Low-Voltage Circuit BreakersSelection Guide
CATALOGUE No. ’05-G90E
1
Terasaki developed its original breaker for the first time in Japan in 1947.
Since then, the company has been offering, as a specialized breaker
manufacturer, the most advanced breakers not only to the Japanese market, but
also to the world markets.
The TemBreak series of Moulded case circuit breakers, which is evaluated as
highly reliable by our customers, has been improved from time to time for better
performance through Terasaki's advanced technologies.
In 2000, the TemPower 2 series was released to replace the Tempower series of
air circuit breakers, which had received high reputations for many years. This
new series consists of small, high-performance air circuit breakers featuring
advanced information and communication capabilities.
Terasaki is ready to meet the customers' requirements in the 21st century through
its diversified model lineup and its broad range of enhanced products.
circuit breakers. Our mature product line supports the wide ranging needs of our customers.
Contents
In September 1993, Terasaki ob-tained certification for the world quali-ty assurance standard ISO9002. In 1994, we obtained certification forthe even more rigorous ISO9001which covers additional items such as“Management Responsibil i t ies”,“Employee Training”, “Design andDevelopment”, and “Service”. In the future, we will respond to theeven higher level of global needs with“international reliability”.
In April 2000, Terasaki was certifiedas conforming to ISO 14001, an inter-national environment-related stan-dard. The company gives priority toits commitment to the curtailment orabolishment of using environmentallyharmful substances, energy saving inthe production activities, reduction ofwastes, and effective utilization of re-sources.
ISO9001 certificate
ISO14001 certificate
World Class Air Circuit Breaker
Energy saving support
Power Monitoring Equipment
Company profile———————————————————— 2
1. TemPower —————————————————————— 6
¡Air Circuit Breakers AR ———————————————— 6
¡Air Circuit Breakers AT•AH ——————————————— 8
¡Air Circuit Breakers AME ———————————————— 9
2. TemBreak ——————————————————————10
z Moulded Case Circuit Breakers —————————————10
¡Economical XE Series ————————————————10
¡Standard XS Series —————————————————12
¡High-fault Level XH Series ——————————————15
¡Motor Protection XM Series ——————————————16
¡D.C. Application Series ————————————————17
¡Current-Limiting Breakers, TL Series ——————————18
¡TO/TT Series ————————————————————20
¡Mining Series ————————————————————21
¡Non-automatic Trip Breakers —————————————22
¡Thyrister Protection Breakers —————————————24
¡TB Series for Distribution Board use ——————————25
¡Adjustable Thermal Trip ————————————————26
¡Marine Approval ———————————————————28
x Earth-leakage Relays ——————————————————30
¡TZS Series —————————————————————30
3. TemMeasure ————————————————————31
4. TemPlug ——————————————————————32
5. TemDin ———————————————————————33
6. Other Electrical Distribution Equipment ——————34
¡Special Circuit Breakers ————————————————34
2
TTTTEEEERRRRAAAASSSSAAAAKKKKIIIIPPPPrrrrooooffffiiii lllleeee
Sales departmentfor marine
Technical departmentfor marine
Sales departmentfor industrial
Technical departmentfor Industrial
Imari factoryYao factory Yabakei factory
Sales department
Technical department
Kami factory
Quality assurancedepartment
Business administrationdivision
Accounting & financedepartment
General affairsdepartment
President
Board of directors
Section of inspector
Board of auditors
Industrial systemsMarine systems
Circuit breakers
Quality assurancedepartment
Short-circuittesting station
Division administrationdepartment
Division administrationdepartment
Customers
■Established: October 1,1923
■President: Masakazu Fujita
■Capital: 641 million yen
■Number of employees: 813
■Sales: (Mar. 2004) 19,353 million yen
■Line of business
• Marine Systems Division:
Power distribution systems, Engine monitoring & control
systems, General instrumentation
• Industrial Systems Division:
Power distribution system, Co-generation system,
Independent generation plant (distributed power supply),
System engineering, Electronic equipment and systems for
factory automation, Monitoring & control system
Medical tools and equipment
• Circuit Breaker Division:
Moulded case circuit breakers, Air circuit breakers.
Minuature circuit breakers, Power monitoring equipments
Circuit Breaker Division
Industrial Systems Division
Marine SystemsDivision
3
TERASAKI ELECTRIC CO., LTD.Osaka, JAPANHeadquarter
Overseas Affiliates
q
o
w
r
t
e
yu
i
TERASAKI (EUROPE) LTD.Glasgow, SCOTLAND U. K.
TERASAKI ITALIA s.r.l.Milano, ITALY
TERASAKI ESPAÑA, S.A.U.Barcelona, SPAIN
TERASAKI SKANDINAVISKA ABSKOGÅS SWEDEN
TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.SINGAPORE
TERASAKI ELECTRIC (M) SDN. BHD.Shah Alam, MALAYSIA
TERASAKI DO BRASIL LTDA.Rio de Janeiro, BRAZIL
TERASAKI ELECTRIC (CHINA) LIMITEDZengcheng, CHINA
TERASAKI ELECTRIC CO., (FAR EAST) PTE. LTD.SINGAPORE
q
w
e
r
t
y
u
i
o
TERASAKI Global NetworkTERASAKI Global Network
●1 TERASAKISKANDINAVISKA AB(SWEDEN)
●2 TERASAKI (EUROPE) LTD.(U.K.)
●3 TERASAKI ESPAÑA, S.A.U.(SPAIN)
●4 TERASAKI ITALIA s.r.l.(ITALY)
■TERASAKI ELECTRIC CO., LTD.(JAPAN)
●5 TERASAKI ELECTRIC(M) SDN. BHD. (MALAYSIA)
●6 TERASAKI CIRCUITBREAKERS (S) PTE. LTD.(SINGAPORE)
●7 TERASAKI ELECTRIC CO.,(FAR EAST) PTE. LTD.(SINGAPORE)
●8 TERASAKI ELECTRIC(CHINA) LTD.(CHINA)
●9 TERASAKI DO BRASIL LTDA.(BRAZIL)
• Short-circuit Testing Station
q Short-circuit test generator No.1w Short-circuit test generator No.2e Voltage change devicer Back-up breakert Making switchy Reactors, Resistanceu Step-down 3ø transformeri 800V d.c. short-circuit testing
equipmento Pit!0 Impulse generator!1 Control room!2 Computerized control equipment
q
w
e
r
t
y
u
i
o
!0
!2
!1
4
Certifications, Authorizations or Approvals by World's Leading Organizations
Air Circuit BreakersASTA/U.K.ASTA CERTIFICATION SERVICES
SECV/AustraliaState Electricity Commission of Victoria
LR/U.K.Lloyd’s Register of Shipping
BV/FranceBureau Veritas
GL/GermanyGermanischer Lloyd
AB/U.S.A.American Bureau of Shipping
NK/JapanNippon Kaiji Kyokai
Moulded Case Circuit BreakersASTA/U.K.ASTA CERTIFICATION SERVICES
SECV/AustraliaState Electricity Commission of Victoria
LR/U.K.Lloyd’s Register of Shipping
BV/FranceBureau Veritas
GL/GermanyGermanischer Lloyd
AB/U.S.A.American Bureau of Shipping
NK/JapanNippon Kaiji Kyokai
Based Standards
Air Circuit BreakersIEC 60947-2International Electrotechnical Commission
BS EN 60947 Part 2/U.K.British Standard
VDE 0660 Part 101/GermanyVerband Deutscher Elektrotechnicker
NEMA PUB NO. SG3/U.S.A.National Electrical Manufacturers Association
ANSI C37. 13/U.S.A.American National Standard institute
JIS C8372/JapanJapanese Industrial Standard
JEC-160/JapanJapanese Electrical Committee
Moulded Case Circuit BreakersIEC 60947-2International Electrotechnical Commission
BS EN 60947 Part 2/U.K.British Standard
VDE 0660 Part 101/GermanyVerband Deutscher Elektrotechnicker
CEI EN 60947 Part 101/GeramanyItalian Standard
NEMA AB-1/U.S.A.National Electrigal Manufacturers Association
JIS C8370/JapanJapanese Industrial Standard
Short-circuit test generator No.1
Short-circuit test generator No.2
TYPE TESTS on every lot
öConstruction testöOperation testöTripping testöOverload testöOvershooting testöTemperature rise testöEndurance testöInsulation resistance testöWithstand voltage testöShort-circuit testöFlexible cord protection testöShort-circuit making capacity testöShort-time withstand current test
RELIABILITY TESTS
öVibration testöMechanical operation testöRust proof testöMechanical impact testöHeat-shock testöGas proof testöAging test
Combined Short-circuit Capacity(MVA) When TwoShort-circuitTest Generators (No.1 and No.2)are Paralleled.
Time after short-circuit (Cycle)
Sym. 3ø R.M.S.
0 10601/2 9501 8603 710
TERASAKI is always pleasedto send you the world’s top-class products.Already for many decades TERASAKI has beeninternationally minded. This is proved by the num-ber of certifications, authorizations and approvalsby the world’s leading organizations and authori-ties.TERASAKI maintains the top position.TERASAKI will exert its further efforts to attainmore international quality recognition.
TemBreakMoulded Case �
Circuit Breakers
(AME series for �Generator Protection)
Power Monitoring �Equipment
Direct bus plug-in �mounting base
Air Circuit Breakers
Earth-leakage Relays
Air Circuit Breakers �with enhanced OCR
5
AAAAppppppppeeeeaaaarrrraaaannnncccceeee ooooffff mmmmaaaajjjjoooorrrr pppprrrroooodddduuuuccccttttssss
6
Air Circuit Breakers
AR Standard Series1AMPERE RATING(A)TYPERATED CURRENT (max) [In](A) IEC, EN, AS
q w JISNEMA, ANSIMarine
NEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLES e rRATED PRIMARY CURRENT OF OVER–CURRENTRELEASE [ICT](A)• for general feeder circuit use
RATED CURRENT OF OVER–CURRENT RELEASE(A)• for generator protection use[In] is generator rated current.
