ASHRAE Chapter MeetingASHRAE Chapter Meeting
HVAC Noise & Vibration ControlHVAC Noise & Vibration Control
Specifications & Best PracticesSpecifications & Best Practices
Presented By
Noise & Vibration Control, Inc.
610-863-6300
www.brd-nonoise.com
![Page 2: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/2.jpg)
2
☺ Brief Intro to Acoustics
☺ Specification Best Practice
☺ Treatment Best Practices
TopicsTopics
![Page 3: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/3.jpg)
3
Why Acoustics Matter!Why Acoustics Matter!
![Page 4: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/4.jpg)
4
Important Acoustic Terminology
• Loudness vs. Pitch
• Decibels: Sound Power vs. Sound
Pressure
• Decibel Weighting Networks
• Tonal Content
![Page 5: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/5.jpg)
5
A 1K Hz tone at 60 dB would require a
102 dB tone at 20 Hz to sound as loud to
the human ear.
![Page 6: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/6.jpg)
6
Common Municipal Code defines tone as:
“any sound which can be distinctly heard as a single pitch or set of single pitches…. and shall exist
of the one-third octave band sound pressure level in the band when the tone exceeds the arithmetic
average of the sound levels of the two contiguous one-third octave bands by five dB for frequencies
of 500 Hz and above, eight dB for frequencies between 160-400 Hz, and by 15 dB for frequencies
less than or equal to 125 Hz.”
Tonal Noise
![Page 7: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/7.jpg)
7
PWL vs. SPL Sound Power vs. Sound Pressure
Cause vs. Effect
![Page 8: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/8.jpg)
8
![Page 9: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/9.jpg)
9
What is the overall dBA level?
Octave Center Unweighted A-weighting A-weighted Overall
Band Frequency Sound factor (dB) Sound Resultant
Pressure (dB) Pressure (dBA) Level
1 63 94 -26 68
2 125 86 -16 70
3 250 85 -9 76
4 500 89 -3 86 91 dBA
5 1,000 89 0 89
6 2,000 77 1 78
7 4,000 75 1 76
8 8,000 76 0 76
86
89
Decibel
Addition
72
86
89
79
![Page 10: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/10.jpg)
10
(Sound Levels 270 ton Air Cooled Chiller)
-37-37-37-37-37-37-37-37-37Loss100’
1008185929497999890Lw
634448555760626153Lp
A8K4K2K1K50025012563Freq (Hz)
1. Where are we now?
2. Where do we need to be?
![Page 11: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/11.jpg)
11
13182022171410----Needed
Attenuation
502628334046526167Ordinance
634448555760626153Chiller
A8K4K2K1K50025012563Freq (Hz)
3. How much noise reduction is required?
4. What needs to be done to achieve compliance?
![Page 12: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/12.jpg)
12
☺ Common Specification
Strategies
☺ Specifications Types
☺ Specification Best
Practices
Sub TopicsSub Topics
![Page 13: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/13.jpg)
13
A Specification Should Provide
“Just the Right Prescription”
• Accountability
• Cost Control
• Predictable Performance
• Review of subjective and objective noise
criteria
![Page 14: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/14.jpg)
14
Common Specification Common Specification
StrategiesStrategies
![Page 15: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/15.jpg)
15
Common Spec Strategies on Noise
Sensitive Projects• Specify sound data for lowest rated model as
equipment basis of design
• Specify all available OEM equipment low noise options
• Specify an equipment model that is not tonal
• Specify the same treatment used on the last noise sensitive project
• Retain an acoustical consultant to write the specification
• Specify base equipment and address any
noise problems at start-up
![Page 16: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/16.jpg)
16
Published Sound Power Data
(No OEM Sound Kit Options)
Overall
A-Wtd
63 125 250 500 1000 2000 4000 8000 (dBA)
1 97 94 92 97 90 88 84 82 97
2 102 103 99 99 98 94 87 84 102
3 67 70 79 83 89 91 88 80 95
4 93 99 97 100 97 91 88 80 105
Sound Power Levels (dB)
Octave Band Center Frequency (Hz) 4 Different
Manufacturers &
Chiller Models
(Screw and Scroll
Designs)
Published Sound Pressure Data at 30’ Away
(No OEM Sound Kit Options)Overall
A-Wtd
63 125 250 500 1000 2000 4000 8000 (dBA)
1 70 67 65 70 63 61 57 55 70
2 75 76 72 72 71 67 60 57 75
3 40 43 52 56 62 64 61 53 68
4 66 72 70 73 70 64 61 53 74
Octave Band Center Frequency (Hz)
Sound Pressure Levels 5 (dB) @ 30'
4 Different Chiller
Manufacturers &
Models (Screw and
Scroll Designs)
Common Specification Strategies:
� Specify sound data for lowest rated model as equipment basis of design
