EN 50288-7 XLPE & PE Insulated
LSZH SheathedInstrumentation Cables
ADDISON
Caledonian2
Table of conTenTs
XlPe Insulated, lsZH sheathed Instrumentation cablesXLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multicore).4XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multicore).............................................................................................................................10XLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Single -triple).......................................................................................................................................16XLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multi-triple).....................................................................................................................................19XLPE Insulated, LSZH Sheathed, Individual and Overall Screened Instrumentation Cables (Multi-triple)...........................................................................................................................24XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single-triple).............................................................................................................29XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multi-triple).............................................................................................................32XLPE Insulated, LSZH Sheathed, Individual and Overall Screened & Armoured Instrumentation Cables (Multi-triple)................................................................................37XLPE Insulated, LSZH Sheathed & CWB Screened Instrumentation Cables (Single Pair)..42XLPE Insulated, LSZH Sheathed & CWB Screened Instrumentation Cables (Multipair).....45XLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Single Pair).........................................................................................................................................49XLPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multipair).52XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single Pair)..........................................................................................................................57XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multipair)......................................................................................................................60XLPE Insulated, LSZH Sheathed, Individual and Overall Screened Instrumentation Cables (Multipair)..........................................................................................................65XLPE Insulated, LSZH Sheathed, Individual and Overall Screened & Armoured Instrumentation Cables (Multipair)......................................................................................70
Pe Insulated, lsZH sheathed Instrumentation cablesPE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multicore).......75PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multicore).............................................................................................................................81PE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Single -triple).87PE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multi-triple).............................................................................................................................90
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
3ADDISON
PE Insulated, LSZH Sheathed, Individual and Overall Screened Instrumentation Cables (Multi-triple).........................................................................................................................95PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single-triple)...........................................................................................................100PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multi-triple).............................................................................................................102PE Insulated, LSZH Sheathed, Individual and Overall Screened & Armoured Instrumentation Cables (Multi-triple)................................................................................108PE Insulated, LSZH Sheathed & CWB Screened Instrumentation Cables (Single Pair)....113PE Insulated, LSZH Sheathed & CWB Screened Instrumentation Cables (Multipair).....106PE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Single Pair).120PE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multipair).123PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single Pair)...................................................................................................................128PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multipair)......................................................................................................................131PE Insulated, LSZH Sheathed, Individual and Overall Screened Instrumentation Cables (Multipair)..........................................................................................................136PE Insulated, LSZH Sheathed, Individual and Overall Screened & Armoured Instrumentation Cables (Multipair)................................................................................141Type Codes For Fire Retardant Instrumentation Cables...................................................146Technical Information...................................................................................................147
ADDISON
Caledonian4
XlPe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multicore)
re-2X(st)H 90°c / 500V
LSZH Outer Sheath
Plain Annealed CopperXLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
5ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
500V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.overall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black numberedouter sheath: Black, blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5 2.5
Insulation thickness (nominal) mm 0.55 0.55 0.55 0.6 0.6 0.7
Conductor resistance (20°C) Ω/km 36.7 25.0 18.5 14.2 12.3 7.4
Insulation resistance (20°C) MΩ.km(Min.) 5000Mutual Capacitance (1 kHz) pF/m(Max.) 115Capacitance unbalance(1 kHz) pF/500 m (Max.) 500 L / R (ratio) (max.) μH/Ω 25 25 25 40 40 60Operating voltage V 500
Test Voltage Urms
Core to Core V 2000
Core to Screen V 2000
ADDISON
Caledonian6
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HNo. of Core x1xCross Section
NominalInsulationThickness
NominalSheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
0.5mm2, Multicore
RE-2X(St)H 2C0.5 2x1x0.5 0.55 0.9 6.2 47
RE-2X(St)H 3C0.5 3x1x0.5 0.55 0.9 6.5 50
RE-2X(St)H 4C0.5 4x1x0.5 0.55 0.9 7.0 60
RE-2X(St)H 5C0.5 5x1x0.5 0.55 0.9 7.6 71
RE-2X(St)H 8C0.5 8x1x0.5 0.55 1.0 9.1 95
RE-2X(St)H 10C0.5 10x1x0.5 0.55 1.0 10.4 127
RE-2X(St)H 12C0.5 12x1x0.5 0.55 1.0 10.7 151
RE-2X(St)H 14C0.5 14x1x0.5 0.55 1.0 11.3 162
RE-2X(St)H 16C0.5 16x1x0.5 0.55 1.1 11.8 180
RE-2X(St)H 20C0.5 20x1x0.5 0.55 1.1 13.3 222
RE-2X(St)H 24C0.5 24x1x0.5 0.55 1.1 14.7 274
RE-2X(St)H 27C0.5 27x1x0.5 0.55 1.2 15.0 282
RE-2X(St)H 30C0.5 30x1x0.5 0.55 1.2 15.7 318
RE-2X(St)H 37C0.5 37x1x0.5 0.55 1.2 16.9 372
RE-2X(St)H 40C0.5 40x1x0.5 0.55 1.2 17.6 372
0.75mm2, Multicore
RE-2X(St)H 2C0.75 2x1x0.75 0.55 0.9 6.5 51
RE-2X(St)H 3C0.75 3x1x0.75 0.55 0.9 6.9 62
RE-2X(St)H 4C0.75 4x1x0.75 0.55 0.9 7.4 74
RE-2X(St)H 5C0.75 5x1x0.75 0.55 0.9 8.1 96
RE-2X(St)H 8C0.75 8x1x0.75 0.55 1.0 9.7 126
RE-2X(St)H 10C0.75 10x1x0.75 0.55 1.0 11.1 156
RE-2X(St)H 12C0.75 12x1x0.75 0.55 1.0 11.5 183
RE-2X(St)H 14C0.75 14x1x0.75 0.55 1.1 12.2 200
RE-2X(St)H 16C0.75 16x1x0.75 0.55 1.1 12.9 224
RE-2X(St)H 20C0.75 20x1x0.75 0.55 1.1 14.3 284
www.caledonian-cables.co.uk www.addison-cables.com
7ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HNo. of Core x1xCross Section
NominalInsulationThickness
NominalSheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
RE-2X(St)H 24C0.75 24x1x0.75 0.55 1.2 16.0 324
RE-2X(St)H 27C0.75 27x1x0.75 0.55 1.2 16.3 363
RE-2X(St)H 30C0.75 30x1x0.75 0.55 1.2 16.9 396
RE-2X(St)H 37C0.75 37x1x0.75 0.55 1.2 18.2 472
RE-2X(St)H 40C0.75 40x1x0.75 0.55 1.3 19.1 514
1.0mm2, Multicore
RE-2X(St)H 2C1.0 2x1x1.0 0.55 0.9 6.9 61
RE-2X(St)H 3C1.0 3x1x1.0 0.55 0.9 7.3 70
RE-2X(St)H 4C1.0 4x1x1.0 0.55 0.9 7.9 85
RE-2X(St)H 5C1.0 5x1x1.0 0.55 0.9 8.6 109
RE-2X(St)H 8C1.0 8x1x1.0 0.55 1.0 10.3 157
RE-2X(St)H 10C1.0 10x1x1.0 0.55 1.0 11.9 193
RE-2X(St)H 12C1.0 12x1x1.0 0.55 1.0 12.2 214
RE-2X(St)H 14C1.0 14x1x1.0 0.55 1.1 13.0 243
RE-2X(St)H 16C1.0 16x1x1.0 0.55 1.1 13.7 280
RE-2X(St)H 20C1.0 20x1x1.0 0.55 1.1 15.2 336
RE-2X(St)H 24C1.0 24x1x1.0 0.55 1.2 17.0 414
RE-2X(St)H 27C1.0 27x1x1.0 0.55 1.2 17.4 443
RE-2X(St)H 30C1.0 30x1x1.0 0.55 1.2 18.0 484
RE-2X(St)H 37C1.0 37x1x1.0 0.55 1.2 19.6 590
RE-2X(St)H 40C1.0 40x1x1.0 0.55 1.3 20.4 631
1.3mm2, Multicore
RE-2X(St)H 2C1.3 2x1x1.3 0.6 0.9 7.4 69
RE-2X(St)H 3C1.3 3x1x1.3 0.6 0.9 7.9 83
RE-2X(St)H 4C1.3 4x1x1.3 0.6 0.9 8.5 105
RE-2X(St)H 5C1.3 5x1x1.3 0.6 1.0 9.5 135
RE-2X(St)H 8C1.3 8x1x1.3 0.6 1.0 11.2 186
RE-2X(St)H 10C1.3 10x1x1.3 0.6 1.1 13.2 228
ADDISON
Caledonian8
Caledonian Cable Code
RE-2X(St)HNo. of Core x1xCross Section
NominalInsulationThickness
NominalSheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
RE-2X(St)H 12C1.3 12x1x1.3 0.6 1.1 13.6 269
RE-2X(St)H 14C1.3 14x1x1.3 0.6 1.1 14.3 305
RE-2X(St)H 16C1.3 16x1x1.3 0.6 1.1 15.0 351
RE-2X(St)H 20C1.3 20x1x1.3 0.6 1.2 16.9 423
RE-2X(St)H 24C1.3 24x1x1.3 0.6 1.2 18.7 507
RE-2X(St)H 27C1.3 27x1x1.3 0.6 1.3 19.3 558
RE-2X(St)H 30C1.3 30x1x1.3 0.6 1.3 20.0 611
RE-2X(St)H 37C1.3 37x1x1.3 0.6 1.3 21.6 743
RE-2X(St)H 40C1.3 40x1x1.3 0.6 1.4 22.7 796
1.5mm2, Multicore
RE-2X(St)H 2C1.5 2x1x1.5 0.6 0.9 7.7 78
RE-2X(St)H 3C1.5 3x1x1.5 0.6 0.9 8.1 98
RE-2X(St)H 4C1.5 4x1x1.5 0.6 0.9 8.8 120
RE-2X(St)H 5C1.5 5x1x1.5 0.6 1.0 9.8 153
RE-2X(St)H 8C1.5 8x1x1.5 0.6 1.0 11.6 218
RE-2X(St)H 10C1.5 10x1x1.5 0.6 1.1 13.7 268
RE-2X(St)H 12C1.5 12x1x1.5 0.6 1.1 14.1 315
RE-2X(St)H 14C1.5 14x1x1.5 0.6 1.1 14.8 341
RE-2X(St)H 16C1.5 16x1x1.5 0.6 1.1 15.6 392
RE-2X(St)H 20C1.5 20x1x1.5 0.6 1.2 17.6 484
RE-2X(St)H 24C1.5 24x1x1.5 0.6 1.3 19.6 579
RE-2X(St)H 27C1.5 27x1x1.5 0.6 1.3 20.1 626
RE-2X(St)H 30C1.5 30x1x1.5 0.6 1.3 20.8 685
RE-2X(St)H 37C1.5 37x1x1.5 0.6 1.4 22.6 834
RE-2X(St)H 40C1.5 40x1x1.5 0.6 1.4 23.6 898
2.5mm2, Multicore
RE-2X(St)H 2C2.5 2x1x2.5 0.7 0.9 8.9 111
RE-2X(St)H 3C2.5 3x1x2.5 0.7 1.0 9.7 132
www.caledonian-cables.co.uk www.addison-cables.com
9ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HNo. of Core x1xCross Section
NominalInsulationThickness
NominalSheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
RE-2X(St)H 4C2.5 4x1x2.5 0.7 1.0 10.5 169
RE-2X(St)H 5C2.5 5x1x2.5 0.7 1.0 11.9 209
RE-2X(St)H 8C2.5 8x1x2.5 0.7 1.1 13.9 321
RE-2X(St)H 10C2.5 10x1x2.5 0.7 1.2 16.3 386
RE-2X(St)H 12C2.5 12x1x2.5 0.7 1.2 16.9 447
RE-2X(St)H 14C2.5 14x1x2.5 0.7 1.2 17.7 509
RE-2X(St)H 16C2.5 16x1x2.5 0.7 1.3 18.9 585
RE-2X(St)H 20C2.5 20x1x2.5 0.7 1.3 21.1 712
RE-2X(St)H 24C2.5 24x1x2.5 0.7 1.4 23.6 855
RE-2X(St)H 27C2.5 27x1x2.5 0.7 1.4 24.1 956
RE-2X(St)H 30C2.5 30x1x2.5 0.7 1.5 25.2 1049
RE-2X(St)H 37C2.5 37x1x2.5 0.7 1.5 27.2 1277
RE-2X(St)H 40C2.5 40x1x2.5 0.7 1.6 28.5 1370Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
500V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian10
XlPe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (Multicore)re-2X(st)HsWaH 90°c / 500V
LSZH Inner Sheath
LSZH Outer Sheath
Plain Annealed CopperXLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
Galvanised Steel Wire Armoured
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
11ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
500V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.overall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmouring: Galvanised steel wire outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black numberedouter sheath: Black, blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5 2.5
Insulation thickness (nominal) mm 0.55 0.55 0.55 0.6 0.6 0.7
Conductor resistance (20°C) Ω/km 36.7 25.0 18.5 14.2 12.3 7.4
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km(Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40 40Operating voltage V 500
Test Voltage Urms
Core to Core V 2000
Core to Screen V 2000
ADDISON
Caledonian12
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Core x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/km0.5mm2, Multicore
RE-2X(St)HSWAH 2C0.5 2x1x0.5 0.55 0.9 6.2 0.9 1.3 10.6 210RE-2X(St)HSWAH 3C0.5 3x1x0.5 0.55 0.9 6.5 0.9 1.3 10.9 230RE-2X(St)HSWAH 4C0.5 4x1x0.5 0.55 0.9 7.0 0.9 1.3 11.4 253RE-2X(St)HSWAH 5C0.5 5x1x0.5 0.55 0.9 7.6 0.9 1.3 12.0 283RE-2X(St)HSWAH 8C0.5 8x1x0.5 0.55 1.0 9.1 0.9 1.4 13.7 344RE-2X(St)HSWAH 10C0.5 10x1x0.5 0.55 1.0 10.4 0.9 1.4 15.0 399RE-2X(St)HSWAH 12C0.5 12x1x0.5 0.55 1.0 10.7 0.9 1.4 15.3 442RE-2X(St)HSWAH 14C0.5 14x1x0.5 0.55 1.0 11.3 0.9 1.4 15.9 474RE-2X(St)HSWAH 16C0.5 16x1x0.5 0.55 1.1 11.8 0.9 1.4 16.4 505RE-2X(St)HSWAH 20C0.5 20x1x0.5 0.55 1.1 13.3 0.9 1.5 18.1 569RE-2X(St)HSWAH 24C0.5 24x1x0.5 0.55 1.1 14.7 0.9 1.5 19.5 642RE-2X(St)HSWAH 27C0.5 27x1x0.5 0.55 1.2 15.0 0.9 1.5 19.8 808RE-2X(St)HSWAH 30C0.5 30x1x0.5 0.55 1.2 15.7 0.9 1.5 20.5 848RE-2X(St)HSWAH 37C0.5 37x1x0.5 0.55 1.2 16.9 0.9 1.6 21.9 963RE-2X(St)HSWAH 40C0.5 40x1x0.5 0.55 1.2 17.6 1.25 1.6 23.3 1014
0.75mm2, MulticoreRE-2X(St)HSWAH 2C0.75 2x1x0.75 0.55 0.9 6.5 0.9 1.3 10.9 230RE-2X(St)HSWAH 3C0.75 3x1x0.75 0.55 0.9 6.9 0.9 1.3 11.3 247RE-2X(St)HSWAH 4C0.75 4x1x0.75 0.55 0.9 7.4 0.9 1.3 11.8 278RE-2X(St)HSWAH 5C0.75 5x1x0.75 0.55 0.9 8.1 0.9 1.4 12.7 322RE-2X(St)HSWAH 8C0.75 8x1x0.75 0.55 1.0 9.7 0.9 1.4 14.3 383RE-2X(St)HSWAH 10C0.75 10x1x0.75 0.55 1.0 11.1 0.9 1.4 15.7 461RE-2X(St)HSWAH 12C0.75 12x1x0.75 0.55 1.0 11.5 0.9 1.4 16.1 477RE-2X(St)HSWAH 14C0.75 14x1x0.75 0.55 1.1 12.2 0.9 1.5 17.0 527RE-2X(St)HSWAH 16C0.75 16x1x0.75 0.55 1.1 12.9 0.9 1.5 17.7 572RE-2X(St)HSWAH 20C0.75 20x1x0.75 0.55 1.1 14.3 0.9 1.5 19.1 669RE-2X(St)HSWAH 24C0.75 24x1x0.75 0.55 1.2 16.0 0.9 1.5 20.8 877RE-2X(St)HSWAH 27C0.75 27x1x0.75 0.55 1.2 16.3 0.9 1.6 21.3 929
www.caledonian-cables.co.uk www.addison-cables.com
13ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Core x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH 30C0.75 30x1x0.75 0.55 1.2 16.9 0.9 1.6 21.9 986RE-2X(St)HSWAH 37C0.75 37x1x0.75 0.55 1.2 18.2 1.25 1.6 23.9 1102RE-2X(St)HSWAH 40C0.75 40x1x0.75 0.55 1.3 19.1 1.25 1.6 24.8 1181
1.0mm2, MulticoreRE-2X(St)HSWAH 2C1.0 2x1x1.0 0.55 0.9 6.9 0.9 1.3 11.3 247RE-2X(St)HSWAH 3C1.0 3x1x1.0 0.55 0.9 7.3 0.9 1.3 11.7 270RE-2X(St)HSWAH 4C1.0 4x1x1.0 0.55 0.9 7.9 0.9 1.4 12.5 299RE-2X(St)HSWAH 5C1.0 5x1x1.0 0.55 0.9 8.6 0.9 1.4 13.2 342RE-2X(St)HSWAH 8C1.0 8x1x1.0 0.55 1.0 10.3 0.9 1.4 14.9 424RE-2X(St)HSWAH 10C1.0 10x1x1.0 0.55 1.0 11.9 0.9 1.4 16.5 514RE-2X(St)HSWAH 12C1.0 12x1x1.0 0.55 1.0 12.2 0.9 1.5 17.0 548RE-2X(St)HSWAH 14C1.0 14x1x1.0 0.55 1.1 13.0 0.9 1.5 17.8 590RE-2X(St)HSWAH 16C1.0 16x1x1.0 0.55 1.1 13.7 0.9 1.5 18.5 649RE-2X(St)HSWAH 20C1.0 20x1x1.0 0.55 1.1 15.2 0.9 1.5 20.0 864RE-2X(St)HSWAH 24C1.0 24x1x1.0 0.55 1.2 17.0 0.9 1.6 22.0 1005RE-2X(St)HSWAH 27C1.0 27x1x1.0 0.55 1.2 17.4 1.25 1.6 23.1 1058RE-2X(St)HSWAH 30C1.0 30x1x1.0 0.55 1.2 18.0 1.25 1.6 23.7 1113RE-2X(St)HSWAH 37C1.0 37x1x1.0 0.55 1.2 19.6 1.25 1.6 25.3 1271RE-2X(St)HSWAH 40C1.0 40x1x1.0 0.55 1.3 20.4 1.25 1.7 26.3 1351
1.3mm2, MulticoreRE-2X(St)HSWAH 2C1.3 2x1x1.3 0.6 0.9 7.4 0.9 1.3 11.8 275RE-2X(St)HSWAH 3C1.3 3x1x1.3 0.6 0.9 7.9 0.9 1.3 12.3 ??RE-2X(St)HSWAH 4C1.3 4x1x1.3 0.6 0.9 8.5 0.9 1.4 13.1 340RE-2X(St)HSWAH 5C1.3 5x1x1.3 0.6 1.0 9.5 0.9 1.4 14.1 383RE-2X(St)HSWAH 8C1.3 8x1x1.3 0.6 1.0 11.2 0.9 1.4 15.8 483RE-2X(St)HSWAH 10C1.3 10x1x1.3 0.6 1.1 13.2 0.9 1.5 18.0 578RE-2X(St)HSWAH 12C1.3 12x1x1.3 0.6 1.1 13.6 0.9 1.5 18.4 633RE-2X(St)HSWAH 14C1.3 14x1x1.3 0.6 1.1 14.3 0.9 1.5 19.1 698RE-2X(St)HSWAH 16C1.3 16x1x1.3 0.6 1.1 15.0 0.9 1.5 19.8 870RE-2X(St)HSWAH 20C1.3 20x1x1.3 0.6 1.2 16.9 0.9 1.6 21.9 1014RE-2X(St)HSWAH 24C1.3 24x1x1.3 0.6 1.2 18.7 1.25 1.6 24.4 1163
ADDISON
Caledonian14
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Core x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH 27C1.3 27x1x1.3 0.6 1.3 19.3 1.25 1.6 25.0 1227RE-2X(St)HSWAH 30C1.3 30x1x1.3 0.6 1.3 20.0 1.25 1.6 25.7 1305RE-2X(St)HSWAH 37C1.3 37x1x1.3 0.6 1.3 21.6 1.25 1.7 27.5 1504RE-2X(St)HSWAH 40C1.3 40x1x1.3 0.6 1.4 22.7 1.25 1.7 28.6 1584
