Alcatel-Lucent 7360INTELLIGENT SERVICES ACCESS MANAGER | RELEASE 4.3S A F E T Y M A N U A L
3HH-10126-AAAA-TCZZA Edition 01 Released
Alcatel-Lucent ProprietaryThis document contains proprietary information of Alcatel-Lucent and is not to be disclosedor used except in accordance with applicable agreements.Copyright 2011 Alcatel-Lucent. All rights reserved.
-
When printed by Alcatel-Lucent, this document is printed on recycled paper.
Alcatel-Lucent assumes no responsibility for the accuracy of the information presented, which is subject to change without notice. Alcatel, Lucent and the Alcatel-Lucent logo are registered trademarks of Alcatel-Lucent. All other trademarks are the property of their respective owners.
Copyright 2011 Alcatel-Lucent.All rights reserved.
Disclaimers
Alcatel-Lucent products are intended for commercial uses. Without the appropriate network design engineering, they must not be sold, licensed or otherwise distributed for use in any hazardous environments requiring fail-safe performance, such as in the operation of nuclear facilities, aircraft navigation or communication systems, air traffic control, direct life-support machines, or weapons systems, in which the failure of products could lead directly to death, personal injury, or severe physical or environmental damage. The customer hereby agrees that the use, sale, license or other distribution of the products for any such application without the prior written consent of Alcatel-Lucent, shall be at the customer's sole risk. The customer hereby agrees to defend and hold Alcatel-Lucent harmless from any claims for loss, cost, damage, expense or liability that may arise out of or in connection with the use, sale, license or other distribution of the products in such applications.This document may contain information regarding the use and installation of non-Alcatel-Lucent products. Please note that this information is provided as a courtesy to assist you. While Alcatel-Lucent tries to ensure that this information accurately reflects information provided by the supplier, please refer to the materials provided with any non-Alcatel-Lucent product and contact the supplier for confirmation. Alcatel-Lucent assumes no responsibility or liability for incorrect or incomplete information provided about non-Alcatel-Lucent products.However, this does not constitute a representation or warranty. The warranties provided for Alcatel-Lucent products, if any, are set forth in contractual documentation entered into by Alcatel-Lucent and its customers.This document was originally written in English. If there is any conflict or inconsistency between the English version and any other version of a document, the English version shall prevail.
-
Alcatel-Lucent 7360 ISAM R4.3 July 2011 iii3HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Preface
This preface provides general information about the documentation set for the 7360 Intelligent Services Access Manager (7360 ISAM FX).
Scope
This documentation set provides information about safety, features and functionality, ordering, hardware installation and maintenance, CLI and TL1 commands, and software upgrade and migration procedures.
Audience
This documentation set is intended for planners, administrators, operators, and maintenance personnel involved in installing, upgrading, or maintaining the 7360 ISAM FX.
Required knowledge
The reader must be familiar with general telecommunications principles.
Acronyms and initialisms
The expansions and optional descriptions of most acronyms and initialisms appear in the glossary, which is included in the System Description document.
-
Preface
iv July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
Assistance and ordering phone numbers
Alcatel-Lucent provides global technical support through regional call centers. Phone numbers for the regional call centers are available at the following URL: http://www.alcatel-lucent.com/myaccess.
For ordering information, contact your Alcatel-Lucent sales representative.
Safety information
For safety information, see the Safety Manual for your product.
Documents
Refer to the 7360 ISAM Product Information document to see a list of all the relevant customer documents and their part numbers for the current release.
Customer documentation is available for download from the Alcatel-Lucent Support Service website at http://www.alcatel-lucent.com/myaccess.
Special information
The following are examples of how special information is presented in this document.
Release notes
Be sure to refer to the release notes (such as the Customer Release Notes or Emergency Fix Release Note) issued for software loads of your product before you install or use the product. The release notes provide important information about the software load.
Danger Danger indicates that the described activity or situation may result in serious personal injury or death; for example, high voltage or electric shock hazards.
Warning Warning indicates that the described activity or situation may, or will, cause equipment damage or serious performance problems.