![Page 17: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/17.jpg)
17
Sound Pressure Data for property line 80’ away
(No OEM Sound Kit Options)Overall
A-Wtd
63 125 250 500 1000 2000 4000 8000 (dBA)
1 61 58 56 61 54 52 48 46 61
2 66 67 63 63 62 58 51 48 66
3 31 34 43 47 53 55 52 44 60
4 57 63 61 64 61 55 52 44 66
Sound Pressure Levels 5 (dB) @ 80'
Octave Band Center Frequency (Hz) 4 Different Chiller
Manufacturers &
Models (Screw
and Scroll
Designs)
Sound Pressure Data for property line 80’ away
(with factory OEM options)Overall
A-Wtd
63 125 250 500 1000 2000 4000 8000 (dBA)
63 57 57 59 54 48 44 42 60
52 60 61 59 56 54 46 41 62
31 33 43 46 49 51 48 42 56
57 63 61 61 60 55 52 42 64
Sound Pressure Levels 5 (dB) @ 80'
Octave Band Center Frequency (Hz)
4 Different Chiller
Manufacturers & Models
(Screw and Scroll
Designs)
None of the chillers will comply with typical nighttime
noise ordinance values of 50 to 55 dBA.
Common Specification Strategies:
� Specify sound data for lowest rated model as equipment basis of design
� Specify all available OEM equipment low noise options
![Page 18: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/18.jpg)
18
Scroll Chiller Sound
Pressure Levels
Z C A 12
16
20
25
32
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1k
1k25
1k6
2k
2k5
3k15
4k
5k
6k3
8k
10k
12k5
16k
20k Hz
30
40
50
60
70
80
90
100dB
Screw Chiller Sound
Pressure Levels
Common Specification Strategies:
� Specify an equipment model that is not tonal
![Page 19: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/19.jpg)
19
☺ Performance
☺ Design
☺ Allowance
Specification TypesSpecification Types
![Page 20: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/20.jpg)
20
Performance Specifications
• Typical performance descriptors– Sound Power and/or Sound Pressure
– Octave band and/or overall dB and/or dBA levels
– NC or RC levels
• Relies on the acoustical credibility of the equipment manufacturer
– May or may not have the capabilities needed
– Commonly will take an exception
• Spec is difficult to enforce– AHRI 370, AHRI 575, AHRI 260, etc...
• Spec is often not based on project target levels at receiver positions
• Performance spec may or may not address equipment integration issues (operating performance, maintenance, etc…)
![Page 21: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/21.jpg)
21
Performance Specification Example
![Page 22: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/22.jpg)
22
Performance Specification Example
![Page 23: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/23.jpg)
23
Contradictory Performance Specification
Sound attenuation solution quiet
![Page 24: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/24.jpg)
24
Contradictory Performance Specification
![Page 25: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/25.jpg)
25
Design Specifications = “Just Right Prescription”
• Evaluates noise sensitive location(s) to provide
– Predictable Performance
– Accountability
– Cost Control
• Right amount of attenuation
• Accounted for in the budget
• Describes, provides performance, and/or
illustrates (schematic details) the materials and
products needed
![Page 26: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/26.jpg)
26
Design Specification
Schematic Design
Detail
ABC model JJJ
![Page 27: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/27.jpg)
27
Schematic
Design Detail
Design
Specification
ABC solution/model
![Page 28: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/28.jpg)
28
“Loose” Design Specification
ABC . . . . . . . . . . . . . . .
Result of a “Loose/Generic” spec
What is criteria for approving or rejecting?
![Page 29: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/29.jpg)
29
“Better” Design Specification
ABC model and manufactured by ABC company or equivalent.
![Page 30: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/30.jpg)
30
“Detailed” Design Specification
![Page 31: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/31.jpg)
31
“Best” Design Specification
Attenuation
![Page 32: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/32.jpg)
32
“Best” Design Specification Cont’d
![Page 33: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/33.jpg)
33
Allowance Specifications
• Equivalent advantages of pre-purchased equipment
– Provides the right material that is wanted on the project
• Assures needed design will be built
• Levels the playing field for bidders
![Page 34: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/34.jpg)
34
Allowance Specification
ABC Acoustic Attenuation DEF Company.