1.5mm2, MulticoreRE-2X(St)HSWAH 2C1.5 2x1x1.5 0.6 0.9 7.7 0.9 1.3 12.1 279RE-2X(St)HSWAH 3C1.5 3x1x1.5 0.6 0.9 8.1 0.9 1.4 12.7 322RE-2X(St)HSWAH 4C1.5 4x1x1.5 0.6 0.9 8.8 0.9 1.4 13.4 347RE-2X(St)HSWAH 5C1.5 5x1x1.5 0.6 1.0 9.8 0.9 1.4 14.4 392RE-2X(St)HSWAH 8C1.5 8x1x1.5 0.6 1.0 11.6 0.9 1.4 16.2 518RE-2X(St)HSWAH 10C1.5 10x1x1.5 0.6 1.1 13.7 0.9 1.5 18.5 614RE-2X(St)HSWAH 12C1.5 12x1x1.5 0.6 1.1 14.1 0.9 1.5 18.9 670RE-2X(St)HSWAH 14C1.5 14x1x1.5 0.6 1.1 14.8 0.9 1.5 19.6 742RE-2X(St)HSWAH 16C1.5 16x1x1.5 0.6 1.1 15.6 0.9 1.5 20.4 925RE-2X(St)HSWAH 20C1.5 20x1x1.5 0.6 1.2 17.6 1.25 1.6 23.3 1062RE-2X(St)HSWAH 24C1.5 24x1x1.5 0.6 1.3 19.6 1.25 1.6 25.3 1218RE-2X(St)HSWAH 27C1.5 27x1x1.5 0.6 1.3 20.1 1.25 1.6 25.8 1289RE-2X(St)HSWAH 30C1.5 30x1x1.5 0.6 1.3 20.8 1.25 1.7 26.7 1418RE-2X(St)HSWAH 37C1.5 37x1x1.5 0.6 1.4 22.6 1.25 1.7 28.5 1586RE-2X(St)HSWAH 40C1.5 40x1x1.5 0.6 1.4 23.6 1.25 1.7 29.5 1687
2.5mm2, MulticoreRE-2X(St)HSWAH 2C2.5 2x1x2.5 0.7 0.9 8.9 0.9 1.4 13.5 364RE-2X(St)HSWAH 3C2.5 3x1x2.5 0.7 1.0 9.7 0.9 1.4 14.3 389RE-2X(St)HSWAH 4C2.5 4x1x2.5 0.7 1.0 10.5 0.9 1.4 15.1 430RE-2X(St)HSWAH 5C2.5 5x1x2.5 0.7 1.0 11.9 0.9 1.4 16.5 547RE-2X(St)HSWAH 8C2.5 8x1x2.5 0.7 1.1 13.9 0.9 1.5 18.7 684RE-2X(St)HSWAH 10C2.5 10x1x2.5 0.7 1.2 16.3 0.9 1.6 21.3 952RE-2X(St)HSWAH 12C2.5 12x1x2.5 0.7 1.2 16.9 0.9 1.6 21.9 1012RE-2X(St)HSWAH 14C2.5 14x1x2.5 0.7 1.2 17.7 1.25 1.6 23.4 1126RE-2X(St)HSWAH 16C2.5 16x1x2.5 0.7 1.3 18.9 1.25 1.6 24.6 1252RE-2X(St)HSWAH 20C2.5 20x1x2.5 0.7 1.3 21.1 1.25 1.7 27.0 1456
www.caledonian-cables.co.uk www.addison-cables.com
15ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Core x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH 24C2.5 24x1x2.5 0.7 1.4 23.6 1.25 1.7 29.5 1644RE-2X(St)HSWAH 27C2.5 27x1x2.5 0.7 1.4 24.1 1.25 1.8 30.2 1811RE-2X(St)HSWAH 30C2.5 30x1x2.5 0.7 1.5 25.2 1.25 1.8 31.3 2154RE-2X(St)HSWAH 37C2.5 37x1x2.5 0.7 1.5 27.2 1.25 1.8 33.3 2477RE-2X(St)HSWAH 40C2.5 40x1x2.5 0.7 1.6 28.5 1.25 1.9 34.8 2614Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
500V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian16
XlPe Insulated, lsZH sheathed & overall screened Instrumentation cables (single Triple)
re-2X(st)H 90°c / 300 V
LSZH Outer Sheath
Plain Annealed Copper
XLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
www.caledonian-cables.co.uk www.addison-cables.com
17ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Triple: Three conductors twisted to form a triple lay-up: Triples laid up in layers of optimum pitch separator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25.0 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000 5000 5000 5000 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km(Max.) 1L / R (ratio) (max.) μH/Ω 25 25 25 40 40Operating voltage V 300
Test Voltage Urms
Core to Core V 1500
Core to Screen V 1500
ADDISON
Caledonian18
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)YHNo. of Triples
x3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2X(St)H 1T0.5 1x3x0,50 0.35 0.8 5.4 45RE-2X(St)H 1T0.75 1x3x0,75 0.38 0.9 6.1 59RE-2X(St)H 1T1.0 1x3x1.0 0.4 0.9 6.6 66
RE-2X(St)H 1T1.3 1x3x1,3 0.45 0.9 7.2 86
RE-2X(St)H 1T1.5 1x3x1,5 0.45 0.9 7.5 95
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
19ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multitriple)
re-2X(st)H 90°c / 300 V
LSZH Outer Sheath
Plain Annealed Copper
XLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
ADDISON
Caledonian20
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Triple: Three conductors twisted to form a triple lay-up: Triples laid up in layers of optimum pitch separator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25.0 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) up to 4 trples pF/m(Max.) 90 90 90 102 102
above 4 trples pF/m(Max.) 75 75 75 85 85
Inductance mH/km(Max.) 1L / R (ratio) (max.) μH/Ω 25 25 25 40 40
www.caledonian-cables.co.uk www.addison-cables.com
21ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Operating voltage V 300
Test Voltage Urms
Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)H
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/km0.5mm2 , Multi-striple
RE-2X(St)H 2T0.5 2x3x0,50 0.35 0.9 8.4 91
RE-2X(St)H 4T0.5 4x3x0,50 0.35 1.0 9.8 123
RE-2X(St)H 5T0.5 5x3x0,50 0.35 1.0 10.8 155
RE-2X(St)H 6T0.5 6x3x0,50 0.35 1.0 12.1 185
RE-2X(St)H 8T0.5 8x3x0,50 0.35 1.1 13.1 221
RE-2X(St)H 10T0.5 10x3x0,50 0.35 1.1 14.7 275
RE-2X(St)H 12T0.5 12x3x0,50 0.35 1.1 15.2 316
RE-2X(St)H 16T0.5 16x3x0,50 0.35 1.2 17.4 414
RE-2X(St)H 20T0.5 20x3x0,50 0.35 1.2 19.1 508
RE-2X(St)H 24T0.5 24x3x0,50 0.35 1.3 20.9 594
0.75mm2 , Multi-striple RE-2X(St)H 2T0.75 2x3x0,75 0.38 0.9 9.3 114
RE-2X(St)H 4T0.75 4x3x0,75 0.38 1.0 10.9 163
RE-2X(St)H 5T0.75 5x3x0,75 0.38 1.0 12.0 199
RE-2X(St)H 6T0.75 6x3x0,75 0.38 1.1 13.7 245
RE-2X(St)H 8T0.75 8x3x0,75 0.38 1.1 14.7 296
RE-2X(St)H 10T0.75 10x3x0,75 0.38 1.2 16.7 366
RE-2X(St)H 12T0.75 12x3x0,75 0.38 1.2 17.3 423
RE-2X(St)H 16T0.75 16x3x0,75 0.38 1.3 19.7 555
RE-2X(St)H 20T0.75 20x3x0,75 0.38 1.3 21.7 681
RE-2X(St)H 24T0.75 24x3x0,75 0.38 1.4 23.7 802
1.0mm2 , Multi-striple RE-2X(St)H 2T1.0 2x3x1 0.4 1.0 10.4 135
ADDISON
Caledonian22
Caledonian Cable Code
RE-2X(St)H
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2X(St)H 4T1.0 4x3x1 0.4 1.0 11.9 202
RE-2X(St)H 5T1.0 5x3x1 0.4 1.0 13.2 251
RE-2X(St)H 6T1.0 6x3x1 0.4 1.1 15.0 303
RE-2X(St)H 8T1.0 8x3x1 0.4 1.1 16.1 379
RE-2X(St)H 10T1.0 10x3x1 0.4 1.2 18.4 461
RE-2X(St)H 12T1.0 12x3x1 0.4 1.2 19.0 544
RE-2X(St)H 16T1.0 16x3x1 0.4 1.3 21.7 717
RE-2X(St)H 20T1.0 20x3x1 0.4 1.4 24.1 880
RE-2X(St)H 24T1.0 24x3x1 0.4 1.4 26.1 10481.3mm2 , Multi-striple
RE-2X(St)H 2T1.3 2x3x1,3 0.45 1.0 11.5 175
RE-2X(St)H 4T1.3 4x3x1,3 0.45 1.1 13.4 258
RE-2X(St)H 5T1.3 5x3x1,3 0.45 1.1 14.8 318
RE-2X(St)H 6T1.3 6x3x1,3 0.45 1.2 16.9 387
RE-2X(St)H 8T1.3 8x3x1,3 0.45 1.2 18.1 474
RE-2X(St)H 10T1.3 10x3x1,3 0.45 1.3 20.7 589
RE-2X(St)H 12T1.3 12x3x1,3 0.45 1.3 21.4 695
RE-2X(St)H 16T1.3 16x3x1,3 0.45 1.4 24.4 918
RE-2X(St)H 20T1.3 20x3x1,3 0.45 1.5 27.1 1124RE-2X(St)H 24T1.3 24x3x1,3 0.45 1.6 29.6 1336
1.5mm2 , Multi-striple RE-2X(St)H 2T1.5 2x3x1,5 0.45 1.0 11.9 191
RE-2X(St)H 4T1.5 4x3x1,5 0.45 1.1 14.0 287
RE-2X(St)H 5T1.5 5x3x1,5 0.45 1.1 15.4 355
RE-2X(St)H 6T1.5 6x3x1,5 0.45 1.2 17.6 432
RE-2X(St)H 8T1.5 8x3x1,5 0.45 1.3 19.1 540
RE-2X(St)H 10T1.5 10x3x1,5 0.45 1.3 21.6 672
RE-2X(St)H 12T1.5 12x3x1,5 0.45 1.4 22.5 779
RE-2X(St)H 16T1.5 16x3x1,5 0.45 1.5 25.7 1031
www.caledonian-cables.co.uk www.addison-cables.com
23ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)H
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2X(St)H 20T1.5 20x3x1,5 0.45 1.6 28.6 1265RE-2X(St)H 24T1.5 24x3x1,5 0.45 1.7 31.1 1508
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian24
XlPe Insulated, lsZH sheathed, Individual & overall screened Instrumentation cables (Multitriple)
re-2X(st)H-TiMf 90°c / 300 V
LSZH Outer Sheath
Plain Annealed Copper
XLPE Insulation
Individual Aluminium/polyester TapeTinned Copper Drain Wire
Overall Aluminium/polyester Tape
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
www.caledonian-cables.co.uk www.addison-cables.com
25ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Individual screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²Triple: Three conductors twisted to form a triple **TiMF Construction: Polyester tape above the triple, AL-PES tape over solid tinned copper drain wire, 0,60 mmlay-up: TiMF laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km(Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
ADDISON
Caledonian26
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)H-TiMF
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/km0.5mm2, Multi-striple
RE-2X(St)H-TiMF 2T0.5 2x3x0.5 0.35 1.0 9.7 104RE-2X(St)H-TiMF 4T0.5 4x3x0.5 0.35 1.0 11.1 151RE-2X(St)H-TiMF 5T0.5 5x3x0.5 0.35 1.1 12.4 183RE-2X(St)H-TiMF 6T0.5 6x3x0.5 0.35 1.1 14.0 225RE-2X(St)H-TiMF 8T0.5 8x3x0.5 0.35 1.1 14.9 283
RE-2X(St)H-TiMF 10T0.5 10x3x0.5 0.35 1.2 17.0 348RE-2X(St)H-TiMF 12T0.5 12x3x0.5 0.35 1.2 17.6 385RE-2X(St)H-TiMF 16T0.5 16x3x0.5 0.35 1.3 20.1 504RE-2X(St)H-TiMF 20T0.5 20x3x0.5 0.35 1.4 22.3 616RE-2X(St)H-TiMF 24T0.5 24x3x0.5 0.35 1.5 24.4 749
0.75mm2, Multi-striple RE-2X(St)H-TiMF 2T0.75 2x3x0.75 0.38 1.0 10.6 121RE-2X(St)H-TiMF 4T0.75 4x3x0.75 0.38 1.1 12.4 186RE-2X(St)H-TiMF 5T0.75 5x3x0.75 0.38 1.1 13.7 242RE-2X(St)H-TiMF 6T0.75 6x3x0.75 0.38 1.1 15.4 280RE-2X(St)H-TiMF 8T0.75 8x3x0.75 0.38 1.2 16.7 362RE-2X(St)H-TiMF 10T0.75 10x3x0.75 0.38 1.3 19.0 446RE-2X(St)H-TiMF 12T0.75 12x3x0.75 0.38 1.3 19.7 495RE-2X(St)H-TiMF 16T0.75 16x3x0.75 0.38 1.4 22.5 652RE-2X(St)H-TiMF 20T0.75 20x3x0.75 0.38 1.5 24.9 833RE-2X(St)H-TiMF 24T0.75 24x3x0.75 0.38 1.6 27.2 966
1.0mm2, Multi-striple RE-2X(St)H-TiMF 2T1.0 2x3x1 0.4 1.0 11.5 154RE-2X(St)H-TiMF 4T1.0 4x3x1 0.4 1.1 13.4 227
www.caledonian-cables.co.uk www.addison-cables.com
27ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)H-TiMF
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2X(St)H-TiMF 5T1.0 5x3x1 0.4 1.1 14.8 286RE-2X(St)H-TiMF 6T1.0 6x3x1 0.4 1.2 16.9 348RE-2X(St)H-TiMF 8T1.0 8x3x1 0.4 1.2 18.1 443
RE-2X(St)H-TiMF 10T1.0 10x3x1 0.4 1.3 20.7 545RE-2X(St)H-TiMF 12T1.0 12x3x1 0.4 1.3 21.4 621RE-2X(St)H-TiMF 16T1.0 16x3x1 0.4 1.4 24.4 836RE-2X(St)H-TiMF 20T1.0 20x3x1 0.4 1.5 27.1 1001RE-2X(St)H-TiMF 24T1.0 24x3x1 0.4 1.6 29.6 1207
1.3mm2, Multi-striple RE-2X(St)H-TiMF 2T1.3 2x3x1,3 0.45 1.1 12.8 185RE-2X(St)H-TiMF 4T1.3 4x3x1,3 0.45 1.1 14.7 283RE-2X(St)H-TiMF 5T1.3 5x3x1,3 0.45 1.2 16.5 357RE-2X(St)H-TiMF 6T1.3 6x3x1,3 0.45 1.3 18.8 425RE-2X(St)H-TiMF 8T1.3 8x3x1,3 0.45 1.3 20.1 553
RE-2X(St)H-TiMF 10T1.3 10x3x1,3 0.45 1.4 23.0 682RE-2X(St)H-TiMF 12T1.3 12x3x1,3 0.45 1.5 24.0 767RE-2X(St)H-TiMF 16T1.3 16x3x1,3 0.45 1.6 27.4 1022RE-2X(St)H-TiMF 20T1.3 20x3x1,3 0.45 1.7 30.4 1252RE-2X(St)H-TiMF 24T1.3 24x3x1,3 0.45 1.8 33.1 1511
1.5mm2, Multi-striple RE-2X(St)H-TiMF 2T1.5 2x3x1,5 0.45 1.1 13.2 207RE-2X(St)H-TiMF 4T1.5 4x3x1,5 0.45 1.2 15.4 314RE-2X(St)H-TiMF 5T1.5 5x3x1,5 0.45 1.2 17.1 396RE-2X(St)H-TiMF 6T1.5 6x3x1,5 0.45 1.3 19.5 482RE-2X(St)H-TiMF 8T1.5 8x3x1,5 0.45 1.4 21.1 617
RE-2X(St)H-TiMF 10T1.5 10x3x1,5 0.45 1.5 24.1 765RE-2X(St)H-TiMF 12T1.5 12x3x1,5 0.45 1.5 24.9 867RE-2X(St)H-TiMF 16T1.5 16x3x1,5 0.45 1.6 28.4 1140RE-2X(St)H-TiMF 20T1.5 20x3x1,5 0.45 1.7 31.6 1421
ADDISON
Caledonian28
Caledonian Cable Code
RE-2X(St)H-TiMF
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2X(St)H-TiMF 24T1.5 24x3x1,5 0.45 1.8 34.4 1691
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
29ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (single Triple)
re-2X(st)HsWaH 70°c / 300 V
Galvenized Round Steel Wire
Plain Annealed Copper
XLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
LSZH Outer Sheath
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian30
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pair: Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmour: Galvenized round steel wire.outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Inductance mH/km(Max.) 1
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
www.caledonian-cables.co.uk www.addison-cables.com
31ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH 1T0.5 1x3x0.50 0.35 0.8 5.4 0.9 1.3 9.8 200
RE-2X(St)HSWAH 1T0.75 1x3x0.75 0.38 0.9 6.1 0.9 1.3 10.5 220RE-2X(St)HSWAH 1T1.0 1x3x1.0 0.4 0.9 6.6 0.9 1.3 11.0 244
RE-2X(St)HSWAH 1T1.3 1x3x1.3 0.45 0.9 7.2 0.9 1.3 11.6 268
RE-2X(St)HSWAH 1T1.5 1x3x1.5 0.45 0.9 7.5 0.9 1.3 11.9 293
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian32
XlPe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (Multitriple)
re-2Xst)HsWaH 70°c / 300 V
Galvenized Round Steel Wire
Plain Annealed Copper
XLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
LSZH Outer Sheath
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
www.caledonian-cables.co.uk www.addison-cables.com
33ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
No Toxic gases NES 02-713; NF C 20-454Sunlight Resistance UL 1581 section 1200Oil Resistance ICEA S-73-532**Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmour: Galvenized round steel wire.outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
ADDISON
Caledonian34
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Inductance mH/km(Max.) 1
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/km0.5mm2, Multi-striple
RE-2X(St)HSWAH 2T0.5 2x3x0.5 0.35 0.9 8.4 0.9 1.4 13.0 326RE-2X(St)HSWAH 4T0.5 4x3x0.5 0.35 1.0 9.8 0.9 1.4 14.4 386RE-2X(St)HSWAH 5T0.5 5x3x0.5 0.35 1.0 10.8 0.9 1.4 15.4 454RE-2X(St)HSWAH 6T0.5 6x3x0.5 0.35 1.0 12.1 0.9 1.4 16.7 513RE-2X(St)HSWAH 8T0.5 8x3x0.5 0.35 1.1 13.1 0.9 1.5 17.9 570
RE-2X(St)HSWAH 10T0.5 10x3x0.5 0.35 1.1 14.7 0.9 1.5 19.5 658RE-2X(St)HSWAH 12T0.5 12x3x0.5 0.35 1.1 15.2 0.9 1.5 20.0 844RE-2X(St)HSWAH 16T0.5 16x3x0.5 0.35 1.2 17.4 0.9 1.6 22.4 1001RE-2X(St)HSWAH 20T0.5 20x3x0.5 0.35 1.2 19.1 1.25 1.6 24.8 1177RE-2X(St)HSWAH 24T0.5 24x3x0.5 0.35 1.3 20.9 1.25 1.7 26.8 1327
0.75mm2, Multi-striple RE-2X(St)HSWAH 2T0.75 2x3x0.75 0.38 1.0 10.6 0.9 1.4 13.9 369RE-2X(St)HSWAH 4T0.75 4x3x0.75 0.38 1.1 12.4 0.9 1.4 15.5 462RE-2X(St)HSWAH 5T0.75 5x3x0.75 0.38 1.1 13.7 0.9 1.4 16.6 526RE-2X(St)HSWAH 6T0.75 6x3x0.75 0.38 1.1 15.4 0.9 1.5 18.5 614RE-2X(St)HSWAH 8T0.75 8x3x0.75 0.38 1.2 16.7 0.9 1.5 19.5 697RE-2X(St)HSWAH 10T0.75 10x3x0.75 0.38 1.3 19.0 0.9 1.5 21.5 918RE-2X(St)HSWAH 12T0.75 12x3x0.75 0.38 1.3 19.7 0.9 1.7 22.3 1027RE-2X(St)HSWAH 16T0.75 16x3x0.75 0.38 1.4 22.5 1.25 1.6 25.4 1237
www.caledonian-cables.co.uk www.addison-cables.com
35ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH 20T0.75 20x3x0.75 0.38 1.5 24.9 1.25 1.7 27.6 1443RE-2X(St)HSWAH 24T0.75 24x3x0.75 0.38 1.6 27.2 1.25 1.7 29.6 1628
1.0mm2, Multi-striple RE-2X(St)HSWAH 2T1.0 2x3x1 0.4 1.0 11.5 0.9 1.4 15.0 403RE-2X(St)HSWAH 4T1.0 4x3x1 0.4 1.1 13.4 0.9 1.4 16.5 528RE-2X(St)HSWAH 5T1.0 5x3x1 0.4 1.1 14.8 0.9 1.5 18.0 619RE-2X(St)HSWAH 6T1.0 6x3x1 0.4 1.2 16.9 0.9 1.5 19.8 829RE-2X(St)HSWAH 8T1.0 8x3x1 0.4 1.2 18.1 0.9 1.5 20.9 945
RE-2X(St)HSWAH 10T1.0 10x3x1 0.4 1.3 20.7 0.9 1.6 24.1 1074RE-2X(St)HSWAH 12T1.0 12x3x1 0.4 1.3 21.4 1.25 1.6 24.7 1212RE-2X(St)HSWAH 16T1.0 16x3x1 0.4 1.4 24.4 1.25 1.7 27.6 1478RE-2X(St)HSWAH 20T1.0 20x3x1 0.4 1.5 27.1 1.25 1.7 30.0 1736RE-2X(St)HSWAH 24T1.0 24x3x1 0.4 1.6 29.6 1.25 1.8 32.2 2197
1.3mm2, Multi-striple RE-2X(St)HSWAH 2T1.3 2x3x1,3 0.45 1.1 12.8 0.9 1.4 16.1 488RE-2X(St)HSWAH 4T1.3 4x3x1,3 0.45 1.1 14.7 0.9 1.5 18.2 620RE-2X(St)HSWAH 5T1.3 5x3x1,3 0.45 1.2 16.5 0.9 1.5 19.6 720RE-2X(St)HSWAH 6T1.3 6x3x1,3 0.45 1.3 18.8 0.9 1.5 21.7 952RE-2X(St)HSWAH 8T1.3 8x3x1,3 0.45 1.3 20.1 0.9 1.6 23.8 1076RE-2X(St)HSWAH 10T1.3 10x3x1,3 0.45 1.4 23.0 1.25 1.7 26.6 1320RE-2X(St)HSWAH 12T1.3 12x3x1,3 0.45 1.5 24.0 1.25 1.7 27.3 1454RE-2X(St)HSWAH 16T1.3 16x3x1,3 0.45 1.6 27.4 1.25 1.8 30.5 1785RE-2X(St)HSWAH 20T1.3 20x3x1,3 0.45 1.7 30.4 1.25 1.8 33.2 2323RE-2X(St)HSWAH 24T1.3 24x3x1,3 0.45 1.8 33.1 1.60 1.9 36.6 2633
1.5mm2, Multi-striple RE-2X(St)HSWAH 2T1.5 2x3x1,5 0.45 1.1 13.2 0.9 1.4 16.5 491RE-2X(St)HSWAH 4T1.5 4x3x1,5 0.45 1.2 15.4 0.9 1.5 18.8 673RE-2X(St)HSWAH 5T1.5 5x3x1,5 0.45 1.2 17.1 0.9 1.5 20.2 894RE-2X(St)HSWAH 6T1.5 6x3x1,5 0.45 1.3 19.5 0.9 1.6 22.6 1021
ADDISON
Caledonian36
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH 8T1.5 8x3x1,5 0.45 1.4 21.1 1.25 1.6 24.8 1208RE-2X(St)HSWAH 10T1.5 10x3x1,5 0.45 1.5 24.1 1.25 1.7 27.5 1433RE-2X(St)HSWAH 12T1.5 12x3x1,5 0.45 1.5 24.9 1.25 1.7 28.4 1565RE-2X(St)HSWAH 16T1.5 16x3x1,5 0.45 1.6 28.4 1.25 1.8 31.8 2157RE-2X(St)HSWAH 20T1.5 20x3x1,5 0.45 1.7 31.6 1.25 1.9 34.9 2510RE-2X(St)HSWAH 24T1.5 24x3x1,5 0.45 1.8 34.4 1.60 2.0 38.3 2873
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
37ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed, Individual & overall screened, armoured Instrumentation cables (Multitriple)
re-2X(st)HsWaH-TiMf 70°c / 300 V
Galvenized Round Steel Wire
Plain Annealed Copper
XLPE Insulation
Overall Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
LSZH Outer Sheath
Individual Aluminium/polyester Tape
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
ADDISON
Caledonian38
No Toxic gases NES 02-713; NF C 20-454Sunlight Resistance UL 1581 section 1200Oil Resistance ICEA S-73-532**Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Individual screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmour: Galvenized round steel wire.outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km(Max.) 1
