CONTENTS
Contents
A
ARTICLE90 Introduction ........................................ 70– 1
Chapter 1 General
100 Definitions ......................................... 70– 4
I. General .......................................... 70– 4II. Over 600 Volts, Nominal ..................... 70– 10
110 Requirements for Electrical Installations ..... 70– 11
I. General .......................................... 70– 11II. 600 Volts, Nominal, or Less ................. 70– 14
III. Over 600 Volts, Nominal ..................... 70– 17IV. Tunnel Installations over 600 Volts,
Nominal .......................................... 70– 20V. Manholes and Other Electric
Enclosures Intended for PersonnelEntry, All Voltages. [ROP 1–240] ........... 70– 20
Chapter 2 Wiring and Protection
200 Use and Identification of GroundedConductors .......................................... 70– 23
210 Branch Circuits ................................... 70– 25
I. General Provisions ............................ 70– 25II. Branch-Circuit Ratings ....................... 70– 29
III. Required Outlets ............................... 70– 31
215 Feeders ............................................. 70– 35
220 Branch-Circuit, Feeder, and ServiceCalculations ........................................ 70– 37
I. General .......................................... 70– 37II. Branch Circuit Load Calculations .......... 70– 38
III. Feeder and Service Load Calculations ..... 70– 40IV. Optional Feeder and Service Load
Calculations ..................................... 70– 43V. Farm Load Calculation ...................... 70– 46
225 Outside Branch Circuits and Feeders ......... 70– 47
I. General .......................................... 70– 47II. More Than One Building or Other
Structure ......................................... 70– 50III. Over 600 Volts ................................. 70– 52
230 Services ............................................ 70– 53
I. General .......................................... 70– 53II. Overhead Service-Drop Conductors ........ 70– 54
III. Underground Service-LateralConductors ...................................... 70– 56
IV. Service-Entrance Conductors ................ 70– 56V. Service Equipment — General .............. 70– 58
VI. Service Equipment — DisconnectingMeans ............................................ 70– 59
VII. Service Equipment — OvercurrentProtection ........................................ 70– 60
VIII. Services Exceeding 600 Volts, Nominal ... 70– 62
DR
2005 Edition i
RTICLE
240 Overcurrent Protection ........................... 70– 63
I. General .......................................... 70– 63II. Location ......................................... 70– 66
III. Enclosures ...................................... 70– 70IV. Disconnecting and Guarding ................ 70– 70V. Plug Fuses, Fuseholders, and Adapters .... 70– 70
VI. Cartridge Fuses and Fuseholders ........... 70– 71VII. Circuit Breakers ............................... 70– 71
VIII. Supervised Industrial Installations .......... 70– 72IX. Overcurrent Protection Over 600 Volts,
Nominal .......................................... 70– 73
250 Grounding and Bonding ......................... 70– 74
I. General .......................................... 70– 74II. System Grounding ............................ 70– 77
III. Grounding Electrode System andGrounding Electrode Conductor ............. 70– 83
IV. Enclosure, Raceway, and Service CableGrounding ....................................... 70– 87
V. Bonding ......................................... 70– 88VI. Equipment Grounding and Equipment
Grounding Conductors ........................ 70– 90VII. Methods of Equipment Grounding ......... 70– 95
VIII. Direct-Current Systems ....................... 70– 97IX. Instruments, Meters, and Relays ............ 70– 98X. Grounding of Systems and Circuits of
1 kV and Over (High Voltage) ............... 70– 99
280 Surge Arresters .................................... 70–100
I. General .......................................... 70–100II. Installation ...................................... 70–101
III. Connecting Surge Arresters .................. 70–101
285 Transient Voltage Surge Suppressors:TVSSs ............................................... 70–102
I. General .......................................... 70–102II. Installation ...................................... 70–102
III. Connecting Transient Voltage SurgeSuppressors ...................................... 70–102
Chapter 3 Wiring Methods and Materials
300 Wiring Methods ................................... 70–104
I. General Requirements ........................ 70–104II. Requirements for Over 600 Volts,
Nominal .......................................... 70–114
310 Conductors for General Wiring ................ 70–115
312 Cabinets, Cutout Boxes, and Meter SocketEnclosures .......................................... 70–141
I. Installation ...................................... 70–141II. Construction Specifications .................. 70–144
314 Outlet, Device, Pull, and Junction Boxes;Conduit Bodies; Fittings; and HandholeEnclosures [ROP 9–15, 9–16] ................... 70–145
I. Scope and General ............................ 70–145II. Installation ...................................... 70–145
AFT
NATIONAL ELECTRICAL CODE
-
CONTENTS
ARTICLE
III. Construction Specifications .................. 70–151IV. Pull and Junction Boxes for Use on
Systems Over 600 Volts, Nominal .......... 70–152
320 Armored Cable: Type AC ....................... 70–152
I. General .......................................... 70–152II. Installation ...................................... 70–153
III. Construction Specifications .................. 70–154
322 Flat Cable Assemblies: Type FC ............... 70–154
I. General .......................................... 70–154II. Installation ...................................... 70–154
III. Construction .................................... 70–154
324 Flat Conductor Cable: Type FCC .............. 70–155
I. General .......................................... 70–155II. Installation ...................................... 70–155
III. Construction .................................... 70–156
326 Integrated Gas Spacer Cable: Type IGS ...... 70–157
I. General .......................................... 70–157II. Installation ...................................... 70–157
III. Construction Specifications .................. 70–157
328 Medium Voltage Cable: Type MV ............. 70–158
I. General .......................................... 70–158II. Installation ...................................... 70–158
III. Construction Specifications .................. 70–158
330 Metal-Clad Cable: Type MC .................... 70–158
I. General .......................................... 70–158II. Installation ...................................... 70–159
III. Construction Specifications .................. 70–160
332 Mineral-Insulated, Metal-Sheathed Cable:Type MI ............................................. 70–160
I. General .......................................... 70–160II. Installation ...................................... 70–160
III. Construction Specifications .................. 70–161
334 Nonmetallic-Sheathed Cable: Types NM,NMC, and NMS ................................... 70–161
I. General .......................................... 70–161II. Installation ...................................... 70–161
III. Construction Specifications .................. 70–163
336 Power and Control Tray Cable: Type TC .... 70–163
I. General .......................................... 70–163II. Installation ...................................... 70–164
III. Construction Specifications .................. 70–164
338 Service-Entrance Cable: Types SE andUSE .................................................. 70–165
I. General .......................................... 70–165II. Installation ...................................... 70–165
III. Construction .................................... 70–165
340 Underground Feeder and Branch-CircuitCable: Type UF .................................... 70–165
I. General .......................................... 70–165II. Installation ...................................... 70–166
DRA
NATIONAL ELECTRICAL CODE ii
ARTICLE
III. Construction Specifications .................. 70–166
342 Intermediate Metal Conduit: Type IMC ...... 70–166
I. General .......................................... 70–166II. Installation ...................................... 70–166
III. Construction Specifications .................. 70–168
344 Rigid Metal Conduit: Type RMC .............. 70–168
I. General .......................................... 70–168II. Installation ...................................... 70–168
III. Construction Specifications .................. 70–169
348 Flexible Metal Conduit: Type FMC ........... 70–169
I. General .......................................... 70–169II. Installation ...................................... 70–170
350 Liquidtight Flexible Metal Conduit: TypeLFMC ............................................... 70–171
I. General .......................................... 70–171II. Installation ...................................... 70–171
III. Construction Specifications .................. 70–172
352 Rigid Nonmetallic Conduit: Type RNC ....... 70–172
I. General .......................................... 70–172II. Installation ...................................... 70–172
III. Construction Specifications .................. 70–174
353 High Density Polyethylene Conduit: TypeHDPE Conduit [ROP 8–96] ..................... 70–174
I. General .......................................... 70–174II. Installation ...................................... 70–175
III. Construction Specifications .................. 70–176
354 Nonmetallic Underground Conduit withConductors: Type NUCC ........................ 70–177
I. General .......................................... 70–177II. Installation ...................................... 70–177
III. Construction Specifications .................. 70–178