Caution Caution indicates that the described activity or situation may, or will, cause service interruption.
Note A note provides information that is, or may be, of special interest.
-
Contents
Preface iiiScope ............................................................................................... iiiAudience ............................................................................................... iiiRequired knowledge................................................................................... iiiAcronyms and initialisms ............................................................................. iiiAssistance and ordering phone numbers ........................................................... ivSafety information..................................................................................... ivDocuments .............................................................................................. ivSpecial information.................................................................................... ivRelease notes........................................................................................... iv
1 Conventions 1-11.1 Introduction.............................................................................. 1-21.2 Safety Instructions in Customer Documentation ................................... 1-21.3 Safety Warning Labels .................................................................. 1-41.4 Waste from Electrical and Electronic Equipment (WEEE)......................... 1-5Alcatel-Lucent 7360 ISAM R4.3 July 2011 v3HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
2 Safety Guidelines for 7360 ISAM FX Equipment 2-12.1 Introduction.............................................................................. 2-22.2 Safety Requirements ................................................................... 2-22.3 Circuit Breakers and Fuses on Shelves for 7360 ISAM FX Equipment ............ 2-72.4 Fuses on Power Units and Fan Units................................................. 2-102.5 Environmental Requirements......................................................... 2-142.6 EMC/EMI ................................................................................. 2-152.7 Acoustic Noise .......................................................................... 2-152.8 ITU-T K.20/K.45 Compliance ......................................................... 2-152.9 Ecology................................................................................... 2-16
-
ContentsIndexvi July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
-
Alcatel-Lucent 7360 ISAM R4.3 July 2011 1-13HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
1 Conventions
1.1 Introduction 1-2
1.2 Safety Instructions in Customer Documentation 1-2
1.3 Safety Warning Labels 1-4
1.4 Waste from Electrical and Electronic Equipment (WEEE) 1-5
-
1 Conventions
1-2 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
1.1 Introduction
This chapter describes the types of safety instructions used in the Hardware Installation Manual and the Unit Data Sheets.
It gives important safety warning labels found on equipment.
1.2 Safety Instructions in Customer Documentation
Safety instructions are placed in customer documentation where the reader should be warned about dangerous or harmful situations or where he should be informed to ease the work.
Safety instructions can be:
Person-related or combined person-equipment related Equipment related Other
Note Familiarize yourself with the safety instructions, warning labels and their meaning before installing, operating or servicing 7360 FX ISAM equipment.
-
1 Conventions
Alcatel-Lucent 7360 ISAM R4.3 July 2011 1-33HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Person- or Combined Person-Equipment Related
Person-Equipment Related
Danger This instruction warns about an immediately threatening danger.
It calls attention to a situation or procedure which, if not correctly performed or adhered to, could result in death or serious physical harm.
In addition, it can warn about a possible equipment-damaging situation or give essential information for avoiding degradation of system operation.
Do not proceed beyond a danger warning note until the indicated conditions are fully understood and met.
Warning This instruction warns about a possibly dangerous situation.
It calls attention to a situation or procedure which, if not correctly performed or adhered to, could result in death or serious physical harm.In addition, it can warn about a possible equipment-damaging situation or give essential information for avoiding degradation of system operation.Do not proceed beyond a warning note until the indicated conditions are fully understood and met.
Caution This instruction warns about a possibly dangerous situation.
This warning calls attention to a situation or procedure which, if not correctly performed or adhered to, could result in slight injury.In addition, it can warn about a possible equipment-damaging situation or give essential information for avoiding degradation of system operation.
Do not proceed beyond a caution note until the indicated conditions are fully understood and met.
Note 1 This instruction warns about a possibly damaging situation!
It calls attention to a situation or procedure which, if not correctly performed or adhered to, could result in damage to equipment or to objects in the surrounding environment.Note 2 This instruction gives essential information to avoid degradation of system operation.
-
1 Conventions
1-4 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
OthersThese instructions do not warn about dangerous or harmful situations, but give information to ease the work.
1.3 Safety Warning Labels
Safety Warning Labels located on equipment call attention to a dangerous situation which, if safety instructions are not correctly performed, could result in bodily harm and/or damage equipment.
