.00Installation, testing, commissioning of 3-phase 11 KV Indoor PotentialTransformers of rating 11/110 Volts as per technical specifications and drawings,

Set ofthree

2

12.00 Erection, testing and Commissioning of 12 KV, 600 A, 3-pole AB Switch as perTechnical Specification, approved Drawing & Scope of works.

Set 5

13.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx300 sqmm

mtr 400

14.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx185 sqmm

mtr 800

15.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.8

16.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 200

Page 29 of 33

Page 159: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

17.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 6.0

18.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 2.0

19.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 2.0

20.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.4

Page 30 of 33

20.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.4

21.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 50

22.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 2

23.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 2

Page 30 of 33

Page 160: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

24.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 2

25.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with fullwave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDBas per approved drawings, technical specifications and scope of the work

Set 2

26.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 3

Page 31 of 33

26.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 3

27.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 2

A Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 4.00

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 24

Page 31 of 33

Page 161: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 56

4.01

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 3.23

5.01

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 320

Page 32 of 33

5.01

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 320

6.01Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 384

7.01Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 192

8.01

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

4.00

9.01

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 80

10.01

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 4.00

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 6.00

Page 32 of 33

Page 162: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 36

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 84

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channelcross arm, angle, flats and all other GI materials for over head structures.

MT 2.73

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 24

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 60

Page 33 of 33

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 24

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 60

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 288

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 144

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

6.00

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 6.00

Page 33 of 33

Page 163: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT

NewS/S,1x5

MVA Sasoni(Dibrugarh)

Augmentation of

KhanikorS/S at

Dibrugarh

Augmentation of

TengakhatS/S at

Dibrugarh

TotalQuantity

1 2 3 4 5 6 7=(4+5+6)

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 12 Boundary wall inculing Gate R/Mt 220 220

3Construction of Assam Type control room building with bestquality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120

4

Water supply: Deep well with 1 HP motor- Pump,Overheadwater resurvior capacity 2x500 Ltr over the GI staging withnecesssary pipeline with connection,stand & power connectionappliances.

set 1 1

5 Approach road , 4.0 Mtr width Mtr 50 506 Drainage System Mtr 100 1007 Foundation of Pad for 33/11KV power transformer No 1 1 1 38 Foundation of Pad for 33/.433 KV power transformer No 1 1

9 Const. of Cable Trenches as per specification with followingsizes : -

0

(a) Width 600mm x Depth . RM 150 100 100 350

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

Sq Mtr. 1200 400 400 2000

11 Earth Filling CM 3900 390012 Sign Board, size: 4 feetx3 feet No 1 1 1 3

BOQ: Construction of 33/11KV New S/S within the Dibrugarh District under DDUGJY-II/XII Plan Scheme.

EQUIPMENT & MATERIALS FOR CONSTRUTION OF

ASSAM POWER DISTRIBUTION COMPANY LIMITED

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DIB

STANDARD BILL OF MATERIALS (as per site requirement)

Rural Electrification works in Dibrugarh Project in Assam under DDUGJY Phase-II (REDB works)

Page 1 of 30

11 Earth Filling CM 3900 390012 Sign Board, size: 4 feetx3 feet No 1 1 1 3

13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1 1 3

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG,ABB, Siemens, Schneider make

Nos. 2 1 1 4

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 1 1 1 3

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Station Type

Set 3 1 1 5

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1

20 33 KV ,1250 Amp Isolator with earth blade Set 2 221 33 KV ,1250 Amp Isolator without earth blade Set 5 1 1 7

22 33KV Transformer Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1 1 3

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1

24 33 KV Potential Transformer Set 1 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferablyCG, ABB, Siemens, Schneider make

No. 5 3 3 11

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 2 2 8

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 1 1 1 3

28 11 Kv Current Transformer 600-300/5-5-5A with MarshillingBox and GI Structure

Set 1 1 1 3

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 2 2 8

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 2 2 8

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 8 2 2 12

37 11 KV Out door Potential Transformer Set 2 1 1 438 11 KV LA Line Type (set of 3 units) Set 4 2 2 839 11 KV LA Station Type (set of 3 units) Set 1 1 1 3

EQUIPMENT & MATERIALS FOR CONSTRUTION OF

Page 1 of 30

Page 164: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT

NewS/S,1x5

MVA Sasoni(Dibrugarh)

Augmentation of

KhanikorS/S at

Dibrugarh

Augmentation of

TengakhatS/S at

Dibrugarh

TotalQuantity

1 2 3 4 5 6 7=(4+5+6)

41 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 1 342 Battery charger etc. No. 1 1 1 349 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4100 2200 2200 850050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800 1200 1200 5200

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,PVC insulated and PVC sheathed cable

Mtr 100 100 100 300

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 1553 11 KV Gantry Structure Set 1 1 255 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 1 356 Distrbutiob Box Nos. 1 1 1 357 LTACDB ,DCDB Etc. Set 1 1

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3 3 9b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 1 3c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 1 3d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.2 0.659 40 mm dia,3000 mm length GI Earth Pipe No 25 25 25 7560 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.4 1.2

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30 30 90

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 54 162

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1 1 3

Page 2 of 30

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1 1 3

65

Substation Tools and Plants like megger, earth tester,Multimeter, Tong tester, Box-spanners, D-spanners, screwdrivers, earthing rods, earth mat etc as required as per scope ofwork.

Set 1 1

66 New 33&11 KV Line Tingkhong SSa 33 KV Line Km 15 15b 11 KV Line Km 18 18

Page 2 of 30

Page 165: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

A New 33 kV Line Ckt.Km.

15.00

1 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 3002 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 1203 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 2704 Jam Clamp of GI Flat 65x6 mm Pair 7805 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 1806 33 KV Polymeric Pin Insulator No. 14407 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 7208 Tension Clamp for Wolf Conductor No. 3609 AAA Wolf Conductor (19/3.40 mm) Km. 49.50

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 150

11 Guy Insulator (HT) No. 30012 Stay Wire 7/4.0 mm Kg 1200

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 900

Rural Electrification works in Dibrugarh Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Dibrugarh District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DIB

Page 3 of 30

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 900

14 Jointing Sleeve for Wolf No. 4515 PG Clamp for Wolf (Alcon 80) No. 36016 Al. Binding Wire (10 SWG.) Kg 9017 GI Nuts & Bolts (assorted) Kg 120018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 60019 33 KV Danger Plate (1.6 mm thick) No. 30020 Barbed Wire Kg 60021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 30022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 300A1 33 KV Overhead Line Crossing - Line to line / Road: Set 151 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 302 GI wire 8 SWG for cross lacing as per T.S Kg. 1503 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 3004 GI 'I' Hook No. 605 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 30

B New 11 kV Line Ckt.Km.

18.00

1 PSC Pole, 8.5 Mt. long 550 Kg. No. 3602 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 2163 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 1444 Composite Polymeric 11 kV Pin Insulator No. 8645 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 4326 Tension Clamp for Raccoon No. 4327 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 59.40

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 180

9 HT Guy Insulator No. 180

Page 3 of 30

Page 166: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

10 GI Stay wire 7/3.15 mm Kg. 1440

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 720

12 GI wire 6 SWG for Earthing Kg. 18013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 7214 Jointing Sleeve for Raccoon No. 5415 PG Clamp for Raccoon No. 43216 AI. Binding Wire (10 SWG.) Kg. 9017 Pole Clamp of GI flat (50x6) mm No. 28818 GI Barbed Wire for anticlimbing device Kg. 72019 11 KV Danger Plate (1.6 mm thick) No. 36020 GI Nuts & Bolts with GI washer (Assorted) Kg. 540B1 11 KV Overhead Line Crossing - Line to line / Road: Set 181 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 362 GI wire 8 SWG for cross lacing as per T.S Kg. 1803 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 3604 GI 'I' Hook No. 725 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 36

Page 4 of 30Page 4 of 30

Page 167: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 3

All prices in Indian RupeesBidder's Name & Address:New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Dibrugarh Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DIB

Page 5 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 3

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 3

3.0011 KV Bus Bar with 10 Nos 9.75 meter long PSC Pole Channel, cross arm,

back clamps, insulator with hardware etc all complete as per technicalspecifications, scope of works and approved drawings.

Set 2

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 15

Page 5 of 30

Page 168: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker, supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Transformer & feeder)

Nos 4

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Feeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 3

Page 6 of 30

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 3

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For 33 kV feeder VCB with Static Tri-Vector EnergyMeter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 7

Page 6 of 30

Page 169: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

5

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.

No 11

Page 7 of 30

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.

No 11

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works. (for Transformer)

Set 3

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 8

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

8

Page 7 of 30

Page 170: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessoriescomplete as per specifications for transformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 3

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 8

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 8

Page 8 of 30

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 8

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 12

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

4

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200 mm²Al. Area) - Panther

Km 1.2

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 300

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 5200

Page 8 of 30

Page 171: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 8500

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 9

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 3

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25 x 6 mm Galvanized GI flat (risers)

MT 3

Page 9 of 30

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25 x 6 mm Galvanized GI flat (risers)

MT 3

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 0.6

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories completeas per technical specification. (for Power Transformer Neutral, StationTransformer Neutral and Lightening Arresters direct earthing)

No 75

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangementsetc as per technical specifications, approved drawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 3

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

90

Page 9 of 30

Page 172: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

162

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 3

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 3

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 3

Page 10 of 30

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 3

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 3

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Roundand D-spanners with various range, screw drivers with various size one each,earthing rods, etc as required as per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as pertechnical specification, approved drawings and scope of work.

No 300

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels,back clamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm),GI flats (65x8mm) of given sizes for over head structures as per technicalspecification, approved drawings and scope of work.

MT 12.07

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work.

MT 1.2

New 33 KV Lines

Page 10 of 30

Page 173: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete asper technical specification, approved drawings and scope of work.

Set 1200

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 300

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.6

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work

Set 720

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 1440

Page 11 of 30

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 1440

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead line andjumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al.alloy Area 173 sqmm ) - Wolf

km 49.5

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG& 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mmlong with nuts & bolts.

Set 15

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 360

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,angle, flats and all other GI materials shown in BOQ for over head structuresas per technical specification, approved drawings and scope of work.

MT 8.18

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.54

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts,2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15mm GI stranded wire etc as required as per technical specification, approveddrawings and scope of work.

Set 180

New 11 KV Lines

Page 11 of 30

Page 174: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 432

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 864

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Saltand other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 72

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.18

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 59.4

Page 12 of 30

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 59.4

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 18

Total Ex-works

Page 12 of 30

Page 175: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 3

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Dibrugarh Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DIB

Page 13 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 3

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 3

3.0011 KV Bus Bar with 10 Nos 9.75 meter long PSC Pole Channel, cross arm, back clamps,

insulator with hardware etc all complete as per technical specifications, scope of worksand approved drawings.

Set 2

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

Nos 4

Page 13 of 30

Page 176: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Sets 3

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

Page 14 of 30

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 7

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

5

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

Page 14 of 30

Page 177: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 11

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 3

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 8

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

Page 15 of 30

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

8

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 3

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 8

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 8

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 12

Page 15 of 30

Page 178: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

4

36.00ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 1.2

37.003.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 300

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 5200

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 8500

Page 16 of 30

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 8500

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 9

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 3

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 3

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.6

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 75

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

Page 16 of 30

Page 179: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 3

47.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

90

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.Set ofthree

162

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 3

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 3

Page 17 of 30

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 3

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 3

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 3

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 300

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 12.07

New 33 KV Lines

Page 17 of 30

Page 180: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 1.2

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 1200

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 300

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.6

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 720

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 1440

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 49.5

Page 18 of 30

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 49.5

10.00Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 15

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 360

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 8.18

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.54

4.00Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 180

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 432

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 864

New 11 KV Lines

Page 18 of 30

Page 181: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 72

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.18

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 59.4

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 18

Total Ex-works

Page 19 of 30

Total Ex-works

Page 19 of 30

Page 182: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil profile

and necessary soil parameters of sub-station site & recommendations of soil

mechanic engineer regarding foundation depth of defferent type of footings with

size including contour survey etc. as per Technical Specification.

PER S/S 1

Schedule-3

All prices in Indian Rupees

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DIB

(Schedule of rates and prices)Rural Electrification works in Dibrugarh Project in Assam under DDUGJY Phase-II (REDB works)

Page 20 of 30

1.00

Detail sub-soil investigation report about specific information about the soil profile

and necessary soil parameters of sub-station site & recommendations of soil

mechanic engineer regarding foundation depth of defferent type of footings with

size including contour survey etc. as per Technical Specification.

PER S/S 1

2.00

Earth work in PSS site for raising low site with approved soil obtained from outsideby truck carriage and filling in layers not more than 150 mm thick,wateringramming etc. complete as directed and specified including payment of landcompensation,forest royalty,sale tax and other duties and taxes as may benecessary.

CuMtr 3900

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5 Cmthickness including supply of materials,spreading, Leveling etc. and labour as perdirection.

Sq. m 2000

5.00

Design and construction of foundation for following power transformer consideringoriginal equipment manufacturer recommendations and as per soil & siterequirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with off load/ on load tap changer

No 3

7.00

Design and construction of foundation for Station Service transformer as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 3

Page 20 of 30

Page 183: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 4

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 11

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as per

Technical Specification, approved Drawing & Scope of works

MT 15

Page 21 of 30

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as per

Technical Specification, approved Drawing & Scope of works

MT 15

11.00

Fabrication and Erection of Gantry structures using PSC Pole, GI channel, GI angleand GI flat of various sizes including GI nuts & bolts, etc as required as per soil &site requirment and as per Technical Specification, approved Drawing & Scope ofworks

Set 2

12.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footing includingpreparation of base by providing soling and 10 cm PCC and plastering skinting etc.including supplying ,fitting and fixing barbed wire on top of brick boundary wallwith eight strands of barbed wire 12 SWG fitting to Y cross arm at 2.5 m apartincluding supplying fitting and fixing with galvanized staples 38mm x 38mm x 3mm. Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in all posts. the verticaldistence from top of boundary wall to the top of Y cross arm is 600 mm,3 Nos ofbarbed wire should be fitted in each arm of the Y cross arm & 2 nos. in strraightportion including fabrication,errection & painting of Y cross arm with anticorrosiveready mixed and aluminium paint complete including straightining and tightening ofbarbed wire as directed and instllation of sliding steel gate at the entrance of S/Sboundary wall including supply of materials,painting and labour as per technicalspecification,approved drawing and scope of works.

R/Mtr 220

Page 21 of 30

Page 184: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

13.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 120

Page 22 of 30

13.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 120

14.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide, requireddepth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop, cablesupporting angles including Labour, Reinforcement Steel, MS Angles, Flats, SteelFrame Work, Excavation etc, all complete as per Technical Specification, approvedDrawing & Scope of works.

R/Mtr 350

15.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80 mtr.height, 45 cm bottom width including preparation base by providing soling and10cm PCC and plastering skinting etc. for easy drainage system inside the sub-station premises including supply of all meterials and labour etc. as per TechnicalSpecification, approved Drawing & Scope of works.

R/Mtr 100

16.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

17.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manhole coverwith locking and cleaning arrangement including providing pads of size as requiredfor inlet and outlet pipe complete including fitting and fixing all materials and filterto get potable water as per approved drawing and specification.

SET 1

A(Ib) Substation Electrical works

Page 22 of 30

Page 185: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, CuWound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 sets of50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring/ cabling, cable supporting tray on the body, transformer wheels, bushing etc asper Technical Specification, approved Drawing & Scope of works

No 3

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 3

A(Ic) 33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 4

Page 23 of 30

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 4

2.00

Design and construction of foundation (as per approved drawings), erection, testingand commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along with junctionbox (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between CT andindoor control panel and required accessories complete as per approved drawings,technical specifications and scope of the work.

Set ofthree

4

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: :: 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

Page 23 of 30

Page 186: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: ::: Power transformer 33 kV VCB with Static Tri-VectorEnergy Meter

No 3

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, Operating Mechanism,Base Channel down Pipe, Jumpering and all required accessories complete as perapproved drawings, technical specifications and scope of the work,

Set 9

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

6

Page 24 of 30

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

6

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including control and power supply cabling, earthing connection using50x6mm GS flat,Jumpering and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

1

A(Id) 11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11kV, Outdoor type Vacuum Circuit breaker along withJumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 11

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 11

Page 24 of 30

Page 187: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Transformer Protection Breaker Panel

Set 3

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 8

Page 25 of 30

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 8

5.00

Design,construction of foundation (as per approved drawings), Erection, testing andCommissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mountingplatform, jumpering from bus bar, earthing connection using 50x6mm GS flat,hardware, etc as required as per approved drawings, technical specifications andscope of the work.

Set ofthree

11

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 20

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including Jumpering, control and power supply cabling, earthing connectionusing 50x6mm GS flat and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

4

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 1.2

Page 25 of 30

Page 188: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 300

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works:::75 x 8 mm MS flat for ground mat

MT 9

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 3

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 3

Page 26 of 30

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 3

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.6

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm long GIpipe earth electrode by providing test link, RCC pit, RCC cover, placed on GI frame,bentonite powder and other accessories complete as per approved drawings,technical specifications and scope of the work for power transformer neutral,station transformer neutral, lightening arresters direct earthing.

Set 75

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutralvoltmeter, three phase ammeter and Selector switches, 200 Amps TPN switch fuseunit as incomer, 32 Amps TPN switches as outgoing feeders suited for number ofcontrol panels, nos of VCB kiosk panel, having 20% spare outgoing feeders, byproviding MS angle 50x50x6 mm structure, cement concrete foundation etc as pertechnical specifications, approved drawings and scope of works.

No 1

Page 26 of 30

Page 189: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 ASP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1 No20 A Industrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specifications andapproved drawings,

No 3

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multi strandcable, terminal connectors, &amp; all other accessories and connectors as per asper approved drawings, technical specifications and scope of the work,

Set 3

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V, 40

Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full wave

rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per

approved drawings, technical specifications and scope of the work

Set 3

Page 27 of 30

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V, 40

Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full wave

rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per

approved drawings, technical specifications and scope of the work

Set 3

19.00

Erection, testing and commissioning of External electrification works of substationincluding area lighting by 6 No, 12m high steel tubular lighting masts, 2x90 wattsLED flood light fittings on each mast, Junction boxes of the fittings, area lightingpower distribution board, 2 nos. 3 Phase 63 Amp power receptacles, tube wellpower supply, etc as required by laying power cables in underground/aboveground/trenches, construction of foundations for receptacles, distribution boardsetc as required as per approved drawings, specifications and scope of work.

Set 3

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipment comprisesof Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of 4.5Kg Capacityfor Control Room and CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard and 3 Nos. fire buckets of 25 ltr capacity filled with sand and mounted on50x50x6 MS stand duly painted as per Technical Specification, approved Drawing &Scope of works.

SET 1

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 15

Page 27 of 30

Page 190: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope ofwork, approved drawings and specifications for 12 M long steel Tubular poles withwelded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III 1980) anderection of following types of poles for 33 KV overhead line by providing andinstalling danger plate, anti-climbing devices (barbed wire), earthing material (coiland 8SWG GI wire), red oxide & aluminium paint, pole numbering including cementconcrete foundation using cement concreting foundation 1 part cement, 3 partsand, 6 part 40 mm size stone aggregate chips (1:3:6) etc as per scope of work,approved drawings and specifications:

No 90

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blasting isnot required as per scope of work, approved drawings and specifications for 12 Mlong steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KV overheadline by providing and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 210

Page 28 of 30

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blasting isnot required as per scope of work, approved drawings and specifications for 12 Mlong steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KV overheadline by providing and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 210

5.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm, topclamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 12.07

7.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 1200

8.01Erection, testing and commissioning of 33 kV polymer Pin insulator including theirGI hardware fittings as per technical specification, approved drawings and scope ofwork.

Set 1440

8.02Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 720

Page 28 of 30

Page 191: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

10.01

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAAC Wolf Conductor of following sizes includingjointing sleeves, helical formed fittings, jumpering and by providing & erecting PGClamps etc as required as per approved drawings, scope of work and technicalspecifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt. km 15

11.01

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plates onGI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 300

12.00

Erection of guading for line Crossing-Line to line, line to road with items, GI AngleCross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm longwith nuts & bolts.

Set 15

C Erection, testing and Commissioning of New 11 KV lines:

Page 29 of 30

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 18

2.01

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No. 108

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No 252

6.00 Erection of galvanised pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials for over head structures.

MT 8.18

7.01 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GI wirefor earthing,

Set 72

9.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HT stay

guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS

stay rod & 7/10 swg GI stranded wire etc as required by providing boulder packing

as per scope of the work, technical specifications and approved drawings.

Set 180

Page 29 of 30

Page 192: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

10.01Erection, testing and commissioning of 11 kV Polymaric Pin insulator including theirhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 864

10.02Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings and scopeof work.

Set 432

11.00

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAA Raccon Conductor including jointing sleeves,helical formed fittings, jumpering and by fitting PG Clamps etc as required as perapproved drawings, scope of work and technical specifications. (7/3.81 mm, 79.80Sqmm)

Ckt. Km 18

12.00

Excavation, Erection, testing and commissioning of Protective guarding as per RECconstruction standard drawing No A-1 to be provided at locations where 11KV/33KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guy with 7/3.14 mmwire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe1800 mm long, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire,8 SWG wire for cross lacing as per scope of work, approved drawings and technicalspecifications.

Set 18

Total

Page 30 of 30

12.00

Excavation, Erection, testing and commissioning of Protective guarding as per RECconstruction standard drawing No A-1 to be provided at locations where 11KV/33KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guy with 7/3.14 mmwire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe1800 mm long, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire,8 SWG wire for cross lacing as per scope of work, approved drawings and technicalspecifications.

Set 18

Total

Page 30 of 30

Page 193: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT NewS/S,1x5

MVAAthakhelia(Golaghat)

New S/S,1x5MVA

Namgarumora(Golaghat)

NewS/S,1x5

MVANawjan

(Golaghat)

Augmentationof Kamarbandha

at Golaghat(1x5+1x2.5 to

2x5)

Augmentation ofNumaligarh at

Golaghat(1x5+1x2.5 to

2x5)

Augmentationof Sarupathar at

Golaghat

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 1 1 32 Boundary wall inculing Gate R/Mt 220 220 220 660

3Construction of Assam Type control room buildingwith best quality Dyna roof (blue clour) including ,Senitary, Internal electrification etc.complete

Sq.M 120 120 120 360

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Golaghat Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Golaghat District under DDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/GLT

Page 1 of 32

3Construction of Assam Type control room buildingwith best quality Dyna roof (blue clour) including ,Senitary, Internal electrification etc.complete

Sq.M 120 120 120 360

4

Water supply: Deep well with 1 HP motor-Pump,Overhead water resurvior capacity 2x500Ltr over the GI staging with necesssary pipelinewith connection,stand & power connectionappliances.

set 1 1 1 3

5 Approach road , 4.0 Mtr width Mtr 50 50 50 1506 Drainage System Mtr 100 100 100 300

7 Foundation of Pad for 33/11KV power transformer No 1 1 1 3

8 Foundation of Pad for 33/.433 KV powertransformer

No 1 1 1 3

9 Const. of Cable Trenches as per specification withfollowing sizes : -

(a) Width 600mm x Depth . RM 150 150 150 450

10 Gravelling of switch yard, depth 22.5 Cm withcrushed stone size 40 mm

SqMtr.

1200 1200 1200 3600

11 Earth Filling CM 3900 3900 3900 1170012 Sign Board, size: 4 feetx3 feet No 1 1 1 1 1 5

EQUIPMENT & MATERIALS FORCONSTRUTION OF SWITCHYARD13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1 1 1 1 5

Page 1 of 32

Page 194: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT NewS/S,1x5

MVAAthakhelia(Golaghat)

New S/S,1x5MVA

Namgarumora(Golaghat)

NewS/S,1x5

MVANawjan

(Golaghat)

Augmentationof Kamarbandha

at Golaghat(1x5+1x2.5 to

2x5)

Augmentation ofNumaligarh at

Golaghat(1x5+1x2.5 to

2x5)

Augmentationof Sarupathar at

Golaghat

TotalQuantity

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breakerpreferably CG, ABB, Siemens, Schneider make

Nos. 1 2 1 4

14(b)33KV,1250A, 25 KA SF6 Circuit Breaker(GSS)preferably CG, ABB, Siemens, Schneider make

Nos. 1 1 2

15 33 KV Current Transformer (400-200/5-5-5 Ampsfor Power Tr.)

Set 1 1 1 1 4

16 33 KV Current Transformer ( 400-200/5-5A forFeeder)

Set 1 1

17 33 KV Current Transformer ( 400-200/1-1A forFeeder)

Set 1 1 2

1833KV , 10 KA Lightning Arrester with chagremonitor and GI mounting(set of 3 units) StationType

Set 3 3 3 1 1 11

1933KV , 10 KA Lightning Arrester with chagremonitor and GI mounting(set of 3 units) LineType

Set 1 1 1 3

Page 2 of 32

1933KV , 10 KA Lightning Arrester with chagremonitor and GI mounting(set of 3 units) LineType

Set 1 1 1 3

20 33 KV ,1250 Amp Isolator with earth blade Set 2 2 2 621 33 KV ,1250 Amp Isolator without earth blade Set 5 5 5 1 16

22 33KV Transformer Panels preferablyCG,ABB,Siemens,Schneider make

Nos. 1 1 1 3

23 33KV Feeder Panels preferablyCG,ABB,Siemens,Schneider make

Nos. 1 1 1 3

24 33 KV Potential Transformer Set 1 1 1 3

2511KV, Vaccum Circuit Breaker with MarshellingBox.preferably CG, ABB, Siemens, Schneidermake

No. 5 5 5 15

26Control & Relay panel for 11 KV out door FeederVCB preferably CG, ABB, Siemens,Schneider make

No. 4 4 4 12

27Control & Relay panel for 11 KV out doorTransformer VCB preferably CG,ABB,Siemens,Schneider make

No. 1 1 1 3

28 11 Kv Current Transformer 600-300/5-5-5A withMarshilling Box and GI Structure

Set 1 1 1 3

29 11 Kv Current Transformer 300-150/5-5A withMarshilling Box and GI Structure

Set 4 4 4 12

Page 2 of 32

Page 195: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT NewS/S,1x5

MVAAthakhelia(Golaghat)

New S/S,1x5MVA

Namgarumora(Golaghat)

NewS/S,1x5

MVANawjan

(Golaghat)

Augmentationof Kamarbandha

at Golaghat(1x5+1x2.5 to

2x5)

Augmentation ofNumaligarh at

Golaghat(1x5+1x2.5 to

2x5)

Augmentationof Sarupathar at

Golaghat

TotalQuantity

30 11 KV Isolator Double break with earth switchwith GI structure(800A)

Set 4 4 4 12

31 11 KV Isolator Double break without earth switchwith GI structure(800A)

Set 8 8 8 24

37 11 KV Out door Potential Transformer Set 2 2 2 638 11 KV LA Line Type (set of 3 units) Set 4 4 4 1239 11 KV LA Station Type (set of 3 units) Set 1 1 1 1 1 541 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 1 1 1 542 Battery charger etc. No. 1 1 1 1 1 5

49 Control Cable Copper 7 Core 2.5 Sq mm(avg.80m)

Mtr 4100 4100 4100 12300

50 Control Cable Copper 4 Core 2.5 Sqmm(avg.80m)

Mtr 2800 2800 2800 8400

513.5 Core 95 Sq. mm armored, stranded aluminiumconductor, PVC insulated and PVC sheathed cable

Mtr 100 100 100 300

Page 3 of 32

513.5 Core 95 Sq. mm armored, stranded aluminiumconductor, PVC insulated and PVC sheathed cable

Mtr 100 100 100 300

52 Substation G.I.steel structure as per T.S.(33 & 11KV Bus)

MT 15 15 15 45

55 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 1 3

56 Distrbutiob Box Nos. 1 1 1 357 LTACDB ,DCDB Etc. Set 1 1 1 3

58Earthing & Grounding conductor as per ApprovedElectrical Layout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3 3 9b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 1 3c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 1 3d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.2 0.659 40 mm dia,3000 mm length GI Earth Pipe No 25 25 25 7560 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.4 1.2

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30 30 90

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 54 162

Page 3 of 32

Page 196: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT NewS/S,1x5

MVAAthakhelia(Golaghat)

New S/S,1x5MVA

Namgarumora(Golaghat)

NewS/S,1x5

MVANawjan

(Golaghat)

Augmentationof Kamarbandha

at Golaghat(1x5+1x2.5 to

2x5)

Augmentation ofNumaligarh at

Golaghat(1x5+1x2.5 to

2x5)

Augmentationof Sarupathar at

Golaghat

TotalQuantity

63

Fire Fighting Equipment comprises of Four nosDry Chemical Powder Type (6 Kg) for controlroom; Two nos CO2 Type of 4.5Kg Capacity forControl Room,two sets of fire buckets setincluding their stand for Control Room & StationYard and One no. CO2 Type Trolley Mounted of22.5 Kg Capacity for Switch Yard.

Set 1 1 1 3

64 External Electrification at station yard lightingwith 12 Nos lightening 90 Watt LED Lamp .

set 1 1 1 1 1 5

65

Substation Tools and Plants like megger, earthtester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers, earthing rods, earth matetc as required as per scope of work.

Set 1 1 1 3

66 New 33&11 KV Line GolaghatGSS

PanichakuaGSS/SS

SarupatharGSS

Page 4 of 32

66 New 33&11 KV Line GolaghatGSS

PanichakuaGSS/SS

SarupatharGSS

a 33 KV Line Km 20 15 22 57b 11 KV Line Km 10 10 12 32d 11 KV Rly-Xing No 1 1

Page 4 of 32

Page 197: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 57.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 11402 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 4563 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 10264 Jam Clamp of GI Flat 65x6 mm Pair 29645 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 6846 33 KV Polymeric Pin Insulator No. 54727 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 27368 Tension Clamp for Wolf Conductor No. 13689 AAA Wolf Conductor (19/3.40 mm) Km. 188.10

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 570

11 Guy Insulator (HT) No. 114012 Stay Wire 7/4.0 mm Kg 4560

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 3420

Rural Electrification works in Golaghat Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Golaghat District under DDUGJY-II/XII PlanScheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/GLT

Page 5 of 32

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 3420

14 Jointing Sleeve for Wolf No. 17115 PG Clamp for Wolf (Alcon 80) No. 136816 Al. Binding Wire (10 SWG.) Kg 34217 GI Nuts & Bolts (assorted) Kg 456018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 228019 33 KV Danger Plate (1.6 mm thick) No. 114020 Barbed Wire Kg 228021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 114022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 1140A1 33 KV Overhead Line Crossing - Line to line / Road: Set 571 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 1142 GI wire 8 SWG for cross lacing as per T.S Kg. 5703 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 11404 GI 'I' Hook No. 2285 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 114B New 11 kV Line Ckt. Km. 32.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 6402 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 3843 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 2564 Composite Polymeric 11 kV Pin Insulator No. 15365 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 7686 Tension Clamp for Raccoon No. 7687 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 105.60

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 320

9 HT Guy Insulator No. 32010 GI Stay wire 7/3.15 mm Kg. 2560

Page 5 of 32

Page 198: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 1280

12 GI wire 6 SWG for Earthing Kg. 32013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 12814 Jointing Sleeve for Raccoon No. 9615 PG Clamp for Raccoon No. 76816 AI. Binding Wire (10 SWG.) Kg. 16017 Pole Clamp of GI flat (50x6) mm No. 51218 GI Barbed Wire for anticlimbing device Kg. 128019 11 KV Danger Plate (1.6 mm thick) No. 64020 GI Nuts & Bolts with GI washer (Assorted) Kg. 960B1 11 KV Overhead Line Crossing - Line to line / Road: Set 321 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 642 GI wire 8 SWG for cross lacing as per T.S Kg. 3203 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 6404 GI 'I' Hook No. 1285 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 64

Page 6 of 32Page 6 of 32

Page 199: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A 33/11 KV Substation Works1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00

MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 5.00

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Golaghat Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/GLT

All prices in Indian RupeesBidder's Name & Address:

Page 7 of 32

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 5.00

2.00 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 3.00

3.00 Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication asper IS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of worksand approved drawings..

MT 45.00

Page 7 of 32

Page 200: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 4.00

5.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scopeof works and approved drawings (for feeder at GSS))

Nos 2.00

6.00 36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 1.00

Page 8 of 32

6.00 36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 1.00

7.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4.00

8.00 36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scopeof works and approved drawings (for Feeder at GSS)

Sets 2.00

9.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 3.00

Page 8 of 32

Page 201: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

10.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector EnergyMeter

No 3.00

11.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 6.00

12.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 16.00

Page 9 of 32

12.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 16.00

13.00 36 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

11.00

14.00 36 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3.00

15.00 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

3.00

16.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as pertechnical specifications, approved drawings and scope of the works.

No 15.00

Page 9 of 32

Page 202: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

17.00 12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 3.00

18.00 12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 12.00

19.00 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

5.00

Page 10 of 32

19.00 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

5.00

20.00 9kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

12.00

21.00 Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector EnergyMeter

No 3.00

22.00 Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 12.00

23.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(With Earth Blade)

Set 12.00

Page 10 of 32

Page 203: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

24.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 24.00

25.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

6.00

26.00 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00mm (200 Sqmm Al. Area) - Panther

Km 1.20

Page 11 of 32

26.00 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00mm (200 Sqmm Al. Area) - Panther

Km 1.20

27.00 3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including their terminationmaterials like glands, lugs, tagging etc. as per technical specifications,approved drawings and scope of the work.

Mtr 300.00

28.00 4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 8400.00

29.00 7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 12300.00

30.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 9.00

31.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 3.00

32.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 3.00

Page 11 of 32

Page 204: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

33.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.60

34.00 40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,RCC cover, placed on GI frame, bantonide powder and other accessoriescomplete as per technical specification. (for Power Transformer Neutral,Station Transformer Neutral and Lightening Arresters direct earthing)

No 75.00

35.00 415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 3.00

Page 12 of 32

35.00 415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 3.00

36.00 Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 3.00

37.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

90.00

38.00 11 KV, 70 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

162.00

39.00 110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 5.00

40.00 110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 5.00

Page 12 of 32

Page 205: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

41.00 External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 5.00

42.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 2.00

43.00 Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 3.00

44.00 Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 3.00

Page 13 of 32

44.00 Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 3.00

B New 33 KV Lines1.00 12 M long steel Tubular poles with welded steel base plate of Designation

540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line asper technical specification, approved drawings and scope of work.

No 1140.00

2.00 Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 45.84

3.00 GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 4.56

4.00 Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire completeas per technical specification, approved drawings and scope of work.

Set 4560.00

Page 13 of 32

Page 206: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00 100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 1140.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 2.287.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas

per technical specification, approved drawings and scope of workSet 2736.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 5472.00

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 188.10

Page 14 of 32

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 188.10

10.00 Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 57.00

C New 11 KV Lines1.00 8.5 m PSC Poles Support for 11 KV overhead line as per technical

specification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 640.00

2.00 Galvanized pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials shown in BOQ for over headstructures as per technical specification, approved drawings and scope ofwork.

MT 14.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.96

4.00 Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 320.00

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsasper technical specification, approved drawings and scope of work.