356 Liquidtight Flexible Nonmetallic Conduit:Type LFNC ......................................... 70–178
I. General .......................................... 70–178II. Installation ...................................... 70–178
III. Construction Specifications .................. 70–180
358 Electrical Metallic Tubing: Type EMT ........ 70–180
I. General .......................................... 70–180II. Installation ...................................... 70–180
III. Construction Specifications .................. 70–181
360 Flexible Metallic Tubing: Type FMT ......... 70–181
I. General .......................................... 70–181II. Installation ...................................... 70–181
III. Construction Specifications .................. 70–182
362 Electrical Nonmetallic Tubing: Type ENT ... 70–182
I. General .......................................... 70–182II. Installation ...................................... 70–183
III. Construction Specifications .................. 70–184
FT
2005 Edition
-
A
CONTENTS
ARTICLE
366 Auxiliary Gutters [ROP 8–167a] ............... 70–184
I. General .......................................... 70–184II. Installation ...................................... 70–185
III. Construction Specifications .................. 70–186
368 Busways [ROP 8–172a] ......................... 70–186
I. General Requirements ........................ 70–186II. Installation ...................................... 70–187
III. Construction .................................... 70–188IV. Requirements for Over 600 Volts,
Nominal .......................................... 70–188
370 Cablebus ........................................... 70–189
372 Cellular Concrete Floor Raceways ............ 70–190
374 Cellular Metal Floor Raceways ................ 70–191
I. Installation ...................................... 70–191II. Construction Specifications .................. 70–192
376 Metal Wireways ................................... 70–192
I. General .......................................... 70–192II. Installation ...................................... 70–192
III. Construction Specifications .................. 70–193
378 Nonmetallic Wireways ........................... 70–193
I. General .......................................... 70–193II. Installation ...................................... 70–193
III. Construction Specifications .................. 70–194
380 Multioutlet Assembly ............................ 70–194
382 Nonmetallic Extensions .......................... 70–195
I. General .......................................... 70–195II. Installation ...................................... 70–195
384 Strut-Type Channel Raceway ................... 70–196
I. General .......................................... 70–196II. Installation ...................................... 70–196
III. Construction Specifications .................. 70–197
386 Surface Metal Raceways ........................ 70–197
I. General .......................................... 70–197II. Installation ...................................... 70–197
III. Construction Specifications .................. 70–198
388 Surface Nonmetallic Raceways ................. 70–198
I. General .......................................... 70–198II. Installation ...................................... 70–198
III. Construction Specifications .................. 70–199
390 Underfloor Raceways ............................ 70–199
392 Cable Trays ........................................ 70–200
394 Concealed Knob-and-Tube Wiring ............. 70–207
I. General .......................................... 70–207II. Installation ...................................... 70–207
III. Construction Specifications .................. 70–208
396 Messenger Supported Wiring ................... 70–208
I. General .......................................... 70–208II. Installation ...................................... 70–208
DR
2005 Edition iii
RTICLE
398 Open Wiring on Insulators ...................... 70–209
I. General .......................................... 70–209II. Installation ...................................... 70–209
III. Construction Specifications .................. 70–210
Chapter 4 Equipment for General Use
400 Flexible Cords and Cables ...................... 70–211
I. General .......................................... 70–211II. Construction Specifications .................. 70–223
III. Portable Cables Over 600 Volts,Nominal .......................................... 70–224
402 Fixture Wires ...................................... 70–224
404 Switches ............................................ 70–229
I. Installation ...................................... 70–229II. Construction Specifications .................. 70–232
406 Receptacles, Cord Connectors, andAttachment Plugs (Caps) ......................... 70–232
408 Switchboards and Panelboards ................. 70–235
I. General .......................................... 70–235II. Switchboards ................................... 70–236
III. Panelboards ..................................... 70–236IV. Construction Specifications .................. 70–238
410 Luminaires (Lighting Fixtures),Lampholders, and Lamps ........................ 70–239
I. General .......................................... 70–239II. Luminaire (Fixture) Locations .............. 70–239
III. Provisions at Luminaire (Fixture)Outlet Boxes, Canopies, and Pans ........... 70–240
IV. Luminaire (Fixture) Supports ................ 70–241V. Grounding ...................................... 70–242
VI. Wiring of Luminaires (Fixtures) ............ 70–242VII. Construction of Luminaires (Fixtures) ..... 70–244
VIII. Installation of Lampholders .................. 70–245IX. Construction of Lampholders ................ 70–245X. Lamps and Auxiliary Equipment ........... 70–245
XI. Special Provisions for Flush andRecessed Luminaires (Fixtures) .............. 70–245
XII. Construction of Flush and RecessedLuminaires (Fixtures) .......................... 70–246
XIII. Special Provisions forElectric-Discharge Lighting Systems of1000 Volts or Less ............................. 70–246
XIV. Special Provisions forElectric-Discharge Lighting Systems ofMore Than 1000 Volts ......................... 70–247
XV. Lighting Track ................................. 70–248
411 Lighting Systems Operating at 30 Volts orLess .................................................. 70–249
422 Appliances ......................................... 70–249
I. General .......................................... 70–249II. Installation ...................................... 70–250
III. Disconnecting Means ......................... 70–252IV. Construction .................................... 70–253V. Marking ......................................... 70–254
AFT
NATIONAL ELECTRICAL CODE
-
CONTENTS
ARTICLE
424 Fixed Electric Space-Heating Equipment ..... 70–254
I. General .......................................... 70–254II. Installation ...................................... 70–255
III. Control and Protection of FixedElectric Space-Heating Equipment .......... 70–255
IV. Marking of Heating Equipment ............. 70–257V. Electric Space-Heating Cables .............. 70–257
VI. Duct Heaters ................................... 70–259VII. Resistance-Type Boilers ...................... 70–260
VIII. Electrode-Type Boilers ....................... 70–261IX. Electric Radiant Heating Panels and
Heating Panel Sets ............................. 70–261
426 Fixed Outdoor Electric Deicing andSnow-Melting Equipment ........................ 70–263
I. General .......................................... 70–263II. Installation ...................................... 70–264
III. Resistance Heating Elements ................ 70–264IV. Impedance Heating ............................ 70–265V. Skin-Effect Heating ........................... 70–266
VI. Control and Protection ........................ 70–266
427 Fixed Electric Heating Equipment forPipelines and Vessels ............................. 70–267
I. General .......................................... 70–267II. Installation ...................................... 70–267
III. Resistance Heating Elements ................ 70–267IV. Impedance Heating ............................ 70–268V. Induction Heating ............................. 70–269
VI. Skin-Effect Heating ........................... 70–269VII. Control and Protection ........................ 70–269
430 Motors, Motor Circuits, and Controllers ...... 70–270
I. General .......................................... 70–270II. Motor Circuit Conductors .................... 70–276
III. Motor and Branch-Circuit OverloadProtection ........................................ 70–278
IV. Motor Branch-Circuit Short-Circuit andGround-Fault Protection ....................... 70–281
V. Motor Feeder Short-Circuit andGround-Fault Protection ....................... 70–285
VI. Motor Control Circuits ....................... 70–285VII. Motor Controllers ............................. 70–287
VIII. Motor Control Centers ........................ 70–290IX. Disconnecting Means ......................... 70–291X. Adjustable-Speed Drive Systems [ROP
11–6] ............................................. 70–294XI. Over 600 Volts, Nominal ..................... 70–295
XII. Protection of Live Parts — AllVoltages .......................................... 70–296
XIII. Grounding — All Voltages ................... 70–296XIV. Tables ............................................ 70–298
440 Air-Conditioning and RefrigeratingEquipment .......................................... 70–301
I. General .......................................... 70–301II. Disconnecting Means ......................... 70–303
III. Branch-Circuit Short-Circuit andGround-Fault Protection ....................... 70–304
IV. Branch-Circuit Conductors ................... 70–305V. Controllers for Motor-Compressors ........ 70–305
VI. Motor-Compressor and Branch-CircuitOverload Protection ............................ 70–306
