FINAL STEP 6. CLOSE BOX
STEP 5. OUTPUT TO FIXTURE
STEP 1. INSTALL HOUSING STEP 2. OPEN BOX
p.1/2
CBX DAISY CHAIN CONFIGURATIONDMX/RDM & ETHERNET
2X
CONNECTION STEPS
CBX-DS ™
Bottom half of CBX housing shown
100-277V &DATAOUTPUT TOFIXTURE(TYPICAL 5CONDUCTORCABLE)
DATA OUT -
100-277V INPUT
SUITABLE STRAIN RELIEFDEVICE TO BEPROVIDED BY INSTALLINGCONTRACTOR.
LIVE (BLACK)NEUTRAL (WHITE)GROUND (GREEN)
GROUND (GREEN)
DATAINPUT DATA IN +
DATA IN-
DATA OUT +
LIVE (BLACK)NEUTRAL (WHITE)
OUT -1
DATAINPUT
100-277V & DATAOUTPUT TO FIXTURE(TYPICAL 5 CONDUCTOR CABLE)(MAXIMUM OF (4X) CASCADINGCONTROL BOXES PER INSTALLATION,ISOLATED)
100-277V INPUTOPTIONAL DATA
OUTPUT TO NEXT CBX(NOT ISOLATED/NOT BOOSTED)
DATA OUT -
GROUND (GREEN)DATA OUT +
DATA IN -DATA IN +
LIVE (BLACK)NEUTRAL (WHITE)
GROUND (GREEN)
LIVE (BLACK)NEUTRAL (WHITE)
2X
MOUNTING HOLES ON THE BOTTOM OF THE CBX
4X
STEP 4. DATA INPUT (ETHERNET CONTROL OPTION)
USE 1/4”-20 UNC OR M6 ANCHORING BOLTS THAT ARE APPROPRIATE FOR USE WITH YOUR MOUNTING SURFACE (PROVIDED BY INSTALLING CONTRACTOR)
[160mm]166 5 "
5 516
"
[135mm]
INSTALL HOUSING WITH COVER FACING
UP WHEN OPEN
NOTICE
KEEP 5" [127mm] CLEARANCE ON ALL SIDES
NOTICE
USE A 5/16" [8mm] STRIP LENGTH FOR CONNECTIONSNOTICE
[8mm]165 "
5"[127mm]
IF INPUT IS ETHERNET, CONNECT CABLE DIRECTLY TO RJ45 PORT ON CONTROL CARD AND PROCEED TO THE NEXT STEP.
AS DELIVERED
CAUTION
WARNING!
DO NOT EXCEED CONTROLSPECIFIED VOLTAGE.
WARNING!
DO NOT USE IF PARTS ORCONNECTORS ARE DAMAGED.
WARNING!
CAUTION
American Color CodeWIRE COLOR / USE
GREEN GROUNDWHITE NEUTRALBLACK LIVE 100-277VRED or PURPLE DATA +ORANGE DATA -
CE Color CodeWIRE COLOR / USE
YELLOW/GREEN GROUNDBLUE NEUTRALBROWN LIVE 220/240VBLACK DATA +GREY DATA -
American Color Code Shown
CONSULT BLOCK CONNECTORMARKINGS FOR APPROPRIATE USAGE
POWER INPUT/DATA OUTPUT:RECOMMENDED WIRE GAUGE: 16 AWG [1.307mm²]
RANGE: 20-12 AWG [0.519-3.301mm²]
DATA INPUT:WIRE GAUGE RANGE: 24-16 AWG [0.205-1.307mm²]
NOTICEWARNING!
SEPARATION OF FIELD INSTALLED POWER LIMITED CIRCUIT (DIMMING/CONTROL) WIRING FROM THE BRANCH CIRCUIT
WIRING IN THE OUTLET BOX ARE TO BE MADE IN ACCORDANCE WITH LOCAL
AND/OR NATIONAL ELECTRICAL INSTALLATION CODES.
DISCONNECT POWER BEFORE INSTALLING OR SERVICING TO
AVOID ELECTRICAL SHOCK.
UNAUTHORIZED FIELD REPAIRS WILL VOID WARRANTY.
THE USE OF RTV SILICONE IS RECOMMENDED TO SEAL ALL
ENTRY POINTS (PRESSURE GLANDS, CONDUIT). THIS WILL ENSURE THE
ASSEMBLY IS WATERTIGHT.