Set 768.00

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 1536.00

Page 14 of 32

Page 207: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

7.00 100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 128.00

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.32

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 105.60

10.00 Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 32.00

Page 15 of 32

10.00 Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 32.00

11.00 11 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx185 Sqmm XLPE Armoured Cable (0.125 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

set 1.00

Total Ex-works

Page 15 of 32

Page 208: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9A 33/11 KV Substation Works

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 5.00

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Golaghat Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/GLT

Page 16 of 32

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 5.00

2.00 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 3.00

3.00 Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 45.00

4.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

Nos 4.00

5.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker , supportingstructures, bi-metallic terminal clamps, permanent maintenance platform, marshallingbox etc required as per technical specifications, scope of works and approved drawings(for feeder at GSS))

Nos 2.00

Page 16 of 32

Page 209: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 96.00 36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along with

junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Sets 1.00

7.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Sets 4.00

8.00 36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (for Feeder at GSS)

Sets 2.00

Page 17 of 32

8.00 36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (for Feeder at GSS)

Sets 2.00

9.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 3.00

10.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3.00

11.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 6.00

12.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 16.00

13.00 36 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

11.00

14.00 36 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

3.00

Page 17 of 32

Page 210: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 915.00 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformer

along with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

3.00

16.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 15.00

17.00 12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 3.00

18.00 12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 12.00

Page 18 of 32

18.00 12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 12.00

19.00 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

5.00

20.00 9kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

12.00

21.00 Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 3.00

22.00 Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 12.00

23.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 12.00

Page 18 of 32

Page 211: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 924.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), Gang

Operated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 24.00

25.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

6.00

26.00 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 Sqmm Al. Area) - Panther

Km 1.20

27.00 3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 300.00

Page 19 of 32

27.00 3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 300.00

28.00 4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 8400.00

29.00 7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 12300.00

30.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 9.00

31.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 3.00

32.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 3.00

33.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.60

34.00 40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 75.00

Page 19 of 32

Page 212: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 935.00 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and

Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 3.00

36.00 Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 3.00

37.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

90.00

38.00 11 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

162.00

Page 20 of 32

38.00 11 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

162.00

39.00 110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 5.00

40.00 110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 5.00

41.00 External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 5.00

42.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 2.0043.00 Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,

One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 3.00

44.00 Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 3.00

B New 33 KV Lines

Page 20 of 32

Page 213: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 91.00 12 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS

2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 1140.00

2.00 Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 45.84

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 4.56

4.00 Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 4560.00

5.00 100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 1140.00

Page 21 of 32

5.00 100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 1140.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 2.287.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technical

specification, approved drawings and scope of workSet 2736.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 5472.00

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 188.10

10.00 Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 57.00

C New 11 KV Lines1.00 8.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approved

drawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 640.00

2.00 Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 14.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.96

Page 21 of 32

Page 214: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

TotalFreight &InsuranceCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 94.00 Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nos

turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 320.00

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 768.00

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 1536.00

7.00 100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 128.00

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.32

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 105.60

Page 22 of 32

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 105.60

10.00 Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 32.00

11.00 11 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos (INCLUDINGONE SPARE) 1Cx185 Sqmm XLPE Armoured Cable (0.125 km each) USING 150MM DIA CIPIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT,OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 33 KV LIGHTENING ARRESTORSTATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK including Wayleave/ Supervision Charges payable to Railway Department on actual basis.

set 1.00

Total

Page 22 of 32

Page 215: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PERS/S

3.00

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 11700.00

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/GLT

(Schedule of rates and prices)Rural Electrification works in Golaghat Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian RupeesBidder's Name & Address:

Page 23 of 32

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 11700.00

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 3600.00

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 5.00

5.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 3.00

6.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 6.00

Page 23 of 32

Page 216: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

7.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 15.00

8.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 45.00

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 660.00

Page 24 of 32

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 660.00

10.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 360.00

Page 24 of 32

Page 217: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

11.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 450.00

12.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 300.00

13.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 150.00

14.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 3.00

Page 25 of 32

14.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 3.00

A-Ib Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 5.00

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 3.00

33KV Yard

Page 25 of 32

Page 218: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 6.00

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

7.00

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 3.00

Page 26 of 32

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 3.00

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 3.00

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 22.00

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

14.00

Page 26 of 32

Page 219: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

3.00

11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 15.00

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 15.00

Page 27 of 32

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 15.00

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 3.00

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 12.00

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

17.00

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 36.00

Page 27 of 32

Page 220: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

6.00

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 1.20

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 300.00

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 9.00

Page 28 of 32

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 9.00

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 3.00

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 3.00

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.60

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 75.00

Page 28 of 32

Page 221: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 3.00

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 3.00

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 5.00

Page 29 of 32

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 5.00

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 5.00

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 5.00

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 3.00

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 57.00

Page 29 of 32

Page 222: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 342.00

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 798.00

Page 30 of 32

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 798.00

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 45.84

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 4560.00

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 5472.00

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 2736.00

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

57.00

Page 30 of 32

Page 223: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 1140.00

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 57.00

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 32.00

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 192.00

Page 31 of 32

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 192.00

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 448.00

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 14.54

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 128.00

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 320.00

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 1536.00

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 768.00

Page 31 of 32

Page 224: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

32.00

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 32.00

11.00

Erection Testing & Cmmissioning of 11 KV LINE FOR UNDER GROUND RAILWAYCROSSING BY 4 Nos (INCLUDING ONE SPARE) 1Cx185 Sqmm XLPE ArmouredCable (0.125 km each) USING 150MM DIA CI PIPES (CLASS-I A TYPE) FOR UGCABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT), OUTDOOR HEATSHRINKABLE CABLE JOINTING KITS, 11 KV LIGHTENING ARRESTOR STATIONCLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OFTHE WORK including Way leave/ Supervision Charges payable to RailwayDepartment on actual basis.

Set 1.00

Page 32 of 32

11.00

Erection Testing & Cmmissioning of 11 KV LINE FOR UNDER GROUND RAILWAYCROSSING BY 4 Nos (INCLUDING ONE SPARE) 1Cx185 Sqmm XLPE ArmouredCable (0.125 km each) USING 150MM DIA CI PIPES (CLASS-I A TYPE) FOR UGCABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT), OUTDOOR HEATSHRINKABLE CABLE JOINTING KITS, 11 KV LIGHTENING ARRESTOR STATIONCLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OFTHE WORK including Way leave/ Supervision Charges payable to RailwayDepartment on actual basis.

Set 1.00

Total

Page 32 of 32

Page 225: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

1 2 3 4

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 12 Boundary wall inculing Gate R/Mt 220

3 Construction of Assam Type control room building with best quality Dyna roof (blue clour)including , Senitary, Internal electrification etc.complete

Sq.M 120

4Water supply: Deep well with 1 HP motor- Pump,Overhead water resurvior capacity 2x500Ltr over the GI staging with necesssary pipeline with connection,stand & power connectionappliances.

set 1

5 Approach road , 4.0 Mtr width Mtr 506 Drainage System Mtr 1007 Foundation of Pad for 33/11KV power transformer No 18 Foundation of Pad for 33/.433 KV power transformer No 19 Const. of Cable Trenches as per specification with following sizes : -

(a) Width 600mm x Depth . RM 15010 Gravelling of switch yard, depth 22.5 Cm with crushed stone size 40 mm Sq Mtr. 120011 Earth Filling CM 390012 Sign Board, size: 4 feetx3 feet No 1

ASSAM POWER DISTRIBUTION COMPANY LIMITED

Sl.No. ITEM DESCRIPTION UNIT

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

BOQ: Construction of 33/11KV New S/S within the Hailakandi District under DDUGJY-II/XII Plan Scheme.

New S/S,1x5MVA at

Panchgram(Hailakandi)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/HKD

STANDARD BILL OF MATERIALS (as per site requirement)

Rural Electrification works in Hailakandi Project in Assam under DDUGJY Phase-II (REDB works)

Page 1 of 26

12 Sign Board, size: 4 feetx3 feet No 1

13(a) 33/11KV 5 MVA Power Transformer Nos. 1

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB, Siemens, Schneider make Nos. 1

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 117 33 KV Current Transformer ( 400-200/1-1A for Feeder) Set 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GI mounting(set of 3 units) StationType

Set 3

19 33KV , 10 KA Lightning Arrester with chagre monitor and GI mounting(set of 3 units) LineType

Set 1

20 33 KV ,1250 Amp Isolator with earth blade Set 221 33 KV ,1250 Amp Isolator without earth blade Set 522 33KV Transformer Panels preferably CG,ABB,Siemens,Schneider make Nos. 123 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 124 33 KV Potential Transformer Set 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG, ABB, Siemens, Schneidermake

No. 5

26 Control & Relay panel for 11 KV out door Feeder VCB preferably CG, ABB,Siemens,Schneider make

No. 4

27 Control & Relay panel for 11 KV out door Transformer VCB preferably CG,ABB,Siemens,Schneider make

No. 1

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Box and GI Structure Set 129 11 Kv Current Transformer 300-150/5-5A with Marshilling Box and GI Structure Set 430 11 KV Isolator Double break with earth switch with GI structure(800A) Set 431 11 KV Isolator Double break without earth switch with GI structure(800A) Set 837 11 KV Out door Potential Transformer Set 238 11 KV LA Line Type (set of 3 units) Set 439 11 KV LA Station Type (set of 3 units) Set 141 110 V, 150 AH Lead Acid Battery bank, etc. Set 142 Battery charger etc. No. 149 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 410050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

Page 1 of 26

Page 226: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

1 2 3 4

Sl.No. ITEM DESCRIPTION UNIT

New S/S,1x5MVA at

Panchgram(Hailakandi)

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVCsheathed cable

Mtr 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 1555 Station service transformer, 33/.433KV,100 KVA Nos. 156 Distrbutiob Box Nos. 157 LTACDB ,DCDB Etc. Set 1

58 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3b 50 x 6 mm Galvanized GS flat (risers) MT 1c 25 x 6 mm Galvanized GI flat (risers) MT 1d 25mm dia MS rod 3 m long for earth mat MT 0.259 40 mm dia,3000 mm length GI Earth Pipe No 2560 ACSR Panther Conductor for Bus bar Km 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of 3 nos. 30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of 3 nos. 54

63

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) for controlroom; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and One no. CO2 Type TrolleyMounted of 22.5 Kg Capacity for Switch Yard.

Set 1

64 External Electrification at station yard lighting with 12 Nos lightening 90 Watt LED Lamp . set 1

65Substation Tools and Plants like megger, earth tester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers, earthing rods, earth mat etc as required as per scopeof work.

Set 1

Page 2 of 26

65Substation Tools and Plants like megger, earth tester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers, earthing rods, earth mat etc as required as per scopeof work.

Set 1

66 New 33&11 KV Linea 33 KV Line Km 0.00b 11 KV Line Km 10.00

Page 2 of 26

Page 227: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

A New 33 kV Line Ckt.Km.

0

1 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 02 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 03 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 04 Jam Clamp of GI Flat 65x6 mm Pair 05 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 06 33 KV Polymeric Pin Insulator No. 07 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 08 Tension Clamp for Wolf Conductor No. 09 AAA Wolf Conductor (19/3.40 mm) Km. 0

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 0

11 Guy Insulator (HT) No. 012 Stay Wire 7/4.0 mm Kg 0

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 0

Rural Electrification works in Hailakandi Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Hailakandi District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/HKD

Page 3 of 26

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 0

14 Jointing Sleeve for Wolf No. 015 PG Clamp for Wolf (Alcon 80) No. 016 Al. Binding Wire (10 SWG.) Kg 017 GI Nuts & Bolts (assorted) Kg 018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 019 33 KV Danger Plate (1.6 mm thick) No. 020 Barbed Wire Kg 021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 0A1 33 KV Overhead Line Crossing - Line to line / Road: Set 01 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 02 GI wire 8 SWG for cross lacing as per T.S Kg. 03 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 04 GI 'I' Hook No. 05 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 0

B New 11 kV Line Ckt.Km.

10

1 PSC Pole, 8.5 Mt. long 550 Kg. No. 2002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 1203 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 804 Composite Polymeric 11 kV Pin Insulator No. 4805 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 2406 Tension Clamp for Raccoon No. 2407 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 33

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 100

9 HT Guy Insulator No. 100

Page 3 of 26

Page 228: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

10 GI Stay wire 7/3.15 mm Kg. 800

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 400

12 GI wire 6 SWG for Earthing Kg. 10013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 4014 Jointing Sleeve for Raccoon No. 3015 PG Clamp for Raccoon No. 24016 AI. Binding Wire (10 SWG.) Kg. 5017 Pole Clamp of GI flat (50x6) mm No. 16018 GI Barbed Wire for anticlimbing device Kg. 40019 11 KV Danger Plate (1.6 mm thick) No. 20020 GI Nuts & Bolts with GI washer (Assorted) Kg. 300B1 11 KV Overhead Line Crossing - Line to line / Road: Set 101 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 202 GI wire 8 SWG for cross lacing as per T.S Kg. 1003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2004 GI 'I' Hook No. 405 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20

Page 4 of 26Page 4 of 26

Page 229: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Hailakandi Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/HKD

Page 5 of 26

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 1

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 15

Page 5 of 26

Page 230: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

Nos 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder at GSS)

Sets 1

Page 6 of 26

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder at GSS)

Sets 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For 33 kVfeeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Powertransformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 2

Page 6 of 26

Page 231: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

1

Page 7 of 26

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per technical

specifications, approved drawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

Page 7 of 26

Page 232: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB

(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessories

complete as per specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kV feederVCB with Static Tri-Vector Energy Meter

No 4

Page 8 of 26

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kV feederVCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200 mm²Al. Area) - Panther

Km 0.4

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 100

Page 8 of 26

Page 233: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 2800

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 1

Page 9 of 26

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25 x 6 mm Galvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories completeas per technical specification. (for Power Transformer Neutral, StationTransformer Neutral and Lightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangementsetc as per technical specifications, approved drawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 1

Page 9 of 26

Page 234: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 1

Page 10 of 26

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Roundand D-spanners with various range, screw drivers with various size one each,earthing rods, etc as required as per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 200

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 4.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.3

New 11 KV Lines

Page 10 of 26

Page 235: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts,2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15mm GI stranded wire etc as required as per technical specification, approveddrawings and scope of work.

Set 100

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 240

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 480

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Saltand other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 40

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.1

Page 11 of 26

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.1

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 33

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 10

Total Ex-works

Page 11 of 26

Page 236: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Hailakandi Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/HKD

Page 12 of 26

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

Nos 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Sets 1

Page 12 of 26

Page 237: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (for Feeder at GSS)

Sets 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

Page 13 of 26

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

Page 13 of 26

Page 238: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 14 of 26

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

36.00ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.4

Page 14 of 26

Page 239: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

37.003.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 100

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 2800

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1

Page 15 of 26

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 1

47.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

30

Page 15 of 26

Page 240: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

Page 16 of 26

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 200

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 4.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.3

4.00Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 100

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 240

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 480

New 11 KV Lines

Page 16 of 26

Page 241: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 40

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.1

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 33

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 10

Total Ex-works

Page 17 of 26Page 17 of 26

Page 242: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil profileand necessary soil parameters of sub-station site & recommendations of soilmechanic engineer regarding foundation depth of defferent type of footings withsize including contour survey etc. as per Technical Specification.

PER S/S 1

Schedule-3

All prices in Indian Rupees

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/HKD

(Schedule of rates and prices)Rural Electrification works in Hailakandi Project in Assam under DDUGJY Phase-II (REDB works)

Page 18 of 26

1.00

Detail sub-soil investigation report about specific information about the soil profileand necessary soil parameters of sub-station site & recommendations of soilmechanic engineer regarding foundation depth of defferent type of footings withsize including contour survey etc. as per Technical Specification.

PER S/S 1

2.00

Earth work in PSS site for raising low site with approved soil obtained from outsideby truck carriage and filling in layers not more than 150 mm thick,wateringramming etc. complete as directed and specified including payment of landcompensation,forest royalty,sale tax and other duties and taxes as may benecessary.

CuMtr 3900

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5 Cmthickness including supply of materials,spreading, Leveling etc. and labour as perdirection.

Sq. m 1200

5.00

Design and construction of foundation for following power transformer consideringoriginal equipment manufacturer recommendations and as per soil & siterequirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with off load/ on load tap changer

No 1

7.00

Design and construction of foundation for Station Service transformer as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

Page 18 of 26

Page 243: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 1

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 5

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and as perTechnical Specification, approved Drawing & Scope of works

MT 15

Page 19 of 26

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and as perTechnical Specification, approved Drawing & Scope of works

MT 15

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footing includingpreparation of base by providing soling and 10 cm PCC and plastering skinting etc.including supplying ,fitting and fixing barbed wire on top of brick boundary wallwith eight strands of barbed wire 12 SWG fitting to Y cross arm at 2.5 m apartincluding supplying fitting and fixing with galvanized staples 38mm x 38mm x 3mm. Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in all posts. the verticaldistence from top of boundary wall to the top of Y cross arm is 600 mm,3 Nos ofbarbed wire should be fitted in each arm of the Y cross arm & 2 nos. in strraightportion including fabrication,errection & painting of Y cross arm with anticorrosiveready mixed and aluminium paint complete including straightining and tightening ofbarbed wire as directed and instllation of sliding steel gate at the entrance of S/Sboundary wall including supply of materials,painting and labour as per technicalspecification,approved drawing and scope of works.

R/Mtr 220

Page 19 of 26

Page 244: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

12.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 120

Page 20 of 26

12.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 120

13.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide, requireddepth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop, cablesupporting angles including Labour, Reinforcement Steel, MS Angles, Flats, SteelFrame Work, Excavation etc, all complete as per Technical Specification, approvedDrawing & Scope of works.

R/Mtr 150

14.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80 mtr.height, 45 cm bottom width including preparation base by providing soling and10cm PCC and plastering skinting etc. for easy drainage system inside the sub-station premises including supply of all meterials and labour etc. as per TechnicalSpecification, approved Drawing & Scope of works.

R/Mtr 100

15.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manhole coverwith locking and cleaning arrangement including providing pads of size as requiredfor inlet and outlet pipe complete including fitting and fixing all materials and filterto get potable water as per approved drawing and specification.

SET 1

A (Ib) Substation Electrical works

Page 20 of 26

Page 245: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, CuWound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 sets of50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring/ cabling, cable supporting tray on the body, transformer wheels, bushing etc asper Technical Specification, approved Drawing & Scope of works

No 1

2.00Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,aluminium would outdoor type Distribution Transformer (Station Transformer) asper Technical Specification, approved Drawing & Scope of works

Set 1

A (Ic) 33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 1

Page 21 of 26

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 1

2.00

Design and construction of foundation (as per approved drawings), erection, testingand commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along with junctionbox (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between CT andindoor control panel and required accessories complete as per approved drawings,technical specifications and scope of the work.

Set ofthree

2

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: :: 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

Page 21 of 26

Page 246: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: ::: Power transformer 33 kV VCB with Static Tri-VectorEnergy Meter

No 1

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, Operating Mechanism,Base Channel down Pipe, Jumpering and all required accessories complete as perapproved drawings, technical specifications and scope of the work,

Set 7

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

4

Page 22 of 26

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

4

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including control and power supply cabling, earthing connection using50x6mm GS flat,Jumpering and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

1

A (Id) 11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11kV, Outdoor type Vacuum Circuit breaker along withJumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 5

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 5

Page 22 of 26

Page 247: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 4

Page 23 of 26

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testing andCommissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mountingplatform, jumpering from bus bar, earthing connection using 50x6mm GS flat,hardware, etc as required as per approved drawings, technical specifications andscope of the work.

Set ofthree

5

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 12

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including Jumpering, control and power supply cabling, earthing connectionusing 50x6mm GS flat and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

2

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.4

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100

Page 23 of 26

Page 248: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works:::75 x 8 mm MS flat for ground mat

MT 3

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.2

Page 24 of 26

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.2

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm long GIpipe earth electrode by providing test link, RCC pit, RCC cover, placed on GI frame,bentonite powder and other accessories complete as per approved drawings,technical specifications and scope of the work for power transformer neutral,station transformer neutral, lightening arresters direct earthing.

Set 25

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutralvoltmeter, three phase ammeter and Selector switches, 200 Amps TPN switch fuseunit as incomer, 32 Amps TPN switches as outgoing feeders suited for number ofcontrol panels, nos of VCB kiosk panel, having 20% spare outgoing feeders, byproviding MS angle 50x50x6 mm structure, cement concrete foundation etc as pertechnical specifications, approved drawings and scope of works.

No 1

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 ASP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1 No20 A Industrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specifications andapproved drawings,

No 1

Page 24 of 26

Page 249: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multi strandcable, terminal connectors, &amp; all other accessories and connectors as per asper approved drawings, technical specifications and scope of the work,

Set 1

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V, 40Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full waverectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as perapproved drawings, technical specifications and scope of the work

Set 1

19.00

Erection, testing and commissioning of External electrification works of substationincluding area lighting by 6 No, 12m high steel tubular lighting masts, 2x90 wattsLED flood light fittings on each mast, Junction boxes of the fittings, area lightingpower distribution board, 2 nos. 3 Phase 63 Amp power receptacles, tube wellpower supply, etc as required by laying power cables in underground/aboveground/trenches, construction of foundations for receptacles, distribution boardsetc as required as per approved drawings, specifications and scope of work.

Set 1

Page 25 of 26

19.00

Erection, testing and commissioning of External electrification works of substationincluding area lighting by 6 No, 12m high steel tubular lighting masts, 2x90 wattsLED flood light fittings on each mast, Junction boxes of the fittings, area lightingpower distribution board, 2 nos. 3 Phase 63 Amp power receptacles, tube wellpower supply, etc as required by laying power cables in underground/aboveground/trenches, construction of foundations for receptacles, distribution boardsetc as required as per approved drawings, specifications and scope of work.

Set 1

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipment comprisesof Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of 4.5Kg Capacityfor Control Room and CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard and 3 Nos. fire buckets of 25 ltr capacity filled with sand and mounted on50x50x6 MS stand duly painted as per Technical Specification, approved Drawing &Scope of works.

SET 1

B Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 10.00

2.01

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No. 60

Page 25 of 26

Page 250: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No 140

6.00 Erection of galvanised pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials for over head structures.

MT 4.54

7.01 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GI wirefor earthing,

Set 40

9.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HT stayguy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GSstay rod & 7/10 swg GI stranded wire etc as required by providing boulder packingas per scope of the work, technical specifications and approved drawings.

Set 100

Page 26 of 26

9.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HT stayguy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GSstay rod & 7/10 swg GI stranded wire etc as required by providing boulder packingas per scope of the work, technical specifications and approved drawings.

Set 100

10.01Erection, testing and commissioning of 11 kV Polymaric Pin insulator including theirhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 480

10.02Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings and scopeof work.

Set 240

11.00

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAA Raccon Conductor including jointing sleeves,helical formed fittings, jumpering and by fitting PG Clamps etc as required as perapproved drawings, scope of work and technical specifications. (7/3.81 mm, 79.80Sqmm)

Ckt. Km 10.00

12.00

Excavation, Erection, testing and commissioning of Protective guarding as per RECconstruction standard drawing No A-1 to be provided at locations where 11KV/33KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guy with 7/3.14 mmwire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe1800 mm long, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire,8 SWG wire for cross lacing as per scope of work, approved drawings and technicalspecifications.

Set 10.00

Total

Page 26 of 26

Page 251: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

NewS/S,2x2.5

MVABongaon(

Majuli)

NewS/S,1x5

MVAGabharu(J

orhat)

NewS/S,1x5

MVABhagamukh

(Jorhat)

Augmentation ofGormurS/S) atMajuli

1 2 3 4 5 6 7A New 33/11 KV Substation Works

CIVIL WORKS1 Soil Testing 1 1 12 Boundary wall inculing Gate R/Mt 220 220 220

3Construction of Assam Type control room building with bestquality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120 120

4

Water supply: Deep well with 1 HP motor- Pump,Overheadwater resurvior capacity 2x500 Ltr over the GI staging withnecesssary pipeline with connection,stand & power connectionappliances.

set 1 1 1

5 Approach road , 4.0 Mtr width Mtr 50 50 506 Drainage System Mtr 100 100 1007 Foundation of Pad for 33/11KV power transformer No 2 1 1 18 Foundation of Pad for 33/.433 KV power transformer No 1 1 1

9 Const. of Cable Trenches as per specification with followingsizes : -

(a) Width 600mm x Depth . RM 150 150 150 40

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

Sq Mtr. 1200 1200 1200 400

11 Earth Filling CM 3900 3900 3900

BOQ: Construction of 33/11KV New S/S within the Jorhat District under DDUGJY-II/XII Plan Scheme.

ASSAM POWER DISTRIBUTION COMPANY LIMITED

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/JRT

STANDARD BILL OF MATERIALS (as per site requirement)

Rural Electrification works in Jorhat Project in Assam under DDUGJY Phase-II (REDB works)

Sl.No. ITEM DESCRIPTION UNIT

Page 1 of 33

11 Earth Filling CM 3900 3900 390012 Sign Board, size: 4 feetx3 feet No 1 1 1 1

13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1 113(b) 33/11KV 2.5 MVA Power Transformer Nos. 2

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG,ABB, Siemens, Schneider make

Nos. 2 2 2 1

14(b) 33KV,1250A, 25 KA SF6 Circuit Breaker(GSS) preferably CG,ABB, Siemens, Schneider make

Nos. 1

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 2 1 1 1

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 117 33 KV Current Transformer ( 400-200/1-1A for Feeder) Set 1 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Station Type

Set 4 3 3 1

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1 1

20 33 KV ,1250 Amp Isolator with earth blade Set 2 2 221 33 KV ,1250 Amp Isolator without earth blade Set 6 5 5 1

22 33KV Transformer Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 2 1 1 1

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1 1

24 33 KV Potential Transformer Set 1 1 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferablyCG, ABB, Siemens, Schneider make

No. 6 5 5

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 2 1 1

28 11 Kv Current Transformer 600-300/5-5-5A with MarshillingBox and GI Structure

Set 2 1 1

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4 4

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

Page 1 of 33

Page 252: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

NewS/S,2x2.5

MVABongaon(

Majuli)

NewS/S,1x5

MVAGabharu(J

orhat)

NewS/S,1x5

MVABhagamukh

(Jorhat)

Augmentation ofGormurS/S) atMajuli

1 2 3 4 5 6 7

Sl.No. ITEM DESCRIPTION UNIT

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 9 8 8 2

37 11 KV Out door Potential Transformer Set 2 2 238 11 KV LA Line Type (set of 3 units) Set 4 4 4 239 11 KV LA Station Type (set of 3 units) Set 2 1 1 141 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 142 Battery charger etc. No. 1 1 143 11 KV XLPE Cable 1x300Sq.mm Mtr 20044 11 KV XLPE Cable 1x300 Sq mm Terminate Box(outdoor) No 445 11 KV XLPE Cable 1x300 Sq mm Terminate Box(indoor) No 446 11 KV XLPE Cable 1x185 Sq.mm for 5 feeder Mtr 20047 11 KV XLPE Cable 1x185 Sq mm Terminate Box(outdoor) No 448 11 KV XLPE Cable 1x185 Sq mm Terminate Box(indoor) No 449 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4700 4100 4100 220050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 3400 2800 2800 200

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,PVC insulated and PVC sheathed cable

Mtr 100 100 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 15 15

54 33 KV Gantry Structure Extension Set at Na-kachari

if possible

55 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 156 Distrbutiob Box Nos. 1 1 157 LTACDB ,DCDB Etc. Set 1 1 1

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3 3 1b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 1 0.5c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 1 0.5d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.2 0.2

Page 2 of 33

d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.2 0.259 40 mm dia,3000 mm length GI Earth Pipe No 25 25 25 1060 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.4 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30 30 30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 54 54

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1 1 1

65

Substation Tools and Plants like megger, earth tester,Multimeter, Tong tester, Box-spanners, D-spanners, screwdrivers, earthing rods, earth mat etc as required as per scope ofwork.

Set 1 1 1

66 New 33&11 KV LineGarmur

GSSNa-

Kachari SS Teok GSS

a 33 KV Line Km 20 15 20b 11 KV Line Km 20 10 10

Page 2 of 33

Page 253: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

A New 33 kV Line Ckt.Km.

55.00

1 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 11002 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 4403 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 9904 Jam Clamp of GI Flat 65x6 mm Pair 28605 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 6606 33 KV Polymeric Pin Insulator No. 52807 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 26408 Tension Clamp for Wolf Conductor No. 13209 AAA Wolf Conductor (19/3.40 mm) Km. 181.50

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 550

11 Guy Insulator (HT) No. 110012 Stay Wire 7/4.0 mm Kg 4400

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 3300

Rural Electrification works in Jorhat Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Jorhat District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/JRT

Page 3 of 33

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 3300

14 Jointing Sleeve for Wolf No. 16515 PG Clamp for Wolf (Alcon 80) No. 132016 Al. Binding Wire (10 SWG.) Kg 33017 GI Nuts & Bolts (assorted) Kg 440018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 220019 33 KV Danger Plate (1.6 mm thick) No. 110020 Barbed Wire Kg 220021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 110022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 1100A1 33 KV Overhead Line Crossing - Line to line / Road: Set 551 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 1102 GI wire 8 SWG for cross lacing as per T.S Kg. 5503 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 11004 GI 'I' Hook No. 2205 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 110

B New 11 kV Line Ckt.Km.

40.00

1 PSC Pole, 8.5 Mt. long 550 Kg. No. 8002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 4803 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 3204 Composite Polymeric 11 kV Pin Insulator No. 19205 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 9606 Tension Clamp for Raccoon No. 9607 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 132.00

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 400

9 HT Guy Insulator No. 400

Page 3 of 33

Page 254: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

10 GI Stay wire 7/3.15 mm Kg. 3200

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 1600

12 GI wire 6 SWG for Earthing Kg. 40013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 16014 Jointing Sleeve for Raccoon No. 12015 PG Clamp for Raccoon No. 96016 AI. Binding Wire (10 SWG.) Kg. 20017 Pole Clamp of GI flat (50x6) mm No. 64018 GI Barbed Wire for anticlimbing device Kg. 160019 11 KV Danger Plate (1.6 mm thick) No. 80020 GI Nuts & Bolts with GI washer (Assorted) Kg. 1200B1 11 KV Overhead Line Crossing - Line to line / Road: Set 401 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 802 GI wire 8 SWG for cross lacing as per T.S Kg. 4003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 8004 GI 'I' Hook No. 1605 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 80

Page 4 of 33Page 4 of 33

Page 255: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 2

All prices in Indian RupeesBidder's Name & Address:New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Jorhat Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/JRT

Page 5 of 33

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 2

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 3

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 3

3.00Extention of 33 or 11 KV Bus Bar with 10 Nos SP-76 MS Pole, Channel, crossarm, back clamps, insulator with hardware etc all complete as per technicalspecifications, scope of works and approved drawings.

Set 2

Page 5 of 33

Page 256: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 45

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

Nos 7

Page 6 of 33

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

Nos 7

6.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,

supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for feeder at GSS))

Nos 1

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Feeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 5

Page 6 of 33

Page 257: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder at GSS)

Sets 2

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 3

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 5

Page 7 of 33

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 5

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 6

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 17

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

11

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

3

Page 7 of 33

Page 258: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per technical

specifications, approved drawings and scope of the works.

No 16

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works. (for Transformer)

Set 4

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 12

Page 8 of 33

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 12

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

5

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

14

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB

(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessories

complete as per specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 4

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kV feeder VCBwith Static Tri-Vector Energy Meter

No 12

Page 8 of 33

Page 259: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 12

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 27

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

6

Page 9 of 33

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

6

32.00

Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etc asrequired as per technical specifications, approved drawings and scope of theworks. 1Cx 300 sqmm size

Mtr 200

33.00

Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etc asrequired as per technical specifications, approved drawings and scope of theworks. 1Cx 185sqmm size

Mtr 200

34.00

Cable termination kit suitable for termination in transformer cable box/ breakerpanel/ outdoor 11 KV terminals complete with all accessories etc. as pertechnical specifications, approved drawings and scope of the works. 1Cx 300sqmm size

Set 4

35.00

Cable termination kit suitable for termination in transformer cable box/ breakerpanel/ outdoor 11 KV terminals complete with all accessories etc. as pertechnical specifications, approved drawings and scope of the works. 1Cx185sqmm size

Set 4

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200 mm²Al. Area) - Panther

Km 1.6

Page 9 of 33

Page 260: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 300

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 9200

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 15100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 10

Page 10 of 33

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 10

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 4

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25 x 6 mm Galvanized GI flat (risers)

MT 4

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 0.8

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories completeas per technical specification. (for Power Transformer Neutral, StationTransformer Neutral and Lightening Arresters direct earthing)

No 85

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangementsetc as per technical specifications, approved drawings and scope of works.

Set 3

Page 10 of 33

Page 261: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 3

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

120

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

216

Page 11 of 33

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

216

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 3

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 3

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 4

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 4

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Roundand D-spanners with various range, screw drivers with various size one each,earthing rods, etc as required as per scope of work.

Set 3

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 3

B. New 33 KV Lines

Page 11 of 33

Page 262: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as pertechnical specification, approved drawings and scope of work.

No 1100

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels,back clamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm),GI flats (65x8mm) of given sizes for over head structures as per technicalspecification, approved drawings and scope of work.

MT 44.24

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work.

MT 4.40

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as

per technical specification, approved drawings and scope of work.

Set 4400

Page 12 of 33

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as

per technical specification, approved drawings and scope of work.

Set 4400

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 1100

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 2.20

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work

Set 2640

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 5280

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead line andjumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al.alloy Area 173 sqmm ) - Wolf

km 181.50

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG& 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mmlong with nuts & bolts.

Set 55.00

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 800

New 11 KV Lines

Page 12 of 33

Page 263: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 18.17

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 1.2

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts,2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15mm GI stranded wire etc as required as per technical specification, approveddrawings and scope of work.

Set 400

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 960

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 1920

Page 13 of 33

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 1920

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Saltand other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 160

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.4

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 132.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 40.00

Page 13 of 33

Page 264: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9A. 33/11 KV Substation Works

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 2

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Jorhat Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/JRT

Page 14 of 33

1.01

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 2.5 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 2

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 3

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 3

3.00Extention of 33 or 11 KV Bus Bar with 10 Nos SP-76 MS Pole, Channel, cross arm, backclamps, insulator with hardware etc all complete as per technical specifications, scope ofworks and approved drawings.

Set 2

Page 14 of 33

Page 265: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 45

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

Nos 7

6.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker , supportingstructures, bi-metallic terminal clamps, permanent maintenance platform, marshallingbox etc required as per technical specifications, scope of works and approved drawings(for feeder at GSS))

Nos 1

Page 15 of 33

6.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker , supportingstructures, bi-metallic terminal clamps, permanent maintenance platform, marshallingbox etc required as per technical specifications, scope of works and approved drawings(for feeder at GSS))

Nos 1

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Sets 5

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along with

junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-

metallic clamps, permanent maintenance platform, marshalling box etc required as per

technical specifications, scope of works and approved drawings (for Feeder at GSS)

Sets 2

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 3

Page 15 of 33

Page 266: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 5

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 6

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 17

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

11

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

3

Page 16 of 33

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

11

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

3

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

3

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 16

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 4

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 12

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

5

Page 16 of 33

Page 267: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

14

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 4

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories complete

for feeder breaker protection as per technical specifications, approved drawings and

scope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 12

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 12

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 27

Page 17 of 33

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 12

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 27

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

6

32.00

Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,

including their termination materials like glands, lugs, tagging etc as required as per

technical specifications, approved drawings and scope of the works. 1Cx 300 sqmm size

Mtr 200

33.00

Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,

including their termination materials like glands, lugs, tagging etc as required as per

technical specifications, approved drawings and scope of the works. 1Cx 185sqmm size

Mtr 200

34.00Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 300 sqmm size

Set 4

35.00Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 185sqmm size

Set 4

Page 17 of 33

Page 268: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware

fittings, hardware, T-claimp etc as per technical specifications, approved drawings and

scope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 1.6

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVC

sheathed LT Power Cables including their termination materials like glands, lugs, tagging

etc. as per technical specifications, approved drawings and scope of the work.

Mtr 300

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 9200

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 15100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 10

Page 18 of 33

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 10

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 4

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 4

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.8

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 85

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 3

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 3

Page 18 of 33

Page 269: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

47.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

120

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.

Set ofthree

216

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 3

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 3

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 4

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 4

Page 19 of 33

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 4

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 4

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 3

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 3

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 1100

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 44.24

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 4.40

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 4400

New 33 KV Lines

Page 19 of 33

Page 270: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 1100

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 2.20

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 2640

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 5280

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 181.50

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 55.00

C New 11 KV Lines

Page 20 of 33

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 55.00

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 800

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 18.17

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 1.2

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nos

turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI stranded

wire etc as required as per technical specification, approved drawings and scope of work.