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) tRATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) yAC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]IEC,EN,AS AC 690V u[Ics = Icu] 440VNEMA AC 600VANSI 480V
240VJIS AC 550V
460V220V
o DC 600V !0
250VNK !2 AC 690V
450VLR, AB, !2 AC 690VGL, BV 450V
RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV)RATED SHORT TIME WITHSTAND 1sCURRENT[Icw][kA rms] 3sLATCHING CURRENT (kA)TOTAL BREAKING TIME (s)CLOSING OPERATION TIMESPRING CHARGING TIME (s) max.CLOSE TIME (s) max.No. of operating cycles Mechanical life with maintenance
without maintenance Electrical life without maintenance AC460V
AC690VWEIGHT (kg) draw-out typeOUTLINE DIMENSION (mm)FIXED TYPE a
bcd
DRAW-OUT aTYPE !3 b
cd
800AR208S8008008008008003 4200400800
100ÖInÖ200200ÉInÖ400400ÉInÖ800
1000690
50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i
126550650.03
100.08
3000015000120001000073 86
360 44546029075354 43946034540
1250AR212S125012501250125012503 44008001250
200ÖInÖ400400ÉInÖ800630ÉInÖ1250
1000690
50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i
126550650.03
100.08
3000015000120001000073 86
360 44546029075354 43946034540
1600AR216S160016001540160016003 440080012501600
200ÖInÖ400400ÉInÖ800630ÉInÖ1250800ÉInÖ1600
1000690
50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i
126550650.03
100.08
3000015000120001000076 90
360 44546029075354 43946034540
2000AR220S200020002000200020003 4400800125016002000200ÖInÖ400400ÉInÖ800630ÉInÖ1250800ÉInÖ16001000ÉInÖ20001000690
50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i
126550650.03
100.08
250001200010000700079 94
360 44546029075354 43946034540
2500AR325S250025002500250025003 42500
1250ÖInÖ2500
1000690
65/14385/187 i50/11565/149.585/195.565/14385/195.585/195.540/4040/4065/15385/201 i65/15385/201 i
128565850.03
100.08
200001000070005000105 125
466 58646029075460 58046034540
3200AR332S320032003200320032003 43200
1600ÖInÖ3200
1000690
65/14385/187 i50/11565/149.585/195.565/14385/195.585/195.540/4040/4065/15385/201 i65/15385/201 i
128565850.03
100.08
200001000070005000105 125
466 58646029075460 58046034540
q : Values in open air at 40°C (45°C for marine applications).w : Values of AR208S ~ 216S for draw-out type with horizontal terminals,
Values of AR220S ~ 440S for draw-out type with vertical terminals.e : For 2poles use both opposite ends poles of 3poles ACBs.r : 4poles ACBs without Neutral phase protection can not be applied to
IT earthing systems.t : Rated insulation voltage depends on applied standard: 1000V AC
according to IEC 60947-2.
4000AR440S400037003700400040003 44000
2000ÖInÖ4000
1000690
75/165100/22065/149.575/172.5100/23075/165100/230100/23040/4040/4075/179100/24575/179100/245
12100851000.03
100.08
15000800050002500139 176
— ————631 80146037553
y : Rated operational voltage depends on applied standard: 690Vaccording to IEC 60947-2.
u : Cannot apply IT earthing system, ie, insulated from earth.i : For 500V AC.o : Please contact TERASAKI for DC application.!0 : 3poles in series should be applied for 600V DC.!2 : Applicable to only 3poles ACBs.!3 : For vertical terminals or horizontal terminals.
a c d
b
a c d
b
7
Air Circuit Breakers
AR High Fault Series1AMPERE RATING(A)TYPERATED CURRENT (max) [In](A) IEC, EN, AS
q w JISNEMA, ANSIMarine
NEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLES e rRATED PRIMARY CURRENT OF OVER–CURRENTRELEASE [ICT](A)• for general feeder circuit use
RATED CURRENT OF OVER–CURRENT RELEASE(A)• for generator protection use[In] is generator rated current.
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) tRATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) yAC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]¶IEC,EN,AS AC 690V u[Ics = Icu] 440VNEMA AC 600VANSI 480V
240VJIS AC 550V
460V220V
o DC 600V !0
250VNK !2 AC 690V
450VLR, AB, !2 AC 690VGL, BV 450V
RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV)RATED SHORT TIME WITHSTAND 1sCURRENT[Icw][kA rms] 3sLATCHING CURRENT (kA)TOTAL BREAKING TIME (s)CLOSING OPERATION TIMESPRING CHARGING TIME (s) max.CLOSE TIME (s) max.No. of operating cycles Mechanical life with maintenance
without maintenance Electrical life without maintenance AC460V
AC690VWEIGHT (kg) draw-out typeOUTLINE DIMENSION (mm)DRAW-OUT aTYPE !3 b
cd
1250AR212H125012501250125012503 42004008001250
100ÖInÖ200200ÉInÖ400400ÉInÖ800630ÉInÖ1250
1000690
55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186
128055650.03
100.08
3000015000120001000079 94
354 43946034540
1600AR216H160016001600160016003 41600
800ÖInÖ1600
1000690
55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186
128055650.03
100.08
3000015000120001000079 94
354 43946034540
2000AR220H200020002000200020003 42000
1000ÖInÖ2000
1000690
55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186
128055650.03
100.08
3000015000120001000079 94
354 43946034540
1600AR316H160016001600160016003 420040080012501600100ÖInÖ200200ÉInÖ400400ÉInÖ800630ÉInÖ1250800ÉInÖ16001000690
85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233
1210075850.03
100.08
2500012000100007000105 125
460 58046034540
2000AR320H200020002000200020003 42000
1000ÖInÖ2000
1000690
85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233
1210075850.03
100.08
200001000070005000105 125
460 58046034540
2500AR325H250025002500250025003 42500
1250ÖInÖ2500
1000690
85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233
1210075850.03
100.08
200001000070005000105 125
460 58046034540
3200AR332H320032003200320032003 43200
1600ÖInÖ3200
1000690
85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233
1210075850.03
100.08
200001000070005000105 125
460 58046034540a c d
b
q : Values in open air at 40°C (45°C for marine applications).w : Values for draw-out type with vertical terminals.e : For 2poles use both opposite ends poles of 3poles ACBs.r : 4poles ACBs without Neutral phase protection can not be applied to
IT earthing systems.t : Rated insulation voltage depends on applied standard: 1000V AC
according to IEC 60947-2.
y : Rated operational voltage depends on applied standard: 690Vaccording to IEC 60947-2.
u : Contact TERASAKI for details.o : Please contact TERASAKI for DC application.!0 : 3poles in series should be applied for 600V DC.!2 : Applicable to only 3poles ACBs.!3 : For vertical terminals.
¶ : When the ACB is used without Instantaneous trip function MCR should be set to work. The rated breaking capacity will reduce to the level of the latching currentwithout MCR function.
8
Air Circuit Breakers
AT•AH Series1Frame Size (A)Type° RATED CURRENT [In] (A) IEC, BS, VDE, AS (Max.) q JIS
JEC !0NEMA, ANSIMarine
Neutral Pole Amperes Frame (A) wNumber of Poles e° RATED PRIMARY CURRENT OF
OVER-CURRENT TRIP DEVICES [ICT] (A)• for general feeder circuit use° RATED CURRENT OF
OVER-CURRENT TRIP DEVICES [Io] (A)• for generator protection use ([Io] is generator rated current)AC Rated insulation voltage [Ui] (V) rRated operational voltage [Ue] (V) t° AC RATED BREAKING CAP.(kA sym.)/MAKING CAP.(kA peak)
with INST AC 690V !1[Ics]=100%[Icu] 600V !1
500VUp to 415V
with MCR AC 690V !1600V !1
Up to 500Vwithout INST AC 690V !1
Up to 500Vwith INST AC 600V
480V240V
with MCR AC 600VUp to 480V
without INST Up to AC 600Vwith INST AC 550V
460V220V
with MCR AC 550VUp to 460V
without INST Up to AC 550Vwith INST only DC 250V uwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500V
Rated impulse withstand voltage [Uimp] (kV)Utilization CategoryRated short time withstand current 1Srms [Icw] (kA) 3SLatching current rms (kA)Total breaking time (s)Closing operation timeSpring charging time (s) max.Close time (s) max.Weight (kg) draw-out type (Motor Charging)° OUTLINE DIMENSION (mm)Fixed aType b
cd
Draw-out aType b
cd
NOTE) — : “no”or “not available”.
q Values in open air at 40°C (45°C for marine applications). w Neutral current rating is equal to the max. applicable current rating, which varies depending on applicable standards. e 2-pole type is identical
to 3-pole type except the centre pole is omitted. 4-poles type can not be applied to Marine approval. r 1000V.AC. according to IEC60947-2. t 690V.AC. according to IEC60947-2. y 1700A for JEC
standard. u DC rating is of special application. i Full rated neutral pole available on request. o Values at 480V AC. !0 Ratings are the actual performance not the recommended values of the standard.
!1 Cannot apply IT earthing system, ie, insulated from earth. !2 86.1/203kA at 660V.AC. !3 87.6/203kA at 660V.AC.
IECBS
VDEAS[Ics]
NEMA
JIS
ANSI
JEC
NK
AB
LR
BV
GL
a c d
b
50
a c d
b
50
2000AT20L200020001700—20002000 y3 4320 1600630 20001250—
690480
———130/286————————————130/325130/325————130/322 o——130/322 o——130/322 o——130/322 o—————8A1717170.02
100.0691 115
— ————368 45349245892
2500AT25L250025002300—25002000 i3 42500
—
690480
———130/286————————————130/325130/325————130/322 o——————————————8A1717170.02
100.06152 188
— ————518 65352645882
4000AH-40C4000400036504000400032002,3 44000
1600ÖIoÖ4000
1000690
85/18785/187120/264120/26485/18785/187100/22060/13260/132100/230120/276120/276100/230100/23060/138100/230120/300120/300100/230100/23060/13240/40120/286100/23160/138120/286100/23160/138124/280 !2108/23962.8/144120/286100/231—120/286100/220—8B10070600.03
100.04240 280
————622 782655566106
5000AH-50C5000500046505000500050002,3 45000
2000ÖIoÖ5000
1000690
85/18785/187120/264120/26485/18785/187100/22070/15470/154100/230120/276120/276100/230100/23070/161100/230120/300120/300100/230100/23070/15440/40120/286100/23170/153120/286100/23170/153124/280108/23976.3/170120/286100/231—120/264100/220—8B10070700.03
100.04350 450
————747 937685589146
6300AH-60C6300615053006150600063002,3 46300
2500ÖIoÖ6300
1000690
85/18785/187120/264120/26485/18785/187120/26470/15470/154100/230120/276120/276100/230120/27670/161100/230120/300120/300100/230100/30070/15440/40120/286120/28670/153120/286120/28670/153124/280 !3124/28077.37/166120/280100/239—120/264——8B12070700.03
100.04380 480
————747 937685589146
9
Air Circuit Breakers
AME Series for Generator protection1
NOTES: ¡ : Available. — : Not available.q : With long time-delay trip and short time-delay trip.w : Cannot use UVT and SHT jointly.e : Equipped as standard.r : Used for testing instantaneous trip function (separate mounting).
NK standard requires at least one checker per vessel.t : Used for testing tripping characteristics with secondary current.