The following items of labels are mandatory in accordance with IEC60950-1 and IEC60825-1:
Hazardous voltage; see Figure 1-1 High temperature; see Figure 1-2 ESD awareness:
Devices and assemblies that are susceptible to ElectroStatic Discharge (ESD) are labelled or tagged with the ESD Awareness symbol; see Figure 1-3
Figure 1-1 Label for Hazardous Voltage Warning
Figure 1-2 Label for High Temperature Warning
Caution This Instruction refers to the documentationThe product is marked with this symbol when it is necessary for the user to refer to the instructions in the documentation.
Note InformationThis note provides information that makes work easier and other useful information.
-
1 Conventions
Alcatel-Lucent 7360 ISAM R4.3 July 2011 1-53HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Figure 1-3 ESD Awareness
1.4 Waste from Electrical and Electronic Equipment (WEEE)
The product at end of life is subject to separate collection and treatment in the EU Member States, Norway and Switzerland and therefore marked with the WEEE label.
Figure 1-4 WEEE Label
Treatment applied at end of life of the product in these countries shall comply with the applicable national laws on wastes from electrical and electronic equipment and more particularly those implementing the European directive 2002/96/EC (WEEE).In countries outside Europe and if not otherwise provided by any mandatory law in those countries where the product is sold, any take back by Alcatel-Lucent of waste electrical and electronic equipment shall be subject to terms and conditions to be agreed upon in writing. Any obligation of Alcatel-Lucent to take back such equipment shall apply only to complete not amended or modified equipment delivered by Alcatel-Lucent, i.e. containing all its components and sub-assemblies.
In case Alcatel-Lucent takes back electrical and electronic equipment, Alcatel-Lucent will ensure for the ecological safe and appropriate treatment in accordance with local regulations.
-
1 Conventions
1-6 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
-
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-13HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
2 Safety Guidelines for 7360 ISAM FX Equipment
2.1 Introduction 2-2
2.2 Safety Requirements 2-2
2.3 Circuit Breakers and Fuses on Shelves for 7360 ISAM FX Equipment 2-7
2.4 Fuses on Power Units and Fan Units 2-10
2.5 Environmental Requirements 2-14
2.6 EMC/EMI 2-15
2.7 Acoustic Noise 2-15
2.8 ITU-T K.20/K.45 Compliance 2-15
2.9 Ecology 2-16
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-2 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
2.1 Introduction
This chapter provides general safety guidelines for the:
7360 ISAM FX-16 equipment (16-slot shelf) 7360 ISAM FX-8 equipment (8-slot shelf) 7360 ISAM FX-4 equipment (4-slot shelf)
2.2 Safety Requirements
The 7360 ISAM FX equipment complies with the following safety requirements:
IEC 60950-1 EN 60950-1 AS/NZ 60950.1 Protection against electric shock: Class I
Danger Observe safety warnings and instructions
Observe all warnings on the equipment and in the operating instructions. These warn about potentially hazardous situations that could cause injury to persons. Failure to follow these instructions may also lead to equipment malfunction or damage.
Carefully follow:
General safety guidelines in the mandatory regulations Specific safety guidelines and instructions in the 7360 ISAM FX
Hardware installation manual document for procedures during which hazardous situations may occur.
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-33HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Access AreaThe 7360 ISAM FX shelves are classified as permanently connected equipment and must be installed in a Restricted Access Location (RAL). The inside of the equipment is classified as service access area in accordance with IEC 60950-1
External InterfacesThe interfaces of the 7360 ISAM FX shelves are classified as follows:
Table 2-1 External Interfaces
Warning Risk of hazardous voltages and electric shock by unintentional contact with circuit inside the shelf, when reaching into the empty card slots or contacting internal circuits.
Hazardous voltages or electric shock can cause serious personal harm or death
Only qualified service personnel have access to equipment and are allowed to perform installation, operational work or repair work.
Caution Prevention of access
The 7360 ISAM FX shelves must be accessible only by authorized personnel. Install the shelves in a restricted access location or similar environment to prevent unauthorized access.
