Connecting edge devices and fiber/copper
cabling
May 9th 2013
1 Confidential Information Wirewerks
![Page 2: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/2.jpg)
Wirewerks – Who we are François-Charles Laberge, VP Engineering & OEM
• Canadian company
• Founded in May 1991 in Montreal, Quebec. Serving the
Canadian Market
• Leader in manufacturing fiber optic and copper structured
cabling solutions.
• Committed to develop high performance fiber optic and copper
solutions with exceptional engineering and design.
• 25 year Warranty on All Products (and labor if project is certified)
• We meet the demands of today’s simplest to most complex connectivity requirements
2 Confidential Information Wirewerks
![Page 3: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/3.jpg)
Connecting Physical Security IP Networks
Confidential Information Wirewerks 3
Surveillance
Emergency Dispatch Access Control
IP Camera
![Page 4: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/4.jpg)
What it Structured Cabling System
The term Structured Cabling System is used to describe standard based
organized cable and connectivity networks designed to facilitate a variety of
internal and multi-building communications services, including integrated
voice, video, data and building management system.
Business Management System
– Fire, life and safety (FLS) or Fire Alarm (FA)
– Security and access control (SAC)
– Energy Management systems (EMS)
– Heating, ventilation and air conditioning (HVAC)
Confidential Information Wirewerks 4
![Page 5: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/5.jpg)
LAN
5
Fiber or copper cable
Telecom room
Horizontal Copper
Work area
Equipment room / Data Center
Entrance facility
Wireless
Camer
a
Access control
Video surveillance
Confidential Information Wirewerks
Camer
a
![Page 6: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/6.jpg)
Campus
Confidential Information Wirewerks 6
Distribution Center
Camera
Main Building Manufacture
Camera
Access control
300m
2km
![Page 7: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/7.jpg)
Telecom room
• Cables
• Patch panels
• Patch cords
• Media converters
• Active equipments
Confidential Information Wirewerks 7
Fiber or Copper Cable
Copper Cable
![Page 8: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/8.jpg)
Cables
• Fiber
– Single Mode, Multimode
– Mini-Distribution cables
– Distribution cables
– Armored cables
– Indoor / Outdoor cables
– Plug and Play Solutions
• Copper
– Cat5e, Cat6 & Cat6A
– 4 Twisted pair
Confidential Information Wirewerks 8
Ribbon Mini Distribution Distribution Breakout Loose Tube
BX Type Light Armor
Fiber Jacket Color Coding Single Mode (SM): Jacket Yellow Multimode 62.5 (MM OM1): Jacket Orange Multimode 50 (MM OM2): Jacket Orange Multimode 50 10g (MM OM3) : Jacket Aqua Outdoor : Jacket black
![Page 9: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/9.jpg)
Distribution Cable
The Distribution cable is used in intra-building and horizontal applications
• 900um fibers Tight Buffers
• Color coded tight buffers
• Aramid Yarn Strength Members
• OFNR and OFNP construction
• General indoor applications
• Trunk cable between floors
Confidential Information Wirewerks 9
Outer Jacket
Aramid Yarn
Colored Glass
![Page 10: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/10.jpg)
Mini-Distribution Cable
The Mini-Distribution cable is used in all density environments as direct-
connect trunk cable into equipment or patch panels
• 250um colored bare fibers
• Small O.D. for tight spaces
• Riser and plenum constructions
• Ready for MTP connectors
• High density Installations
Confidential Information Wirewerks 10
Outer Jacket
Aramid Yarn
Central Member
Inner Tube
Colored Glass
Rip Cord
![Page 11: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/11.jpg)
Armored Cable
• Provides superior crush resistance for added protection
• Eliminates the need for inner duct or conduit thus saving installation time
• OFNR and OFNP ratings allow products to be installed throughout the
facility
• Indoor areas where heavy traffic requires extra protection
• Intra building backbones and general purpose
Confidential Information Wirewerks 11
![Page 12: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/12.jpg)
Indoor / Outdoor Cable
Indoor-Outdoor cables are used in inter and intra-building backbones in
aerial, duct, and riser applications.
• 900μm Tight Buffers.
•Water blocking aramid yarn strength members.