www.caledonian-cables.co.uk www.addison-cables.com
39ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH-TiMF
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/km0.5mm2, Multi-striple
RE-2X(St)HSWAH-TiMF 2T0.5 2x3x0.5 0.35 1.0 9.7 0.9 1.4 14.3 363RE-2X(St)HSWAH-TiMF 4T0.5 4x3x0.5 0.35 1.0 11.1 0.9 1.4 15.7 456RE-2X(St)HSWAH-TiMF 5T0.5 5x3x0.5 0.35 1.1 12.4 0.9 1.5 17.2 516
RE-2X(St)HSWAH-TiMF 6T0.5 6x3x0.5 0.35 1.1 14.0 0.9 1.5 18.8 611
RE-2X(St)HSWAH-TiMF 8T0.5 8x3x0.5 0.35 1.1 14.9 0.9 1.5 19.7 766
RE-2X(St)HSWAH-TiMF 10T0.5 10x3x0.5 0.35 1.2 17.0 1.25 1.6 22.7 950RE-2X(St)HSWAH-TiMF 12T0.5 12x3x0.5 0.35 1.2 17.6 1.25 1.6 23.3 975RE-2X(St)HSWAH-TiMF 16T0.5 16x3x0.5 0.35 1.3 20.1 1.25 1.7 26.0 1169RE-2X(St)HSWAH-TiMF 20T0.5 20x3x0.5 0.35 1.4 22.3 1.25 1.7 28.2 1365RE-2X(St)HSWAH-TiMF 24T0.5 24x3x0.5 0.35 1.5 24.4 1.25 1.8 30.5 1604
0.75mm2, Multi-striple RE-2X(St)HSWAH-TiMF 2T0.75 2x3x0.75 0.38 1.0 10.6 0.9 1.4 15.2 408RE-2X(St)HSWAH-TiMF 4T0.75 4x3x0.75 0.38 1.1 12.4 0.9 1.5 17.2 521RE-2X(St)HSWAH-TiMF 5T0.75 5x3x0.75 0.38 1.1 13.7 0.9 1.5 18.5 590RE-2X(St)HSWAH-TiMF 6T0.75 6x3x0.75 0.38 1.1 15.4 0.9 1.5 20.2 819
RE-2X(St)HSWAH-TiMF 8T0.75 8x3x0.75 0.38 1.2 16.7 0.9 1.6 21.7 941
RE-2X(St)HSWAH-TiMF 10T0.7510x3x0.75 0.38 1.3 19.0 1.25 1.6 24.7 1103
RE-2X(St)HSWAH-TiMF 12T0.7512x3x0.75 0.38 1.3 19.7 1.25 1.7 25.6 1176
RE-2X(St)HSWAH-TiMF 16T0.7516x3x0.75 0.38 1.4 22.5 1.25 1.7 28.4 1439
ADDISON
Caledonian40
Caledonian Cable Code
RE-2X(St)HSWAH-TiMF
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH-TiMF 20T0.7520x3x0.75 0.38 1.5 24.9 1.25 1.8 31.0 1804RE-2X(St)HSWAH-TiMF 24T0.7524x3x0.75 0.38 1.6 27.2 1.25 1.9 33.5 2164
1.0mm2, Multi-striple RE-2X(St)HSWAH-TiMF 2T1.0 2x3x1 0.4 1.0 11.5 0.9 1.4 16.1 447RE-2X(St)HSWAH-TiMF 4T1.0 4x3x1 0.4 1.1 13.4 0.9 1.5 18.2 579RE-2X(St)HSWAH-TiMF 5T1.0 5x3x1 0.4 1.1 14.8 0.9 1.5 19.6 688RE-2X(St)HSWAH-TiMF 6T1.0 6x3x1 0.4 1.2 16.9 0.9 1.5 21.7 913RE-2X(St)HSWAH-TiMF 8T1.0 8x3x1 0.4 1.2 18.1 1.25 1.6 23.8 1033
RE-2X(St)HSWAH-TiMF 10T1.0 10x3x1 0.4 1.3 20.7 1.25 1.7 26.6 1277RE-2X(St)HSWAH-TiMF 12T1.0 12x3x1 0.4 1.3 21.4 1.25 1.7 27.3 1380
RE-2X(St)HSWAH-TiMF 16T1.0 16x3x1 0.4 1.4 24.4 1.25 1.7 30.3 1686
RE-2X(St)HSWAH-TiMF 20T1.0 20x3x1 0.4 1.5 27.1 1.25 1.8 33.2 2200RE-2X(St)HSWAH-TiMF 24T1.0 24x3x1 0.4 1.6 29.6 1.6 1.9 36.6 2504
1.3mm2, Multi-striple RE-2X(St)HSWAH-TiMF 2T1.3 2x3x1,3 0.45 1.1 12.8 0.9 1.5 17.6 532RE-2X(St)HSWAH-TiMF 4T1.3 4x3x1,3 0.45 1.1 14.7 0.9 1.5 19.5 684RE-2X(St)HSWAH-TiMF 5T1.3 5x3x1,3 0.45 1.2 16.5 0.9 1.6 21.5 924RE-2X(St)HSWAH-TiMF 6T1.3 6x3x1,3 0.45 1.3 18.8 1.25 1.6 24.5 1089RE-2X(St)HSWAH-TiMF 8T1.3 8x3x1,3 0.45 1.3 20.1 1.25 1.7 26.0 1249
RE-2X(St)HSWAH-TiMF 10T1.3 10x3x1,3 0.45 1.4 23.0 1.25 1.8 29.1 1482RE-2X(St)HSWAH-TiMF 12T1.3 12x3x1,3 0.45 1.5 24.0 1.25 1.8 30.1 1592RE-2X(St)HSWAH-TiMF 16T1.3 16x3x1,3 0.45 1.6 27.4 1.25 1.9 33.7 2222RE-2X(St)HSWAH-TiMF 20T1.3 20x3x1,3 0.45 1.7 30.4 1.6 2.0 37.6 2592RE-2X(St)HSWAH-TiMF 24T1.3 24x3x1,3 0.45 1.8 33.1 1.6 2.0 40.3 2957
RE-2X(St)HSWAH-TiMF 2T1.5 2x3x1,5 0.45 1.1 13.2 0.9 1.5 18.0 531RE-2X(St)HSWAH-TiMF 4T1.5 4x3x1,5 0.45 1.2 15.4 0.9 1.5 20.2 817RE-2X(St)HSWAH-TiMF 5T1.5 5x3x1,5 0.45 1.2 17.1 1.25 1.6 22.8 998
www.caledonian-cables.co.uk www.addison-cables.com
41ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH-TiMF
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2X(St)HSWAH-TiMF 6T1.5 6x3x1,5 0.45 1.3 19.5 1.25 1.6 25.2 1162RE-2X(St)HSWAH-TiMF 8T1.5 8x3x1,5 0.45 1.4 21.1 1.25 1.7 27.0 1304
RE-2X(St)HSWAH-TiMF 10T1.5 10x3x1,5 0.45 1.5 24.1 1.25 1.8 30.2 1541RE-2X(St)HSWAH-TiMF 12T1.5 12x3x1,5 0.45 1.5 24.9 1.25 1.8 31.0 1952RE-2X(St)HSWAH-TiMF 16T1.5 16x3x1,5 0.45 1.6 28.4 1.6 1.9 35.4 2384RE-2X(St)HSWAH-TiMF 20T1.5 20x3x1,5 0.45 1.7 31.6 1.6 2.0 38.8 2795RE-2X(St)HSWAH-TiMF 24T1.5 24x3x1,5 0.45 1.8 34.4 1.6 2.1 41.8 3093
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian42
XlPe Insulated, lsZH sheathed, cWb screened Instrumentation cables (single Pair)
re-2X(c)H 90°c / 300V
Copper Wire Braid Screen
LSZH Outer Sheath
Plain Annealed Copper
XLPE Insulation
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
43ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Tinned copper wire braidouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 300
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
ADDISON
Caledonian44
consTrUcTIon ParaMeTers
Caledonian Cable CodeRE-2X(C)H
No. of Pairsx2xCross Section
Copper Weight
Approx.Weight
No.x2xmm2 Kg/km Kg/kmRE-2X(C)H 1P0.5 1x2x0.50 8.3 110
RE-2X(C)H 1P0.75 1x2x0.75 8.7 119RE-2X(C)H 1P1.0 1x2x1.0 9.4 135RE-2X(C)H 1P1.3 1x2x1.3 9.7 140
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
45ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed, cWb screened Instrumentation cables (Multipair)
re-2X(c)H 90°c / 300V
Copper Wire Braid Screen
LSZH Outer Sheath
Plain Annealed CopperXLPE Insulation
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian46
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Tinned copper wire braidouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
≤ 4 pairs 115 115 115 120 120
all other pairs 90 90 90 105 105
Capacitance unbalance(1 kHz) pF/500 m (Max.) 300
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
www.caledonian-cables.co.uk www.addison-cables.com
47ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable CodeRE-2X(C)H
No. of Pairsx2xCross Section
Copper Weight
Approx. Weight
No.x2xmm2 Kg/km Kg/km0.5mm2, Multipair
RE-2X(C)H 2P0.5 2x2x0.50 10.7 143RE-2X(C)H 3P0.5 3x2x0.50 11.1 159RE-2X(C)H 4P0.5 4x2x0.50 11.9 181RE-2X(C)H 6P0.5 6x2x0.50 13.6 230RE-2X(C)H 8P0.5 8x2x0.50 14.2 264RE-2X(C)H 12P0.5 12x2x0.50 16.4 343RE-2X(C)H 16P0.5 16x2x0.50 18.2 418RE-2X(C)H 20P0.5 20x2x0.50 19.7 487RE-2X(C)H 24P0.5 24x2x0.50 21.1 557
0.75mm2, Multipair RE-2X(C)H 2P0.75 2x2x0.75 11.4 160RE-2X(C)H 3P0.75 3x2x0.75 11.9 185RE-2X(C)H 4P0.75 4x2x0.75 12.7 214RE-2X(C)H 6P0.75 6x2x0.75 14.6 278RE-2X(C)H 8P0.75 8x2x0.75 15.4 324
RE-2X(C)H 12P0.75 12x2x0.75 17.8 427RE-2X(C)H 16P0.75 16x2x0.75 19.8 526RE-2X(C)H 20P0.75 20.x2x0.75 21.5 623RE-2X(C)H 24P0.75 24x2x0.75 23.1 714
1.0mm2, Multipair RE-2X(C)H 2P1.0 2x2x1.0 12.3 184RE-2X(C)H 3P1.0 3x2x1.0 12.8 214RE-2X(C)H 4P1.0 4x2x1.0 13.7 251RE-2X(C)H 6P1.0 6x2x1.0 15.6 326RE-2X(C)H 8P1.0 8x2x1.0 16.4 382RE-2X(C)H 12P1.0 12x2x1.0 19.0 511RE-2X(C)H 16P1.0 16x2x1.0 21.2 636
ADDISON
Caledonian48
Caledonian Cable CodeRE-2X(C)H
No. of Pairsx2xCross Section
Copper Weight
Approx. Weight
No.x2xmm2 Kg/km Kg/kmRE-2X(C)H 20P1.0 20.x2x1.0 23.5 775RE-2X(C)H 24P1.0 24x2x1.0 25.3 892
1.3mm2, Multipair RE-2X(C)H 2P1.3 2x2x1.3 12.9 204RE-2X(C)H 3P1.3 3x2x1.3 13.5 242RE-2X(C)H 4P1.3 4x2x1.3 14.5 285RE-2X(C)H 6P1.3 6x2x1.3 16.7 375RE-2X(C)H 8P1.3 8x2x1.3 17.4 444RE-2X(C)H 12P1.3 12x2x1.3 20.2 599RE-2X(C)H 16P1.3 16x2x1.3 22.6 750RE-2X(C)H 20P1.3 20x2x1.3 25.1 916RE-2X(C)H 24P1.3 24x2x1.3 27.0 1064
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
49ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed & overall screened Instrumentation cables (single Pair)
re-2X(st)H 90°c / 300V
PETP Transparent Tape
LSZH Outer Sheath
Plain Annealed CopperXLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian50
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
www.caledonian-cables.co.uk www.addison-cables.com
51ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)H
No. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2X(St)H 1P0.5 1x2x0.50 0.35 0.8 5.2 38
RE-2X(St)H 1P0.75 1x2x0.75 0.38 0.8 5.6 49
RE-2X(St)H 1P1.0 1x2x1.0 0.40 0.9 6.3 56
RE-2X(St)H 1P1.3 1x2x1.3 0.45 0.9 6.8 65
RE-2X(St)H 1P1.5 1x2x1.5 0.45 0.9 7.1 71
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian52
XlPe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multipair)
re-2X(st)H 90°c / 300V
PETP Transparent Tape
LSZH Outer Sheath
Plain Annealed CopperXLPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
53ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIesConductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
ADDISON
Caledonian54
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HNo. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
0.5mm2, Multipair
RE-2X(St)H 2P0.5 2x2x0.5 0.35 0.9 7.6 66
RE-2X(St)H 4P0.5 3x2x0.5 0.35 0.9 8.8 98
RE-2X(St)H 5P0.5 4x2x0.5 0.35 1.0 9.8 112
RE-2X(St)H 6P0.5 5x2x0.5 0.35 1.0 10.6 133
RE-2X(St)H 8P0.5 8x2x0.5 0.35 1.0 11.3 161
RE-2X(St)H 10P0.5 10x2x0.5 0.35 1.1 12.9 200
RE-2X(St)H 12P0.5 12x2x0.5 0.35 1.1 13.5 242
RE-2X(St)H 16P0.5 16x2x0.5 0.35 1.1 15.2 288
RE-2X(St)H 20P0.5 20x2x0.5 0.35 1.2 16.9 376
RE-2X(St)H 24P0.5 24x2x0.5 0.35 1.2 18.3 426
0.75mm2, Multipair
RE-2X(St)H 2P0.75 2x2x0.75 0.38 0.9 8.5 87
RE-2X(St)H 4P0.75 3x2x0.75 0.38 1.0 10.0 122
RE-2X(St)H 5P0.75 4x2x0.75 0.38 1.0 10.9 154
RE-2X(St)H 6P0.75 5x2x0.75 0.38 1.0 11.8 174
RE-2X(St)H 8P0.75 8x2x0.75 0.38 1.1 12.8 213
RE-2X(St)H 10P0.75 10x2x0.75 0.38 1.1 14.5 266
RE-2X(St)H 12P0.75 12x2x0.75 0.38 1.1 15.1 304
RE-2X(St)H 16P0.75 16x2x0.75 0.38 1.2 17.3 398
RE-2X(St)H 20P0.75 20x2x0.75 0.38 1.3 19.2 478
RE-2X(St)H 24P0.75 24x2x0.75 0.38 1.3 20.8 559
www.caledonian-cables.co.uk www.addison-cables.com
55ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HNo. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
1.0mm2, Multipair
RE-2X(St)H 2P1.0 2x2x1.0 0.4 0.9 9.2 101
RE-2X(St)H 4P1.0 3x2x1.0 0.4 1.0 10.9 157
RE-2X(St)H 5P1.0 4x2x1.0 0.4 1.0 11.9 194
RE-2X(St)H 6P1.0 5x2x1.0 0.4 1.0 13.0 223
RE-2X(St)H 8P1.0 8x2x1.0 0.4 1.1 14.0 272
RE-2X(St)H 10P1.0 10x2x1.0 0.4 1.1 15.9 334
RE-2X(St)H 12P1.0 12x2x1.0 0.4 1.2 16.8 390
RE-2X(St)H 16P1.0 16x2x1.0 0.4 1.2 19.0 511
RE-2X(St)H 20P1.0 20x2x1.0 0.4 1.3 21.1 617
RE-2X(St)H 24P1.0 24x2x1.0 0.4 1.4 23.1 749
1.3mm2, Multipair
RE-2X(St)H 2P1.3 2x2x1.3 0.45 1.0 10.4 124
RE-2X(St)H 4P1.3 3x2x1.3 0.45 1.0 12.0 184
RE-2X(St)H 5P1.3 4x2x1.3 0.45 1.1 13.4 226
RE-2X(St)H 6P1.3 5x2x1.3 0.45 1.1 14.6 289
RE-2X(St)H 8P1.3 8x2x1.3 0.45 1.2 15.7 337
RE-2X(St)H 10P1.3 10x2x1.3 0.45 1.2 17.9 411
RE-2X(St)H 12P1.3 12x2x1.3 0.45 1.3 18.9 495
RE-2X(St)H 16P1.3 16x2x1.3 0.45 1.3 21.4 651
RE-2X(St)H 20P1.3 20x2x1.3 0.45 1.4 23.8 772
RE-2X(St)H 24P1.3 24x2x1.3 0.45 1.5 25.9 933
1.5mm2, Multipair
RE-2X(St)H 2P1.5 2x2x1.5 0.45 1.0 10.8 139*
RE-2X(St)H 4P1.5 3x2x1.5 0.45 1.1 12.7 214
RE-2X(St)H 5P1.5 4x2x1.5 0.45 1.1 14.0 259
RE-2X(St)H 6P1.5 5x2x1.5 0.45 1.2 15.2 305
ADDISON
Caledonian56
Caledonian Cable Code
RE-2X(St)HNo. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2X(St)H 8P1.5 8x2x1.5 0.45 1.2 16.4 385
RE-2X(St)H 10P1.5 10x2x1.5 0.45 1.3 18.8 460
RE-2X(St)H 12P1.5 12x2x1.5 0.45 1.3 19.7 558
RE-2X(St)H 16P1.5 16x2x1.5 0.45 1.4 22.5 725
RE-2X(St)H 20P1.5 20x2x1.5 0.45 1.5 25.0 881
RE-2X(St)H 24P1.5 24x2x1.5 0.45 1.5 27.1 147Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
57ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed & overall screened, armoured Instrumentation cables (single Pair)
re-2X(st)HsWaH 90°c / 300V
LSZH Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperXLPE Insulation
PETP Transparent Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian58
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²Inner sheath: LSZH compoundamouring: Galvanized steel wire armourouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 6 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
www.caledonian-cables.co.uk www.addison-cables.com
59ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Pairs
x2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2X(St)HSWAH 1P0.5 1x2x0.50 0.35 0.8 5.2 0.9 1.3 9.6 179
RE-2X(St)HSWAH 1P0.75 1x2x0.75 0.38 0.8 5.6 0.9 1.3 10.0 199
RE-2X(St)HSWAH 1P1.0 1x2x1.0 0.40 0.9 6.3 0.9 1.3 10.7 220
RE-2X(St)HSWAH 1P1.3 1x2x1.3 0.45 0.9 6.8 0.9 1.3 11.2 241
RE-2X(St)HSWAH 1P1.5 1x2x1.5 0.45 0.9 7.1 0.9 1.3 11.5 259
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian60
XlPe Insulated, lsZH sheathed & overall screened, armoured Instrumentation cables (Multipair)
re-2X(st)HsWaH 90°c / 300V
LSZH Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperXLPE Insulation
PETP Transparent Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
61ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300/500V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²Inner sheath: LSZH compoundamouring: Galvanized steel wire armourouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
up to 4 pairs 90 90 90 102 102
above 4 pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
ADDISON
Caledonian62
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
0.5mm2, MultipairRE-2X(St)HSWAH 2P0.5 2x2x0.5 0.35 0.9 7.6 0.9 1.3 12.0 269
RE-2X(St)HSWAH 4P0.5 3x2x0.5 0.35 0.9 8.8 0.9 1.4 13.4 325
RE-2X(St)HSWAH 5P0.5 4x2x0.5 0.35 1.0 9.8 0.9 1.4 14.4 375
RE-2X(St)HSWAH 6P0.5 5x2x0.5 0.35 1.0 10.6 0.9 1.4 15.2 423
RE-2X(St)HSWAH 8P0.5 8x2x0.5 0.35 1.0 11.3 0.9 1.4 15.9 473
RE-2X(St)HSWAH 10P0.5 10x2x0.5 0.35 1.1 12.9 0.9 1.5 17.7 521
RE-2X(St)HSWAH 12P0.5 12x2x0.5 0.35 1.1 13.5 0.9 1.5 18.3 592
RE-2X(St)HSWAH 16P0.5 16x2x0.5 0.35 1.1 15.2 0.9 1.5 20.0 823
RE-2X(St)HSWAH 20P0.5 20x2x0.5 0.35 1.2 16.9 0.9 1.6 21.9 920
RE-2X(St)HSWAH 24P0.5 24x2x0.5 0.35 1.2 18.3 1.25 1.6 24.0 1028
0.75mm2, Multipair
RE-2X(St)HSWAH 2P0.75 2x2x0.75 0.38 0.9 8.5 0.9 1.4 13.1 308
RE-2X(St)HSWAH 4P0.75 3x2x0.75 0.38 1.0 10.0 0.9 1.4 14.6 371
RE-2X(St)HSWAH 5P0.75 4x2x0.75 0.38 1.0 10.9 0.9 1.4 15.5 436
RE-2X(St)HSWAH 6P0.75 5x2x0.75 0.38 1.0 11.8 0.9 1.4 16.4 495
RE-2X(St)HSWAH 8P0.75 8x2x0.75 0.38 1.1 12.8 0.9 1.5 17.6 533
RE-2X(St)HSWAH 10P0.75 10x2x0.75 0.38 1.1 14.5 0.9 1.5 19.3 637
RE-2X(St)HSWAH 12P0.75 12x2x0.75 0.38 1.1 15.1 0.9 1.5 19.9 825
RE-2X(St)HSWAH 16P0.75 16x2x0.75 0.38 1.2 17.3 0.9 1.6 22.3 965
RE-2X(St)HSWAH 20P0.75 20x2x0.75 0.38 1.3 19.2 1.25 1.6 24.9 1116
RE-2X(St)HSWAH 24P0.75 24x2x0.75 0.38 1.3 20.8 1.25 1.6 26.7 1257
www.caledonian-cables.co.uk www.addison-cables.com
63ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
1.0mm2, Multipair
RE-2X(St)HSWAH 2P1.0 2x2x1.0 0.4 0.9 9.2 0.9 1.4 13.8 336
RE-2X(St)HSWAH 4P1.0 3x2x1.0 0.4 1.0 10.9 0.9 1.4 15.5 436
RE-2X(St)HSWAH 5P1.0 4x2x1.0 0.4 1.0 11.9 0.9 1.4 16.5 494
RE-2X(St)HSWAH 6P1.0 5x2x1.0 0.4 1.0 13.0 0.9 1.4 17.6 550
RE-2X(St)HSWAH 8P1.0 8x2x1.0 0.4 1.1 14.0 0.9 1.5 18.8 633
RE-2X(St)HSWAH 10P1.0 10x2x1.0 0.4 1.1 15.9 0.9 1.5 20.7 859
RE-2X(St)HSWAH 12P1.0 12x2x1.0 0.4 1.2 16.8 0.9 1.5 21.6 972
RE-2X(St)HSWAH 16P1.0 16x2x1.0 0.4 1.2 19.0 1.25 1.6 24.7 1171
RE-2X(St)HSWAH 20P1.0 20x2x1.0 0.4 1.3 21.1 1.25 1.7 27.0 1316
RE-2X(St)HSWAH 24P1.0 24x2x1.0 0.4 1.4 23.1 1.25 1.7 29.0 1520
1.3mm2, Multipair
RE-2X(St)HSWAH 2P1.3 2x2x1.3 0.45 1.0 10.4 0.9 1.4 15.0 382
RE-2X(St)HSWAH 4P1.3 3x2x1.3 0.45 1.0 12.0 0.9 1.4 16.6 510
RE-2X(St)HSWAH 5P1.3 4x2x1.3 0.45 1.1 13.4 0.9 1.5 18.2 595
RE-2X(St)HSWAH 6P1.3 5x2x1.3 0.45 1.1 14.6 0.9 1.5 19.4 657
RE-2X(St)HSWAH 8P1.3 8x2x1.3 0.45 1.2 15.7 0.9 1.5 20.5 869
RE-2X(St)HSWAH 10P1.3 10x2x1.3 0.45 1.2 17.9 0.9 1.6 23.6 1011
RE-2X(St)HSWAH 12P1.3 12x2x1.3 0.45 1.3 18.9 1.25 1.6 24.6 1110
RE-2X(St)HSWAH 16P1.3 16x2x1.3 0.45 1.3 21.4 1.25 1.7 27.3 1361
RE-2X(St)HSWAH 20P1.3 20x2x1.3 0.45 1.4 23.8 1.25 1.8 29.9 1599
RE-2X(St)HSWAH 24P1.3 24x2x1.3 0.45 1.5 25.9 1.25 1.8 32.0 1960
1.5mm2, Multipair
RE-2X(St)HSWAH 2P1.5 2x2x1.5 0.45 1.0 10.8 0.9 1.4 15.4 419
RE-2X(St)HSWAH 4P1.5 3x2x1.5 0.45 1.1 12.7 0.9 1.5 17.5 544
RE-2X(St)HSWAH 5P1.5 4x2x1.5 0.45 1.1 14.0 0.9 1.5 18.8 627
RE-2X(St)HSWAH 6P1.5 5x2x1.5 0.45 1.2 15.2 0.9 1.5 20.0 833
ADDISON
Caledonian64
Caledonian Cable Code
RE-2X(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2X(St)HSWAH 8P1.5 8x2x1.5 0.45 1.2 16.4 0.9 1.6 21.4 943
RE-2X(St)HSWAH 10P1.5 10x2x1.5 0.45 1.3 18.8 1.25 1.6 24.5 1095
RE-2X(St)HSWAH 12P1.5 12x2x1.5 0.45 1.3 19.7 1.25 1.7 25.6 1197
RE-2X(St)HSWAH 16P1.5 16x2x1.5 0.45 1.4 22.5 1.25 1.7 28.4 1511
RE-2X(St)HSWAH 20P1.5 20x2x1.5 0.45 1.5 25.0 1.25 1.8 31.1 1968
RE-2X(St)HSWAH 24P1.5 24x2x1.5 0.45 1.5 27.1 1.25 1.8 33.2 2247
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
500V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
65ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
XlPe Insulated, lsZH sheathed, Individual and overall screened Instrumentation cables (Multipair)
re-2X(st)H PiMf 90°c / 300V
PETP Transparent Tape
LSZH Outer Sheath
Plain Annealed CopperXLPE Insulation
Aluminium/polyester Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian66