Interface Classification
Optical GE XFP Class I Laser product
Optical GE SFP Class I Laser product
Optical FE SFP Class I Laser product
Optical SFP+ Class I Laser product
EPON SFP Class I Laser product
GPON SFP Class I Laser product
Electrical GE Safety Extra Low Voltage (SELV) circuit
Electrical FE SELV circuit
BITS SELV circuit
Craft Terminal SELV circuit(for configuration purposes by personnel only)
CO Alarm TNV-2 circuit
External Power Lines TNV-2 circuit, when using 60 VDC batterySELV circuit, when using 48 VDC battery
Alarm/Service Power Lines TNV-2 circuit, when using 60 VDC batterySELV circuit, when using 48 VDC battery
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-4 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
SELV
Connect SELV circuits on this equipment only to other circuits that comply with the requirements of the SELV circuits as defined in IEC 60950-1, EN 60950-1 and AS/NZ 60950.1.
TNV
TNV can be classified as TNV1, TNV2 or TNV3.
TNV1 circuits are telecommunications circuits whose voltages during normal operation do not exceed SELV limits but are subjected to off-premises overvoltages.
TNV2 circuits are telecommunications circuits whose voltages under normal operation exceed the SELV limits but are not subject to off-premises overvoltages. TNV2 also classifies dc mains suppliers whose voltages during normal operation exceed 60V but do not exceed 80V.
TNV3 circuits are telecommunications circuits with voltages above SELV limits that are also subject to off-premises overvoltages.
Connect TNV circuits on this equipment only to other circuits that comply with the requirements of the TNV circuits as defined in IEC 60950-1, EN 60950-1 and AS/NZ 60950.1.
Equipment Bonding and GroundingThe 7360 ISAM FX equipment is classified as Class 1 laser product according to their protection against electric shock. Protection against electric shock is achieved by:
Using basic insulation Providing means of connection to the protective earth in the building for those
conductive parts that are otherwise capable of assuming hazardous voltages if the basic insulation fails.
The 7360 ISAM FX shelves comply with the following product power and grounding standards:
ETS 300 253, Earthing and bonding of telecommunication equipment in telecommunication centers
ETS 300 132-2, Power supply interface at the input to telecommunication equipment: Part 2 Operated by direct DC current.
7360 ISAM FX equipment is classified as Class 1 Laser Products.
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-53HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Classification of Laser and LED Transmitter Modules
Normal Laser Operation
The optical fibre communication systems used in the 7360 ISAM FX shelves consist of a laser transmitter module and an optical receiver. Optical connectors have been provided at:
the front panel of the NT boards the front panel of the NTIO boards
These optical connectors are located behind doors.
In normal operation, the laser transmitter is enclosed by the optical connector and the external optical fibre. Laser radiation is always present when the laser unit is powered on, limited to a maximum accessible emission limit of Class 1 according to IEC 60825-1.
Laser Transmitter Classification
The 7360 ISAM FX equipment is classified as Class 1 laser product according to IEC 60825-1.
LED Classification
According to the current version of IEC60825-1, LEDS do not exceed the accessible emission limit of Class 1 under all conditions of operation, maintenance, service and failure.
Optical Fiber Communication System Installation Access
According to IEC 60825-2, the laser device, when used in a 7360 ISAM FX shelf that is installed in a rack, is classified as a "hazard level 1" product.
The fibre cables pass through the bottom or top rack entrance. The use of cable supports and guides protects the receptacles from strain.
The 7360 ISAM FX shelves are located in controlled access locations only (telecom areas) which implies that activity inside the equipment must be executed by trained maintenance personnel only.
Warning 1 Risk of skin burns when in contact with hot parts!Skin (fingers) can get burns when touching the case of hot devices.The surface temperature must not exceed 70C.Warning 2 Risk of eye damage by laser radiationEyes can get damaged when they are exposed to a laser beam.
Observe the laser explanatory label, before plugging in the module.
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-6 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
Direct viewing in the laser beam is only possible with a disconnected fibre in an open rack.