DRA
NATIONAL ELECTRICAL CODE iv
ARTICLE
VII. Provisions for Room Air Conditioners ..... 70–307
445 Generators ......................................... 70–308
450 Transformers and Transformer Vaults(Including Secondary Ties) ...................... 70–309
I. General Provisions ............................ 70–309II. Specific Provisions Applicable to
Different Types of Transformers ............. 70–314III. Transformer Vaults ............................ 70–315
455 Phase Converters ................................. 70–316
I. General .......................................... 70–316II. Specific Provisions Applicable to
Different Types of Phase Converters ........ 70–318
460 Capacitors .......................................... 70–318
I. 600 Volts, Nominal, and Under ............. 70–318II. Over 600 Volts, Nominal ..................... 70–319
470 Resistors and Reactors....................................................... 70–320
I. 600 Volts, Nominal, and Under ............. 70–320II. Over 600 Volts, Nominal ..................... 70–320
480 Storage Batteries .................................. 70–320
490 Equipment, Over 600 Volts, Nominal ......... 70–322
I. General .......................................... 70–322II. Equipment — Specific Provisions .......... 70–322
III. Equipment — Metal-Enclosed PowerSwitchgear and Industrial ControlAssemblies ...................................... 70–324
IV. Mobile and Portable Equipment ............ 70–326V. Electrode-Type Boilers ....................... 70–327
Chapter 5 Special Occupancies
500 Hazardous (Classified) Locations, ClassesI, II, and III, Divisions 1 and 2 ................. 70–328
501 Class I Locations [ROP 14–19a] ............... 70–336
I. General .......................................... 70–336II. Wiring ........................................... 70–336
III. Equipment ...................................... 70–342
502 Class II Locations [ROP 14–51a] .............. 70–346
I. General .......................................... 70–346II. Wiring ........................................... 70–346
III. Equipment ...................................... 70–348
503 Class III Locations [ROP 14–60a] ............. 70–352
I. General .......................................... 70–352II. Wiring ........................................... 70–352
III. Equipment ...................................... 70–353
504 Intrinsically Safe Systems ....................... 70–355
505 Class I, Zone 0, 1, and 2 Locations ........... 70–358
506 Zone 20, 21, and 22 Locations forFlammable Dusts, Fibers, and Flyings ......... 70–371
510 Hazardous (Classified) Locations —Specific .............................................. 70–377
FT
2005 Edition
-
A
CONTENTS
ARTICLE
511 Commercial Garages, Repair and Storage .... 70–377
513 Aircraft Hangars .................................. 70–380
514 Motor Fuel Dispensing Facilities .............. 70–383
515 Bulk Storage Plants .............................. 70–387
516 Spray Application, Dipping, and CoatingProcesses ............................................ 70–391
517 Health Care Facilities ............................ 70–397
I. General .......................................... 70–397II. Wiring and Protection ........................ 70–399
III. Essential Electrical System .................. 70–403IV. Inhalation Anesthetizing Locations ......... 70–410V. X-Ray Installations ............................ 70–412
VI. Communications, Signaling Systems,Data Systems, Fire Alarm Systems, andSystems Less Than 120 Volts, Nominal .... 70–414
VII. Isolated Power Systems ...................... 70–414
518 Assembly Occupancies [ROP 15–57] ......... 70–415
520 Theaters, Audience Areas of MotionPicture and Television Studios,Performance Areas, and Similar Locations ... 70–417
I. General .......................................... 70–417II. Fixed Stage Switchboards .................... 70–418
III. Fixed Stage Equipment Other ThanSwitchboards .................................... 70–419
IV. Portable Switchboards on Stage ............ 70–420V. Portable Stage Equipment Other Than
Switchboards .................................... 70–423VI. Dressing Rooms ............................... 70–425
VII. Grounding ...................................... 70–425
525 Carnivals, Circuses, Fairs, and SimilarEvents ............................................... 70–425
I. General Requirements ........................ 70–425II. Power Sources ................................. 70–425
III. Wiring Methods ................................ 70–426IV. Grounding and Bonding ...................... 70–427
530 Motion Picture and Television Studiosand Similar Locations ............................ 70–427
I. General .......................................... 70–427II. Stage or Set .................................... 70–428
III. Dressing Rooms ............................... 70–430IV. Viewing, Cutting, and Patching Tables .... 70–430V. Cellulose Nitrate Film Storage Vaults ..... 70–430
VI. Substations ...................................... 70–430
540 Motion Picture Projection Rooms ............. 70–431
I. General .......................................... 70–431II. Equipment and Projectors of the
Professional Type .............................. 70–431III. Nonprofessional Projectors .................. 70–432IV. Audio Signal Processing, Amplification,
and Reproduction Equipment ................ 70–432
545 Manufactured Buildings ......................... 70–432
547 Agricultural Buildings ........................... 70–433
DR
2005 Edition v
RTICLE
550 Mobile Homes, Manufactured Homes, andMobile Home Parks ............................... 70–436
I. General .......................................... 70–436II. Mobile and Manufactured Homes .......... 70–437
III. Services and Feeders .......................... 70–444
551 Recreational Vehicles and RecreationalVehicle Parks ....................................... 70–446
I. General .......................................... 70–446III. Combination Electrical Systems ............ 70–447IV. Other Power Sources ......................... 70–448V. Nominal 120-Volt or 120/240-Volt
Systems .......................................... 70–449VI. Factory Tests ................................... 70–455
VII. Recreational Vehicle Parks ................... 70–455
552 Park Trailers ....................................... 70–458
I. General .......................................... 70–458II. Low-Voltage Systems ......................... 70–458
III. Combination Electrical Systems ............ 70–459IV. Nominal 120-Volt or 120/240-Volt
Systems .......................................... 70–460V. Factory Tests ................................... 70–467
553 Floating Buildings ................................ 70–467
I. General .......................................... 70–467II. Services and Feeders .......................... 70–467
III. Grounding ...................................... 70–468
555 Marinas and Boatyards .......................... 70–468
590 Temporary Installations [TCC 3–108] ........ 70–471
Chapter 6 Special Equipment
600 Electric Signs and Outline Lighting ........... 70–474
I. General .......................................... 70–474II. Field-Installed Skeleton Tubing ............. 70–477
604 Manufactured Wiring Systems ................. 70–478
605 Office Furnishings (Consisting of LightingAccessories and Wired Partitions) .............. 70–479
610 Cranes and Hoists ................................ 70–480
I. General .......................................... 70–480II. Wiring ........................................... 70–481
III. Contact Conductors ........................... 70–483IV. Disconnecting Means ......................... 70–484V. Overcurrent Protection ........................ 70–484
VI. Control .......................................... 70–485VII. Grounding ...................................... 70–486
620 Elevators, Dumbwaiters, Escalators,Moving Walks, Wheelchair Lifts, andStairway Chair Lifts .............................. 70–486
I. General .......................................... 70–486II. Conductors ...................................... 70–488
III. Wiring ........................................... 70–489IV. Installation of Conductors .................... 70–491V. Traveling Cables ............................... 70–492
VI. Disconnecting Means and Control .......... 70–493VII. Overcurrent Protection ........................ 70–494
AFT
NATIONAL ELECTRICAL CODE
-
CONTENTS
ARTICLE
VIII. Machine Rooms, Control Rooms,Machinery Spaces, and Control Spaces .... 70–495
IX. Grounding ...................................... 70–495X. Emergency and Standby Power
Systems .......................................... 70–495
625 Electric Vehicle Charging System ............. 70–496
I. General .......................................... 70–496II. Wiring Methods ................................ 70–496
III. Equipment Construction ...................... 70–497IV. Control and Protection ........................ 70–497V. Electric Vehicle Supply Equipment
Locations ........................................ 70–498
630 Electric Welders ................................... 70–499
I. General .......................................... 70–499II. Arc Welders .................................... 70–500
III. Resistance Welders ............................ 70–501IV. Welding Cable ................................. 70–502
640 Audio Signal Processing, Amplification,and Reproduction Equipment .................... 70–502
I. General .......................................... 70–502II. Permanent Audio System Installations ..... 70–505
III. Portable and Temporary Audio SystemInstallations ...................................... 70–506
645 Information Technology Equipment ........... 70–507
647 Sensitive Electronic Equipment ................ 70–509
650 Pipe Organs ........................................ 70–510
660 X-Ray Equipment ................................ 70–511
