Chartered Institute of Building Service Engineers
(CIBSE)
‘code for interior lighting design’
![Page 2: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/2.jpg)
The maintenance factor gives an estimate of how lighting
conditions will deteriorate through everyday use.
Dust and dirt
Aging of lamps
Cleaning of room surfaces
It should be noted that without detailed knowledge of the maintenance plan a maintenance factor of 0.8 must be used.
MF = RSMF x LMF x LLMF x LSF
![Page 3: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/3.jpg)
Where:
RSMF:
Room Surface Maintenance Factor
(dirt on the surfaces of the room)
LMF
Luminaire Maintenance Factor
(dirt on luminaire)
![Page 4: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/4.jpg)
Where:
LLMF:
Lamp Lumen Maintenance Factor
(dirt on the lamp)
LSF
Luminaire Survival Factor
(reduced light output due to lamps failing)
![Page 5: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/5.jpg)
UF = lumens received on working plane
lumen output of luminaires
Utilisation factor takes account of the loss of
light due to absorption on room surfaces
![Page 6: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/6.jpg)
Type of luminaire
Room index
Reflectance of room surfaces
![Page 7: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/7.jpg)
A luminaire with a concentrated light output
directed on the working plane will have a
higher UF than a luminaire with a dispersed
output
![Page 8: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/8.jpg)
![Page 9: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/9.jpg)
This takes into account the length and
width of the given room, also the height of
the luminaires above the working plane
(Hm).
RI = L x W
(L + W) Hm
![Page 10: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/10.jpg)
![Page 11: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/11.jpg)
Brighter colours with high reflectance result
in a higher UF.
Note: A high UF means fewer lamps are
needed (see formula) resulting in a more
energy efficient light design.
![Page 12: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/12.jpg)
Ceiling Walls
Floor
Room index
![Page 13: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/13.jpg)
A garage 20m long by 12m wide with a ceiling
height of 6m is required to be illuminated to a
level of 200 lx at a working plane height of 1 m.
The luminaires will be suspended 2m below the
ceiling height. The reflectance's are as follows:
Ceiling 0.5, Walls 0.5, Floor 0.2.
The utilisation factor can be calculated from the
previous table.
![Page 14: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/14.jpg)
Room index:
RI = L x W
(L + W) Hm Therefore:
= 20 x 12
(20 + 12) 3
= 240
96
= 2.5
![Page 15: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/15.jpg)
Therefore UF is ……..
C.W.F
RI
UF
![Page 16: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/16.jpg)
A garage 26m long by 16 m wide with a ceiling
height of 7m is required to be illuminated to a level
of 500 lx at a working plane height of 1.5 m. The
luminaires will be suspended 1.5m below the
ceiling height. The reflectance's are as follows:
Ceiling 0.3, Walls 0.5, Floor 0.2.
Calculate the utilisation factor from the previous
table.
![Page 17: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/17.jpg)
Room index:
RI = L x W
(L + W) Hm Therefore:
= 26 x 16
(26 + 16) 4
= 416
168
= 2.48 (2.5)
![Page 18: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/18.jpg)
UF
![Page 19: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/19.jpg)
This is the ratio of space between luminaires
to their installed height above the working
plane.
Manufactures will generally specify a
recommended SHR to ensure their products
best performance.
![Page 20: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/20.jpg)
Example
Room dimensions: Ceiling height = 4m
Working plane = 1m
(recessed luminaire)
Manufactures recommended SHR 2:1
Therefore: SHR = 2:1
= 6:3
![Page 21: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/21.jpg)
Calculate the number of luminaires required for a given room. Dimensions: L = 20m W = 40m H = 8m • Luminaire suspended 1.5m from ceiling • Working plane 1m Manufactures recommended SHR (1.5:1)
![Page 22: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/22.jpg)
Gap from working plane to luminaire = 5.5m
Therefore: SHR 1.5 : 1
8.25 : 5.5
Width = 40m = 4.8 luminaires
8.25
Length = 20m = 2.4 luminaires
8.25
![Page 23: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/23.jpg)
s o u rce I ca n d e la
flo w lu m e n s
i l l u m in a n ce E lu x
Fig . 1 .9
Luminous Intensity
Luminous Flux
Illuminance
Luminance
![Page 24: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/24.jpg)
Luminous Intensity
The measure of light from a source .i.e. a lamp. It
is measured in candelas (cd).
Symbol: I
Luminous Flux
It is the rate at which light flows from a source. It is
measured in lumens (lm).
Symbol: F
![Page 25: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/25.jpg)
Illuminance
The measure of the amount of light falling on a surface. It is
measured in lux (lx).
Symbol: E
Luminance
Is the measure of the light intensity leaving the surface which
has been illuminated by a given source. It is measured in
candelas per meters squared (cd / m²)
Symbol: L
![Page 26: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/26.jpg)
Typical recommended maintained Lux levels:
Corridors and stairs 100
Warehouses 100 - 200
Medium bench and machine work 500
Fine painting spraying and finishing 750
Printing inspection 1000
Proof reading / drawing offices 750
General offices (desk based) 500
General offices (screen based) 300
Supermarkets 750
![Page 27: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/27.jpg)
E = (F x n) x N x MF x UF
A
![Page 28: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/28.jpg)
Where:
E = Average Illuminance (lux)
F = Initial lamp lumen output (lm)
N = Number of luminaires
n = Number of lamps per luminaire
MF = Maintenance factor
UF = Utilisation factor
A = Area (m²)
![Page 29: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/29.jpg)
This method is most suitable for interior lighting design,
where a high proportion of light on the working plane is
reflected by internal surfaces.
The lumen method, sometimes called the luminous flux
method of calculation, is normally used to calculate the
average illuminance (Lux) on working planes, or to calculate
the number of luminaires required providing a specified
average illuminance in rooms.
![Page 30: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/30.jpg)
A factory floor, 30m x 20 m, is to be illuminated
with 2 x 58 W LPMV luminaires. Calculate the
number of luminaires needed to maintain an
average illuminance of 500 lux. The initial lamp
output is 5,200 lumens. Calculations are to be
carried out using a MF of 0.8 and a UF of 0.7
![Page 31: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/31.jpg)
E = (F x n) x N x MF x UF
A
Therefore:
N = E x A
(n x F) x MF x UF
N = 500 x (30 x 20)
(2 x 5,200) x 0.8 x 0.7
= 51.51 (52 luminaires)
![Page 32: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/32.jpg)
A hotel reception area, 18m x 11 m, is to be
illuminated with 40, 70 W, 2 pin pod MBI
luminaires. The initial lamp output is
6,600lm, the MF is 0.8 and the UF is 0.65.
Calculate the average illuminance in the
reception area. Also calculate the efficacy of
the lamp.
![Page 33: Chartered Institute of Building Service Engineers (CIBSE)](https://reader031.vdocument.in/reader031/viewer/2022012016/615acd4e0d48b21870169339/html5/thumbnails/33.jpg)
E = (F x n) x N x MF x UF
A
= 6600 x 40 x 0.8 x 0.65
18 x 11
= 693.33 lux
Efficacy = 6600 / 70 = 94.3 lm/W