Set 400

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 960

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 1920

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 160

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.4

New 11 KV Lines

Page 20 of 33

Page 271: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 132.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 40.00

Page 21 of 33Page 21 of 33

Page 272: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

A 33/11 KV Grid Substation works

A-I 33/11 KV Grid Substation works - Common for fully outdoor / partlyoutdoor substation

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil profile

and necessary soil parameters of sub-station site & recommendations of soil

mechanic engineer regarding foundation depth of defferent type of footings with

size including contour survey etc. as per Technical Specification.

PER S/S 3

Schedule-3

All prices in Indian Rupees

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/JRT

(Schedule of rates and prices)Rural Electrification works in Jorhat Project in Assam under DDUGJY Phase-II (REDB works)

Page 22 of 33

1.00

Detail sub-soil investigation report about specific information about the soil profile

and necessary soil parameters of sub-station site & recommendations of soil

mechanic engineer regarding foundation depth of defferent type of footings with

size including contour survey etc. as per Technical Specification.

PER S/S 3

2.00

Earth work in PSS site for raising low site with approved soil obtained from outsideby truck carriage and filling in layers not more than 150 mm thick,wateringramming etc. complete as directed and specified including payment of landcompensation,forest royalty,sale tax and other duties and taxes as may benecessary.

CuMtr 11700

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5 Cmthickness including supply of materials,spreading, Leveling etc. and labour as perdirection.

Sq. m 4000

4.00

Design and construction of foundation for following power transformer consideringoriginal equipment manufacturer recommendations and as per soil & siterequirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works: 2.5 MVA with off load/ on load tap changer

No 2

5.00

Design and construction of foundation for following power transformer consideringoriginal equipment manufacturer recommendations and as per soil & siterequirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with off load/ on load tap changer

No 3

Page 22 of 33

Page 273: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

7.00

Design and construction of foundation for Station Service transformer as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 3

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 8

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 16

Page 23 of 33

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 16

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as per

Technical Specification, approved Drawing & Scope of works

MT 45

Fabrication and Erection of Gantry structures using PSC Pole, GI channel, GI angleand GI flat of various sizes including GI nuts & bolts, etc as required as per soil &site requirment and as per Technical Specification, approved Drawing & Scope ofworks

Set 2

Page 23 of 33

Page 274: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footing includingpreparation of base by providing soling and 10 cm PCC and plastering skinting etc.including supplying ,fitting and fixing barbed wire on top of brick boundary wallwith eight strands of barbed wire 12 SWG fitting to Y cross arm at 2.5 m apartincluding supplying fitting and fixing with galvanized staples 38mm x 38mm x 3mm. Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in all posts. the verticaldistence from top of boundary wall to the top of Y cross arm is 600 mm,3 Nos ofbarbed wire should be fitted in each arm of the Y cross arm & 2 nos. in strraightportion including fabrication,errection & painting of Y cross arm with anticorrosiveready mixed and aluminium paint complete including straightining and tightening ofbarbed wire as directed and instllation of sliding steel gate at the entrance of S/Sboundary wall including supply of materials,painting and labour as per technicalspecification,approved drawing and scope of works.

R/Mtr 660

Page 24 of 33

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footing includingpreparation of base by providing soling and 10 cm PCC and plastering skinting etc.including supplying ,fitting and fixing barbed wire on top of brick boundary wallwith eight strands of barbed wire 12 SWG fitting to Y cross arm at 2.5 m apartincluding supplying fitting and fixing with galvanized staples 38mm x 38mm x 3mm. Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in all posts. the verticaldistence from top of boundary wall to the top of Y cross arm is 600 mm,3 Nos ofbarbed wire should be fitted in each arm of the Y cross arm & 2 nos. in strraightportion including fabrication,errection & painting of Y cross arm with anticorrosiveready mixed and aluminium paint complete including straightining and tightening ofbarbed wire as directed and instllation of sliding steel gate at the entrance of S/Sboundary wall including supply of materials,painting and labour as per technicalspecification,approved drawing and scope of works.

R/Mtr 660

12.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 360

13.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide, requireddepth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop, cablesupporting angles including Labour, Reinforcement Steel, MS Angles, Flats, SteelFrame Work, Excavation etc, all complete as per Technical Specification, approvedDrawing & Scope of works.

R/Mtr 490

Page 24 of 33

Page 275: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

14.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80 mtr.height, 45 cm bottom width including preparation base by providing soling and10cm PCC and plastering skinting etc. for easy drainage system inside the sub-station premises including supply of all meterials and labour etc. as per TechnicalSpecification, approved Drawing & Scope of works.

R/Mtr 300

15.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 150

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manhole coverwith locking and cleaning arrangement including providing pads of size as requiredfor inlet and outlet pipe complete including fitting and fixing all materials and filterto get potable water as per approved drawing and specification.

SET 3

Page 25 of 33

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manhole coverwith locking and cleaning arrangement including providing pads of size as requiredfor inlet and outlet pipe complete including fitting and fixing all materials and filterto get potable water as per approved drawing and specification.

SET 3

A-I(b) Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, CuWound, Outdoor Conventional type 2.5 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 sets of50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring/ cabling, cable supporting tray on the body, transformer wheels, bushing etc asper Technical Specification, approved Drawing & Scope of works

No 2

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, CuWound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 sets of50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring/ cabling, cable supporting tray on the body, transformer wheels, bushing etc asper Technical Specification, approved Drawing & Scope of works

No 3

Page 25 of 33

Page 276: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 3

A-I(c) 33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 8

2.00

Design and construction of foundation (as per approved drawings), erection, testingand commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along with junctionbox (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between CT andindoor control panel and required accessories complete as per approved drawings,technical specifications and scope of the work.

Set ofthree

8

Page 26 of 33

2.00

Design and construction of foundation (as per approved drawings), erection, testingand commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along with junctionbox (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between CT andindoor control panel and required accessories complete as per approved drawings,technical specifications and scope of the work.

Set ofthree

8

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: :: 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 3

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: ::: Power transformer 33 kV VCB with Static Tri-VectorEnergy Meter

No 5

Page 26 of 33

Page 277: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, Operating Mechanism,Base Channel down Pipe, Jumpering and all required accessories complete as perapproved drawings, technical specifications and scope of the work,

Set 23

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

14

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including control and power supply cabling, earthing connection using50x6mm GS flat,Jumpering and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

3

Page 27 of 33

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including control and power supply cabling, earthing connection using50x6mm GS flat,Jumpering and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

3

A-I(d) 11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11kV, Outdoor type Vacuum Circuit breaker along withJumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 16

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 16

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Transformer Protection Breaker Panel

Set 4

Page 27 of 33

Page 278: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 12

5.00

Design,construction of foundation (as per approved drawings), Erection, testing andCommissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mountingplatform, jumpering from bus bar, earthing connection using 50x6mm GS flat,hardware, etc as required as per approved drawings, technical specifications andscope of the work.

Set ofthree

19

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 39

Page 28 of 33

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 39

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including Jumpering, control and power supply cabling, earthing connectionusing 50x6mm GS flat and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

6

8.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx300 sqmm

mtr 200

9.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx185 sqmm

mtr 200

10.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 1.6

11.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 300

Page 28 of 33

Page 279: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works:::75 x 8 mm MS flat for ground mat

MT 10

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 3.5

14.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 3.5

15.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.8

Page 29 of 33

15.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.8

16.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm long GIpipe earth electrode by providing test link, RCC pit, RCC cover, placed on GI frame,bentonite powder and other accessories complete as per approved drawings,technical specifications and scope of the work for power transformer neutral,station transformer neutral, lightening arresters direct earthing.

Set 85

17.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutralvoltmeter, three phase ammeter and Selector switches, 200 Amps TPN switch fuseunit as incomer, 32 Amps TPN switches as outgoing feeders suited for number ofcontrol panels, nos of VCB kiosk panel, having 20% spare outgoing feeders, byproviding MS angle 50x50x6 mm structure, cement concrete foundation etc as pertechnical specifications, approved drawings and scope of works.

No 3

18.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 ASP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1 No20 A Industrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specifications andapproved drawings,

No 3

Page 29 of 33

Page 280: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

19.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multi strandcable, terminal connectors, &amp; all other accessories and connectors as per asper approved drawings, technical specifications and scope of the work,

Set 3

20.00

Design, Installation, interconnection cabling, testing and commissioning of 24V, 40

Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full wave

rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per

approved drawings, technical specifications and scope of the work

Set 3

21.00

Erection, testing and commissioning of External electrification works of substationincluding area lighting by 6 No, 12m high steel tubular lighting masts, 2x90 wattsLED flood light fittings on each mast, Junction boxes of the fittings, area lightingpower distribution board, 2 nos. 3 Phase 63 Amp power receptacles, tube wellpower supply, etc as required by laying power cables in underground/aboveground/trenches, construction of foundations for receptacles, distribution boardsetc as required as per approved drawings, specifications and scope of work.

Set 4

Page 30 of 33

21.00

Erection, testing and commissioning of External electrification works of substationincluding area lighting by 6 No, 12m high steel tubular lighting masts, 2x90 wattsLED flood light fittings on each mast, Junction boxes of the fittings, area lightingpower distribution board, 2 nos. 3 Phase 63 Amp power receptacles, tube wellpower supply, etc as required by laying power cables in underground/aboveground/trenches, construction of foundations for receptacles, distribution boardsetc as required as per approved drawings, specifications and scope of work.

Set 4

22.00

Supply, Erection, testing and commissioning of Fire Fighting Equipment comprisesof Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of 4.5Kg Capacityfor Control Room and CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard and 3 Nos. fire buckets of 25 ltr capacity filled with sand and mounted on50x50x6 MS stand duly painted as per Technical Specification, approved Drawing &Scope of works.

SET 3

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 55

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope ofwork, approved drawings and specifications for 12 M long steel Tubular poles withwelded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III 1980) anderection of following types of poles for 33 KV overhead line by providing andinstalling danger plate, anti-climbing devices (barbed wire), earthing material (coiland 8SWG GI wire), red oxide & aluminium paint, pole numbering including cementconcrete foundation using cement concreting foundation 1 part cement, 3 partsand, 6 part 40 mm size stone aggregate chips (1:3:6) etc as per scope of work,approved drawings and specifications:

No 330

Page 30 of 33

Page 281: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blasting isnot required as per scope of work, approved drawings and specifications for 12 Mlong steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KV overheadline by providing and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 770

5.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm, topclamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 44.24

Page 31 of 33

5.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm, topclamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 44.24

7.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 4400

8.01Erection, testing and commissioning of 33 kV polymer Pin insulator including theirGI hardware fittings as per technical specification, approved drawings and scope ofwork.

Set 5280

8.02Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 2640

10.01

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAAC Wolf Conductor of following sizes includingjointing sleeves, helical formed fittings, jumpering and by providing & erecting PGClamps etc as required as per approved drawings, scope of work and technicalspecifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt. km 55

11.01

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plates onGI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 1100

Page 31 of 33

Page 282: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

12.00

Erection of guading for line Crossing-Line to line, line to road with items, GI AngleCross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm longwith nuts & bolts.

Set 55

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 40

2.01

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No. 240

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No 560

Page 32 of 33

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No 560

6.00 Erection of galvanised pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials for over head structures.

MT 18.17

7.01 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GI wirefor earthing,

Set 160

9.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HT stay

guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS

stay rod & 7/10 swg GI stranded wire etc as required by providing boulder packing

as per scope of the work, technical specifications and approved drawings.

Set 400

10.01Erection, testing and commissioning of 11 kV Polymaric Pin insulator including theirhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 1920

10.02Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings and scopeof work.

Set 960

Page 32 of 33

Page 283: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

11.00

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAA Raccon Conductor including jointing sleeves,helical formed fittings, jumpering and by fitting PG Clamps etc as required as perapproved drawings, scope of work and technical specifications. (7/3.81 mm, 79.80Sqmm)

Ckt. Km 40

12.00

Excavation, Erection, testing and commissioning of Protective guarding as per RECconstruction standard drawing No A-1 to be provided at locations where 11KV/33KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guy with 7/3.14 mmwire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe1800 mm long, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire,8 SWG wire for cross lacing as per scope of work, approved drawings and technicalspecifications.

Set 40

Total

Page 33 of 33

Total

Page 33 of 33

Page 284: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT New S/S,1x5MVA atBihdia

(Kamrup)

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 12 Boundary wall inculing Gate R/Mt 220 220

3Construction of Assam Type control room building with bestquality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120

4

Water supply: Deep well with 1 HP motor- Pump,Overheadwater resurvior capacity 2x500 Ltr over the GI staging withnecesssary pipeline with connection,stand & powerconnection appliances.

set 1 1

5 Approach road , 4.0 Mtr width Mtr 50 506 Drainage System Mtr 100 1007 Foundation of Pad for 33/11KV power transformer No 1 18 Foundation of Pad for 33/.433 KV power transformer No 1 1

9 Const. of Cable Trenches as per specification with followingsizes : -

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Kamrup Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S,1x5 MVA at Bihdia within the Kamrup District underDDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM

Page 1 of 29

9 Const. of Cable Trenches as per specification with followingsizes : -

(a) Width 600mm x Depth . RM 150 150

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

SqMtr.

1200 1200

11 Earth Filling CM 3900 390012 Sign Board, size: 4 feetx3 feet No 1 1

EQUIPMENT & MATERIALS FOR CONSTRUTION OF13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG,ABB, Siemens, Schneider make

Nos. 1 1

15 33 KV Current Transformer (400-200/5-5-5 Amps for PowerTr.)

Set 1 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Station Type

Set 3 3

20 33 KV ,1250 Amp Isolator with earth blade Set 1 121 33 KV ,1250 Amp Isolator without earth blade Set 4 4

22 33KV Transformer Panels preferablyCG,ABB,Siemens,Schneider make

Nos. 1 1

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1

24 33 KV Potential Transformer Set 1 1

25 11KV, Vaccum Circuit Breaker with MarshellingBox.preferably CG, ABB, Siemens, Schneider make

No. 5 5

26 Control & Relay panel for 11 KV out door Feeder VCBpreferably CG, ABB, Siemens,Schneider make

No. 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 1 1

Page 1 of 29

Page 285: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT New S/S,1x5MVA atBihdia

(Kamrup)

TotalQuantity

28 11 Kv Current Transformer 600-300/5-5-5A withMarshilling Box and GI Structure

Set 1 1

29 11 Kv Current Transformer 300-150/5-5A with MarshillingBox and GI Structure

Set 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 8 8

37 11 KV Out door Potential Transformer Set 2 238 11 KV LA Line Type (set of 3 units) Set 4 439 11 KV LA Station Type (set of 3 units) Set 1 141 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 142 Battery charger etc. No. 1 149 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4100 410050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800 2800

51 3.5 Core 95 Sq. mm armored, stranded aluminiumconductor, PVC insulated and PVC sheathed cable

Mtr 100 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 15

55 Station service transformer, 33/.433KV,100 KVA Nos. 1 156 Distrbutiob Box Nos. 1 157 LTACDB ,DCDB Etc. Set 1 1

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

Page 2 of 29

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3b 50 x 6 mm Galvanized GS flat (risers) MT 1 1c 25 x 6 mm Galvanized GI flat (risers) MT 1 1d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.259 40 mm dia,3000 mm length GI Earth Pipe No 25 2560 ACSR Panther Conductor for Bus bar Km 0.4 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN)Set of3 nos.

30 30

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Typeof 4.5Kg Capacity for Control Room,two sets of fire bucketsset including their stand for Control Room & Station Yardand One no. CO2 Type Trolley Mounted of 22.5 Kg Capacityfor Switch Yard.

Set 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1

65

Substation Tools and Plants like megger, earth tester,Multimeter, Tong tester, Box-spanners, D-spanners, screwdrivers, earthing rods, earth mat etc as required as perscope of work.

Set 1 1

66 New 33&11 KV Line KamalpurGSS

a 33 KV Line Km 10 10b 11 KV Line Km 20 20

Page 2 of 29

Page 286: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 10.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 2002 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 803 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 1804 Jam Clamp of GI Flat 65x6 mm Pair 5205 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 1206 33 KV Polymeric Pin Insulator No. 9607 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 4808 Tension Clamp for Wolf Conductor No. 2409 AAA Wolf Conductor (19/3.40 mm) Km. 33.00

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 100

11 Guy Insulator (HT) No. 20012 Stay Wire 7/4.0 mm Kg 800

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as perT.S.

Mtr. 600

14 Jointing Sleeve for Wolf No. 30

Rural Electrification works in Kamrup Project in Assam under DDUGJY Phase-II (REDB works)

For New S/S, 2x5 MVA at Uttar Barpeta (Barpeta) and New S/S, 2x5 MVA at Gobardhana (Barpeta)

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM

Page 3 of 29

14 Jointing Sleeve for Wolf No. 3015 PG Clamp for Wolf (Alcon 80) No. 24016 Al. Binding Wire (10 SWG.) Kg 6017 GI Nuts & Bolts (assorted) Kg 80018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 40019 33 KV Danger Plate (1.6 mm thick) No. 20020 Barbed Wire Kg 40021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 200A1 33 KV Overhead Line Crossing - Line to line / Road: Set 101 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 202 GI wire 8 SWG for cross lacing as per T.S Kg. 1003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2004 GI 'I' Hook No. 405 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20B New 11 kV Line Ckt. Km. 20.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 4002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 2403 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 1604 Composite Polymeric 11 kV Pin Insulator No. 9605 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 4806 Tension Clamp for Raccoon No. 4807 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 66.00

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 200

9 HT Guy Insulator No. 20010 GI Stay wire 7/3.15 mm Kg. 1600

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as perT.S.

Mtr. 800

12 GI wire 6 SWG for Earthing Kg. 200

Page 3 of 29

Page 287: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT QTY

13 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8014 Jointing Sleeve for Raccoon No. 6015 PG Clamp for Raccoon No. 48016 AI. Binding Wire (10 SWG.) Kg. 10017 Pole Clamp of GI flat (50x6) mm No. 32018 GI Barbed Wire for anticlimbing device Kg. 80019 11 KV Danger Plate (1.6 mm thick) No. 40020 GI Nuts & Bolts with GI washer (Assorted) Kg. 600B1 11 KV Overhead Line Crossing - Line to line / Road: Set 201 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 402 GI wire 8 SWG for cross lacing as per T.S Kg. 2003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 4004 GI 'I' Hook No. 805 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 40

Page 4 of 29Page 4 of 29

Page 288: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works -

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer,transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Kamrup Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 29

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer,transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 1

3.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 15.000

Page 5 of 29

Page 289: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 1.000

5.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

6.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specifications andscope of works controlling: For 33kV feeder VCB with Static Tri-Vector Energy Meter

No 1

Page 6 of 29

6.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specifications andscope of works controlling: For 33kV feeder VCB with Static Tri-Vector Energy Meter

No 1

7.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specifications andscope of works controlling: ForPower transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

8.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withEarth Blade)

Set 1

9.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 4

10.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

11.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

1

Page 6 of 29

Page 290: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

12.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per technical

specifications, approved drawings and scope of the works.

No 5

13.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (for Transformer)

Set 1

14.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 4

Page 7 of 29

14.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 4

15.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

16.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

17.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB

(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessories

complete as per specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

18.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

19.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 4

Page 7 of 29

Page 291: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

20.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 8

21.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

2

22.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm(200 mm² Al. Area) - Panther

Km 0.400

Page 8 of 29

22.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm(200 mm² Al. Area) - Panther

Km 0.400

23.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 100.000

24.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 2800.000

25.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 4100.000

26.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 3.000

27.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 1.000

28.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 1.000

29.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.200

Page 8 of 29

Page 292: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

30.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,

RCC cover, placed on GI frame, bantonide powder and other accessories

complete as per technical specification. (for Power Transformer Neutral,

Station Transformer Neutral and Lightening Arresters direct earthing)

No 25.00

31.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders, mountingarrangements etc as per technical specifications, approved drawings andscope of works.

Set 1

32.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clampsand hardware as per scope of work, technical specifications and approveddrawings,

Set 1

Page 9 of 29

32.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clampsand hardware as per scope of work, technical specifications and approveddrawings,

Set 1

33.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

30

34.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

35.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-

battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,

terminal connectors, & all other accessories and connectors as per technical

specifications, approved drawings and scope of works.

Set 1

36.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 1

37.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 1

Page 9 of 29

Page 293: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

38.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One

Multimeter, One Tong tester, One set of Box spanner, One set each Round

and D-spanners with various range, screw drivers with various size one each,

earthing rods, etc as required as per scope of work.

Set 1

39.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

B. New 33 KV Lines

1.00

12 M long steel Tubular poles with welded steel base plate of Designation 540

SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per

technical specification, approved drawings and scope of work.

No 200

Page 10 of 29

1.00

12 M long steel Tubular poles with welded steel base plate of Designation 540

SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per

technical specification, approved drawings and scope of work.

No 200

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp,DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp etc made of GI Channels(100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) of givensizes for over head structures as per technical specification,approved drawings and scope of work.

MT 8.040

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work.

MT 0.800

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete

as per technical specification, approved drawings and scope of work.

Set 800

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 200.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.400

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per

technical specification, approved drawings and scope of workSet 480

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 960.00

Page 10 of 29

Page 294: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al.alloy Area 173 sqmm ) - Wolf

km 33.000

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 10

C New 11 KV Lines

1.008.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 400.00

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 9.090

Page 11 of 29

1.008.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 400.00

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 9.090

3.00 Galvanized Steel Nuts, Bolts with Washers as per technicalspecification, approved drawings and scope of work.

MT0.600

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 200

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per

technical specification, approved drawings and scope of work.Set 480.00

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 960

7.00

100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt

and other accessories complete as per technical specification, approved

drawings and scope of work for 11 KV line earthing

Set 80

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.200

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required asper technical specification, approved drawings and scope of work. (7/3.81mm, 79.80 Sqmm)

Km 66.000

Page 11 of 29

Page 295: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 20

Total Ex-worksTotal Ex-works

Page 12 of 29Page 12 of 29

Page 296: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

New 33/11 KV Substation Works (Excluding civil works)A. 33/11 KV Substation Works

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Kamrup Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM

Page 13 of 29

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 1

3.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15.00

4.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 1

Page 13 of 29

Page 297: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

5.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 1

6.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

7.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

8.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 1

Page 14 of 29

8.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 1

9.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 4

10.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

11.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

12.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

13.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

Page 14 of 29

Page 298: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

14.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

15.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

16.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

17.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

18.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories complete

for feeder breaker protection as per technical specifications, approved drawings and

scope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

Page 15 of 29

18.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories complete

for feeder breaker protection as per technical specifications, approved drawings and

scope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

19.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

20.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 8

21.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

22.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware

fittings, hardware, T-claimp etc as per technical specifications, approved drawings and

scope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.40

23.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVC

sheathed LT Power Cables including their termination materials like glands, lugs, tagging

etc. as per technical specifications, approved drawings and scope of the work.

Mtr 100.00

Page 15 of 29

Page 299: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

24.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 2800.00

25.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4100.00

26.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3.00

27.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1.00

28.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1.00

29.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.20

Page 16 of 29

29.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.20

30.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 25.0

31.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

32.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 1

33.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

30

34.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.

Set ofthree

54

Page 16 of 29

Page 300: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

35.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 1

36.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

37.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 1

38.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

39.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

Page 17 of 29

39.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B. New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 200.00

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 8.04

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 0.80

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 800.00

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 200.00

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.40

Page 17 of 29

Page 301: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 480.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 960.00

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 33.00

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 10.00

C New 11 KV Lines

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 400.00

Page 18 of 29

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 400.00

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 9.09

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.60

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nos

turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI stranded

wire etc as required as per technical specification, approved drawings and scope of work.

Set 200.00

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 480.00

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 960.00

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 80.00

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.20

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

Page 18 of 29

Page 302: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 20.00

Total

Page 19 of 29Page 19 of 29

Page 303: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A-I 33/11 KV Grid Substation worksA-Ia Civil works:

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PERS/S

1

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 3900.000

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM

(Schedule of rates and prices)Rural Electrification works in Kamrup Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian Rupees

Page 20 of 29

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 3900.000

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 1200.000

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 1

5.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

6.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 1

Page 20 of 29

Page 304: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 5

8.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 15.000

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220.000

Page 21 of 29

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220.000

10.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 120.000

Page 21 of 29

Page 305: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

11.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 150.000

12.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 100.000

13.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50.000

14.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

Page 22 of 29

14.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

A (Ib) Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changerPower Transformer along with transformer oil, Buchholtz relay, breather, OTI &WTI, Marshalling Box, Conservator tank, oil level indicator, valves by providing2 sets of 50x8 mm GS Neutral Earthing strips with braided conductor onbushing end supported with insulators, OTI & WTI Indicators, Vent explosionplug, control wiring / cabling, cable supporting tray on the body, transformerwheels, bushing etc as per Technical Specification, approved Drawing & Scopeof works

No 1

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 1

33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 1

Page 22 of 29

Page 306: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

1

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 1

Page 23 of 29

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 1

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 5

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set of three 3

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

1

11KV Yard

Page 23 of 29

Page 307: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breakeralong with Jumpers, earthing, supporting structures, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings

No 5

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 5

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

Page 24 of 29

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set of three 5

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 12

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set of three 2

Page 24 of 29

Page 308: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.400

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100.000

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 3.000

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1.000

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1.000

Page 25 of 29

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1.000

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1.000

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.200

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 25.0

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 1

Page 25 of 29

Page 309: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 1

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 1

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

Page 26 of 29

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 1

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 1

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 10.000

Page 26 of 29

Page 310: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as perscope of work, approved drawings and specifications for 12 M long steelTubular poles with welded steel base plate of Designation 540 SP 60 (IS 2713,Pt I, II, III 1980) and erection of following types of poles for 33 KV overheadline by providing and installing danger plate, anti-climbing devices (barbedwire), earthing material (coil and 8SWG GI wire), red oxide & aluminium paint,pole numbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregatechips (1:3:6) etc as per scope of work, approved drawings and specifications:

No 60.00

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 140

Page 27 of 29

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 140

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 8.040

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 800

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 960

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 480

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

10.000

Page 27 of 29

Page 311: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 200.00

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 10

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 20.000

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filledby earth as per scope of work, approved drawings and technical specifications.8.5 mtr PSC pole as per approved GTP.

No. 120

Page 28 of 29

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filledby earth as per scope of work, approved drawings and technical specifications.8.5 mtr PSC pole as per approved GTP.

No. 120

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 280.00

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 9.090

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 80

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 200.00

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 960

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 480

Page 28 of 29

Page 312: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

20.000

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 20

Total

Page 29 of 29Page 29 of 29

Page 313: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT NewS/S,2x5MVA atKhetri

(Kamrup-M)

Augmentation of Maloibarifrom 2x2.5 to2x5 MVA atKamrup-M

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 1 2

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 1 From ADB 1

24 33 KV Potential Transformer Set 1 1 2

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG,ABB, Siemens, Schneider make

No. 6 6

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 2 2

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Boxand GI Structure

Set 2 2

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Kamrup(M) Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Kamrup(M) District under DDUGJY-II/XII PlanScheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM(M)

Page 1 of 33

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 9 2 11

32 11 KV Gang Operated Switch (Line) Nos. From ADB

33 11 KV indoor VCB Panel for Transformer preferably CG, ABB,Siemens, Schneider make

Set From ADB

34 11 KV indoor VCB Panel for Feeder preferablyCG,ABB,Siemens,Schneider make

Set From ADB

35 12 KV indoor VCB Panel for Bus-cuplar preferablyCG,ABB,Siemens,Schneider make

Set From ADB

36 11 KV In door Potential Transformer Set From ADB37 11 KV Out door Potential Transformer Set 2 238 11 KV LA Line Type (set of 3 units) Set 4 1 5

12 KV LA Line Type (set of 3 units) Set From ADB39 11 KV LA Station Type (set of 3 units) Set 2 2 441 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 From ADB 142 Battery charger etc. No. 1 From ADB 143 11 KV XLPE Cable 1x300Sq.mm Mtr 400 40044 11 KV XLPE Cable 1x300 Sq mm Terminate Box(outdoor) No 8 845 11 KV XLPE Cable 1x300 Sq mm Terminate Box(indoor) No 8 846 11 KV XLPE Cable 1x185 Sq.mm for 5 feeder Mtr 800 80047 11 KV XLPE Cable 1x185 Sq mm Terminate Box(outdoor) No 16 1648 11 KV XLPE Cable 1x185 Sq mm Terminate Box(indoor) No 16 1649 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4700 900 560050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 3400 400 3800

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,PVC insulated and PVC sheathed cable

Mtr 100 100 200

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 17 7 2453 11 KV Gantry Structure Set 1 155 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 256 Distrbutiob Box Nos. 1 1 2

Page 1 of 33

Page 314: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT NewS/S,2x5MVA atKhetri

(Kamrup-M)

Augmentation of Maloibarifrom 2x2.5 to2x5 MVA atKamrup-M

TotalQuantity

57 LTACDB ,DCDB Etc. Set 1 1 2

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3 6b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 2c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 2d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.459 40 mm dia,3000 mm length GI Earth Pipe No 25 25 5060 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.8

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30 60

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 108

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1 2

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1 2

65Substation Tools and Plants like megger, earth tester, Multimeter,Tong tester, Box-spanners, D-spanners, screw drivers, earthingrods, earth mat etc as required as per scope of work.

Set 1 1 2

Page 2 of 33

65Substation Tools and Plants like megger, earth tester, Multimeter,Tong tester, Box-spanners, D-spanners, screw drivers, earthingrods, earth mat etc as required as per scope of work.

Set 1 1 2

66 New 33&11 KV Line Sonapur SS From KhetriNew SS

a 33 KV Line Km 18 8 26b 11 KV Line Km 16 4 20c 33 KV Rly-Xing No 1 1d 11 KV Rly-Xing No 1 1e 33 KV NH-Xing No 1 1 2f 11 KV NH-Xing No 1 1

Page 2 of 33

Page 315: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 26.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 5202 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 2083 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 4684 Jam Clamp of GI Flat 65x6 mm Pair 13525 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 3126 33 KV Polymeric Pin Insulator No. 24967 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 12488 Tension Clamp for Wolf Conductor No. 6249 AAA Wolf Conductor (19/3.40 mm) Km. 85.80

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 260

11 Guy Insulator (HT) No. 52012 Stay Wire 7/4.0 mm Kg 2080

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 1560

Rural Electrification works in Kamrup(M) Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Kamrup(M) District under DDUGJY-II/XII PlanScheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM(M)

Page 3 of 33

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 1560

14 Jointing Sleeve for Wolf No. 7815 PG Clamp for Wolf (Alcon 80) No. 62416 Al. Binding Wire (10 SWG.) Kg 15617 GI Nuts & Bolts (assorted) Kg 208018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 104019 33 KV Danger Plate (1.6 mm thick) No. 52020 Barbed Wire Kg 104021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 52022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 520A1 33 KV Overhead Line Crossing - Line to line / Road: Set 261 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 522 GI wire 8 SWG for cross lacing as per T.S Kg. 2603 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 5204 GI 'I' Hook No. 1045 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 52B New 11 kV Line Ckt. Km. 20.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 4002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 2403 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 1604 Composite Polymeric 11 kV Pin Insulator No. 9605 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 4806 Tension Clamp for Raccoon No. 4807 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 66.00

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 200

9 HT Guy Insulator No. 20010 GI Stay wire 7/3.15 mm Kg. 1600

Page 3 of 33

Page 316: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 800

12 GI wire 6 SWG for Earthing Kg. 20013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8014 Jointing Sleeve for Raccoon No. 6015 PG Clamp for Raccoon No. 48016 AI. Binding Wire (10 SWG.) Kg. 10017 Pole Clamp of GI flat (50x6) mm No. 32018 GI Barbed Wire for anticlimbing device Kg. 80019 11 KV Danger Plate (1.6 mm thick) No. 40020 GI Nuts & Bolts with GI washer (Assorted) Kg. 600B1 11 KV Overhead Line Crossing - Line to line / Road: Set 201 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 402 GI wire 8 SWG for cross lacing as per T.S Kg. 2003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 4004 GI 'I' Hook No. 805 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 40

Page 4 of 33Page 4 of 33

Page 317: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A 33/11 KV Substation Works1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00

MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 4

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Kamrup(M) Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM(M)

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 33

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along withtransformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box,Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS NeutralEarthing strips {(with braided conductor on bushing end), isolating link,isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the bodyof transformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 4

2.00 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 2

3.00 11 KV Bus Bar with 12Nos 9.75 meter long PSC Pole, Channel, cross arm,back clamps, insulator with hardware etc all complete as per technicalspecifications, scope of works and approved drawings.

Set 1

Page 5 of 33

Page 318: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00 Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication asper IS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of worksand approved drawings..

MT 24

5.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 5

Page 6 of 33

5.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 5

6.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scopeof works and approved drawings (for feeder at GSS))

Nos 1

7.00 36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 2

8.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4

Page 6 of 33

Page 319: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00 36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scopeof works and approved drawings (for Feeder at GSS)

Sets 1

10.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector EnergyMeter

No 2

Page 7 of 33

11.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector EnergyMeter

No 2

12.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 4

13.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 12

14.00 36 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

15.00 36 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

Page 7 of 33

Page 320: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

16.00 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2

17.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as pertechnical specifications, approved drawings and scope of the works.

No 6

18.00 12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 2

Page 8 of 33

18.00 12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 2

19.00 12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 4

20.00 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

21.00 9kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

5

22.00 Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector EnergyMeter

No 2

Page 8 of 33

Page 321: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

23.00 Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

24.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(With Earth Blade)

Set 4

25.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 11

Page 9 of 33

25.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 11

26.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2

27.00 Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etcas required as per technical specifications, approved drawings and scope ofthe works. 1Cx 300 sqmm size

Mtr 400

28.00 Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etcas required as per technical specifications, approved drawings and scope ofthe works. 1Cx 185sqmm size

Mtr 800

29.00 Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc. asper technical specifications, approved drawings and scope of the works. 1Cx300 sqmm size

Set 8

30.00 Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc. asper technical specifications, approved drawings and scope of the works. 1Cx185sqmm size

Set 16

Page 9 of 33

Page 322: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

31.00 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00mm (200 sqmm Al. Area) - Panther

Km 0.8

32.00 3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including their terminationmaterials like glands, lugs, tagging etc. as per technical specifications,approved drawings and scope of the work.

Mtr 200

33.00 4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 3800

34.00 7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 5600

Page 10 of 33

34.00 7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 5600

35.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 6

36.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 2

37.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 2

38.00 Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.4

39.00 40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,RCC cover, placed on GI frame, bantonide powder and other accessoriescomplete as per technical specification. (for Power Transformer Neutral,Station Transformer Neutral and Lightening Arresters direct earthing)

No 50

Page 10 of 33

Page 323: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

40.00 415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 2

41.00 Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 2

Page 11 of 33

41.00 Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 2

42.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

60

43.00 11 KV, 70 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

108

44.00 110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 1

45.00 110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 1

46.00 External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 2

Page 11 of 33

Page 324: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

47.00 Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 2

48.00 Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 2

B1.00 12 M long steel Tubular poles with welded steel base plate of Designation

540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line asper technical specification, approved drawings and scope of work.

No 520New 33 KV Lines

Page 12 of 33

1.00 12 M long steel Tubular poles with welded steel base plate of Designation540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line asper technical specification, approved drawings and scope of work.

No 520

2.00 Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 20.91

3.00 GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 2.08

4.00 Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire completeas per technical specification, approved drawings and scope of work.

Set 2080

5.00 100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 520

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.047.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas

per technical specification, approved drawings and scope of workSet 1248

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 2496

Page 12 of 33

Page 325: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 85.80

10.00 Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 26.00

11.00 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

Set 1

New 11 KV Lines

Page 13 of 33

11.00 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

Set 1

C1.00 8.5 m PSC Poles Support for 11 KV overhead line as per technical

specification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 400

2.00 Galvanized pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials shown in BOQ for over headstructures as per technical specification, approved drawings and scope ofwork.

