Download - 2.0MG Layton Water Tank
![Page 1: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/1.jpg)
Intermountain Section AWWA Conference
- 2.0MG Layton Water
Tank
Jake O’Brien
![Page 2: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/2.jpg)
Presentation Outline
Layton City’s decision process
Tank Design/Construction Tendon Tanks - don’t shed
the good stuff
![Page 3: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/3.jpg)
Layton City’s Decision
Schedule Quality Cost
![Page 4: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/4.jpg)
Competition
Schedule Quality Cost Construction Space Req’s
Tendon Tanks (D115)
vs.
Multiple slab pours Shotcrete is weather
dependent Specialized equipment
Single slab pours Not dependent on
weather Standardized equipment
Min. cover on primary reinforcement
Mildly reinforced slab Joints in slabs
Triple protection on primary reinforcement
Prestressed flexible slab Monolithic slabs Seismic conditions
Competitive Internal resources
Competitive Use local resources
15’ – 20’ for wrapping and shotcrete equip.
3’ outside of wall Adjacent to structures
![Page 5: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/5.jpg)
Design/Construction of a Tendon Prestressed Tank
![Page 6: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/6.jpg)
Effect of Applied Loads
![Page 7: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/7.jpg)
Effect of Prestressing
![Page 8: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/8.jpg)
Combined Effect During Service
![Page 9: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/9.jpg)
Prestressed Concrete Tank Wall
![Page 10: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/10.jpg)
Types of Post-Tensioning
![Page 11: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/11.jpg)
Unbonded System
Coated and sheathed strand
Sleeve
Permanent cap
Bearing plate Wedges
![Page 12: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/12.jpg)
Bonded Wall System
Anchor head Transition trumpet
Galvanized bearing plate
Duct and coupler
Permanent grout cap w/ stainless steel bolts
Grout injection port w/ shut-off valve
Strand and wedges
![Page 13: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/13.jpg)
Benefits of Post-Tensioning Reduction in reinforcement: P-T is 4.5x
capacity of rebar, 270 ksi / 60 ksi Thinner members (economy in materials,
labor, and schedule) Reduced congestion: simpler consolidation
of concrete, particularly wall placements Concrete stress control: specified minimum
pre-compressions, and tension limits Durability resulting from crack control Watertight structures Superior corrosion protection on primary
reinforcement (post-tensioning tendons)
![Page 14: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/14.jpg)
National Building Codes American Concrete Institute ACI 350-06 Code Requirements for Environmental Engineering
Concrete Structures and Commentary
American Water Works Association ANSI / AWWA D115-06 Tendon - Prestressed Concrete Water Tanks
American Concrete Institute ACI 373R-97 Design and Construction of Circular Prestressed Concrete
Structures with Circumferential Tendons (Report Recommendations)
![Page 15: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/15.jpg)
Base Slab
![Page 16: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/16.jpg)
Construction Sequence Base slab
1) Prepare subgrade 2) Install underslab
piping 3) Set edge
formwork 4) Place P-T and
rebar 5) Place concrete 6) Cure properly 7) Strip edge form 8) Stage stress P-T
![Page 17: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/17.jpg)
Construction Sequence
![Page 18: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/18.jpg)
Walls
![Page 19: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/19.jpg)
Walls
![Page 20: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/20.jpg)
Construction Sequence
Wall Segments 1) Set inner form 2) Install P-T and
rebar 3) Set outer form 4) Place concrete
![Page 21: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/21.jpg)
Construction Sequence
![Page 22: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/22.jpg)
Construction Sequence Footings and Columns Concurrent with wall construction
![Page 23: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/23.jpg)
Construction Sequence Wall Post-Tensioning
1) Insert horizontal strands 2) Stress verticals 3) Stress horizontals 4) Injection grout tendons
![Page 24: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/24.jpg)
Roof Slab
![Page 25: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/25.jpg)
Construction Sequence
Roof Slab 1) Set shoring and
deck 2) Install P-T and
rebar 3) Place concrete 4) Strip edge form 5) Stage stress P-T
![Page 26: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/26.jpg)
Tendon Tank Advantages 1. Durability
• Solid concrete sections • No joints in slab or roof • Controlled concrete
stresses • Bi-axial compression on all concrete members • Superior corrosion
protection on primary reinforcement
![Page 27: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/27.jpg)
Tendon Tank Advantages 2. Versatility
![Page 28: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/28.jpg)
Tendon Tank Advantages 3. Watertightness
![Page 29: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/29.jpg)
Watertightness AWWA D115 Criteria Walls and wall-floor joints 100% watertight
Floors, piping and valves Less than 0.0125% loss in 24 hours
“Many tanks have been constructed and found to have no measurable leakage when tested for watertightness”
![Page 30: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/30.jpg)
Tendon Tank Advantages 4. Economical
![Page 31: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/31.jpg)
Tendon Tank Advantages Reduce excavation costs No need for 10’-15’ access for wrapping and
shotcrete equipment
Larger capacity tanks on small sites Adjacent structures
![Page 32: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/32.jpg)
Tendon Tank Advantages No structural maintenance Coatings and liners not required No unplanned down time No joint maintenance
![Page 33: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/33.jpg)
Tendon Tank Advantages Includes local resources Subcontractors Mutiple skilled trades Labor services Material suppliers Equipment rentals Testing agencies Consultants Non-proprietary construction methods
![Page 34: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/34.jpg)
Tendon Tank Advantages Structural modifications Pre-construction (planned) Post-construction (unplanned) Avoid tendons or apply exterior
reinforcement (P-T or CFRP) Vertical wall tendon spacings 3x – 5x wall
thickness depending on base fixity Horizontal tendon normally spacings 1.5’ – 5.0’
depending on location up wall
![Page 35: 2.0MG Layton Water Tank](https://reader030.vdocument.in/reader030/viewer/2022012209/61deec3c1825ed48e01ab3b3/html5/thumbnails/35.jpg)
Questions?