Frame Size [A]TypeNumber of polesRated current of overcurrent trip device [A](ln is generator rated current)
Rated insulation voltage (Ui) [VAC]Rated frequency [Hz]° AC RATED BREAKING CAPACITY [kA sym. rms.] /RATED MAKING CAPACITY [kA peak]LR, AB, GL, with INST 460VBV, NK without INST q 460VRated short-time current (lcw) [kA, rms.]° OPERATIONDirect manualExternal manual (option)Motorized (option)° DIMENSIONS (mm)rear-connected (RC)/plug-in (PM)
abcd
° CONNECTIONS AND MOUNTINGSRear connected Flat bar stud RCPlug-in For switchboard PMweight Direct manual operation/(Rear connected)(kg) Direct manual operation/(Plug-in)° ACCESSORIES (option)Undervoltage trip w UTVShunt trip w SHTAuxiliary switch AXAlarm switch ALHandle extension (For direct manual) EHATerminal cover for rear connected • plug-in TCROCR checker rOCR adapter t° PROTECTIVE FUNCTIONSElectronic type LTD • STD • INST
STD • INST° ENDURANCE
Number of operations with currentNumber of operations without current
c d
b
a
Type AME 4B( Direct manual operation ) Type AME 4B( Motorized operation )
250AME3B316 ÖI
nÖ31.5
31.5 ÉInÖ63
63 ÉInÖ125
125 ÉInÖ250
60050/60
16/34.84/6.874 (150ms)
¡¡¡
182/161260/282121/121255/245
¡¡6.58.2
¡¡¡ e¡—¡¡¡
¡¡
20008000
400AME4B3200ÖI
nÖ400
60050/60
16/34.86/10.26 (150ms)
¡¡¡
182/161260/282121/121255/245
¡¡6.58.2
¡¡¡ e¡—¡¡¡
¡¡
10009000
630AME6B3315ÖI
nÖ630
60050/60
20/42.610/17.410 (150ms)
¡¡¡
252/231273/303121/121267/270
¡¡1016.1
¡¡¡ e¡¡ e¡¡¡
¡¡
5004500
800AME8B3500ÖI
nÖ800
60050/60
30/63.815/33.015 (150ms)
¡¡¡
252/231370/370120/138282/336
¡¡19.530.1
¡¡¡ e¡¡ e—¡¡
¡¡
5004500
1000AME10B3800ÖI
nÖ1000
60050/60
30/63.815/33.015 (150ms)
¡¡¡
252/231370/370120/138282/336
¡¡19.530.1
¡¡¡ e¡¡ e—¡¡
¡¡
5004500
10
TemBreakz Moulded Case Circuit Breakers
Economical XE Series2Frame Size [A]TypeNumber of PolesOutside view
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
3 155 2010 30(40°C only)—220
——2.5—————2.5/1.3(220V)———————A
45.5 689652670.27 0.4
' e——õ————
———
¡ y—
——
— ¡ (AXE)——————————¡¡¡—————
30XE30NS2 3
3 15 405 20 5010 30
6660
1.52.55—1.5/0.8 @52.5/1.3 @52.5/1.32.5/1.35/2.5——5—2.55—A
50 7513068870.48 0.74
' e—õõ—— õ— õ—
———
¡ u—
¡¡
¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡
50XE50NB2 3
15 40 7520 50 10030 60(40°C only)6660
257.5—2/1 @55/2.5 @55/2.55/2.57.5/3.8——7.5—510—A
50 7513068870.48 0.74
' r—õõ————
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡
100XE100CB2 3
10 30 6015 40 7520 50 100
6660
7.51025—7.5/3.8 @510/5 @510/515/7.525/13——25—7.515—A
50 7513068870.48 0.74
' r—õõ—õõ—
———
¡ u—
¡¡
¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡
100XE100NS2 3
15 40 7520 50 10030 60
8690
101425—10/5 @514/714/718/925/13——25—1015—A
60 9015568860.78 1.1
'—õõ—õõ—
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡
100XE100HB2 3
125 200150 225175
8690
57.515—5/2.5 @57.5/3.87.5/3.87.5/3.815/7.5—7.515—1010—A
10516060831.4
'õ (BAR)õ—————
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡————————¡¡¡—¡ !2—¡¡
225XE225CS3
125 200150 225175
8690
101525—10/5 @515/7.515/7.518/925/13—1525—1015—A
10516060831.4
'õ (BAR)õ—õ———
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡—¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡
225XE225NC3
250 400300350
8690
152535—15/7.5 @518/925/1325/1335/18—1835—2020—A
1402601031314.7
'õ (BAR)õ—õ———
———
—¡
¡¡
¡ (AX)¡ (AX)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡
400XE400NS3
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.e : Comes with conductor pressing terminal.r : Comes with conductor pressing terminal for below 50A rating.
y : Hydraulic-magnetic type for below 5A rating.u : Hydraulic-magnetic type for below 10A rating.o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
11
TemBreakz Moulded Case Circuit Breakers
Economical XE Series2Frame Size [A]TypeNumber of PolesOutside view
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
600XE600NS3
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.
o : The UVT controller is installed externally, when provided with AC UVT.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
500600
8690
182535—18/9 @520/1025/1325/1335/18—2035—2020—A
2102731031459.0
—'õ—õ———
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
12
TemBreakz Moulded Case Circuit Breakers
Standard XS Series2Frame Size [A]TypeNumber of PolesOutside view
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.e : Comes with conductor pressing terminal.
u : Hydraulic-magnetic type for below 10A rating.o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
3 155 2010 30
6660
1.52.55—1.5/0.8 @52.5/1.3 @52.5/1.32.5/1.35/2.5——5—2.55—A
50 7513068870.48 0.74
' e—õõ—— õ— õ—
———
¡ u—
¡¡
¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡
30XS30NB2 3
10 3015 4020 50
6660
57.510—5/2.5 @57.5/3.8 @57.5/3.810/510/5——10—7.515—A
50 7513068870.48 0.74
' e—õõ—õõ—
———
¡ u—
¡¡
¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡
50XS50CB2 3
10 3015 4020 50
6660
7.51025—7.5/3.8 @510/5 @510/515/7.525/13——25—7.515—A
50 7513068870.48 0.74
' e—õõ—õõ—
———
¡ u—
¡¡
¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡
50XS50NB2 3
60
6660
7.51025—7.5/3.8 @510/5 @510/515/7.525/13——25—7.515—A
50 7513068870.48 0.74
'—õõ—õõ—
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡
15 40 7520 50 10030 60
8690
1525505/2.5 @512/6 @525/1325/1330/1550/25——50—1520—A
60 90 12015568860.78 1.1 1.4
'—õõ—õõ ——
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡ !2—¡¡
100XS100NB2 3 4
125 200150 225175
8690
2225508/4 @522/11 @525/1325/1335/1850/25222550—4040—A
105 140165861071.85 2.4
'õ (BAR)õ—õõ——
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡——¡¡
225XS225NS3 4
60XS60NS2 3
FOR JAPANESE MARKET
13
TemBreakz Moulded Case Circuit Breakers
Standard XS Series2600XS600NE3 4
800XS800NS3 4
800XS800CS3 4
600XS600NS3 4
600XS600CS3 4
400XS400NS3 4
400XS400NE3 4
700800
8690
35508520/10 @535/18 @550/2550/2565/3385/43305085—4040—A
210 2802731031459.4 12.2
—'õ—õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
700800
8690
25355016/8 @525/13 @530/1535/1845/2350/25253550—4040—A
210 2802731031459.4 12.2
—'õ—õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
Adjustable300 500350 6004008690
35508520/10 @535/18 @550/2550/2550/2585/4330508510——10 (0.3sec)B
210 2802731031459.6 12.0
—'õ—õõ—õ !3
¡¡—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
300 6004005008690
35508520/10 @535/18 @550/2550/2565/3385/43305085—4040—A
210 2802731031459.0 11.5
—'õ—õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
300 6004005008690
25355016/8 @525/13 @530/1535/1845/2350/25253550—4040—A
210 2802731031459.0 11.5
—'õ—õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
Adjustable125 200 200 300150 225 225 350175 250 4008690
35508518/9 @530/15 @542/2150/2550/2585/433042855——5 (0.3sec)B
140 1852601031314.8 6.2
'õ (BAR)õ—õõ—õ !3
¡¡(PTA only)—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡
125 200 300150 225 350175 250 4008690
35508518/9 @530/15 @542/2150/2550/2585/43304285—4040—A
140 1852601031314.7 6.1
'õ (BAR)õ—õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡
125 200 300150 225 350175 250 4008690
22305016/8 @522/11 @530/1535/1835/1850/25223050—4040—A
140 1852601031314.7 6.1
'õ (BAR)õ—õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡
400XS400CS3 4
Frame Size [A]TypeNumber of PolesOutside view
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.
o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!3 : Special specification.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
……
……
14
TemBreakz Moulded Case Circuit Breakers
Standard XS Series2Frame Size [A]TypeNumber of PolesOutside view* 2 pole breaker is a 3 pole breaker with the center pole omitted.
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.
o : The UVT controller is installed externally, when provided with AC UVT.!0 : One is supplied with every five breakers. Please specify if more are required.!3 : Special specification.!4 : Handle is supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Magnetic trip only. Contact Terasaki for details.@5 : The application on IT systems on this voltage is not available.
2500XS2500NE3 4
2000XS2000NE3 4
1600XS1600NE3 4
1000XS1000NE3 4
1200XS1200NE3 4
Adjustable1200 20001400 250016008690
658513045/42 @565/49 @585/6485/64100/75125/94658512542——42 (0.3sec)B
320 42945018524562.5 78.2
————'———
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡——¡ !4¡¡¡¡———¡—¡
Adjustable1000 16001200 18001400 20008690
658513045/42 @565/49 @585/6485/64100/75125/94658512542——42 (0.3sec)B
320 42945018524554.0 67.0
—õ——'——õ
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡——¡ !4¡¡¡¡———¡—¡
Adjustable800 1200900 14001000 16008690
658513045/34 @565/49 @585/6485/64100/75125/94658512520——20 (0.3sec)B
210 28037014019127.0 35.0
—õ——'——õ
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
Adjustable600 1000700 12008008690
506510025/19 @545/34 @565/4965/4985/64100/7542658515——15 (0.3sec)B
210 28037012017122.0 28.0
—'——õõ—õ !3
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡¡—¡¡—¡
Adjustable500 800600 900700 10008690
506510025/19 @545/34 @565/4965/4985/64100/7542658515——15 (0.3sec)B
210 28037012017122.0 28.0
—'——õõ—õ !3
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡¡—¡¡—¡
800XS800NE3 4
Adjustable400 600450 700500 8008690
35508520/10 @535/18 @550/2550/2550/2585/4330508510——10 (0.3sec)B
210 2802731031459.7 12.5
—'õ—õõ—õ !3
¡¡—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
15
TemBreakz Moulded Case Circuit Breakers
High-fault Level XH Series2
15 4020 50308690
3550858/4 @525/13 @542/2150/2550/2585/43——85—4040—A
90 120155861041.3 1.58
'—õõ—õõ ——
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡
400XH400NE3 4
800XH800PS3 4
800XH800NE3 4
600XH600NE3 4
225XH225NE3 4
225XH225NS3 4
50XH50NS3 4
100XH100NS3 4
700800
8690
658513045/23 @565/33 @585/4385/43100/50125/636585125—4040—A
210 2802731031459.4 12.2
—'——õõ—õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
Adjustable400 600450 700500 8008690
506510020/10 @542/21 @565/3365/3365/33100/5042658510——10 (0.3sec)B
210 2802731031459.7 12.5
—'õ—õõ—õ !3
¡¡—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
Adjustable300 500350 6004008690
506510020/10 @542/21 @565/3365/3365/33100/5042658510——10 (0.3sec)B
210 2802731031459.6 12.0
—'õ—õõ—õ !3
¡¡—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
Adjustable125 200 200 300150 225 225 350175 250 4008690
506510020/10 @542/21 @565/3365/3365/33100/504265855——5 (0.3sec)B
140 1852601031314.8 6.2
'õ (BAR)õ—õõ—õ !3
¡¡(PTA only)—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡
Adjustable125 200150 2251758690
35508518/9 @530/15 @542/2150/2550/2585/433042855——5 (0.3sec)B
140 1852601031314.8 6.2
'õ (BAR)õ—õõ—õ !3
¡¡ (PTA only)—
——
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡
125 200150 2251758690
35508515/7.5 @525/13 @542/2150/2550/2585/43254285—4040—A
105 1401651031242.1 2.6
'õ (BAR)õ—õõ—õ !3
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡
15 40 7520 50 10030 608690
3550858/4 @525/13 @542/2150/2550/2585/43——85—4040—A
90 120155861041.3 1.58
'—õõ—õõ ——
———
¡—
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡
Frame Size [A]TypeNumber of PolesOutside view
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
NOTES: ' : Standard. This configuration is used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.
