OXYGEN

OXYGEN

VACUUM

VACUUM

OXYGEN

MEDICAL AIR

MEDICAL AIR

CENTER EMBED 4"

5/8" DOWEL 12" ON

3/4" 45° CHAMFERED EDGE

FLOOR SLAB

T.O.S.

PLAN DIMENSION AS REQ'D

FOR EQUIPMENT (COORDINATE

W/APPROVED SHOP DRAWINGS)

6X6-W1.4XW1.4 W.W.F.

COUNTERTOP

6"

1/2" DCW

WALL BOX

FLOOR SLAB

NO WEIGHT PERMITTED

SUPPORTS. ABSOLUTELY

PIPE JACKET &

INSULATION

PIPE WITH INDEPENDENT

PIPE

TO BEAR ON SLEEVE.

FLOOR SLAB

BACKER ROD OR MINERAL

WOOL DAMMING MATERIAL

PIPE SLEEVE

FIRE BARRIER CAULK.THICKNESS BASED ONMANUFACTURER'SRECOMMENDATIONS ANDPRODUCT LISTING.

FIRE RATED "LINKSEAL"BRAND MECHANICALSEAL MODEL FS/FD

FIRE BARRIER CAULK.THICKNESS BASED ONMANUFACTURER'SRECOMMENDATIONS ANDPRODUCT LISTING.

INSULATION

PIPE JACKET &

PIPE SLEEVE WITHWATER STOP

BACKER ROD ORMINERAL WOOLDAMMING MATERIAL

WALL/FLOOR PENETRATION W/CAST IN PLACE SLEEVE WALL/FLOOR PENETRATION THROUGH CORE DRILLED HOLE

MIN. 2"

MIN. 2"

SUPPLY STOP (TYP)COPPER TUBING

ADAPTER (TYP)

INSULATE(INSIDE WALL)DOMESTIC HOTWATER SUPPLY(130°F)

FLEX CONNECTORBRAIDED-STAINLESS STEEL3/8"C X 1/2" FIP -16" FAUCETSUPPLY (TYP.)

NOTE:

1. 4" OR 8" CENTER TO CENTER ILLUSTRATION

SHOWN. SINGLE HOLE FAUCET SUPPLIES

SIMILAR FOR SINKS.

FRONT VIEW SIDE VIEW

PIPING TO PRESSURE TRANSDUCERIN ALARM PANEL

ALARM MONITORING PANEL, AP

(COORDINATE LOCATION

WITH HOSPICE STAFF)

OXYGEN

VACUUM

FINISHED FLOOR

CRASH RAIL

3"

MIN

.3

" M

IN.

WALL FRAMING

CEILING

MEDICAL GAS

VALVE CABINET

VC

VERIFY HEIGHTW/ ARCHITECT

USE SIDESOURCE SIDE

5"

TY

P.

48"

UN

LE

SS

NO

TE

D O

TH

ER

WIS

E

(SLIDE)

TYP.

5"

TYP.

5"

20"

GO1

GO3

5"

INS

ULA

TE

IN

SID

E

WA

LL T

O E

LB

OW

/LA

ST

FIT

TIN

G (

TY

P.)

4-SIDES

1/2" ANGLE VALVE W/ 3/8" COMPRESSION

FITTING, 3/8" CONTINUOUS PRESSURE TYPE

DOUBLE CHECK VALVE (FDA APPROVED)

60" OF 3/8" CLEAR (NSF APPROVED) TUBING,

AND UNION. MAKE FINAL CONNECTION.

JDETAILTYPICAL PIPE TRAPEZE HANGER N.T.S.

12 GAUGE STEEL (ASTM A570) 2 7__16

" HEIGHT x

15/8" WIDTH POWER-STRUT PS-150 CHANNEL, TOLCO

OR APPROVED EQUAL, CONTINUOUS SLOT W/

INTURNED LIPS, INTERMITTENT SLOTTED BOTTOM,

AND GALVANIZED AFTER FABRICATION PER ASTM

A123.

TO STRUCTURE

2" WIDE x 1/4" THICK STEEL BAR

LENGTH AS REQ'D. (BEND TO SUIT)

(EVERY THIRD SUPPORT)

2.5 PCF RIGID INSULATIONSATISFIES 25/50 FLAME-SMOKERATING PER ASTM E-84 (TYP.)

G90 180° CARBON STEELFLARED EDGE SADDLE, RIBBEDTO PREVENT SADDLE MOVMENTINSIDE HANGER.

3/4"

3/4" NPT

PRESSURE RELIEF VALVE

SET AT 75 PSIG

THRU EXTERIOR WALL10'-0" ABOVE GRADETURN DOWN ELBOWW/STAINLESS STEELSCREEN

TO SYSTEM

¾"

1" NPTEMERGENCY OXYGENSUPPLY CONNECTION

FINISHED FLOOR

36"

RECESSED, WEATHERTIGHTBOX W/PADLOCK

5"

TY

P.