Equipment Protection
Electrostatic Discharge
Devices and assemblies that are susceptible to ESD are labeled or tagged with the ESD awareness symbol (Figure 2-1).
Figure 2-1 ESD Awareness Label
The necessary precautions must be taken to discharge operating personnel by the use of approved discharge straps/links and a conductive layer on the exchange floor. The maximum resistance to discharge must be 106 .
Precautions
The following precautions must be observed:
Wear an antistatic wristband when: Replacing plug-in units Operating circuit breakers The ESD awareness label (Figure 2-1) is present;
Do not wear or use clothes made of wool, nylon, or any synthetic material; such fabrics are major sources of static build-up
When handling plug-in units, do not use gloves and finger covers, unless they are made of cotton
Always handle the boards by the edges Do not touch conductor paths with fingers or palms Remove the antistatic wristband and connection cord after use. They must not be
left connected to the shelf or left inside the rack when not used.
Earth bonding points for the wristband are provided on the shelf or in the rack and are indicated by the label as shown in Figure 2-2.
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-73HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Figure 2-2 Label for Earth Bonding Point
2.3 Circuit Breakers and Fuses on Shelves for 7360 ISAM FX Equipment
This section gives an overview of the power rating of circuit breakers, switches and fuses located on:
Circuit Breakers on 7360 ISAM FX-16 equipment Circuit Breakers on 7360 ISAM FX-8 equipment Fuses on 7360 ISAM FX-4 equipment
General Warning
Warning Electrical shock hazard due to battery voltage present at connectors.
Risk of personnel injury at unintentional contact with connectors.The service personnel has to be protected against the battery voltage present on the connectors.
Before removing a board from the subrack, switch off the circuit breaker feeding that subrack.
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-8 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
Circuit Breakers on 7360 ISAM FX-16 equipmentThe circuit breakers of the 7360 ISAM FX-16 shelves are located on the front panel of the power unit of the shelf. The equipment contains two circuit breakers, one for each redundant power branch (BATA and BATB).Figure 2-3 shows the location of the fuses on the FX-16 shelf.
Figure 2-3 Fuses on FX-16 Slot Shelf
Table 2-2 Circuit Breakers on 8 & 16 Slot Shelf
Circuit Breakers on 7360 ISAM FX-8 equipmentThe circuit breakers of the 7360 ISAM FX-8 shelves are located on the front panel of the power unit of the shelf. The equipment contains two circuit breakers, one for each redundant power branch (BATA and BATB).Figure 2-4 shows the location of the fuses on the FX-8 shelf.
Figure 2-4 Fuses on FX-8 Slot Shelf
Table 2-3 Circuit Breakers on 8-Slot Shelf
Equipment Type Circuit Breaker Type
7360 ISAM FX-16 (NFXS-D) 70 A (dual pole 2 x 35 A)
Circuit breakers
Equipment Type Circuit Breaker Type
7360 ISAM FX-8 (NFXS-E) 40 A (single pole)
B/40 A
A/40 A
Circuit breaker
Circuit breaker
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-93HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Fuses on 7360 ISAM FX-4 equipmentThe fuses of the 7360 ISAM FX-4 shelves are located on front panel of the power unit of the shelf. The equipment contains six fuses, three for each redundant power branch (BATA and BATB).Figure 2-5 shows the location of the fuses on an FX-4 slot shelf.
Figure 2-5 Fuses on FX-4 Slot Shelf
Table 2-4 Fuses on 4-Slot Shelf
Equipment Type Fuse Type
7360 ISAM FX-4 (NFXS-F) 10 A (cartridge 5x20mm slow blow, T10AH/250V)
Fuses
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-10 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
2.4 Fuses on Power Units and Fan Units
This section gives an overview of the fuses used on the power units and the fan units of the 7360 ISAM FX-16, FX-8 and and FX-4 shelves.
Fuses on 7360 ISAM FX-16 Power Unit Fuses on 7360 ISAM FX-8 Power Unit Fuses on 7360 ISAM FX-4 Power Unit Fuses on 7360 ISAM FX-16 Fan Unit (EFCU-E) Fuses on 7360 ISAM FX-8 Fan Unit (EFCU-D) Fuses on 7360 ISAM FX-4 Fan Unit (EFCU-G)
Fuses on 7360 ISAM FX-16 Power UnitTable 2-5 lists the fuses on the power unit (PDBP-B) of the 7360 ISAM FX-16 subrack.