o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!3 : Special specification.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
……
……
FOR JAPANESE MARKET
FOR JAPANESE MARKET
16
TemBreakz Moulded Case Circuit Breakers
Motor Protection XM Series2
200- 400-220V 440V
[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 2515 32
6660
2.552.5/1.32.5/1.35/2.5—5A
7513068870.74
' e—õõ—õõ—
—¡ i
¡¡
¡ (AXE)¡ (ALE)¡——¡¡¡—¡—¡¡¡¡¡—¡¡
100- 200-110V 220V
[Kw] [A] [A]0.1 40.2 6.3 1.40.4 10 2.60.75 16 4.21.5 7.42.2 103.7 165.5 257.5 33
6220
—2.5——2.5/1.3-(220V)——A
45.5 689652670.27 0.4
' e——õ————
¡—
——
— ¡(AXE)——————————¡¡¡—————
° RATINGSVoltage for motor 50/60 Hz
Motor output and rated current at 40°C(45°C for marine applications)
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 460V
220VIEC 60947-2 Icu/Ics 415VBS EN 60947-2 380V
240VNEMA AB-1 480V
240VUtilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSHydraulic-magnetic tripsThermal and fixed magnetic trips° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
50XM50NB3
225XM225NS3
100XM100NB3
100XM100CS3
50XM50CB3
30XM30PB3
30XM30CS2 3
30XM30NB3
200- 400-220V 440V
[Kw] [A] [A]30 12537 15045 17555 22575 15090 175110 225
8690
255025/1335/1850/252550A
105165861071.85
'õ (BAR)õ—õ———
—¡
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡
200- 400-220V 440V
[Kw] [A] [A]3.7 165.5 257.5 32 1611 45 2515 60 3218.5 75 4022 90 4530 6037 7545 9055 100
8690
255025/1330/1550/25—50A
9015568861.1
'—õõ————
—¡
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡
200- 400-220V 440V
[Kw] [A] [A]15 6318.5 7522 9030 6337 7545 9055 100
6660
102510/515/7.525/13—25A
7513068870.74
'—õõ————
—¡
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡—¡¡
200- 400-220V 440V
[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 45 2515 3218.5 4022 456660
10 !62510!6/5!715!6/7.5!725/13—25A
7513068870.74
' e—õõ————
—¡ i
¡¡
¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡—¡¡
200- 400-220V 440V
[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 45 2515 3218.5 4022 456660
2.552.5/1.32.5/1.35/2.5—5A
7513068870.74
' e—õõ—õõ—
—¡ i
¡¡
¡ (AXE)¡ (ALE)¡——¡¡¡—¡—¡¡¡¡¡—¡¡
200- 400-220V 440V
[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 85.5 12
6660
8512585/8585/85125/125—125A
78147.5981171.78
' e—õõ—õ——
¡—
¡¡
¡ (AXE)¡ (ALE)¡——¡¡¡—¡—¡¡————¡¡
Frame Size [A]TypeNumber of PolesOutside view
d
b
ca
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.e : Comes with conductor pressing terminal.i : Hydraulic-magnetic type for below 25A rating.
o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!6 : 7.5kA for below 8A rating.!7 : 3.8kA for below 8A rating.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.
17
TemBreakz Moulded Case Circuit Breakers
D.C. Application Series2Frame Size [A]TypeNumber of PolesOutside view* 2 pole breaker is a 3 pole breaker with the center pole omitted.
° RATED CURRENT (In) [A]at 40°C
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VDC]° RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 AC 550V
460V220V
DC 250VIEC 60947-2 Icu/Ics AC 690VBS EN 60947-2 500V
440V415V380V240V
DC 250VNEMA AB-1 AC 600V
480V240V
Without Inst. AC 240-690VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
d
b
ca
2500XS2500ND*2 3
2000XS2000ND*2 3
1200XS1200ND*2 3
1600XS1600ND*2 3
2500 @4
8600
———40——————40/30—————A
32045018524555.7 62.5
————'———
———
—¡ @4
¡¡
¡ (AX)¡ (AL)¡—¡¡——¡ !4¡¡¡¡———¡—¡
2000 @4
8600
———40——————40/30—————A
32045018524550.0 54.0
—õ——'——õ
———
—¡ @4
¡¡
¡ (AX)¡ (AL)¡—¡¡——¡ !4¡¡¡¡———¡—¡
1600 @4
8600
———40——————40/30—————A
21037014019124.0 27.0
—õ——'——õ
———
—¡ @4
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
1200 @4
8600
———40——————40/30—————A
21037014019123.8 26.0
—'——õ———
———
—¡ @4
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
1000XS1000ND*2 3
1000
8600
———40——————40/20—————A
2102731031459.2 10.3
—'——õ———
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.
!0 : One is supplied with every five breakers. Please specify if more are required.!4 : Handle is supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Magnetic trip only.
18
600TL-600NE3 4
1200TL-1200NE3 4
1000TL-1000NE3 4
800TL-800NE3 4
400TL-400E3 4
225TL-225F3
100TL-100F3 4
BAdjustable600 1000700 1200800690
6512515045/34 @575/57 @5125/65125/65125/65150/113658512515——815 (0.3sec)
210 28037014019126.0 33.7
—'——õõ—õ !3
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
Frame Size [A]TypeNumber of PolesOutside view
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.o : The UVT controller is installed externally when provided with AC UVT.!0 : One is supplied with every five breakers. Please specify if more are required.
!3 : Special specification.!4 : Rated current shown in ( ) is for 4 poles only, and special specification.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
BAdjustable500 800600 900700 1000690
6512515045/34 @575/57 @5125/65125/65125/65150/113658512515——815 (0.3sec)
210 28037014019126.0 33.7
—'——õõ—õ !3
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
Utilization Category° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.]° DIMENSIONS (mm)
abcd/e
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
BAdjustable400 600450 700500 800690
6512515045/34 @575/57 @5125/70125/70125/70150/113658512515——815 (0.3sec)
210 28037014019125.8 33.5
—'——õõ—õ !3
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
BAdjustable300 500350 600400690
6512515045/34 @575/57 @5125/70125/70125/70150/113658512515——815 (0.3sec)
210 28037014019125.8 33.5
—'——õõ—õ !3
¡¡¡
——
¡¡
¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡
A250 400 (175)300 (125) (200)350 (150) (225)!4690
7512012045/23 @575/38 @5120/60120/60120/60120/6075120120—40408—
160 2122601331678.5 10
'õ (BAR)õ—õõ ——õ !3
———
—¡
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡——¡——¡ —¡ (TYD)—¡
A125 200150 225175
690
6012012025/13 @560/30 @5120/60120/60120/60120/606075120—40408—
1402601331676.0
'õ (BAR)õ—õõ——
———
¡—
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡——¡———¡ (TYD)—¡
A15 40 7520 50 10030 60
690
4212012025/13 @560/30 @5120/60120/60120/60120/604275120—40408—
105 1401651251433.2 3.8
'—õõ—õ ———
———
¡—
¡¡
¡ (AX)¡ (AL)¡¡¡¡¡¡—¡—¡¡———¡ (TYD)—¡
z Moulded Case Circuit Breakers
Current-limiting Breakers, TL Series (120kA)2
d e
b
ca
19
800TL-8003
600TL-6003
400TL-4003
100TL-100C3
225TL-225B3
Frame Size [A]TypeNumber of PolesOutside view
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.
!5 : Specify rated frequency, 50 or 60Hz.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.
Utilization Category° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.]° DIMENSIONS (mm)
abcd/e
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
A15 40 7520 50 10030 60
690
8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—
110230133162/—4.7
'—õõ—õ——
———
¡—
——
¡ (AX)¡ (AL)¡¡¡¡—¡—¡——¡———¡ (TYD)——
A700800 !4
!5690
8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—
240400133199/6327
—'õ—õõ——
———
—¡
——
¡ (AX)¡ (AL)¡¡¡¡—¡¡¡——¡———¡ (TYD)——
A450500600
690
8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—
240400133199/6327
—'õ—õõ——
———
—¡
——
¡ (AX)¡ (AL)¡¡¡¡—¡¡¡——¡———¡ (TYD)——
A125 200 300150 225 350175 250 400
690
8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—
210300133202/5617.7
'õ (BAR)õ—õõ——
———
—¡
——
¡ (AX)¡ (AL)¡¡¡¡—¡¡¡——¡———¡ (TYD)——
A125 200150 225175
690
8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—
140260133183/469.3
'õ (BAR)õ—õõ——
———
¡—
——
¡ (AX)¡ (AL)¡¡¡¡—¡—¡——¡———¡ (TYD)——
z Moulded Case Circuit Breakers
Current-limiting Breakers, TL Series (180kA)2
d e
b
ca
20
3200TT-32003
4000TO-40003
3200TO-32003
Frame Size [A]TypeNumber of PolesOutside view
NOTES: ' : Standard. This configuration is used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.
!3 : Special specificacion.!5 : Specify rated frequency, 50 or 60Hz.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.
A4000
!5690
658513045/3465/4985/6485/64100/75130/986585130—40408—
390560235315120
————'———
———
—¡
——
¡ (AX)¡ (AL)¡¡¡———¡———————¡(TYD)—¡
B250028003200
!5690
658513045/4265/4985/6485/64100/75130/98658513042——842 (0.3sec)
390560235315120
————'——õ
———
¡(with Adi. STD)—
——
¡ (AX)¡ (AL)¡¡¡———¡—¡ !6—————¡(TYD)—¡
A250028003200
!5690
658513045/3465/4985/6485/64100/75130/986585130—40408—
390560235315120
————'——õ
———
—¡
——
¡ (AX)¡ (AL)¡¡¡———¡—¡ !6—————¡(TYD)—¡
Utilization Category° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V
460V220V
IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.]° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips
° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.F
z Moulded Case Circuit Breakers
TO/TT Series2
d
b
ca
21
Frame Size [A]TypeNumber of PolesOutside viewNRC=Nominal Rated CurrentASR=Adjustable Setting Range
NOTES: ' : Standard. This configuration is used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.
o : For AC UVT, a UVT controller is mounted externally.!0 : One is supplied with every five breakers. Please Specify if more are required.!2 : Line side interpole barriers are supplied as standard.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Values at 1000V AC.