I. General .......................................... 70–511II. Control .......................................... 70–512
III. Transformers and Capacitors ................ 70–512IV. Guarding and Grounding ..................... 70–512
665 Induction and Dielectric HeatingEquipment .......................................... 70–513
I. General .......................................... 70–513II. Guarding, Grounding, and Labeling ........ 70–514
668 Electrolytic Cells ................................. 70–514
669 Electroplating ...................................... 70–517
670 Industrial Machinery ............................. 70–518
675 Electrically Driven or ControlledIrrigation Machines ............................... 70–519
I. General .......................................... 70–519II. Center Pivot Irrigation Machines ........... 70–521
680 Swimming Pools, Fountains, and SimilarInstallations ......................................... 70–521
I. General .......................................... 70–521II. Permanently Installed Pools ................. 70–524
III. Storable Pools .................................. 70–531IV. Spas and Hot Tubs ............................ 70–532V. Fountains ........................................ 70–534
VI. Pools and Tubs for Therapeutic Use ....... 70–535VII. Hydromassage Bathtubs ...................... 70–536
DRA
NATIONAL ELECTRICAL CODE vi
ARTICLE
682 Natural and Artificially Made Bodies ofWater [ROP 17–154] .............................. 70–537
I. General .......................................... 70–537II. Installation ...................................... 70–537
III. Grounding and Bonding ...................... 70–538
685 Integrated Electrical Systems ................... 70–538
I. General .......................................... 70–538II. Orderly Shutdown ............................. 70–538
690 Solar Photovoltaic Systems ..................... 70–539
I. General .......................................... 70–539II. Circuit Requirements ......................... 70–541
III. Disconnecting Means ......................... 70–543IV. Wiring Methods ................................ 70–545V. Grounding ...................................... 70–546
VI. Marking ......................................... 70–546VII. Connection to Other Sources ................ 70–547
VIII. Storage Batteries ............................... 70–548IX. Systems Over 600 Volts ...................... 70–549
692 Fuel Cell Systems ................................ 70–549
I. General .......................................... 70–549II. Circuit Requirements ......................... 70–550
III. Disconnecting Means ......................... 70–550IV. Wiring Methods ................................ 70–551V. Grounding ...................................... 70–551
VI. Marking ......................................... 70–551VII. Connection to Other Circuits ................ 70–551
VIII. Outputs Over 600 Volts ...................... 70–552
695 Fire Pumps ......................................... 70–552
Chapter 7 Special Conditions
700 Emergency Systems .............................. 70–557
I. General .......................................... 70–557II. Circuit Wiring .................................. 70–558
III. Sources of Power .............................. 70–559IV. Emergency System Circuits for
Lighting and Power ............................ 70–560V. Control — Emergency Lighting
Circuits ........................................... 70–561VI. Overcurrent Protection ........................ 70–561
701 Legally Required Standby Systems ............ 70–561
I. General .......................................... 70–561II. Circuit Wiring .................................. 70–563
III. Sources of Power .............................. 70–563IV. Overcurrent Protection ........................ 70–564
702 Optional Standby Systems ...................... 70–564
I. General .......................................... 70–564II. Circuit Wiring .................................. 70–565
III. Grounding ...................................... 70–565IV. Sources of Power [ROP 13–155] ........... 70–565
705 Interconnected Electric Power ProductionSources .............................................. 70–566
720 Circuits and Equipment Operating at LessThan 50 Volts ...................................... 70–567
FT
2005 Edition
-
A
T
1
1
1
CONTENTS
ARTICLE
725 Class 1, Class 2, and Class 3Remote-Control, Signaling, andPower-Limited Circuits [ROP 3–126] .......... 70–568
I. General .......................................... 70–568II. Class 1 Circuits ................................ 70–569
III. Class 2 and Class 3 Circuits ................. 70–571VI. Listing Requirements ......................... 70–576
727 Instrumentation Tray Cable: Type ITC ........ 70–577
760 Fire Alarm Systems [ROP 3–223] ............. 70–578
I. General .......................................... 70–578II. Non–Power-Limited Fire Alarm
(NPLFA) Circuits .............................. 70–579III. Power-Limited Fire Alarm (PLFA)
Circuits ........................................... 70–582
770 Optical Fiber Cables and Raceways [ROP16–5] ................................................ 70–587
I. General .......................................... 70–587II. Protection ....................................... 70–588
III. Cables Within Buildings ...... .................... {ROP 16-24]... 70–589VI. Listing Requirements ......................... 70–591
780 Closed-Loop and Programmed PowerDistribution ......................................... 70–592
Chapter 8 Communications Systems
800 Communications Circuits ........................ 70–594
I. General .......................................... 70–594II. Wires and Cables Outside and Entering
Buildings [ROP 16–84] ....................... 70–595III. Protection ....................................... 70–596IV. Grounding Methods ........................... 70–597V. Wires and Cables Within Buildings
[ROP 16–100] ................................... 70–598VI. Listing Requirements ......................... 70–601
810 Radio and Television Equipment ............... 70–603
I. General .......................................... 70–603II. Receiving Equipment — Antenna
Systems .......................................... 70–603III. Amateur Transmitting and Receiving
Stations — Antenna Systems ................. 70–606IV. Interior Installation — Transmitting
Stations ........................................... 70–606
820 Community Antenna Television and RadioDistribution Systems .............................. 70–607
I. General .......................................... 70–607II. Cables Outside and Entering Buildings .... 70–608
III. Protection ....................................... 70–609IV. Grounding Methods ........................... 70–609V. Cables Within Buildings ..................... 70–610
DR
VI. Listing Requirements ......................... 70–612
2005 Edition vii
RTICLE
830 Network-Powered BroadbandCommunications Systems ........................ 70–614
I. General .......................................... 70–614II. Cables Outside and Entering Buildings .... 70–615
III. Protection ....................................... 70–618IV. Grounding Methods ........................... 70–619V. Cables Within Buildings ..................... 70–620
VI. Listing Requirements ......................... 70–622ABLES
Chapter 9 Tables
1 Percent of Cross Section of Conduit andTubing for Conductors ........................... 70–624
2 Radius of Conduit and Tubing Bends[ROP 8–24a] ....................................... 70–624
4 Dimensions and Percent Area of Conduitand Tubing(Areas of Conduit or Tubing for theCombinations of Wires Permitted in Table1, Chapter 9) [ROP 8–294] ...................... 70–625
5 Dimensions of Insulated Conductors andFixture Wires ....................................... 70–629
5A Compact Aluminum Building WireNominal Dimensions* and Areas [ROP6–108, 6–109] ...................................... 70–634
8 Conductor Properties [ROP 6–111] ........... 70–634
9 Alternating-Current Resistance andReactance for 600-Volt Cables, 3-Phase,60 Hz, 75°C (167°F) — Three SingleConductors in Conduit ............................ 70–635
1(A) Class 2 and Class 3 Alternating-CurrentPower Source Limitations ........................ 70–637
11(B) Class 2 and Class 3 Direct-Current PowerSource Limitations ................................ 70–637
2(A) PLFA Alternating-Current Power SourceLimitations .......................................... 70–638
2(B) PLFA Direct-Current Power SourceLimitations [ROP 3–301] ........................ 70–638
Annex A ............................................ 70–640
Annex B ............................................ 70–643
Annex C ............................................ 70–657
Annex D ............................................ 70–679
Annex E ............................................. 70–691
Annex F ............................................. 70–693
Annex G ............................................ 70–696
AFT
NATIONAL ELECTRICAL CODE
-
ARTICLE 90Introduction
90.1 Purpose.
(A) Practical Safeguarding. The purpose of this Code isthe practical safeguarding of persons and property fromhazards arising from the use of electricity.
(B) Adequacy. This Code contains provisions that are con-sidered necessary for safety. Compliance therewith andproper maintenance will result in an installation that is es-sentially free from hazard but not necessarily efficient, con-venient, or adequate for good service or future expansion ofelectrical use.
FPN: Hazards often occur because of overloading of wir-ing systems by methods or usage not in conformity withthis Code. This occurs because initial wiring did not pro-vide for increases in the use of electricity. An initial ad-equate installation and reasonable provisions for systemchanges will provide for future increases in the use ofelectricity.
(C) Intention. This Code is not intended as a design speci-fication or an instruction manual for untrained persons.