VolTaGe raTInG300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmIndividual screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²binder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIesConductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
www.caledonian-cables.co.uk www.addison-cables.com
67ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)H PiMFNo. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
0.5mm2, Multipair
RE-2X(St)H PiMF 2P0.5 2x2x0.5 0.35 0.9 8.7 85
RE-2X(St)H PiMF 4P0.5 3x2x0.5 0.35 1.0 10.2 120
RE-2X(St)H PiMF 5P0.5 4x2x0.5 0.35 1.0 11.2 145
RE-2X(St)H PiMF 6P0.5 5x2x0.5 0.35 1.0 12.1 170
RE-2X(St)H PiMF 8P0.5 8x2x0.5 0.35 1.1 13.1 214
RE-2X(St)H PiMF 10P0.5 10x2x0.5 0.35 1.2 15.1 265
RE-2X(St)H PiMF 12P0.5 12x2x0.5 0.35 1.2 15.7 286
RE-2X(St)H PiMF 16P0.5 16x2x0.5 0.35 1.2 17.8 380
RE-2X(St)H PiMF 20P0.5 20x2x0.5 0.35 1.3 19.7 475
RE-2X(St)H PiMF 24P0.5 24x2x0.5 0.35 1.4 21.5 561
0.75mm2, Multipair
RE-2X(St)H PiMF 2P0.75 2x2x0.75 0.38 1.0 9.7 101
RE-2X(St)H PiMF 4P0.75 3x2x0.75 0.38 1.0 11.2 159
RE-2X(St)H PiMF 5P0.75 4x2x0.75 0.38 1.1 12.5 183
RE-2X(St)H PiMF 6P0.75 5x2x0.75 0.38 1.1 13.6 215
RE-2X(St)H PiMF 8P0.75 8x2x0.75 0.38 1.1 14.4 272
RE-2X(St)H PiMF 10P0.75 10x2x0.75 0.38 1.2 16.6 333
RE-2X(St)H PiMF 12P0.75 12x2x0.75 0.38 1.2 17.4 383
RE-2X(St)H PiMF 16P0.75 16x2x0.75 0.38 1.3 19.8 492
RE-2X(St)H PiMF 20P0.75 20x2x0.75 0.38 1.4 22.0 603
RE-2X(St)H PiMF 24P0.75 24x2x0.75 0.38 1.5 24.0 704
1.0mm2, Multipair
RE-2X(St)H PiMF 2P1.0 2x2x1.0 0.4 1.0 10.4 112
ADDISON
Caledonian68
Caledonian Cable Code
RE-2X(St)H PiMFNo. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2X(St)H PiMF 4P1.0 3x2x1.0 0.4 1.0 12.1 179
RE-2X(St)H PiMF 5P1.0 4x2x1.0 0.4 1.1 13.5 220
RE-2X(St)H PiMF 6P1.0 5x2x1.0 0.4 1.1 14.7 256
RE-2X(St)H PiMF 8P1.0 8x2x1.0 0.4 1.2 15.8 323
RE-2X(St)H PiMF 10P1.0 10x2x1.0 0.4 1.2 18.0 401
RE-2X(St)H PiMF 12P1.0 12x2x1.0 0.4 1.3 19.0 454
RE-2X(St)H PiMF 16P1.0 16x2x1.0 0.4 1.3 21.5 601
RE-2X(St)H PiMF 20P1.0 20x2x1.0 0.4 1.4 23.9 719
RE-2X(St)H PiMF 24P1.0 24x2x1.0 0.4 1.5 26.1 884
1.3mm2, Multipair
RE-2X(St)H PiMF 2P1.3 2x2x1.3 0.45 1.0 11.4 153
RE-2X(St)H PiMF 4P1.3 3x2x1.3 0.45 1.1 13.4 208
RE-2X(St)H PiMF 5P1.3 4x2x1.3 0.45 1.1 14.8 263
RE-2X(St)H PiMF 6P1.3 5x2x1.3 0.45 1.2 16.3 318
RE-2X(St)H PiMF 8P1.3 8x2x1.3 0.45 1.3 17.6 406
RE-2X(St)H PiMF 10P1.3 10x2x1.3 0.45 1.3 20.0 501
RE-2X(St)H PiMF 12P1.3 12x2x1.3 0.45 1.4 21.1 552
RE-2X(St)H PiMF 16P1.3 16x2x1.3 0.45 1.5 24.1 728
RE-2X(St)H PiMF 20P1.3 20x2x1.3 0.45 1.6 26.8 892
RE-2X(St)H PiMF 24P1.3 24x2x1.3 0.45 1.7 29.2 1067
1.5mm2, Multipair
RE-2X(St)H PiMF 2P1.5 2x2x1.5 0.45 1.0 11.8 164
RE-2X(St)H PiMF 4P1.5 3x2x1.5 0.45 1.1 13.9 235
RE-2X(St)H PiMF 5P1.5 4x2x1.5 0.45 1.2 15.5 289
RE-2X(St)H PiMF 6P1.5 5x2x1.5 0.45 1.2 16.9 366
RE-2X(St)H PiMF 8P1.5 8x2x1.5 0.45 1.3 18.2 446
RE-2X(St)H PiMF 10P1.5 10x2x1.5 0.45 1.4 21.0 565
www.caledonian-cables.co.uk www.addison-cables.com
69ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)H PiMFNo. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2X(St)H PiMF 12P1.5 12x2x1.5 0.45 1.4 21.9 637
RE-2X(St)H PiMF 16P1.5 16x2x1.5 0.45 1.5 25.1 828
RE-2X(St)H PiMF 20P1.5 20x2x1.5 0.45 1.6 27.8 1024
RE-2X(St)H PiMF 24P1.5 24x2x1.5 0.45 1.7 30.4 1219Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian70
XlPe Insulated, lsZH sheathed, Individual and overall screened & armoured Instrumentation cables (Multipair)
re-2X(st)HsWaH PiMf 90°c / 300V
LSZH Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperXLPE Insulation
PETP Transparent Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
Aluminium/polyester Tape
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
71ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: Extruded cross-linked XLPE compound as per EN 50290-2-29.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmIndividual screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²binder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²Inner sheath: LSZH compoundamouring: Galvanized steel wire armourouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -20°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIesConductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
ADDISON
Caledonian72
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH PiMF
No. of Pairs
x2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
0.5mm2, MultipairRE-2X(St)HSWAH PiMF 2P0.5 2x2x0.5 0.35 0.9 8.7 0.9 1.4 13.3 311
RE-2X(St)HSWAH PiMF 4P0.5 3x2x0.5 0.35 1.0 10.2 0.9 1.4 14.8 373
RE-2X(St)HSWAH PiMF 5P0.5 4x2x0.5 0.35 1.0 11.2 0.9 1.4 15.8 451
RE-2X(St)HSWAH PiMF 6P0.5 5x2x0.5 0.35 1.0 12.1 0.9 1.6 16.9 483
RE-2X(St)HSWAH PiMF 8P0.5 8x2x0.5 0.35 1.1 13.1 0.9 1.6 17.9 537
RE-2X(St)HSWAH PiMF 10P0.5 10x2x0.5 0.35 1.2 15.1 0.9 1.5 19.9 781
RE-2X(St)HSWAH PiMF 12P0.5 12x2x0.5 0.35 1.2 15.7 0.9 1.5 20.5 804
RE-2X(St)HSWAH PiMF 16P0.5 16x2x0.5 0.35 1.2 17.8 1.25 1.6 23.5 968
RE-2X(St)HSWAH PiMF 20P0.5 20x2x0.5 0.35 1.3 19.7 1.25 1.7 25.6 1143
RE-2X(St)HSWAH PiMF 24P0.5 24x2x0.5 0.35 1.4 21.5 1.25 1.7 27.4 1264
0.75mm2, Multipair
RE-2X(St)HSWAH PiMF 2P0.75 2x2x0.75 0.38 1.0 9.7 0.9 1.4 14.3 342
RE-2X(St)HSWAH PiMF 4P0.75 3x2x0.75 0.38 1.0 11.2 0.9 1.4 15.8 439
RE-2X(St)HSWAH PiMF 5P0.75 4x2x0.75 0.38 1.1 12.5 0.9 1.5 17.3 496
RE-2X(St)HSWAH PiMF 6P0.75 5x2x0.75 0.38 1.1 13.6 0.9 1.5 18.4 578
RE-2X(St)HSWAH PiMF 8P0.75 8x2x0.75 0.38 1.1 14.4 0.9 1.5 19.2 664
RE-2X(St)HSWAH PiMF 10P0.7510x2x0.75 0.38 1.2 16.6 1.25 1.6 22.3 876
RE-2X(St)HSWAH PiMF 12P0.7512x2x0.75 0.38 1.2 17.4 1.25 1.6 23.1 942
RE-2X(St)HSWAH PiMF 16P0.7516x2x0.75 0.38 1.3 19.8 1.25 1.7 25.7 1130
RE-2X(St)HSWAH PiMF 20P0.7520x2x0.75 0.38 1.4 22.0 1.25 1.7 27.9 1325
RE-2X(St)HSWAH PiMF 24P0.7524x2x0.75 0.38 1.5 24.0 1.25 1.8 30.1 1490
www.caledonian-cables.co.uk www.addison-cables.com
73ADDISON
caledonianXlPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH PiMF
No. of Pairs
x2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
1.0mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.0 2x2x1.0 0.4 1.0 10.4 0.9 1.4 15.0 382
RE-2X(St)HSWAH PiMF 4P1.0 3x2x1.0 0.4 1.0 12.1 0.9 1.4 16.7 487
RE-2X(St)HSWAH PiMF 5P1.0 4x2x1.0 0.4 1.1 13.5 0.9 1.5 18.3 566
RE-2X(St)HSWAH PiMF 6P1.0 5x2x1.0 0.4 1.1 14.7 0.9 1.5 19.5 641
RE-2X(St)HSWAH PiMF 8P1.0 8x2x1.0 0.4 1.2 15.8 0.9 1.5 20.6 718
RE-2X(St)HSWAH PiMF 10P1.0 10x2x1.0 0.4 1.2 18.0 1.25 1.6 23.7 994
RE-2X(St)HSWAH PiMF 12P1.0 12x2x1.0 0.4 1.3 19.0 1.25 1.7 24.7 1083
RE-2X(St)HSWAH PiMF 16P1.0 16x2x1.0 0.4 1.3 21.5 1.25 1.7 27.4 1361
RE-2X(St)HSWAH PiMF 20P1.0 20x2x1.0 0.4 1.4 23.9 1.25 1.7 29.8 1510
RE-2X(St)HSWAH PiMF 24P1.0 24x2x1.0 0.4 1.5 26.1 1.25 1.8 32.2 1902
1.3mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.3 2x2x1.3 0.45 1.0 11.4 0.9 1.4 16.0 452
RE-2X(St)HSWAH PiMF 4P1.3 3x2x1.3 0.45 1.1 13.4 0.9 1.5 18.2 576
RE-2X(St)HSWAH PiMF 5P1.3 4x2x1.3 0.45 1.1 14.8 0.9 1.5 19.6 647
RE-2X(St)HSWAH PiMF 6P1.3 5x2x1.3 0.45 1.2 16.3 0.9 1.6 21.3 857
RE-2X(St)HSWAH PiMF 8P1.3 8x2x1.3 0.45 1.3 17.6 1.25 1.6 23.3 980
RE-2X(St)HSWAH PiMF 10P1.3 10x2x1.3 0.45 1.3 20.0 1.25 1.7 25.9 1195
RE-2X(St)HSWAH PiMF 12P1.3 12x2x1.3 0.45 1.4 21.1 1.25 1.7 27.0 1256
RE-2X(St)HSWAH PiMF 16P1.3 16x2x1.3 0.45 1.5 24.1 1.25 1.8 30.2 1562
RE-2X(St)HSWAH PiMF 20P1.3 20x2x1.3 0.45 1.6 26.8 1.25 1.9 33.1 1958
RE-2X(St)HSWAH PiMF 24P1.3 24x2x1.3 0.45 1.7 29.2 1.25 2.0 36.4 2251
1.5mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.5 2x2x1.5 0.45 1.0 11.8 0.9 1.5 16.6 475
RE-2X(St)HSWAH PiMF 4P1.5 3x2x1.5 0.45 1.1 13.9 0.9 1.5 18.7 599
RE-2X(St)HSWAH PiMF 5P1.5 4x2x1.5 0.45 1.2 15.5 0.9 1.5 20.3 818
RE-2X(St)HSWAH PiMF 6P1.5 5x2x1.5 0.45 1.2 16.9 1.25 1.6 22.6 940
ADDISON
Caledonian74
Caledonian Cable Code
RE-2X(St)HSWAH PiMF
No. of Pairs
x2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2X(St)HSWAH PiMF 8P1.5 8x2x1.5 0.45 1.3 18.2 1.25 1.7 24.1 1037
RE-2X(St)HSWAH PiMF 10P1.5 10x2x1.5 0.45 1.4 21.0 1.25 1.7 26.9 1273
RE-2X(St)HSWAH PiMF 12P1.5 12x2x1.5 0.45 1.4 21.9 1.25 1.7 27.8 1353
RE-2X(St)HSWAH PiMF 16P1.5 16x2x1.5 0.45 1.5 25.1 1.25 1.8 31.2 1932
RE-2X(St)HSWAH PiMF 20P1.5 20x2x1.5 0.45 1.6 27.8 1.25 1.9 34.8 2224
RE-2X(St)HSWAH PiMF 24P1.5 24x2x1.5 0.45 1.7 30.4 1.25 2.0 37.6 2541
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
75ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multicore)
re-2y(st)H 90°c / 500V
LSZH Outer Sheath
Plain Annealed CopperPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian76
VolTaGe raTInG
500V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.overall screen: Aluminium/polyester tape with 0.5mm2 screen (7/0.3mm) tinned copper drain wire.Inner sheath(optional): LSZH compoundarmouring(optional): Galvanised steel wire outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / Blue, continuously numbered on blue core(1, 2..) for wrapped conductorouter sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5 2.5
Insulation thickness (nominal) mm 0.55 0.55 0.55 0.6 0.6 0.7
Conductor resistance (20°C) Ω/km 36.0 24.5 18.1 13.9 12.1 7.4
Insulation resistance (20°C) MΩ.km(Min.) 5000Mutual Capacitance (1 kHz) pF/m(Max.) 115Capacitance unbalance(1 kHz) pF/500 m (Max.) 500 L / R (ratio) (max.) μH/Ω 25 25 25 40 40 60Operating voltage V 500
Test Voltage Urms
Core to Core V 2000
Core to Screen V 2000
www.caledonian-cables.co.uk www.addison-cables.com
77ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HNo. of Cores
x1xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km0.5mm2, Multicore
RE-2Y(St)H 2C0.5 2x1x0.5 0.55 0.9 6.2 45
RE-2Y(St)H 3C0.5 3x1x0.5 0.55 0.9 6.5 53
RE-2Y(St)H 4C0.5 4x1x0.5 0.55 0.9 7.0 60
RE-2Y(St)H 5C0.5 5x1x0.5 0.55 0.9 7.6 71
RE-2Y(St)H 8C0.5 8x1x0.5 0.55 1.0 9.1 95
RE-2Y(St)H 10C0.5 10x1x0.5 0.55 1.0 10.4 122
RE-2Y(St)H 12C0.5 12x1x0.5 0.55 1.0 10.7 145
RE-2Y(St)H 14C0.5 14x1x0.5 0.55 1.0 11.3 162
RE-2Y(St)H 16C0.5 16x1x0.5 0.55 1.1 11.8 180
RE-2Y(St)H 20C0.5 20x1x0.5 0.55 1.1 13.3 214
RE-2Y(St)H 24C0.5 24x1x0.5 0.55 1.1 14.7 258
RE-2Y(St)H 27C0.5 27x1x0.5 0.55 1.2 15.0 282
RE-2Y(St)H 30C0.5 30x1x0.5 0.55 1.2 15.7 308
RE-2Y(St)H 37C0.5 37x1x0.5 0.55 1.2 16.9 372
RE-2Y(St)H 40C0.5 40x1x0.5 0.55 1.2 17.6 398
0.75mm2, Multicore
RE-2Y(St)H 2C0.75 2x1x0.75 0.55 0.9 6.5
RE-2Y(St)H 3C0.75 3x1x0.75 0.55 0.9 6.9
RE-2Y(St)H 4C0.75 4x1x0.75 0.55 0.9 7.4
RE-2Y(St)H 5C0.75 5x1x0.75 0.55 0.9 8.1
RE-2Y(St)H 8C0.75 8x1x0.75 0.55 1.0 9.7
RE-2Y(St)H 10C0.75 10x1x0.75 0.55 1.0 11.1
RE-2Y(St)H 12C0.75 12x1x0.75 0.55 1.0 11.5
RE-2Y(St)H 14C0.75 14x1x0.75 0.55 1.1 12.2
RE-2Y(St)H 16C0.75 16x1x0.75 0.55 1.1 12.9
RE-2Y(St)H 20C0.75 20x1x0.75 0.55 1.1 14.3
RE-2Y(St)H 24C0.75 24x1x0.75 0.55 1.2 16.0
ADDISON
Caledonian78
Caledonian Cable Code
RE-2Y(St)HNo. of Cores
x1xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
RE-2Y(St)H 27C0.75 27x1x0.75 0.55 1.2 16.3
RE-2Y(St)H 30C0.75 30x1x0.75 0.55 1.2 16.9
RE-2Y(St)H 37C0.75 37x1x0.75 0.55 1.2 18.2
RE-2Y(St)H 40C0.75 40x1x0.75 0.55 1.3 19.1
1.0mm2, Multicore
RE-2Y(St)H 2C1.0 2x1x1.0 0.55 0.9 6.9 58
RE-2Y(St)H 3C1.0 3x1x1.0 0.55 0.9 7.3 70
RE-2Y(St)H 4C1.0 4x1x1.0 0.55 0.9 7.9 85
RE-2Y(St)H 5C1.0 5x1x1.0 0.55 0.9 8.6 98
RE-2Y(St)H 8C1.0 8x1x1.0 0.55 1.0 10.3 136
RE-2Y(St)H 10C1.0 10x1x1.0 0.55 1.0 11.9 194
RE-2Y(St)H 12C1.0 12x1x1.0 0.55 1.0 12.2 214
RE-2Y(St)H 14C1.0 14x1x1.0 0.55 1.1 13.0 243
RE-2Y(St)H 16C1.0 16x1x1.0 0.55 1.1 13.7 280
RE-2Y(St)H 20C1.0 20x1x1.0 0.55 1.1 15.2 336
RE-2Y(St)H 24C1.0 24x1x1.0 0.55 1.2 17.0 404
RE-2Y(St)H 27C1.0 27x1x1.0 0.55 1.2 17.4 443
RE-2Y(St)H 30C1.0 30x1x1.0 0.55 1.2 18.0 484
RE-2Y(St)H 37C1.0 37x1x1.0 0.55 1.2 19.6 590
RE-2Y(St)H 40C1.0 40x1x1.0 0.55 1.3 20.4 632
1.3mm2, Multicore
RE-2Y(St)H 2C1.3 2x1x1.3 0.6 0.9 7.4 72
RE-2Y(St)H 3C1.3 3x1x1.3 0.6 0.9 7.9 86
RE-2Y(St)H 4C1.3 4x1x1.3 0.6 0.9 8.5 105
RE-2Y(St)H 5C1.3 5x1x1.3 0.6 1.0 9.5 135
RE-2Y(St)H 8C1.3 8x1x1.3 0.6 1.0 11.2 176
RE-2Y(St)H 10C1.3 10x1x1.3 0.6 1.1 13.2 228
www.caledonian-cables.co.uk www.addison-cables.com
79ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)HNo. of Cores
x1xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
RE-2Y(St)H 12C1.3 12x1x1.3 0.6 1.1 13.6 269
RE-2Y(St)H 14C1.3 14x1x1.3 0.6 1.1 14.3 305
RE-2Y(St)H 16C1.3 16x1x1.3 0.6 1.1 15.0 351
RE-2Y(St)H 20C1.3 20x1x1.3 0.6 1.2 16.9 423
RE-2Y(St)H 24C1.3 24x1x1.3 0.6 1.2 18.7 507
RE-2Y(St)H 27C1.3 27x1x1.3 0.6 1.3 19.3 558
RE-2Y(St)H 30C1.3 30x1x1.3 0.6 1.3 20.0 611
RE-2Y(St)H 37C1.3 37x1x1.3 0.6 1.3 21.6 743
RE-2Y(St)H 40C1.3 40x1x1.3 0.6 1.4 22.7 796
1.5mm2, Multicore
RE-2Y(St)H 2C1.5 2x1x1.5 0.6 0.9 7.7 78
RE-2Y(St)H 3C1.5 3x1x1.5 0.6 0.9 8.1 94
RE-2Y(St)H 4C1.5 4x1x1.5 0.6 0.9 8.8 116
RE-2Y(St)H 5C1.5 5x1x1.5 0.6 1.0 9.8 149
RE-2Y(St)H 8C1.5 8x1x1.5 0.6 1.0 11.6 196
RE-2Y(St)H 10C1.5 10x1x1.5 0.6 1.1 13.7 261
RE-2Y(St)H 12C1.5 12x1x1.5 0.6 1.1 14.1 300
RE-2Y(St)H 14C1.5 14x1x1.5 0.6 1.1 14.8 340
RE-2Y(St)H 16C1.5 16x1x1.5 0.6 1.1 15.6 392
RE-2Y(St)H 20C1.5 20x1x1.5 0.6 1.2 17.6 474
RE-2Y(St)H 24C1.5 24x1x1.5 0.6 1.3 19.6 567
RE-2Y(St)H 27C1.5 27x1x1.5 0.6 1.3 20.1 625
RE-2Y(St)H 30C1.5 30x1x1.5 0.6 1.3 20.8 685
RE-2Y(St)H 37C1.5 37x1x1.5 0.6 1.4 22.6 834
RE-2Y(St)H 40C1.5 40x1x1.5 0.6 1.4 23.6 898
2.5mm2, Multicore
RE-2Y(St)H 2C2.5 2x1x2.5 0.7 0.9 8.9 113
ADDISON
Caledonian80
Caledonian Cable Code
RE-2Y(St)HNo. of Cores
x1xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm kg/km
RE-2Y(St)H 3C2.5 3x1x2.5 0.7 1.0 9.7 145
RE-2Y(St)H 4C2.5 4x1x2.5 0.7 1.0 10.5 178
RE-2Y(St)H 5C2.5 5x1x2.5 0.7 1.0 11.9 285
RE-2Y(St)H 8C2.5 8x1x2.5 0.7 1.1 13.9 376
RE-2Y(St)H 10C2.5 10x1x2.5 0.7 1.2 16.3 426
RE-2Y(St)H 12C2.5 12x1x2.5 0.7 1.2 16.9 537
RE-2Y(St)H 14C2.5 14x1x2.5 0.7 1.2 17.7 609
RE-2Y(St)H 16C2.5 16x1x2.5 0.7 1.3 18.9 711
RE-2Y(St)H 20C2.5 20x1x2.5 0.7 1.3 21.1 826
RE-2Y(St)H 24C2.5 24x1x2.5 0.7 1.4 23.6 930
RE-2Y(St)H 27C2.5 27x1x2.5 0.7 1.4 24.1 1040
RE-2Y(St)H 30C2.5 30x1x2.5 0.7 1.5 25.2 1142
RE-2Y(St)H 37C2.5 37x1x2.5 0.7 1.5 27.2 1392
RE-2Y(St)H 40C2.5 40x1x2.5 0.7 1.6 28.5 1494Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
500V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
81ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (Multicore)
re-2y(st)HsWaH 90°c / 500V
LSZH Inner Sheath
LSZH Outer Sheath
Plain Annealed CopperPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
Steel Wire Armoured
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian82
VolTaGe raTInG
500V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.overall screen: Aluminium/polyester tape with 0.5mm2 screen (7/0.3mm) tinned copper drain wire.Inner sheath: LSZH compoundarmouring: Galvanised steel wire outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / Blue, continuously numbered on blue core(1, 2..) for wrapped conductorouter sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5 2.5
Insulation thickness (nominal) mm 0.55 0.55 0.55 0.6 0.6 0.7
Conductor resistance (20°C) Ω/km 36.0 24.5 18.1 13.9 12.1 7.4
Insulation resistance (20°C) MΩ.km(Min.) 5000 5000 5000 5000 5000 2000
Mutual Capacitance (1 kHz) pF/m(Max.) 115 115 115 115 115 2000
Inductance mH/km(Max.) 1 1 1 1 1 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40 10Operating voltage V 500
Test Voltage Urms
Core to Core V 2000
Core to Screen V 2000
www.caledonian-cables.co.uk www.addison-cables.com
83ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Cores
x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/km0.5mm2, Multicore
RE-2Y(St)HSWAH 2C0.5 2x1x0.5 0.55 0.9 6.2 0.9 1.3 10.6 217RE-2Y(St)HSWAH 3C0.5 3x1x0.5 0.55 0.9 6.5 0.9 1.3 10.9 230RE-2Y(St)HSWAH 4C0.5 4x1x0.5 0.55 0.9 7.0 0.9 1.3 11.4 253RE-2Y(St)HSWAH 5C0.5 5x1x0.5 0.55 0.9 7.6 0.9 1.3 12.0 283RE-2Y(St)HSWAH 8C0.5 8x1x0.5 0.55 1.0 9.1 0.9 1.4 13.7 337RE-2Y(St)HSWAH 10C0.5 10x1x0.5 0.55 1.0 10.4 0.9 1.4 15.0 399RE-2Y(St)HSWAH 12C0.5 12x1x0.5 0.55 1.0 10.7 0.9 1.4 15.3 442RE-2Y(St)HSWAH 14C0.5 14x1x0.5 0.55 1.0 11.3 0.9 1.4 15.9 474RE-2Y(St)HSWAH 16C0.5 16x1x0.5 0.55 1.1 11.8 0.9 1.4 16.4 505RE-2Y(St)HSWAH 20C0.5 20x1x0.5 0.55 1.1 13.3 0.9 1.5 18.1 569RE-2Y(St)HSWAH 24C0.5 24x1x0.5 0.55 1.1 14.7 0.9 1.5 19.5 659RE-2Y(St)HSWAH 27C0.5 27x1x0.5 0.55 1.2 15.0 0.9 1.5 19.8 808RE-2Y(St)HSWAH 30C0.5 30x1x0.5 0.55 1.2 15.7 0.9 1.5 20.5 848RE-2Y(St)HSWAH 37C0.5 37x1x0.5 0.55 1.2 16.9 0.9 1.6 21.9 963RE-2Y(St)HSWAH 40C0.5 40x1x0.5 0.55 1.2 17.6 1.25 1.6 23.3 1014