15 5020 6030 7540 1001100
6.510
1051651251433.2
'——õ—õ——
—¡
———
¡———
¡(AX)¡(AL)¡¡¡¡¡¡—¡—¡¡——¡ !2¡ (TYD)—¡—
NRC ASRmin. max.
250 125 250400 200 4001100
12.5—
1402601031314.8
'õ (BAR)——õõ——
¡¡
¡¡(PTA only)—
————
¡(AX)¡(AL)¡¡ o¡¡¡¡—¡¡¡¡¡¡¡¡—¡¡
NRC ASRmin. max.
630 315 630
1100
12.518 @4
2102731031459.6
—'——õõ——
¡¡
¡¡—
————
¡(AX)¡(AL)¡¡ o¡¡¡¡¡¡¡¡¡¡¡¡¡—¡¡
NRC ASRmin. max.
800 400 800
1100
12.518 @4
2102731031459.7
—'——õõ——
¡¡
¡¡—
————
¡(AX)¡(AL)¡¡ o¡¡¡¡¡¡¡¡¡¡¡¡¡—¡¡
NRC ASRmin. max.
1000 500 10001250 630 12501100
20—
21037012017122.0
—'——õõ——
¡¡
¡¡¡
————
¡(AX)¡(AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡¡¡¡¡—¡¡
° RATED CURRENT (IN) [A]Calibrated at 40°C
Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]cos ø=0.3 1100V
900V° DIMENSIONS (mm)
abcd
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° STANDARD FEATURESon • off colour indicationTrip button° PROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INSTAdjustable GFT or Adjustable PTA (option)Trip indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips
° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2 LTF
@3 LTSDoor flange D.FIP20 protection (plug-in type) IP20
TemBreakz Moulded Case Circuit Breakers
Mining Series2
d
b
ca
100TL-100EM3
400XV400NE3
630XV630PE3
800XV800PE3
1250XV1250NE3
22
TemBreakz Moulded Case Circuit Breakers
Non-automatic Trip Breakers2Frame size (A)TypeNumber of polesOutside view
°°°°° RATINGRated current (In) [A] at 45°CRated insulation voltage (Ui) [V AC]Rated operational voltage [V] AC 50/60Hz
DCRated short circuit making capacity [kA peak]Rated short time current (Icw) [kA rms]°°°°° DIMENSIONS (mm)
abcd
Outline dimensions same as forWeight (kg) ' marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar
Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard
For distribution boardDraw-out (DO)°°°°° STANDARD FEATURESon • off colour indicationTrip button°°°°° ACCESSORIES (option) CODEInternally Auxiliary switch AX,AXEmounted Alarm switch AL,ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear connect/ plug-in type TCRInterpole barrier TBAAccessory lead terminal LTF
LTSDoor flange D.F
Max. Switching Current [A] ACDC
Endurance with current(No. of operating cycles) without current
e : Comes with conductor pressing terminal.o : The UVT controller is installed externally, when provided with AC UVT.
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.
d
b
ca
100XS100NNB2 3 4
1006906902502.51.8 (1sec)
60 90 1201556886XS100NB0.78 1.1 1.4
'—õõ—õõ ——
¡¡
¡(AXE)¡(ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡60025060004000
30XS30NNB2 3
306606602502.51.8 (1sec)
50 751306887XS30NB0.48 0.74
' e—õõ—— õ— õ—
¡¡
¡(AXE)¡(ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡1807560004000
50XS50NNB2 3
506606602502.51.8 (1sec)
50 751306887XS50NB0.48 0.74
' e—õõ—õõ—
¡¡
¡(AXE)¡(ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡30012560004000
100XE100NN2 3
1006606602502.51.8 (1sec)
50 751306887XE100NS0.48 0.74
'—õõ—õõ—
¡¡
¡(AXE)¡(ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡60025060004000
225XE225NNC3
2256906902505.53 (1sec)
1051606083XE225NC1.4
'õ (BAR)õ—õ———
¡¡
¡(AXE)¡(ALE)¡—¡¡¡¡—¡¡¡¡¡¡¡—¡¡135056040004000
225XS225NN3 4
22569069025064 (1sec)
105 14016586107XS225NS1.85 2.4
'õ (BAR)õ—õõ——
¡¡
¡(AXE)¡(ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡—¡¡135056040004000
400XS400NN3 4
40069069025095 (1sec)
140 185260103131XS400NS4.7 6.1
'õ (BAR)õ—õõ—õ
¡¡
¡(AX)¡(AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡¡—¡2400100010005000
23
TemBreakz Moulded Case Circuit Breakers
Non-automatic Trip Breakers2Frame size (A)TypeNumber of polesOutside view
°°°°° RATINGRated current (In) [A] at 45°CRated insulation voltage (Ui) [V AC]Rated operational voltage [V] AC 50/60Hz
DCRated short circuit making capacity [kA peak]Rated short time current (Icw) [kA rms] 1sec°°°°° DIMENSIONS (mm)
abcd
Outline dimensions same as forWeight (kg) ' marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar
Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard
For distribution boardDraw-out (DO)°°°°° STANDARD FEATURESon • off colour indicationTrip button°°°°° ACCESSORIES (option) CODEInternally Auxiliary switch AX,AXEmounted Alarm switch AL,ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear connect/ plug-in type TCRInterpole barrier TBAAccessory lead terminal LTF
LTSDoor flange D.F
Max. Switching Current [A] ACDC
Endurance with current(No. of operating cycles) without current
d
b
ca
600XS600NN3 4
600690690250159.6 (0.3sec)
210 280273103145XS600NS9.0 11.5
—'õ—õõ—õ
¡¡
¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡3600150010005000
800XS800NN3 4
800690690250159.6 (0.3sec)
210 280273103145XS800NS9.4 12.2
—'õ—õõ—õ
¡¡
¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡480020005003500
1000XS1000NN3 4
10006906902503215 (0.3sec)
210 280370120171XS1000NE20.4 26.4
—'õ—õõ—õ
¡¡
¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡—¡¡—¡600025005002500
1200XS1200NN3 4
12006906902503215 (0.3sec)
210 280370120171XS1200NE20.4 26.4
—'õ—õõ—õ
¡¡
¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡—¡¡—¡720030005002000
1600XS1600NN3 4
16006906902504520 (0.3sec)
210 280370140191XS1600NE24.9 32.9
—õ——'——õ
¡¡
¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡——¡¡—¡960040005002000
2000XS2000NN3 4
20006906902509035 (0.3sec)
320 429450185245XS2000NE51.8 64.8
—õ——'——õ
¡¡
¡(AX)¡(AL)¡¡¡¡——¡ !2¡¡¡¡———¡—¡1200050005002000
2500XS2500NN3 4
25006906902509035 (0.3sec)
320 429450185245XS2500NE60 75.7
————'———
¡¡
¡(AX)¡(AL)¡¡¡¡——¡ !2¡¡¡¡———¡—¡1500062505002000
o : The UVT controller is installed externally, when provided with AC UVT.!2 : Handle is supplied as standard.
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.
These are the switches without automatic trip units, and the switching capacity is 6 times the rated current.
Remote tripping is possible when equipped with shunt trip or undervoltage trip.
Auxiliary switch or alarm switch can also be fitted. For the details on the specifications please contact
TERASAKI.
24
15/30}620/45}935/75}1550/100}20100/200}40250500
6 12.852.5 23.355 170
110230133162—4.7
'—õõ—õ——
¡
¡(AX)¡(AL)¡¡¡¡—¡—¡—¡—¡ (TYD)——
100TL-100SC3
225TL-225SB3
400TL-400S3
600TL-600S3
800TL-800S3
900TL-1000S3
125/300}30200/400}40225/600}60225/750}75
250500
6 12.852.5 23.370 450
140260133183469.3
'õõ—õõ——
¡
¡(AX)¡(AL)¡¡¡¡—¡—¡—¡—¡ (TYD)——
250/500}50300/600}60400/800}80400/1100}110400/1500}150250500
6 12.852.5 23.3140 430
2103001332025617.7
'õõ—õõ——
¡
¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——
600/1100}110600/1500}150600/1900}190600/2300}230
250500
6 12.852.5 23.3140 330
2404001331996327
—'õ—õõ——
¡
¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——
800/1100}110800/1500}150800/1900}190800/2300}230
250500
6 12.852.5 23.3220 400
2404001331996327
—'õ—õõ——
¡
¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——
900/1900}190900/2300}230
250500
6 12.852.5 23.3220 400
2404001331996327
—'——————
¡
¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——
° RATINGSRated current [A] at 40°C / magnetic trip current [A]
DC rated voltage [V] 2 poles in series3 poles in series
Examples of I2t let-through at faultinterruption (500V DC)Prospective SC fault [kA]Time-constant [ms]I2t×103 A2 • s° DIMENSIONS (mm)
abcde
Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw
Attached flat barSolderless terminal (PWC)
Rear connect (RC) Bolt studFlat bar stud
Plug-in (PM) For switchboardFor distribution board
Draw-out (DO)° PROTECTIVE FUNCTIONSFixed magnetic trip (INST trip only)° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip UVT
Externally Motor operator MOTmounted External operating handle OHE
OHJOHH
Extension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle lock HLInterpole barrier TBAAccessory lead terminal @2 LTF
@3 LTSDoor flange D.F
Frame Size [A]TypeNumber of polesOutside view
NOTES: ' : Standard, this configuration used unless otherwise specified.õ : Optional standard, specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.