Table 2-5 Fuses on NFXS-D
Fuses on 7360 ISAM FX-8 Power UnitTable 2-6 lists the fuses located on the power board NGFC-E of the 7360 FX-8 subrack.
Fuse Number Fuse Rating Fuse Type
F1 125V/10A Quick / SMD
F2 125V/10A Quick / SMD
F3 125V/10A Quick / SMD
F4 125V/10A Quick / SMD
F5 125V/10A Quick / SMD
F6 125V/10A Quick / SMD
F7 125V/10A Quick / SMD
R85 72V/900mA Radial PTC / leaded
R86 72V/900mA Radial PTC / leaded
R87 72V/900mA Radial PTC / leaded
R88 72V/900mA Radial PTC / leaded
R89 72V/900mA Radial PTC / leaded
R252 72V/1,6A Radial PTC / leaded
R253 72V/1,6A Radial PTC / leaded
R254 72V/1,6A Radial PTC / leaded
R445 72V/900mA Radial PTC / leaded
R459 72V/900mA Radial PTC / leaded
R460 72V/900mA Radial PTC / leaded
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-113HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Table 2-6 Fuses on NGFC-E
Fuses on 7360 ISAM FX-4 Power UnitTable 2-7 lists the fuses located on the power board NGFC-F of the 7360 FX-4 subrack.
Table 2-7 Fuses on NGFC-F
Fuse Number Fuse Rating Fuse Type
F1 125 V / 10 A Quick / SMD
F2 125 V / 10 A Quick / SMD
F3 125 V / 10 A Quick / SMD
F4 125 V / 10 A Quick / SMD
F5 125 V / 10 A Quick / SMD
R85 72 V / 900 mA Radial PTC / leaded
R86 72 V / 900 mA Radial PTC / leaded
R88 72 V / 900 mA Radial PTC / leaded
R89 72 V / 900 mA Radial PTC / leaded
R252 72V/1,6A Radial PTC / leaded
R253 72V/1,6A Radial PTC / leaded
R254 72V/1,6A Radial PTC / leaded
R304 72V/900mA Radial PTC / leaded
R305 72V/900mA Radial PTC / leaded
R306 72V/900mA Radial PTC / leaded
Fuse Number Fuse Rating Fuse Type
F1 125 V / 10 A Quick / SMD
F2 125 V / 10 A Quick / SMD
F3 125 V / 10 A Quick / SMD
F4 125 V / 10 A Quick / SMD
F5 125 V / 10 A Quick / SMD
R85 72 V / 900 mA Radial PTC / leaded
R86 72 V / 900 mA Radial PTC / leaded
R87 72 V / 900 mA Radial PTC / leaded
R88 72 V / 900 mA Radial PTC / leaded
R89 72 V / 900 mA Radial PTC / leaded
R252 72V/1,6A Radial PTC / leaded
R253 72V/1,6A Radial PTC / leaded
(1 of 2)
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-12 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
Fuses on 7360 ISAM FX-16 Fan Unit (EFCU-E)Table 2-8 lists the fuses on the 7360 ISAM FX-16 fan unit.
Table 2-8 Fuses on 7360 ISAM FX-16 Fan Unit
Fuses on 7360 ISAM FX-8 Fan Unit (EFCU-D)Table 2-9 lists the fuses on the 7360 ISAM FX-8 fan unit.