0.75mm2, MulticoreRE-2Y(St)HSWAH 2C0.75 2x1x0.75 0.55 0.9 6.5 0.9 1.3 10.9 345RE-2Y(St)HSWAH 3C0.75 3x1x0.75 0.55 0.9 6.9 0.9 1.3 11.3 420RE-2Y(St)HSWAH 4C0.75 4x1x0.75 0.55 0.9 7.4 0.9 1.3 11.8 507RE-2Y(St)HSWAH 5C0.75 5x1x0.75 0.55 0.9 8.1 0.9 1.4 12.7 609RE-2Y(St)HSWAH 8C0.75 8x1x0.75 0.55 1.0 9.7 0.9 1.4 14.3 846RE-2Y(St)HSWAH 10C0.75 10x1x0.75 0.55 1.0 11.1 0.9 1.4 15.7 1035RE-2Y(St)HSWAH 12C0.75 12x1x0.75 0.55 1.0 11.5 0.9 1.4 16.1 1183RE-2Y(St)HSWAH 14C0.75 14x1x0.75 0.55 1.1 12.2 0.9 1.5 17.0 1334RE-2Y(St)HSWAH 16C0.75 16x1x0.75 0.55 1.1 12.9 0.9 1.5 17.7 1495RE-2Y(St)HSWAH 20C0.75 20x1x0.75 0.55 1.1 14.3 0.9 1.5 19.1 1823RE-2Y(St)HSWAH 24C0.75 24x1x0.75 0.55 1.2 16.0 0.9 1.5 20.8 2258RE-2Y(St)HSWAH 27C0.75 27x1x0.75 0.55 1.2 16.3 0.9 1.6 21.3 2482RE-2Y(St)HSWAH 30C0.75 30x1x0.75 0.55 1.2 16.9 0.9 1.6 21.9 2713
ADDISON
Caledonian84
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Cores
x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH 37C0.75 37x1x0.75 0.55 1.2 18.2 1.25 1.6 23.9 3231RE-2Y(St)HSWAH 40C0.75 40x1x0.75 0.55 1.3 19.1 1.25 1.6 24.8 3483
1.0mm2, MulticoreRE-2Y(St)HSWAH 2C1.0 2x1x1.0 0.55 0.9 6.9 0.9 1.3 11.3 247RE-2Y(St)HSWAH 3C1.0 3x1x1.0 0.55 0.9 7.3 0.9 1.3 11.7 270RE-2Y(St)HSWAH 4C1.0 4x1x1.0 0.55 0.9 7.9 0.9 1.4 12.5 299RE-2Y(St)HSWAH 5C1.0 5x1x1.0 0.55 0.9 8.6 0.9 1.4 13.2 342RE-2Y(St)HSWAH 8C1.0 8x1x1.0 0.55 1.0 10.3 0.9 1.4 14.9 417RE-2Y(St)HSWAH 10C1.0 10x1x1.0 0.55 1.0 11.9 0.9 1.4 16.5 514RE-2Y(St)HSWAH 12C1.0 12x1x1.0 0.55 1.0 12.2 0.9 1.5 17.0 548RE-2Y(St)HSWAH 14C1.0 14x1x1.0 0.55 1.1 13.0 0.9 1.5 17.8 590RE-2Y(St)HSWAH 16C1.0 16x1x1.0 0.55 1.1 13.7 0.9 1.5 18.5 649RE-2Y(St)HSWAH 20C1.0 20x1x1.0 0.55 1.1 15.2 0.9 1.5 20.0 864RE-2Y(St)HSWAH 24C1.0 24x1x1.0 0.55 1.2 17.0 0.9 1.6 22.0 1005RE-2Y(St)HSWAH 27C1.0 27x1x1.0 0.55 1.2 17.4 1.25 1.6 23.1 1058RE-2Y(St)HSWAH 30C1.0 30x1x1.0 0.55 1.2 18.0 1.25 1.6 23.7 1113RE-2Y(St)HSWAH 37C1.0 37x1x1.0 0.55 1.2 19.6 1.25 1.6 25.3 1271RE-2Y(St)HSWAH 40C1.0 40x1x1.0 0.55 1.3 20.4 1.25 1.7 26.3 1351
1.3mm2, MulticoreRE-2Y(St)HSWAH 2C1.3 2x1x1.3 0.6 0.9 7.4 0.9 1.3 11.8 275RE-2Y(St)HSWAH 3C1.3 3x1x1.3 0.6 0.9 7.9 0.9 1.3 12.3 301RE-2Y(St)HSWAH 4C1.3 4x1x1.3 0.6 0.9 8.5 0.9 1.4 13.1 340RE-2Y(St)HSWAH 5C1.3 5x1x1.3 0.6 1.0 9.5 0.9 1.4 14.1 383RE-2Y(St)HSWAH 8C1.3 8x1x1.3 0.6 1.0 11.2 0.9 1.4 15.8 436RE-2Y(St)HSWAH 10C1.3 10x1x1.3 0.6 1.1 13.2 0.9 1.5 18.0 578RE-2Y(St)HSWAH 12C1.3 12x1x1.3 0.6 1.1 13.6 0.9 1.5 18.4 633RE-2Y(St)HSWAH 14C1.3 14x1x1.3 0.6 1.1 14.3 0.9 1.5 19.1 698RE-2Y(St)HSWAH 16C1.3 16x1x1.3 0.6 1.1 15.0 0.9 1.5 19.8 870RE-2Y(St)HSWAH 20C1.3 20x1x1.3 0.6 1.2 16.9 0.9 1.6 21.9 1014RE-2Y(St)HSWAH 24C1.3 24x1x1.3 0.6 1.2 18.7 1.25 1.6 24.4 1163RE-2Y(St)HSWAH 27C1.3 27x1x1.3 0.6 1.3 19.3 1.25 1.6 25.0 1227
www.caledonian-cables.co.uk www.addison-cables.com
85ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Cores
x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH 30C1.3 30x1x1.3 0.6 1.3 20.0 1.25 1.6 25.7 1305RE-2Y(St)HSWAH 37C1.3 37x1x1.3 0.6 1.3 21.6 1.25 1.7 27.5 1504RE-2Y(St)HSWAH 40C1.3 40x1x1.3 0.6 1.4 22.7 1.25 1.7 28.6 1584
1.5mm2, MulticoreRE-2Y(St)HSWAH 2C1.5 2x1x1.5 0.6 0.9 7.7 0.9 1.3 12.1 279RE-2Y(St)HSWAH 3C1.5 3x1x1.5 0.6 0.9 8.1 0.9 1.4 12.7 312RE-2Y(St)HSWAH 4C1.5 4x1x1.5 0.6 0.9 8.8 0.9 1.4 13.4 358RE-2Y(St)HSWAH 5C1.5 5x1x1.5 0.6 1.0 9.8 0.9 1.4 14.4 403RE-2Y(St)HSWAH 8C1.5 8x1x1.5 0.6 1.0 11.6 0.9 1.4 16.2 526RE-2Y(St)HSWAH 10C1.5 10x1x1.5 0.6 1.1 13.7 0.9 1.5 18.5 630RE-2Y(St)HSWAH 12C1.5 12x1x1.5 0.6 1.1 14.1 0.9 1.5 18.9 669RE-2Y(St)HSWAH 14C1.5 14x1x1.5 0.6 1.1 14.8 0.9 1.5 19.6 742RE-2Y(St)HSWAH 16C1.5 16x1x1.5 0.6 1.1 15.6 0.9 1.5 20.4 925RE-2Y(St)HSWAH 20C1.5 20x1x1.5 0.6 1.2 17.6 1.25 1.6 23.3 1090RE-2Y(St)HSWAH 24C1.5 24x1x1.5 0.6 1.3 19.6 1.25 1.6 25.3 1218RE-2Y(St)HSWAH 27C1.5 27x1x1.5 0.6 1.3 20.1 1.25 1.6 25.8 1320RE-2Y(St)HSWAH 30C1.5 30x1x1.5 0.6 1.3 20.8 1.25 1.7 26.7 1385RE-2Y(St)HSWAH 37C1.5 37x1x1.5 0.6 1.4 22.6 1.25 1.7 28.5 1586RE-2Y(St)HSWAH 40C1.5 40x1x1.5 0.6 1.4 23.6 1.25 1.7 29.5 1723
2.5mm2, Multicore
RE-2Y(St)HSWAH 2C2.5 2x1x2.5 0.7 0.9 8.9 0.9 1.4 13.5 370
RE-2Y(St)HSWAH 3C2.5 3x1x2.5 0.7 1.0 9.7 0.9 1.4 14.3 387RE-2Y(St)HSWAH 4C2.5 4x1x2.5 0.7 1.0 10.5 0.9 1.4 15.1 442RE-2Y(St)HSWAH 5C2.5 5x1x2.5 0.7 1.0 11.9 0.9 1.4 16.5 568RE-2Y(St)HSWAH 8C2.5 8x1x2.5 0.7 1.1 13.9 0.9 1.5 18.7 729RE-2Y(St)HSWAH 10C2.5 10x1x2.5 0.7 1.2 16.3 0.9 1.6 21.3 957RE-2Y(St)HSWAH 12C2.5 12x1x2.5 0.7 1.2 16.9 0.9 1.6 21.9 1049RE-2Y(St)HSWAH 14C2.5 14x1x2.5 0.7 1.2 17.7 1.25 1.6 23.4 1198RE-2Y(St)HSWAH 16C2.5 16x1x2.5 0.7 1.3 18.9 1.25 1.6 24.6 1302RE-2Y(St)HSWAH 20C2.5 20x1x2.5 0.7 1.3 21.1 1.25 1.7 27.0 1485
ADDISON
Caledonian86
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Cores
x1xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH 24C2.5 24x1x2.5 0.7 1.4 23.6 1.25 1.7 29.5 1718RE-2Y(St)HSWAH 27C2.5 27x1x2.5 0.7 1.4 24.1 1.25 1.8 30.2 1895RE-2Y(St)HSWAH 30C2.5 30x1x2.5 0.7 1.5 25.2 1.25 1.8 31.3 2166RE-2Y(St)HSWAH 37C2.5 37x1x2.5 0.7 1.5 27.2 1.25 1.8 33.3 2505RE-2Y(St)HSWAH 40C2.5 40x1x2.5 0.7 1.6 28.5 1.25 1.9 34.8Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
500V
NStandard
BS 5308Part1 Type2
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
87ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed & overall screened Instrumentation cables (single Triple)
re-2y(st)H 90°c / 300 V
LSZH Outer Sheath
Plain Annealed Copper
PE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
ADDISON
Caledonian88
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Triple: Three conductors twisted to form a triple lay-up: Triples laid up in layers of optimum pitch separator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or Blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25.0 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000 5000 5000 5000 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115 115 115 115 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 0 0 0 0 0
Inductance mH/km(Max.) 1 1 1 1 1L / R (ratio) (max.) μH/Ω 25 25 25 40 40Operating voltage V 300
Test Voltage Urms
Core to Core V 1500 1500 1500 1500 1500
Core to Screen V 1500 1500 1500 1500 1500
www.caledonian-cables.co.uk www.addison-cables.com
89ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HNo. of Triples
x3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2Y(St)H 1T0.5 1x3x0,50 0.35 0.8 5.4 49RE-2Y(St)H 1T0.75 1x3x0,75 0.38 0.9 6.1 60RE-2Y(St)H 1T1.0 1x3x1.0 0.4 0.9 6.6 71
RE-2Y(St)H 1T1.3 1x3x1,3 0.45 0.9 7.2 86
RE-2Y(St)H 1T1.5 1x3x1,5 0.45 0.9 7.5 97
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian90
Pe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multitriple)
re-2y(st)H 90°c / 300 V
LSZH Outer Sheath
Plain Annealed Copper
PE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
www.caledonian-cables.co.uk www.addison-cables.com
91ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Triple: Three conductors twisted to form a triple lay-up: Triples laid up in layers of optimum pitch separator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or Blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.0 24.5 18.1 13.9 12.1
Insulation resistance (20°C) MΩ.km(Min.) 5000 5000 5000 5000 5000
Mutual Capacitance (1 kHz) up to 4 trples pF/m(Max.) 90 90 90 102 102
above 4 trples pF/m(Max.) 75 75 75 85 85
Inductance mH/km(Max.) 1L / R (ratio) (max.) μH/Ω 25 25 25 40 40
ADDISON
Caledonian92
Operating voltage V 300
Test Voltage Urms
Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)H
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/km0.5mm2 , Multitriple
RE-2Y(St)H 2T0.5 2x3x0,50 0.35 0.9 8.4 92
RE-2Y(St)H 4T0.5 4x3x0,50 0.35 1.0 9.8 124
RE-2Y(St)H 5T0.5 5x3x0,50 0.35 1.0 10.8 155
RE-2Y(St)H 6T0.5 6x3x0,50 0.35 1.0 12.1 186
RE-2Y(St)H 8T0.5 8x3x0,50 0.35 1.1 13.1 222
RE-2Y(St)H 10T0.5 10x3x0,50 0.35 1.1 14.7 276
RE-2Y(St)H 12T0.5 12x3x0,50 0.35 1.1 15.2 325
RE-2Y(St)H 16T0.5 16x3x0,50 0.35 1.2 17.4 416
RE-2Y(St)H 20T0.5 20x3x0,50 0.35 1.2 19.1 510
RE-2Y(St)H 24T0.5 24x3x0,50 0.35 1.3 20.9 597
0.75mm2 , Multitriple RE-2Y(St)H 2T0.75 2x3x0,75 0.38 0.9 9.3 114
RE-2Y(St)H 4T0.75 4x3x0,75 0.38 1.0 10.9 163
RE-2Y(St)H 5T0.75 5x3x0,75 0.38 1.0 12.0 199
RE-2Y(St)H 6T0.75 6x3x0,75 0.38 1.1 13.7 246
RE-2Y(St)H 8T0.75 8x3x0,75 0.38 1.1 14.7 297
RE-2Y(St)H 10T0.75 10x3x0,75 0.38 1.2 16.7 368
RE-2Y(St)H 12T0.75 12x3x0,75 0.38 1.2 17.3 425
RE-2Y(St)H 16T0.75 16x3x0,75 0.38 1.3 19.7 558
RE-2Y(St)H 20T0.75 20x3x0,75 0.38 1.3 21.7 685
RE-2Y(St)H 24T0.75 24x3x0,75 0.38 1.4 23.7 806
1.0mm2 , Multitriple RE-2Y(St)H 2T1.0 2x3x1 0.4 1.0 10.4 135
RE-2Y(St)H 4T1.0 4x3x1 0.4 1.0 11.9 203
www.caledonian-cables.co.uk www.addison-cables.com
93ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)H
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2Y(St)H 5T1.0 5x3x1 0.4 1.0 13.2 252
RE-2Y(St)H 6T1.0 6x3x1 0.4 1.1 15.0 304
RE-2Y(St)H 8T1.0 8x3x1 0.4 1.1 16.1 381
RE-2Y(St)H 10T1.0 10x3x1 0.4 1.2 18.4 463
RE-2Y(St)H 12T1.0 12x3x1 0.4 1.2 19.0 546
RE-2Y(St)H 16T1.0 16x3x1 0.4 1.3 21.7 720
RE-2Y(St)H 20T1.0 20x3x1 0.4 1.4 24.1 884
RE-2Y(St)H 24T1.0 24x3x1 0.4 1.4 26.1 10531.3mm2 , Multitriple
RE-2Y(St)H 2T1.3 2x3x1,3 0.45 1.0 11.5 175
RE-2Y(St)H 4T1.3 4x3x1,3 0.45 1.1 13.4 252
RE-2Y(St)H 5T1.3 5x3x1,3 0.45 1.1 14.8 319
RE-2Y(St)H 6T1.3 6x3x1,3 0.45 1.2 16.9 388
RE-2Y(St)H 8T1.3 8x3x1,3 0.45 1.2 18.1 476
RE-2Y(St)H 10T1.3 10x3x1,3 0.45 1.3 20.7 591
RE-2Y(St)H 12T1.3 12x3x1,3 0.45 1.3 21.4 697
RE-2Y(St)H 16T1.3 16x3x1,3 0.45 1.4 24.4 921
RE-2Y(St)H 20T1.3 20x3x1,3 0.45 1.5 27.1 1128RE-2Y(St)H 24T1.3 24x3x1,3 0.45 1.6 29.6 1341
1.5mm2 , Multitriple RE-2Y(St)H 2T1.5 2x3x1,5 0.45 1.0 11.9 192
RE-2Y(St)H 4T1.5 4x3x1,5 0.45 1.1 14.0 288
RE-2Y(St)H 5T1.5 5x3x1,5 0.45 1.1 15.4 356
RE-2Y(St)H 6T1.5 6x3x1,5 0.45 1.2 17.6 433
RE-2Y(St)H 8T1.5 8x3x1,5 0.45 1.3 19.1 543
RE-2Y(St)H 10T1.5 10x3x1,5 0.45 1.3 21.6 675
RE-2Y(St)H 12T1.5 12x3x1,5 0.45 1.4 22.5 782
RE-2Y(St)H 16T1.5 16x3x1,5 0.45 1.5 25.7 1035RE-2Y(St)H 20T1.5 20x3x1,5 0.45 1.6 28.6 1271
ADDISON
Caledonian94
Caledonian Cable Code
RE-2Y(St)H
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2Y(St)H 24T1.5 24x3x1,5 0.45 1.7 31.1 1514
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
95ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed, Individual & overall screened Instrumentation cables (Multitriple)
re-2y(st)H-TiMf 70°c / 300 V
LSZH Outer Sheath
Plain Annealed Copper
PE Insulation
Individual Aluminium/polyester TapeTinned Copper Drain Wire
Overall Aluminium/polyester Tape
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian96
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Individual screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²Triple: Three conductors twisted to form a triple **TiMF Construction: Polyester tape above the triple, AL-PES tape over solid tinned copper drain wire, 0,60 mmlay-up: TiMF laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km(Max.) 1 1 1 1 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
www.caledonian-cables.co.uk www.addison-cables.com
97ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)H-TiMF
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/km0.5mm2 , Multitriple
RE-2Y(St)H-TiMF 2T0.5 2x3x0.5 0.35 1.0 9.7 104RE-2Y(St)H-TiMF 4T0.5 4x3x0.5 0.35 1.0 11.1 156RE-2Y(St)H-TiMF 5T0.5 5x3x0.5 0.35 1.1 12.4 183RE-2Y(St)H-TiMF 6T0.5 6x3x0.5 0.35 1.1 14.0 236RE-2Y(St)H-TiMF 8T0.5 8x3x0.5 0.35 1.1 14.9 288
RE-2Y(St)H-TiMF 10T0.5 10x3x0.5 0.35 1.2 17.0 350RE-2Y(St)H-TiMF 12T0.5 12x3x0.5 0.35 1.2 17.6 386RE-2Y(St)H-TiMF 16T0.5 16x3x0.5 0.35 1.3 20.1 506RE-2Y(St)H-TiMF 20T0.5 20x3x0.5 0.35 1.4 22.3 619RE-2Y(St)H-TiMF 24T0.5 24x3x0.5 0.35 1.5 24.4 752
0.75mm2 , Multitriple RE-2Y(St)H-TiMF 2T0.75 2x3x0.75 0.38 1.0 10.6 125RE-2Y(St)H-TiMF 4T0.75 4x3x0.75 0.38 1.1 12.4 187RE-2Y(St)H-TiMF 5T0.75 5x3x0.75 0.38 1.1 13.7 238RE-2Y(St)H-TiMF 6T0.75 6x3x0.75 0.38 1.1 15.4 281RE-2Y(St)H-TiMF 8T0.75 8x3x0.75 0.38 1.2 16.7 364RE-2Y(St)H-TiMF 10T0.75 10x3x0.75 0.38 1.3 19.0 448RE-2Y(St)H-TiMF 12T0.75 12x3x0.75 0.38 1.3 19.7 497RE-2Y(St)H-TiMF 16T0.75 16x3x0.75 0.38 1.4 22.5 655RE-2Y(St)H-TiMF 20T0.75 20x3x0.75 0.38 1.5 24.9 802RE-2Y(St)H-TiMF 24T0.75 24x3x0.75 0.38 1.6 27.2 970
1.0mm2 , Multitriple RE-2Y(St)H-TiMF 2T1.0 2x3x1 0.4 1.0 11.5 154RE-2Y(St)H-TiMF 4T1.0 4x3x1 0.4 1.1 13.4 228
ADDISON
Caledonian98
Caledonian Cable Code
RE-2Y(St)H-TiMF
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2Y(St)H-TiMF 5T1.0 5x3x1 0.4 1.1 14.8 287RE-2Y(St)H-TiMF 6T1.0 6x3x1 0.4 1.2 16.9 350RE-2Y(St)H-TiMF 8T1.0 8x3x1 0.4 1.2 18.1 445
RE-2Y(St)H-TiMF 10T1.0 10x3x1 0.4 1.3 20.7 547RE-2Y(St)H-TiMF 12T1.0 12x3x1 0.4 1.3 21.4 624RE-2Y(St)H-TiMF 16T1.0 16x3x1 0.4 1.4 24.4 822RE-2Y(St)H-TiMF 20T1.0 20x3x1 0.4 1.5 27.1 1005RE-2Y(St)H-TiMF 24T1.0 24x3x1 0.4 1.6 29.6 1212
1.3mm2 , Multitriple RE-2Y(St)H-TiMF 2T1.3 2x3x1,3 0.45 1.1 12.8 186RE-2Y(St)H-TiMF 4T1.3 4x3x1,3 0.45 1.1 14.7 284RE-2Y(St)H-TiMF 5T1.3 5x3x1,3 0.45 1.2 16.5 358RE-2Y(St)H-TiMF 6T1.3 6x3x1,3 0.45 1.3 18.8 427RE-2Y(St)H-TiMF 8T1.3 8x3x1,3 0.45 1.3 20.1 551
RE-2Y(St)H-TiMF 10T1.3 10x3x1,3 0.45 1.4 23.0 684RE-2Y(St)H-TiMF 12T1.3 12x3x1,3 0.45 1.5 24.0 769RE-2Y(St)H-TiMF 16T1.3 16x3x1,3 0.45 1.6 27.4 1025RE-2Y(St)H-TiMF 20T1.3 20x3x1,3 0.45 1.7 30.4 1256RE-2Y(St)H-TiMF 24T1.3 24x3x1,3 0.45 1.8 33.1 1516
1.5mm2 , Multitriple RE-2Y(St)H-TiMF 2T1.5 2x3x1,5 0.45 1.1 13.2 199RE-2Y(St)H-TiMF 4T1.5 4x3x1,5 0.45 1.2 15.4 322RE-2Y(St)H-TiMF 5T1.5 5x3x1,5 0.45 1.2 17.1 397RE-2Y(St)H-TiMF 6T1.5 6x3x1,5 0.45 1.3 19.5 484RE-2Y(St)H-TiMF 8T1.5 8x3x1,5 0.45 1.4 21.1 616
RE-2Y(St)H-TiMF 10T1.5 10x3x1,5 0.45 1.5 24.1 768RE-2Y(St)H-TiMF 12T1.5 12x3x1,5 0.45 1.5 24.9 870RE-2Y(St)H-TiMF 16T1.5 16x3x1,5 0.45 1.6 28.4 1144RE-2Y(St)H-TiMF 20T1.5 20x3x1,5 0.45 1.7 31.6 1404
www.caledonian-cables.co.uk www.addison-cables.com
99ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)H-TiMF
No. of Triplesx3xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm kg/kmRE-2Y(St)H-TiMF 24T1.5 24x3x1,5 0.45 1.8 34.4 1698
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian100
Pe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (single Triple)
re-2y(st)HsWaH 70°c / 300 V
Galvenized Round Steel Wire
Plain Annealed Copper
PE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
LSZH Outer Sheath
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
www.caledonian-cables.co.uk www.addison-cables.com
101ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pair: Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmour: Galvenized round steel wire.outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
ADDISON
Caledonian102
Inductance mH/km(Max.) 1 1 1 1 1
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH 1T0.5 1x3x0.50 0.35 0.8 5.4 0.9 1.3 9.8 200
RE-2Y(St)HSWAH 1T0.75 1x3x0.75 0.38 0.9 6.1 0.9 1.3 10.5 220RE-2Y(St)HSWAH 1T1.0 1x3x1.0 0.4 0.9 6.6 0.9 1.3 11.0 244
RE-2Y(St)HSWAH 1T1.3 1x3x1.3 0.45 0.9 7.2 0.9 1.3 11.6 268
RE-2Y(St)HSWAH 1T1.5 1x3x1.5 0.45 0.9 7.5 0.9 1.3 11.9 277
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
103ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (Multitriple)
re-2y(st)HsWaH 70°c / 300 V
Galvenized Round Steel Wire
Plain Annealed Copper
PE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
LSZH Outer Sheath
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
ADDISON
Caledonian104
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmour: Galvenized round steel wire.outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
www.caledonian-cables.co.uk www.addison-cables.com
105ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Inductance mH/km(Max.) 1
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/km0.5mm2, Multitriple
RE-2Y(St)HSWAH 2T0.5 2x3x0.5 0.35 0.9 8.4 0.9 1.4 13.0 326RE-2Y(St)HSWAH 4T0.5 4x3x0.5 0.35 1.0 9.8 0.9 1.4 14.4 386RE-2Y(St)HSWAH 5T0.5 5x3x0.5 0.35 1.0 10.8 0.9 1.4 15.4 454RE-2Y(St)HSWAH 6T0.5 6x3x0.5 0.35 1.0 12.1 0.9 1.4 16.7 513RE-2Y(St)HSWAH 8T0.5 8x3x0.5 0.35 1.1 13.1 0.9 1.5 17.9 571
RE-2Y(St)HSWAH 10T0.5 10x3x0.5 0.35 1.1 14.7 0.9 1.5 19.5 677RE-2Y(St)HSWAH 12T0.5 12x3x0.5 0.35 1.1 15.2 0.9 1.5 20.0 845RE-2Y(St)HSWAH 16T0.5 16x3x0.5 0.35 1.2 17.4 0.9 1.6 22.4 1031RE-2Y(St)HSWAH 20T0.5 20x3x0.5 0.35 1.2 19.1 1.25 1.6 24.8 1179RE-2Y(St)HSWAH 24T0.5 24x3x0.5 0.35 1.3 20.9 1.25 1.7 26.8 1330
0.75mm2, Multitriple RE-2Y(St)HSWAH 2T0.75 2x3x0.75 0.38 1.0 10.6 0.9 1.4 13.9 370RE-2Y(St)HSWAH 4T0.75 4x3x0.75 0.38 1.1 12.4 0.9 1.4 15.5 462RE-2Y(St)HSWAH 5T0.75 5x3x0.75 0.38 1.1 13.7 0.9 1.4 16.6 526RE-2Y(St)HSWAH 6T0.75 6x3x0.75 0.38 1.1 15.4 0.9 1.5 18.5 615RE-2Y(St)HSWAH 8T0.75 8x3x0.75 0.38 1.2 16.7 0.9 1.5 19.5 698RE-2Y(St)HSWAH 10T0.75 10x3x0.75 0.38 1.3 19.0 0.9 1.5 21.5 947RE-2Y(St)HSWAH 12T0.75 12x3x0.75 0.38 1.3 19.7 0.9 1.7 22.3 1029RE-2Y(St)HSWAH 16T0.75 16x3x0.75 0.38 1.4 22.5 1.25 1.6 25.4 1240