@2 : Draw out leads horizontally.@3 : Draw out leads vertically.
d e
b
ca
z Moulded Case Circuit Breakers
Thyristor Protection Breakers2
25
10 30 (6) (32)15 40 (16) (63)20 50 (25)q460
— 2.5 2.5 2.52.5 2.5 — —2.5 5 w 5 w 5 w— 5 5 —5 5 — —— 6(3) 6(3) 6(3)6(3) — — —— 6(3) 6(3) 6(3)6(3) — — —— 6(5) 6(5) —r 10(5) 10(5) —10(5) 10(5) 10(5) —1 5 — —
25 50 75 100956077 79160 340 500 660
'
—
—
'¡——
¡
¡¡¡ —¡ —¡¡ — ¡ —— ¡
10 30 (25)15 40 (32)20 50 (63)q460
— 2.5 —2.5 2.5 —2.5 5 w —— 5 —5 5 —— — 6(3)— — —— 6(3) 6(3)6(3) — 6(5)— 6(5) 10(5)r 10(5) 10(5)10(5) 10(5) 10(5)— 5 —
25 50 7574.56077 79130 280 410
—
'
—
——¡ —¡ —
¡
—¡¡ —¡ ———— ¡
10 3015 4020 50
250
—————————5555
5074.56079280
—
—
'
——¡¡
¡
—¡————¡
60 (80)75100q460
— 5 5 55 5 — —5 5 5 55 5 5 —5 5 — —— 6 6 66 — — —— 6 6 66 — — —— 10 10 1010 10 10 —10 10 10 —1 5 — —
25 50 75 100956077 80210 420 630 840
'
—
—
'¡——
¡
¡¡¡ —¡ —¡¡— ¡
60 (80)75100q460
—————— 6 66 — —— 6 66 — —— 10 1010 10 1010 10 101 5 —
25 50 7577.56077 80210 420 490
—
'
—
————
¡
—¡¡¡ ———— ¡
50TB-5S1 2 3 4
50TB-5P1 2 3
50TB-5D2
100TB-10S1 2 3 4
100TB-10P1 2 3
° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)
Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 460V
265V220V110/220V110V
BS 3871 part1 e 440V254/440V380V,415V220/380V,240/415V220V,240V120/240V120V
° DC RATED BREAKING CAPACITY [kA] 125V° DIMENSIONS (mm)
abcd
Weight (g)° CONNECTIONSFront-connect (FC)Plug-in (line end)Front-connect (load end)Plug-in° MOUNTINGS (optional)ClipClip-in chassisDouble mounting baseSingle mounting base° PROTECTIVE FUNCTIONSThermal and fixed magnetic trips° ACCESSORIES (option) CODEShunt trip SHTHandle holder HHHandle lock HLHandle capFlash plateProtection coverInterpole barrier TBA
Frame Size [A]TypeNumber of polesOutside view
Accessories for TB series
NOTES: ' : Standard.¡ : “yes” or “available”.— : “no” or “not available”.
q : Rated current shown in ( ) available on request. (except JIS and marine standard).w : 2.5kA for 10A rating.e : Rated breaking capacities shown in ( ) are applied to 6A and 10A ratings.r : Apply its breaking capacity at 120V. AC if necessary.
shunt trip protective cover handle holder handle lock(for single poletype use only)
handle cap flash plate
type: TKB-50SGH (red) type: TKB-50SG (red)
type: TAA-5CR (red)TAA-5CY (yellow)TAA-5CG (green)
d
b
ca
Miniature Circuit Breakers
TB Series for Distribution Board Use2
26
TemBreakz Moulded Case Circuit Breakers
Adjustable Thermal Trip2° RATED CURRENT (In) [A]at 45°C
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V400V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category°°°°° DIMENSIONS (mm)
abcd
Weight (kg) ' Marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar
Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard
For distribution boardDraw-out (DO)°°°°° PROTECTIVE FUNCTIONSAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips°°°°° STANDARD FEATURESon • off color indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.FIP20 protection Plug-in type IP20
125 125 160 250 250 400 400 630XS125CJ XS125NJ XS160NJ XS250NJ XS250PJ XS400CJ XS400NJ XS630CJ*3 4 *3 4 *3 4 *3 4 *3 4 *3 4 *3 4 *3 4
d
b
ca
Frame Size [A]TypeNumber of PolesOutside viewNOTE: *2 pole breaker is 3 pole breaker with centre pole
omitted.
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : D C rating available on request.o : The UVT controller is installed externally when provided with AC UVT.@2 : Draw out leads horizontally@3 : Draw out leads vertically@5 : The application on IT systems on this voltage is not available.
Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj.range Rated Adj.range Rated Adj.range Rated Adj.range Rated Adj.rangeCurr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. 20 12.5 20 20 12.5 20 160 100 160 160 100 160 160 100 160 250 160 250 250 160 250 400 250 400 32 20 32 32 20 32 250 160 250 250 160 250 400 250 400 400 250 400 630 400 630 50 32 50 50 32 50 63 40 63 63 40 63100 63 100 100 63 100125 80 125 125 80 1258 8 8 8 8 8 8 8690 690 690 690 690 690 690 690
— 5/2.5 @5 8/4 @5 8/4 @5 8/4 @5 16/8 @5 18/9 @5 16/8 @57.5/3.8 @5 12/6 @5 22/11 @5 22/11 @5 22/11 @5 22/11 @5 30/15 @5 25/13 @510/5 22/11 25/13 25/13 25/13 30/15 42/21 30/1514/7 25/13 25/13 25/13 35/18 35/18 50/25 35/1818/9 30/15 35/18 35/18 35/18 35/18 50/25 45/2318/9 30/15 35/18 35/18 35/18 35/18 50/25 45/2325/13 50/25 50/25 50/25 50/25 50/25 85/43 50/25— 12 22 22 22 22 30 2510 22 25 25 25 30 42 3525 50 50 50 50 50 85 50— — — — — — — —10 15 40 40 40 40 40 4015 20 40 40 40 40 40 40— — — — — — — —A A A A A A A A
90 120 90 120 105 140 105 140 105 140 140 185 140 185 210 280155 155 165 165 165 260 260 27386 86 86 86 103 103 103 103104 104 107 107 124 131 131 1451.3 1.58 1.3 1.58 1.85 2.4 1.85 2.4 2.1 2.6 4.7 6.1 4.7 6.1 9.0 11.5
' ' ' ' ' ' ' —— — õ (BAR) õ (BAR) õ (BAR) õ (BAR) õ (BAR) 'õ õ õ õ õ õ õ õõ õ — — — — — —– – õ õ õ õ õ õõ õ õ õ õ õ õ õõ — õ — — — — — — —— — — — õ õ õ õ
¡ ¡ ¡ ¡ ¡ — — —— — — — — ¡ ¡ ¡
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡
¡(AXE) ¡(AXE) ¡(AXE) ¡(AXE) ¡(AXE) ¡(AX) ¡(AX) ¡(AX)¡(ALE) ¡(ALE) ¡(ALE) ¡(ALE) ¡(ALE) ¡(AL) ¡(AL) ¡(AL)¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡— — — — — — — ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡— — — — — ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ — — —¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡õ õ õ õ õ õ õ õ
27
TemBreakz Moulded Case Circuit Breakers
Adjustable Thermal Trip2630 800 125 160 250XS630NJ XS800NJ XH125NJ XH160NJ XH250NJ*3 4 *3 4 *3 4 *3 4 *3 4
Frame Size [A]TypeNumber of PolesOutside viewNOTE: *2 pole breaker is 3 pole breaker with centre pole
omitted.
° RATED CURRENT (In) [A]at 45°C
Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V
440V415V400V380V240V
NEMA AB-1 600V480V240V
Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V
125VRated short time current (lcw) [kA. rms.]Utilization Category°°°°° DIMENSIONS (mm)
abcd
Weight (kg) ' Marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar
Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard
For distribution boardDraw-out (DO)°°°°° PROTECTIVE FUNCTIONSAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips°°°°° STANDARD FEATURESon • off color indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE
Shunt trip SHTUndervoltage trip o UVT
Externally Motor operator MOTmounted External Panel mount. type OHE
operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF
@3LTSDoor flange D.FIP20 protection Plug-in type IP20
d
b
ca
Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj. rangeCurr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max.400 250 400 800 500 800 20 12.5 20 160 100 160 160 100 160630 400 630 32 20 32 250 160 250
50 32 50 63 40 63100 63 100125 80 125
8 8 8 8 8690 690 690 690 690
20/10 @5 20/10 @5 8/4 @5 15/7.5 @5 15/7.5 @535/18 @5 35/18 @5 25/13 @5 25/13 @5 25/13 @550/25 50/25 42/21 42/21 42/2150/25 50/25 50/25 50/25 50/2565/33 65/33 50/25 50/25 50/2565/33 65/33 50/25 50/25 50/2585/43 85/43 85/43 85/43 85/4330 30 25 25 2550 50 42 42 4285 85 85 85 85— — — — —40 40 40 40 4040 40 40 40 40— — — — —A A A A A
210 280 210 280 90 120 105 140 105 140273 273 155 165 165103 103 86 103 103145 145 104 124 1249.0 11.5 9.4 12.2 1.3 1.58 2.1 2.6 2.1 2.6
— — ' ' '' ' — õ (BAR) õ (BAR)õ õ õ õ õ— — õ — —õ õ — õ õõ õ õ õ õ— — õ — — —õ õ — õ õ
— — ¡ ¡ ¡¡ ¡ — — —
¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡
¡(AX) ¡(AX) ¡(AXE) ¡(AXE) ¡(AXE)¡(AL) ¡(AL) ¡(ALE) ¡(ALE) ¡(ALE)¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ — — —¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ — — —— — ¡ ¡ ¡¡ ¡ ¡ ¡ ¡õ õ õ õ õ
NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : D C rating available on request.o : The UVT controller is installed externally when provided with AC UVT.@2 : Draw out leads horizontally@3 : Draw out leads vertically@5 : The application on IT systems on this voltage is not available.
28
Approvals and Applicable Breaking Capacities to Marine Standards.