MT 9.09

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.6

4.00 Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 200

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsasper technical specification, approved drawings and scope of work.

Set 480

New 11 KV Lines

Page 13 of 33

Page 326: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 960

7.00 100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 80

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.2

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

Page 14 of 33

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

10.00 Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 20.00

11.00 11 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx185 Sqmm XLPE Armoured Cable (0.125 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

set 1

Total Ex-works

Page 14 of 33

Page 327: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

New 33/11 KV Substation Works (Excluding civil works)A 33/11 KV Substation Works -

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 4

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Kamrup(M) Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM(M)

Page 15 of 33

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 4

2.00 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 2

3.00 11 KV Bus Bar with 12Nos 9.75 meter long PSC Pole, Channel, cross arm, back clamps,insulator with hardware etc all complete as per technical specifications, scope of worksand approved drawings.

Set 1

4.00 Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 24

5.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 5

Page 15 of 33

Page 328: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

6.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker , supportingstructures, bi-metallic terminal clamps, permanent maintenance platform, marshallingbox etc required as per technical specifications, scope of works and approved drawings(for feeder at GSS))

No 1

7.00 36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Set 2

8.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 4

Page 16 of 33

8.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 4

9.00 36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (for Feeder at GSS)

Set 1

10.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 2

12.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 4

13.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 12

Page 16 of 33

Page 329: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

14.00 36 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

15.00 36 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

16.00 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

17.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 6

Page 17 of 33

17.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 6

18.00 12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 2

19.00 12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

20.00 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

4

21.00 9kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

5

22.00 Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 2

Page 17 of 33

Page 330: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

23.00 Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

24.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

25.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 11

26.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

Page 18 of 33

26.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

27.00 Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,including their termination materials like glands, lugs, tagging etc as required as pertechnical specifications, approved drawings and scope of the works. 1Cx 300 sqmm size

Mtr 400

28.00 Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,including their termination materials like glands, lugs, tagging etc as required as pertechnical specifications, approved drawings and scope of the works. 1Cx 185sqmm size

Mtr 800

29.00 Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 300 sqmm size

Set 8

30.00 Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 185sqmm size

Set 16

31.00 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.8

Page 18 of 33

Page 331: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

32.00 3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 200

33.00 4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 3800

34.00 7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 5600

35.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 6

36.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 2

Page 19 of 33

36.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 2

37.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 2

38.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.4

39.00 40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 50

40.00 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 2

41.00 Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 2

Page 19 of 33

Page 332: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

42.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

60

43.00 11 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

108

44.00 110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 1

45.00 110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

46.00 External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 2

Page 20 of 33

46.00 External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 2

47.00 Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 2

48.00 Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 2

B New 33 KV Lines1.00 12 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS

2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 520

2.00 Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 21

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 2.08

Page 20 of 33

Page 333: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

4.00 Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 2080

5.00 100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 520

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.047.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technical

specification, approved drawings and scope of workSet 1248

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 2496

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 85.80

Page 21 of 33

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 85.80

10.00 Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 26.00

11.00 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos (INCLUDINGONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 km each) USING 150MM DIA CIPIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT,OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 33 KV LIGHTENING ARRESTORSTATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK including Wayleave/ Supervision Charges payable to Railway Department on actual basis.

set 1

C New 11 KV Lines1.00 8.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approved

drawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 400

2.00 Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 9.09

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.60

Page 21 of 33

Page 334: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

4.00 Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 200

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 480

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 960

7.00 100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 80

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.2

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

Page 22 of 33

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 66.00

10.00 Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 20.00

11.00 11 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos (INCLUDINGONE SPARE) 1Cx185 Sqmm XLPE Armoured Cable (0.125 km each) USING 150MM DIA CIPIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT,OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 33 KV LIGHTENING ARRESTORSTATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK including Wayleave/ Supervision Charges payable to Railway Department on actual basis.

set 1

Total

Page 22 of 33

Page 335: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PERS/S

2

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 2000

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAM(M)

(Schedule of rates and prices)Rural Electrification works in Kamrup(M) Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian RupeesBidder's Name & Address:

Page 23 of 33

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 2000

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 2400

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 4

5.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 2

6.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 6

Page 23 of 33

Page 336: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

7.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 6

8.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 24

9.00

Fabrication and Erection of Gantry structures using PSC Pole, GI channel, GIangle and GI flat of various sizes including GI nuts & bolts, etc as required asper soil & site requirment and as per Technical Specification, approved Drawing& Scope of works

Set 1

10.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 400

Page 24 of 33

10.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 400

Page 24 of 33

Page 337: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

11.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 240

12.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 250

Page 25 of 33

12.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 250

13.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 200

14.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

15.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 2

A-Ib Substation Electrical works

Page 25 of 33

Page 338: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 4

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 2

33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 6

Page 26 of 33

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 6

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

7

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

Page 26 of 33

Page 339: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 2

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 16

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

7

Page 27 of 33

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

7

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 6

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 6

Page 27 of 33

Page 340: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 2

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

9

Page 28 of 33

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

9

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 15

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

8.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx300 sqmm

mtr 400

9.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx185 sqmm

mtr 800

10.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.8

Page 28 of 33

Page 341: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

11.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 200

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 6

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 2

14.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 2

Page 29 of 33

14.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 2

15.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.4

16.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 50

17.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 2

Page 29 of 33

Page 342: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

18.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 2

19.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 1

20.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

Page 30 of 33

20.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

21.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 2

22.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 2

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 26.00

Page 30 of 33

Page 343: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 156

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 364

Page 31 of 33

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 364

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 20.91

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 2080

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 2496

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 1248

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

26.00

Page 31 of 33

Page 344: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 520

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 26.00

11.00

Erection of 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4 Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 km each)USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MMHDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLE CABLEJOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.),LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GI WIRES, CABLEMARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORKincluding Way leave/ Supervision Charges payable to RailwayDepartment on actual basis.

Set 1

Page 32 of 33

11.00

Erection of 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4 Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.125 km each)USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MMHDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLE CABLEJOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.),LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GI WIRES, CABLEMARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORKincluding Way leave/ Supervision Charges payable to RailwayDepartment on actual basis.

Set 1

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 20.00

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 120

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 280

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 9.09

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 80

Page 32 of 33

Page 345: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 200

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 960

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 480

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

20.00

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 20.00

Page 33 of 33

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 20.00

11.00

Erection Testing & Cmmissioning of 11 KV LINE FOR UNDER GROUND RAILWAYCROSSING BY 4 Nos (INCLUDING ONE SPARE) 1Cx185 Sqmm XLPE ArmouredCable (0.125 km each) USING 150MM DIA CI PIPES (CLASS-I A TYPE) FOR UGCABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT), OUTDOOR HEATSHRINKABLE CABLE JOINTING KITS, 11 KV LIGHTENING ARRESTOR STATIONCLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OFTHE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

Set 1

Total

Page 33 of 33

Page 346: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

New S/S,1x5MVA

Chandmari(Karbi)(LILO)

Augmentationof Bakolia at

Karbi anglong

Augmentation of Kheroni

at Karbianglong

1 2 3 4 5 6 7A New 33/11 KV Substation Works

2333KV Feeder Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1

24 33 KV Potential Transformer Set 1 1

25 11KV, Vaccum Circuit Breaker with MarshellingBox.preferably CG, ABB, Siemens, Schneider make

No. 5 5

26 Control & Relay panel for 11 KV out door Feeder VCBpreferably CG, ABB, Siemens,Schneider make

No. 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 1 1

28 11 Kv Current Transformer 600-300/5-5-5A withMarshilling Box and GI Structure

Set 1 1

29 11 Kv Current Transformer 300-150/5-5A with MarshillingBox and GI Structure

Set 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 8 2 2 12

32 11 KV Gang Operated Switch (Line) Nos. 5 5 10

BOQ: Construction of 33/11KV New S/S within the Karbi Anglong District under DDUGJY-II/XII Plan Scheme.

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAN

STANDARD BILL OF MATERIALS (as per site requirement)

Rural Electrification works in Karbi Anglong Project in Assam under DDUGJY Phase-II (REDB works)

ASSAM POWER DISTRIBUTION COMPANY LIMITED

Sl.No. ITEM DESCRIPTION

UNIT

TotalQuantity

Page 1 of 33

32 11 KV Gang Operated Switch (Line) Nos. 5 5 10

33 11 KV indoor VCB Panel for Transformer preferably CG,ABB, Siemens, Schneider make

Set 2 2

34 11 KV indoor VCB Panel for Feeder preferablyCG,ABB,Siemens,Schneider make

Set 6 6

35 12 KV indoor VCB Panel for Bus-cuplar preferablyCG,ABB,Siemens,Schneider make

Set 1 1

36 11 KV In door Potential Transformer Set 2 237 11 KV Out door Potential Transformer Set 2 238 11 KV LA Line Type (set of 3 units) Set 4 4 4 1239 11 KV LA Station Type (set of 3 units) Set 1 1 2 441 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 242 Battery charger etc. No. 1 143 11 KV XLPE Cable 1x300Sq.mm Mtr 200 200 400

44 11 KV XLPE Cable 1x300 Sq mm Terminate Box(outdoor) No 4 4 8

45 11 KV XLPE Cable 1x300 Sq mm Terminate Box(indoor) No 4 4 8

46 11 KV XLPE Cable 1x185 Sq.mm for 5 feeder Mtr 200 200

47 11 KV XLPE Cable 1x185 Sq mm Terminate Box(outdoor) No 4 4

48 11 KV XLPE Cable 1x185 Sq mm Terminate Box(indoor) No 4 4

49 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4100 400 800 530050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800 300 600 3700

51 3.5 Core 95 Sq. mm armored, stranded aluminiumconductor, PVC insulated and PVC sheathed cable

Mtr 100 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 15

55 Station service transformer, 33/.433KV,100 KVA Nos. 1 156 Distrbutiob Box Nos. 1 157 LTACDB ,DCDB Etc. Set 1 1

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3b 50 x 6 mm Galvanized GS flat (risers) MT 1 1c 25 x 6 mm Galvanized GI flat (risers) MT 1 1

Page 1 of 33

Page 347: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

New S/S,1x5MVA

Chandmari(Karbi)(LILO)

Augmentationof Bakolia at

Karbi anglong

Augmentation of Kheroni

at Karbianglong

1 2 3 4 5 6 7

Sl.No. ITEM DESCRIPTION

UNIT

TotalQuantity

d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.259 40 mm dia,3000 mm length GI Earth Pipe No 25 10 10 4560 ACSR Panther Conductor for Bus bar Km 0.4 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN)Setof 3nos.

30 30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN)Setof 3nos.

54 54

63

Fire Fighting Equipment comprises of Four nos DryChemical Powder Type (6 Kg) for control room; Two nosCO2 Type of 4.5Kg Capacity for Control Room,two sets offire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of22.5 Kg Capacity for Switch Yard.

Set 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1 1 3

65

Substation Tools and Plants like megger, earth tester,Multimeter, Tong tester, Box-spanners, D-spanners, screwdrivers, earthing rods, earth mat etc as required as perscope of work.

Set 1 1 2

66 New 33&11 KV Line Diphu GSSa 33 KV Line Km 12 12b 11 KV Line Km 10 10

Page 2 of 33Page 2 of 33

Page 348: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 121 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 2402 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 963 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 2164 Jam Clamp of GI Flat 65x6 mm Pair 6245 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 1446 33 KV Polymeric Pin Insulator No. 11527 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 5768 Tension Clamp for Wolf Conductor No. 2889 AAA Wolf Conductor (19/3.40 mm) Km. 39.60

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 120

11 Guy Insulator (HT) No. 24012 Stay Wire 7/4.0 mm Kg 960

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 720

Rural Electrification works in Karbi Anglong Project in Assam under DDUGJY Phase-II (REDBworks)

BOQ: Construction of 33/11KV New S/S within the Karbi Anglong District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAN

Page 3 of 33

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 720

14 Jointing Sleeve for Wolf No. 3615 PG Clamp for Wolf (Alcon 80) No. 28816 Al. Binding Wire (10 SWG.) Kg 7217 GI Nuts & Bolts (assorted) Kg 96018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 48019 33 KV Danger Plate (1.6 mm thick) No. 24020 Barbed Wire Kg 48021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 24022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 240A1 33 KV Overhead Line Crossing - Line to line / Road: Set 121 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 242 GI wire 8 SWG for cross lacing as per T.S Kg. 1203 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2404 GI 'I' Hook No. 485 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 24B New 11 kV Line Ckt. Km. 10.00

1MS Steel Tubular Pole SP-22, 8.5 Mtr (141 Kg.) as per T.S ,IS and approved GTP, dulypainted .

No. 200

2 G I Channel Section 75x40x6x1100 mm and 75x40x6x350 mm GI top cleat for fixing of 11KV polymeric Pin insulator

No. 120

3 Galvanized Channel Cross Arm (75x40x6X2200) mm No. 80

4 Composite Polymeric 11 kV Pin Insulator No. 480

5 Composite Polymeric 11 kV Disc Insulator (70 KN) with H/W Set 240

6 Tension Clamp for Raccoon No. 2407 AAAC Raccoon Conductor ( Ckt Km x3.3) Km. 33.00

8 Stay Set (HT) 50x8 mm Stay Clamp, Anchor Plate (200x200x6)mm 2 Nos. of Turn Buckles,1.8 mtr long, 16 mm diameter Solid GS Stay Rod complete HT Stay Set.

Set 100

Page 3 of 33

Page 349: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

9 Guy Insulator (HT) No. 10010 GI Stay wire 7/10 SWG Kg. 800.00

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 400.00

12 GI wire 6 SWG for Earthing Kg. 400.0013 CI Earth Pipe 100mm dia (1.8 Mtr.) as per TS. No. 20014 Jointing Sleeve for Raccoon No. 3015 PG Clamp for Raccoon No. 24016 AI. Binding Wire (10 SWG.) Kg. 50.0017 GI Flat (50x6 mm) Jam Clamp Pair 16018 GI Barbed Wire for anticlimbing device (12 SWG=2.5mm) Kg. 40019 Danger Plate 11KV(1.6mm thick) No. 20020 GI Nuts & Bolts with GI washer (Assorted) Kg. 300.00B1 11 KV Overhead Line Crossing - Line to line / Road: Set 101 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 20

2 GI wire 8 SWG for cross lacing as per T.S Kg. 100

3 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 200

4 GI 'I' Hook No. 40

5 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20

Page 4 of 33Page 4 of 33

Page 350: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators, Ventexplosion plug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels, LV/HVbushing etc as required as per technical specifications, approved drawings andscope of the work.

No 4

All prices in Indian RupeesBidder's Name & Address:New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Karbi Anglong Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAN

Page 5 of 33

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators, Ventexplosion plug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels, LV/HVbushing etc as required as per technical specifications, approved drawings andscope of the work.

No 4

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be 6mmfilled weld unless specified otherwise. All nuts and bolts shall be of propertyclass 5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washersshall be IS: 3063 as per technical specifications, scope of works and approveddrawings..

MT 15

Page 5 of 33

Page 351: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker, supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Transformer & feeder)

Nos 4

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of worksand approved drawings (for Feeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4

Page 6 of 33

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For 33 kV feederVCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Powertransformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 2

Page 6 of 33

Page 352: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 7

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree 6

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree 1

Page 7 of 33

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree 1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree 1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree 4

Page 7 of 33

Page 353: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree 12

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessoriescomplete as per specifications for transformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kV feederVCB with Static Tri-Vector Energy Meter

No 4

Page 8 of 33

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kV feederVCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 12

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree 2

27.00

12kV, 800A, 25kA for 3 sec, 3-Phase, 3 Pin type, Horizonal/Vertical Mountingtype (as desired by DISCOM), Gang Operated, AB Switch, along with supportinsulators, Base Channel, down pipe, Arching Horns etc. and all completeaccessories as per technical specifications, scope of works and approveddrawings

Set 10

Page 8 of 33

Page 354: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

28.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breakeralong with 12 kV, 1-Phase, 600-300/5-5-5 3 Nos indoor type CurrentTransformer, indoor mounting type control panel for Transformer breaker,and required accessories, bi-metallic clamps, A-meter, volt-meter,3-phaseelectronic energy meter, Relay & accessories complete for transformer breakerprotection as per technical specifications, approved drawings and scope ofworks.

No 2

29.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breakeralong with 12 kV, 1-Phase, 300-150/5-5 3 Nos indoor type CurrentTransformer, indoor mounting type control panel for Feeder protection, andrequired accessories, bi-metallic clamps, A-meter, volt-meter, 3-phaseelectronic energy meter, Relay & accessories complete for feeder breakerprotection as per technical specifications, approved drawings and scope ofworks.

No 6

Page 9 of 33

29.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breakeralong with 12 kV, 1-Phase, 300-150/5-5 3 Nos indoor type CurrentTransformer, indoor mounting type control panel for Feeder protection, andrequired accessories, bi-metallic clamps, A-meter, volt-meter, 3-phaseelectronic energy meter, Relay & accessories complete for feeder breakerprotection as per technical specifications, approved drawings and scope ofworks.

No 6

30.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breakeralong with 12 kV, 1-Phase, 600-300/5-5 3 Nos indoor type CurrentTransformer, indoor mounting type control panel for Bus coupler, andrequired accessories, bi-metallic clamps, A-meter, volt-meter, 3-phaseelectronic energy meter, Relay & accessories complete as per specifications forbus coupler protection

No 1

31.0012 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core Indoor type PotentialTransformer along with required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set 2

32.00

Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etc asrequired as per technical specifications, approved drawings and scope of theworks. 1Cx 300 sqmm size

Mtr 400

33.00

Single Core 11 KV, XLPE, power cable armored, aluminium conductor,stranded, including their termination materials like glands, lugs, tagging etc asrequired as per technical specifications, approved drawings and scope of theworks. 1Cx 185sqmm size

Mtr 200

34.00

Cable termination kit suitable for termination in transformer cable box/ breakerpanel/ outdoor 11 KV terminals complete with all accessories etc. as pertechnical specifications, approved drawings and scope of the works. 1Cx 300sqmm size

Set 8

Page 9 of 33

Page 355: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

35.00

Cable termination kit suitable for termination in transformer cable box/ breakerpanel/ outdoor 11 KV terminals complete with all accessories etc. as pertechnical specifications, approved drawings and scope of the works. 1Cx185sqmm size

Set 4

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200mm² Al. Area) - Panther

Km 0.4

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 100

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 3700

Page 10 of 33

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 3700

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 5300

40.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories completeas per technical specification. (for Power Transformer Neutral, StationTransformer Neutral and Lightening Arresters direct earthing)

No 45

Page 10 of 33

Page 356: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangementsetc as per technical specifications, approved drawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 1

Page 11 of 33

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 1

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree 30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree 54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 2

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 3

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 2

Page 11 of 33

Page 357: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Roundand D-spanners with various range, screw drivers with various size one each,earthing rods, etc as required as per scope of work.

Set 2

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as pertechnical specification, approved drawings and scope of work.

No 240

New 33 KV Lines

Page 12 of 33

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as pertechnical specification, approved drawings and scope of work.

No 240

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels,back clamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm),GI flats (65x8mm) of given sizes for over head structures as per technicalspecification, approved drawings and scope of work.

MT 9.66

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work. MT 0.96

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete asper technical specification, approved drawings and scope of work.

Set 960

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 240

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.48

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work Set 576

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work Set 1152

Page 12 of 33

Page 358: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al. alloyArea 173 sqmm ) - Wolf

km 39.60

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 12.00

C

1.00

8.5 m Steel Tubular pole SP-22 (141 Kg.) Poles Support for 11 KV overheadline as per technical specification, approved drawings and scope of workalongwith Danger Plate and Barbed Wire as per approved GTP, as per statepractice.

No. 200

New 11 KV Lines

Page 13 of 33

1.00

8.5 m Steel Tubular pole SP-22 (141 Kg.) Poles Support for 11 KV overheadline as per technical specification, approved drawings and scope of workalongwith Danger Plate and Barbed Wire as per approved GTP, as per statepractice.

No. 200

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,angle, flats and all other GI materials shown in BOQ for over head structuresas per technical specification, approved drawings and scope of work.

MT 4.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work. MT 0.3

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts,2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mmGI stranded wire etc as required as per technical specification, approveddrawings and scope of work.

Set 100

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work. Set 240

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work. Set 480

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Saltand other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 40

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work. MT 0.10

Page 13 of 33

Page 359: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No. ITEM DESCRIPTION Unit Qty

Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)Excise Duty @

Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 33.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mm diameterEye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meter long, 6 SWGGI wires for earthing connection, 6 SWG wire for guard wire, 8 SWG wire forcross lacing.

set 10.00

Total Ex-works

Page 14 of 33

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mm diameterEye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meter long, 6 SWGGI wires for earthing connection, 6 SWG wire for guard wire, 8 SWG wire forcross lacing.

set 10.00

Total Ex-works

Page 14 of 33

Page 360: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9New 33/11 KV Substation Works (Excluding civil works)

A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 4

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Karbi Anglong Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAN

Page 15 of 33

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 4

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 4

Page 15 of 33

Page 361: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Set 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 4

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

Page 16 of 33

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 7

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

6

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

Page 16 of 33

Page 362: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

Page 17 of 33

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

4

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

12

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 12

Page 17 of 33

Page 363: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

27.00

12kV, 800A, 25kA for 3 sec, 3-Phase, 3 Pin type, Horizonal/Vertical Mounting type (asdesired by DISCOM), Gang Operated, AB Switch, along with support insulators, BaseChannel, down pipe, Arching Horns etc. and all complete accessories as per technicalspecifications, scope of works and approved drawings

Set 10

28.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 600-300/5-5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Transformer breaker, and required accessories, bi-metallic clamps, A-meter, volt-meter,3-phase electronic energy meter, Relay &accessories complete for transformer breaker protection as per technical specifications,approved drawings and scope of works.

No 2

29.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 300-150/5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Feeder protection, and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay &accessories complete for feeder breaker protection as per technical specifications,approved drawings and scope of works.

No 6

Page 18 of 33

29.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 300-150/5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Feeder protection, and required accessories, bi-metallic clamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay &accessories complete for feeder breaker protection as per technical specifications,approved drawings and scope of works.

No 6

30.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Indoor type Vacuum Circuit breaker alongwith 12 kV, 1-Phase, 600-300/5-5 3 Nos indoor type Current Transformer, indoormounting type control panel for Bus coupler, and required accessories, bi-metallicclamps, A-meter, volt-meter, 3-phase electronic energy meter, Relay & accessoriescomplete as per specifications for bus coupler protection

No 1

31.0012 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core Indoor type Potential Transformeralong with required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set 2

32.00Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,including their termination materials like glands, lugs, tagging etc as required as pertechnical specifications, approved drawings and scope of the works. 1Cx 300 sqmm size

Mtr 400

33.00Single Core 11 KV, XLPE, power cable armored, aluminium conductor, stranded,including their termination materials like glands, lugs, tagging etc as required as pertechnical specifications, approved drawings and scope of the works. 1Cx 185sqmm size

Mtr 200

34.00Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 300 sqmm size

Set 8

Page 18 of 33

Page 364: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

35.00Cable termination kit suitable for termination in transformer cable box/ breaker panel/outdoor 11 KV terminals complete with all accessories etc. as per technical specifications,approved drawings and scope of the works. 1Cx 185sqmm size

Set 200

36.00ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.4

37.003.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 100

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 3700

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 5300

Page 19 of 33

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 5300

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 45

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

Page 19 of 33

Page 365: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 1

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 2

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

Page 20 of 33

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 3

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 2

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 2

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B. New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 240

Page 20 of 33

Page 366: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 9.7

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 1.0

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 960

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 240

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.48

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 576

Page 21 of 33

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 576

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 1152

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 39.60

10.00Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 12.00

C New 11 KV Lines

1.008.5 m Steel Tubular pole SP-22 (141 Kg.) Poles Support for 11 KV overhead line as pertechnical specification, approved drawings and scope of work alongwith Danger Plate andBarbed Wire as per approved GTP, as per state practice.

No. 200

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 4.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.30

4.00Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 100

Page 21 of 33

Page 367: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 240

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 480

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 40

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.1

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 33.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 10.00

Total

Page 22 of 33

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 10.00

Total

Page 22 of 33

Page 368: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PER S/S 1

Schedule-3

All prices in Indian Rupees

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KAN

(Schedule of rates and prices)Rural Electrification works in Karbi Anglong Project in Assam under DDUGJY Phase-II (REDB works)

Page 23 of 33

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PER S/S 1

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 0

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 2800

5.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 4

7.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

Page 23 of 33

Page 369: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 4

9.00

Design and construction of foundation for following 11 KV outdoor mounted

Vacuume Circuit Breaker considering original equipment manufacturer

recommendation and as per soil & site requirment including excavation of pit,

shuttering and by providing reinforcement, cement concreting, painting etc as

per Technical Specification, approved Drawing & Scope of works. Works also

includes providing working platform for operation of breakers and painting.

Nos. 5

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 15

Page 24 of 33

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 15

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

Page 24 of 33

Page 370: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

12.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 120

Page 25 of 33

12.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 120

13.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 300

14.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 100

15.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

A (Ib) Substation Electrical works

Page 25 of 33

Page 371: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 4

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 1

A (Ic) 33KV Yard

3.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 4

Page 26 of 33

3.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 4

4.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

5

5.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

Page 26 of 33

Page 372: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

6.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 3

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 9

8.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

7

Page 27 of 33

8.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

7

9.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

1

A (Id) 11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 5

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 5

Page 27 of 33

Page 373: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

16

Page 28 of 33

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

16

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 16

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

8.00

Design, construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Transformer Protection Breaker Panel along with 12 kV, 1-Phase, 25kAfor 3 seconds, 600- 300/5-5-5 A and 300-150/5-5, indoor type CurrentTransformer along with control and relay panel consisting of A-meter, volt-meter,Relay &amp; accessories complete cabling between VCB and indoor control paneland required accessories complete as per approved drawings, technicalspecifications and scope of the work,

NO 2

Page 28 of 33

Page 374: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Design,construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Feeder Protection Breaker Panel along with 12 kV, 1-Phase, 25kA for 3seconds, 600- 300/5-5-5 A and 300-150/5-5, indoor type Current Transformeralong with control and relay panel consisting of A-meter, volt-meter, Relay&amp; accessories complete cabling between VCB and indoor control panel andrequired accessories complete as per approved drawings, technical specificationsand scope of the work,

No 6

10.00

Design, construction of foundation (as per approved drawings), erection, wiring,testing and commissioning of 12 kV, 1250 A, 25kA, 3-ph, Indoor type VacuumCircuit Bus Coupler Panel along with 12 kV, 1-Phase, 25kA for 3 seconds, 600-300/5-5-5 A and 300-150/5-5, indoor type Current Transformer along withcontrol and relay panel consisting of A-meter, volt-meter, Relay &; accessoriescomplete cabling between VCB and indoor control panel and required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

NO 1

11.00Installation, testing, commissioning of 3-phase 11 KV Indoor Potential

Transformers of rating 11/110 Volts as per technical specifications and drawings,

Set ofthree

2

Page 29 of 33

11.00Installation, testing, commissioning of 3-phase 11 KV Indoor Potential

Transformers of rating 11/110 Volts as per technical specifications and drawings,

Set ofthree

2

12.00 Erection, testing and Commissioning of 12 KV, 600 A, 3-pole AB Switch as perTechnical Specification, approved Drawing & Scope of works.

Set 10

13.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx300 sqmm

mtr 400

14.00 Laying, erection, termination using indoor & outdoor termination kit, 11KV XLPE,Power armored cables of following sizes: 1Cx185 sqmm

mtr 200

15.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.4

16.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100

17.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 3

18.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1

Page 29 of 33

Page 375: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

19.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

20.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.2

21.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 45

22.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 1

Page 30 of 33

22.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 1

23.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 1

24.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 2

25.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

Page 30 of 33

Page 376: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

26.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 3

27.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 1

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 12

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 72

Page 31 of 33

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 12

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 72

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 168

5.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 9.66

Page 31 of 33

Page 377: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 960

8.01Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 1152

8.02Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 576

10.01

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt. km 12

11.01

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 240

Page 32 of 33

10.01

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt. km 12

11.01

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 240

12.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 12

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 10.00

2.01

Excavation and erection of support for 11 KV overhead line by providing andinstalling danger plate, anti-climbing devices (barbed wire) and pole numbering,earthing, painting with red oxide and aluminum paint and making cementconcrete foundation and mufflering as per scope of work, approved drawingsspecifiactions. 8.5 meter long MS Steel Tubular poles with welded steel baseplate of SP-22 (141 Kg.) as per IS

No. 200

6.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 4.54

7.01 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 40

9.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 100

Page 32 of 33

Page 378: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

10.01Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 480

10.02Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 240

11.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt. Km 10

12.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 10

Total

Page 33 of 33

12.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 10

Total

Page 33 of 33

Page 379: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

1 2 3 4

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 12 Boundary wall inculing Gate R/Mt 220

3 Construction of Assam Type control room building with best quality Dyna roof (blueclour) including , Senitary, Internal electrification etc.complete

Sq.M 120

4Water supply: Deep well with 1 HP motor- Pump,Overhead water resurvior capacity2x500 Ltr over the GI staging with necesssary pipeline with connection,stand &power connection appliances.

set 1

5 Approach road , 4.0 Mtr width Mtr 506 Drainage System Mtr 1007 Foundation of Pad for 33/11KV power transformer No 18 Foundation of Pad for 33/.433 KV power transformer No 19 Const. of Cable Trenches as per specification with following sizes : -

(a) Width 600mm x Depth . RM 15010 Gravelling of switch yard, depth 22.5 Cm with crushed stone size 40 mm Sq Mtr. 120011 Earth Filling CM 390012 Sign Board, size: 4 feetx3 feet No 1

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

ASSAM POWER DISTRIBUTION COMPANY LIMITED

Sl.No. ITEM DESCRIPTION UNIT

BOQ: Construction of 33/11KV New S/S within the Karimganj District under DDUGJY-II/XII Plan Scheme.

New S/S,1x5MVA at

Dullavcherra(Karimganj)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KMJ

STANDARD BILL OF MATERIALS (as per site requirement)

Rural Electrification works in Karimganj Project in Assam under DDUGJY Phase-II (REDB works)

Page 1 of 30

12 Sign Board, size: 4 feetx3 feet No 1

13(a) 33/11KV 5 MVA Power Transformer Nos. 1

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB, Siemens, Schneidermake

Nos. 1

14(b) 33KV,1250A, 25 KA SF6 Circuit Breaker(GSS) preferably CG, ABB, Siemens,Schneider make

Nos. 1

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 117 33 KV Current Transformer ( 400-200/1-1A for Feeder) Set 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GI mounting(set of 3 units)Station Type

Set 3

19 33KV , 10 KA Lightning Arrester with chagre monitor and GI mounting(set of 3 units)Line Type

Set 1

20 33 KV ,1250 Amp Isolator with earth blade Set 221 33 KV ,1250 Amp Isolator without earth blade Set 522 33KV Transformer Panels preferably CG,ABB,Siemens,Schneider make Nos. 123 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 124 33 KV Potential Transformer Set 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG, ABB, Siemens,Schneider make

No. 5

26 Control & Relay panel for 11 KV out door Feeder VCB preferably CG, ABB,Siemens,Schneider make

No. 4

27 Control & Relay panel for 11 KV out door Transformer VCB preferably CG,ABB,Siemens,Schneider make

No. 1

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Box and GI Structure Set 1

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Box and GI Structure Set 4

30 11 KV Isolator Double break with earth switch with GI structure(800A) Set 431 11 KV Isolator Double break without earth switch with GI structure(800A) Set 837 11 KV Out door Potential Transformer Set 238 11 KV LA Line Type (set of 3 units) Set 4

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

Page 1 of 30

Page 380: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

1 2 3 4

Sl.No. ITEM DESCRIPTION UNIT

New S/S,1x5MVA at

Dullavcherra(Karimganj)

39 11 KV LA Station Type (set of 3 units) Set 141 110 V, 150 AH Lead Acid Battery bank, etc. Set 142 Battery charger etc. No. 149 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 410050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVCsheathed cable

Mtr 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 1555 Station service transformer, 33/.433KV,100 KVA Nos. 156 Distrbutiob Box Nos. 157 LTACDB ,DCDB Etc. Set 1

58 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3b 50 x 6 mm Galvanized GS flat (risers) MT 1c 25 x 6 mm Galvanized GI flat (risers) MT 1d 25mm dia MS rod 3 m long for earth mat MT 0.259 40 mm dia,3000 mm length GI Earth Pipe No 2560 ACSR Panther Conductor for Bus bar Km 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of 3nos.

30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of 3nos.

54

63

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg)for control room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two setsof fire buckets set including their stand for Control Room & Station Yard and One no.CO2 Type Trolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

Page 2 of 30

63

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg)for control room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two setsof fire buckets set including their stand for Control Room & Station Yard and One no.CO2 Type Trolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

64 External Electrification at station yard lighting with 12 Nos lightening 90 Watt LEDLamp .

set 1

65Substation Tools and Plants like megger, earth tester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers, earthing rods, earth mat etc as required as perscope of work.

Set 1

66 New 33&11 KV Linea 33 KV Line Km 1b 11 KV Line Km 25

Page 2 of 30

Page 381: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 1.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 202 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 83 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 184 Jam Clamp of GI Flat 65x6 mm Pair 525 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 126 33 KV Polymeric Pin Insulator No. 967 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 488 Tension Clamp for Wolf Conductor No. 249 AAA Wolf Conductor (19/3.40 mm) Km. 3.30

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 10

11 Guy Insulator (HT) No. 2012 Stay Wire 7/4.0 mm Kg 80

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 60

Rural Electrification works in Karimganj Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Karimganj District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KMJ

Page 3 of 30

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 60

14 Jointing Sleeve for Wolf No. 315 PG Clamp for Wolf (Alcon 80) No. 2416 Al. Binding Wire (10 SWG.) Kg 617 GI Nuts & Bolts (assorted) Kg 8018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 4019 33 KV Danger Plate (1.6 mm thick) No. 2020 Barbed Wire Kg 4021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 2022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 20A1 33 KV Overhead Line Crossing - Line to line / Road: Set 11 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 22 GI wire 8 SWG for cross lacing as per T.S Kg. 103 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 204 GI 'I' Hook No. 45 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 2B New 11 kV Line Ckt. Km. 25.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 5002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 3003 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 2004 Composite Polymeric 11 kV Pin Insulator No. 12005 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 6006 Tension Clamp for Raccoon No. 6007 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 82.50

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 250

9 HT Guy Insulator No. 25010 GI Stay wire 7/3.15 mm Kg. 2000

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 1000

Page 3 of 30

Page 382: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 412 GI wire 6 SWG for Earthing Kg. 25013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 10014 Jointing Sleeve for Raccoon No. 7515 PG Clamp for Raccoon No. 60016 AI. Binding Wire (10 SWG.) Kg. 12517 Pole Clamp of GI flat (50x6) mm No. 40018 GI Barbed Wire for anticlimbing device Kg. 100019 11 KV Danger Plate (1.6 mm thick) No. 50020 GI Nuts & Bolts with GI washer (Assorted) Kg. 750B1 11 KV Overhead Line Crossing - Line to line / Road: Set 251 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 502 GI wire 8 SWG for cross lacing as per T.S Kg. 2503 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 5004 GI 'I' Hook No. 1005 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 50

Page 4 of 30Page 4 of 30

Page 383: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 1

Schedule-1Rural Electrification works in Karimganj Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KMJ

All prices in Indian RupeesBidder's Name & Address:New 33/11 KV Substation Works (Excluding civil works)

Page 5 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 1

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 15

Page 5 of 30

Page 384: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

Nos 1

6.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,

supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for feeder at GSS))

Nos 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

Page 6 of 30

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder at GSS)

Sets 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For 33 kVfeeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Powertransformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 6 of 30

Page 385: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

Page 7 of 30

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per technical

specifications, approved drawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 4

Page 7 of 30

Page 386: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB

(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessories

complete as per specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

Page 8 of 30

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200 mm²Al. Area) - Panther

Km 0.4

Page 8 of 30

Page 387: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 100

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 2800

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 3

Page 9 of 30

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25 x 6 mm Galvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories completeas per technical specification. (for Power Transformer Neutral, StationTransformer Neutral and Lightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangementsetc as per technical specifications, approved drawings and scope of works.