•UV resistant jacket, OFNR and OFNP listed construction
Confidential Information Wirewerks 12
Outer Jacket
Water Blocking Aramid
Yarn
Inner Tube
Colored Glass
![Page 13: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/13.jpg)
Plug and Play Cable
• High count cables
• Pre-terminated
– MPO
– LC
• Easy and efficient pull cable
Confidential Information Wirewerks 13
![Page 14: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/14.jpg)
Twisted Pair
• 4 Pair twisted pair
– Orange
– Blue
– Green
– Brown
• Rip cord
• 24 or 23 AWG bare copper
• Riser and plenum constructions
• Indoor / outdoor version
Confidential Information Wirewerks 14
![Page 15: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/15.jpg)
Cables Performances Cat5e Cat6 Cat6A
100MHz 250MHz 500MHz
Data Rate (Networks supported) 1000BASE-T 1000BASE-T 10GBASE-T
Maximum Distance 100m 100m 100m
10GBASE-T
37-55m
Confidential Information Wirewerks 15
Fast Ethernet = 100 Mbs = 100BASE-T
Gigabit Ethernet = 1,000Mbs = 1Gbs = 1000BASE-T
10 Gig Ethernet = 10,000Mbs = 10Gbs = 10GBASE-T
*Maximum distance may vary in relation to active components
Max. Distance/
Data Rate*
Single mode
OS2
Multimode
OM1
Multimode
OM2
Multimode
OM3
Multimode
OM4
Fast
Ethernet N/A 2 Km 2 Km 2 Km 2 Km
Giga
Ethernet 120 Km 275 m 550 m 550 m 1100 m
10G
Ethernet 40 Km 33 m 82 m 300 m 550 m
![Page 16: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/16.jpg)
Fire Rating
RISER - CMR/OFNR
Flammability: LOW – Burns but will self extinguish, prevent the flame from traveling up the cable in a
vertical
burn test
Toxicity: HIGH – Burning, gives off toxic gasses
Applications: Cables find inside walls, vertical shaft, runs between floors
PLENUM – CMP/OFNP
Flammability: LOW – Burns but will self extinguish, not reignite. They also produce less smoke than
traditional PVC cables
Toxicity: HIGH – Burning, gives off toxic gasses
Applications: Cables find in air plenums such as raised flooring systems and air handling ducts.
Confidential Information Wirewerks 16
Class Name Standards
CMP Communications Plenum CSA FT6 or NFPA 262(UL 910)
CMR Communications Riser UL 1666
CMG Communications General
purpose CSA FT4
CM Communications UL 1685 (UL 1581, Sec. 1160)
Vertical-Tray
![Page 17: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/17.jpg)
Fire Rating - Substitution Table
Confidential Information Wirewerks 17
Similarly, the Canadian Standard CSA C22.2 No. 214 specifies
the following substitutions:
• Communication codes marked CMP, CMR, CMG, CM, CMX,
FT6, FT4/1202 have been found to meet the standard
criteria for FT1.
• Communications codes marked CMP, CMR, CMG, or FT6
have been found to meet the standard criteria for FT4.
• Communications codes marked CMP have been found to
meet
the standard criteria for FT6
Cable A shall be permitted
to be used in place of cable B
![Page 18: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/18.jpg)
Patch Panels
• From the equipment to the patch
panel
• Where the cables are connecting
• Interface
Confidential Information Wirewerks 18
![Page 19: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/19.jpg)
Patch Cords
Confidential Information Wirewerks 19
![Page 20: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/20.jpg)
Fiber Patch Cords
Confidential Information Wirewerks 20
![Page 21: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/21.jpg)
Termination connector – RJ45
Wirewerks Confidential Information 21
RJ-45
T568-B (USA)
T568-A (Canada)
Solid Cable
![Page 22: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/22.jpg)
Termination connector – RJ45
Confidential Information Wirewerks 22
![Page 23: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/23.jpg)
How to terminate an RJ45 connection
Confidential Information Wirewerks 23
Remove jacket 1”
![Page 24: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/24.jpg)
Termination connector – Jack
IDC • T568A or T568B
• Simple tool
Confidential Information Wirewerks 24
Take off 2” of outer jacket
Follow IDC pattern to insert wires
Put all pairs in place
Cut off plastic inset
Slide module bottom-up into lower jaw until it clicks
Verify alignment Press firmly until excess wire fall off
Completed termination
![Page 25: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/25.jpg)
Media Converters • Ethernet on Coax
• Ethernet and POE on
Coax
• Ether on fiber
Confidential Information Wirewerks 25
![Page 26: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/26.jpg)
Media
Converters
Confidential Information Wirewerks 26
Cable options: Coax (ethernet),
fibre optic, power + ethernet
![Page 27: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/27.jpg)
Coax vs Structure Cable Systems
Analog video surveillance systems historically been installed with a separate
cable each for the video, control & power. Now we can combine the three
cables into one versatile UTP cable. Would you rather use 1 UTP cable or
three cables including one COAX cable – the choice is clear
Confidential Information Wirewerks 27
![Page 28: Connecting edge devices and fiber/copper cabling May … PS... · Connecting edge devices and fiber/copper cabling May 9th 2013 Confidential Information Wirewerks 1](https://reader031.vdocument.in/reader031/viewer/2022021509/5a8ccc507f8b9ac87a8d10f9/html5/thumbnails/28.jpg)
10 Good reasons why use Twisted Pair
1. Highly reduced overall cable purchase cost and installation (labor costs)
– Cat5e $87 per 1,000 ft
– RG59 $141 per 1,000ft
2. Data transfer rate (UTP results in better video quality)
– Cat5e up to 1GB per second
– Coax from 10MB to 350MB
3. Physically smaller than coax, Lighter weight cable bundles than COAX and no bend radius issues
4. Easier installation following UTP structured cabling
5. Easiest media to install and reconfigure
6. Color-coded cabling
7. Future-Proofing; Supports both Analog & IP Cameras – Prepare for the future while saving cost today
8. Easier to Add Cameras over Structured Cabling
9. Longer distances for remote cameras; over 1 Mile (1.6 Km)
10. Video, Control and Power signals on one UTP cable segment
Confidential Information Wirewerks 28