Breaker Rated Poles Rated
type current[A] voltage[V]
XS30NB 3,5,10,15,20,30 2,3 500250125
XE50NB 3,5,10,15,20,30,40,50 2,3 500250125
XS50CB 10,15,20,30,40,50 2,3 500250125
XS50NB 10,15,20,30,40,50 2,3 500250125
XH50NS 15,20,30,40,50 3 500FOR JAPANESE MARKET 250
XS60NS 60 2,3 500FOR JAPANESE MARKET 250
125
XE100NS 10,15,20,30,40, 2,3 50050,60,75,100 250
125
XS100NB 15,20,30,40,50, 2,3 50060,75,100 250
XH100NS 15,20,30,40,50, 3 50060,75,100 250
XE225NS!7 125,150,175,200,225 3 500FOR JAPANESE MARKET 250
XS225NS 125,150,175,200, 3 500225 250
XH225NS 125,150,175,200, 3 500225 250
XH225NE 125~225 3 500125,150,175,200, 250225 500
FOR JAPANESE MARKET 250
XS400CS 125,150,175,200,225 3 500250,300,350,400 250
XS400NS 125,150,175,200,225 3 500250,300,350,400 250
XS400NE 125~225,200~400 3 500125,150,175,200, 250225,250,300,350, 500400 250
XS600CS 300,400,500,600 3 500250
XS600NS 300,400,500,600 3 500250
XS600NE 300~600 3 500300,350,400,500, 250600 500
250
XS800CS 700,800 3 500250
XS800NS 700,800 3 500250
XS800NE 400~800 3 500400,450,500,600, 250700,800 500
250
AC Rated breaking capacity [kA sym. rms.]/Rated making capacity [kA peak]
NK LR AB GL BV2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.642/96.785/19810/18.525/53.242/95.610/18.525/53.242/95.622/50.150/11542/96.785/19815/31.325/53.225/56.250/11542/96.785/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w
5 5 5
5 5 5
7.5 7.5 7.5
7.5 7.5 7.5 7.5 7.515
40 40.6 40 40
7.5 7.85 7.5 7.515
7.5 7.85 7.5 7.515
15 15 15 15 15
40 40.6 40 40
10 10.1 10 10
40 40.6 40 40
40 40.6 40 40
40
DC Ratedbreaking capacity [kA]
NK LR AB GL BV2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.643.7/96.888.8/20410.25/18.125.6/53.243.3/96.910/17.2!1
25/60.5!2
42/97.9!4
22/50.150/11543.7/96.888.8/20415.4/31.425.6/53.226.0/56.651.0/11643.7/96.888.8/20451.9/121q88.8/204q5.09/9.4w5.09/9.4w33.1/72.651.0/11653.5/12588.8/20451.9/121q88.8/204q5.09/9.4w5.09/9.4w33.1/72.651.0/11653.5/12588.8/20453.5/125q88.8/204q10.2/19.3w10.2/19.3w33.1/72.651.0/11653.5/12588.8/20453.5/125q88.8/204q10.2/19.3w10.2/19.3w
2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.642/96.785/19810/18.525/53.242/95.610/18.525/53.242/95.622/50.150/11542/96.785/19815/31.325/53.225/56.250/11542/96.785/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w
10/18.5!1
25/52.5!2
42/95.6!9
42/88.2!1
85/187!2
10/18.5!1
25/52.5!2
42/95.6!9
10/18.5!1
25/52.5!2
42/95.6!9
25/52.5!1
50/105!2
42/88.2!1
85/187!2
15/30!1
25/52.5!2
25/52.5!1
50/105!2
42/88.2!1
85/187!2
42/88.2!1q
85/187!2q
30/63!1
50/105!2
42/88.2!1
85/187!2
42/88.2!1q
85/187!2q
30/63!1
50/105!2
50/105!1
85/187!2
50/105!1q
85/187!2q
30/63!1
50/105!2
50/105!1
85/187!2
50/105!1q
85/187!2q
10/17!1
25/52.5!2
42/88.2!9
10/17e25/52.5!3
25/52.5!1
50/105!2
42/88.2!1
85/187!2
25/52.5!1
50/105!2
42/88.2!1
85/187!2
42/88.2!1
85/187!2
50/105!1
85/187!2
NOTES: q : with INSTw : without INSTe : at 450V AC!1 : The value is Icu at 450V AC. Contact Terasaki for Ics value.!2 : The value is Icu at 240V AC. Contact Terasaki for Ics value.!3 : at 240V AC!4 : at 120V AC!5 : Being or will be applied!7 : Plug-in type only. For the mounting and the other details refer to XS225NS.!9 : The value is Icu at 120V AC. Contact Terasaki for Ics value.
TemBreakz Moulded Case Circuit Breakers
Marine Approval2
29
NOTES: q : with INSTw : without INSTe : at 450V ACr : at 220V ACt : 50/116kA at 660V ACy : 50/115kA at 690V ACu : 2.5/4.1kA for 10A ratingi : at 110V AC
o : at 225V AC!0 : at 250V DC!1 : The value is Icu at 450V AC. Contact Terasaki for Ics value.!3 : at 240V AC!5 : Being or will be applied!6 : The value is Icu!8 : Contact Terasaki for Ics value.!9 : 2.5/3.57kA for 10A rating.
Approvals and Applicable Breaking Capacities to Marine Standards.
Breaker Rated Poles Rated
type current[A] voltage[V]
XH800PS 700,800 3 460
XS1200NE 200~400,400~800, 3 500600~1200 250200,225,250,300,350,400,450 500500,600,700,800,1000,1200 250
XS1600NE 800~1600 3 500800,900,1000, 5001200,1400,1600
XS2000NE 1200~2000 3 5001200,1400,1600 5001800,2000
XM30NB 0.7,1.4,2,2.6,4,5, 3 5008,10,12,16,25,32 250
XM50CB 0.7,1.4,2,2.6,4,5,8,10, 3 50012,16,25,32,40,45 250
TB-5D 10,15,20,30,40 2 25050 125
TB-5S 10,15,20,30,40 2 25050 125
TB-5P 10,15,20,30,40 2 25050 125
TL-100F 15,20,30,40,50 3 46060,75,100
TL-225F 125,150,175,200, 3 460225
TL-400E 250,300,350,400 3 460
TL-600NE 300~600 3 690300,350,400, 460500,600 240
TL-800NE 400~800 3 690400,450,500, 460600,700,800 240
TL-1000NE 500~1000 3 690500,600,700, 460800,900,1000 240
TL-1200NE 600~1200 3 690600,700,800, 4601000,1200 240
TL-100C 15,20,30,40,50, 3 50060,75,100
TL-225B 125,150,175,200, 3 500225 250
TL-400 125,150,175,200,225, 3 500250,300,350,400 250
TL-600 450,500,600 3 500250
TL-800 700,800 3 500250
AC Rated breaking capacity [kA sym. rms.]/Rated making capacity [kA peak]
NK LR AB GL BV85/19350/117q85/198q15/31.3w15/31.3w85/196q20/46w
85/195q42/99w
2.5/3.85/8.72.5/3.85/8.75/8.0u42/99.35/8.0u42/99.35/8.0u42/99.3120/280
120/280
120/280—125/295——125/295——125/295——125/295—180/396
180/396
180/396
180/396
180/396
5 5 5
5 5
5 5 5
40 40
40 40
40 40
40 40
DC Ratedbreaking capacity [kA]
NK LR AB GL BV85/19353.5/125q88.8/204q15.4/31.4w15.4/31.4w87.1/194.9q21.5/51.5w
87.1/194.9q43.0/102.9w
2.5/3.85/8.72.5/3.85/8.75/8.0u43.5/101.65/8.0u43.5/101.65/8.0u43.5/101.6120/280
120/280
120/280—125/295——125/295—45/93.8!8
125/295!1
150/345!8
45/93.8!8
125/295!1
150/345!8
180/419y!1
180/419y!1
180/419y!1
180/419y!1
180/419y!1
85/19350/117q85/198q15/31.3w15/31.3w85/196q20/46w
85/195q42/99w
2.5/3.85/8.72.5/3.85/8.75/8.0u42/99.3
5/8.0u42/99.3120/280
120/280
120/280—125/295——125/295——125/295——125/295—180/396
180/396
180/396
180/396
180/396
85/187!1
65/143q!1
100/220q!2
85/187q!1
85/187q!1
5/7.98r!9
42/102i5/7.98r!9
42/102i5/7.98r!9
42/102i120/288!1
120/288!1
120/288!1
45/92!8
125/298!1
150/347!8
45/92!8
125/298!1
150/347!8
45/92!8
125/298!1
150/347!8
45/92!8
125/298!1
150/347!8
180/419!1
180/419!1
180/419!1
180/419!1
180/419!1
65/143q!1
5/8.0uo
7.5/13.7i
5/8.0uo
7.5/13.7i120/280!6
120/280!6
120/280!8
45/94.5!8
125/275!1
150/330!8
45/94.5!8
125/275!1
150/330!8
45/94.5!8
125/275!1
150/330!8
45/94.5!8
125/275!1
150/330!8
180/415!8
180/415!8
180/415!8
180/415!8
180/415!8
30
ø1002.0
1185A850mm2
45mm1185A850mm2
45mm992A600mm2
38mm
TZS-100
ø681.1
650A325mm2
29mm650A325mm2
29mm556A250mm2
26mm
TZS-68
ø400.7
298A100mm2
17mm298A100mm2
17mm257A80mm2
15.5mm
TZS-40
ø240.3
139A30mm2
10.5mm139A30mm2
10.5mm115A22mm2
9.5mm
TZS-24
ø150.2
61A8mm2
6mm61A8mm2
6mm49A5.5mm2
5mm
TZS-15
120 qw24096-132192-26430100300 e5001000below 0.040.30.5 er1260/78/1000.22
'¡
t1C yLED (Red)electrical u1VA
TZS-AD¡¡
TypePhase and 3ø3W, 1ø2Wwires 3ø4WOutside view
° RATINGSRated control voltage [V AC]
50/60HzApplicable range 120V AC
240V ACRated sensitivity current [mA]
Rated operating time (sec)
Dimensions [mm] (surface mount) W/H/DWeight [kg] (surface mount)° MOUNTINGSurface mountFlush mount° STANDARD FEATURESEarth leakage detectionOutput contactEarth leakage indicationReset functionPower source required
Ratings of Relays
TypeOutside view
Diameter of transit part [mm]Weighr [kg]Applicable numbers, size and continuous currentof wires (IV cable wires)2 max. continuous currentwires max. wire size
max.diameter of wire3 max. continuous currentwires max. wire size
max.diameter of wire4 max. continuous currentwires max. wire size
max.diameter of wire
Ratings of ZCT (Core Balanced Current Transformers)
NOTE ' : Standard, this configuration is used unless otherwise specified.¡ : “yes” or “available”.q : Terminals for 120V AC and 240V AC are provided.
CAUTION : DO NOT APPLY 240V AC TO THE 12OV AC TERMINAL.,BURNOUT CAN RESULT.
w : For 415V AC or 440V AC, Please contact to TERASAKI.e : Adjustable type by Dip slide swnch.r : Operating time range and Non-operating time range.
t : Solied-state type, current operating type.y : Ratings of output contact.
u : The output contacts remain until the RESET button is operated.Provided the control power supply fails the contacts automatically reset.
gnitarepodetaR)ces(emit
)ces(egnaremitgnitarepOgnitarepo-noN
)ces(egnaremit
3.0 63.0~2.0 51.0
5.0 6.0~4.0 83.0
1 2.1~8.0 7.0
2 2~3.1 52.1
daolecnatsiseR1=øsoc
daolevitcudnI)sm7=R/L(4.0=øsoc
daol.niM
CAV021 A6 A5.3
CDV5taAm01CAV042 A6 A5.3
CDV03 A6 A3
xEarth-leakage Relays
TZS Series2
31
TemMeasurePower Monitoring Equipment3
To protect the world's ecology, Terasaki addresses ourselves to energy saving and minimization of environmental pollution.TemMeasure allows power consumption to be monitored for each branch circuit, assisting you in saving energy. Features ofTemMeasure include the following:
¡Current, voltage, instantaneous power, integrated power, and power factor of low-voltage power distribution systems can bemeasured and displayed.
¡Easy-to-use membrane switches and a clear 6-digit LED display, with a wide viewing angle.¡Applicable both to 3-phase and single-phase circuits.¡A cable extension permits separation between the display unit and the sensor unit and therefore installation of the display unit
anywhere.¡Field fittable to the load side of the existing TemBreak range, MCCB 400AF, 600AF, 800AF.¡RS-485 serial transmission or pulse output of measured values is available.
NOTES: ¡ : “yes” or “available”.q : Do not perform a dielectric strength test between poles. Doing so may cause damage to the internal VT or CT.w : When the breaker is OFF or tripped, control power is lost, resulting in the measuring, display and transmission functions being disabled. Stored data including
setting data and integrated power, however, are preserved.e : Not available for Display separate type.r : When control power is lost, integrated power is not measured and not integrated.t : A lead terminal block is fitted. An external transformer with a capacity of 30 VA or more is needed, because of inrush current occurring at control power ON.y : When the ambient temperature is 25°Cu : The device reads 0 for less than 2%.i : Integrated time error: 0.01% ±1 sec.o : If current is 0A, the device reads “FF”.