PROVIDED TOOL:FLAT SCREWDRIVER
(FOR BLOCK CONNECTOR WIRING)
REQUIRED TOOL:#3 PHILLIPS
SCREWDRIVER
DMX/Data Cable SpecificationDMX Cable from Controller to CBX and CBX to CBX shall adhere to ANSI E1.11 – 2008 (r2013) – Entertainment Technology – USITT DMX512-A, Asynchronous Serial Digital Data Transmission Standard for
Controlling Lighting Equipment and Accessories. At minimum DMX Cable shall be 1-Pair (24 AWG, 7x32 Stranding)Twisted (minimum of 4.8 twists/foot), Shielded, minimum of 100 ohms Impedance, and <25 pF/ft. Capacitance.
Combined Power & Data Cable SpecificationFixture cabling from CBX to Fixtures shall be installed per NEC and Local Codes. All cables shall be SOOW style cables with minimum of 16 AWG annealed stranded bare copper per ASTM B-174 with a
minimum temperature range of -40°C to +90°C. All conductor standing must be a minimum of 26/30 and capable of handling 13 amps. Cable must be water resistant, UL Listed and CSA certified for indoor and outdoor use. Must be Ozone-sunlight (UV) and weather resistant.
STEP 3. 100-277V INPUTLOCKING CONNECTION
STEP 4. DATA INPUT (DMX/RDM CONTROL OPTION)PUSH IN CONNECTION LOCKING CONNECTION
SHIFT THE TERMINATION SWITCH TO THE "ON"
POSITION TO TERMINATE THE LAST CBX IN THE DAISY
CHAIN.
FOR ALL OTHER CBX IN THE RUN SHIFT THE TERMINATION
SWITCH TO THE "OFF" POSITION.
NOTICE
OFF
ON
100-277V
drawing number 121846
INSTALLATION INSTRUCTIONS
2016.07.28NK - R5
Lumenpulse, 1751 Richardson, Suite 1505, Montreal (Quebec) Canada H3K 1G6 1.877.937.3003 P. 514.937.3003 F. [email protected] www.lumenpulse.com
Copyright © Lumenpulse 2016
Lumenpulse reserves the right to make changes to this product and related instructions at any time without prior notice and such changes shall be effective immediately. See www.lumenpulse.com/support/downloads for current data and instructions.
This product must be installed in accordance with applicable national and local electrical and constructioncodes by a person familiar with the construction and operation of the product and the hazards involved.
Failure to comply with the following installation instructions may result in death or serious injury. !
OUT -1
p.2/2
CBX DAISY CHAIN CONFIGURATIONDMX/RDM & ETHERNET
CBX-DS ™
FINAL STEP 6. CLOSE BOX
STEP 3. 347V INPUT STEP 4. DATA INPUT (DMX/RDM CONTROL OPTION)
STEP 4. DATA INPUT (ETHERNET CONTROL OPTION)
STEP 5. OUTPUT TO FIXTURE
2X
CONNECTION STEPS
Bottom half of CBX housing shown
347V & DATAOUTPUT TO FIXTURE(TYPICAL 5 CONDUCTOR CABLE)
IF INPUT IS ETHERNET, CONNECT CABLE DIRECTLY TO RJ45 PORT ON CONTROL CARD
AND PROCEED TO THE NEXT STEP.
STEP 1. INSTALL HOUSING STEP 2. OPEN BOX
2X
MOUNTING HOLES ON THE BOTTOM OF THE CBX
4X
PROVIDED TOOL:FLAT SCREWDRIVER
(FOR BLOCK CONNECTOR WIRING)
REQUIRED TOOL:#3 PHILLIPS
SCREWDRIVER
USE 1/4”-20 UNC OR M6 ANCHORING BOLTS THAT ARE APPROPRIATE FOR USE WITH YOUR MOUNTING SURFACE (PROVIDED BY INSTALLING CONTRACTOR)
[162mm]6 3
8 "
10 38 "
[264mm]
USE A 5/16" [8mm] STRIP LENGTH FOR CONNECTIONS
NOTICE
SHIFT THE TERMINATION SWITCH TO THE "ON"
POSITION TO TERMINATE THE LAST CBX IN THE DAISY
CHAIN.
FOR ALL OTHER CBX IN THE RUN SHIFT THE TERMINATION
SWITCH TO THE "OFF" POSITION.
NOTICE
[8mm]165 "
5"[127mm]
AS DELIVERED
CAUTION
WARNING!
DO NOT EXCEED CONTROLSPECIFIED VOLTAGE.
WARNING!
DO NOT USE IF PARTS ORCONNECTORS ARE DAMAGED.
WARNING!