Table 2-9 Fuses on 7360 ISAM FX-8 Fan Unit
R254 72V/1,6A Radial PTC / leaded
R413 72V/900mA Radial PTC / leaded
R414 72V/900mA Radial PTC / leaded
R415 72V/900mA Radial PTC / leaded
R416 72V/900mA Radial PTC / leaded
R461 72V/900mA Radial PTC / leaded
R462 72V/900mA Radial PTC / leaded
Fuse Number Fuse Rating Fuse Type
(2 of 2)
Fuse Number Fyse Rating Fuse Type
F1 125V/2,5A Slow / SMD
F2 125V/2,5A Slow / SMD
F3 125V/1,5A Quick / SMD
F4 125V/1,5A Quick / SMD
F5 125V/1,5A Quick / SMD
F6 125V/1,5A Quick / SMD
F7 125V/1,5A Quick / SMD
F8 125V/1,5A Quick / SMD
F9 125V/1,5A Quick / SMD
F10 125V/1,5A Quick / SMD
Fuse Number Fyse Rating Fuse Type
F1 125V/1,5A Slow / SMD
F2 125V/1,5A Slow / SMD
F3 125V/1,5A Slow / SMD
F5 125V/1,5A Slow / SMD
F6 125V/1,5A Slow / SMD
(1 of 2)
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-133HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Fuses on 7360 ISAM FX-4 Fan Unit (EFCU-G)Table 2-10 lists the fuses on the 7360 ISAM FX-4 fan unit.
Table 2-10 Fuses on 7360 ISAM FX-4 Fan Unit
Fuses on Plug-in Units
Table 2-11 gives an overview of the fuse rating of the various plug-in units (with number, rating and type) applied in the 7360 FX subracks.
Table 2-11 Fuse Rating of Plug-in Units applied in FX subracks
F7 125V/1,5A Slow / SMD
F9 125V/2,5A Slow / SMD
F10 125V/2,5A Slow / SMD
Fuse Number Fyse Rating Fuse Type
(2 of 2)
Fuse Number Fuse Rating Fuse Type
F1 125V/1,5A Quick / SMD
F2 125V/1,5A Quick / SMD
F3 125V/1,5A Quick / SMD
F4 125V/1,5A Quick / SMD
F5 125V/1,5A Quick / SMD
Warning Risk of malfunctioning due to replacement with wrong fuse.Applying fuses on plug-in units with ratings different from the prescribed could result in damage to the equipment.
Always replace with fuses which have the prescribed rating.
Mnemonic Board Code Fuse Number Fuse Rating Fuse Type
FANT-F 3FE 53699 XX F1 125V/6.3A Quick / SMD
F3 125V/0.5A Quick / SMD
F4 125V/0.5A Quick / SMD
F5 125V/6.3A Quick / SMD
FNIO-B 3FE 54057 AA F1 125V/3.15 Fuse, quick
F2 125V/0.5A Fuse, quick
(1 of 2)
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-14 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
2.5 Environmental Requirements
The 7360 ISAM FX equipment meets the environmental criteria defined by ETS 300 019-1-X: Equipment Engineering (EE): Environmental conditions and environmental tests for telecommunication equipment.
The 7360 ISAM FX equipment complies with the following classes:
StorageStorage is according to ETSI EN 300 019-1-1, Class 1.1:
Weather protected, partly temperature controlled storage locations.
TransportationTransport according to ETSI EN 300 019-1-2 - Class 2.3:
Packed, public transportation. No rain on packing allowed.
Stationary UseStationary use of the 7360 ISAM FX equipment is in accordance with ETS 300 019-1-3 Class 3.1E for multi-shelf configurations:
Stationary use in temperature controlled locations.
Stationary use of the 7360 ISAM FX equipment according ETS 300 019-1-3 Class 3.3* for single-shelf configurations.
Stationary use in not temperature-controlled locations No condensation allowed No conditions of wind-driven rain, snow, hail, water from other sources than rain
allowed.