ADDISON
Caledonian106
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH 20T0.75 20x3x0.75 0.38 1.5 24.9 1.25 1.7 27.6 1446RE-2Y(St)HSWAH 24T0.75 24x3x0.75 0.38 1.6 27.2 1.25 1.7 29.6 1632
1.0mm2, Multitriple RE-2Y(St)HSWAH 2T1.0 2x3x1 0.4 1.0 11.5 0.9 1.4 15.0 412RE-2Y(St)HSWAH 4T1.0 4x3x1 0.4 1.1 13.4 0.9 1.4 16.5 529RE-2Y(St)HSWAH 5T1.0 5x3x1 0.4 1.1 14.8 0.9 1.5 18.0 620RE-2Y(St)HSWAH 6T1.0 6x3x1 0.4 1.2 16.9 0.9 1.5 19.8 830RE-2Y(St)HSWAH 8T1.0 8x3x1 0.4 1.2 18.1 0.9 1.5 20.9 946
RE-2Y(St)HSWAH 10T1.0 10x3x1 0.4 1.3 20.7 0.9 1.6 24.1 1105RE-2Y(St)HSWAH 12T1.0 12x3x1 0.4 1.3 21.4 1.25 1.6 24.7 1215RE-2Y(St)HSWAH 16T1.0 16x3x1 0.4 1.4 24.4 1.25 1.7 27.6 1482RE-2Y(St)HSWAH 20T1.0 20x3x1 0.4 1.5 27.1 1.25 1.7 30.0 1740RE-2Y(St)HSWAH 24T1.0 24x3x1 0.4 1.6 29.6 1.25 1.8 32.2 2202
1.3mm2, Multitriple RE-2Y(St)HSWAH 2T1.3 2x3x1,3 0.45 1.1 12.8 0.9 1.4 16.1 463RE-2Y(St)HSWAH 4T1.3 4x3x1,3 0.45 1.1 14.7 0.9 1.5 18.2 621RE-2Y(St)HSWAH 5T1.3 5x3x1,3 0.45 1.2 16.5 0.9 1.5 19.6 721RE-2Y(St)HSWAH 6T1.3 6x3x1,3 0.45 1.3 18.8 0.9 1.5 21.7 979RE-2Y(St)HSWAH 8T1.3 8x3x1,3 0.45 1.3 20.1 0.9 1.6 23.8 1105
RE-2Y(St)HSWAH 10T1.3 10x3x1,3 0.45 1.4 23.0 1.25 1.7 26.6 1322RE-2Y(St)HSWAH 12T1.3 12x3x1,3 0.45 1.5 24.0 1.25 1.7 27.3 1456RE-2Y(St)HSWAH 16T1.3 16x3x1,3 0.45 1.6 27.4 1.25 1.8 30.5 1788RE-2Y(St)HSWAH 20T1.3 20x3x1,3 0.45 1.7 30.4 1.25 1.8 33.2 2327RE-2Y(St)HSWAH 24T1.3 24x3x1,3 0.45 1.8 33.1 1.60 1.9 36.6 2637
1.5mm2, Multitriple RE-2Y(St)HSWAH 2T1.5 2x3x1,5 0.45 1.1 13.2 0.9 1.4 16.5 518RE-2Y(St)HSWAH 4T1.5 4x3x1,5 0.45 1.2 15.4 0.9 1.5 18.8 674RE-2Y(St)HSWAH 5T1.5 5x3x1,5 0.45 1.2 17.1 0.9 1.5 20.2 869
www.caledonian-cables.co.uk www.addison-cables.com
107ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH 6T1.5 6x3x1,5 0.45 1.3 19.5 0.9 1.6 22.6 1049RE-2Y(St)HSWAH 8T1.5 8x3x1,5 0.45 1.4 21.1 1.25 1.6 24.8 1210
RE-2Y(St)HSWAH 10T1.5 10x3x1,5 0.45 1.5 24.1 1.25 1.7 27.5 1435RE-2Y(St)HSWAH 12T1.5 12x3x1,5 0.45 1.5 24.9 1.25 1.7 28.4 1569RE-2Y(St)HSWAH 16T1.5 16x3x1,5 0.45 1.6 28.4 1.25 1.8 31.8 2162RE-2Y(St)HSWAH 20T1.5 20x3x1,5 0.45 1.7 31.6 1.25 1.9 34.9 2515RE-2Y(St)HSWAH 24T1.5 24x3x1,5 0.45 1.8 34.4 1.60 2.0 38.3 2879
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian108
Pe Insulated, lsZH sheathed, Individual & overall screened, armoured Instrumentation cables (Multitriple)
re-2y(st)HsWaH-TiMf 70°c / 300 V
Galvenized Round Steel Wire
Plain Annealed Copper
PE Insulation
Overall Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
LSZH Outer Sheath
Individual Aluminium/polyester Tape
aPPlIcaTIon:
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
www.caledonian-cables.co.uk www.addison-cables.com
109ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Individual screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: Thermoplastic LSZH compoundarmour: Galvenized round steel wire.outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km(Max.) 1
ADDISON
Caledonian110
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HSWAH-TiMF
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/km0.5mm2, Multitriple
RE-2Y(St)HSWAH-TiMF 2T0.5 2x3x0.5 0.35 1.0 9.7 0.9 1.4 14.3 363RE-2Y(St)HSWAH-TiMF 4T0.5 4x3x0.5 0.35 1.0 11.1 0.9 1.4 15.7 456RE-2Y(St)HSWAH-TiMF 5T0.5 5x3x0.5 0.35 1.1 12.4 0.9 1.5 17.2 517
RE-2Y(St)HSWAH-TiMF 6T0.5 6x3x0.5 0.35 1.1 14.0 0.9 1.5 18.8 612
RE-2Y(St)HSWAH-TiMF 8T0.5 8x3x0.5 0.35 1.1 14.9 0.9 1.5 19.7 800
RE-2Y(St)HSWAH-TiMF 10T0.5 10x3x0.5 0.35 1.2 17.0 1.25 1.6 22.7 951RE-2Y(St)HSWAH-TiMF 12T0.5 12x3x0.5 0.35 1.2 17.6 1.25 1.6 23.3 978RE-2Y(St)HSWAH-TiMF 16T0.5 16x3x0.5 0.35 1.3 20.1 1.25 1.7 26.0 1201RE-2Y(St)HSWAH-TiMF 20T0.5 20x3x0.5 0.35 1.4 22.3 1.25 1.7 28.2 1394RE-2Y(St)HSWAH-TiMF 24T0.5 24x3x0.5 0.35 1.5 24.4 1.25 1.8 30.5 1607
0.75mm2, Multitriple RE-2Y(St)HSWAH-TiMF 2T0.75 2x3x0.75 0.38 1.0 10.6 0.9 1.4 15.2 418RE-2Y(St)HSWAH-TiMF 4T0.75 4x3x0.75 0.38 1.1 12.4 0.9 1.5 17.2 521RE-2Y(St)HSWAH-TiMF 5T0.75 5x3x0.75 0.38 1.1 13.7 0.9 1.5 18.5 608RE-2Y(St)HSWAH-TiMF 6T0.75 6x3x0.75 0.38 1.1 15.4 0.9 1.5 20.2 820
RE-2Y(St)HSWAH-TiMF 8T0.75 8x3x0.75 0.38 1.2 16.7 0.9 1.6 21.7 942
RE-2Y(St)HSWAH-TiMF 10T0.7510x3x0.75 0.38 1.3 19.0 1.25 1.6 24.7 1104
RE-2Y(St)HSWAH-TiMF 12T0.7512x3x0.75 0.38 1.3 19.7 1.25 1.7 25.6 1178
RE-2Y(St)HSWAH-TiMF 16T0.7516x3x0.75 0.38 1.4 22.5 1.25 1.7 28.4 1441RE-2Y(St)HSWAH-TiMF 20T0.7520x3x0.75 0.38 1.5 24.9 1.25 1.8 31.0 1888
www.caledonian-cables.co.uk www.addison-cables.com
111ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)HSWAH-TiMF
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH-TiMF 24T0.7524x3x0.75 0.38 1.6 27.2 1.25 1.9 33.5 2168
1.0mm2, Multitriple RE-2Y(St)HSWAH-TiMF 2T1.0 2x3x1 0.4 1.0 11.5 0.9 1.4 16.1 472RE-2Y(St)HSWAH-TiMF 4T1.0 4x3x1 0.4 1.1 13.4 0.9 1.5 18.2 597RE-2Y(St)HSWAH-TiMF 5T1.0 5x3x1 0.4 1.1 14.8 0.9 1.5 19.6 689RE-2Y(St)HSWAH-TiMF 6T1.0 6x3x1 0.4 1.2 16.9 0.9 1.5 21.7 940RE-2Y(St)HSWAH-TiMF 8T1.0 8x3x1 0.4 1.2 18.1 1.25 1.6 23.8 1035
RE-2Y(St)HSWAH-TiMF 10T1.0 10x3x1 0.4 1.3 20.7 1.25 1.7 26.6 1279RE-2Y(St)HSWAH-TiMF 12T1.0 12x3x1 0.4 1.3 21.4 1.25 1.7 27.3 1383
RE-2Y(St)HSWAH-TiMF 16T1.0 16x3x1 0.4 1.4 24.4 1.25 1.7 30.3 1689
RE-2Y(St)HSWAH-TiMF 20T1.0 20x3x1 0.4 1.5 27.1 1.25 1.8 33.2 2204RE-2Y(St)HSWAH-TiMF 24T1.0 24x3x1 0.4 1.6 29.6 1.6 1.9 36.6 2509
1.3mm2, Multitriple RE-2Y(St)HSWAH-TiMF 2T1.3 2x3x1,3 0.45 1.1 12.8 0.9 1.5 17.6 532RE-2Y(St)HSWAH-TiMF 4T1.3 4x3x1,3 0.45 1.1 14.7 0.9 1.5 19.5 685RE-2Y(St)HSWAH-TiMF 5T1.3 5x3x1,3 0.45 1.2 16.5 0.9 1.6 21.5 925RE-2Y(St)HSWAH-TiMF 6T1.3 6x3x1,3 0.45 1.3 18.8 1.25 1.6 24.5 1090RE-2Y(St)HSWAH-TiMF 8T1.3 8x3x1,3 0.45 1.3 20.1 1.25 1.7 26.0 1250
RE-2Y(St)HSWAH-TiMF 10T1.3 10x3x1,3 0.45 1.4 23.0 1.25 1.8 29.1 1484RE-2Y(St)HSWAH-TiMF 12T1.3 12x3x1,3 0.45 1.5 24.0 1.25 1.8 30.1 1595RE-2Y(St)HSWAH-TiMF 16T1.3 16x3x1,3 0.45 1.6 27.4 1.25 1.9 33.7 2225RE-2Y(St)HSWAH-TiMF 20T1.3 20x3x1,3 0.45 1.7 30.4 1.6 2.0 37.6 2596RE-2Y(St)HSWAH-TiMF 24T1.3 24x3x1,3 0.45 1.8 33.1 1.6 2.0 40.3 2962
RE-2Y(St)HSWAH-TiMF 2T1.5 2x3x1,5 0.45 1.1 13.2 0.9 1.5 18.0 561RE-2Y(St)HSWAH-TiMF 4T1.5 4x3x1,5 0.45 1.2 15.4 0.9 1.5 20.2 818RE-2Y(St)HSWAH-TiMF 5T1.5 5x3x1,5 0.45 1.2 17.1 1.25 1.6 22.8 999RE-2Y(St)HSWAH-TiMF 6T1.5 6x3x1,5 0.45 1.3 19.5 1.25 1.6 25.2 1164RE-2Y(St)HSWAH-TiMF 8T1.5 8x3x1,5 0.45 1.4 21.1 1.25 1.7 27.0 1354
ADDISON
Caledonian112
Caledonian Cable Code
RE-2Y(St)HSWAH-TiMF
No. of Triples
x3xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x3xmm2 mm mm mm mm mm mm kg/kmRE-2Y(St)HSWAH-TiMF 10T1.5 10x3x1,5 0.45 1.5 24.1 1.25 1.8 30.2 1596RE-2Y(St)HSWAH-TiMF 12T1.5 12x3x1,5 0.45 1.5 24.9 1.25 1.8 31.0 1953RE-2Y(St)HSWAH-TiMF 16T1.5 16x3x1,5 0.45 1.6 28.4 1.6 1.9 35.4 2388RE-2Y(St)HSWAH-TiMF 20T1.5 20x3x1,5 0.45 1.7 31.6 1.6 2.0 38.8 2800RE-2Y(St)HSWAH-TiMF 24T1.5 24x3x1,5 0.45 1.8 34.4 1.6 2.1 41.8 3100
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
113ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed, cWb screened Instrumentation cables (single Pair)
re-2y(c)H 90°c / 300V
Copper Wire Braid Screen
LSZH Outer Sheath
Plain Annealed Copper
PE Insulation
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian114
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Tinned copper wire braidouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDeInsulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 300
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
www.caledonian-cables.co.uk www.addison-cables.com
115ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
consTrUcTIon ParaMeTers
Caledonian Cable CodeRE-2Y(C)H
No. of Pairsx2xCross Section
Copper Weight
Approx.Weight
No.x2xmm2 Kg/km Kg/kmRE-2Y(C)H 1P0.5 1x2x0.50 8.3 110
RE-2Y(C)H 1P0.75 1x2x0.75 8.7 119RE-2Y(C)H 1P1.0 1x2x1.0 9.4 135RE-2Y(C)H 1P1.3 1x2x1.3 9.7 140
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian116
Pe Insulated, lsZH sheathed, cWb screened Instrumentation cables (Multipair)
re-2y(c)H 90°c / 300V
Copper Wire Braid Screen
LSZH Outer Sheath
Plain Annealed CopperPE Insulation
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
117ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pair:Two conductors twisted to form a pairlay-up: Pairs laid up in layers of optimum pitchseparator: Polyester tapeoverall screen: Tinned copper wire braidouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +70°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
≤ 4 pairs 115 115 115 120 120
all other pairs 90 90 90 105 105
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300 300 300 300 300
ADDISON
Caledonian118
Test Voltage Core to Core V 1500 1500 1500 1500 1500
Core to Screen V 1500 1500 1500 1500 1500
consTrUcTIon ParaMeTers
Caledonian Cable CodeRE-2Y(C)H
No. of Pairsx2xCross Section
Copper Weight
Approx. Weight
No.x2xmm2 Kg/km Kg/km0.5mm2, Multipair
RE-2Y(C)H 1P0.5 1x2x0.50 8.3 110RE-2Y(C)H 2P0.5 2x2x0.50 10.7 143RE-2Y(C)H 3P0.5 3x2x0.50 11.1 158RE-2Y(C)H 4P0.5 4x2x0.50 11.9 181RE-2Y(C)H 6P0.5 6x2x0.50 13.6 230RE-2Y(C)H 8P0.5 8x2x0.50 14.2 264RE-2Y(C)H 12P0.5 12x2x0.50 16.4 343RE-2Y(C)H 16P0.5 16x2x0.50 18.2 418RE-2Y(C)H 20P0.5 20x2x0.50 19.7 487RE-2Y(C)H 24P0.5 24x2x0.50 21.1 557
0.75mm2, Multipair RE-2Y(C)H 1P0.75 1x2x0.75 8.7 119RE-2Y(C)H 2P0.75 2x2x0.75 11.4 161RE-2Y(C)H 3P0.75 3x2x0.75 11.9 185RE-2Y(C)H 4P0.75 4x2x0.75 12.7 214RE-2Y(C)H 6P0.75 6x2x0.75 14.6 278RE-2Y(C)H 8P0.75 8x2x0.75 15.4 324RE-2Y(C)H 12P0.75 12x2x0.75 17.8 427RE-2Y(C)H 16P0.75 16x2x0.75 19.8 526RE-2Y(C)H 20P0.75 20.x2x0.75 21.5 623RE-2Y(C)H 24P0.75 24x2x0.75 23.1 714
1.0mm2, Multipair RE-2Y(C)H 1P1.0 1x2x1.0 9.4 1.3.5RE-2Y(C)H 2P1.0 2x2x1.0 12.3 184RE-2Y(C)H 3P1.0 3x2x1.0 12.8 214RE-2Y(C)H 4P1.0 4x2x1.0 13.7 251
www.caledonian-cables.co.uk www.addison-cables.com
119ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable CodeRE-2Y(C)H
No. of Pairsx2xCross Section
Copper Weight
Approx. Weight
No.x2xmm2 Kg/km Kg/kmRE-2Y(C)H 6P1.0 6x2x1.0 15.6 326RE-2Y(C)H 8P1.0 8x2x1.0 16.4 382RE-2Y(C)H 12P1.0 12x2x1.0 19.0 511RE-2Y(C)H 16P1.0 16x2x1.0 21.2 636RE-2Y(C)H 20P1.0 20.x2x1.0 23.5 775RE-2Y(C)H 24P1.0 24x2x1.0 25.3 892
1.3mm2, Multipair RE-2Y(C)H 1P1.3 1x2x1.3 9.7 140RE-2Y(C)H 2P1.3 2x2x1.3 12.9 204RE-2Y(C)H 3P1.3 3x2x1.3 13.5 242RE-2Y(C)H 4P1.3 4x2x1.3 14.5 285RE-2Y(C)H 6P1.3 6x2x1.3 16.7 375RE-2Y(C)H 8P1.3 8x2x1.3 17.4 444RE-2Y(C)H 12P1.3 12x2x1.3 20.2 599RE-2Y(C)H 16P1.3 16x2x1.3 22.6 750RE-2Y(C)H 20P1.3 20.x2x1.3 25.1 916RE-2Y(C)H 24P1.3 24x2x1.3 27.0 1064
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian120
Pe Insulated, lsZH sheathed & overall screened Instrumentation cables (single Pair)
re-2y(st)H 90°c / 300V
PETP Transparent Tape
LSZH Outer Sheath
Plain Annealed CopperPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
121ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -20°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
ADDISON
Caledonian122
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)H
No. of Pairsx2xCross Section
NominalInsulationThickness
NominalOuter
SheathThickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2Y(St)H 1P0.5 1x2x0.50 0.35 0.8 5.2 38
RE-2Y(St)H 1P0.75 1x2x0.75 0.38 0.8 5.6 49
RE-2Y(St)H 1P1.0 1x2x1.0 0.40 0.9 6.3 56
RE-2Y(St)H 1P1.3 1x2x1.3 0.45 0.9 6.8 65
RE-2Y(St)H 1P1.5 1x2x1.5 0.45 0.9 7.1 74
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
500V
NStandard
BS 5308Part1 Type1
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
123ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multipair)
re-2y(st)H 90°c / 300V
PETP Transparent Tape
LSZH Outer Sheath
Plain Annealed CopperPE Insulation
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
VolTaGe raTInG
300V
ADDISON
Caledonian124
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIesConductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
www.caledonian-cables.co.uk www.addison-cables.com
125ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HNo. of
Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
0.5mm2, Multipair
RE-2Y(St)H 2P0.5 2x2x0.5 0.35 0.9 7.6 66
RE-2Y(St)H 4P0.5 3x2x0.5 0.35 0.9 8.8 98
RE-2Y(St)H 5P0.5 4x2x0.5 0.35 1.0 9.8 118
RE-2Y(St)H 6P0.5 5x2x0.5 0.35 1.0 10.6 138
RE-2Y(St)H 8P0.5 8x2x0.5 0.35 1.0 11.3 160
RE-2Y(St)H 10P0.5 10x2x0.5 0.35 1.1 12.9 201
RE-2Y(St)H 12P0.5 12x2x0.5 0.35 1.1 13.5 236
RE-2Y(St)H 16P0.5 16x2x0.5 0.35 1.1 15.2 300
RE-2Y(St)H 20P0.5 20x2x0.5 0.35 1.2 16.9 367
RE-2Y(St)H 24P0.5 24x2x0.5 0.35 1.2 18.3 419
0.75mm2, Multipair
RE-2Y(St)H 2P0.75 2x2x0.75 0.38 0.9 8.5 87
RE-2Y(St)H 4P0.75 3x2x0.75 0.38 1.0 10.0 123
RE-2Y(St)H 5P0.75 4x2x0.75 0.38 1.0 10.9 150
RE-2Y(St)H 6P0.75 5x2x0.75 0.38 1.0 11.8 175
RE-2Y(St)H 8P0.75 8x2x0.75 0.38 1.1 12.8 220
RE-2Y(St)H 10P0.75 10x2x0.75 0.38 1.1 14.5 267
RE-2Y(St)H 12P0.75 12x2x0.75 0.38 1.1 15.1 298
RE-2Y(St)H 16P0.75 16x2x0.75 0.38 1.2 17.3 409
RE-2Y(St)H 20P0.75 20x2x0.75 0.38 1.3 19.2 480
RE-2Y(St)H 24P0.75 24x2x0.75 0.38 1.3 20.8 561
ADDISON
Caledonian126
Caledonian Cable Code
RE-2Y(St)HNo. of
Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
1.0mm2, Multipair
RE-2Y(St)H 2P1.0 2x2x1.0 0.4 0.9 9.2 102
RE-2Y(St)H 4P1.0 3x2x1.0 0.4 1.0 10.9 156
RE-2Y(St)H 5P1.0 4x2x1.0 0.4 1.0 11.9 183
RE-2Y(St)H 6P1.0 5x2x1.0 0.4 1.0 13.0 224
RE-2Y(St)H 8P1.0 8x2x1.0 0.4 1.1 14.0 273
RE-2Y(St)H 10P1.0 10x2x1.0 0.4 1.1 15.9 324
RE-2Y(St)H 12P1.0 12x2x1.0 0.4 1.2 16.8 383
RE-2Y(St)H 16P1.0 16x2x1.0 0.4 1.2 19.0 513
RE-2Y(St)H 20P1.0 20x2x1.0 0.4 1.3 21.1 619
RE-2Y(St)H 24P1.0 24x2x1.0 0.4 1.4 23.1 738
1.3mm2, Multipair
RE-2Y(St)H 2P1.3 2x2x1.3 0.45 1.0 10.4 122
RE-2Y(St)H 4P1.3 3x2x1.3 0.45 1.0 12.0 190
RE-2Y(St)H 5P1.3 4x2x1.3 0.45 1.1 13.4 233
RE-2Y(St)H 6P1.3 5x2x1.3 0.45 1.1 14.6 273
RE-2Y(St)H 8P1.3 8x2x1.3 0.45 1.2 15.7 330
RE-2Y(St)H 10P1.3 10x2x1.3 0.45 1.2 17.9 422
RE-2Y(St)H 12P1.3 12x2x1.3 0.45 1.3 18.9 487
RE-2Y(St)H 16P1.3 16x2x1.3 0.45 1.3 21.4 678
RE-2Y(St)H 20P1.3 20x2x1.3 0.45 1.4 23.8 790
RE-2Y(St)H 24P1.3 24x2x1.3 0.45 1.5 25.9 921
1.5mm2, Multipair
RE-2Y(St)H 2P1.5 2x2x1.5 0.45 1.0 10.8 139
RE-2Y(St)H 4P1.5 3x2x1.5 0.45 1.1 12.7 212
RE-2Y(St)H 5P1.5 4x2x1.5 0.45 1.1 14.0 259
RE-2Y(St)H 6P1.5 5x2x1.5 0.45 1.2 15.2 312
www.caledonian-cables.co.uk www.addison-cables.com
127ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)HNo. of
Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2Y(St)H 8P1.5 8x2x1.5 0.45 1.2 16.4 378
RE-2Y(St)H 10P1.5 10x2x1.5 0.45 1.3 18.8 473
RE-2Y(St)H 12P1.5 12x2x1.5 0.45 1.3 19.7 548
RE-2Y(St)H 16P1.5 16x2x1.5 0.45 1.4 22.5 727
RE-2Y(St)H 20P1.5 20x2x1.5 0.45 1.5 25.0 903
RE-2Y(St)H 24P1.5 24x2x1.5 0.45 1.5 27.1 1051Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian128
Pe Insulated, lsZH sheathed & overall screened, armoured Instrumentation cables (single Pair)
re-2y(st)HsWaH 90°c / 300V
LSZH Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperPE Insulation
PETP Transparent Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
129ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300/500V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²Inner sheath: LSZH compoundamouring: Galvanized steel wire armourouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -5°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
ADDISON
Caledonian130
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2Y(St)HSWAH 1P0.5 1x2x0.50 0.35 0.8 5.2 0.9 1.3 9.6 177
RE-2Y(St)HSWAH 1P0.75 1x2x0.75 0.38 0.8 5.6 0.9 1.3 10.0 199
RE-2Y(St)HSWAH 1P1.0 1x2x1.0 0.40 0.9 6.3 0.9 1.3 10.7 219
RE-2Y(St)HSWAH 1P1.3 1x2x1.3 0.45 0.9 6.8 0.9 1.3 11.2 241
RE-2Y(St)HSWAH 1P1.5 1x2x1.5 0.45 0.9 7.1 0.9 1.3 11.5 255
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
EN 50288-7
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
131ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed, overall screened & armoured Instrumentation cables (Multipair)
re-2y(st)HsWaH 90°c / 300V
LSZH Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperPE Insulation
PETP Transparent Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian132
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmbinder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²Inner sheath: LSZH compoundamouring: Galvanized steel wire armourouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -20°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIes
Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)
up to 4 pairs 90 90 90 102 102
above 4 pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
www.caledonian-cables.co.uk www.addison-cables.com
133ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
0.5mm2, MultipairRE-2Y(St)HSWAH 2P0.5 2x2x0.5 0.35 0.9 7.6 0.9 1.3 12.0 262
