ALARM
ANNUNCIATOR
MODULE FOUR
-
8/10/2019 14 Annunciator
2/17
Metso Automation Inc. 2005
ALAMANNUNC
IATOR
Alarm Annunciator
Alarm Annunciation in the maxSTATION provides an audible signal that an alarm
has occurred within a pre-defined hierarchical group. Some features of the
annunciation subsystem are listed below
The audible signal is selectable from a library of !A" files.
The !A" files can be set to single play or loop mode.
The !A" file is played when an alarm occurs in a hierarchical group that has
been assigned to an annunciator. #p to $% groups can be assigned to one
annunciator.
An annunciator supports a range of alarm severity and has an assigned priority.The !A" file of a lower priority annunciator is pre-empted by the !A" file of a
higher priority annunciator.
The alarm annunciator can also drive a digital output.
A tas& is included that allows annunciator configuration. The configuration is
saved in a 'icrosoft Access database file.
The annunciator configuration can be changed online.
A Silence button is included on the "ertical template of (untime. This button
turns off the currently playing sound and)or the digital output point. Note that
the alarm ac&nowledge buttons on the Alarm Summary* Alarm +ist* and ,oint
ac&nowledge button also perform the annunciator silence function.
-
8/10/2019 14 Annunciator
3/17
Metso Automation Inc. 2005
Functionality
The Alarm Annunciation subsystem consists of two programs. The'S Annunciation Setup Tas& is used to define annunciators and
transmit this data to the Annunciator Tas&. The Annunciator Tas&
monitors alarm activity in each max,#/0)1 and will play the
configured sound if an alarm occurs in a group assigned to an
annunciator.
2ierarchical 3roups are defined in the max,#TOO+S onfigurator.
3roups are assigned to individual points in the max,#TOO+S
onfigurator.
3roup definition must be performed in the customer
database and the group names must be assigned to the desired points.
This database is then installed in each max,#/0)1 for annunciators tobe operational. See the max,#TOO+S onfigurator instructions for
information on group definition.
ALAMANNUNC
IATOR
-
8/10/2019 14 Annunciator
4/17
Metso Automation Inc. 2005
The 'A4Station should be e5uipped with a soundboard and spea&ers if
sound files will be played. The soundboard driver should support !A"formatted files. The annunciator configuration should be built and
saved on the station e5uipped for sound.
The 'S (egistry must be updated to allow the Annunciator Tas& to
run 6See the picture below7. The 80nable Annunciator Tas&9 fieldunder 8'achine Settings9 must be changed to :es. This field is read by
the Annunciator Tas& during startup. (estart the station if necessary. If
the value is 8:es9* the tas& will continue. If the value is 8No9* the tas&
will exit.
ALAMANNUNC
IATOR
-
8/10/2019 14 Annunciator
5/17
Metso Automation Inc. 2005
ALAMANNUNC
IATOR
Annunciator Tas& 0nable in 'S (egistry.
-
8/10/2019 14 Annunciator
6/17
Metso Automation Inc. 2005
There is no auto failover of alarm annunciation from one maxSTATION
to another* so a system should have two maxSTATIONs set up to
perform alarm annunciation.
The alarm silence function as installed from the release is not global. 2owever*
global silence is supported provided a registry update is made to eachmaxSTATION. ,erform this update as follows +og on to the station at the
engineer or administrator level. 1rom the Start menu* select ,rograms*
maxNA* #tilities* 'S (egistry 0dit. This brings up the following display.
'S (egistry 0ditor.
-
8/10/2019 14 Annunciator
7/17
Metso Automation Inc. 2005
Select the 'achine Settings folder and expand the 'A4 ontrol Systems* Inc. tree.
lic& on Annunciator Silence Station $ to bring up an edit box. 0nter the omputer
Name of the maxSTATION where the annunciator tas& is running. Always include
the opening and closing brac&et. The omputer Name is viewable from ontrol
,anel* Networ& on the desired station. If the annunciator tas& is running on this
station* no entry is necessary. An open and close brac&et with no text in between
indicates that the current station processes the silence re5uest. If the annunciator tas&
is running on more than one station* enter the omputer Names in the Annunciator
Silence Station ; and Station < fields. o not delete the brac&ets from any of the
annunciator silence station fields.
After entering the desired omputer Names* clic& O= to save the changes and
terminate the 'S (egistry 0dit program. It is necessary to restart the
maxSTATION programs to read in the new registry data. 0ither log on as a different
user or use the maxSTATION Startup program to stop and then restart the system.
3lobal silence re5uires that the 'A4Transport program is running on each
maxSTATION.
-
8/10/2019 14 Annunciator
8/17
Metso Automation Inc. 2005
ALAMANNUNC
IATOR
Alarm Annunciator onfiguration
The Alarm Annunciation subsystem includes a configuration tas& that provides
easy modification to the annunciator database. This tas& runs automatically at
startup to send the configuration to the annunciator tas&. It can also be manuallre5uested from a es&top shortcut 6'S Annunciator Setup7. The main window
appears as follows
Alarm Annunciator Setup.
-
8/10/2019 14 Annunciator
9/17
Metso Automation Inc. 2005
ALAMANNUNC
IATOR
The main display includes three main buttons 0dit* isplay and Send.
0dit and isplay will call up new displays that are described below.
Send causes the current annunciator configuration to be sent to the
annunciator tas&. The 8Send9 should be performed after edits are
successfully made to the database. The 8Send9 can be done at any time*
even while the system is online.