(D) Relation to Other International Standards. The re-quirements in this Code address the fundamental principlesof protection for safety contained in Section 131 of Inter-national Electrotechnical Commission Standard 60364-1,Electrical Installations of Buildings. [ROP 1–16a]
FPN: IEC 60364-1, Section 131, contains fundamentalprinciples of protection for safety that encompass protec-tion against electric shock, protection against thermal ef-fects, protection against overcurrent, protection againstfault currents, and protection against overvoltage. All ofthese potential hazards are addressed by the requirements inthis Code.
90.2 Scope.
(A) Covered. This Code covers the installation of electricconductors, cables, equipment, and raceways; signaling andcommunications conductors, cables, equipment, and race-ways; and optical fiber cables and raceways for the follow-ing: [ROP 1–18]
(1) Public and private premises, including buildings, struc-tures, mobile homes, recreational vehicles, and floatingbuildings
(2) Yards, lots, parking lots, carnivals, and industrial sub-stations
FPN: For additional information concerning such installa-tions in an industrial or multibuilding complex, see theANSI C2-2002, National Electrical Safety Code. [ROP1–22a]
(3) Installations of conductors and equipment that connectto the supply of electricity
(4) Installations used by the electric utility, such as officebuildings, warehouses, garages, machine shops, andrecreational buildings, which are not an integral part ofa generating plant, substation, or control center. [ROP1–23]
(B) Not Covered. This Code does not cover the following:
(1) Installations in ships, watercraft other than floatingbuildings, railway rolling stock, aircraft, or automotivevehicles other than mobile homes and recreational ve-hicles
FPN: Although the scope of this Code indicates that theCode does not cover installations in ships, portions of thisCode are incorporated by reference into Title 46, Code ofFederal Regulations, Parts 110–113.
(2) Installations underground in mines and self-propelledmobile surface mining machinery and its attendantelectrical trailing cable [ROP 1–28]
(3) Installations of railways for generation, transformation,transmission, or distribution of power used exclusivelyfor operation of rolling stock or installations used ex-clusively for signaling and communications purposes
(4) Installations of communications equipment under theexclusive control of communications utilities locatedoutdoors or in building spaces used exclusively forsuch installations
(5) Installations under the exclusive control of an electricutility where such installations
a. Consist of service drops or service laterals, and as-sociated metering, or
b. Are located in legally established easements, rights-of-way, or by other agreements either designated byor recognized by public service commissions, utilitycommissions, or other regulatory agencies havingjurisdiction for such installations, or
c. Are on property owned or leased by the electricutility for the purpose of communications, metering,generation, control, transformation, transmission, ordistribution of electric energy.
FPN to (4) and (5): Utilities are organizations, typicallydesignated or recognized by governmental law or regula-tion by public service/utility commissions, that install, op-erate, and maintain electric supply (such as generation,transmission, or distribution systems) or communicationsystems (such as telephone, CATV, Internet, satellite, or
NFPA 70
National Electrical Code®
2005 Edition
70-1ARTICLE 90 INTRODUCTION
2005 EditionNATIONAL ELECTRICAL CODE
DRAF
T
-
data services). As such, the utility is subject to compliancewith codes and standards covering these activities relevantto their industry as adopted under governmental law orregulation. Refer to the appropriate governmental bodies,such as state regulatory commissions, Federal EnergyRegulatory Commission, and Federal CommunicationsCommission. [ROP 1–25]
(C) Special Permission. The authority having jurisdictionfor enforcing this Code may grant exception for the instal-lation of conductors and equipment that are not under theexclusive control of the electric utilities and are used toconnect the electric utility supply system to the service-entrance conductors of the premises served, provided suchinstallations are outside a building or terminate immedi-ately inside a building wall.
90.3 Code Arrangement. This Code is divided into theintroduction and nine chapters, as shown in Figure 90.3.Chapters 1, 2, 3, and 4 apply generally; Chapters 5, 6, and7 apply to special occupancies, special equipment, or otherspecial conditions. These latter chapters supplement ormodify the general rules. Chapters 1 through 4 apply exceptas amended by Chapters 5, 6, and 7 for the particular con-ditions.
Chapter 8 covers communications systems and is notsubject to the requirements of Chapters 1 through 7 exceptwhere the requirements are specifically referenced in Chap-ter 8.
Chapter 9 consists of tables.Annexes are not part of the requirements of this Code
but are included for informational purposes only.
90.4 Enforcement. This Code is intended to be suitablefor mandatory application by governmental bodies that ex-ercise legal jurisdiction over electrical installations, includ-ing signaling and communications systems, and for use byinsurance inspectors. The authority having jurisdiction forenforcement of the Code has the responsibility for makinginterpretations of the rules, for deciding on the approval ofequipment and materials, and for granting the special per-mission contemplated in a number of the rules.
By special permission, the authority having jurisdictionmay waive specific requirements in this Code or permitalternative methods where it is assured that equivalent ob-jectives can be achieved by establishing and maintainingeffective safety.
This Code may require new products, constructions, ormaterials that may not yet be available at the time the Codeis adopted. In such event, the authority having jurisdictionmay permit the use of the products, constructions, or mate-rials that comply with the most recent previous edition ofthis Code adopted by the jurisdiction.
90.5 Mandatory Rules, Permissive Rules, and Explana-tory Material.
(A) Mandatory Rules. Mandatory rules of this Code arethose that identify actions that are specifically required orprohibited and are characterized by the use of the termsshall or shall not.
(B) Permissive Rules. Permissive rules of this Code arethose that identify actions that are allowed but not required,are normally used to describe options or alternative meth-ods, and are characterized by the use of the terms shall bepermitted or shall not be required.
(C) Explanatory Material. Explanatory material, such asreferences to other standards, references to related sectionsof this Code, or information related to a Code rule, is in-cluded in this Code in the form of fine print notes (FPNs).Fine print notes are informational only and are not enforce-able as requirements of this Code.
Brackets containing section references to another NFPAdocument are for informational purposes only and are pro-vided as a guide to indicate the source of the extracted text.These bracketed references immediately follow the ex-tracted text. [ROP 1–34]
FPN: The format and language used in this Code followsguidelines established by NFPA and published in the NECStyle Manual. Copies of this manual can be obtained fromNFPA.
90.6 Formal Interpretations. To promote uniformity ofinterpretation and application of the provisions of thisCode, formal interpretation procedures have been estab-
Chapter 1 — General
Chapter 2 — Wiring and Protection
Chapter 3 — Wiring Methods and Materials
Chapter 4 — Equipment for General Use
Applies generallyto all electrical
installations
Chapter 5 — Special Occupancies
Chapter 6 — Special Equipment
Chapter 7 — Special Conditions
Supplements or modifiesChapters 1 through 4
Chapter 9 — Tables
Annex A through Annex G
Chapter 8 — Communications Systems
Informational only; not mandatory
Applicable as referenced
Chapter 8 is not subject to the requirements of Chapters 1 through 7 except where the requirements are specifically referenced in Chapter 8.
Figure 90.3 Code arrangement.
70-2 ARTICLE 90 INTRODUCTION
2005 Edition NATIONAL ELECTRICAL CODE
DRAF
T
-
lished and are found in the NFPA Regulations GoverningCommittee Projects.
90.7 Examination of Equipment for Safety. For specificitems of equipment and materials referred to in this Code,examinations for safety made under standard conditionsprovide a basis for approval where the record is made gen-erally available through promulgation by organizationsproperly equipped and qualified for experimental testing,inspections of the run of goods at factories, and service-value determination through field inspections. This avoidsthe necessity for repetition of examinations by differentexaminers, frequently with inadequate facilities for suchwork, and the confusion that would result from conflictingreports on the suitability of devices and materials examinedfor a given purpose.
It is the intent of this Code that factory-installed inter-nal wiring or the construction of equipment need not beinspected at the time of installation of the equipment, ex-cept to detect alterations or damage, if the equipment hasbeen listed by a qualified electrical testing laboratory that isrecognized as having the facilities described in the preced-ing paragraph and that requires suitability for installation inaccordance with this Code.
FPN No. 1: See requirements in 110.3.
FPN No. 2: Listed is defined in Article 100.