RE-2Y(St)HSWAH 4P0.5 3x2x0.5 0.35 0.9 8.8 0.9 1.4 13.4 325
RE-2Y(St)HSWAH 5P0.5 4x2x0.5 0.35 1.0 9.8 0.9 1.4 14.4 375
RE-2Y(St)HSWAH 6P0.5 5x2x0.5 0.35 1.0 10.6 0.9 1.4 15.2 411
RE-2Y(St)HSWAH 8P0.5 8x2x0.5 0.35 1.0 11.3 0.9 1.4 15.9 473
RE-2Y(St)HSWAH 10P0.5 10x2x0.5 0.35 1.1 12.9 0.9 1.5 17.7 537
RE-2Y(St)HSWAH 12P0.5 12x2x0.5 0.35 1.1 13.5 0.9 1.5 18.3 576
RE-2Y(St)HSWAH 16P0.5 16x2x0.5 0.35 1.1 15.2 0.9 1.5 20.0 824
RE-2Y(St)HSWAH 20P0.5 20x2x0.5 0.35 1.2 16.9 0.9 1.6 21.9 949
RE-2Y(St)HSWAH 24P0.5 24x2x0.5 0.35 1.2 18.3 1.25 1.6 24.0 1030
0.75mm2, Multipair
RE-2Y(St)HSWAH 2P0.75 2x2x0.75 0.38 0.9 8.5 0.9 1.4 13.1 308
RE-2Y(St)HSWAH 4P0.75 3x2x0.75 0.38 1.0 10.0 0.9 1.4 14.6 383
RE-2Y(St)HSWAH 5P0.75 4x2x0.75 0.38 1.0 10.9 0.9 1.4 15.5 448
RE-2Y(St)HSWAH 6P0.75 5x2x0.75 0.38 1.0 11.8 0.9 1.4 16.4 482
RE-2Y(St)HSWAH 8P0.75 8x2x0.75 0.38 1.1 12.8 0.9 1.5 17.6 534
RE-2Y(St)HSWAH 10P0.75 10x2x0.75 0.38 1.1 14.5 0.9 1.5 19.3 654
RE-2Y(St)HSWAH 12P0.75 12x2x0.75 0.38 1.1 15.1 0.9 1.5 19.9 826
RE-2Y(St)HSWAH 16P0.75 16x2x0.75 0.38 1.2 17.3 0.9 1.6 22.3 967
ADDISON
Caledonian134
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2Y(St)HSWAH 20P0.75 20x2x0.75 0.38 1.3 19.2 1.25 1.6 24.9 1118
RE-2Y(St)HSWAH 24P0.75 24x2x0.75 0.38 1.3 20.8 1.25 1.6 26.7 1294
1.0mm2, Multipair
RE-2Y(St)HSWAH 2P1.0 2x2x1.0 0.4 0.9 9.2 0.9 1.4 13.8 357
RE-2Y(St)HSWAH 4P1.0 3x2x1.0 0.4 1.0 10.9 0.9 1.4 15.5 450
RE-2Y(St)HSWAH 5P1.0 4x2x1.0 0.4 1.0 11.9 0.9 1.4 16.5 509
RE-2Y(St)HSWAH 6P1.0 5x2x1.0 0.4 1.0 13.0 0.9 1.4 17.6 565
RE-2Y(St)HSWAH 8P1.0 8x2x1.0 0.4 1.1 14.0 0.9 1.5 18.8 651
RE-2Y(St)HSWAH 10P1.0 10x2x1.0 0.4 1.1 15.9 0.9 1.5 20.7 886
RE-2Y(St)HSWAH 12P1.0 12x2x1.0 0.4 1.2 16.8 0.9 1.5 21.6 946
RE-2Y(St)HSWAH 16P1.0 16x2x1.0 0.4 1.2 19.0 1.25 1.6 24.7 1173
RE-2Y(St)HSWAH 20P1.0 20x2x1.0 0.4 1.3 21.1 1.25 1.7 27.0 1318
RE-2Y(St)HSWAH 24P1.0 24x2x1.0 0.4 1.4 23.1 1.25 1.7 29.0 1488
1.3mm2, Multipair
RE-2Y(St)HSWAH 2P1.3 2x2x1.3 0.45 1.0 10.4 0.9 1.4 15.0 405
RE-2Y(St)HSWAH 4P1.3 3x2x1.3 0.45 1.0 12.0 0.9 1.4 16.6 511
RE-2Y(St)HSWAH 5P1.3 4x2x1.3 0.45 1.1 13.4 0.9 1.5 18.2 595
RE-2Y(St)HSWAH 6P1.3 5x2x1.3 0.45 1.1 14.6 0.9 1.5 19.4 673
RE-2Y(St)HSWAH 8P1.3 8x2x1.3 0.45 1.2 15.7 0.9 1.5 20.5 870
RE-2Y(St)HSWAH 10P1.3 10x2x1.3 0.45 1.2 17.9 0.9 1.6 23.6 1012
RE-2Y(St)HSWAH 12P1.3 12x2x1.3 0.45 1.3 18.9 1.25 1.6 24.6 1143
RE-2Y(St)HSWAH 16P1.3 16x2x1.3 0.45 1.3 21.4 1.25 1.7 27.3 1407
RE-2Y(St)HSWAH 20P1.3 20x2x1.3 0.45 1.4 23.8 1.25 1.8 29.9 1601
RE-2Y(St)HSWAH 24P1.3 24x2x1.3 0.45 1.5 25.9 1.25 1.8 32.0 2048
1.5mm2, Multipair
RE-2Y(St)HSWAH 2P1.5 2x2x1.5 0.45 1.0 10.8 0.9 1.4 15.4 448
RE-2Y(St)HSWAH 4P1.5 3x2x1.5 0.45 1.1 12.7 0.9 1.5 17.5 530
RE-2Y(St)HSWAH 5P1.5 4x2x1.5 0.45 1.1 14.0 0.9 1.5 18.8 628
RE-2Y(St)HSWAH 6P1.5 5x2x1.5 0.45 1.2 15.2 0.9 1.5 20.0 835
www.caledonian-cables.co.uk www.addison-cables.com
135ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)HSWAH
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2Y(St)HSWAH 8P1.5 8x2x1.5 0.45 1.2 16.4 0.9 1.6 21.4 944
RE-2Y(St)HSWAH 10P1.5 10x2x1.5 0.45 1.3 18.8 1.25 1.6 24.5 1097
RE-2Y(St)HSWAH 12P1.5 12x2x1.5 0.45 1.3 19.7 1.25 1.7 25.6 1230
RE-2Y(St)HSWAH 16P1.5 16x2x1.5 0.45 1.4 22.5 1.25 1.7 28.4 1471
RE-2Y(St)HSWAH 20P1.5 20x2x1.5 0.45 1.5 25.0 1.25 1.8 31.1 1971
RE-2Y(St)HSWAH 24P1.5 24x2x1.5 0.45 1.5 27.1 1.25 1.8 33.2 2251
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
BS 5308Part1 Type2
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian136
Pe Insulated, lsZH sheathed, Individual and overall screened Instrumentation cables (Multipair)
re-2y(st)H PiMf 90°c / 300V
PETP Transparent Tape
LSZH Outer Sheath
Plain Annealed CopperPE Insulation
Aluminium/polyester Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
www.caledonian-cables.co.uk www.addison-cables.com
137ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmIndividual screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²binder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²outer sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -20°C – +50°C Minimum bending radius: 7.5 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIesConductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500
ADDISON
Caledonian138
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2Y(St)H PiMFNo. of
Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
0.5mm2, Multipair
RE-2Y(St)H PiMF 2P0.5 2x2x0.5 0.35 0.9 8.7 84
RE-2Y(St)H PiMF 4P0.5 3x2x0.5 0.35 1.0 10.2 120
RE-2Y(St)H PiMF 5P0.5 4x2x0.5 0.35 1.0 11.2 145
RE-2Y(St)H PiMF 6P0.5 5x2x0.5 0.35 1.0 12.1 171
RE-2Y(St)H PiMF 8P0.5 8x2x0.5 0.35 1.1 13.1 212
RE-2Y(St)H PiMF 10P0.5 10x2x0.5 0.35 1.2 15.1 266
RE-2Y(St)H PiMF 12P0.5 12x2x0.5 0.35 1.2 15.7 287
RE-2Y(St)H PiMF 16P0.5 16x2x0.5 0.35 1.2 17.8 387
RE-2Y(St)H PiMF 20P0.5 20x2x0.5 0.35 1.3 19.7 463
RE-2Y(St)H PiMF 24P0.5 24x2x0.5 0.35 1.4 21.5 554
0.75mm2, Multipair
RE-2Y(St)H PiMF 2P0.75 2x2x0.75 0.38 1.0 9.7 101
RE-2Y(St)H PiMF 4P0.75 3x2x0.75 0.38 1.0 11.2 152
RE-2Y(St)H PiMF 5P0.75 4x2x0.75 0.38 1.1 12.5 177
RE-2Y(St)H PiMF 6P0.75 5x2x0.75 0.38 1.1 13.6 224
RE-2Y(St)H PiMF 8P0.75 8x2x0.75 0.38 1.1 14.4 269
RE-2Y(St)H PiMF 10P0.75 10x2x0.75 0.38 1.2 16.6 335
RE-2Y(St)H PiMF 12P0.75 12x2x0.75 0.38 1.2 17.4 376
RE-2Y(St)H PiMF 16P0.75 16x2x0.75 0.38 1.3 19.8 485
RE-2Y(St)H PiMF 20P0.75 20x2x0.75 0.38 1.4 22.0 589
RE-2Y(St)H PiMF 24P0.75 24x2x0.75 0.38 1.5 24.0 713
1.0mm2, Multipair
RE-2Y(St)H PiMF 2P1.0 2x2x1.0 0.4 1.0 10.4 117
RE-2Y(St)H PiMF 4P1.0 3x2x1.0 0.4 1.0 12.1 174
RE-2Y(St)H PiMF 5P1.0 4x2x1.0 0.4 1.1 13.5 220
www.caledonian-cables.co.uk www.addison-cables.com
139ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2Y(St)H PiMFNo. of
Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2Y(St)H PiMF 6P1.0 5x2x1.0 0.4 1.1 14.7 257
RE-2Y(St)H PiMF 8P1.0 8x2x1.0 0.4 1.2 15.8 324
RE-2Y(St)H PiMF 10P1.0 10x2x1.0 0.4 1.2 18.0 403
RE-2Y(St)H PiMF 12P1.0 12x2x1.0 0.4 1.3 19.0 456
RE-2Y(St)H PiMF 16P1.0 16x2x1.0 0.4 1.3 21.5 603
RE-2Y(St)H PiMF 20P1.0 20x2x1.0 0.4 1.4 23.9 721
RE-2Y(St)H PiMF 24P1.0 24x2x1.0 0.4 1.5 26.1 866
1.3mm2, Multipair
RE-2Y(St)H PiMF 2P1.3 2x2x1.3 0.45 1.0 11.4 143
RE-2Y(St)H PiMF 4P1.3 3x2x1.3 0.45 1.1 13.4 208
RE-2Y(St)H PiMF 5P1.3 4x2x1.3 0.45 1.1 14.8 271
RE-2Y(St)H PiMF 6P1.3 5x2x1.3 0.45 1.2 16.3 319
RE-2Y(St)H PiMF 8P1.3 8x2x1.3 0.45 1.3 17.6 407
RE-2Y(St)H PiMF 10P1.3 10x2x1.3 0.45 1.3 20.0 502
RE-2Y(St)H PiMF 12P1.3 12x2x1.3 0.45 1.4 21.1 554
RE-2Y(St)H PiMF 16P1.3 16x2x1.3 0.45 1.5 24.1 730
RE-2Y(St)H PiMF 20P1.3 20x2x1.3 0.45 1.6 26.8 912
RE-2Y(St)H PiMF 24P1.3 24x2x1.3 0.45 1.7 29.2 1090
1.5mm2, Multipair
RE-2Y(St)H PiMF 2P1.5 2x2x1.5 0.45 1.0 11.8 158
RE-2Y(St)H PiMF 4P1.5 3x2x1.5 0.45 1.1 13.9 243
RE-2Y(St)H PiMF 5P1.5 4x2x1.5 0.45 1.2 15.5 290
RE-2Y(St)H PiMF 6P1.5 5x2x1.5 0.45 1.2 16.9 358
RE-2Y(St)H PiMF 8P1.5 8x2x1.5 0.45 1.3 18.2 447
RE-2Y(St)H PiMF 10P1.5 10x2x1.5 0.45 1.4 21.0 550
RE-2Y(St)H PiMF 12P1.5 12x2x1.5 0.45 1.4 21.9 625
RE-2Y(St)H PiMF 16P1.5 16x2x1.5 0.45 1.5 25.1 831
ADDISON
Caledonian140
Caledonian Cable Code
RE-2Y(St)H PiMFNo. of
Pairsx2xCross Section
NominalInsulationThickness
NominalOuter Sheath
Thickness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm mm mm kg/km
RE-2Y(St)H PiMF 20P1.5 20x2x1.5 0.45 1.6 27.8 1007
RE-2Y(St)H PiMF 24P1.5 24x2x1.5 0.45 1.7 30.4 1223Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
BS 5308Part1 Type1
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
www.caledonian-cables.co.uk www.addison-cables.com
141ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Pe Insulated, lsZH sheathed, Individual and overall screened & armoured Instrumentation cables (Multipair)
re-2y(st)HsWaH PiMf 90°c / 300V
LSZH Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperPE Insulation
PETP Transparent Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
LSZH Inner Sheath
Aluminium/polyester Tape
aPPlIcaTIon
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral.Recommended for use as fire protection messure for people and important material assets.
sTanDarDs
Basic design to EN 50288-7
fIre PerforMance
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard, *** denotes optional.
ADDISON
Caledonian142
VolTaGe raTInG
300V
cable consTrUcTIon
conductor: Annealed bare copper, stranded to IEC 60228 Class 2.Insulation: PE compound as per EN 50290. 2-23.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmIndividual screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²binder tape: PETP transparent tapeoverall screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²Inner sheath: LSZH compoundamouring: Galvanized steel wire armourouter sheath: LSZH compound as per EN 50290-2-27. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
coloUr coDe
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.outer sheath: Black or blue for intrinsically safe systems
PHysIcal anD THerMal ProPerTIes
Temperature range During operation (fixed state): -30°C – +90°C Temperature range During Installation (Mobile state): -20°C – +50°C Minimum bending radius: 10 X Overall Diameter sunlight resistance: UL 1581 section 1200 oil resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)
elecTrIcal ProPerTIesConductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
www.caledonian-cables.co.uk www.addison-cables.com
143ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Test Voltage Core to Core V 1500
Core to Screen V 1500
consTrUcTIon ParaMeTers
Caledonian Cable Code
RE-2X(St)HSWAH PiMF
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
0.5mm2, MultipairRE-2X(St)HSWAH PiMF 2P0.5 2x2x0.5 0.35 0.9 8.7 0.9 1.4 13.3 311
RE-2X(St)HSWAH PiMF 4P0.5 3x2x0.5 0.35 1.0 10.2 0.9 1.4 14.8 374
RE-2X(St)HSWAH PiMF 5P0.5 4x2x0.5 0.35 1.0 11.2 0.9 1.4 15.8 451
RE-2X(St)HSWAH PiMF 6P0.5 5x2x0.5 0.35 1.0 12.1 0.9 1.6 16.9 484
RE-2X(St)HSWAH PiMF 8P0.5 8x2x0.5 0.35 1.1 13.1 0.9 1.6 17.9 563
RE-2X(St)HSWAH PiMF 10P0.5 10x2x0.5 0.35 1.2 15.1 0.9 1.5 19.9 782
RE-2X(St)HSWAH PiMF 12P0.5 12x2x0.5 0.35 1.2 15.7 0.9 1.5 20.5 804
RE-2X(St)HSWAH PiMF 16P0.5 16x2x0.5 0.35 1.2 17.8 1.25 1.6 23.5 970
RE-2X(St)HSWAH PiMF 20P0.5 20x2x0.5 0.35 1.3 19.7 1.25 1.7 25.6 1145
RE-2X(St)HSWAH PiMF 24P0.5 24x2x0.5 0.35 1.4 21.5 1.25 1.7 27.4 1272
0.75mm2, Multipair
RE-2X(St)HSWAH PiMF 2P0.75 2x2x0.75 0.38 1.0 9.7 0.9 1.4 14.3 342
RE-2X(St)HSWAH PiMF 4P0.75 3x2x0.75 0.38 1.0 11.2 0.9 1.4 15.8 439
RE-2X(St)HSWAH PiMF 5P0.75 4x2x0.75 0.38 1.1 12.5 0.9 1.5 17.3 498
RE-2X(St)HSWAH PiMF 6P0.75 5x2x0.75 0.38 1.1 13.6 0.9 1.5 18.4 565
RE-2X(St)HSWAH PiMF 8P0.75 8x2x0.75 0.38 1.1 14.4 0.9 1.5 19.2 639
RE-2X(St)HSWAH PiMF 10P0.75 10x2x0.75 0.38 1.2 16.6 1.25 1.6 22.3 878
RE-2X(St)HSWAH PiMF 12P0.75 12x2x0.75 0.38 1.2 17.4 1.25 1.6 23.1 944
RE-2X(St)HSWAH PiMF 16P0.75 16x2x0.75 0.38 1.3 19.8 1.25 1.7 25.7 1132
RE-2X(St)HSWAH PiMF 20P0.75 20x2x0.75 0.38 1.4 22.0 1.25 1.7 27.9 1329
RE-2X(St)HSWAH PiMF 24P0.75 24x2x0.75 0.38 1.5 24.0 1.25 1.8 30.1 1488
ADDISON
Caledonian144
Caledonian Cable Code
RE-2X(St)HSWAH PiMF
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
1.0mm2, MultipairRE-2X(St)HSWAH PiMF 2P1.0 2x2x1.0 0.4 1.0 10.4 0.9 1.4 15.0 377
RE-2X(St)HSWAH PiMF 4P1.0 3x2x1.0 0.4 1.0 12.1 0.9 1.4 16.7 502
RE-2X(St)HSWAH PiMF 5P1.0 4x2x1.0 0.4 1.1 13.5 0.9 1.5 18.3 567
RE-2X(St)HSWAH PiMF 6P1.0 5x2x1.0 0.4 1.1 14.7 0.9 1.5 19.5 658
RE-2X(St)HSWAH PiMF 8P1.0 8x2x1.0 0.4 1.2 15.8 0.9 1.5 20.6 865
RE-2X(St)HSWAH PiMF 10P1.0 10x2x1.0 0.4 1.2 18.0 1.25 1.6 23.7 994
RE-2X(St)HSWAH PiMF 12P1.0 12x2x1.0 0.4 1.3 19.0 1.25 1.7 24.7 1112
RE-2X(St)HSWAH PiMF 16P1.0 16x2x1.0 0.4 1.3 21.5 1.25 1.7 27.4 1363
RE-2X(St)HSWAH PiMF 20P1.0 20x2x1.0 0.4 1.4 23.9 1.25 1.7 29.8 1512
RE-2X(St)HSWAH PiMF 24P1.0 24x2x1.0 0.4 1.5 26.1 1.25 1.8 32.2 1996
1.3mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.3 2x2x1.3 0.45 1.0 11.4 0.9 1.4 16.0 452
RE-2X(St)HSWAH PiMF 4P1.3 3x2x1.3 0.45 1.1 13.4 0.9 1.5 18.2 577
RE-2X(St)HSWAH PiMF 5P1.3 4x2x1.3 0.45 1.1 14.8 0.9 1.5 19.6 647
RE-2X(St)HSWAH PiMF 6P1.3 5x2x1.3 0.45 1.2 16.3 0.9 1.6 21.3 858
RE-2X(St)HSWAH PiMF 8P1.3 8x2x1.3 0.45 1.3 17.6 1.25 1.6 23.3 982
RE-2X(St)HSWAH PiMF 10P1.3 10x2x1.3 0.45 1.3 20.0 1.25 1.7 25.9 1153
RE-2X(St)HSWAH PiMF 12P1.3 12x2x1.3 0.45 1.4 21.1 1.25 1.7 27.0 1287
RE-2X(St)HSWAH PiMF 16P1.3 16x2x1.3 0.45 1.5 24.1 1.25 1.8 30.2 1564
RE-2X(St)HSWAH PiMF 20P1.3 20x2x1.3 0.45 1.6 26.8 1.25 1.9 33.1 1960
RE-2X(St)HSWAH PiMF 24P1.3 24x2x1.3 0.45 1.7 29.2 1.25 2.0 36.4 2356
1.5mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.5 2x2x1.5 0.45 1.0 11.8 0.9 1.5 16.6 475
RE-2X(St)HSWAH PiMF 4P1.5 3x2x1.5 0.45 1.1 13.9 0.9 1.5 18.7 616
RE-2X(St)HSWAH PiMF 5P1.5 4x2x1.5 0.45 1.2 15.5 0.9 1.5 20.3 819
RE-2X(St)HSWAH PiMF 6P1.5 5x2x1.5 0.45 1.2 16.9 1.25 1.6 22.6 941
www.caledonian-cables.co.uk www.addison-cables.com
145ADDISON
caledonianPe Insulated, lsZH sheathed en 50288-7 Instrumentation cables
Caledonian Cable Code
RE-2X(St)HSWAH PiMF
No. of Pairsx2xCross Section
NominalInsulation
Thick-ness
NominalInner
SheathThick-ness
Nominal Overall
Diameter OverInner
Sheath
Nominal Armour
Wire Diameter
NominalOuter
SheathThick-ness
Nominal Overall
Diameter
Approx. Weight
No.x2xmm2 mm2 mm mm mm mm mm kg/km
RE-2X(St)HSWAH PiMF 8P1.5 8x2x1.5 0.45 1.3 18.2 1.25 1.7 24.1 1039
RE-2X(St)HSWAH PiMF 10P1.5 10x2x1.5 0.45 1.4 21.0 1.25 1.7 26.9 1242
RE-2X(St)HSWAH PiMF 12P1.5 12x2x1.5 0.45 1.4 21.9 1.25 1.7 27.8 1387
RE-2X(St)HSWAH PiMF 16P1.5 16x2x1.5 0.45 1.5 25.1 1.25 1.8 31.2 1935
RE-2X(St)HSWAH PiMF 20P1.5 20x2x1.5 0.45 1.6 27.8 1.25 1.9 34.8 2227
RE-2X(St)HSWAH PiMF 24P1.5 24x2x1.5 0.45 1.7 30.4 1.25 2.0 37.6 2545
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300V
NStandard
BS 5308Part1 Type2
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24EN50266-2-4
Sunlight ResistanceUL 1581
section 1200
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
Oil ResistanceICEA S-73-532
ADDISON
Caledonian146
Type codes for fire retardant Instrumentation cables
re-2X(st)HsWaH
ArmourSWA: Steel Wire Armour
Outer SheathH: LSZH
ScreenSt: Aluminium/polyester TapeCWB: Copper Wire Braid
Inner SheathH: LSZH
Insulation2X: XLPE2Y: PE
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
147ADDISON
Technical Information
flaMe reTarDance In accorDance WITH DIfferenT sTanDarDs
The following standards specify a method for flame propagation test for single core cables. The single cable sample undergoes the flame action of a bunsen burner. The test only lasts few minutes.
The IEC 60332-1 standards are taken over as EN standards and transferred to national standards Example: IEC 60332-1 becomes EN 60332-1 and introduced in Germany as DIN EN 60332-1.
flame retardance in accordance with en 60332:2004 EN 60332:2004 Tests on electrical and optical cables under fire conditions. The standard applies to single insulated wires (cables) and requires a vertical flame test with a maximum flame climb of 450mm. The test lasts between 1 and 8 minutes, depending on the cable diameter.
EN 60332-1-1:2004 / BS EN 60332-1-1:2004 / IEC 60332-1-1:2004 / DIN EN 60332-1-1:2004 / VDE 0482-1-1:2005-06 Test on electrical and optical cables under fire conditions. Test for a vertical flame propagation fo a single insulated wire or cables.
EN 60332-1-2:2004 / BS EN 60332-1-2:2004 / IEC 60332-1-2:2004 / DIN EN 60332-1-2:2004 / VDE 0482-1-2:2005-06 / CEI 60332-1-2( CEI 20-35/1-2 ) Tests on electrical and optical fiber cables under fire conditions. Test for a vertical flame propagation for a single insulated wire or cable – Procedure for 1kW premixed flame.
This standard specifies a method of test for resistance to vertical flame propagation for a single insulated wire or cable. Part 1-1 specifies the test apparatus and Part 1-2 specifies the test procedure.
The cable sample is deemed to pass the test if the distance between the lower edge of the top support and the onset of charring is greater than 50mm. In addition, a failure shall be recorded if burning extends downward to a point greater than 540mm from the lower edge of the top support.
EN 60332-1-2:2004 specifies the use of 1kW premix flame and is for general use, except that the procedure may not be suitable for the testing of small insulated conductors or cables of less than 0.5mm sq cross section because the conductor melts before the test is completed, or for the testing of small optic fiber cables because the fiber will be broken before the test is completed. In this case, the procedure given by EN 60332-2-1/2 is recommended.