![Page 35: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/35.jpg)
35
Specification Best Specification Best
PracticesPractices
![Page 36: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/36.jpg)
36
Best Practices
Acoustic Design
• Answer 4 design questions
1. Where are we now?
2. Where do we need to be?
3. What needs to be done to get there?
4. How much will that cost?
• Use 3-5 dBA safety factor
• Cursory review on every project, in depth review when
warranted
• Assess site ambient noise levels
• Evaluate airborne and structure-borne transmission
• System problems require system solutions
![Page 37: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/37.jpg)
37
Best Practices
Specifications
• Job specific combined design/performance specs
preferred over generic performance specs
• Evaluate project specific objective and subjective criteria
– Indoor criteria: NC, RC, NCB, RC Mark II
– Outdoor criteria: Zoning and ordinance criteria
• Place in Division 15/23 with equipment
• Specify single source for system acoustic performance
• Specify turnkey where installation critical
• Require submission for approval as “or
equal” 10 days before bid date
![Page 38: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/38.jpg)
38
Take Away
• Location specific performance is “king”and drives the design spec
• Design specs provide “just the right”knowledge of costs that can get into the budget
• Acoustic treatments/solutions need to be in the equipment spec to ensure predictable performance, acceptability, and accountability
![Page 39: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/39.jpg)
39
☺ Construction Trends
☺ Specifications
☺ Vibration Isolation
☺ Chiller Noise Treatments
☺ Roof Mounted Treatments
☺ Duct Work & Silencers
☺ Rooftop Unit Treatments
Sub TopicsSub Topics
![Page 40: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/40.jpg)
40
Construction Trends
• Less mass in building
• Less space between floors
• Curb mounted equipment
• Drop ceilings
• Premium for rentable/usable space
• Value Engineering
• Heightened sensitivity of owners
• ANSI S12.60
• LEED
![Page 41: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/41.jpg)
41
Best Practices
• Thickened slab above and
below
• Floating floors
• Pneumatic isolation systems
• 6 sided enclosures
• Stay away from midpoints of
column spans
• Buffer from noise sensitive
spaces
• Source & path acoustic
treatments
Indoor Chillers
![Page 42: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/42.jpg)
42
![Page 43: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/43.jpg)
43
Source Treatments
![Page 44: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/44.jpg)
44
Critical Design Factors
• Broadband Performance
• Tonal Performance
• Aerodynamic Performance
• Operating Efficiency
• Operating Costs
![Page 45: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/45.jpg)
45
“Soft” Enclosure Path Treatments
![Page 46: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/46.jpg)
46
“Hard” Enclosure Path Treatments
![Page 47: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/47.jpg)
47
Best Practices
Outdoor Chillers
• Thickened slab for
rooftop
• Evaluate loudness and
tonal content
• Special consideration for
remote evap piping
• Evaluate building and
property line noise
• Optimize aerodynamic
and acoustic performance
• Source and path acoustic
treatment
![Page 48: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/48.jpg)
48
Compressor Source Treatments
Sound Blankets
• Treat all accessible compressor circuit
components
• 3 to 4 lb. surface density
• Fit/refit attachment features must be “user
friendly”
• UL 764C Listed
![Page 49: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/49.jpg)
49
Treating Compressor Circuits
![Page 50: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/50.jpg)
50
Result of “generic” spec
![Page 51: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/51.jpg)
51
Air Intake Source Treatments
![Page 52: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/52.jpg)
52
![Page 53: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/53.jpg)
53
Condenser Fan Source Treatments
• Acoustical plenums
• Plenum with baffles
• Plenum with silencer bank
• Individual stack silencers
![Page 54: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/54.jpg)
54
Open Plenums
![Page 55: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/55.jpg)
55
Plenum with Baffles
![Page 56: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/56.jpg)
56
Plenum with Silencer Bank
![Page 57: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/57.jpg)
57
Not Recommended by OEMs
“Dedicated” Stack Silencers
![Page 58: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/58.jpg)
58
Path Treatments
Wall and Fence Liners
![Page 59: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/59.jpg)
59
Turnkey Acoustical Barrier Walls
![Page 60: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/60.jpg)
60
20+ dBA Attenuation Systems
![Page 61: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/61.jpg)
61
Best Practices
• Integral vibration/seismic
curb
• Lock down internal
isolation
• Add mass inside curbs
• Seal (acoustic) duct
drops
• Dissipate supply breakout
noise above deck
• Plenum style acoustic
curbs
Rooftop Curb
Mounted AHU
![Page 62: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/62.jpg)
62
![Page 63: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/63.jpg)
63
Poor “Best Practice”This is a seismic job!