Set 1

Page 9 of 30

Page 388: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 1

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

Page 10 of 30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Roundand D-spanners with various range, screw drivers with various size one each,earthing rods, etc as required as per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

B. New 33 KV Lines

Page 10 of 30

Page 389: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as pertechnical specification, approved drawings and scope of work.

No 20

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels,back clamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm),GI flats (65x8mm) of given sizes for over head structures as per technicalspecification, approved drawings and scope of work.

MT 0.81

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work.

MT 0.08

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as

per technical specification, approved drawings and scope of work.

Set 80

Page 11 of 30

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as

per technical specification, approved drawings and scope of work.

Set 80

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 20

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.04

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work

Set 48

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 96

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead line andjumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al.alloy Area 173 sqmm ) - Wolf

km 3.30

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG& 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mmlong with nuts & bolts.

Set 1.00

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 500

New 11 KV Lines

Page 11 of 30

Page 390: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 11.36

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.75

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts,2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15mm GI stranded wire etc as required as per technical specification, approveddrawings and scope of work.

Set 250

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 600

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 1200

Page 12 of 30

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 1200

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Saltand other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 100

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.25

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 82.50

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 25

Total Ex-works

Page 12 of 30

Page 391: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Karimganj Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KMJ

Page 13 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

Nos 1

6.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker , supportingstructures, bi-metallic terminal clamps, permanent maintenance platform, marshallingbox etc required as per technical specifications, scope of works and approved drawings(for feeder at GSS))

Nos 1

Page 13 of 30

Page 392: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Sets 1

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along with

junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-

metallic clamps, permanent maintenance platform, marshalling box etc required as per

technical specifications, scope of works and approved drawings (for Feeder at GSS)

Sets 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 14 of 30

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

Page 14 of 30

Page 393: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

Page 15 of 30

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories complete

for feeder breaker protection as per technical specifications, approved drawings and

scope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

Page 15 of 30

Page 394: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware

fittings, hardware, T-claimp etc as per technical specifications, approved drawings and

scope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.4

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVC

sheathed LT Power Cables including their termination materials like glands, lugs, tagging

etc. as per technical specifications, approved drawings and scope of the work.

Mtr 100

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 2800

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3

Page 16 of 30

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 1

Page 16 of 30

Page 395: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

47.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.

Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

Page 17 of 30

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 20

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 0.81

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 0.08

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 80

New 33 KV Lines

Page 17 of 30

Page 396: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 20

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.04

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 48

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 96

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 3.30

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 1.00

C New 11 KV Lines

Page 18 of 30

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 1.00

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 500

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 11.36

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.75

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nos

turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI stranded

wire etc as required as per technical specification, approved drawings and scope of work.

Set 250

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 600

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 1200

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 100

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.25

New 11 KV Lines

Page 18 of 30

Page 397: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 82.50

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 25

Total

Page 19 of 30Page 19 of 30

Page 398: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil profileand necessary soil parameters of sub-station site & recommendations of soilmechanic engineer regarding foundation depth of defferent type of footings withsize including contour survey etc. as per Technical Specification.

PER S/S 1

Schedule-3

All prices in Indian Rupees

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KMJ

(Schedule of rates and prices)Rural Electrification works in Karimganj Project in Assam under DDUGJY Phase-II (REDB works)

Page 20 of 30

1.00

Detail sub-soil investigation report about specific information about the soil profileand necessary soil parameters of sub-station site & recommendations of soilmechanic engineer regarding foundation depth of defferent type of footings withsize including contour survey etc. as per Technical Specification.

PER S/S 1

2.00

Earth work in PSS site for raising low site with approved soil obtained from outsideby truck carriage and filling in layers not more than 150 mm thick,wateringramming etc. complete as directed and specified including payment of landcompensation,forest royalty,sale tax and other duties and taxes as may benecessary.

CuMtr 3900

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5 Cmthickness including supply of materials,spreading, Leveling etc. and labour as perdirection.

Sq. m 1200

5.00

Design and construction of foundation for following power transformer consideringoriginal equipment manufacturer recommendations and as per soil & siterequirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with off load/ on load tap changer

No 1

7.00

Design and construction of foundation for Station Service transformer as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

Page 20 of 30

Page 399: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 2

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc as perTechnical Specification, approved Drawing & Scope of works. Works also includesproviding working platform for operation of breakers and painting.

Nos. 5

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and as perTechnical Specification, approved Drawing & Scope of works

MT 15

Page 21 of 30

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and as perTechnical Specification, approved Drawing & Scope of works

MT 15

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footing includingpreparation of base by providing soling and 10 cm PCC and plastering skinting etc.including supplying ,fitting and fixing barbed wire on top of brick boundary wallwith eight strands of barbed wire 12 SWG fitting to Y cross arm at 2.5 m apartincluding supplying fitting and fixing with galvanized staples 38mm x 38mm x 3mm. Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in all posts. the verticaldistence from top of boundary wall to the top of Y cross arm is 600 mm,3 Nos ofbarbed wire should be fitted in each arm of the Y cross arm & 2 nos. in strraightportion including fabrication,errection & painting of Y cross arm with anticorrosiveready mixed and aluminium paint complete including straightining and tightening ofbarbed wire as directed and instllation of sliding steel gate at the entrance of S/Sboundary wall including supply of materials,painting and labour as per technicalspecification,approved drawing and scope of works.

R/Mtr 220

Page 21 of 30

Page 400: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

12.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 120

Page 22 of 30

12.00

Design and construction of Assam type Control Room Building with PPGI sheet Dynaroofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting & fixing withself drilling,self tapping screws over truss, burse board, gutter,down water rainpipe, bird net, vitified tiles white cement flooring, indoor cable tranch, plainasbestor ceiling (4 mm thickness)oil bound plastic paint washable distemper onsmooth surface of wall applied with POP putty,doors,windows ,ventilation should beAnodised aluminium Indal or equivalent,glass min 5.5 mm thick, Acid proof tiles forbattery room,including water supply alongwith supply and installation of Aqua gurrdwater purifier, sanitary works , septic tank,soak pit,drain appron, sign boardincluding labour etc. .Erection, testing and commissioning of Internal electrificationwork in Substation Control room as per approved drawings, specifications andscope of work by installing, erection, testing and commissioning of fans, exhaustfans, fluorescent lighting, LED lamps, L&F, power points, wiring materials,Distribution Boards, Sub-distribution boards etc. as per Technical Specification,

Sqm 120

13.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide, requireddepth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop, cablesupporting angles including Labour, Reinforcement Steel, MS Angles, Flats, SteelFrame Work, Excavation etc, all complete as per Technical Specification, approvedDrawing & Scope of works.

R/Mtr 150

14.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80 mtr.height, 45 cm bottom width including preparation base by providing soling and10cm PCC and plastering skinting etc. for easy drainage system inside the sub-station premises including supply of all meterials and labour etc. as per TechnicalSpecification, approved Drawing & Scope of works.

R/Mtr 100

15.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manhole coverwith locking and cleaning arrangement including providing pads of size as requiredfor inlet and outlet pipe complete including fitting and fixing all materials and filterto get potable water as per approved drawing and specification.

SET 1

A (Ia) Substation Electrical works

Page 22 of 30

Page 401: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, CuWound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 sets of50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring/ cabling, cable supporting tray on the body, transformer wheels, bushing etc asper Technical Specification, approved Drawing & Scope of works

No 1

2.00Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,aluminium would outdoor type Distribution Transformer (Station Transformer) asper Technical Specification, approved Drawing & Scope of works

Set 1

A (Ib) 33KV Yard

Page 23 of 30

A (Ib) 33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 2

2.00

Design and construction of foundation (as per approved drawings), erection, testingand commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along with junctionbox (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between CT andindoor control panel and required accessories complete as per approved drawings,technical specifications and scope of the work.

Set ofthree

2

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: :: 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

Page 23 of 30

Page 402: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: ::: Power transformer 33 kV VCB with Static Tri-VectorEnergy Meter

No 1

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, Operating Mechanism,Base Channel down Pipe, Jumpering and all required accessories complete as perapproved drawings, technical specifications and scope of the work,

Set 7

Page 24 of 30

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, Operating Mechanism,Base Channel down Pipe, Jumpering and all required accessories complete as perapproved drawings, technical specifications and scope of the work,

Set 7

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

4

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including control and power supply cabling, earthing connection using50x6mm GS flat,Jumpering and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

1

A (Ic) 11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11kV, Outdoor type Vacuum Circuit breaker along withJumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 5

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 5

Page 24 of 30

Page 403: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 4

Page 25 of 30

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of 11kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays andother components etc as per approved drawings, technical specifications and scopeof the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testing andCommissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mountingplatform, jumpering from bus bar, earthing connection using 50x6mm GS flat,hardware, etc as required as per approved drawings, technical specifications andscope of the work.

Set ofthree

5

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 12

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phasePTs) including Jumpering, control and power supply cabling, earthing connectionusing 50x6mm GS flat and required accessories etc., complete as per as perapproved drawings, technical specifications and scope of the work,

Set ofthree

2

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.4

Page 25 of 30

Page 404: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works:::75 x 8 mm MS flat for ground mat

MT 3

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

Page 26 of 30

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up to variousequipment/gantry structures as per Technical Specification, approved Drawing &Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.2

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm long GIpipe earth electrode by providing test link, RCC pit, RCC cover, placed on GI frame,bentonite powder and other accessories complete as per approved drawings,technical specifications and scope of the work for power transformer neutral,station transformer neutral, lightening arresters direct earthing.

Set 25

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutralvoltmeter, three phase ammeter and Selector switches, 200 Amps TPN switch fuseunit as incomer, 32 Amps TPN switches as outgoing feeders suited for number ofcontrol panels, nos of VCB kiosk panel, having 20% spare outgoing feeders, byproviding MS angle 50x50x6 mm structure, cement concrete foundation etc as pertechnical specifications, approved drawings and scope of works.

No 1

Page 26 of 30

Page 405: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 ASP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1 No20 A Industrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specifications andapproved drawings,

No 1

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multi strandcable, terminal connectors, &amp; all other accessories and connectors as per asper approved drawings, technical specifications and scope of the work,

Set 1

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V, 40Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full waverectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as perapproved drawings, technical specifications and scope of the work

Set 1

Page 27 of 30

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V, 40Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full waverectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as perapproved drawings, technical specifications and scope of the work

Set 1

19.00

Erection, testing and commissioning of External electrification works of substationincluding area lighting by 6 No, 12m high steel tubular lighting masts, 2x90 wattsLED flood light fittings on each mast, Junction boxes of the fittings, area lightingpower distribution board, 2 nos. 3 Phase 63 Amp power receptacles, tube wellpower supply, etc as required by laying power cables in underground/aboveground/trenches, construction of foundations for receptacles, distribution boardsetc as required as per approved drawings, specifications and scope of work.

Set 1

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipment comprisesof Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of 4.5Kg Capacityfor Control Room and CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard and 3 Nos. fire buckets of 25 ltr capacity filled with sand and mounted on50x50x6 MS stand duly painted as per Technical Specification, approved Drawing &Scope of works.

SET 1

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 1

Page 27 of 30

Page 406: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

2.01

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope ofwork, approved drawings and specifications for 12 M long steel Tubular poles withwelded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III 1980) anderection of following types of poles for 33 KV overhead line by providing andinstalling danger plate, anti-climbing devices (barbed wire), earthing material (coiland 8SWG GI wire), red oxide & aluminium paint, pole numbering including cementconcrete foundation using cement concreting foundation 1 part cement, 3 partsand, 6 part 40 mm size stone aggregate chips (1:3:6) etc as per scope of work,approved drawings and specifications:

No 6

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blasting isnot required as per scope of work, approved drawings and specifications for 12 Mlong steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KV overheadline by providing and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 14

Page 28 of 30

3.01

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blasting isnot required as per scope of work, approved drawings and specifications for 12 Mlong steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KV overheadline by providing and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 14

5.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm, topclamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 0.81

7.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 80

8.01Erection, testing and commissioning of 33 kV polymer Pin insulator including theirGI hardware fittings as per technical specification, approved drawings and scope ofwork.

Set 96

8.02Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 48

Page 28 of 30

Page 407: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

10.01

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAAC Wolf Conductor of following sizes includingjointing sleeves, helical formed fittings, jumpering and by providing & erecting PGClamps etc as required as per approved drawings, scope of work and technicalspecifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt. km 1

11.01

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plates onGI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 20

12.00

Erection of guading for line Crossing-Line to line, line to road with items, GI AngleCross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm longwith nuts & bolts.

Set 1

Page 29 of 30

12.00

Erection of guading for line Crossing-Line to line, line to road with items, GI AngleCross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm longwith nuts & bolts.

Set 1

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 25

2.01

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No. 150

3.01

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed with excavatedearth etc per pole at the bottom and surrounding the pole with thorough &vigorous ramming. The gaps between the boulders are to be filled by earth as perscope of work, approved drawings and technical specifications. 8.5 mtr PSC pole asper approved GTP.

No 350

6.00 Erection of galvanised pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials for over head structures.

MT 11.36

7.01 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GI wirefor earthing,

Set 100

9.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HT stayguy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GSstay rod & 7/10 swg GI stranded wire etc as required by providing boulder packingas per scope of the work, technical specifications and approved drawings.

Set 250

Page 29 of 30

Page 408: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit

ErectionCharges

TotalErectionCharges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%)

8=(6+7)x@___%

9

10.01Erection, testing and commissioning of 11 kV Polymaric Pin insulator including theirhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 1200

10.02Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings and scopeof work.

Set 600

11.00

Laying out, tensioning, binding of conductor and tightening of stays and stringing,testing and commissioning of AAA Raccon Conductor including jointing sleeves,helical formed fittings, jumpering and by fitting PG Clamps etc as required as perapproved drawings, scope of work and technical specifications. (7/3.81 mm, 79.80Sqmm)

Ckt. Km 25

12.00

Excavation, Erection, testing and commissioning of Protective guarding as per RECconstruction standard drawing No A-1 to be provided at locations where 11KV/33KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guy with 7/3.14 mmwire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe1800 mm long, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire,8 SWG wire for cross lacing as per scope of work, approved drawings and technicalspecifications.

Set 25

Total

Page 30 of 30

12.00

Excavation, Erection, testing and commissioning of Protective guarding as per RECconstruction standard drawing No A-1 to be provided at locations where 11KV/33KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guy with 7/3.14 mmwire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe1800 mm long, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire,8 SWG wire for cross lacing as per scope of work, approved drawings and technicalspecifications.

Set 25

Total

Page 30 of 30

Page 409: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT NewS/S,1x5

MVADotama(Ko

krajhar)

New S/S,1x5MVA

Patgaon(Kokrajhar)

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 1 22 Boundary wall inculing Gate R/Mt 220 220 4403 Construction of Assam Type control room building with best

quality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120 240

4 Water supply: Deep well with 1 HP motor- Pump,Overhead waterresurvior capacity 2x500 Ltr over the GI staging with necesssarypipeline with connection,stand & power connection appliances.

set 1 1 2

5 Approach road , 4.0 Mtr width Mtr 50 50 1006 Drainage System Mtr 100 100 2007 Foundation of Pad for 33/11KV power transformer No 1 1 28 Foundation of Pad for 33/.433 KV power transformer No 1 1 29 Const. of Cable Trenches as per specification with following sizes

: -

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Kokrajhar Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S 1x5 MVA at Dotama & New S/s 1x5 MVA at Patgaon within the KokrajharDistrict under DDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KOK

Page 1 of 30

9 Const. of Cable Trenches as per specification with following sizes: -

(a) Width 600mm x Depth . RM 150 150 30010 Gravelling of switch yard, depth 22.5 Cm with crushed stone size

40 mmSqMtr.

1200 1200 2400

11 Earth Filling CM 2000 3900 590012 Sign Board, size: 4 feetx3 feet No 1 1 2

EQUIPMENT & MATERIALS FOR CONSTRUTION OFSWITCHYARD13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1 2

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG,ABB, Siemens, Schneider make

Nos. 1 2 3

14(b) 33KV,1250A, 25 KA SF6 Circuit Breaker(GSS) preferably CG,ABB, Siemens, Schneider make

Nos. 1 1

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 1 1 2

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1 117 33 KV Current Transformer ( 400-200/1-1A for Feeder) Set 1 118 33KV , 10 KA Lightning Arrester with chagre monitor and GI

mounting(set of 3 units) Station TypeSet 3 3 6

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1 2

20 33 KV ,1250 Amp Isolator with earth blade Set 2 2 421 33 KV ,1250 Amp Isolator without earth blade Set 5 5 1022 33KV Transformer Panels preferably

CG,ABB,Siemens,Schneider makeNos. 1 1 2

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 1 1 2

24 33 KV Potential Transformer Set 1 1 225 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably

CG, ABB, Siemens, Schneider makeNo. 5 5 10

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4 8

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 1 1 2

Page 1 of 30

Page 410: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT NewS/S,1x5

MVADotama(Ko

krajhar)

New S/S,1x5MVA

Patgaon(Kokrajhar)

TotalQuantity

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Boxand GI Structure

Set 1 1 2

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4 8

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4 8

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 8 8 16

37 11 KV Out door Potential Transformer Set 2 2 438 11 KV LA Line Type (set of 3 units) Set 4 4 839 11 KV LA Station Type (set of 3 units) Set 1 1 241 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 242 Battery charger etc. No. 1 1 249 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4100 4100 820050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800 2800 560051 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,

PVC insulated and PVC sheathed cableMtr 100 100 200

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 18 15 3354 33 KV Gantry Structure Extension MT ext. at PSS 2 255 Station service transformer, 33/.433KV,100 KVA Nos. 1 1 256 Distrbutiob Box Nos. 1 1 257 LTACDB ,DCDB Etc. Set 1 1 258 Earthing & Grounding conductor as per Approved Electrical

Layout for each sub-station witha 75 x8 mm MS flat for ground mat MT 3 3 6

Page 2 of 30

a 75 x8 mm MS flat for ground mat MT 3 3 6b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 2.00c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 2d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.4059 40 mm dia,3000 mm length GI Earth Pipe No 25 25 5060 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.8061 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of

3 nos.30 30 60

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54 108

63 Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1 2

64 External Electrification at station yard lighting with 12 Nos lightening 90 Watt LED Lamp .set 1 1 265 Substation Tools and Plants like megger, earth tester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers, earthing rods, earth mat etc as required as per scope of work.Set 1 1 266 New 33&11 KV Line Joyma GSS Serfungguri

SSa 33 KV Line Km 21 21 42b 11 KV Line Km 8 8 16

Page 2 of 30

Page 411: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 42.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 8402 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 3363 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 7564 Jam Clamp of GI Flat 65x6 mm Pair 21845 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 5046 33 KV Polymeric Pin Insulator No. 40327 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 20168 Tension Clamp for Wolf Conductor No. 10089 AAA Wolf Conductor (19/3.40 mm) Km. 138.60

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 420

11 Guy Insulator (HT) No. 84012 Stay Wire 7/4.0 mm Kg 3360

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as perT.S.

Mtr. 2520

14 Jointing Sleeve for Wolf No. 126

Rural Electrification works in Kokrajhar Project in Assam under DDUGJY Phase-II (REDB works)

For New S/S, 2x5 MVA at Uttar Barpeta (Barpeta) and New S/S, 2x5 MVA at Gobardhana (Barpeta)

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KOK

Page 3 of 30

14 Jointing Sleeve for Wolf No. 12615 PG Clamp for Wolf (Alcon 80) No. 100816 Al. Binding Wire (10 SWG.) Kg 25217 GI Nuts & Bolts (assorted) Kg 336018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 168019 33 KV Danger Plate (1.6 mm thick) No. 84020 Barbed Wire Kg 168021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 84022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 840A1 33 KV Overhead Line Crossing - Line to line / Road: Set 421 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 842 GI wire 8 SWG for cross lacing as per T.S Kg. 4203 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 8404 GI 'I' Hook No. 1685 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 84B New 11 kV Line Ckt. Km. 16.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 3202 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 1923 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 1284 Composite Polymeric 11 kV Pin Insulator No. 7685 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 3846 Tension Clamp for Raccoon No. 3847 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 52.80

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 160

9 HT Guy Insulator No. 16010 GI Stay wire 7/3.15 mm Kg. 1280

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as perT.S.

Mtr. 640

12 GI wire 6 SWG for Earthing Kg. 160

Page 3 of 30

Page 412: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT QTY

13 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 6414 Jointing Sleeve for Raccoon No. 4815 PG Clamp for Raccoon No. 38416 AI. Binding Wire (10 SWG.) Kg. 8017 Pole Clamp of GI flat (50x6) mm No. 25618 GI Barbed Wire for anticlimbing device Kg. 64019 11 KV Danger Plate (1.6 mm thick) No. 32020 GI Nuts & Bolts with GI washer (Assorted) Kg. 480B1 11 KV Overhead Line Crossing - Line to line / Road: Set 161 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 322 GI wire 8 SWG for cross lacing as per T.S Kg. 1603 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 3204 GI 'I' Hook No. 645 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 32

Page 4 of 30Page 4 of 30

Page 413: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer,transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 2

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Kokrajhar Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KOK

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 30

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer,transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 2

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 2

3.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 35

Page 5 of 30

Page 414: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 3

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,

supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for feeder at GSS))

Nos 1

6.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Feeder)

Sets 1

Page 6 of 30

6.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Feeder)

Sets 1

7.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 2

8.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of worksand approved drawings (for Feeder at GSS)

Sets 1

9.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specifications andscope of works controlling: For 33kV feeder VCB with Static Tri-Vector Energy Meter

No 2

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specifications andscope of works controlling: ForPower transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 2

Page 6 of 30

Page 415: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

11.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withEarth Blade)

Set 4

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 10

13.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

6

14.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

2

Page 7 of 30

13.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

6

14.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

2

15.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

2

16.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker, supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.

No 10

17.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (for Transformer)

Set 2

18.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 8

Page 7 of 30

Page 416: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

19.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

2

20.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

8

21.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB

(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessories

complete as per specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 2

22.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 8

Page 8 of 30

22.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 8

23.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 8

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 16.0

25.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

4

26.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm(200 mm² Al. Area) - Panther

Km 1

27.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 200

Page 8 of 30

Page 417: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

28.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 5600

29.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 8200

30.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 6.00

31.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 2

Page 9 of 30

31.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 2

32.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 2

33.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0

34.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,

RCC cover, placed on GI frame, bantonide powder and other accessories

complete as per technical specification. (for Power Transformer Neutral,

Station Transformer Neutral and Lightening Arresters direct earthing)

No 50

35.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders, mountingarrangements etc as per technical specifications, approved drawings andscope of works.

Set 2

36.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clampsand hardware as per scope of work, technical specifications and approveddrawings,

Set 2

Page 9 of 30

Page 418: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

37.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

60

38.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

108

39.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-

battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,

terminal connectors, & all other accessories and connectors as per technical

specifications, approved drawings and scope of works.

Set 2

40.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 2

Page 10 of 30

40.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectificationfor 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as pertechnical specifications, approved drawings and scope of works.

Set 2

41.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 2

42.00

Substation Tools and Plants like One 5/2.5 KV megger, One earthtester, One Multimeter, One Tong tester, One set of Box spanner,One set each Round and D-spanners with various range, screwdrivers with various size one each, earthing rods, etc as required asper scope of work.

Set 2

43.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 2

B. New 33 KV Lines

1.00

12 M long steel Tubular poles with welded steel base plate of Designation 540

SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per

technical specification, approved drawings and scope of work.

No 840.00

Page 10 of 30

Page 419: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 34

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work.

MT 3

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete

as per technical specification, approved drawings and scope of work.

Set 3360.00

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 840

Page 11 of 30

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete

as per technical specification, approved drawings and scope of work.

Set 3360.00

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 840

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 2

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per

technical specification, approved drawings and scope of workSet 2016.00

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 4032.00

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al.alloy Area 173 sqmm ) - Wolf

km 139

10.00

Line Crossing-Line to line, line to road with items, GI Angle CrossArm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earthPipe 100 mm dia, 1800 mm long with nuts & bolts.

Set

42C New 11 KV Lines

1.008.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 320.00

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 7.28

Page 11 of 30

Page 420: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue Added

Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 160

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per

technical specification, approved drawings and scope of work.Set 384

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 768

7.00

100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt

and other accessories complete as per technical specification, approved

drawings and scope of work for 11 KV line earthing

Set 64

Page 12 of 30

7.00

100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt

and other accessories complete as per technical specification, approved

drawings and scope of work for 11 KV line earthing

Set 64

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.16

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required asper technical specification, approved drawings and scope of work. (7/3.81mm, 79.80 Sqmm)

Km 52.80

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 16

Total Ex-works

Page 12 of 30

Page 421: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

New 33/11 KV Substation Works (Excluding civil works)A. 33/11 KV Substation Works

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators, Ventexplosion plug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels, LV/HVbushing etc as required as per technical specifications, approved drawings andscope of the work.

No 2

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Kokrajhar Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KOK

Page 13 of 30

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators, Ventexplosion plug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels, LV/HVbushing etc as required as per technical specifications, approved drawings andscope of the work.

No 2

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 2

3.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structuralsteel members and bolts shall be galvanized after fabrication as per IS:4759 andzinc coating shall not be less than 610gm/sq. meter for all structural steelmembers. All L45x45x5 will have 23 mm back mark. All L50x50x6 will have28mm back mark. 3.5mm spring washers are to be used under each nut, structuralsteel shall conform to IS 2026. All weld shall be 6mm filled weld unless specifiedotherwise. All nuts and bolts shall be of property class 5.6 of IS 1367. Plainwashers shall be as per IS 2016 & spring washers shall be IS: 3063 as pertechnical specifications, scope of works and approved drawings..

MT 35

Page 13 of 30

Page 422: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

4.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

No 3

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for feeder at GSS))

No 1

6.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder)

Set 1

Page 14 of 30

6.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder)

Set 1

7.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer)

Set 2

8.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshalling boxetc required as per technical specifications, scope of works and approveddrawings (for Feeder at GSS)

Set 1

9.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scope ofworks controlling: For 33 kV feeder VCBwith Static Tri-Vector Energy Meter

No 2

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scope ofworks controlling: For Powertransformer 33 kV VCB with Static Tri-Vector Energy Meter

No 2

Page 14 of 30

Page 423: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

11.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 4

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 10

13.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

6

14.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

2

Page 15 of 30

14.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

2

15.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phase PTs),bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

2

16.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.

No 10

17.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshalling box,and required accessories complete as per technical specifications, approveddrawings and scope of the works. (for Transformer)

Set 2

18.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshalling box,and required accessories complete as per technical specifications, approveddrawings and scope of the works.(for Feeder)

Set 8

Page 15 of 30

Page 424: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

19.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

2

20.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

8

21.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer

Breaker) consisting of A-meter, volt-meter, Relays & accessories complete as per

specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 2

22.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technical specifications,approved drawings and scope of works. For 11 kV feeder VCB withStatic Tri-Vector Energy Meter

No 8

Page 16 of 30

22.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technical specifications,approved drawings and scope of works. For 11 kV feeder VCB withStatic Tri-Vector Energy Meter

No 8

23.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (With EarthBlade)

Set 8

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 16

25.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phase PTs),bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

4

26.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200mm² Al. Area) - Panther

Km 0.8

Page 16 of 30

Page 425: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

27.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated andPVC sheathed LT Power Cables including their termination materials like glands,lugs, tagging etc. as per technical specifications, approved drawings and scope ofthe work.

Mtr 200

28.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC

sheathed LT Control cables including their termination materials like glands, lugs

etc. as per technical specifications, approved drawings and scope of the work

Mtr 5600

29.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC

sheathed LT Control cables including their termination materials like glands, lugs

etc. as per technical specifications, approved drawings and scope of the work

Mtr 8200

30.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works ::75x 8 mm GI flat for ground mat

MT 6

Page 17 of 30

30.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works ::75x 8 mm GI flat for ground mat

MT 6

31.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works:: 50x 6 mm Galvanized GI flat (risers)

MT 2

32.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works ::25x 6 mm Galvanized GI flat (risers)

MT 2

33.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 0.4

34.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories complete asper technical specification. (for Power Transformer Neutral, Station TransformerNeutral and Lightening Arresters direct earthing)

No 50

35.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangements etcas per technical specifications, approved drawings and scope of works.

Set 2

Page 17 of 30

Page 426: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

36.00

Outdoor type Distribution Box for station transformer comprising 200 A switch

fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor

controlled yard lighting timer unit, tri-vector electronic energy meter with

suitable CT, control/power cabling and terminals, 1 No 20 A Industrial socket and

switch for local power supply requirements, mounting channel, clamps and

hardware as per scope of work, technical specifications and approved drawings,

Set 2

37.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

60

38.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

108

39.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-batterywiring using 30 sqm, 1.1 kv, copper single core multi strand cable, terminalconnectors, & all other accessories and connectors as per technical specifications,approved drawings and scope of works.

Set 2

Page 18 of 30

39.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-batterywiring using 30 sqm, 1.1 kv, copper single core multi strand cable, terminalconnectors, & all other accessories and connectors as per technical specifications,approved drawings and scope of works.

Set 2

40.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 2

41.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation410 – SP - 60, complete as per technical specifications, approved drawings andscope of the work.

Set 2

42.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Round andD-spanners with various range, screw drivers with various size one each, earthingrods, etc as required as per scope of work.

Set 2

43.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 2

Page 18 of 30

Page 427: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @B. New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technicalspecification, approved drawings and scope of work.

No 840

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, backclamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats(65x8mm) of given sizes for over head structures as per technical specification,approved drawings and scope of work.

MT 34

3.00GI Nuts, bolts and washers as per technical specification, approved drawings andscope of work.

MT 3

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchorplate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mmdiameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as pertechnical specification, approved drawings and scope of work.

Set 3360

Page 19 of 30

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchorplate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mmdiameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as pertechnical specification, approved drawings and scope of work.

Set 3360

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 840

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.68

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work

Set 2016

8.0033 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 4032

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead line andjumpers as required as per technical specification, approved drawings and scopeof work Size:: 19/3.40 (Al. alloy Area173 sqmm ) - Wolf

km 138.60

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 42.00

C New 11 KV Lines

Page 19 of 30

Page 428: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 320

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,angle, flats and all other GI materials shown in BOQ for over head structures asper technical specification, approved drawings and scope of work.

MT 7.28

3.00Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.48

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GIstranded wire etc as required as per technical specification, approved drawingsand scope of work.

Set 160

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 384

Page 20 of 30

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 384

6.00Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 768

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt andother accessories complete as per technical specification, approved drawings andscope of work for 11 KV line earthing

Set 64

8.006 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.16

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, Tension Clamps,bi-metallic clamp etc. for overhead line and jumpers as required as per technicalspecification, approved drawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 52.80

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mm diameterEye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meter long, 6 SWGGI wires for earthing connection, 6 SWG wire for guard wire, 8 SWG wire forcross lacing.

set 16.00

Total

Page 20 of 30

Page 429: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A-I 33/11 KV Grid Substation worksA-Ia Civil works:

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PERS/S

2

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 5900

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/KOK

(Schedule of rates and prices)Rural Electrification works in Kokrajhar Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian Rupees

Page 21 of 30

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 5900

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 2400

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 2

5.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 2

6.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 4

Page 21 of 30

Page 430: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 10

8.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 33

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 440

Page 22 of 30

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 440

10.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 240

Page 22 of 30

Page 431: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

11.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 300

12.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 200

13.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 100

14.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 2

Page 23 of 30

14.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 2

A (Ib) Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 2

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 2

33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 4

Page 23 of 30

Page 432: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

4

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 2

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 2

Page 24 of 30

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 2

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 14

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

8

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

11KV Yard

Page 24 of 30

Page 433: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 10

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 10

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 2

Page 25 of 30

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 2

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 8

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

10

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 24

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

4

Page 25 of 30

Page 434: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.8

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 200

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 6

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 2

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 2

Page 26 of 30

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 2

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 2

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.4

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 50

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 2

Page 26 of 30

Page 435: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 2

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 2

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 2

Page 27 of 30

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 2

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 2

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 2

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 42.00

Page 27 of 30

Page 436: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 252

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 588

Page 28 of 30

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 588

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 33.77

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 3360

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 4032

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 2016

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

42.00

Page 28 of 30

Page 437: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 840

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 42.00

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 16.00

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 96

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 224

Page 29 of 30

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 96

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 224

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 7.28

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 64

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 160

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 768

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 384

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

16.00

Page 29 of 30

Page 438: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 16.00

Total

Page 30 of 30Page 30 of 30

Page 439: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT New S/S,1x5 MVA

Nelli(Morigaon)

New S/S,1x5 MVA

Jagi BhakatGaon

(Morigaon)

New S/S,1x5 MVAHahchara

(Morigaon)

Augmen-tation ofMorigaon

atMorigaon

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 1 1 32 Boundary wall inculing Gate R/Mt 220 220 220 660

3

Construction of Assam Type control roombuilding with best quality Dyna roof (blueclour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120 120 360

4

Water supply: Deep well with 1 HP motor-Pump,Overhead water resurvior capacity2x500 Ltr over the GI staging withnecesssary pipeline with connection,stand &power connection appliances.

set 1 1 1 3

5 Approach road , 4.0 Mtr width Mtr 50 50 50 1506 Drainage System Mtr 100 100 100 300

7 Foundation of Pad for 33/11KV powertransformer

No 1 1 1 3

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Morigaon Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Morigaon District under DDUGJY-II/XII Plan Scheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/MRG

Page 1 of 33

7 Foundation of Pad for 33/11KV powertransformer

No 1 1 1 3

8 Foundation of Pad for 33/.433 KV powertransformer

No 1 1 1 3

9 Const. of Cable Trenches as perspecification with following sizes : -

(a) Width 600mm x Depth . RM 150 150 150 450

10 Gravelling of switch yard, depth 22.5 Cmwith crushed stone size 40 mm

SqMtr.

1200 1200 1200 500 4100

11 Earth Filling CM 3900 3900 3900 1170012 Sign Board, size: 4 feetx3 feet No 1 1 1 1 4

EQUIPMENT & MATERIALS FORCONSTRUCTION OF SWITCHYARD

13(a) 33/11KV 5 MVA Power Transformer Nos. 1 1 1 313 (c) 33/11KV 10 MVA Power Transformer Nos. 1 1

14(a)33KV,1250A, 25 KA Vaccum Circuit Breakerpreferably CG, ABB, Siemens, Schneidermake

Nos. 1 1 2 1 5

14(b)33KV,1250A, 25 KA SF6 CircuitBreaker(GSS) preferably CG, ABB, Siemens,Schneider make

Nos. 1 1 2

15 33 KV Current Transformer (400-200/5-5-5Amps for Power Tr.)

