![Page 1: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/1.jpg)
1
HVAC OVERVIEWfor Single Tunnel
Configuration
November 17, 2008
ILC CFS Workshop 2008 Chicago, IL
Lee Hammond, Fermilab
![Page 2: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/2.jpg)
Klystron Cluster August Cost Basis
2
![Page 3: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/3.jpg)
Single Tunnel Alcove Layout • Alcove and Area of Refuge Consideration• NFPA 520 …shall have fresh air from the surface during a fire emergency• Air quantity shall be 34m³/hr (944 L/s, 20cfm) per person or minimum required to
prevent smoke infiltration. • Shall maintain 12.5Pa (0.05in.wg) relative to adjacent space.• Shall be provided with food, water, emergency lighting, blankets, toilets facilities, first
aid kits, two communications.
3
Area of Refuge Rack Alcove
![Page 4: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/4.jpg)
Tunnel Section with Ventilation Piping in Floor
4
SE
VENTILATION DUCTS
![Page 5: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/5.jpg)
Area of refuge Layout
5
![Page 6: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/6.jpg)
Single tunnel Airflow
• Air supply into area of refuge and rack alcoves. “Heat to air” in beam tunnel considered to be quite small. 95% reduction from RDR
6
![Page 7: 1 HVAC OVERVIEW for Single Tunnel Configuration November 17, 2008 ILC CFS Workshop 2008 Chicago, IL Lee Hammond, Fermilab](https://reader035.vdocument.in/reader035/viewer/2022071806/56649f4f5503460f94c71a2b/html5/thumbnails/7.jpg)
Airflow during Emergency
• Smoke barrier/water curtain at approx. 600m intervals
7
test