48"

UN

LE

SS

NO

TE

D O

TH

ER

WIS

E

20"

GO2

5"

TY

P.

48"

UN

LE

SS

NO

TE

D O

TH

ER

WIS

E

PAD HEIGHTVARIES (REFERTO DETAILS)

INSULATE (INSIDEWALL) DOMESTICCOLD WATER SUPPLY

120V SINGLE POINTPOWER SUPPLY TOASSEMBLY BY E.C.

RECIRCULATION PUMPPOWER SWITCH

MIXING VALVE (CASTBRONZE BODY) W/INTEGRAL CHECKS& SCREEN (ASSE1070) SET @110°F ADJUSTABLE

S

S

PUMP SEQUENCINGOPERATION BY BMS

1"

1"

RCP1

RCP2

NOTE: ONE PUMP OPERATESCONTINUOUSLY. ALTERNATEPUMP OPERATION WEEKLY.INTER LOCK PUMP OPERATIONw/ SOLENOID VALVE.

1" 1"

DHWR(130°F)

MED AIR

M

SHUT OFFVALVE

ACCESS PANEL

PROVIDE ½" STUB OUT W/ SHUT OFFVALVE AND PNEUMATIC FITTINGFOR BLOW DOWN (WINTERIZATION)

DC

W

DC

W

TO IRRIGATIONSYSTEM

TO POND

FINISHEDGRADE

PIPE SLEEVEL

P6-2 FINISHED FLOOR

2"BFP5

2" DEDUCTWATER METER

DCW

DCW

REMOTEREADER

CHECK VALVE

(SLIDE)

FOR LOCATIONS

AIR COMPRESSOR(OIL-LESSRECIPROCATING)

FINISHED FLOOR

3" HIGH CONCRETEHOUSEKEEPING PAD(REFER TO DETAIL F)

½" DRAIN CONN.

2"DISCHARGEFLANGE

2½"

2"

3" HIGH CONCRETEHOUSEKEEPING PAD(REFER TO DETAIL F)

1¼" FNPT INLETCONNECTION

FINISHED FLOOR

2"

¾" FNPT SYSTEMDISCHARGECONNECTION

2"

TERMINATE ½" FNPTCONDENSATE DRAINABOVE / NEARFLOOR DRAIN

1"

REFER TO SPECIFICATION SECTION 22 63 00FOR FURTHER REQUIREMENTS

TERMINATECONDENSATEABOVEFLOOR DRAIN

TERMINATE 2" VACUUMEXHAUST / DISCHARGE PIPING48" ABOVE ROOF w/ TURNDOWNOUTSIDE AIR INTAKE

(TURNED DOWN ANDSCREENED ORFILTERED)

CO

2" INLETFLANGE (BACKSIDE)

FLEX CONNECTOR

TERMINATETANK DRAINABOVEFLOOR DRAIN

FILTER (TYP.)

GFWH1

(130º F DOMESTICHOT WATER)

ET1

2½" SW FROMDCW SOURCE

DHW (130º F)TO DISTRIBUTIONSYSTEM

DC

W

DHW (130º F)

G (2 PSIG)1½" FROMGAS MAIN

1¼"

3/4" NPTDRAIN CONN.

1½"CONN.

2

6

3

1 3

GPR1REDUCER

1½"CONN.

FINISHED FLOOR5

DOMESTIC HOT WATER GENERATION SYSTEM DETAIL CODED NOTES

1. DOWN - FIRED POWERED BURNER.

2. CSA CERTIFIED AND ASME RATED T & P RELIEF VALVE.

3. CONNECT TO FACTORY PROVIDED DIRECT VENTING CONNECTION AT

THIS LOCATION.

4. 3" HIGH CONCRETE HOUSEKEEPING PAD W/ 3/4" CHAMFERED EDGES.

5. TERMINATE DRAIN 6" ABOVE FINISH FLOOR.

6. MAKE FINAL CONNECTION TO GAS SUPPLY TRAIN.

2½"

2½"

DC

W

GFWH2

(130º F DOMESTICHOT WATER)

STORAGE100 GALLON

STORAGE100 GALLON

6

1 3

GPR2

FULL SIZEDIRT LEG

3/4" NPTDRAIN CONN.

1½"CONN.

2

5

3

1½"1¼"

THERMOMETER(TYP.)

2½"

2½"

2½"

C

P6.1D

C

P6.1D

1¼"

4G

P6.1G

VACUUM RELIEF VALVE(BOTTOM FED WATER HEATER)

4"

VACUUM RELIEF VALVE(BOTTOM FED WATER HEATER)

CONCENTRIC VENTKIT TERMINATION(TYP.)

ROOF

4"

4"

4"4"

SW

1½"CONN.

FULL SIZEDIRT LEG

REDUCER

3" HIGH CONCRETEHOUSEKEEPING PAD (TYP.)REFER TO DETAIL F.

M

WATER METER

2" DCW

MDETAILICE MAKER CONNECTION N.T.S.