NELT-B 3FE 62543 AA F1 125 V / 500 mA Fuse, quick
F1P0 125 V / 3.15 A Fuse, quick
NGLT-A 3FE 64279 AA F3 125 V / 5 A Fuse, quick
FPLT-A 3FE 53711 AA F1 125 V / 4 A Fuse, quick
F2 125 V / 500 mA Fuse, quick
F3 125 V / 500 mA Fuse, quick
Mnemonic Board Code Fuse Number Fuse Rating Fuse Type
(2 of 2)
-
2 Safety Guidelines for 7360 ISAM FX Equipment
Alcatel-Lucent 7360 ISAM R4.3 July 2011 2-153HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
2.6 EMC/EMI
The 7360 ISAM FX equipment complies with the following Electromagnetic Compatibility (EMC) and Electromagnetic Immunity (EMI) specifications: ETSI EN 300 382-2 telecommunication centre installation environment ETSI EN 300 386-2 telecommunication centre installation environment ETSI EN 201 468 for telecommunication centres, level 2 EN 61000-4-2 ESD EN 61000-4-3 Radiated immunity EN 61000-4-4 EFT EN 61000-4-5 Surge EN 61000-4-6 Low Frequency common immunity EN 55022, CISPR22, AS/NZS 3548, CLASS B EN 50082-1 and EN 50082-2 (ESD, RF Immunity, EFT etc. - Industrial &
Commercial). CE compliance marking (safety and EMC for Europe)The 7360 ISAM FX equipment complies with and has been CE-marked in accordance with the following European directives:
99/05/EC (R&TTE) 73/23/EEC (LVD as amended by directive 93/68) 89/336 (EMC as amended by directive 93/68)
2.7 Acoustic Noise
The 7360 ISAM FX equipment meets the acoustic noise requirements defined by ETS 300 753: Equipment Engineering (EE); Acoustic noise emitted by telecommunications equipment, category: telecommunication equipment room.
2.8 ITU-T K.20/K.45 Compliance
The 7360 ISAM FX equipment is compliant with the following specifications:
ITU-T K.20 and ITU-T K.45 specifications for the full unit. In CO deployment, the equipment complies with the enhanced test levels as
specified in the ITU-T K.20 recommendation when external 420V primary Gas Discharge Tube (GDT) protectors are used on the external LINE interface.
In remote deployment, the equipment complies with the basic test levels for permanently grounded systems as specified in the ITU-T K.45 recommendation when used in combination with 420V primary protection GDTs on both the POTS and the LINE interface sides.
-
2 Safety Guidelines for 7360 ISAM FX Equipment
2-16 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
2.9 Ecology
The 7360 ISAM FX equipment complies to:
Restriction on the use of Hazardous Substances (RoHS) Directive 2002/95/EC Waste from Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC
-
Alcatel-Lucent 7360 ISAM R4.3 July 2011 IN-13HH-10126-AAAA-TCZZA Edition 01 Released Safety Manual
Index
F
FusesPlug-in units, 2-13
R
requirementsacoustic noise, 2-15EMC/EMI, 2-15environmental, 2-14safety, 2-2
S
safetyinstructions, 1-2requirements, 2-2warning labels, 1-4
W
WEEE, 1-5
-
Index
IN-2 July 2011 Alcatel-Lucent 7360 ISAM R4.3Safety Manual Edition 01 Released 3HH-10126-AAAA-TCZZA
-
Customer documentation and product support
Customer documentationhttp://www.alcatel-lucent.com/myaccessProduct manuals and documentation updates are available at alcatel-lucent.com. If you are a new user and require access to this service, please contact your Alcatel-Lucent sales representative.
Technical Supporthttp://www.alcatel-lucent.com/support
Documentation [email protected]
-
2011 Alcatel-Lucent. All rights reserved.3HH-10126-AAAA-TCZZA Edition 01 Released
Safety ManualPrefaceScopeAudienceRequired knowledgeAcronyms and initialismsAssistance and ordering phone numbersSafety informationDocumentsSpecial informationRelease notes
Contents1 - Conventions1.1 Introduction1.2 Safety Instructions in Customer Documentation1.3 Safety Warning Labels1.4 Waste from Electrical and Electronic Equipment (WEEE)
2 - Safety Guidelines for 7360 ISAM FX Equipment2.1 Introduction2.2 Safety Requirements2.3 Circuit Breakers and Fuses on Shelves for 7360 ISAM FX Equipment2.4 Fuses on Power Units and Fan Units2.5 Environmental Requirements2.6 EMC/EMI2.7 Acoustic Noise2.8 ITU-T K.20/K.45 Compliance2.9 Ecology
IndexFRSW