Product Benefits• CPDapprovedtoEN54-2&4• Simpletoinstall• RobustfireresistantABSmouldedenclosure• Batteryspaceforupto72hourstand-by• 2,4or8zoneversionsavailable

Advanced Features• Zonesconfigurablefordelay,coincidence,short-circuit

alarm,capacitororresistiveendofline.• Fireandfaultoutputs-volt-freerelayormonitored• Auxiliarypoweroutputforancillaryequipment• 2configurableinputsforancillaryequipment(e.g.class

change,alert,etc.)• Spacefortwooptionmodules

• Optional8-wayrelaymodule,commonorzonalswitching

• Optional1.5A4-waysoundermodule,commonorzonalswitching

Developedwithefficiencyinmind,NFS2-8zonenon-addressablefirealarmpanelsofferbothinstallersandendusersatechnicallyadvancedrangeoffunctionswhileremainingeasytoinstall,programandoperate.Afullrangeofnon-addressabledetectors,advancednon-addressabledetectors,beamdetectors,manualcallpoints,ductmountingapplications,audibleandvisibledevicesareavailableforusewiththepanels.

NFS2-8seriesfirealarmpanelsareideallysuitedforfacilitiesincludingoffices,shopunits,publichouses,B&B,clubs,smallindustrialunits,nursinghomesandschools,offeringawiderangeofbenefitstoinstallersandend-users.

InstallationNFS2-8firealarmpanelsaredesignedtosimplifyinstallation.Theenclosureconsistsofatwopartarrangementoffrontcoverandbackbox.Thebackboxcontainsacentraltopkeyholefixingwithtwoadditionalfixingpointsthatareangledtofacilitatefinalalignment.

Eighteenknockoutsinthetopofthebackboxprovideamplecableentrypointsandaresuitableforbothstandardandenhancedcables.

Allcableconnectionsareconvenientlylocatedalongthetopedgeofthecontrolandpowersupplyunit(PSU)modules.Screwterminalsareprovidedandallowforcablecoresuptoandincluding2.5mm2C.S.A.

Spaceisprovidedwithintheboxfortwooptionmodules.

NFS2-8 Non Addressable Fire Alarm Data Sheet

Thisdocumentisnotintendedtobeusedforinstallationpurposes.Everycarehasbeentakeninthepreparationofthisdocumentbutnoliabilitycanbeacceptedfortheuseoftheinformationtherein.Designfeaturesmaybechangedoramendedwithoutpriornotice.Formoreinformation,contact:NotifierbyHoneywell,CharlesAvenue,BurgessHill,WestSussex,RH159UF.UnitedKingdomPhone:+44(0)1162462255Fax:+44(0)1162462210

ISO9001Design,ManufactureandSupplytoQualityManage-mentSystemsCertifiedto

ISO9001:1994

Page1of2-990-086ISSUE5_1209

Page 2: 603 Notifire Honeywell

SpecificationsDimensions• 356mm(w)x318mm(h)x96mm(d)• Weight2kg(withoutbatteries)

Electrical• Supplyrating:230V~(ac)±15%,50/60Hz,1.6A• Auxiliaryoutputvoltage:18.0-28.5Vdc• Auxiliaryoutputcurrent:0.5Amaximum• Soundercircuit:0.5Amaximumpercircuit• Soundercircuittotal:1.0Amaximum• Optionalsoundermodulemaybeusedwithanexternal

powersupplytogiveanadditional1.5Apermodule

Environmental Limits • Operatingtemperature:-5°Cto+45°C• 5%to95%,non-condensingrelativehumidity• IPrating:IP30

Ordering Information

Part Number Description002-490-129 Twozonenon-addressablefirealarmpanel,completewithfire/faultrelayand

capacitorendofline.002-490-149 Fourzonenon-addressablefirealarmpanel,completewithfire/faultrelayand

capacitorendofline.002-490-189 Eightzonenon-addressablefirealarmpanel,completewithfire/faultrelayand

capacitorendofline.020-772 4waysoundercard.

Adds4configurablesounders.1Apercircuit.Maximumtotalload-1.5A020-747 8Wayrelaycard.

Adds8configurablerelays.Thesecanbeconfiguredasinputsoroutputs.020-745-008 Spareinstallationkit.

Includes8capacitiveendoflines,batteryleads,Allenkey,panelcontrolskeyandsounderendoflineresistors.

020-710-001 Sparetextinserts020-743 CapacitorkitfordetectorsnotcompatiblewithcapacitiveEOLmonitoring.

Includes8x10μƒcapacitors.ActiveEOL’srequired-Seepartnumber020-417.Activeendoflinemonitormodule.

020-417 Activeendoflinemodule.Usewithdiodebasestomonitordetectorremovalwhilemaintainingzoneoperation.

Charles AvenueBurgess HillW. SussexRH15 9UF