EN 60332-2-1:2004 / BS EN 60332-2-1:2004 / IEC 60332-2-1:2004 / DIN EN 60332-2-1:2004 / VDE 0482-2-1:2005-06 Tests on electrical and optical cables under fire conditions. Test for a vertical flame propagation for a single small insulated wire or cable.
EN 60332-2-2:2004 / BS EN 60332-2-2:2004 / IEC60332-2-2:2004 / DIN EN 60332-2-2:2004 / VDE 0482-2-2:2005-06 / CEI 60332-2-2 (CEI 20-35/2-2) Test on electric and optical fiber cables under fire conditions. Tests for vertical flame propagation for a single small insulated wire or cable. Procedure for diffusion flame.
ADDISON
Caledonian148
This test applies to small dimensions cables.This standard specifies a method of test for resistance to vertical flame propagation for a single insulated wire or cable. Part 2-1 specifies the test apparatus and Part 2-2 specifies the test procedure.
flame retardance in accordance with nf c32-070-2.1(c2) NF C32-070:2001 Insulated conductors and cables for installation - Classification tests on conductors and cables with regard to fire behavior.NF C32-070 2.1 Procedure for 1 kW pre-mixed flame.
The NF F 32070 2.1 (Category C2) and IEC 60332-1-2 are very similar. The sole difference is the time during which the flame is applied.
flame retardance in accordance with en 50265-1:1999 (replaced by en 60332)EN 50265-1:1999 / BS EN 50265-1:1999 / DIN EN 50265-1:1999 / VDE 0482-265-1:1999-04– Common test methods for cables under fire conditions. Test for resistance to a vertical flame propagation for a single insulated conductor or cable. Apparatus (Replaced by EN 60332-1-1:2004 and EN 60332-2-1:2004).EN 50265-2-1:1999 / BS EN 50265-2-1:1999 / DIN EN 50265-2-1:1999 / VDE 0482-265-2-1:1999-04 – Common test methods for cables under fire conditions. Test for resistance to a vertical flame propagation for a single insulated conductor or cable. Part 2-1: Procedure 1kW pre-mixed flame (Replaced by EN 60332-1-2:2004).
EN 50265-2-2:1999 / BS EN 50265-2-2:1999 / DIN EN 50265-2-2:1999 / VDE 0482-265-2-2:1999-04 – Common test methods for cables under fire conditions. Test for resistance to a vertical flame propagation for a single insulated conductor or cable. Part 2-2: Procedure Diffusion flame (Replaced by EN 60332-2-2:2004).
flame retardance in accordance with bs 4066 Part 1 & 2 (replaced by en 60332) BS 4066-2:1980 (superseded) – Tests on electic cables under fire conditions. Method of test on a single vertical insulated wire or cable.
This standard is no longer in force and is replaced by BS EN 50265-2-1 which was also superseded by BS EN 60332-1:2009.
flame retardance in accordance with nbn c 30-004 (cat. f1) NBN C 32-004 specifies a method of test for measuring the vertical flame propagation characteristics of a single wire or cable. The cable specimen is deemed to have passed the test and categorized as F1 if after burning has ceased, the charred or affected portion does not reach within 50mm of the lower edge of the top clamp which is equivalent to 425mm above the point of flame application.
flame retardance in accordance with Ieee 383In the IEEE 383 test, cables are supported by a one foot wide vertical rack eight feet high. The cables are positioned in the centre six inches of the rack, spaced one-half diameter apart. The rack is centered in an eight foot enclosure. A ten inch ribbon burner ignites the cable with a 21 kW (70000 BTU). The burner is positioned 2 feet above the floor and 9 to 12 inches of cables are exposed to
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
149ADDISON
direct flames for 20 minutes. Cables on which flame extends above the top of the 8 foot rack fail the test.reDUceD fIre ProPaGaTIon In accorDance WITH DIfferenT sTanDarDs
These standards specify a method for fire propagation test for vertically mounted bunched cables. These tests simulate the chimney effect in vertical installation of bunch of cables. A certain number of cable sections with a length of 3.5 m is fastened to a vertical ladder in an adapted chamber. The amount of combustible materials for cables and duration of flame application depends on the category the cable has to meet.
Resistance of the wires bundle arranged vertically to the spread of the flame should be such that after a certain time and stopping the source of ignition, flame is extinguished by itself and the length of charred fragments will not exceed 2.5 m in height measured above the lower edge of the burner.
reduced fire Propagation in accordance with Iec 60332-3This test is the most common one to verify the behaviour of a cables for the fire propagation. The cables are installed on a bunch of vertical ladder inside a metal cabinet and undergo the action of a ribbon flame at 750°C.The standard is subdivided in several parts that differ one from the other for the quantity of cable to be installed, the installation mode and the flame application time.
EN 60332-3-10:2009 / BS EN 60332-3-10:2009 / IEC 60332-3-10 ed1.1 / DIN EN 60332-3-10:2009 / VDE 0482-332-3-10:2010-08 – Common test methods for cables under fire conditions. Tests on electric and optical fiber cables under fire conditions - Part 3-10: Test for vertical flame spread of vertically mounted bunched wires or cables.
EN 60332-3-21:2009 / BS EN 60332-3-21:2009 / IEC 60332-3-21 ed1.1 / DIN EN 60332-3-21 / VDE 0482-332-3-21:2010-08 / CEI EN 60332-3-21:2009 (CEI 20-22/3-1)– Procedures. Tests on electric and optical fiber cables under fire conditions - Part 3-21: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category A . F/R-Installation In one layer (front). -Installation In two layers (front and rear)-The quantity of the Installed cable is equal to 7 litres/m of combustible materials for cables-The time of application of the flame is 40 minutes
EN 60332-3-22:2009 / BS EN 60332-3-22:2009 / IEC 60332-3-22 ed1.1 / DIN EN 60332-3-22:2009 /VDE 0482-332-3-22:2010-08 / CEI EN 60332-3-22:2009 (CEI 20-22/3-2)– Procedures. Tests on electric and optical fiber cables under fire conditions - Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cable - Category A
-Installation In one layer (front). -The quantity of the installed cable is equal to 7 litres/m of combustible materials for cables
ADDISON
Caledonian150
-The time of application of the flame is 40 minutes
EN 60332-3-23:2009 / BS EN 60332-3-23:2009 / IEC 60332-3-23 ed1.1 / DIN EN 60332-3-23:2009 / VDE 0482-332-3-23:2010-08 / CEI EN 60332-3-23:2009 (CEI 20-22/3-3)– Procedures. Tests on electric and optical fiber cables under fire conditions - Part 3-23: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category B
-Installation In one layer (front). -The quantity of the installed cable is equal to 3.5 litres/m of combustible materials for cables-The time of application of the flame is 40 minutes
EN 60332-3-24:2009 / BS EN 60332-3-24:2009 / IEC 60332-3-24 ed1.1 / DIN EN 60332-3-24:2009 / VDE 0482-332-3-24:2010-08 / CEI EN 60332-3-24:2009 (CEI 20-22/3-4) – Procedures. Tests on electric and optical fiber cables under fire conditions - Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C
-Installation In one layer (front). -The quantity of the installed cable is equal to 1.5 litres/m of combustible materials for cables-The time of application of the flame is 20 minutes
EN 60332-3-25:2009 / BS EN 60332-3-25:2009 / IEC 60332-3-25 ed1.1 / DIN EN 60332-3-25: 2009 / VDE 0482-332-3-25:2010-08 / CEI EN 60332-3-25:2009 (CEI 20-22/3-5)– Procedures. Tests on electric and optical fiber cables under fire conditions - Part 3-25: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category D-Installation In one layer (front). -The quantity of the installed cable is equal to 0.5 litres/m of combustible materials for cables-The time of application of the flame is 20 minutes.
Summary of test condition:Iec 60332-3-21 60332-3-22 60332-3-23 60332-3-24 60332-3-25bs en 50266 50266-2-1 50266-2-2 50266-2-3 50266-2-4 50266-2-5ceI 20-22/3-1 20-22/3-2 20-22/3-3 20-22/3-4 20-22/3-5category AF/R A B C Dconductor cross-sectionsmm2
>35 >35 ≤35 >35 ≤35 >35 ≤35 >35 ≤35
nMV(Iitres per metre of cable)
7 7 3.5 1.5 0.5
Minimum length of test pieces(m)
3.5 3.5 3.5 3.5 3.5
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
151ADDISON
standard ladder (500 mm wide):• number of layers• maximum width of test sampIe
1front+1rear300mm
≥1front300mm
1front300mm
--
≥1front300mm
1front300mm
≥1front300mm
1front300mm
≥1front300mm
Wide ladder (800 mm wide):• number of layers• maximum width of test sampIe
--
--
--
1front600mm
--
--
--
Positioning of test pieces
Spaced 0.5×Diameter
cable(Max.20mm)
TouchingSpaced
0.5×Diameter cable
(Max.20mm)Touching
Spaced 0.5×Diameter
cable(Max.20mm)
TouchingSpaced
0.5×Diameter cable
(Max.20mm)Touching
number of burners 1 1 1 2 1 1 1ladder mounting
Front and rear
Front, Wider ladder forlarger cables Front Front Front
flame application time(min)
40 40 40 40 40 40
Testconditions Wind speed: <8 m/s; Ternperature: 5°C - +40°C
extent of the charred portion≤2.5m above the bottom edge of the burner, neither at the front nor at the rear of the ladder.
Reduced fire propagation in accordance with NF C32-070-2.2(C1)NF C32-070 :2001 Insulated conductors and cables for installation.-Classification tests on conductors and cables with regard to fire behavior.
A 1600mm vertically installed bundled of cable is exposed to the effects of a radiating oven (approx 830°C) and forced ventilation. Pilot flames arranged above the oven burn off the emitted gases. The test duration is 30 minutes, with the ventilation stopped for every 10 minutes during the flame application period. The cable sample is classified under Category C1 according to NF F 32070-2.2 if the carbonised pathe cable sample does not extend more than 0.8m above the upper base of the oven.
Depending on the damaged length, they can be further classified into 4 classes A, B, C and D according to NF F 16-101 as follows:category Test resultA No damaged length from top of the oven in upper position.B Damaged length from top of oven in upper position not extending more than 50mm.C Damaged length from top of oven in upper position not extending more than 300mm
D Damaged length from top of oven in upper position not extending above the top of the chimney
ADDISON
Caledonian152
reduced fire Propagation in accordance to en 50266-1, en 50266-2-2, en 50266-2-3, en 50266-2-4. EN 50266-1:2001 / BS EN 50266-1:2001 / DIN EN 50266-1:2001 / VDE 0482-266-1:2001-09– Common test methods for cables under fire conditions. Test for vertical flame spread of vertically mounted bunched wires or cables - Part 1: Apparatus (Replaced by EN 60332-3-10:2009)
EN 50266-2-1 :2001 / BS EN 50266-2-1 :2001 / D IN EN 50266-2-1 :2001 / VDE 0482-266-2-1:2001-09 / CEI EN 50266-2-1– Common test methods for cables under fire conditions. Test for vertical flame spread of vertically mounted bunched wires or cables - Part 2-1 : Procedures. Category A F/R (Replaced by EN 60332-3-21:2009)
EN 50266-2-2 :2001 / BS EN 50266-2-2 :2001 / D IN EN 50266-2-2:2001 / VDE 0482-266-2-2:2001-09 / CEI EN 50266-2-2– Common test methods for cables under fire conditions. Test for vertical flame spread of vertically mounted bunched wires or cables - Part 2-2: Procedures. Category A (Replaced by EN 60332-3-22:2009)
EN 50266-2-3 :2001 / BS EN 50266-2-3 :2001 / D IN EN 50266-2-3:2001 / VDE 0482-266-2-3:2001-09 / CEI EN 50266-2-1– Common test methods for cables under fire conditions. Test for vertical flame spread of vertically mounted bunched wires or cables - Part 2-3: Procedures. Category B (Replaced by EN 60332-3-23:2009)
EN 50266-2-4 :2001 / BS EN 50266-2-4 :2001 / D IN EN 50266-2-4 :2001 / VDE 0482-266-2-4:2001-09 / CEI EN 50266-2-4:2001 – Common test methods for cables under fire conditions. Test for vertical flame spread of vertically mounted bunched wires or cables - Part 2-4: Procedures. Category C (Replaced by EN 60332-3-24:2009).
reduced fire Propagation in accordance with bs 4066-3BS 4066-3:1994 (superseded) – Tests on electic cables under fire conditions. Tests on bunched wires or cables. This standard is no longer in force and is replaced by the BS EN 50266-1:2001
reduced fire Propagation in accordance with nbn c 32-004 (f2)NBN C 32-004 specifies a method of test for measuring the vertical flame propagation characteristics of a bunch of cables. The cable specimen is deemed to have passed the test and categorized as F2 if after burning has ceased, the extent of charred or affected portion does not reach a height exceeding 2.5m above the bottom edge of the burner.
HaloGen conTenT TesT In accorDance WITH DIfferenT sTanDarDs
In the event of a fire, many fumes are produced. This test is concerned with the possibilities of corrosive acid gases being released from halogen containing cables and the damage such cables can cause (to equipments). These standards specify a method for determination of the amount of halogen acid gas, evolved during combustion of compound.
Halogen content Test in accordance with en 50267-2-1
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
153ADDISON
EN 50267-2-1:1998 / BS EN 50267-2-1:1999 / DIN EN 50267-2-1:1999 / VDE 0482-267-2-1:1999-04 / CEI EN 50267-2-1:1999 (CEI 20-37/2-1) Common test methods for cables under fire conditions- Test on gases evolved during combustion of materials from cables- Part 2-1: Procedures. Determination of the amount of halogen acid gas.This pathe standard defines the method to measure the amount of halogen acid evolved and which should be expressed in hydrochloric acid. The amount of halogen acid contained in the test solution is determined by a titration method. If the cables are described as zero halogen or halogen free, it is recommended that the hydrochoric acid yield should be less than 0.5%.
Halogen content Test in accordance with Iec 60754-1IEC 60754-1 ed 2.0 Common test methods for cables under fire conditions. Test on gases evolved during combustion of materials from cables. Part 1: Procedures. Determination of the amount of halogen acid gas. Basically, this is same as EN 50267-2-1.
Halogen content Test in accordance with bs 6425-1BS 6425-1:1990(superseded): Test on gases evolved during the combustion of materials from cables. Method for determination of amount of halogen acid gas evolved during combustion of polmeric materials taken from cables. This standard is no longer in force and is replaced by the EN 50267-2-1.
acID Gas eMIssIon TesT In accorDance WITH DIfferenT sTanDarDs
The following standards specify a method for determination of acidity of gas evolved during combustion of cables by measuring PH and conductivity. This test allows to determine the corrosivity of the acid gases generally halogens, that develop during the electric cable combustion.
acid Gas emission Test in accordance with en 50267-2-2EN 50267-2-2:1999 / BS EN 50267-2-2:1999 / DIN EN 50267-2-2:1999 / VDE 0482-267-2-2:1999-04 / CEI EN 50267-2-2:1999 (CEI 20-37/2-2). Common test methods for cables under fire conditions- Test on gases evolved during combustion of materials from cables- Part 2-2: Procedures. Determination of degree of acidity of gases for materials by measuring PH and conductivity The standard states that the pH and the conductivity of a test solution should be measured, using calibrated PH and conductivity meters.
If the cables are described as zero halogen or halogen free, it is recommended that at least both of the following requirements should be met for each of the individual materials of a cable:
-The PH value should not be less than 4.3 when related to 1 litre of water -The conductivity should not be less than 10us/mm when related to 1 litre of water
ADDISON
Caledonian154
EN 50267-2-3 :1999 / BS EN 50267-2-3 :1999 / D IN EN 50267-2-3 :1999 / VDE 0482-267-2-3:1999-04 / CEI EN 50267-2-3:1999 (CEI 20-37/2-3). Common test methods for cables under fire conditions- Test on gases evolved during combustion of materials from cables- Part 2-3:Procedures. Determination of degree of acidity of gases for cables by determination of the weighted average of pH and conductivity. The standard states that the pH and the conductivity of a test solution should be measured, using calibrated pH and conductivity meters. The results from the different components of the cable are then weighted.
acid Gas emission Test in accordance with Iec 60754-2IEC 60754-2 ed1.0 Test on gases evolved during combustion of electric cables - Part 2 : Determination of degree of acidity of gases evolved during combustion of materials taken from electric cables by measuring pH and conductivity.
acid Gas emission Test in accordance with nf c32-074NF C32-074 Common test methods for cables under fire conditions - Test on gases evolved during combustion of materials from cables. This standard is equivalent to IEC 60754-2
acid Gas emission Test in accordance with bs 6425-2BS 6425-2:1993 (superseded) Test on gases evolved during the combusion of materials from cables. Determination of degree of acidity (corrosivity) of gases by measuring pH and conductivity.
This standard is no longer in force and is replaced by the EN 50267-2-2:1999.
acid Gas emission Test in accordance with DIn VDe 0472-813 / VDe 0472-813:1994 DIN VDE 0472-813 / VDE 0472-813:1994 Corrosivity of combustion gases. The standards are no longer in force and are replaced by the EN 50267-2-2 & VDE 0482-267-2-2.
sMoKe DensITy TesT In accorDance WITH DIfferenT sTanDarDs
The smoke density measurement taken from a material under fire conditions gives an indication of the visibility through the smoke. This is important as reduced visibility in a real fire situation makes it more difficult to escape from the fire thus increasing the threat to human life from the toxic gas, fumes and heat
The following standards specify the method for measuring the generation of smoke from cables during fire.
smoke Density Test in accordance with Iec 61034-1 & Iec 61034-2IEC 61034-1:2005 / EN 61034-1:2005 / BS EN 61034-1:2005 / DIN EN 61034-1:2006 / VDE 0482-1034-1:2006 Measurement of smoke density of cables burning under defined conditions. Part 1: Test apparatus
IEC 61034-2:2005 / EN 61034-2:2005 / BS EN 61034-2:2005 / DIN EN 61034-2:2006 / VDE 0482-1034-2:2006 / CEI EN 61034-2:2006 (CEI 20-37/3-1) Measurement of smoke density of cables burning under defined conditions.
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
155ADDISON
Part 2: Test procedure and requirements. The standard specifies a method of measurement of smoke density of cables. Part 1 specifies the test apparatus and Part 2 specifies the test procedure.
The test is usually performed inside a chamber of 3m x3m x3m and the test is sometimes described as 3 metre cube test. The test is performed by monitoring the tranmittance reduction of a white light beam, running from one side of the chamber to the other, at a set height, thus monitoring the build up of smoke inside the chamber. The minimum percentage of light transmittance is often used to determine if the cable has passed or failed the test , often a minimum light transmittance of 60% is applied in order to classify a cable as low smoke.
smoke Density Test in accordance with nf c32- 073NF C32 073 Common test methods for cables under fire conditions. - Measurement of smoke density of cables burning under defined conditions. This standard is equivalent to IEC 61034-2
smoke Density Test in accordance with bs 7622-1 & bs 7622-2BS 7622-1:1993 (superseded) – Measurement of smoke density of electric cables burning under defined condiitions. Test apparatus. BS 7622-2:1993 (superseded) – Measurement of smoke density of electric cables burning under defined condiitions. Test procedure and requirements.
The standards are no longer in force and were replaced by the EN 50268-1:2000 and EN 50268-2:2000 even though they too were superseded by EN 61034-1:2005 and EN 61034-2:2005.
smoke Density Test in accordance with en 50268-1 & en 50268-2EN 50268-1:2000 / BS EN 50268-1:2000 / DIN EN 50268-1:2000 / VDE 0482-268-1:2000 (superseded) – Common test methods for cables under fire conditions. Measurement of smoke density of cable burning under defined conditions. Part 1: ApparatusEN 50268-2:2000 / BS EN 50268-2:2000 / DIN EN 50268-2:2000 / VDE 0482-268-2:2000 (superseded) – Common test methods for cables under fire conditions. Measurement of smoke density of cable burning under defined conditions. Part 2: Procedure.The standards are no longer in force and are replaced by the EN 61034-1:2005 and EN 61034-2:2005. Although these standards have been withdrawn, they are still called upon in some specification documents such as in the London Underground specification 1-085.
smoke Density Test In accordance with DIn VDe 0472-816 / VDe 0472-816:1994DIN VDE 0472-816/VDE 0472-816:1994 Testing of cables, wires and flexible cords. Smoke Density.
The standards are no longer in force and are replaced by the EN 50268-1, VDE 0482-268-1, EN 50268-2 & VDE 0482-268-2 which are also replaced by the EN 61034-1:2005 and EN 61034-2:2005.
oXyGen InDeX TesT In accorDance WITH DIfferenT sTanDarDs
The oxygen index is defined as the minimum concentration of oxygen, expressed as volume percentage, in a mixture of
ADDISON
Caledonian156
oxygen and nitrogen that will just support combustion of a material initially at room temperature under specified test conditions.
oxygen Index Test in accordance with asTM D 2863ASTM D 2863-10 Measuring the minimum oxygen concentration to support candle-like combustion of plastics (Oxygen Index).
The test is performed in accordance with the procedure specified in ASTM 2863-95 using test piece cut from the outer sheath of the cable. The apparatus holds a small specimen which is clamped vertically in a tube in an atmosphere where the relative concentration of oxygen and nitrogen can be changed. The aim is to test the flammability of the sample with a small pilot flame to find the minimum oxygen concentration required to just sustain combustion of the sample.
oxygen Index Test in accordance with Iso 4589-2ISO4589-2:1996 Determination of burning behaviour by oxygen index Part 2: Ambient temperature test. Specimens measuring 100mm long by 6mm wide are used for testing. The test is performed in accordance with the procedure specified in the standard.
TeMPeraTUre InDeX TesT In accorDance WITH DIfferenT sTanDarDs
This is a test for assessing the performance of a material when it is tested in accordance with BS2782: Part 1: Method 143a and 143b. The oxygen index of a material will drop when the temperature rises. When the temperature rises and the oxygen index drops to 21%, the material will burn automatically. This temperature is defined as temperature index. For example, the oxygen index of the coal at room temperature is 50% and when the temperature climbs to 150°C, it’s oxygen index drops to 21°C and the coal will burn by itself automatically. The temperature index of the coal is defined as 150°C. In general, the temperature index of fire retardant cable exceeds 250°C.
Temperature Index Test in accordance with bs 2782BS 2782: Part 1:1989 Method 143a and 143b Temperature of materials. Determination of flammability.Specimens measuring nominally 100mm long by 6.5mm wide by 3mm thick are used for testing. The specimens are then tested in accordance with the test procedure specified in the standard.
Temperature Index Test in accordance with Iso 4589-3ISO4589-3:1996 Determination of burning behaviour by oxygen index Part 3: Elevated temperature test.Specimens measuring 100mm long by 6mm wide are used for testing. The test is performed in accordance with the procedure specified in the standard.
ToXIcITy TesT In accorDance WITH DIfferenT sTanDarDs
Toxicity test in accordance with nes 02-713Measuring a fume from a material exposed to a controlled fire conditions gives an indication of the
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables
157ADDISON
fumes which may be produced in a real fire situation. A standard method of test for determining the toxicity of materials under fire condition is Defense Standard NES 02-713- Toxicity. This method gives the level of toxicity of the fumes produced from the material under test. During the test, the test specimen is heated via direct flame application at 1150°C.
The flame is applied via a bunsen burner with a flame height of between 100m and 125mm formed with a methane gas and an external supply of compressed air. The specimen toxicity is determined from accurate pre-analysis weight (4pp) colorimetric tubes and ion chromatography.
The test may determine the following species: Hydrogen Bromide, Hydrochloric Acid, Hydrogen Fluoride, Formaldehyde, Nitrous gases, Carbon Monoxide, Carbon Dioxide, Acrylonitrile, Phenol, Hydrogen Sulphide, Sulphur Dioxide, Hydrocyanic Acid, Ammonia. The concentration in ppm for each gas detected are provided. The toxicity index of the speciments summates the toxic gases, taking into account of their level of danger to humans. The smaller the toxicity index, the better the product. A limit of 5 is often applicable.
Toxicity test in accordance with nf c 20-454NF C 20-454 base environmental testing procedures. Fire behaviour. Analysis and titration of gases evolved during pyrolysis or combustion of materials used in electrotechnics. Exposure to abnormal heat or fire. Tube furnace method.
The test defined by this standard serves to define the conventional toxicity index (cti) of the gases emitted by the insulating or sleeving materials during combustion at 800°C.
Toxicity test in accordance with nf X 70-100NF X 70-100 Fire Tests; Analysis of gaseous effluents. The test is conducted within a tube furnace where the temperature is set at either 400°C, 600°C, 800°C (commonly 600°C is used for most of the materials or 800°C for some electrical products) for 40 minutes throughout the test by analysis of the toxicity index of the gases including CO, CO2, HCL, HBr, HCN, HF and SO2.
ADDISON
Caledonian158
Address:
Marchants Industrial Centre, Mill Lane, Laughton, Lewes,
East Sussex, BN8 6AJ, UK
Tel: 44(0) 207 4195087
Fax: 44(0) 207 8319489
E-mail: [email protected]
www.caledonian-cables.co.uk
Caledonian
EN 50288-7 XLPE & PE Insulated
LSZH SheathedInstrumentation Cables
www.caledonian-cables.co.uk www.addison-cables.com
CaledonianfIreToX fire retardant en 50288-7 Instrumentation cables