FPN No. 3: Annex A contains an informative list of prod-uct safety standards for electrical equipment.
90.8 Wire and Cable Planning.
(A) Future Expansion and Convenience. Plans andspecifications that provide ample space in raceways, spareraceways, and additional spaces allow for future increasesin electric power and communication circuits. Distributioncenters located in readily accessible locations provide con-venience and safety of operation. [ROP 1–35]
(B) Number of Circuits in Enclosures. It is elsewhereprovided in this Code that the number of wires and circuitsconfined in a single enclosure be varyingly restricted. Lim-iting the number of circuits in a single enclosure minimizesthe effects from a short circuit or ground fault in one cir-cuit.
90.9 Units of Measurement.
(A) Measurement System of Preference. For the purposeof this Code, metric units of measurement are in accor-
dance with the modernized metric system known as theInternational System of Units (SI).
(B) Dual System of Units. The SI units shall appear first,and the inch-pound units shall immediately follow in pa-rentheses. The conversion from the inch-pound units to SIunits shall be based on hard conversion except as providedin 90.9(C).
(C) Permitted Uses of Soft Conversion. The cases givenin 90.9(C)(1) through (4) shall not be required to use hardconversion and shall be permitted to use soft conversion.
(1) Trade Sizes. Where the actual measured size of a prod-uct is not the same as the nominal size, trade size designa-tors shall be used rather than dimensions. Trade practicesshall be followed in all cases.
(2) Extracted Material. Where material is extracted fromanother standard, the context of the original material shallnot be compromised or violated. Any editing of the ex-tracted text shall be confined to making the style consistentwith that of the NEC.
(3) Industry Practice. Where industry practice is to ex-press units in inch-pound units, the inclusion of SI unitsshall not be required.
(4) Safety. Where a negative impact on safety would re-sult, soft conversion shall be used. [ROP 1–45]
(D) Compliance. The conversion from inch-pound units toSI units shall be permitted to be an approximate conver-sion. Compliance with the numbers shown in either the SIsystem or the inch-pound system shall constitute compli-ance with this Code.
FPN No. 1: Hard conversion is considered a change indimensions or properties of an item into new sizes thatmight or might not be interchangeable with the sizes usedin the original measurement. Soft conversion is considereda direct mathematical conversion and involves a change inthe description of an existing measurement but not in theactual dimension.
FPN No. 2: SI conversions are based on IEEE/ASTM SI10-1997, Standard for the Use of the International Systemof Units (SI): The Modern Metric System.
70-3ARTICLE 90 INTRODUCTION
2005 EditionNATIONAL ELECTRICAL CODE
DRAF
T
-
Chapter 1 General
ARTICLE 100Definitions
Scope. This article contains only those definitions essentialto the proper application of this Code. It is not intended toinclude commonly defined general terms or commonly de-fined technical terms from related codes and standards. Ingeneral, only those terms that are used in two or morearticles are defined in Article 100. Other definitions areincluded in the article in which they are used but may bereferenced in Article 100.
Part I of this article contains definitions intended toapply wherever the terms are used throughout this Code.Part II contains definitions applicable only to the parts ofarticles specifically covering installations and equipmentoperating at over 600 volts, nominal.
I. General
Abandoned Cables. Cable that is neither terminated atboth ends nor identified for future use with a tag. [ROP1–46]
Accessible (as applied to equipment). Admitting closeapproach; not guarded by locked doors, elevation, or othereffective means.
Accessible (as applied to wiring methods). Capable ofbeing removed or exposed without damaging the buildingstructure or finish or not permanently closed in by the struc-ture or finish of the building.
Accessible, Readily (Readily Accessible). Capable of be-ing reached quickly for operation, renewal, or inspectionswithout requiring those to whom ready access is requisiteto climb over or remove obstacles or to resort to portableladders, and so forth.
Air Duct. A conduit for or passageway for conveying air toor from heating, cooling, air conditioning, or ventilatingequipment, but not including the plenum. [ROP 1–49]
Ampacity. The current, in amperes, that a conductor cancarry continuously under the conditions of use without ex-ceeding its temperature rating.
Appliance. Utilization equipment, generally other than in-dustrial, that is normally built in standardized sizes or typesand is installed or connected as a unit to perform one ormore functions such as clothes washing, air conditioning,food mixing, deep frying, and so forth.
Approved. Acceptable to the authority having jurisdiction.[TCC 1–54]
Askarel. A generic term for a group of nonflammable syn-thetic chlorinated hydrocarbons used as electrical insulatingmedia. Askarels of various compositional types are used.Under arcing conditions, the gases produced, while consist-ing predominantly of noncombustible hydrogen chloride,can include varying amounts of combustible gases, depend-ing on the askarel type.
Attachment Plug (Plug Cap) (Plug). A device that, byinsertion in a receptacle, establishes a connection betweenthe conductors of the attached flexible cord and the conduc-tors connected permanently to the receptacle.
Authority Having Jurisdiction (AHJ). The organization,office, or individual responsible for approving equipment,materials, an installation, or a procedure. [ROP 1–57]
FPN: The phrase “authority having jurisdiction” is used inNFPA documents in a broad manner, since jurisdictions andapproval agencies vary, as do their responsibilities. Wherepublic safety is primary, the AHJ may be a federal, state,local, or other regional department or individual such as afire chief; fire marshal; chief of a fire prevention bureau,labor department, or health department; building official;electrical inspector; or others having statutory authority.For insurance purposes, an insurance inspection depart-ment, rating bureau, or other insurance company represen-tative may be the AHJ. In many circumstances, the propertyowner or his or her designated agent assumes the role of theAHJ; at government installations, the commanding officeror departmental official may be the AHJ. [ROP 1–57]
Automatic. Self-acting, operating by its own mechanismwhen actuated by some impersonal influence, as, for ex-ample, a change in current, pressure, temperature, or me-chanical configuration.
Bathroom. An area including a basin with one or more ofthe following: a toilet, a tub, or a shower.
Bonding (Bonded). The permanent joining of metallicparts to form an electrically conductive path that ensureselectrical continuity and the capacity to conduct safely anycurrent likely to be imposed.
Bonding Jumper. A reliable conductor to ensure the re-quired electrical conductivity between metal parts requiredto be electrically connected.
Bonding Jumper, Equipment. The connection betweentwo or more portions of the equipment grounding conduc-tor.
Bonding Jumper, Main. The connection between thegrounded circuit conductor and the equipment groundingconductor at the service.
70-4 ARTICLE 100 DEFINITIONS
2005 Edition NATIONAL ELECTRICAL CODE
DRAF
T
-
Bonding Jumper, System. The connection between thegrounded circuit conductor and the equipment groundingconductor at a separately derived system. [ROP 1–63, TCC1–63]
Branch Circuit. The circuit conductors between the finalovercurrent device protecting the circuit and the outlet(s).
Branch Circuit, Appliance. A branch circuit that suppliesenergy to one or more outlets to which appliances are to beconnected and that has no permanently connected lumi-naires (lighting fixtures) that are not a part of an appliance.
Branch Circuit, General-Purpose. A branch circuit thatsupplies two or more receptacles or outlets for lighting andappliances.
Branch Circuit, Individual. A branch circuit that suppliesonly one utilization equipment.
Branch Circuit, Multiwire. A branch circuit that consistsof two or more ungrounded conductors that have a voltagebetween them, and a grounded conductor that has equalvoltage between it and each ungrounded conductor of thecircuit and that is connected to the neutral or groundedconductor of the system.
Building. A structure that stands alone or that is cut offfrom adjoining structures by fire walls with all openingstherein protected by approved fire doors.
Cabinet. An enclosure that is designed for either surfacemounting or flush mounting and is provided with a frame,mat, or trim in which a swinging door or doors are or canbe hung.
Circuit Breaker. A device designed to open and close acircuit by nonautomatic means and to open the circuit au-tomatically on a predetermined overcurrent without damageto itself when properly applied within its rating.
FPN: The automatic opening means can be integral, directacting with the circuit breaker, or remote from the circuitbreaker.
Adjustable (as applied to circuit breakers). A qualifyingterm indicating that the circuit breaker can be set to trip atvarious values of current, time, or both, within a predeter-mined range.