Set 1 1 1 1 4

16 33 KV Current Transformer ( 400-200/5-5Afor Feeder)

Set 1 1

17 33 KV Current Transformer ( 400-200/1-1Afor Feeder)

Set 1 1 2

1833KV , 10 KA Lightning Arrester with chagremonitor and GI mounting(set of 3 units)Station Type

Set 3 3 3 1 10

1933KV , 10 KA Lightning Arrester with chagremonitor and GI mounting(set of 3 units)Line Type

Set 1 1 1 3

Page 1 of 33

Page 440: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT New S/S,1x5 MVA

Nelli(Morigaon)

New S/S,1x5 MVA

Jagi BhakatGaon

(Morigaon)

New S/S,1x5 MVAHahchara

(Morigaon)

Augmen-tation ofMorigaon

atMorigaon

TotalQuantity

20 33 KV ,1250 Amp Isolator with earth blade Set 2 2 2 6

21 33 KV ,1250 Amp Isolator without earthblade

Set 5 5 5 1 16

22 33KV Transformer Panels preferablyCG,ABB,Siemens,Schneider make

Nos. 1 1 1 1 4

23 33KV Feeder Panels preferablyCG,ABB,Siemens,Schneider make

Nos. 1 1 1 3

24 33 KV Potential Transformer Set 1 1 1 3

2511KV, Vaccum Circuit Breaker withMarshelling Box.preferably CG, ABB,Siemens, Schneider make

No. 5 5 5 15

26Control & Relay panel for 11 KV out doorFeeder VCB preferably CG, ABB,Siemens,Schneider make

No. 4 4 4 12

27Control & Relay panel for 11 KV out doorTransformer VCB preferably CG,ABB,Siemens,Schneider make

No. 1 1 1 3

28 11 Kv Current Transformer 600-300/5-5-5Awith Marshilling Box and GI Structure

Set 1 1 1 3

29 11 Kv Current Transformer 300-150/5-5Awith Marshilling Box and GI Structure

Set 4 4 4 12

30 11 KV Isolator Double break with earthswitch with GI structure(800A)

Set 4 4 4 12

31 11 KV Isolator Double break without earthswitch with GI structure(800A)

Set 8 8 8 1 25

Page 2 of 33

31 11 KV Isolator Double break without earthswitch with GI structure(800A)

Set 8 8 8 1 25

37 11 KV Out door Potential Transformer Set 2 2 2 638 11 KV LA Line Type (set of 3 units) Set 4 4 4 1239 11 KV LA Station Type (set of 3 units) Set 1 1 1 1 4

41 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 1 1 3

42 Battery charger etc. No. 1 1 1 3

49 Control Cable Copper 7 Core 2.5 Sq mm(avg.80m)

Mtr 4100 4100 4100 400 12700

50 Control Cable Copper 4 Core 2.5 Sqmm(avg.80m)

Mtr 2800 2800 2800 300 8700

513.5 Core 95 Sq. mm armored, strandedaluminium conductor, PVC insulated andPVC sheathed cable

Mtr 100 100 100 300

52 Substation G.I.steel structure as per T.S.(33& 11 KV Bus)

MT 15 15 15 45

54 33 KV Gantry Structure Extension Set 7 7 14

55 Station service transformer, 33/.433KV,100KVA

Nos. 1 1 1 3

56 Distrbutiob Box Nos. 1 1 1 357 LTACDB ,DCDB Etc. Set 1 1 1 3

58Earthing & Grounding conductor as perApproved Electrical Layout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3 3 9b 50 x 6 mm Galvanized GS flat (risers) MT 1 1 1 3c 25 x 6 mm Galvanized GI flat (risers) MT 1 1 1 3d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2 0.2 0.659 40 mm dia,3000 mm length GI Earth Pipe No 25 25 25 7560 ACSR Panther Conductor for Bus bar Km 0.4 0.4 0.4 1.2

61 33KV Disc Insulators,fittings,clamps,etc.(90KN)

Set of3 nos.

30 30 30 90

Page 2 of 33

Page 441: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. ITEM DESCRIPTION UNIT New S/S,1x5 MVA

Nelli(Morigaon)

New S/S,1x5 MVA

Jagi BhakatGaon

(Morigaon)

New S/S,1x5 MVAHahchara

(Morigaon)

Augmen-tation ofMorigaon

atMorigaon

TotalQuantity

62 11KV Disc Insulators,fittings,clamps,etc.(70KN)

Set of3 nos.

54 54 54 162

63

Fire Fighting Equipment comprises of Fournos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5KgCapacity for Control Room,two sets of firebuckets set including their stand for ControlRoom & Station Yard and One no. CO2Type Trolley Mounted of 22.5 Kg Capacityfor Switch Yard.

Set 1 1 1 3

64External Electrification at station yardlighting with 12 Nos lightening 90 Watt LEDLamp .

set 1 1 1 1 4

65

Substation Tools and Plants like megger,earth tester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers,earthing rods, earth mat etc as required asper scope of work.

Set 1 1 1 3

66 New 33&11 KV Line BaghjapGSS

BaghjapGSS

LILO

a 33 KV Line Km 20 7 11 38b 11 KV Line Km 10 17 11 38c 33 KV Rly-Xing No 1 1g 33 KV Gantry Structure (Exiention) No 1 1 2

Page 3 of 33Page 3 of 33

Page 442: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 38.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 7602 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 3043 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 6844 Jam Clamp of GI Flat 65x6 mm Pair 19765 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 4566 33 KV Polymeric Pin Insulator No. 36487 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 18248 Tension Clamp for Wolf Conductor No. 9129 AAA Wolf Conductor (19/3.40 mm) Km. 125.40

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 380

11 Guy Insulator (HT) No. 76012 Stay Wire 7/4.0 mm Kg 3040

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 2280

Rural Electrification works in Morigaon Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Morigaon District under DDUGJY-II/XII PlanScheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/MRG

Page 4 of 33

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 2280

14 Jointing Sleeve for Wolf No. 11415 PG Clamp for Wolf (Alcon 80) No. 91216 Al. Binding Wire (10 SWG.) Kg 22817 GI Nuts & Bolts (assorted) Kg 304018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 152019 33 KV Danger Plate (1.6 mm thick) No. 76020 Barbed Wire Kg 152021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 76022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 760A1 33 KV Overhead Line Crossing - Line to line / Road: Set 381 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 762 GI wire 8 SWG for cross lacing as per T.S Kg. 3803 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 7604 GI 'I' Hook No. 1525 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 76B New 11 kV Line Ckt. Km. 38.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 7602 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 4563 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 3044 Composite Polymeric 11 kV Pin Insulator No. 18245 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 9126 Tension Clamp for Raccoon No. 9127 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 125.40

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 380

9 HT Guy Insulator No. 38010 GI Stay wire 7/3.15 mm Kg. 3040

Page 4 of 33

Page 443: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 1520

12 GI wire 6 SWG for Earthing Kg. 38013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 15214 Jointing Sleeve for Raccoon No. 11415 PG Clamp for Raccoon No. 91216 AI. Binding Wire (10 SWG.) Kg. 19017 Pole Clamp of GI flat (50x6) mm No. 60818 GI Barbed Wire for anticlimbing device Kg. 152019 11 KV Danger Plate (1.6 mm thick) No. 76020 GI Nuts & Bolts with GI washer (Assorted) Kg. 1140B1 11 KV Overhead Line Crossing - Line to line / Road: Set 381 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 762 GI wire 8 SWG for cross lacing as per T.S Kg. 3803 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 7604 GI 'I' Hook No. 1525 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 76

Page 5 of 33Page 5 of 33

Page 444: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A 33/11 KV Substation Works

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservatortank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthingstrips {(with braided conductor on bushing end), isolating link, isolationwith insulators, Vent explosion plug, control wiring between sensingequipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 3

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Morigaon Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/MRG

All prices in Indian RupeesBidder's Name & Address:

Page 6 of 33

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservatortank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthingstrips {(with braided conductor on bushing end), isolating link, isolationwith insulators, Vent explosion plug, control wiring between sensingequipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 3

2.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 10.0MVA with on load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservatortank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthingstrips {(with braided conductor on bushing end), isolating link, isolationwith insulators, Vent explosion plug, control wiring between sensingequipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as pertechnical specifications, approved drawings and scope of the work.

No 1

3.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 3

Page 6 of 33

Page 445: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication asper IS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of worksand approved drawings..

MT 59

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 5

Page 7 of 33

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuitbreaker , supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer &feeder)

Nos 5

6.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker ,

supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope

of works and approved drawings (for feeder at GSS))

Nos 2

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Feeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 4

Page 7 of 33

Page 446: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

9.00

36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scopeof works and approved drawings (for Feeder at GSS)

Sets 2

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 3

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 4

Page 8 of 33

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciationrelays and other components etc as per approved drawings, specificationsand scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 4

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings (withEarth Blade)

Set 6

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(without Earth Blade)

Set 16

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

10

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

3

Page 8 of 33

Page 447: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per

technical specifications, approved drawings and scope of the works.

No 15

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works. (forTransformer)

Set 3

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 12

Page 9 of 33

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformeralong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.(for Feeder)

Set 12

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

12

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 3

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 12

Page 9 of 33

Page 448: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(With Earth Blade)

Set 12

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories completeas per technical specifications, scope of works and approved drawings(Without Earth Blade)

Set 25

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

6

Page 10 of 33

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential

Transformer along with junction box (1 no junction box for 3 no of 1-phase

PTs), bi-metallic clamp and required accessories etc., complete as per

technical specifications, approved drawings and scope of the works.

Set ofthree

6

27.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm(200 mm² Al. Area) - Panther

Km 1.2

28.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including their terminationmaterials like glands, lugs, tagging etc. as per technical specifications,approved drawings and scope of the work.

Mtr 300

29.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 8700

30.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings andscope of the work

Mtr 12700

31.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::75 x 8 mm GI flat for ground mat

MT 9

32.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 50 x 6 mm Galvanized GI flat (risers)

MT 3

Page 10 of 33

Page 449: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

33.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks ::25 x 6 mm Galvanized GI flat (risers)

MT 3

34.00Earthing & Grounding conductor as per Approved Electrical Layout for eachsub-station as per technical specifications, approved drawings and scope ofworks:: 25mm dia GI rod 3 m long for earth mat

MT 0.6

35.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit,

RCC cover, placed on GI frame, bantonide powder and other accessories

complete as per technical specification. (for Power Transformer Neutral,

Station Transformer Neutral and Lightening Arresters direct earthing)

No 75

36.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 3

Page 11 of 33

36.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer,32 Amps TPN switches as outgoing feeders suited for number of controlpanels, nos of VCB kiosk panel, having 20% spare outgoing feeders,mounting arrangements etc as per technical specifications, approveddrawings and scope of works.

Set 3

37.00

Outdoor type Distribution Box for station transformer comprising 200 Aswitch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A,contactor controlled yard lighting timer unit, tri-vector electronic energymeter with suitable CT, control/power cabling and terminals, 1 No 20 AIndustrial socket and switch for local power supply requirements, mountingchannel, clamps and hardware as per scope of work, technical specificationsand approved drawings,

Set 3

38.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

90

39.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

162

40.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 3

Page 11 of 33

Page 450: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

41.00

110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification

for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per

technical specifications, approved drawings and scope of works.

Set 3

42.00

External Electrification in switch yard area including power receptacles,station yard lighting with 6 Nos lightening mast (fitted with 2x90 watts LEDfittings) made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III)of designation 410 – SP - 60, complete as per technical specifications,approved drawings and scope of the work.

Set 4

43.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 1

44.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 3

Page 12 of 33

44.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester,One Multimeter, One Tong tester, One set of Box spanner, One set eachRound and D-spanners with various range, screw drivers with various sizeone each, earthing rods, etc as required as per scope of work.

Set 3

45.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type(6 Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 3

B New 33 KV Lines

1.00

12 M long steel Tubular poles with welded steel base plate of Designation

540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as

per technical specification, approved drawings and scope of work.

No 760

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guardingchannels, back clamp etc made of GI Channels (100x50x6mm), GI angle(65x65x6mm), GI flats (65x8mm) of given sizes for over head structures asper technical specification, approved drawings and scope of work.

MT 30.56

3.00 GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 3.04

Page 12 of 33

Page 451: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete

as per technical specification, approved drawings and scope of work.

Set 3040

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 760

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.52

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas

per technical specification, approved drawings and scope of workSet 1824

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 3648

Page 13 of 33

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 3648

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead lineand jumpers as required as per technical specification, approved drawingsand scope of work Size::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 125.40

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia,1800 mm long with nuts & bolts.

Set 38.00

11.00

33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.140 kmeach) USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND100 MM HDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLECABLE JOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GIWIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING ASREQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPEOF THE WORK including Way leave/ Supervision Charges payable toRailway Department on actual basis.

Set 1

C New 11 KV Lines

Page 13 of 33

Page 452: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

1.008.5 m PSC Poles Support for 11 KV overhead line as per technicalspecification, approved drawings and scope of work alongwith Danger Plateand Barbed Wire as per approved GTP, as per state practice.

No. 760

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel crossarm, angle, flats and all other GI materials shown in BOQ for over headstructures as per technical specification, approved drawings and scope ofwork.

MT 17.27

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 1.14

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 380

Page 14 of 33

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nutbolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &7/3.15 mm GI stranded wire etc as required as per technical specification,approved drawings and scope of work.

Set 380

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas

per technical specification, approved drawings and scope of work.Set 912

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 1824

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal,Salt and other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 152

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.38

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAARaccoon Conductors with Jointing sleeves, binding materials, PG clamps,Tension Clamps, bi-metallic clamp etc. for overhead line and jumpers asrequired as per technical specification, approved drawings and scope ofwork. (7/3.81 mm, 79.80 Sqmm)

Km 125.40

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle crossarm (50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 38.00

Total Ex-works

Page 14 of 33

Page 453: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9New 33/11 KV Substation Works (Excluding civil works)

A 33/11 KV Substation Works1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with off

load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 3

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Morigaon Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/MRG

Page 15 of 33

1.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA with offload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 3

2.00 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 10.0 MVA with onload tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

3.00 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 3

4.00 Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 59

Page 15 of 33

Page 454: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 95.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,

supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 5

6.00 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type SF6 Circuit breaker , supportingstructures, bi-metallic terminal clamps, permanent maintenance platform, marshallingbox etc required as per technical specifications, scope of works and approved drawings(for feeder at GSS))

No 2

7.00 36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Set 1

8.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 4

Page 16 of 33

8.00 36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 4

9.00 36kV, 1-Phase, 200-100/1-1 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (for Feeder at GSS)

Set 2

10.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 3

11.00 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 4

12.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 6

Page 16 of 33

Page 455: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 913.00 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang

Operated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 16

14.00 36 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

10

15.00 36 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

3

16.00 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

3

17.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 15

Page 17 of 33

17.00 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 15

18.00 12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 3

19.00 12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 12

20.00 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

4

21.00 9kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etcas required as per technical specifications, approved drawings and scope of the works.

Set ofthree

12

22.00 Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 3

Page 17 of 33

Page 456: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 923.00 Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories completefor feeder breaker protection as per technical specifications, approved drawings andscope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 12

24.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 12

25.00 12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 25

26.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

6

Page 18 of 33

26.00 12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

6

27.00 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 1.2

28.00 3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 300

29.00 4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 8700

30.00 7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 12700

31.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 9

32.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 3

Page 18 of 33

Page 457: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 933.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station

as per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 3

34.00 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.6

35.00 40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 75

36.00 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 3

Page 19 of 33

36.00 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 3

37.00 Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 3

38.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

90

39.00 11 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

162

40.00 110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 3

41.00 110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 3

42.00 External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 4

43.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 1

Page 19 of 33

Page 458: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 944.00 Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,

One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 3

45.00 Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 3

B New 33 KV Lines1.00 12 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS

2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 760

2.00 Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 31

Page 20 of 33

2.00 Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 31

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 3.0

4.00 Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 3040

5.00 100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 760

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 1.527.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technical

specification, approved drawings and scope of workSet 1824

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 3648

9.00 AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 125.40

10.00 Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guardearthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 38.00

Page 20 of 33

Page 459: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 911.00 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4(Four) Nos (INCLUDING

ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.140 km each) USING 150MM DIA CIPIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MM HDPE PIPE FOR POLE SUPPORT,OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 33 KV LIGHTENING ARRESTORSTATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWGGI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK including Wayleave/ Supervision Charges payable to Railway Department on actual basis.

set 1

C New 11 KV Lines1.00 8.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approved

drawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 760

2.00 Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 17.27

Page 21 of 33

2.00 Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 17.27

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 1.14

4.00 Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nosturn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI strandedwire etc as required as per technical specification, approved drawings and scope of work.

Set 380

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 912

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 1824

7.00 100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 152

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.38

9.00 AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 125.40

Page 21 of 33

Page 460: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 910.00 Protective guarding as per REC construction standard drawing No A-1 to be provided at

locations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 38.00

Total

Page 22 of 33Page 22 of 33

Page 461: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00 Detail sub-soil investigation report about specific information about the soilprofile and necessary soil parameters of sub-station site & recommendations ofsoil mechanic engineer regarding foundation depth of defferent type of footingswith size including contour survey etc. as per Technical Specification.

PERS/S

3

2.00 Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 11700

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/MRG

(Schedule of rates and prices)Rural Electrification works in Morigaon Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian RupeesBidder's Name & Address:

Page 23 of 33

2.00 Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 11700

3.00 Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 4100

4.00 Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 3

5.00 Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works: 10.00 MVA with offload / on load tap changer

No 1

6.00 Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 3

Page 23 of 33

Page 462: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 97.00 Design and construction of foundation for following 33 KV outdoor mounted

Vacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 7

8.00 Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 15

9.00 Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and asper Technical Specification, approved Drawing & Scope of works

MT 59

Page 24 of 33

9.00 Fabrication ,Foundation and Erection of Gantry structures using , lattice structure(galvanised including hardware), GI channel, GI angle and GI flat of various sizesincluding GI nuts & bolts, etc as required as per soil & site requirment and asper Technical Specification, approved Drawing & Scope of works

MT 59

10.00 Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 660

Page 24 of 33

Page 463: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 911.00 Design and construction of Assam type Control Room Building with PPGI sheet

Dyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 360

12.00 Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 450

Page 25 of 33

12.00 Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 450

13.00 Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 300

14.00 Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 150

15.00 Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 3

A-Ib Substation Electrical works

Page 25 of 33

Page 464: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 91.00 Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,

Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 3

2.00 Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 10.0 MVA with off/on load tap changerPower Transformer along with transformer oil, Buchholtz relay, breather, OTI &WTI, Marshalling Box, Conservator tank, oil level indicator, valves by providing 2sets of 50x8 mm GS Neutral Earthing strips with braided conductor on bushingend supported with insulators, OTI & WTI Indicators, Vent explosion plug,control wiring / cabling, cable supporting tray on the body, transformer wheels,bushing etc as per Technical Specification, approved Drawing & Scope of works

No 1

Page 26 of 33

2.00 Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 10.0 MVA with off/on load tap changerPower Transformer along with transformer oil, Buchholtz relay, breather, OTI &WTI, Marshalling Box, Conservator tank, oil level indicator, valves by providing 2sets of 50x8 mm GS Neutral Earthing strips with braided conductor on bushingend supported with insulators, OTI & WTI Indicators, Vent explosion plug,control wiring / cabling, cable supporting tray on the body, transformer wheels,bushing etc as per Technical Specification, approved Drawing & Scope of works

No 1

3.00 Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,aluminium would outdoor type Distribution Transformer (Station Transformer) asper Technical Specification, approved Drawing & Scope of works

Set 3

33KV Yard1.00 Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,

Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 7

2.00 Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

7

Page 26 of 33

Page 465: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 93.00 Design, providing and installation of ISMC 75 channel on top of indoor trench,

erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 3

4.00 Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 4

Page 27 of 33

4.00 Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 4

5.00 Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 22

6.00 Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

13

7.00 Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

3

11KV Yard1.00 Design, construction of foundation (as per approved drawings), erection,

testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 15

Page 27 of 33

Page 466: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 92.00 Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 15

3.00 Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 3

4.00 Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 12

Page 28 of 33

4.00 Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 12

5.00 Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

16

6.00 Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 37

7.00 Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

6

8.00 Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 1.2

Page 28 of 33

Page 467: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 99.00 Power Cables including their termination at indoor/outdoor terminals including

supply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 300

10.00 Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 9

11.00 Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 3

12.00 Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 3

Page 29 of 33

12.00 Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 3

13.00 Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.6

14.00 Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 75

15.00 Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 3

Page 29 of 33

Page 468: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 916.00 Erection, testing & commissioning of Outdoor type Distribution Box for station

transformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 3

17.00 Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 3

18.00 Design, Installation, interconnection cabling, testing and commissioning of 24V,40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with fullwave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDBas per approved drawings, technical specifications and scope of the work

Set 3

Page 30 of 33

18.00 Design, Installation, interconnection cabling, testing and commissioning of 24V,40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with fullwave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDBas per approved drawings, technical specifications and scope of the work

Set 3

19.00 Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 4

20.00 Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 3

B Erection, testing and Commissioning of New 33 KV lines:1.00 Survey, route alignment & pole spotting, preparation of survey report and

uploading in the web portal after approval of Project ManagerKm 38.00

Page 30 of 33

Page 469: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 92.00 Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope

of work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 228

3.00 Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 532

Page 31 of 33

3.00 Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 532

4.00 Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 30.56

5.00 Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of staywire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 partcement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as pertechnical specifications, approved drawings and scope of works.

Set 3040

6.00 Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 3648

7.00 Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 1824

8.00 Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

38.00

Page 31 of 33

Page 470: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 99.00 Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CI

pipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 760

10.00 Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 38.00

11.00 Erection of 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4 Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.140 km each)USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MMHDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLE CABLEJOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.),LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GI WIRES, CABLEMARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORKincluding Way leave/ Supervision Charges payable to RailwayDepartment on actual basis.

Set 1

Page 32 of 33

11.00 Erection of 33 KV LINE FOR UNDER GROUND RAILWAY CROSSING BY 4 Nos(INCLUDING ONE SPARE) 1Cx300 Sqmm XLPE Armoured Cable (0.140 km each)USING 150MM DIA CI PIPES(CLASS-I A TYPE) FOR UG CABLE AND 100 MMHDPE PIPE FOR POLE SUPPORT, OUTDOOR HEAT SHRINKABLE CABLEJOINTING KITS, 33 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.),LUGS, 4 Nos GI 3-Meters LONG PIPE EARTHING, 6 SWG GI WIRES, CABLEMARKERS, BI METALLICK CLAMPS, JUMPERING AS REQUIRED AS PERTECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORKincluding Way leave/ Supervision Charges payable to RailwayDepartment on actual basis.

Set 1

C Erection, testing and Commissioning of New 11 KV lines:1.00 Survey, route alignment & pole spotting, preparation of survey report and

uploading in the web portal after approval of Project ManagerKm 38.00

2.00 Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 228

3.00 Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 532

4.00 Erection of galvanised pre-fabricated steel materials like T Cross arm, channelcross arm, angle, flats and all other GI materials for over head structures.

MT 17.27

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 152

Page 32 of 33

Page 471: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 96.00 Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HT

stay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 380

7.00 Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 1824

8.00 Erection, testing and commissioning of 11 kV Polymaric Disc insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 912

9.00 Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

38.00

10.00 Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 38.00

Page 33 of 33

10.00 Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 38.00

Total

Page 33 of 33

Page 472: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT

NewS/S,2x5MVA at

Gangapur(Nalbari)

TotalQuantity

A New 33/11 KV Substation WorksCIVIL WORKS

1 Soil Testing 1 12 Boundary wall inculing Gate R/Mt 220 220

3Construction of Assam Type control room building with bestquality Dyna roof (blue clour) including , Senitary, Internalelectrification etc.complete

Sq.M 120 120

4Water supply: Deep well with 1 HP motor- Pump,Overhead waterresurvior capacity 2x500 Ltr over the GI staging with necesssarypipeline with connection,stand & power connection appliances.

set 1 1

5 Approach road , 4.0 Mtr width Mtr 50 506 Drainage System Mtr 100 1007 Foundation of Pad for 33/11KV power transformer No 2 28 Foundation of Pad for 33/.433 KV power transformer No 1 1

9 Const. of Cable Trenches as per specification with following sizes: -

ASSAM POWER DISTRIBUTION COMPANY LIMITEDRural Electrification works in Nalbari Project in Assam under DDUGJY Phase-II (REDB

works)

BOQ: Construction of 33/11KV New S/S within the Nalbari District under DDUGJY-II/XII PlanScheme.

STANDARD BILL OF MATERIALS (as per site requirement)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/NAL

Page 1 of 32

9 Const. of Cable Trenches as per specification with following sizes: -

(a) Width 600mm x Depth . RM 150 150

10 Gravelling of switch yard, depth 22.5 Cm with crushed stonesize 40 mm

SqMtr.

1200 1200

11 Earth Filling CM 3900 390012 Sign Board, size: 4 feetx3 feet No 1 1

13(a) 33/11KV 5 MVA Power Transformer Nos. 2 2

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB,Siemens, Schneider make

Nos. 3 3

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 2 2

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Station Type

Set 4 4

19 33KV , 10 KA Lightning Arrester with chagre monitor and GImounting(set of 3 units) Line Type

Set 1 1

20 33 KV ,1250 Amp Isolator with earth blade Set 3 321 33 KV ,1250 Amp Isolator without earth blade Set 6 6

22 33KV Transformer Panels preferably CG,ABB,Siemens,Schneidermake

Nos. 2 2

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 1 1

24 33 KV Potential Transformer Set 1 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG,ABB, Siemens, Schneider make

No. 6 6

26 Control & Relay panel for 11 KV out door Feeder VCB preferablyCG, ABB, Siemens,Schneider make

No. 4 4

27 Control & Relay panel for 11 KV out door Transformer VCBpreferably CG, ABB,Siemens,Schneider make

No. 2 2

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Boxand GI Structure

Set 2 2

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

Page 1 of 32

Page 473: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT

NewS/S,2x5MVA at

Gangapur(Nalbari)

TotalQuantity

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Boxand GI Structure

Set 4 4

30 11 KV Isolator Double break with earth switch with GIstructure(800A)

Set 4 4

31 11 KV Isolator Double break without earth switch with GIstructure(800A)

Set 9 9

37 11 KV Out door Potential Transformer Set 2 238 11 KV LA Line Type (set of 3 units) Set 4 439 11 KV LA Station Type (set of 3 units) Set 2 241 110 V, 150 AH Lead Acid Battery bank, etc. Set 1 142 Battery charger etc. No. 1 149 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 4700 470050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 3400 3400

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor,PVC insulated and PVC sheathed cable

Mtr 100 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 15 1554 33 KV Gantry Structure Extension MT 8 855 Station service transformer, 33/.433KV,100 KVA Nos. 1 156 Distrbutiob Box Nos. 1 157 LTACDB ,DCDB Etc. Set 1 1

58 Earthing & Grounding conductor as per Approved ElectricalLayout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3 3b 50 x 6 mm Galvanized GS flat (risers) MT 1 1c 25 x 6 mm Galvanized GI flat (risers) MT 1 1d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.2

Page 2 of 32

d 25mm dia MS rod 3 m long for earth mat MT 0.2 0.259 40 mm dia,3000 mm length GI Earth Pipe No 25 2560 ACSR Panther Conductor for Bus bar Km 0.4 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of3 nos.

30 30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of3 nos.

54 54

63

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of4.5Kg Capacity for Control Room,two sets of fire buckets setincluding their stand for Control Room & Station Yard and Oneno. CO2 Type Trolley Mounted of 22.5 Kg Capacity for SwitchYard.

Set 1 1

64 External Electrification at station yard lighting with 12 Noslightening 90 Watt LED Lamp .

set 1 1

65Substation Tools and Plants like megger, earth tester, Multimeter,Tong tester, Box-spanners, D-spanners, screw drivers, earthingrods, earth mat etc as required as per scope of work.

Set 1 1

66 New 33&11 KV Line MukalmuaSS

a 33 KV Line Km 10 10b 11 KV Line Km 10 10g 33 KV Gantry Structure (Exiention) No 1 1

Page 2 of 32

Page 474: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT QTY

1 2 3 4A New 33 kV Line Ckt. Km. 10.001 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 2002 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 803 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 1804 Jam Clamp of GI Flat 65x6 mm Pair 5205 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 1206 33 KV Polymeric Pin Insulator No. 9607 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 4808 Tension Clamp for Wolf Conductor No. 2409 AAA Wolf Conductor (19/3.40 mm) Km. 33.00

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 100

11 Guy Insulator (HT) No. 20012 Stay Wire 7/4.0 mm Kg 800

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 600

Rural Electrification works in Nalbari Project in Assam under DDUGJY Phase-II (REDB works)

Construction of 33/11KV New S/S,2x5 MVA at Gangapur within the Nalbari District under DDUGJY-II/XII PlanScheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/NAL

Page 3 of 32

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 600

14 Jointing Sleeve for Wolf No. 3015 PG Clamp for Wolf (Alcon 80) No. 24016 Al. Binding Wire (10 SWG.) Kg 6017 GI Nuts & Bolts (assorted) Kg 80018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 40019 33 KV Danger Plate (1.6 mm thick) No. 20020 Barbed Wire Kg 40021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 200A1 33 KV Overhead Line Crossing - Line to line / Road: Set 101 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 202 GI wire 8 SWG for cross lacing as per T.S Kg. 1003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2004 GI 'I' Hook No. 405 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20B New 11 kV Line Ckt. Km. 10.001 PSC Pole, 8.5 Mt. long 550 Kg. No. 2002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 1203 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 804 Composite Polymeric 11 kV Pin Insulator No. 4805 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 2406 Tension Clamp for Raccoon No. 2407 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 33.00

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2Nos.), Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 100

9 HT Guy Insulator No. 10010 GI Stay wire 7/3.15 mm Kg. 800

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 400

Page 3 of 32

Page 475: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No. ITEM DESCRIPTION UNIT QTY

12 GI wire 6 SWG for Earthing Kg. 10013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 4014 Jointing Sleeve for Raccoon No. 3015 PG Clamp for Raccoon No. 24016 AI. Binding Wire (10 SWG.) Kg. 5017 Pole Clamp of GI flat (50x6) mm No. 16018 GI Barbed Wire for anticlimbing device Kg. 40019 11 KV Danger Plate (1.6 mm thick) No. 20020 GI Nuts & Bolts with GI washer (Assorted) Kg. 300B1 11 KV Overhead Line Crossing - Line to line / Road: Set 101 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 202 GI wire 8 SWG for cross lacing as per T.S Kg. 1003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2004 GI 'I' Hook No. 405 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20

Page 4 of 32Page 4 of 32

Page 476: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

A. 33/11 KV Substation Works

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventionaltype 5.00 MVA with off load tap changer Power Transformer alongwith transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor onbushing end), isolating link, isolation with insulators, Vent explosionplug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels,LV/HV bushing etc as required as per technical specifications,approved drawings and scope of the work.

No 2

New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Nalbari Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/NAL

All prices in Indian RupeesBidder's Name & Address:

Page 5 of 32

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventionaltype 5.00 MVA with off load tap changer Power Transformer alongwith transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor onbushing end), isolating link, isolation with insulators, Vent explosionplug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels,LV/HV bushing etc as required as per technical specifications,approved drawings and scope of the work.

No 2

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminiumwound, CRGO core, outdoor type Station Transformer along withtransformer oil and all accessories as required as per technicalspecifications, scope of works and approved drawings.

No 1

Page 5 of 32

Page 477: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

3.00

Gantry structures made of Lattice structures of equal angles sections,flat as per approved drawings. State practices are to be adopted in thedesign. All structural steel members and bolts shall be galvanizedafter fabrication as per IS:4759 and zinc coating shall not be less than610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark.3.5mm spring washers are to be used under each nut, structural steelshall conform to IS 2026. All weld shall be 6mm filled weld unlessspecified otherwise. All nuts and bolts shall be of property class 5.6of IS 1367. Plain washers shall be as per IS 2016 & spring washersshall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 23

Page 6 of 32

3.00

Gantry structures made of Lattice structures of equal angles sections,flat as per approved drawings. State practices are to be adopted in thedesign. All structural steel members and bolts shall be galvanizedafter fabrication as per IS:4759 and zinc coating shall not be less than610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark.3.5mm spring washers are to be used under each nut, structural steelshall conform to IS 2026. All weld shall be 6mm filled weld unlessspecified otherwise. All nuts and bolts shall be of property class 5.6of IS 1367. Plain washers shall be as per IS 2016 & spring washersshall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 23

4.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type VacuumCircuit breaker , supporting structures, bi-metallic terminal clamps,permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (forTransformer & feeder)

Nos 3

5.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps,permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (forFeeder)

Sets 1

6.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps,permanent maintenance platform, marshalling box etc required as pertechnical specifications, scope of works and approved drawings (forTransformer)

Sets 2

Page 6 of 32

Page 478: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

7.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays,Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows withannunciation relays and other components etc as per approveddrawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

8.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays,Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows withannunciation relays and other components etc as per approveddrawings, specifications and scope of works controlling:For Power transformer 33 kV VCB with Static Tri-Vector EnergyMeter

No 2

9.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotatingtype (DBCR), Gang Operated isolator along with Support Insulators,Operating Mechanism, Base Channel down Pipe and all requiredaccessories complete as per technical specifications, scope of worksand approved drawings (with Earth Blade)

Set 3

Page 7 of 32

9.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotatingtype (DBCR), Gang Operated isolator along with Support Insulators,Operating Mechanism, Base Channel down Pipe and all requiredaccessories complete as per technical specifications, scope of worksand approved drawings (with Earth Blade)

Set 3

10.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotatingtype (DBCR), Gang Operated isolator along with Support Insulators,Operating Mechanism, Base Channel down Pipe and all requiredaccessories complete as per technical specifications, scope of worksand approved drawings (without Earth Blade)

Set 6

11.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mountingplatform, hardware etc as required as per technical specifications,approved drawings and scope of the works.

Set ofthree

4

12.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mountingplatform, hardware etc as required as per technical specifications,approved drawings and scope of the works.

Set ofthree

1

Page 7 of 32

Page 479: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

13.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor typePotential Transformer along with junction box (1 no junction box for3 no of 1-phase PTs), bi-metallic clamp and required accessories etc.,complete as per technical specifications, approved drawings andscope of the works.

Set ofthree

1

14.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type VacuumCircuit breaker, supporting structures, bi-metallic clamps, permanentmaintenance platform, marshalling box, and required accessoriescomplete as per technical specifications, approved drawings andscope of the works.

No 6

15.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type CurrentTransformer along with junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanentmaintenance platform, marshalling box, and required accessoriescomplete as per technical specifications, approved drawings andscope of the works. (for Transformer)

Set 2

Page 8 of 32

15.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type CurrentTransformer along with junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanentmaintenance platform, marshalling box, and required accessoriescomplete as per technical specifications, approved drawings andscope of the works. (for Transformer)

Set 2

16.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type CurrentTransformer along with junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanentmaintenance platform, marshalling box, and required accessoriescomplete as per technical specifications, approved drawings andscope of the works.(for Feeder)

Set 4

17.009kV, 10kA, 1-ph Station Class Lightening Arrester with mountingplatform, hardware, etc as required as per technical specifications,approved drawings and scope of the works.

Set ofthree

2

18.009kV, 10kA, 1-ph Line Class Lightening Arrester with mountingplatform, hardware, etc as required as per technical specifications,approved drawings and scope of the works.

Set ofthree

4

Page 8 of 32

Page 480: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

19.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB(Transformer Breaker) consisting of A-meter, volt-meter, Relays &accessories complete as per specifications for transformer breakerprotectionFor Power transformer 11 kV VCB with Static Tri-Vector EnergyMeter

No 2

20.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB

(Feeder Breakers) consisting of A-meter, volt-meter, Relays, energy

meter (TVM) & accessories complete for feeder breaker protection as

per technical specifications, approved drawings and scope of works.

For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

Page 9 of 32

20.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB

(Feeder Breakers) consisting of A-meter, volt-meter, Relays, energy

meter (TVM) & accessories complete for feeder breaker protection as

per technical specifications, approved drawings and scope of works.

For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

21.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotatingtype (DBCR), Gang Operated Isolator along with Support Insulators,Operating Mechanism, Base Channel, down Pipe and all requiredaccessories complete as per technical specifications, scope of worksand approved drawings (With Earth Blade)

Set 4

22.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotatingtype (DBCR), Gang Operated Isolator along with Support Insulators,Operating Mechanism, Base Channel, down Pipe and all requiredaccessories complete as per technical specifications, scope of worksand approved drawings (Without Earth Blade)

Set 9

23.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor typePotential Transformer along with junction box (1 no junction box for3 no of 1-phase PTs), bi-metallic clamp and required accessories etc.,complete as per technical specifications, approved drawings andscope of the works.