Note that the annunciator database is automatically sent to the
annunciator tas& every time the startup program is run.
-
8/10/2019 14 Annunciator
10/17
Metso Automation Inc. 2005
Edit the Annunciator Display
This display is called from the 80dit Annunciators9 button on the main
display. It provides an enterable field for each item in the annunciator
database. A default database with one record is included in the release.
This database must be modified to include valid hierarchical group data for
annunciators to be operational.
ALAMANNUNC
IATOR
Add or 0dit an Alarm Annunciator pop-up.
-
8/10/2019 14 Annunciator
11/17
Metso Automation Inc. 2005
The functionality of the six buttons on the bottom of the display is as
follows
Add > Add a new record to the annunciator database. The fields on the
display are filled with default data.
Delete> eletes the current record. An ac&nowledge pop-up will appear
when elete is re5uested. Once a record is deleted* it is not recoverable.
Accept > Accepts the changes made to the current record. The Accept
button moves the data on the display to the annunciator database. Ifchanges are made to a record and Accept is not pressed* the changes are
thrown away. #se the Accept button after modifying fields on a new or
existing record to force those changes to be saved.
Next> 'oves to the next record in the annunciator database.
Preious> 'oves to the previous record in the annunciator database.
Close> (eturn to the main display.
ALAMANNUNC
IATOR
-
8/10/2019 14 Annunciator
12/17
Metso Automation Inc. 2005
Any of the following fields on the 0dit display can be modified. #se the mouse or
tab &ey to move to the desired field. After modifying one or more fields* use the
Accept button to save the changes.
Output This field specified the output that is exercised when an
annunciator condition is detected. The output of an annunciatorcan be 8Spea&er9* 8O9 or 8Spea&er* O9. If Spea&er is
selected* a sound file must be provided. If O is selected* an
Output ,oint must be provided 6tagname)attribute7.
!ound File -lic& this field or button to call up the wave file pic&er.
-urrently wave file selection is restricted to the -ustom?Sounds
folder. The user can add files to this folder as long as the files are
in wave format. This field is re5uired if Spea&er output is
selected.Play Mode This field determines how the sound file is played when an
annunciator condition is detected. It is only used if Spea&er
output is selected. To play the selected sound file repeatedly*
select 8+oop9. This is advisable for short sound files. To play
the sound file once* select 8Single9.
Output Point 0nter the name of the output point that is controlled when an
annunciator condition is detected. This field is re5uired if Ooutput is selected. The point name should represent a digital
output. The attribute of the point can be included. The point
name and attribute are separated with a period. 0x.
O@$%$.(#NST-. If an attribute is not included* the (#NST-
attribute is used by default. There is no error chec&ing performed
on the entered point name.
-
8/10/2019 14 Annunciator
13/17
Metso Automation Inc. 2005
!eerity Min An annunciator supports a range of severities. 0nter the
minimum severity of the points in the specified hierarchical group
that can trigger this annunciator. "alid severities range from $ to
. 'inimum severity must be less than or e5ual to the maximum
severity.
!eerity Max 0nter the maximum severity of the points in the specified
hierarchical group that can trigger this annunciator. "alid
severities range from $ to . 'aximum severity must be greater
than or e5ual to the minimum severity.
Priority ,riorities can range from $ to B with B being the highest priority.
The priority of an annunciator determines whether or not it is
processed. The sound file for a priority $ annunciator will not
play if a priority B annunciator is active 6currently playing7. The
sound file for a priority B annunciator will replace the sound of an
active priority $ annunciator.
-
8/10/2019 14 Annunciator
14/17
Metso Automation Inc. 2005
"ierarchical
#roup$
This field is re5uired for each annunciator. 0nter the text of the
desired hierarchical group. #se a forward slash to separate
hierarchical levels. 0x. )3roup$)Subgroup;)+evel
-
8/10/2019 14 Annunciator
15/17
Metso Automation Inc. 2005
ALAMANNUNCIATOR
Display Alar' annunciator
The display below is called from the isplay Annunciators button on the
main display. It provides a list of the annunciator database. This
display is read only. #se the 0dit Annunciators display to modify the
database.
Annunciator Summary.
-
8/10/2019 14 Annunciator
16/17
Metso Automation Inc. 2005
Alar' Annunciator Tas(
This tas& runs automatically at startup. It receives the annunciator
configuration sent by the configuration tas& and monitors the alarms in the
groups specified by the configuration. It will perform the output action
specified in the configuration if an annunciator is triggered. Triggeredannunciators are processed according to their priority. A lower priority
annunciator is ignored if a higher priority annunciator is active. A higher
priority annunciator will pre-empt an active lower priority annunciator.
The annunciator tas& icon resides in the tray on the toolbar. lic& this icon
to bring up the Annunciator Tas& dialog box. The dialog box contains a
Test Sound button that can be used to verify sound and spea&er operation on
the 'A4Station. The test sound can be played once or looped. !hen
looped* press the Test Sound button again to stop the sound. The dialog box
also contains a Silence button. This button functions the same as the
Silence button on the vertical template.
!ound Files
Sound files are saved in the ?ustom?Sounds folder. A set of sound files
is included in each release. 1iles can be added to this folder and assigned to
an annunciator as long as the file is in !ave format.
ALAMANNUNCIATOR
-
8/10/2019 14 Annunciator
17/17
Metso Automation Inc. 2005
END
ALAMANNUNCIATOR