Display separate typeAdd-on type
sepyT 3ABX 4ABX 6ABX 8ABX
rekaerbelbacilppA,SN004SX,SC004SX,SN004EX
EN004HX,EN004SX,EN522HXEN006SXEN006HX
EN008SXEN008HX
eriwdnaesahP3 3ø W ¡ ¡ ¡ ¡
1 3ø W ¡ ¡ ¡ ¡
° sgnitaR
]CAV[egatlovtiucricniaM q 064
]A[tnerrucgnirusaemdetaR 052 004 006 008
]zH[ycneuqerfdetaR zH06/05
rewoplortnoClanretnI ew .tiucricniamV001–042CAehtmorfdeilppussirewoplortnoC
lanretxE tr–064CAehtotdeilppaebnacecivedeht,V001–042CAsirewoplortnocnehW
.tiucricniamV001° yalpsiDdnagnirusaeM
esahpT/S/RfotnerrucdaoL uegnaR tnerrucgnirusaemdetarfo%003–2
ycarucca y tnerrucgnirusaemdetarfo%1±
neewtebfoegatloveniLsesahpT/S/R
egnaR V064–001CA
ycarucca y egatlovdetarfo%1±
rewopsuoenatnatsnIegnaR Wk999999–0
ycarucca y %5.2±
rewopdetargetnIegnaR hWM9.99999rohWk9.99999.xaM
ycarucca y %5.2± i
rotcafrewoPegnaR %001–1 o
ycarucca y %5.2±
32
TemPlugDirect bus plug-in mounting base4
Just plug the TemPlug into the main bus.That completes the connection!We offer solutions to downsizing and standardizing them,shortening the manufacturing periods, and reducing the costs.
°Downsizing of switchboardsThe TemPlug is inserted directly into themain bus, requiring no space for branchedbus bars. This allows for decreasing thewidth of a switchboard.
°Standardization of switchboardsThe size of the main bus is determined bythe power capacity. Therefore, theswitchboards of the same capacity can bestandardized.
°Shortening of manufacturingperiods
The time-consuming jobs for making andmounting branched bus bars are no longerrequired.The working time can be greatly saved,resulting in shorter lead-time of aswitchboard.
°Flexibility in changingspecification
If there is any change in the frame size orrated current of a breaker, you can complywith that change by merely changing theTemPlug.
°Standardization of order ofphases
The order of load-side phases can bestandardized into R, S, and T from the topregardless of the mounting orientation ofthe breaker.
°Improvement of safety byseparating sections
The use of the TemPlug allows you toseparate the bus and breaker sections tomanufacture a safer switchboard.
Applicable to 100A to 630A frame circuit breakers
FigA
FigB
a
d
d c
70
¶
70
c
b
600/630A400A225/250A100/125A
¶Supply the round-edge type main bus with plate thickness of 10 mm and corner radius of 5 mm. Suitable for 70mm main bus pitch.
epyT S2IDX H2IDX S3IDX ZS3IDX H3IDX 4IDX 5IDX
)A(ezisemarF 001 521 052 522 052 004 036
tiucricelbacilppAsrekaerb
,BN001SX,BNN001SX
BN001ZT
,SN001HX,JC521SX,JN521SX
JN521HX
,SN522SX,JN061SX,JN052SX
NN522SX
BN522ZT ,SN522HX,JN061HX,JP052SX
JN052HX
,SC004SX,SN004EX,EN004SX,SN004SX,EN004HX,EN522HX
,JN004SX,JC004SXNN004SX
,SC006SX,SN006EX,EN006SX,SN006SX,JC036SX,EN006HX
JN036SX
snoisnemiD
a 032 272 782
b 09 021 081 042
c )B.giF(721 )A.giF(421 )A.giF(221
d 521
33
NOTES: ¡ : Yes or available.— : No or not available.q : AC breaking capacity (kA) @ 415V – 6/6kA. [Icu/Ics]w : Available on request – ICP–M, U and L characteristics.e : 1 pole + neutral and 3 pole + neutral available on request.
(4.5kA and 6kA types only).r : Inst is set between 3 In to 5 Int : Inst is set between 5 In to 10 Iny : Inst is set between 10 In to 20 In
Ampere FrameSeriesNumber of polesAC RATED INSULATION VOLTAGE [Ui]AC BREKING CAPAClTY sym. r.m.s.(kA)EN 60 898 [Icn]/[Ics]EN 60 947-2 [Icu]/[Ics]MCB Characteristics wEN 60 898 0.5AType TDB 1A
2ACharacteristics: B 3Ar 4A
6A10A13A16A20A25A32A40A50A63A
EN 60 898 0.5AType TDC 1A
2ACharacteristics: C 3At 4A
6A10A13A16A20A25A32A40A50A63A
EN 60 898 0.5AType TDD 1A
2ACharacteristics: D 3Ay 4A
6A10A13A16A20A25A32A40A50A63A
OUTLINE DIMENSIONS (mm)abcdef
STANDARD FEATURESContact position indicatorNumber of units per boxIP 20 Terminal protectionACCESSORIESShunt tripAuxiliary contactsTerminal coversPadlock device
TemDinMiniature Circuit Breakers5
bc f
a e d
5
63E–Series1 2 3 4415
e 4.5/4.5—
————————————————————¡¡¡¡¡¡¡¡¡¡———————————————
457343873617.8 35.6 53.4 71.2
—12 6 4 3¡
——¡¡
63S–Series1 2 3 4415
e 6/610/6
—————¡¡¡¡¡¡¡¡———————¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡
457343873617.8 35.6 53.4 71.2
—12 6 4 3¡
——¡¡
63R–Series1 2 3 4415
10/7.510/7.5
—————¡¡¡¡¡¡¡————————¡¡¡¡¡¡¡¡ q¡ q¡ q¡¡¡¡¡¡¡¡¡¡¡¡¡ q¡ q¡ q
457343873617.8 35.6 53.4 71.2
¡12 6 4 3¡
¡¡¡¡
34
This is a standard breaker excluding thermaloverload trip. It has an instantaneous trippingcharacteristic only. This is used where short-circuit protection is exclusively needed.
Circuit Breaker withMagnetic Trip Only
High-lNST Trip Breaker
This is a standard molded case circuit breaker(electronic type) with a high instantaneous trip-ping value, in one-point fixed. This is recom-mended for zone selective interruption or theprimary side of transformer application.
Breakers for Coordination
TERASAKI Standard Breakers are manufac-tured based on the “standard operating condi-tions”If an application in other places than those of“standard operating conditions”, specify as “Spe-cial Environment Breakers” when ordering yourbreakers.
Special Environment Breakers
Standard Operating Conditions
• Operating ambient temperature: –5°C to 40°CIf used at a higher temperature than 40°C, the operating currenthas to be reduced;50°C: Approx. 90%60°C: Approx. 70%
• Relative humidity: Below 85%• Altitude: Below 2000m• Atmosphere: Contents of dust, smoke, corrosive gases, flammable gases, moisture and salt should
be moderately low.
Low-temperature Circuit Breaker
This is a breaker designed for use in low tem-perature environment. Storage and operatingconditions are –40°C and –20°C respectively.Since the operating characteristics of the low-temperature breaker are adjusted at 40°C(45°C), the characteristics vary at a lower tem-perature.Conditions: This type of breaker should not be
used where thermal changes arerapid and dew-formation and freez-ing exist.
Anti-fungus Circuit Breaker (Tropical-proof)
Dielectric strength and other electrical propertiesmay deteriorate under unusual high temperatureand high-humidity conditions. This type ofbreaker is specially prepared with specialsurface treatment, special materials and tropical-proof processing.Operating conditions are:
Temperature: Below 60°CHumidity: Below 95%
Conditions: This type of breaker should be usedin a constant humidity environmentwithout rapid thermal changes anddew formation.
Highly Anti corrosive Circuit Breaker
In highly corrosive or saline atmosphere,breakers are used in sealed corrosion-proofboxes or enclosures.However, in a place where the influence ofcorrosive gases is relatively low a simplermethod is applicable:This is the Highly Anti-corrosive Breaker withspecial surface treatment of high corrosion-proofness.This eliminates needs for such a box orenclosure.
Low-INST Trip Breaker
Low Instantaneous Trip Breakers is also avail-able on request. Ask TERASAKI or its agent fordetails.
Other Electrical Distribution EquipmentSpecial Circuit Breakers ¶ Special Circuit Breakers are available on request.6
CAUTION!
Be sure to read the instruction manual carefully to ensure
correct and safe use of the product.
OVERSEAS NETWORK
TERASAKI (EUROPE) LTD.80 Beardmore Way, Clydebank Industrial Estate, Clydebank, Glasgow, G81 4HT. SCOTLAND (U. K.)Telephone : 44-141-941-1940 / Fax : 44-141-952-9246E-mail : [email protected]://www.terasaki.com/
TERASAKI ITALIA s.r.l.Via Ambrosoli 4a, 20090 Rodano, Milano, ITALYTelephone : 39-02-92278300 / Fax : 39-02-92278320E-mail : [email protected]://www.terasaki.it/
TERASAKI ESPAÑA, S.A.U.Roma, s/n, 08400 Granollers, Barcelona, SPAINTelephone : 34-93-879-60-50 / Fax : 34-93-870-39-05E-mail : [email protected]://www.terasaki.es/
TERASAKI SKANDINAVISKA ABFrasarvagen 32 SE-142 50 SKOGÅS SwedenTelephone : 46-8-556-282-30 / Fax : 46-8-556-282-39E-mail : [email protected]://www.terasaki.se/
TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.9 Toh Guan Road East 03-01 Alliance Building, Singapore 608604, SINGAPORETelephone : 65-6744-9752 / Fax : 65-6748-7592E-mail : [email protected]
TERASAKI ELECTRIC (M) SDN. BHD.Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor Darul Ehsan, MALAYSIATelephone : 60-3-5549-3820 / Fax : 60-3-5549-3960 E-mail : [email protected]
TERASAKI DO BRASIL LTDA.Rua Cordovil, 259-Parada de Lucas, 21250-450 Rio de Janeiro-R. J., BRAZILTelephone : 55-21-3301-9898 / Fax : 55-21-3301-9861E-mail : [email protected]://www.terasaki.com.br/
TERASAKI ELECTRIC (CHINA) LIMITED72 Pacific Industrial Park, Xingtang Zengcheng, Guangzhou 511340, CHINATelephone : 86-20-8270-8556 / Fax : 86-20-8270-8586E-mail : [email protected]
Head Office : 7-2-10 Hannancho, Abenoku, Osaka, JAPANCircuit Breaker Division : 7-2-10 Kamihigashi, Hiranoku, Osaka, JAPANTelephone : 81-6-6791-9323 / Fax : 81-6-6791-9274E-mail : [email protected]://www.terasaki.co.jp/
JUN ’05-2.0K Catalogue No. The contents of this publication may be subject to change without notice.Recycled paper used for environmental protection.
’05-G90E