Set ofthree

2

24.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminationsincluding hardware fittings, hardware, T-claimp etc as per technicalspecifications, approved drawings and scope of works.30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0

Page 9 of 32

Page 481: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

25.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVCinsulated and PVC sheathed LT Power Cables including theirtermination materials like glands, lugs, tagging etc. as per technicalspecifications, approved drawings and scope of the work.

Mtr 100

26.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVCinsulated and PVC sheathed LT Control cables including theirtermination materials like glands, lugs etc. as per technicalspecifications, approved drawings and scope of the work

Mtr 3400

27.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVCinsulated and PVC sheathed LT Control cables including theirtermination materials like glands, lugs etc. as per technicalspecifications, approved drawings and scope of the work

Mtr 4700

Page 10 of 32

27.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVCinsulated and PVC sheathed LT Control cables including theirtermination materials like glands, lugs etc. as per technicalspecifications, approved drawings and scope of the work

Mtr 4700

28.00Earthing & Grounding conductor as per Approved Electrical Layoutfor each sub-station as per technical specifications, approveddrawings and scope of works ::75 x 8 mm GI flat for ground mat

MT 3

29.00Earthing & Grounding conductor as per Approved Electrical Layoutfor each sub-station as per technical specifications, approveddrawings and scope of works:: 50 x 6 mm Galvanized GI flat (risers)

MT 1

30.00

Earthing & Grounding conductor as per Approved Electrical Layout

for each sub-station as per technical specifications, approved

drawings and scope of works ::25 x 6 mm Galvanized GI flat (risers)

MT 1.00

31.00

Earthing & Grounding conductor as per Approved Electrical Layoutfor each sub-station as per technical specifications, approveddrawings and scope of works:: 25mm dia GI rod 3 m long for earthmat

MT 0

32.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link,RCC pit, RCC cover, placed on GI frame, bantonide powder andother accessories complete as per technical specification. (for PowerTransformer Neutral, Station Transformer Neutral and LighteningArresters direct earthing)

No 25

Page 10 of 32

Page 482: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

33.00

415 V, ACDB along with three phase-neutral voltmeter, three phaseammeter and Selector switches, 200 Amps TPN switch fuse unit asincomer, 32 Amps TPN switches as outgoing feeders suited fornumber of control panels, nos of VCB kiosk panel, having 20% spareoutgoing feeders, mounting arrangements etc as per technicalspecifications, approved drawings and scope of works.

Set 1

34.00

Outdoor type Distribution Box for station transformer comprising 200

A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB,

3-ph, 63A, contactor controlled yard lighting timer unit, tri-vector

electronic energy meter with suitable CT, control/power cabling and

terminals, 1 No 20 A Industrial socket and switch for local power

supply requirements, mounting channel, clamps and hardware as per

scope of work, technical specifications and approved drawings,

Set 1

Page 11 of 32

34.00

Outdoor type Distribution Box for station transformer comprising 200

A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB,

3-ph, 63A, contactor controlled yard lighting timer unit, tri-vector

electronic energy meter with suitable CT, control/power cabling and

terminals, 1 No 20 A Industrial socket and switch for local power

supply requirements, mounting channel, clamps and hardware as per

scope of work, technical specifications and approved drawings,

Set 1

35.0033 KV, 90 KN porcelain Disc insulators along with suitablehardware & accessories suitable for Panther conductors as perapproved drawings & specifications.

Set ofthree

30

36.0011 KV, 70 KN porcelain Disc insulators along with suitable

hardware & accessories suitable for Panther conductors as perapproved drawings & specifications.

Set ofthree

54

37.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators,inter-battery wiring using 30 sqm, 1.1 kv, copper single core multistrand cable, terminal connectors, & all other accessories andconnectors as per technical specifications, approved drawings andscope of works.

Set 1

38.00

110V, 40 Amp. Float-cum-Boost Battery Charger with full waverectification for 220 V, 1 phase, 50 Hz AC Input Supply with builtin DCDB as per technical specifications, approved drawings andscope of works.

Set 1

Page 11 of 32

Page 483: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

39.00

External Electrification in switch yard area including powerreceptacles, station yard lighting with 6 Nos lightening mast (fittedwith 2x90 watts LED fittings) made of 12 meters high Steel TubularPoles (IS 2713 part I, II III) of designation 410 – SP - 60, complete asper technical specifications, approved drawings and scope of thework.

Set 1

40.00

Substation Tools and Plants like One 5/2.5 KV megger, One earthtester, One Multimeter, One Tong tester, One set of Box spanner, Oneset each Round and D-spanners with various range, screw driverswith various size one each, earthing rods, etc as required as per scopeof work.

Set 1

41.00

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of 4.5KgCapacity for Control Room,two sets of fire buckets set including theirstand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

Page 12 of 32

41.00

Fire Fighting Equipment comprises of Four nos Dry ChemicalPowder Type (6 Kg) for control room; Two nos CO2 Type of 4.5KgCapacity for Control Room,two sets of fire buckets set including theirstand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B. New 33 KV Lines

1.00

12 M long steel Tubular poles with welded steel base plate ofDesignation 540 SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KVoverhead line as per technical specification, approved drawings andscope of work.

No 200

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp,DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp etc made of GI Channels(100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) of givensizes for over head structures as per technical specification, approveddrawings and scope of work.

MT 8.04

3.00GI Nuts, bolts and washers as per technical specification, approveddrawings and scope of work.

MT 0.80

Page 12 of 32

Page 484: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2Nos.), anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles,1.8 m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GIstranded wire complete as per technical specification, approveddrawings and scope of work.

Set 800

5.00100 mm dia., 1800 mm long CI pipe earth electrode and otheraccessories complete for earthing arrangement as per technicalspecificatons, approved drawings and scope of work.

Set 200

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.40

7.0033 KV polymer Disc insulator 70 KN along with suitable hardwarefittingsas per technical specification, approved drawings and scope ofwork

Set 480

Page 13 of 32

7.0033 KV polymer Disc insulator 70 KN along with suitable hardwarefittingsas per technical specification, approved drawings and scope ofwork

Set 480

8.0033 KV Polymer Pin Insulators 10 KN with GI PIN as per technicalspecification, approved drawings and scope of work

Set 960

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves,binding materials, PG clamps, bi-metallic conductor, hardware etc foroverhead line and jumpers as required as per technical specification,approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 33.00

10.00

Line Crossing-Line to line, line to road with items, GI Angle CrossArm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG forguarding, GI Wire 6 SWG & 8 SWG for guard earthing, GI 'I' Hook,CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 10.00

C New 11 KV Lines

1.00

8.5 m PSC Poles Support for 11 KV overhead line as pertechnical specification, approved drawings and scope of workalongwith Danger Plate and Barbed Wire as per approved GTP,as per state practice.

No. 200

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channelcross arm, angle, flats and all other GI materials shown in BOQ forover head structures as per technical specification, approved drawingsand scope of work.

MT 5

Page 13 of 32

Page 485: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit Qty Unit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as applicable)

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.

Assam VAT @1 2 3 4 5 6=4x5 7 8 9=(6+8)x

@__%10

3.00Galvanized Steel Nuts, Bolts with Washers as per technicalspecification, approved drawings and scope of work.

MT 0.30

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator,nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GSstay rod & 7/3.15 mm GI stranded wire etc as required as pertechnical specification, approved drawings and scope of work.

Set 100

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardwarefittingsas per technical specification, approved drawings and scope ofwork.

Set 240

6.00Composite Polymeric 11 KV Pin insulator as per technicalspecification, approved drawings and scope of work.

Set 480

7.00

100 mm dia., 1800 mm long CI earth pipe earth electrode withCharcoal, Salt and other accessories complete as per technicalspecification, approved drawings and scope of work for 11 KV lineearthing

Set 40

Page 14 of 32

7.00

100 mm dia., 1800 mm long CI earth pipe earth electrode withCharcoal, Salt and other accessories complete as per technicalspecification, approved drawings and scope of work for 11 KV lineearthing

Set 40

8.006 SWG GI Wire for earthing of 11 KV Line, as per technicalspecification, approved drawings and scope of work.

MT 0

9.00

AAA Racoon coductor alongwith Supply of items for erection ofAAA Raccoon Conductors with Jointing sleeves, binding materials,PG clamps, Tension Clamps, bi-metallic clamp etc. for overhead lineand jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 33

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided at locations where 11KV/33 KV line is crossingroad, 11 KV line is crossing LT Lines/ P&T lines etc. Supplying 2Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nosearthing of 100mm dia CI earth pipe of 1.8 meter long, 6 SWG GIwires for earthing connection, 6 SWG wire for guard wire, 8 SWGwire for cross lacing.

set 10.00

Total Ex-worksTotal Ex-works

Page 14 of 32

Page 486: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%) 9

New 33/11 KV Substation Works (Excluding civil works)A. 33/11 KV Substation Works

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators, Ventexplosion plug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels, LV/HVbushing etc as required as per technical specifications, approved drawings andscope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Nalbari Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/NAL

Page 15 of 32

1.00

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformer oil,Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oillevel indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators, Ventexplosion plug, control wiring between sensing equipment and marshalling box,cable supporting tray on the body of transformer, transformer wheels, LV/HVbushing etc as required as per technical specifications, approved drawings andscope of the work.

No 1

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 23

3.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structuralsteel members and bolts shall be galvanized after fabrication as per IS:4759 andzinc coating shall not be less than 610gm/sq. meter for all structural steelmembers. All L45x45x5 will have 23 mm back mark. All L50x50x6 will have28mm back mark. 3.5mm spring washers are to be used under each nut, structuralsteel shall conform to IS 2026. All weld shall be 6mm filled weld unless specifiedotherwise. All nuts and bolts shall be of property class 5.6 of IS 1367. Plainwashers shall be as per IS 2016 & spring washers shall be IS: 3063 as pertechnical specifications, scope of works and approved drawings..

MT 3

Page 15 of 32

Page 487: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

4.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

No 1

5.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Feeder)

Set 2

6.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer)

Set 1

Page 16 of 32

6.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer)

Set 1

7.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scope ofworks controlling: For 33 kV feeder VCBwith Static Tri-Vector Energy Meter

No 2

8.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scope ofworks controlling: For Powertransformer 33 kV VCB with Static Tri-Vector Energy Meter

No 3

9.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 6

Page 16 of 32

Page 488: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

10.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 4

11.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

1

12.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

1

13.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phase PTs),bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

0

Page 17 of 32

13.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phase PTs),bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

0

14.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform,marshalling box, and required accessories complete as per technicalspecifications, approved drawings and scope of the works.

No 2

15.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshalling box,and required accessories complete as per technical specifications, approveddrawings and scope of the works. (for Transformer)

Set 4

16.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshalling box,and required accessories complete as per technical specifications, approveddrawings and scope of the works.(for Feeder)

Set 2

17.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

4

Page 17 of 32

Page 489: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

18.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawings andscope of the works.

Set ofthree

2

19.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer

Breaker) consisting of A-meter, volt-meter, Relays & accessories complete as per

specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 4

20.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technical specifications,approved drawings and scope of works. For 11 kV feeder VCB withStatic Tri-Vector Energy Meter

No 4

21.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (With EarthBlade)

Set 9

Page 18 of 32

21.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (With EarthBlade)

Set 9

22.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 2

23.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phase PTs),bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

0

24.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm (200mm² Al. Area) - Panther

Km 100.0

Page 18 of 32

Page 490: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

25.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated andPVC sheathed LT Power Cables including their termination materials like glands,lugs, tagging etc. as per technical specifications, approved drawings and scope ofthe work.

Mtr 3400

26.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC

sheathed LT Control cables including their termination materials like glands, lugs

etc. as per technical specifications, approved drawings and scope of the work

Mtr 4700

27.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC

sheathed LT Control cables including their termination materials like glands, lugs

etc. as per technical specifications, approved drawings and scope of the work

Mtr 3

28.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works ::75x 8 mm GI flat for ground mat

MT 1

Page 19 of 32

28.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works ::75x 8 mm GI flat for ground mat

MT 1

29.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works:: 50x 6 mm Galvanized GI flat (risers)

MT 1

30.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works ::25x 6 mm Galvanized GI flat (risers)

MT 0

31.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 25.0

32.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories complete asper technical specification. (for Power Transformer Neutral, Station TransformerNeutral and Lightening Arresters direct earthing)

No 1

33.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeterand Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 AmpsTPN switches as outgoing feeders suited for number of control panels, nos ofVCB kiosk panel, having 20% spare outgoing feeders, mounting arrangements etcas per technical specifications, approved drawings and scope of works.

Set 1

Page 19 of 32

Page 491: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

34.00

Outdoor type Distribution Box for station transformer comprising 200 A switch

fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor

controlled yard lighting timer unit, tri-vector electronic energy meter with

suitable CT, control/power cabling and terminals, 1 No 20 A Industrial socket and

switch for local power supply requirements, mounting channel, clamps and

hardware as per scope of work, technical specifications and approved drawings,

Set 30

35.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

36.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

1

37.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-batterywiring using 30 sqm, 1.1 kv, copper single core multi strand cable, terminalconnectors, & all other accessories and connectors as per technical specifications,approved drawings and scope of works.

Set 1

Page 20 of 32

37.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-batterywiring using 30 sqm, 1.1 kv, copper single core multi strand cable, terminalconnectors, & all other accessories and connectors as per technical specifications,approved drawings and scope of works.

Set 1

38.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 1

39.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation410 – SP - 60, complete as per technical specifications, approved drawings andscope of the work.

Set 1

40.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Round andD-spanners with various range, screw drivers with various size one each, earthingrods, etc as required as per scope of work.

Set 1

41.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 0

Page 20 of 32

Page 492: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

B. New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technicalspecification, approved drawings and scope of work.

No 8

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, backclamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats(65x8mm) of given sizes for over head structures as per technical specification,approved drawings and scope of work.

MT 1

3.00GI Nuts, bolts and washers as per technical specification, approved drawings andscope of work.

MT 800.0

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchorplate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mmdiameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as pertechnical specification, approved drawings and scope of work.

Set 200

Page 21 of 32

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchorplate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mmdiameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as pertechnical specification, approved drawings and scope of work.

Set 200

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 0

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 480.00

7.0033 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work

Set 960

8.0033 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 33

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead line andjumpers as required as per technical specification, approved drawings and scopeof work Size:: 19/3.40 (Al. alloy Area173 sqmm ) - Wolf

km 10.00

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6SWG & 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 0.00

C New 11 KV Lines

Page 21 of 32

Page 493: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr. No. Description Unit QtyUnit Freight& Insurance

Charges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 5

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,angle, flats and all other GI materials shown in BOQ for over head structures asper technical specification, approved drawings and scope of work.

MT 0.30

3.00Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 100.00

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GIstranded wire etc as required as per technical specification, approved drawingsand scope of work.

Set 240

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 480

Page 22 of 32

5.00Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 480

6.00Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 40

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt andother accessories complete as per technical specification, approved drawings andscope of work for 11 KV line earthing

Set 0

8.006 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 33

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, Tension Clamps,bi-metallic clamp etc. for overhead line and jumpers as required as per technicalspecification, approved drawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 10.00

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mm diameterEye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meter long, 6 SWGGI wires for earthing connection, 6 SWG wire for guard wire, 8 SWG wire forcross lacing.

set 0.00

Total

Page 22 of 32

Page 494: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A-I 33/11 KV Grid Substation worksA-Ia Civil works:

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PERS/S

1

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 3900

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/NAL

(Schedule of rates and prices)Rural Electrification works in Nalbari Project in Assam under DDUGJY Phase-II (REDB works)

Schedule-3

All prices in Indian Rupees

Page 23 of 32

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 3900

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 1200

4.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 2

5.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

6.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 3

Page 23 of 32

Page 495: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 6

8.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 23

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

Page 24 of 32

9.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

10.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 120

Page 24 of 32

Page 496: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

11.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 150

12.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 100

13.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

14.00

Supply and Installation of deep tube well with Single PhaseSubmersible motor pump set (Texmo/Crompton Greaves/Aquastic/CRI/V-Guar suitable for 100 mm bore well and above. 1 HPSTAGE 5 to 18 with control panel along with 2x500 Ltr overhead Sintexmake water storage Tank over the GI staging with manhole cover withlocking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixingall materials and filter to get potable water as per approved drawingand specification.

SET 1

Page 25 of 32

14.00

Supply and Installation of deep tube well with Single PhaseSubmersible motor pump set (Texmo/Crompton Greaves/Aquastic/CRI/V-Guar suitable for 100 mm bore well and above. 1 HPSTAGE 5 to 18 with control panel along with 2x500 Ltr overhead Sintexmake water storage Tank over the GI staging with manhole cover withlocking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixingall materials and filter to get potable water as per approved drawingand specification.

SET 1

A (Ib) Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 2

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,aluminium would outdoor type Distribution Transformer (Station Transformer) asper Technical Specification, approved Drawing & Scope of works

Set 1

33KV Yard

Page 25 of 32

Page 497: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 3

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

3

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

Page 26 of 32

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 2

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 9

6.00

Design, construction of foundation (as per approved drawings), Erection,testing and Commissioning of 36kV, 10kA, 1-ph Station Class LighteningArresters with mounting platform, jumpering , earthing connection using50x6mm GS flat, hardware etc as required, as per approved drawings, technicalspecifications and scope of the work,

Set of three 5

Page 26 of 32

Page 498: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set of three 1

11KV Yard

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 6

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 6

Page 27 of 32

2.00

Design, construction of foundation (as per approved drawings), erection, testingand commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5with Marshilling Box and GI Structure, jumpering.etc required as per technicalspecifications, scope of works and approved drawings

Set 6

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 2

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

6

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 13.0

Page 27 of 32

Page 499: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set of three 2

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 3

Page 28 of 32

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 3

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1.0

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 25

Page 28 of 32

Page 500: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 1

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 1

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 1

Page 29 of 32

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 1

18.00

Design, Installation, interconnection cabling, testing andcommissioning of 24V, 40 Amp. Float-Cum-Boost Battery Charger (oras per state practice) with full wave rectification for 230 V, 1 phase,50 Hz AC Input Supply with built in DCDB as per approved drawings,technical specifications and scope of the work

Set 1

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lightingmasts, 2x90 watts LED flood light fittings on each mast, Junction boxes of thefittings, area lighting power distribution board, 2 nos. 3 Phase 63 Amp powerreceptacles, tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations forreceptacles, distribution boards etc as required as per approved drawings,specifications and scope of work.

Set

1

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled withsand and mounted on 50x50x6 MS stand duly painted as per TechnicalSpecification, approved Drawing & Scope of works.

SET 1.00

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 10

Page 29 of 32

Page 501: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 60

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 140

Page 30 of 32

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 140

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 8

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 800

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 960.00

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 480

8.00

Laying out, tensioning, binding of conductor and tightening of staysand stringing, testing and commissioning of AAAC Wolf Conductor offollowing sizes including jointing sleeves, helical formed fittings,jumpering and by providing & erecting PG Clamps etc as required asper approved drawings, scope of work and technical specifications:::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt.km

10.00

Page 30 of 32

Page 502: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 200

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG forguarding, GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mmdia, 1800 mm long with nuts & bolts.

Set 10

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 10

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 60

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 140.00

Page 31 of 32

2.00

Excavation(of depth 1/6th of pole length) in normal soil and erection of 8.5 mPSC Poles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No. 60

3.00

Excavation(of depth 1/6th of pole length) in Soft soil and erection of 8.5 m PSCPoles with boulder packing of 200 mm average size bolders mixed withexcavated earth etc per pole at the bottom and surrounding the pole withthorough & vigorous ramming. The gaps between the boulders are to be filled byearth as per scope of work, approved drawings and technical specifications. 8.5mtr PSC pole as per approved GTP.

No 140.00

4.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 5

5.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 40

6.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 100

7.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 480

8.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 240.00

9.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt.Km

10.00

Page 31 of 32

Page 503: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

10.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 10

Total:

Page 32 of 32Page 32 of 32

Page 504: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

1 2 3 4A New 33/11 KV Substation Works

CIVIL WORKS1 Soil Testing 12 Boundary wall inculing Gate R/Mt 220

3 Construction of Assam Type control room building with best quality Dyna roof (blueclour) including , Senitary, Internal electrification etc.complete

Sq.M 120

4Water supply: Deep well with 1 HP motor- Pump,Overhead water resurvior capacity2x500 Ltr over the GI staging with necesssary pipeline with connection,stand & powerconnection appliances.

set 1

5 Approach road , 4.0 Mtr width Mtr 506 Drainage System Mtr 1007 Foundation of Pad for 33/11KV power transformer No 18 Foundation of Pad for 33/.433 KV power transformer No 19 Const. of Cable Trenches as per specification with following sizes : -

(a) Width 600mm x Depth . RM 150

10 Gravelling of switch yard, depth 22.5 Cm with crushed stone size 40 mm Sq Mtr. 1200

11 Earth Filling CM

ASSAM POWER DISTRIBUTION COMPANY LIMITED

Sl.No. ITEM DESCRIPTION UNIT

BOQ: Construction of 33/11KV New S/S within the Dima Hasao District under DDUGJY-II/XII Plan Scheme.

New S/S,1x5 MVAMahur (DimaHasao)(LILO)

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DMH

STANDARD BILL OF MATERIALS (as per site requirement)

Rural Electrification works in Dima Hasao Project in Assam under DDUGJY Phase-II (REDB works)

Page 1 of 30

11 Earth Filling CM12 Sign Board, size: 4 feetx3 feet No 1

13(a) 33/11KV 5 MVA Power Transformer Nos. 1

14(a) 33KV,1250A, 25 KA Vaccum Circuit Breaker preferably CG, ABB, Siemens, Schneidermake

Nos. 2

15 33 KV Current Transformer (400-200/5-5-5 Amps for Power Tr.) Set 1

16 33 KV Current Transformer ( 400-200/5-5A for Feeder) Set 1

18 33KV , 10 KA Lightning Arrester with chagre monitor and GI mounting(set of 3 units)Station Type

Set 3

19 33KV , 10 KA Lightning Arrester with chagre monitor and GI mounting(set of 3 units)Line Type

Set 1

20 33 KV ,1250 Amp Isolator with earth blade Set 221 33 KV ,1250 Amp Isolator without earth blade Set 5

22 33KV Transformer Panels preferably CG,ABB,Siemens,Schneider make Nos. 1

23 33KV Feeder Panels preferably CG,ABB,Siemens,Schneider make Nos. 1

24 33 KV Potential Transformer Set 1

25 11KV, Vaccum Circuit Breaker with Marshelling Box.preferably CG, ABB, Siemens,Schneider make

No. 5

26 Control & Relay panel for 11 KV out door Feeder VCB preferably CG, ABB,Siemens,Schneider make

No. 4

27 Control & Relay panel for 11 KV out door Transformer VCB preferably CG,ABB,Siemens,Schneider make

No. 1

28 11 Kv Current Transformer 600-300/5-5-5A with Marshilling Box and GI Structure Set 1

29 11 Kv Current Transformer 300-150/5-5A with Marshilling Box and GI Structure Set 4

30 11 KV Isolator Double break with earth switch with GI structure(800A) Set 431 11 KV Isolator Double break without earth switch with GI structure(800A) Set 837 11 KV Out door Potential Transformer Set 238 11 KV LA Line Type (set of 3 units) Set 4

EQUIPMENT & MATERIALS FOR CONSTRUTION OF SWITCHYARD

Page 1 of 30

Page 505: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

1 2 3 4

Sl.No. ITEM DESCRIPTION UNIT

New S/S,1x5 MVAMahur (DimaHasao)(LILO)

39 11 KV LA Station Type (set of 3 units) Set 141 110 V, 150 AH Lead Acid Battery bank, etc. Set 142 Battery charger etc. No. 149 Control Cable Copper 7 Core 2.5 Sq mm (avg.80m) Mtr 410050 Control Cable Copper 4 Core 2.5 Sq mm(avg.80m) Mtr 2800

51 3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVCsheathed cable

Mtr 100

52 Substation G.I.steel structure as per T.S.(33 & 11 KV Bus) MT 1555 Station service transformer, 33/.433KV,100 KVA Nos. 156 Distrbutiob Box Nos. 157 LTACDB ,DCDB Etc. Set 1

58 Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station with

a 75 x8 mm MS flat for ground mat MT 3b 50 x 6 mm Galvanized GS flat (risers) MT 1c 25 x 6 mm Galvanized GI flat (risers) MT 1d 25mm dia MS rod 3 m long for earth mat MT 0.259 40 mm dia,3000 mm length GI Earth Pipe No 2560 ACSR Panther Conductor for Bus bar Km 0.4

61 33KV Disc Insulators, fittings,clamps,etc.(90KN) Set of 3nos.

30

62 11KV Disc Insulators, fittings,clamps,etc.(70KN) Set of 3nos.

54

63

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2Type Trolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

Page 2 of 30

63

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2Type Trolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

64 External Electrification at station yard lighting with 12 Nos lightening 90 Watt LEDLamp .

set 1

65Substation Tools and Plants like megger, earth tester, Multimeter, Tong tester, Box-spanners, D-spanners, screw drivers, earthing rods, earth mat etc as required as perscope of work.

Set 1

66 New 33&11 KV Line LILO from MaibongFeeder

a 33 KV Line Km 4b 11 KV Line Km 10

Page 2 of 30

Page 506: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

1 2 3 4

A New 33 kV Line Ckt.Km.

4.00

1 MS Steel Tubular Pole SP 60, 12 M long 208 Kg as per T.S.(12 Mtr) No. 802 33 KV GI Channel Cross Arm (100x50x6x3200 mm) No. 323 33 KV GI GI Channel Cross Arm (100x50x6 mm) Mtr. 724 Jam Clamp of GI Flat 65x6 mm Pair 2085 33KV GI Line Pole Top Cleat (100x50x6 mm) No. 486 33 KV Polymeric Pin Insulator No. 3847 33 KV Polymeric Disc Insulator 90 KN with Hardware fittings No. 1928 Tension Clamp for Wolf Conductor No. 969 AAA Wolf Conductor (19/3.40 mm) Km. 13.2

10 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm, Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 40

11 Guy Insulator (HT) No. 8012 Stay Wire 7/4.0 mm Kg 320

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 240

Rural Electrification works in Dima Hasao Project in Assam under DDUGJY Phase-II (REDB works)

BOQ: Construction of 33/11KV New S/S within the Dima Hasao District under DDUGJY-II/XII Plan Scheme.

(Bill of Quantities)Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DMH

Page 3 of 30

13 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 240

14 Jointing Sleeve for Wolf No. 1215 PG Clamp for Wolf (Alcon 80) No. 9616 Al. Binding Wire (10 SWG.) Kg 2417 GI Nuts & Bolts (assorted) Kg 32018 G. I. Wire (6 SWG) for Earthing & Guarding Kg 16019 33 KV Danger Plate (1.6 mm thick) No. 8020 Barbed Wire Kg 16021 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8022 GI 'I' Hook No. 023 GI Angle Cross Arm (65x65x8x3500)mm for Guarding No. 024 Materials for Grouting of Steel Tubular Pole with CC works as per TS No. 80A1 33 KV Overhead Line Crossing - Line to line / Road: Set 41 Galvanized Angle Cross Arm (65x65x8x3500) mm for Guarding No. 82 GI wire 8 SWG for cross lacing as per T.S Kg. 403 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 804 GI 'I' Hook No. 165 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 8

B New 11 kV Line Ckt.Km.

10

1 PSC Pole, 8.5 Mt. long 550 Kg. No. 2002 11 KV GI 'T' Cross Arm of angle size 50x50x6 mm No. 1203 Galvanized Channel Cross Arm 75x40x6X2200 mm No. 804 Composite Polymeric 11 kV Pin Insulator No. 4805 Composite Polymeric 11 kV Disc Insulator (70 KN) with Hardware fittings. Set 2406 Tension Clamp for Raccoon No. 2407 AAA Raccoon Conductor (7/3.81 mm, 79.80 Sqmm) Km. 33

8 HT Stay Set, Stay Clamp 50x8 mm , Anchor Plate (200x200x6)mm,Turn Buckles (2 Nos.),Solid GS Stay Rod (1.8 mtr long, 16 mm diameter) complete.

Set 100

9 HT Guy Insulator No. 100

Page 3 of 30

Page 507: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl.No.

ITEM DESCRIPTION UNIT QTY

10 GI Stay wire 7/3.15 mm Kg. 800

11 Galvanized Angle Cross Arm (50x50x6) mm for Cross Bracing for DP/TPs/FPs, as per T.S. Mtr. 400

12 GI wire 6 SWG for Earthing Kg. 10013 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 4014 Jointing Sleeve for Raccoon No. 3015 PG Clamp for Raccoon No. 24016 AI. Binding Wire (10 SWG.) Kg. 5017 Pole Clamp of GI flat (50x6) mm No. 16018 GI Barbed Wire for anticlimbing device Kg. 40019 11 KV Danger Plate (1.6 mm thick) No. 20020 GI Nuts & Bolts with GI washer (Assorted) Kg. 300B1 11 KV Overhead Line Crossing - Line to line / Road: Set 101 Galvanized Angle Cross Arm (50x50x6X2500) mm for Guarding No. 202 GI wire 8 SWG for cross lacing as per T.S Kg. 1003 GI wire 6 SWG for Earthing & Guarding with GI Nut and Bolts Kg. 2004 GI 'I' Hook No. 405 CI Earth Pipe 1.8 Mtr. longm, 100 mm dia as per TS. No. 20

Page 4 of 30Page 4 of 30

Page 508: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:New 33/11 KV Substation Works (Excluding civil works)

Schedule-1Rural Electrification works in Dima Hasao Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Ex-works Supply of Materials

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DMH

Page 5 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00MVA with off load tap changer Power Transformer along with transformeroil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank,oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(withbraided conductor on bushing end), isolating link, isolation with insulators,Vent explosion plug, control wiring between sensing equipment andmarshalling box, cable supporting tray on the body of transformer, transformerwheels, LV/HV bushing etc as required as per technical specifications, approveddrawings and scope of the work.

No 1

2.00

100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGOcore, outdoor type Station Transformer along with transformer oil and allaccessories as required as per technical specifications, scope of works andapproved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat asper approved drawings. State practices are to be adopted in the design. Allstructural steel members and bolts shall be galvanized after fabrication as perIS:4759 and zinc coating shall not be less than 610gm/sq. meter for allstructural steel members. All L45x45x5 will have 23 mm back mark. AllL50x50x6 will have 28mm back mark. 3.5mm spring washers are to be usedunder each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be ofproperty class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & springwashers shall be IS: 3063 as per technical specifications, scope of works andapproved drawings..

MT 15

Page 5 of 30

Page 509: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

, supporting structures, bi-metallic terminal clamps, permanent maintenance

platform, marshalling box etc required as per technical specifications, scope of

works and approved drawings (for Transformer & feeder)

Nos 2

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformersalong with junction box (1 no junction box for 3 no of 1-phase CTs),supporting structures, bi-metallic terminal clamps, permanent maintenanceplatform, marshalling box etc required as per technical specifications, scope ofworks and approved drawings (for Feeder)

Sets 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

Page 6 of 30

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type CurrentTransformers along with junction box (1 no junction box for 3 no of 1-phaseCTs), supporting structures, bi-metallic terminal clamps, permanentmaintenance platform, marshalling box etc required as per technicalspecifications, scope of works and approved drawings (for Transformer)

Sets 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For 33 kV feeder VCB with Static Tri-Vector EnergyMeter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, specifications and scopeof works controlling: For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (with EarthBlade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type(DBCR), Gang Operated isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (withoutEarth Blade)

Set 5

Page 6 of 30

Page 510: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

3

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as per technicalspecifications, approved drawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per technical

specifications, approved drawings and scope of the works.

No 5

Page 7 of 30

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker, supporting structures, bi-metallic clamps, permanent maintenance

platform, marshalling box, and required accessories complete as per technical

specifications, approved drawings and scope of the works.

No 5

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supportingstructures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications,approved drawings and scope of the works.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform,hardware, etc as required as per technical specifications, approved drawingsand scope of the works.

Set ofthree

4

Page 7 of 30

Page 511: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB

(Transformer Breaker) consisting of A-meter, volt-meter, Relays & accessories

complete as per specifications for transformer breaker protection

For Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (FeederBreakers) consisting of A-meter, volt-meter, Relays, energy meter (TVM) &accessories complete for feeder breaker protection as per technicalspecifications, approved drawings and scope of works. For 11 kVfeeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 4

Page 8 of 30

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithEarth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type(DBCR), Gang Operated Isolator along with Support Insulators, OperatingMechanism, Base Channel, down Pipe and all required accessories complete asper technical specifications, scope of works and approved drawings (WithoutEarth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type PotentialTransformer along with junction box (1 no junction box for 3 no of 1-phasePTs), bi-metallic clamp and required accessories etc., complete as pertechnical specifications, approved drawings and scope of the works.

Set ofthree

2

36.00

ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations includinghardware fittings, hardware, T-claimp etc as per technical specifications,approved drawings and scope of works. 30/3.00 + 7/3.00 mm(200 mm² Al. Area) - Panther

Km 0.4

37.00

3.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulatedand PVC sheathed LT Power Cables including their termination materials likeglands, lugs, tagging etc. as per technical specifications, approved drawingsand scope of the work.

Mtr 100

Page 8 of 30

Page 512: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

38.00

4 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 2800

39.00

7 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated andPVC sheathed LT Control cables including their termination materials likeglands, lugs etc. as per technical specifications, approved drawings and scopeof the work

Mtr 4100.00

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::75 x 8 mm GI flat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 1

Page 9 of 30

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::50 x 6 mm Galvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25 x 6 mm Galvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works::25mm dia GI rod 3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCCcover, placed on GI frame, bantonide powder and other accessories completeas per technical specification. (for Power Transformer Neutral, StationTransformer Neutral and Lightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter

and Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps

TPN switches as outgoing feeders suited for number of control panels, nos of

VCB kiosk panel, having 20% spare outgoing feeders, mounting arrangements

etc as per technical specifications, approved drawings and scope of works.

Set 1

Page 9 of 30

Page 513: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switchfuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactorcontrolled yard lighting timer unit, tri-vector electronic energy meter withsuitable CT, control/power cabling and terminals, 1 No 20 A Industrial socketand switch for local power supply requirements, mounting channel, clamps andhardware as per scope of work, technical specifications and approveddrawings,

Set 1

47.0033 KV, 90 KN porcelain Disc insulators along with suitable hardware &accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

Page 10 of 30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware &

accessories suitable for Panther conductors as per approved drawings &specifications.

Set ofthree

54

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single core multi strand cable,terminal connectors, & all other accessories and connectors as per technicalspecifications, approved drawings and scope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB as per technicalspecifications, approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, stationyard lighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings)made of 12 meters high Steel Tubular Poles (IS 2713 part I, II III) ofdesignation 410 – SP - 60, complete as per technical specifications, approveddrawings and scope of the work.

Set 1

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, OneMultimeter, One Tong tester, One set of Box spanner, One set each Roundand D-spanners with various range, screw drivers with various size one each,earthing rods, etc as required as per scope of work.

Set 1

Page 10 of 30

Page 514: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6Kg) for control room; Two nos CO2 Type of 4.5Kg Capacity for ControlRoom,two sets of fire buckets set including their stand for Control Room &Station Yard and One no. CO2 Type Trolley Mounted of 22.5 Kg Capacity forSwitch Yard.

Set 1

B.

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540SP 60 (IS 2713, Pt I, II, III 1980)Supports for 33 KV overhead line as pertechnical specification, approved drawings and scope of work.

No 80

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels,back clamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm),GI flats (65x8mm) of given sizes for over head structures as per technicalspecification, approved drawings and scope of work.

MT 3.23

New 33 KV Lines

Page 11 of 30

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC crossarm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels,back clamp etc made of GI Channels (100x50x6mm), GI angle (65x65x6mm),GI flats (65x8mm) of given sizes for over head structures as per technicalspecification, approved drawings and scope of work.

MT 3.23

3.00 GI Nuts, bolts and washers as per technical specification, approved drawingsand scope of work.

MT 0.32

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.),

anchor plate (300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20

mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete as

per technical specification, approved drawings and scope of work.