Instantaneous Trip (as applied to circuit breakers). Aqualifying term indicating that no delay is purposely intro-duced in the tripping action of the circuit breaker.
Inverse Time (as applied to circuit breakers). A qualifyingterm indicating that there is purposely introduced a delay inthe tripping action of the circuit breaker, which delay de-creases as the magnitude of the current increases.
Nonadjustable (as applied to circuit breakers). A quali-fying term indicating that the circuit breaker does not have
any adjustment to alter the value of current at which it willtrip or the time required for its operation.
Setting (of circuit breakers). The value of current, time, orboth, at which an adjustable circuit breaker is set to trip.
Concealed. Rendered inaccessible by the structure or finishof the building. Wires in concealed raceways are consid-ered concealed, even though they may become accessibleby withdrawing them.
Conductor, Bare. A conductor having no covering or elec-trical insulation whatsoever.
Conductor, Covered. A conductor encased within materialof composition or thickness that is not recognized by thisCode as electrical insulation.
Conductor, Insulated. A conductor encased within mate-rial of composition and thickness that is recognized by thisCode as electrical insulation.
Conduit Body. A separate portion of a conduit or tubingsystem that provides access through a removable cover(s)to the interior of the system at a junction of two or moresections of the system or at a terminal point of the system.
Boxes such as FS and FD or larger cast or sheet metalboxes are not classified as conduit bodies.
Connector, Pressure (Solderless). A device that estab-lishes a connection between two or more conductors orbetween one or more conductors and a terminal by meansof mechanical pressure and without the use of solder.
Continuous Load. A load where the maximum current isexpected to continue for 3 hours or more.
Controller. A device or group of devices that serves togovern, in some predetermined manner, the electric powerdelivered to the apparatus to which it is connected.
Cooking Unit, Counter-Mounted. A cooking appliancedesigned for mounting in or on a counter and consisting ofone or more heating elements, internal wiring, and built-inor mountable controls.
Coordination (Selective). Localization of an overcurrentcondition to restrict outages to the equipment affected, ac-complished by the choice of overcurrent-protective devicesor settings. [ROP 1–76]
Copper-Clad Aluminum Conductors. Conductors drawnfrom a copper-clad aluminum rod with the copper metallur-gically bonded to an aluminum core. The copper forms aminimum of 10 percent of the cross-sectional area of asolid conductor or each strand of a stranded conductor.
Cutout Box. An enclosure designed for surface mountingthat has swinging doors or covers secured directly to andtelescoping with the walls of the box proper.
70-5ARTICLE 100 DEFINITIONS
2005 EditionNATIONAL ELECTRICAL CODE
DRAF
T
-
Dead Front. Without live parts exposed to a person on theoperating side of the equipment.
Demand Factor. The ratio of the maximum demand of asystem, or part of a system, to the total connected load of asystem or the part of the system under consideration.
Device. A unit of an electrical system that is intended tocarry or control but not utilize electric energy. [ROP 1–78]
Disconnecting Means. A device, or group of devices, orother means by which the conductors of a circuit can bedisconnected from their source of supply.
Dusttight. Constructed so that dust will not enter the en-closing case under specified test conditions.
Duty, Continuous. Operation at a substantially constantload for an indefinitely long time.
Duty, Intermittent. Operation for alternate intervals of (1)load and no load; or (2) load and rest; or (3) load, no load,and rest.
Duty, Periodic. Intermittent operation in which the loadconditions are regularly recurrent.
Duty, Short-Time. Operation at a substantially constantload for a short and definite, specified time.
Duty, Varying. Operation at loads, and for intervals oftime, both of which may be subject to wide variation.
Dwelling Unit. One or more rooms for the use of one ormore persons as a housekeeping unit with space for eating,living, cooking, and sleeping, and permanent provisions forsanitation. [ROP 1–84]
Dwelling, One-Family. A building that consists solely ofone dwelling unit.
Dwelling, Two-Family. A building that consists solely oftwo dwelling units.
Dwelling, Multifamily. A building that contains three ormore dwelling units.
Electric Sign. A fixed, stationary, or portable self-contained, electrically illuminated utilization equipmentwith words or symbols designed to convey information orattract attention.
Enclosed. Surrounded by a case, housing, fence, or wall(s)that prevents persons from accidentally contacting ener-gized parts.
Enclosure. The case or housing of apparatus, or the fenceor walls surrounding an installation to prevent personnelfrom accidentally contacting energized parts or to protectthe equipment from physical damage.
FPN: See Table 430.91 for examples of enclosure types.
Energized. Electrically connected to, or is, a source ofvoltage. [ROP 1–88]
Equipment. A general term including material, fittings, de-vices, appliances, luminaires (fixtures), apparatus, and thelike used as a part of, or in connection with, an electricalinstallation.
Explosionproof Apparatus. Apparatus enclosed in a casethat is capable of withstanding an explosion of a specifiedgas or vapor that may occur within it and of preventing theignition of a specified gas or vapor surrounding the enclo-sure by sparks, flashes, or explosion of the gas or vaporwithin, and that operates at such an external temperaturethat a surrounding flammable atmosphere will not be ig-nited thereby.
FPN: For further information, see ANSI/UL 1203-1999,Explosion-Proof and Dust-Ignition-Proof Electrical Equip-ment for Use in Hazardous (Classified) Locations.
Exposed (as applied to live parts). Capable of being in-advertently touched or approached nearer than a safe dis-tance by a person. It is applied to parts that are not suitablyguarded, isolated, or insulated.
Exposed (as applied to wiring methods). On or attachedto the surface or behind panels designed to allow access.
Externally Operable. Capable of being operated withoutexposing the operator to contact with live parts.
Feeder. All circuit conductors between the service equip-ment, the source of a separately derived system, or otherpower supply source and the final branch-circuit overcur-rent device.
Festoon Lighting. A string of outdoor lights that is sus-pended between two points.
Fitting. An accessory such as a locknut, bushing, or otherpart of a wiring system that is intended primarily to per-form a mechanical rather than an electrical function.
Garage. A building or portion of a building in which one ormore self-propelled vehicles can be kept for use, sale, stor-age, rental, repair, exhibition, or demonstration purposes.
FPN: For commercial garages, repair and storage, see Ar-ticle 511.
Ground. A conducting connection, whether intentional oraccidental, between an electrical circuit or equipment andthe earth or to some conducting body that serves in place ofthe earth.
Grounded. Connected to earth or to some conducting bodythat serves in place of the earth.
Grounded, Effectively. Intentionally connected to earththrough a ground connection or connections of sufficiently
70-6 ARTICLE 100 DEFINITIONS
2005 Edition NATIONAL ELECTRICAL CODE
DRAF
T
-
low impedance and having sufficient current-carrying ca-pacity to prevent the buildup of voltages that may result inundue hazards to connected equipment or to persons.
Grounded, Solidly. Connected to ground without insertingany resistor or impedance device. [ROP 1–136]
Grounded Conductor. A system or circuit conductor thatis intentionally grounded.
Grounding Conductor. A conductor used to connectequipment or the grounded circuit of a wiring system to agrounding electrode or electrodes.
Grounding Conductor, Equipment. The conductor usedto connect the non–current-carrying metal parts of equip-ment, raceways, and other enclosures to the systemgrounded conductor, the grounding electrode conductor, orboth, at the service equipment or at the source of a sepa-rately derived system.
Grounding Electrode. A device that establishes an electri-cal connection to the earth. [ROP 1–97]
Grounding Electrode Conductor. The conductor used toconnect the grounding electrode(s) to the equipmentgrounding conductor, to the grounded conductor, or to both,at the service, at each building or structure where suppliedby a feeder(s) or branch circuit(s), or at the source of aseparately derived system. [ROP 1–98]
Ground-Fault Circuit Interrupter (GFCI). A device in-tended for the protection of personnel that functions to de-energize a circuit or portion thereof within an establishedperiod of time when a current to ground exceeds the valuesestablished for a Class A device. [ROP 1–94]
FPN: Class A ground-fault circuit interrupters trip whenthe current to ground has a value in the range of 4 mA to 6mA. For further information, see UL 943, Standard forGround-Fault Circuit Interrupters.