CAUTION
American Color CodeWIRE COLOR / USE
GREEN GROUNDWHITE NEUTRALBLACK LIVE 347VRED or PURPLE DATA +ORANGE DATA -
CONSULT BLOCK CONNECTORMARKINGS FOR APPROPRIATE USAGE
POWER INPUT/DATA OUTPUT:RECOMMENDED WIRE GAUGE: 16 AWG [1.307mm²]
RANGE: 20-12 AWG [0.519-3.301mm²]
DATA INPUT:WIRE GAUGE RANGE: 24-16 AWG [0.205-1.307mm²]
NOTICE
WARNING!
SEPARATION OF FIELD INSTALLED POWER LIMITED CIRCUIT (DIMMING/CONTROL) WIRING FROM THE BRANCH CIRCUIT
WIRING IN THE OUTLET BOX ARE TO BE MADE IN ACCORDANCE WITH LOCAL
AND/OR NATIONAL ELECTRICAL INSTALLATION CODES.
DISCONNECT POWER BEFORE INSTALLING OR SERVICING TO
AVOID ELECTRICAL SHOCK.
UNAUTHORIZED FIELD REPAIRS WILL VOID WARRANTY.
THE USE OF RTV SILICONE IS RECOMMENDED TO SEAL ALL
ENTRY POINTS (PRESSURE GLANDS, CONDUIT). THIS WILL ENSURE THE
ASSEMBLY IS WATERTIGHT.
DMX/Data Cable SpecificationDMX Cable from Controller to CBX and CBX to CBX shall adhere to ANSI E1.11 – 2008 (r2013) – Entertainment Technology – USITT DMX512-A, Asynchronous Serial Digital Data Transmission Standard for
Controlling Lighting Equipment and Accessories. At minimum DMX Cable shall be 1-Pair (24 AWG, 7x32 Stranding)Twisted (minimum of 4.8 twists/foot), Shielded, minimum of 100 ohms Impedance, and <25 pF/ft. Capacitance.
Combined Power & Data Cable SpecificationFixture cabling from CBX to Fixtures shall be installed per NEC and Local Codes. All cables shall be SOOW style cables with minimum of 16 AWG annealed stranded bare copper per ASTM B-174 with a
minimum temperature range of -40°C to +90°C. All conductor standing must be a minimum of 26/30 and capable of handling 13 amps. Cable must be water resistant, UL Listed and CSA certified for indoor and outdoor use. Must be Ozone-sunlight (UV) and weather resistant.
LOCKING CONNECTION PUSH IN CONNECTION LOCKING CONNECTION
347V & DATAOUTPUT TO FIXTURE(TYPICAL 5 CONDUCTOR CABLE)(MAXIMUM OF (4X) CASCADINGCONTROL BOXES PER INSTALLATION, ISOLATED)
DATA INPUT
OPTIONAL DATAOUTPUT TO NEXT CBX
(NOT ISOLATED/NOT BOOSTED)
347VINPUT
DATA OUT -DATA OUT +
DATA IN +DATA IN -
DATA OUT +DATA OUT -
NEUTRAL (WHITE)GROUND (GREEN)
LIVE (BLACK)
NEUTRAL (WHITE)LIVE (BLACK)
GROUND (GREEN)
SUITABLE STRAIN RELIEFDEVICE TO BE PROVIDED
BY INSTALLING CONTRACTOR.
347VINPUT
LIVE (BLACK)GROUND (GREEN)
NEUTRAL (WHITE)
TERMINATIONSWITCH
DATA OUT +DATA OUT -
NEUTRAL (WHITE)GROUND (GREEN)
LIVE (BLACK)
DATA INPUT
DATA IN +DATA IN -
OFF
ON
KEEP 5" [127mm] CLEARANCE ON ALL SIDES
NOTICE
INSTALL HOUSING WITH COVER FACING
UP WHEN OPEN
NOTICE
347V
drawing number 121846
INSTALLATION INSTRUCTIONS
2016.07.28NK - R5
Lumenpulse, 1751 Richardson, Suite 1505, Montreal (Quebec) Canada H3K 1G6 1.877.937.3003 P. 514.937.3003 F. [email protected] www.lumenpulse.com
Copyright © Lumenpulse 2016
Lumenpulse reserves the right to make changes to this product and related instructions at any time without prior notice and such changes shall be effective immediately. See www.lumenpulse.com/support/downloads for current data and instructions.
This product must be installed in accordance with applicable national and local electrical and constructioncodes by a person familiar with the construction and operation of the product and the hazards involved.
Failure to comply with the following installation instructions may result in death or serious injury. !