![Page 64: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/64.jpg)
64
In-Curb Treatment
![Page 65: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/65.jpg)
65
Best Practices
RTU Configurations
• Increase plenum liner thickness
• Utilize RTU discharge plenums on the supply
side
• Avoid vane type flow modulation devices. VFD
controllers are preferred
• Slower fan speeds = lower noise levels
• Evaluate fan wheel types. Backward inclined (BI)
and aerofoil (AF) wheels are preferred over
forward curved models (FC)
![Page 66: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/66.jpg)
66
Integrated Sound Attenuators
![Page 67: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/67.jpg)
67
External
Acoustic Duct
Lagging
7 - 9 dB reduction in first 3
octave bands
![Page 68: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/68.jpg)
68
Rooftop Unit Condenser Section
Treatments
![Page 69: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/69.jpg)
69
Best Practices
Roof Mounted Equipment on
Dunnage Steel
• Restrained isolators if spring
• UV compatible shear mounts
• 3” to 4” thickened slab 8’ to 10’ around unit
perimeter
• Locate over utility space
• Keep away from skylights and operable
windows
![Page 70: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/70.jpg)
70
Cooling Towers
• Similar to Chiller strategies
• Restrained spring isolators
• Condenser fan discharge
treatment
• Path treatments
![Page 71: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/71.jpg)
71
![Page 72: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/72.jpg)
72
Best Practices
Vibration Isolation
• Follow ASHRAE guidelines for static deflection
• Review actual deflections
• Isolate pipes and ducts at riser and wall
penetrations
• Avoid suspended piping in mechanical rooms
below noise sensitive space
• Avoid cantilevered loads
• Proper adjustment of isolator lockdowns
and snubbers
![Page 73: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/73.jpg)
73
Acoustical Sealant
in ½” Gap Acoustical Batt Mineral Fiber
Packing
Pipe and Duct Penetrations
![Page 74: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/74.jpg)
74
![Page 75: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/75.jpg)
75
![Page 76: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/76.jpg)
76
![Page 77: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/77.jpg)
77
![Page 78: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/78.jpg)
78
![Page 79: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/79.jpg)
79
![Page 80: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/80.jpg)
80
Best Practices
• Concrete inertia bases
• Support elbows on base
• Open springs
• Seismic snubbers for base
• Molded neoprene flexes
• Vibration isolation hangers for 50’ or entire mechanical room
• Acoustic treatment rarely needed
Pumps
![Page 81: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/81.jpg)
81
• Avoid high pressure
drop models
• Evaluate self
generated noise
• Apply ∆p correction
factors
• Stay 3 equivalent duct
diameters away from
fittings
Best Practices
AHU Duct Silencers
![Page 82: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/82.jpg)
82
Guidelines for Sound Trap Placement
Near Fans and Duct Fittings
![Page 83: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/83.jpg)
83
Best Practices
Avoiding Respirable Fibers
• Fiber free reactive duct silencers
(packless)
• Media wrap of packed silencers
with spacers
• Closed cell thermal insulation
• Open cell melamine foams
![Page 84: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/84.jpg)
84
![Page 85: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/85.jpg)
85
Best Practices
Duct Design
• Follow ASHRAE guidelines
• Follow SMACNA guidelines
• Control ductwork aspect ratios
• Increase gauge and stiffening near units
• Double wall duct
• Duct shape
• Target velocities consistent with target NC goals
![Page 86: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/86.jpg)
86
Turbulence = Regenerated Noise
![Page 87: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/87.jpg)
87
Regenerated Noise at Fittings
Recommended maximum airflow
velocities for various installations
![Page 88: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/88.jpg)
88
Duct
Shapes
![Page 89: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/89.jpg)
89
Best Practices
• Select diffusers for 6 to 8 NC points below room target NC
• Long radius 90° flexes to diffusers add 1 to 3 NC points
• “Kinked” flexes add 7 to 9 NC points
• Balancing dampers should be located three equivalent duct diameters away from diffusers and fittings
• Open plenum return grilles may require lined elbow
Room Diffusers
![Page 90: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/90.jpg)
90
Best Practices
VAV Boxes
• Lined discharge 10’ to 15’
• First take-off minimum 3’ from discharge
• Single duct VAV 1500 – 1700 CFM
• Fan powered VAV 1100 – 1200 CFM
• External wraps for casing radiated noise
![Page 91: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/91.jpg)
91
Recommended VAV Detail
![Page 92: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/92.jpg)
92
Removable Wraps Reduce
Radiated Noise
![Page 93: ASHRAE Chapter Meeting HVAC Noise & Vibration Control](https://reader033.vdocument.in/reader033/viewer/2022052318/584919161a28ab002f8b559b/html5/thumbnails/93.jpg)
93