Set 320

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessoriescomplete for earthing arrangement as per technical specificatons, approveddrawings and scope of work.

Set 80

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.16

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas pertechnical specification, approved drawings and scope of work

Set 192

8.0033 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification,approved drawings and scope of work

Set 384

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, bindingmaterials, PG clamps, bi-metallic conductor, hardware etc for overhead line andjumpers as required as per technical specification, approved drawings andscope of work Size:: 19/3.40 (Al.alloy Area 173 sqmm ) - Wolf

km 13.20

Page 11 of 30

Page 515: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm(65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG& 8 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mmlong with nuts & bolts.

Set 4.00

C

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification,approved drawings and scope of work alongwith Danger Plate and Barbed Wireas per approved GTP, as per state practice.

No. 200

2.00

Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm,

angle, flats and all other GI materials shown in BOQ for over head structures

as per technical specification, approved drawings and scope of work.

MT 4.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.3

New 11 KV Lines

Page 12 of 30

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification,approved drawings and scope of work.

MT 0.3

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts,2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15mm GI stranded wire etc as required as per technical specification, approveddrawings and scope of work.

Set 100

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas pertechnical specification, approved drawings and scope of work.

Set 240

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification,approved drawings and scope of work.

Set 480

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Saltand other accessories complete as per technical specification, approveddrawings and scope of work for 11 KV line earthing

Set 40

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification,approved drawings and scope of work.

MT 0.1

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA RaccoonConductors with Jointing sleeves, binding materials, PG clamps, TensionClamps, bi-metallic clamp etc. for overhead line and jumpers as required as pertechnical specification, approved drawings and scope of work. (7/3.81 mm,79.80 Sqmm)

Km 33.00

Page 12 of 30

Page 516: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

ITEM DESCRIPTION Unit QtyUnit Ex-worksprice

Total Ex-worksprice

Mode ofTransaction

(Direct/Bought-out items)

Excise Duty,Levies. Etc

andOther Central

Taxes etc.(as

applicable)

AssamValue

Added Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Excise Duty @Central Tax etc.Assam VAT @

1 2 3 4 5 6=4x5 7 8 9=(6+8)x@__%

10

10.00

Protective guarding as per REC construction standard drawing No A-1 to beprovided at locations where 11KV/33 KV line is crossing road, 11 KV line iscrossing LT Lines/ P&T lines etc. Supplying 2 Nos guarding GI angle cross arm(50x50x6x2500mm), 2 Nos Y- guy with 7/3.14 mm wire, 2 Nos 16 mmdiameter Eye-bolts, 2 Nos earthing of 100mm dia CI earth pipe of 1.8 meterlong, 6 SWG GI wires for earthing connection, 6 SWG wire for guard wire, 8SWG wire for cross lacing.

set 10.00

Total Ex-works

Page 13 of 30Page 13 of 30

Page 517: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

1 2 3 4 5 6=(4x5) 7=6x15% 8=(6+7)x@_%)

9

New 33/11 KV Substation Works (Excluding civil works)A. 33/11 KV Substation Works

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

All prices in Indian RupeesBidder's Name & Address:

Schedule-2Rural Electrification works in Dima Hasao Project in Assam under DDUGJY Phase-II (REDB works)

(Schedule of rates and prices)Local Transportaion, Insurance and other Incidental Services

Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DMH

Page 14 of 30

1.02

33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type 5.00 MVA withoff load tap changer Power Transformer along with transformer oil, Buchholtz relay,breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 setsof 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end),isolating link, isolation with insulators, Vent explosion plug, control wiring betweensensing equipment and marshalling box, cable supporting tray on the body oftransformer, transformer wheels, LV/HV bushing etc as required as per technicalspecifications, approved drawings and scope of the work.

No 1

2.00100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN, Four Star Aluminium wound, CRGO core,outdoor type Station Transformer along with transformer oil and all accessories asrequired as per technical specifications, scope of works and approved drawings.

No 1

4.00

Gantry structures made of Lattice structures of equal angles sections, flat as perapproved drawings. State practices are to be adopted in the design. All structural steelmembers and bolts shall be galvanized after fabrication as per IS:4759 and zinc coatingshall not be less than 610gm/sq. meter for all structural steel members. All L45x45x5 willhave 23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring washersare to be used under each nut, structural steel shall conform to IS 2026. All weld shall be6mm filled weld unless specified otherwise. All nuts and bolts shall be of property class5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063as per technical specifications, scope of works and approved drawings..

MT 15

5.00

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker ,supporting structures, bi-metallic terminal clamps, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings (for Transformer & feeder)

No 2

Page 14 of 30

Page 518: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

7.00

36kV, 1-Phase, 200-100/5-5 Amps 3 Nos outdoor type Current Transformers along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forFeeder)

Set 1

8.00

36kV, 1-Phase, 200-100/5-5-5 Amps 3 Nos outdoor type Current Transformers alongwith junction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic terminal clamps, permanent maintenance platform, marshalling box etcrequired as per technical specifications, scope of works and approved drawings (forTransformer)

Set 1

10.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and othercomponents etc as per approved drawings, specifications and scope of works controlling:For 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 15 of 30

11.00

33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram,

Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other

components etc as per approved drawings, specifications and scope of works controlling:

For Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No 1

12.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (with Earth Blade)

Set 2

13.00

36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), GangOperated isolator along with Support Insulators, Operating Mechanism, Base Channeldown Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (without Earth Blade)

Set 5

14.0036 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardwareetc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

3

15.0036 kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

1

16.00

36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

1

17.00

12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker,supporting structures, bi-metallic clamps, permanent maintenance platform, marshallingbox, and required accessories complete as per technical specifications, approveddrawings and scope of the works.

No 5

Page 15 of 30

Page 519: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

18.00

12 kV, 1-Phase, 600-300/5-5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks. (for Transformer)

Set 1

19.00

12 kV, 1-Phase, 300-150/5-5 3 Nos outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box, and requiredaccessories complete as per technical specifications, approved drawings and scope of theworks.(for Feeder)

Set 4

20.009kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, hardware,etc as required as per technical specifications, approved drawings and scope of theworks.

Set ofthree

1

21.009kV, 10kA, 1-ph Line Class Lightening Arrester with mounting platform, hardware, etc

as required as per technical specifications, approved drawings and scope of the works.

Set ofthree

4

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

Page 16 of 30

22.00

Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of A-meter, volt-meter, Relays & accessories complete as per specifications fortransformer breaker protectionFor Power transformer 11 kV VCB with Static Tri-Vector Energy Meter

No 1

23.00

Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers)

consisting of A-meter, volt-meter, Relays, energy meter (TVM) & accessories complete

for feeder breaker protection as per technical specifications, approved drawings and

scope of works. For 11 kV feeder VCB with Static Tri-Vector Energy Meter

No 4

24.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (With Earth Blade)

Set 4

25.00

12 kV, 800A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), GangOperated Isolator along with Support Insulators, Operating Mechanism, Base Channel,down Pipe and all required accessories complete as per technical specifications, scope ofworks and approved drawings (Without Earth Blade)

Set 8

26.00

12 kV, 3-pole, 1-Phase, 11kV/110 volt, Single core outdoor type Potential Transformeralong with junction box (1 no junction box for 3 no of 1-phase PTs), bi-metallic clampand required accessories etc., complete as per technical specifications, approveddrawings and scope of the works.

Set ofthree

2

36.00ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardwarefittings, hardware, T-claimp etc as per technical specifications, approved drawings andscope of works. 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther

Km 0.4

Page 16 of 30

Page 520: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

37.003.5 Core 95 Sq. mm armoured, stranded aluminium conductor, PVC insulated and PVCsheathed LT Power Cables including their termination materials like glands, lugs, taggingetc. as per technical specifications, approved drawings and scope of the work.

Mtr 100

38.004 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 2800

39.007 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVCsheathed LT Control cables including their termination materials like glands, lugs etc. asper technical specifications, approved drawings and scope of the work

Mtr 4100

40.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::75 x 8 mm GIflat for ground mat

MT 3

41.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 50 x 6 mmGalvanized GI flat (risers)

MT 1

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1

Page 17 of 30

42.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works ::25 x 6 mmGalvanized GI flat (risers)

MT 1

43.00Earthing & Grounding conductor as per Approved Electrical Layout for each sub-stationas per technical specifications, approved drawings and scope of works:: 25mm dia GI rod3 m long for earth mat

MT 0.2

44.00

40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover,placed on GI frame, bantonide powder and other accessories complete as per technicalspecification. (for Power Transformer Neutral, Station Transformer Neutral andLightening Arresters direct earthing)

No 25

45.00

415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter andSelector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches asoutgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mounting arrangements etc as per technical specifications,approved drawings and scope of works.

Set 1

46.00

Outdoor type Distribution Box for station transformer comprising 200 A switch fuse unit,6 Nos SP MCCB– 90 A, 2 Nos 32 A SP MCCB, 3-ph, 63A, contactor controlled yardlighting timer unit, tri-vector electronic energy meter with suitable CT, control/powercabling and terminals, 1 No 20 A Industrial socket and switch for local power supplyrequirements, mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

Set 1

47.00 33 KV, 90 KN porcelain Disc insulators along with suitable hardware & accessoriessuitable for Panther conductors as per approved drawings & specifications.

Set ofthree

30

48.0011 KV, 70 KN porcelain Disc insulators along with suitable hardware & accessories

suitable for Panther conductors as per approved drawings & specifications.Set ofthree

54

Page 17 of 30

Page 521: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

49.00

110V, 150 AH Lead Acid battery on battery stand, battery insulators, inter-battery wiringusing 30 sqm, 1.1 kv, copper single core multi strand cable, terminal connectors, & allother accessories and connectors as per technical specifications, approved drawings andscope of works.

Set 1

50.00110V, 40 Amp. Float-cum-Boost Battery Charger with full wave rectification for 220 V,1 phase, 50 Hz AC Input Supply with built in DCDB as per technical specifications,approved drawings and scope of works.

Set 1

51.00

External Electrification in switch yard area including power receptacles, station yardlighting with 6 Nos lightening mast (fitted with 2x90 watts LED fittings) made of 12meters high Steel Tubular Poles (IS 2713 part I, II III) of designation 410 – SP - 60,complete as per technical specifications, approved drawings and scope of the work.

Set 1

52.00 33/11 KV Sub-Station Sign Board, Size: 4 feet x 3 feet as per specification Set 1

53.00

Substation Tools and Plants like One 5/2.5 KV megger, One earth tester, One Multimeter,One Tong tester, One set of Box spanner, One set each Round and D-spanners withvarious range, screw drivers with various size one each, earthing rods, etc as requiredas per scope of work.

Set 1

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

Page 18 of 30

54.00

Fire Fighting Equipment comprises of Four nos Dry Chemical Powder Type (6 Kg) forcontrol room; Two nos CO2 Type of 4.5Kg Capacity for Control Room,two sets of firebuckets set including their stand for Control Room & Station Yard and One no. CO2 TypeTrolley Mounted of 22.5 Kg Capacity for Switch Yard.

Set 1

B. New 33 KV Lines

1.0012 M long steel Tubular poles with welded steel base plate of Designation 540 SP 60 (IS2713, Pt I, II, III 1980)Supports for 33 KV overhead line as per technical specification,approved drawings and scope of work.

No 80

2.00

Pre-fabricated(Galvanised) steel items like V cross arm, top clamp, DC cross arm,bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp etcmade of GI Channels (100x50x6mm), GI angle (65x65x6mm), GI flats (65x8mm) ofgiven sizes for over head structures as per technical specification, approved drawingsand scope of work.

MT 3.23

3.00 GI Nuts, bolts and washers as per technical specification, approved drawings and scopeof work.

MT 0.32

4.00

Stay Set (Galvanised) with 50x8 mm stay clamps, guy insulator (2 Nos.), anchor plate(300x300x8mm) , nut bolts, 2 Nos turn-buckles, 1.8 m long, 20 mm diameter solid GSstay rod & 7/4.00 mm dia GI stranded wire complete as per technical specification,approved drawings and scope of work.

Set 320

5.00100 mm dia., 1800 mm long CI pipe earth electrode and other accessories complete forearthing arrangement as per technical specificatons, approved drawings and scope ofwork.

Set 80

6.00 6 SWG GI wire for earthing with GI nuts, bolts & washers MT 0.16

7.00 33 KV polymer Disc insulator 70 KN along with suitable hardware fittingsas per technicalspecification, approved drawings and scope of work

Set 192

Page 18 of 30

Page 522: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

8.00 33 KV Polymer Pin Insulators 10 KN with GI PIN as per technical specification, approveddrawings and scope of work

Set 384

9.00

AAAC Wolf Conductors of following sizes with Jointing sleeves, binding materials, PGclamps, bi-metallic conductor, hardware etc for overhead line and jumpers as required asper technical specification, approved drawings and scope of workSize:: 19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

km 13.2

10.00

Line Crossing-Line to line, line to road with items, GI Angle Cross Arm (65x65x6x3500

mm) for guarding, GI Wire 8 SWG for guarding, GI Wire 6 SWG & 8 SWG for guard

earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800 mm long with nuts & bolts.

Set 4

C New 11 KV Lines

1.008.5 m PSC Poles Support for 11 KV overhead line as per technical specification, approveddrawings and scope of work alongwith Danger Plate and Barbed Wire as per approvedGTP, as per state practice.

No. 200

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 4.54

Page 19 of 30

2.00Galvanized pre-fabricated steel materials like T Cross arm, channel cross arm, angle, flatsand all other GI materials shown in BOQ for over head structures as per technicalspecification, approved drawings and scope of work.

MT 4.54

3.00 Galvanized Steel Nuts, Bolts with Washers as per technical specification, approveddrawings and scope of work.

MT 0.3

4.00

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut bolts, 2 Nos

turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm GI stranded

wire etc as required as per technical specification, approved drawings and scope of work.

Set 100

5.00 Composite Polymeric 11 KV Disc Insulator 70 KN with Hardware fittingsas per technicalspecification, approved drawings and scope of work.

Set 240

6.00 Composite Polymeric 11 KV Pin insulator as per technical specification, approveddrawings and scope of work.

Set 480

7.00100 mm dia., 1800 mm long CI earth pipe earth electrode with Charcoal, Salt and otheraccessories complete as per technical specification, approved drawings and scope ofwork for 11 KV line earthing

Set 40

8.00 6 SWG GI Wire for earthing of 11 KV Line, as per technical specification, approveddrawings and scope of work.

MT 0.1

9.00

AAA Racoon coductor alongwith Supply of items for erection of AAA Raccoon Conductorswith Jointing sleeves, binding materials, PG clamps, Tension Clamps, bi-metallic clampetc. for overhead line and jumpers as required as per technical specification, approveddrawings and scope of work. (7/3.81 mm, 79.80 Sqmm)

Km 33

Page 19 of 30

Page 523: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sr.No.

Description Unit Qty

UnitFreight &InsuranceCharges

Total Freight& Insurance

Charges

ServiceTax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages tobe mentioned

here)Assam VAT @

10.00

Protective guarding as per REC construction standard drawing No A-1 to be provided atlocations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&Tlines etc. Supplying 2 Nos guarding GI angle cross arm (50x50x6x2500mm), 2 Nos Y-guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 100mmdia CI earth pipe of 1.8 meter long, 6 SWG GI wires for earthing connection, 6 SWG wirefor guard wire, 8 SWG wire for cross lacing.

set 10

Total

Page 20 of 30Page 20 of 30

Page 524: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Bidder's Name & Address:

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1 2 3 4 5 6=(4x5) 7=(6x15%) 8=(6+7)x@___% 9

A 33/11 KV Grid Substation works

A-Ia Civil works: Design, supply of all material, T&P, labour etc for thefollowing civil works complete

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PER S/S 1

Schedule-3

All prices in Indian Rupees

Installation / Erection Charges :Specification No. APDCL/DDUGJY/II/XII/REDB :: Package No: DDU/II/XII/REDB/DMH

(Schedule of rates and prices)Rural Electrification works in Dima Hasao Project in Assam under DDUGJY Phase-II (REDB works)

Page 21 of 30

1.00

Detail sub-soil investigation report about specific information about the soil

profile and necessary soil parameters of sub-station site & recommendations of

soil mechanic engineer regarding foundation depth of defferent type of footings

with size including contour survey etc. as per Technical Specification.

PER S/S 1

2.00

Earth work in PSS site for raising low site with approved soil obtained fromoutside by truck carriage and filling in layers not more than 150 mmthick,watering ramming etc. complete as directed and specified includingpayment of land compensation,forest royalty,sale tax and other duties and taxesas may be necessary.

CuMtr 0

3.00Switchyard gravel filling with crushed stone size 40 mm(HBG) with depth 22.5Cm thickness including supply of materials,spreading, Leveling etc. and labouras per direction.

Sq. m 1200

5.00

Design and construction of foundation for following power transformerconsidering original equipment manufacturer recommendations and as per soil &site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:5.00 MVA with offload / on load tap changer

No 1

7.00

Design and construction of foundation for Station Service transformer as per soil& site requirment including excavation of pit, shuttering, reinforcement, cementconcreting including providing and erecting guiding rail, wheel stopper etc as perTechnical Specification, approved Drawing & Scope of works:::33/.4 ,100 KVAStation Service Transformer

No 1

8.00

Design and construction of foundation for following 33 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 2

Page 21 of 30

Page 525: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Design and construction of foundation for following 11 KV outdoor mountedVacuume Circuit Breaker considering original equipment manufacturerrecommendation and as per soil & site requirment including excavation of pit,shuttering and by providing reinforcement, cement concreting, painting etc asper Technical Specification, approved Drawing & Scope of works. Works alsoincludes providing working platform for operation of breakers and painting.

Nos. 5

10.00

Fabrication ,Foundation and Erection of Gantry structures using , lattice structure

(galvanised including hardware), GI channel, GI angle and GI flat of various sizes

including GI nuts & bolts, etc as required as per soil & site requirment and as

per Technical Specification, approved Drawing & Scope of works

MT 15

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

Page 22 of 30

11.00

Construction of 1st Class brick wall made of RCC Beam, Column & Footingincluding preparation of base by providing soling and 10 cm PCC and plasteringskinting etc. including supplying ,fitting and fixing barbed wire on top of brickboundary wall with eight strands of barbed wire 12 SWG fitting to Y cross arm at2.5 m apart including supplying fitting and fixing with galvanized staples 38mm x38mm x 3mm . Y cross arm 65 x 65 x 5 mm should be embeded 350 mm in allposts. the vertical distence from top of boundary wall to the top of Y cross arm is600 mm,3 Nos of barbed wire should be fitted in each arm of the Y cross arm &2 nos. in strraight portion including fabrication,errection & painting of Y crossarm with anticorrosive ready mixed and aluminium paint complete includingstraightining and tightening of barbed wire as directed and instllation of slidingsteel gate at the entrance of S/S boundary wall including supply ofmaterials,painting and labour as per technical specification,approved drawingand scope of works.

R/Mtr 220

12.00

Design and construction of Assam type Control Room Building with PPGI sheetDyna roofing of 0.8 mm thick (Supreme quaility, Blue Clour)including fitting &fixing with self drilling,self tapping screws over truss, burse board, gutter,downwater rain pipe, bird net, vitified tiles white cement flooring, indoor cable tranch,plain asbestor ceiling (4 mm thickness)oil bound plastic paint washabledistemper on smooth surface of wall applied with POP putty,doors,windows,ventilation should be Anodised aluminium Indal or equivalent,glass min 5.5 mmthick, Acid proof tiles for battery room,including water supply alongwith supplyand installation of Aqua gurrd water purifier, sanitary works , septic tank,soakpit,drain appron, sign board including labour etc. .Erection, testing andcommissioning of Internal electrification work in Substation Control room as perapproved drawings, specifications and scope of work by installing, erection,testing and commissioning of fans, exhaust fans, fluorescent lighting, LED lamps,L&F, power points, wiring materials, Distribution Boards, Sub-distribution boardsetc. as per Technical Specification, approved Drawing & Scope of works.

Sqm 120

Page 22 of 30

Page 526: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

13.00

Design and construction of cement concrete Cable Trench of 0.6 Mtr wide,required depth(not less than 0.6 mtr), precast RCC Trench Cover, Water slop,cable supporting angles including Labour, Reinforcement Steel, MS Angles, Flats,Steel Frame Work, Excavation etc, all complete as per Technical Specification,approved Drawing & Scope of works.

R/Mtr 150

14.00

Construction of pucca drainage with 150 mm thick 1st class brick wall of 0.80mtr. height, 45 cm bottom width including preparation base by providing solingand 10cm PCC and plastering skinting etc. for easy drainage system inside thesub-station premises including supply of all meterials and labour etc. as perTechnical Specification, approved Drawing & Scope of works.

R/Mtr 100

15.00Construction of 4.0 m width approach road with WBM & bitumen carpeting etc.including supply of all meterials and labour and all complete as per TechnicalSpecification, approved Drawing & Scope of works

R/Mtr 50

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

Page 23 of 30

16.00

Supply and Installation of deep tube well with Single Phase Submersible motorpump set (Texmo/Crompton Greaves/ Aquastic/CRI/V-Guar suitable for 100 mmbore well and above. 1 HP STAGE 5 to 18 with control panel along with 2x500 Ltroverhead Sintex make water storage Tank over the GI staging with manholecover with locking and cleaning arrangement including providing pads of size asrequired for inlet and outlet pipe complete including fitting and fixing allmaterials and filter to get potable water as per approved drawing andspecification.

SET 1

A(Ib) Substation Electrical works

1.00

Erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type 5.00 MVA with off load tap changer PowerTransformer along with transformer oil, Buchholtz relay, breather, OTI & WTI,Marshalling Box, Conservator tank, oil level indicator, valves by providing 2 setsof 50x8 mm GS Neutral Earthing strips with braided conductor on bushing endsupported with insulators, OTI & WTI Indicators, Vent explosion plug, controlwiring / cabling, cable supporting tray on the body, transformer wheels, bushingetc as per Technical Specification, approved Drawing & Scope of works

No 1

2.00

Erection, testing and commissioning of 100 KVA, 33/0.4 kV, 3 ph, 50 Hz, ONAN,

aluminium would outdoor type Distribution Transformer (Station Transformer) as

per Technical Specification, approved Drawing & Scope of works

Set 1

A (Ic) 33KV Yard

1.00

Erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor type Vacuum Circuit breaker along with Jumpers, earthing, supportingstructures, maintenance platform, marshalling box, control cabling between VCBand indoor control panel and required accessories complete as per approveddrawings, technical specifications and scope of the work.

No 2

Page 23 of 30

Page 527: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Design and construction of foundation (as per approved drawings), erection,testing and commissioning of 36kV, 1-Phase, 25kA for 3 seconds, 400-200/5-5-5, 400-200/5-5,400-200/1-1 Amps outdoor type Current Transformer along withjunction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing,supporting structures, maintenance platform, marshalling box, control cablingbetween CT and indoor control panel and required accessories complete as perapproved drawings, technical specifications and scope of the work.

Set ofthree

2

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: :: 33 kV feeder VCB with Static Tri-VectorEnergy Meter

No 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 1

Page 24 of 30

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of33kV indoor Control &amp; Relay panel along with E/F &amp; O/C relays, controland power supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: ::: Power transformer 33 kV VCB with StaticTri-Vector Energy Meter

No 1

5.00

Design, construction of foundation (as per approved drawings), Erection, testingand commissioning of 36kV, 1250A, 25kA for 3 sec, 3-ph double break centerrotating type (DBCR) isolator along with Support Insulators, OperatingMechanism, Base Channel down Pipe, Jumpering and all required accessoriescomplete as per approved drawings, technical specifications and scope of thework,

Set 7

6.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36kV, 10kA, 1-ph Station Class Lightening Arresters withmounting platform, jumpering , earthing connection using 50x6mm GS flat,hardware etc as required, as per approved drawings, technical specifications andscope of the work,

Set ofthree

4

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 36 kV, 1-Phase, 33 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling, earthing connectionusing 50x6mm GS flat,Jumpering and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

1

A (Id) 11KV Yard

Page 24 of 30

Page 528: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

1.00

Design, construction of foundation (as per approved drawings), erection,testing and commissioning of 11kV, Outdoor type Vacuum Circuit breaker alongwith Jumpers, earthing, supporting structures, permanent maintenance platform,marshalling box etc required as per technical specifications, scope of works andapproved drawings

No 5

2.00

Design, construction of foundation (as per approved drawings), erection, testing

and commissioning of 11 Kv Current Transformer 600-300/5-5-5A,300-150/5-5

with Marshilling Box and GI Structure, jumpering.etc required as per technical

specifications, scope of works and approved drawings

Set 5

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

Page 25 of 30

3.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Transformer Protection Breaker Panel

Set 1

4.00

Design, providing and installation of ISMC 75 channel on top of indoor trench,erection of panels on ISMC 75 channels, welding, testing and commissioning of11 kV indoor Control &amp; Relay panel along with E/F & O/C relays, control andpower supply cabling in trench between field equipment and panels, MimicDiagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relaysand other components etc as per approved drawings, technical specifications andscope of the work for controlling: Feeder Protection Breaker Panel

Set 4

5.00

Design,construction of foundation (as per approved drawings), Erection, testingand Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester withmounting platform, jumpering from bus bar, earthing connection using 50x6mmGS flat, hardware, etc as required as per approved drawings, technicalspecifications and scope of the work.

Set ofthree

5

6.00

Design, construction of foundation , Erection, testing and commissioning of 3phase, 11 kV, 800A double break center rotating Type(DBCR), Base Channel,Jumpering and all required accessories complete as per approved drawings,technical specifications and scope of the work,

set 12

7.00

Design, construction of foundation (as per approved drawings), Erection, testingand Commissioning of 11 kV, 1-Phase, 11 kV/110 volt, Single core outdoor typePotential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including Jumpering, control and power supply cabling, earthingconnection using 50x6mm GS flat and required accessories etc., complete as peras per approved drawings, technical specifications and scope of the work,

Set ofthree

2

Page 25 of 30

Page 529: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

8.00

Erection, testing and commissioning of Bus Conductor (Panther Conductor), busjumpers to various equipment using 11 KV and 33 KV insulators, GI Pin, GIHardware fittings, PG Clamps, T-connectors etc as required as per approveddrawings, specifications and scope of the work.

Km 0.4

9.00

Power Cables including their termination at indoor/outdoor terminals includingsupply of glands, lugs, cable ties, etc as required3.5 Core 95 Sq. mm armored, stranded aluminium conductor, PVC insulated andPVC sheathed cable

mtr 100

10.00

Excavation, laying, welding, refilling, earthing & grounding conductor as perApproved Electrical Layout for each sub-station and erection of riser up tovarious equipment/gantry structures as per Technical Specification, approvedDrawing & Scope of works:::75 x 8 mm MS flat for ground mat

MT 3

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

Page 26 of 30

11.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::50 x 6 mm Galvanized GS flat (risers)

MT 1

12.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 x 3 mm Galvanized GI flat (risers)

MT 1

13.00

Excavation, laying, welding, refilling, earthing & grounding conductor as per

Approved Electrical Layout for each sub-station and erection of riser up to

various equipment/gantry structures as per Technical Specification, approved

Drawing & Scope of works :::25 mm dia GI Rod 3 m long for earth mat

MT 0.2

14.00

Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm longGI pipe earth electrode by providing test link, RCC pit, RCC cover, placed on GIframe, bentonite powder and other accessories complete as per approveddrawings, technical specifications and scope of the work for power transformerneutral, station transformer neutral, lightening arresters direct earthing.

Set 25

15.00

Erection, testing & commissioning of 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suitedfor number of control panels, nos of VCB kiosk panel, having 20% spare outgoingfeeders, by providing MS angle 50x50x6 mm structure, cement concretefoundation etc as per technical specifications, approved drawings and scope ofworks.

No 1

Page 26 of 30

Page 530: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

16.00

Erection, testing & commissioning of Outdoor type Distribution Box for stationtransformer comprising 200 A switch fuse unit, 6 Nos SP MCCB– 90 A, 2 Nos 32A SP MCCB, 3-ph, 63A, contactor controlled yard lighting timer unit, tri-vectorelectronic energy meter with suitable CT, control/power cabling and terminals, 1No 20 A Industrial socket and switch for local power supply requirements,mounting channel, clamps and hardware as per scope of work, technicalspecifications and approved drawings,

No 1

17.00

Installation, initial charging, cabling, interconnection cabling, testing andcommissioning of 110V, 150 AH Lead Acid battery on battery on battery standbattery insulators, inter-battery wiring using 30 sqm copper single core multistrand cable, terminal connectors, &amp; all other accessories and connectors asper as per approved drawings, technical specifications and scope of the work,

Set 1

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

Page 27 of 30

18.00

Design, Installation, interconnection cabling, testing and commissioning of 24V,

40 Amp. Float-Cum-Boost Battery Charger (or as per state practice) with full

wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per approved drawings, technical specifications and scope of the work

Set 1

19.00

Erection, testing and commissioning of External electrification works ofsubstation including area lighting by 6 No, 12m high steel tubular lighting masts,2x90 watts LED flood light fittings on each mast, Junction boxes of the fittings,area lighting power distribution board, 2 nos. 3 Phase 63 Amp power receptacles,tube well power supply, etc as required by laying power cables inunderground/above ground/trenches, construction of foundations for receptacles,distribution boards etc as required as per approved drawings, specifications andscope of work.

Set 1

20.00

Supply, Erection, testing and commissioning of Fire Fighting Equipmentcomprises of Dry Chemical Powder Type (6 Kg) for control room; CO2 Type of4.5Kg Capacity for Control Room and CO2 Type Trolley Mounted of 22.5 KgCapacity for Switch Yard and 3 Nos. fire buckets of 25 ltr capacity filled with sandand mounted on 50x50x6 MS stand duly painted as per Technical Specification,approved Drawing & Scope of works.

SET 1

B Erection, testing and Commissioning of New 33 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 4

Page 27 of 30

Page 531: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

2.00

Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scopeof work, approved drawings and specifications for 12 M long steel Tubular poleswith welded steel base plate of Designation 540 SP 60 (IS 2713, Pt I, II, III1980) and erection of following types of poles for 33 KV overhead line byproviding and installing danger plate, anti-climbing devices (barbed wire),earthing material (coil and 8SWG GI wire), red oxide & aluminium paint, polenumbering including cement concrete foundation using cement concretingfoundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips(1:3:6) etc as per scope of work, approved drawings and specifications:

No 24

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 56

Page 28 of 30

3.00

Excavation of pole pit (of depth 1/6th of pole length) in soft rock where blastingis not required as per scope of work, approved drawings and specifications for 12M long steel Tubular poles with welded steel base plate of Designation 540 SP 60(IS 2713, Pt I, II, III 1980) and Erection of following types of poles for 33 KVoverhead line by providing and installing danger plate, anti-climbing devices(barbed wire), earthing material (coil and 8SWG GI wire), red oxide & aluminiumpaint, pole numbering including cement concrete foundation using cementconcreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stoneaggregate chips (1:3:6) etc as per scope of work, approved drawings andspecifications:

No 56

4.00

Erection, testing & commissioning of pre-fabricated steel items like V cross arm,top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate,guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats ofgiven sizes for over head structures and MS nuts, bolts & washers includingpainting by red oxide & aluminium paint as per technical specification, approveddrawings and scope of work.

MT 3.23

5.00

Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay

wire, by providing Guy stay insulator (2 Nos.) and 0.3 cmt concreting 1 part

cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per

technical specifications, approved drawings and scope of works.

Set 320

6.00Erection, testing and commissioning of 33 kV polymer Pin insulator includingtheir GI hardware fittings as per technical specification, approved drawings andscope of work.

Set 384

7.00Erection, testing and commissioning of 33 kV polymer Disc insulator with strainhardware fittings as per technical specification, approved drawings and scope ofwork.

Set 192

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAAC Wolf Conductor of following sizesincluding jointing sleeves, helical formed fittings, jumpering and by providing &erecting PG Clamps etc as required as per approved drawings, scope of work andtechnical specifications :::19/3.40 (Al. alloy Area 173 sqmm ) - Wolf

Ckt. km 4

Page 28 of 30

Page 532: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Excavation, erection, testing & commissioning of 100 mm dia.,1800 mm long CIpipe earth electrode and 6 SWG Gi wire with test link, RCC pit, RCC cover plateson GI frame, bentonite powder and other accessories complete for earthing byproviding GI nut, bolts & washers, turn buckle etc

Set 80

10.00

Erection of guading for line Crossing-Line to line, line to road with items, GIAngle Cross Arm (65x65x6x3500 mm) for guarding, GI Wire 8 SWG for guarding,GI Wire 6 SWG for guard earthing, GI 'I' Hook, CI earth Pipe 100 mm dia, 1800mm long with nuts & bolts.

Set 4

C Erection, testing and Commissioning of New 11 KV lines:

1.00 Survey, route alignment & pole spotting, preparation of survey report anduploading in the web portal after approval of Project Manager

Km 10

2.00

Excavation and erection of support for 11 KV overhead line by providing andinstalling danger plate, anti-climbing devices (barbed wire) and pole numbering,earthing, painting with red oxide and aluminum paint and making cementconcrete foundation and mufflering as per scope of work, approved drawingsspecifiactions. 8.5 meter long MS Steel Tubular poles with welded steel baseplate of SP-22 (141 Kg.) as per IS

No. 200

3.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 4.54

Page 29 of 30

2.00

Excavation and erection of support for 11 KV overhead line by providing andinstalling danger plate, anti-climbing devices (barbed wire) and pole numbering,earthing, painting with red oxide and aluminum paint and making cementconcrete foundation and mufflering as per scope of work, approved drawingsspecifiactions. 8.5 meter long MS Steel Tubular poles with welded steel baseplate of SP-22 (141 Kg.) as per IS

No. 200

3.00Erection of galvanised pre-fabricated steel materials like T Cross arm, channel

cross arm, angle, flats and all other GI materials for over head structures.MT 4.54

4.00 Erection, testing and commissioning of CI Earth Pipe connected with 6 SWG GIwire for earthing,

Set 40

5.00

Excavation and erection of galvanised Stay set with 50x8 mm Stay clamp, HTstay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diametersolid GS stay rod & 7/10 swg GI stranded wire etc as required by providingboulder packing as per scope of the work, technical specifications and approveddrawings.

Set 100

6.00Erection, testing and commissioning of 11 kV Polymaric Pin insulator includingtheir hardware fittings as per technical specification, approved drawings andscope of work.

Set 480

7.00Erection, testing and commissioning of 11 kV Polymaric Disc insulator including

their hardware fittings as per technical specification, approved drawings andscope of work.

Set 240

8.00

Laying out, tensioning, binding of conductor and tightening of stays andstringing, testing and commissioning of AAA Raccon Conductor includingjointing sleeves, helical formed fittings, jumpering and by fitting PG Clamps etcas required as per approved drawings, scope of work and technicalspecifications. (7/3.81 mm, 79.80 Sqmm)

Ckt. Km 10

Page 29 of 30

Page 533: DOCUMENT NO.: II - APDCL · Every document, letter, progress report, ... c. 100% of all 33/11 kV sub stations ... insulation resistance of 66/33/22/11 KV line & Distribution

Sl. No. Description Unit QtyUnit Erection

ChargesTotal Erection

ChargesService Tax

Assam ValueAdded Tax

REMARKS(Rate of Tax

Percentages to bementioned here)

Assam VAT @

9.00

Excavation, Erection, testing and commissioning of Protective guarding as perREC construction standard drawing No A-1 to be provided at locations where11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/ P&T lines etc.Supplying 2 Nos guarding angle cross arm (50x50x6x2500)mm, 2 Nos Y- guywith 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 Nos earthing of100mm dia CI earth pipe 1800 mm long, 6 SWG GI wires for earthingconnection, 6 SWG wire for guard wire, 8 SWG wire for cross lacing as per scopeof work, approved drawings and technical specifications.

Set 10

Total

Page 30 of 30Page 30 of 30