FDETAILMAINTENANCE/HOUSEKEEPING PAD N.T.S.

KDETAILTYPICAL PIPE HANGER N.T.S.

LDETAILFLOOR/WALL PENETRATION N.T.S.

ADETAILDOMESTIC HOT WATER GENERATION SYSTEM N.T.S.

HDETAILASSE 1070 CONNECTION (TYPICAL UNDER

SINK/LAVATORY WATER SUPPLY PIPING)

N.T.S.

DDETAILMEDICAL GAS VALVE CABINET

/ALARM MONITORING PANEL

N.T.S. ETYPICAL DETAILMEDICAL GAS OUTLETS

REFER TO P3 SERIES (PLUMBING) AND ARCHITECTURAL PLANS

N.T.S.

REFER TO SPEC. SECTION 22 63 00FOR FURTHER REQUIREMENTS FOR FURTHER REQUIREMENTS

NDETAILWATER SERVICES FOR IRRIGATION AND POND N.T.S.

CDETAILMEDICAL VACUUM PUMP, MVS1 N.T.S.REFER TO SPEC. SECTION 22 62 00FOR FURTHER REQUIREMENTS

BDETAILMEDICAL AIR SYSTEM, MAS1 N.T.S.

GDETAILEMERGENCY OXYGEN SUPPLY CONNECTION

REFER TO SPEC. SECTION 22 63 00

N.T.S.

PIPE

CLAMP

UNISTRUT

CHANNEL

HANGER

ROD

PIPE

INSULATION

PROVIDE A SECTION OF HIGH

COMPRESSION STRENGTH

INSULATION AT EACH HANGER

POINT. INSULATION MAY BE

HALF ROUND OR FULL ROUND

& EXTEND 2" BEYOND

GALVANIZED SHIELD EACH WAY.

GALVANIZED%%032CARBON

STEEL%%032SHIELD

PIPE

INSULATION

PRECOMPRESSED

FIBERGLASS

BLOCK

BLOCK

FIBERGLASS

PRECOMPRESSED

SUPPORT FROM STRUCTURE

LOOSE FIT 3/8"∅

U-BOLT

(TYPICAL)1/2"∅ HANGER ROD

NOTE:

EACH CHANNEL TO

BE INDEPENDENTLY

SUPPORTED FOR

MULTITIER

ARRANGEMENT.

PRECOMPRESSED

FIBERGLASS

BLOCK (TYPICAL)

PIPE (TYPICAL)U-BOLT (TYPICAL)

FROM MEDICALGAS (OXYGEN)MANIFOLD

1" DHWR(130°F)

¾"

PROJECT NUMBER:

CHECKED BY:

DESIGNED BY:

1650 WATERMARK DRIVE

COLUMBUS, OHIO 43215SUITE 200

DRAWN BY:

1 2 3 4 5

A

B

C

D

MKC JOB #:

SUBMITTED:

DEVELOPER / OFFEROR

THIS DRAWING SHALL NOT BE REPRODUCED, PUBLISHED, STORED IN AN ELECTRONIC RETRIEVAL SYSTEM, OR USED IN ANY WAY WITHOUT WRITTEN PERMISSION OF THE ARCHITECT. COPYRIGHT C 2015 MKC ASSOCIATES, INC

6

E

55 Monument Circle, Suite 450Indianapolis, Indiana 46204

GENERAL CONTRACTOR

Phone: 317-573-4600www.ambrosegp.com

9550 W. Higgins Road, Suite 200Rosemont, Illinois 60018

Phone: 847-292-4300Fax: 847-292-4312www.mcshaneconstruction.com

ENGINEERINGStructural, Mechanical, Electrical, Plumbing,Fire Protection

1650 Watermark Drive, Suite 200Columbus, Ohio 43215

Phone: 614-487-1650Fax: 614-487-8981www.korda.com

LANDSCAPE & SITE DESIGN

330 West Spring Street, Suite 350Columbus, Ohio 43215

Phone: 614-486-3343Fax: 614-486-3344www.edgela.com

CIVIL ENGINEERING

SFO: VA-101-12-I-0063

MISHAWAKA, INDIANA

VA ST. JOSEPHCOUNTY CBOC

PHYSICAL SECURITY / FORCE PROTECTION

2015-0211

100% CONSTRUCTION DOCUMENTS

C:\

Local R

evit\R

evit 2

016\1

6-5

0211 V

A S

outh

Bend P

LU

MB

ING

(YU

CH

EN

).rv

t

2/1

5/2

017 9

:47:3

4 A

M

JUNE 1, 2016

PLUMBING DETAILS

P6-2

15-089

Steve Glinsky

Bill Rezabek

W. P. Stafa

1 07-15-2016 Addendum 1

2 08-03-2016 Bulletin 1, Rev 2

4 09-09-2016 RFP 3, Steam VE

5 12-07-2016 Bulletin 3

6 02-15-2017 Bulletin 4