Ground-Fault Protection of Equipment (GFPE). A sys-tem intended to provide protection of equipment from dam-aging line-to-ground fault currents by operating to cause adisconnecting means to open all ungrounded conductors ofthe faulted circuit. This protection is provided at currentlevels less than those required to protect conductors fromdamage through the operation of a supply circuit overcur-rent device. [ROP 1–94]
Guarded. Covered, shielded, fenced, enclosed, or other-wise protected by means of suitable covers, casings, barri-ers, rails, screens, mats, or platforms to remove the likeli-hood of approach or contact by persons or objects to a pointof danger.
Guest Room. An accommodation combining living, sleep-ing, sanitary, and storage facilities within a compartment.[ROP 1–101]
Guest Suite. An accommodation with two or more con-tiguous rooms comprising a compartment, with or withoutdoors between such rooms, that provides living, sleeping,sanitary, and storage facilities. [ROP 1–101]
Hoistway. Any shaftway, hatchway, well hole, or other ver-tical opening or space in which an elevator or dumbwaiteris designed to operate.
Identified (as applied to equipment). Recognizable assuitable for the specific purpose, function, use, environ-ment, application, and so forth, where described in a par-ticular Code requirement.
FPN: Some examples of ways to determine suitability ofequipment for a specific purpose, environment, or applica-tion include investigations by a qualified testing laboratory(listing and labeling), an inspection agency, or other orga-nizations concerned with product evaluation.
In Sight From (Within Sight From, Within Sight).Where this Code specifies that one equipment shall be “insight from,” “within sight from,” or “within sight,” and soforth, of another equipment, the specified equipment is tobe visible and not more than 15 m (50 ft) distant from theother.
Interrupting Rating. The highest current at rated voltagethat a device is intended to interrupt under standard testconditions.
FPN: Equipment intended to interrupt current at other thanfault levels may have its interrupting rating implied in otherratings, such as horsepower or locked rotor current.
Isolated (as applied to location). Not readily accessibleto persons unless special means for access are used.
Kitchen. An area used, or designated to be used, for thepreparation of food. [ROP 1–114]
Labeled. Equipment or materials to which has been at-tached a label, symbol, or other identifying mark of anorganization that is acceptable to the authority having juris-diction and concerned with product evaluation, that main-tains periodic inspection of production of labeled equip-ment or materials, and by whose labeling the manufacturerindicates compliance with appropriate standards or perfor-mance in a specified manner.
Lighting Outlet. An outlet intended for the direct connec-tion of a lampholder, a luminaire (lighting fixture), or apendant cord terminating in a lampholder.
Listed. Equipment, materials, or services included in a listpublished by an organization that is acceptable to the au-thority having jurisdiction and concerned with evaluationof products or services, that maintains periodic inspectionof production of listed equipment or materials or periodicevaluation of services, and whose listing states that the
70-7ARTICLE 100 DEFINITIONS
2005 EditionNATIONAL ELECTRICAL CODE
DRAF
T
-
equipment, material, or services either meets appropriatedesignated standards or has been tested and found suitablefor a specified purpose.
FPN: The means for identifying listed equipment mayvary for each organization concerned with product evalua-tion, some of which do not recognize equipment as listedunless it is also labeled. Use of the system employed by thelisting organization allows the authority having jurisdictionto identify a listed product.
Live Parts. Energized conductive components.
Location, Damp. Locations protected from weather andnot subject to saturation with water or other liquids butsubject to moderate degrees of moisture. Examples of suchlocations include partially protected locations under cano-pies, marquees, roofed open porches, and like locations,and interior locations subject to moderate degrees of mois-ture, such as some basements, some barns, and some cold-storage warehouses.
Location, Dry. A location not normally subject to damp-ness or wetness. A location classified as dry may be tem-porarily subject to dampness or wetness, as in the case of abuilding under construction.
Location, Wet. Installations under ground or in concreteslabs or masonry in direct contact with the earth; in loca-tions subject to saturation with water or other liquids, suchas vehicle washing areas; and in unprotected locations ex-posed to weather.
Luminaire. A complete lighting unit consisting of a lampor lamps together with the parts designed to distribute thelight, to position and protect the lamps and ballast (whereapplicable), and to connect the lamps to the power supply.
Metal-Enclosed Power Switchgear. A switchgear assem-bly completely enclosed on all sides and top with sheetmetal (except for ventilating openings and inspection win-dows) containing primary power circuit switching, inter-rupting devices, or both, with buses and connections. Theassembly may include control and auxiliary devices. Accessto the interior of the enclosure is provided by doors, remov-able covers, or both.
Motor Control Center. An assembly of one or more en-closed sections having a common power bus and princi-pally containing motor control units.
Multioutlet Assembly. A type of surface, flush, or free-standing raceway designed to hold conductors and recep-tacles, assembled in the field or at the factory.
Neutral Conductor. A conductor, other than a groundingconductor, that is connected to the common point of a wyeconnection in a polyphase system or the point of a sym-metrical system that is normally at zero voltage. [ROP1–122]
Nonautomatic. Action requiring personal intervention forits control. As applied to an electric controller, nonauto-matic control does not necessarily imply a manual control-ler, but only that personal intervention is necessary.[ROP 1–123]
Nonlinear Load. A load where the wave shape of thesteady-state current does not follow the wave shape of theapplied voltage.
FPN: Electronic equipment, electronic/electric-dischargelighting, adjustable-speed drive systems, and similar equip-ment may be nonlinear loads.
Outlet. A point on the wiring system at which current istaken to supply utilization equipment.
Outline Lighting. An arrangement of lighting equipmentto outline or call attention to certain features such as theshape of a building or the decoration of a window. [ROP1–125]
Overcurrent. Any current in excess of the rated currentof equipment or the ampacity of a conductor. It may resultfrom overload, short circuit, or ground fault.
FPN: A current in excess of rating may be accommodatedby certain equipment and conductors for a given set ofconditions. Therefore the rules for overcurrent protectionare specific for particular situations.
Overload. Operation of equipment in excess of normal,full-load rating, or of a conductor in excess of rated ampac-ity that, when it persists for a sufficient length of time,would cause damage or dangerous overheating. A fault,such as a short circuit or ground fault, is not an overload.
Panelboard. A single panel or group of panel units de-signed for assembly in the form of a single panel, includingbuses and automatic overcurrent devices, and equippedwith or without switches for the control of light, heat, orpower circuits; designed to be placed in a cabinet or cutoutbox placed in or against a wall, partition, or other support;and accessible only from the front.
Plenum. A compartment or chamber to which one ormore air ducts are connected and that forms part of the airdistribution system.
Power Outlet. An enclosed assembly that may includereceptacles, circuit breakers, fuseholders, fused switches,buses, and watt-hour meter mounting means; intended tosupply and control power to mobile homes, recreationalvehicles, park trailers, or boats or to serve as a means fordistributing power required to operate mobile or tempo-rarily installed equipment.
Premises Wiring (System). That interior and exteriorwiring, including power, lighting, control, and signal circuitwiring together with all their associated hardware, fittings,and wiring devices, both permanently and temporarily in-stalled, that extends from the service point or source ofpower, such as a battery, a solar photovoltaic system, or a
70-8 ARTICLE 100 DEFINITIONS
2005 Edition NATIONAL ELECTRICAL CODE
DRAF
T
-
generator, transformer, or converter windings, to the out-let(s). Such wiring does not include wiring internal to ap-pliances, luminaires (fixtures), motors, controllers, motorcontrol centers, and similar equipment.
Qualified Person. One who has skills and knowledge re-lated to the construction and operation of the electricalequipment and installations and has received safety trainingon the hazards involved.
FPN: Examples of this safety training include, but are notlimited to, training in the use of special precautionary tech-niques, personal protective equipment, insulating andshielding materials, and insulated tools and test equipmentwhen working on or near exposed conductors and or circuitparts that are or can become energized. [ROP 1–130]
Raceway. An enclosed channel of metal or nonmetallicmaterials designed expressly for holding wires, cables, orbusbars, with additional functions as permitted in thisCode. Raceways include, but are not limited to, rigid metalconduit, rigid nonmetallic conduit, intermediate metal con-duit, liquidtight flexible conduit, flexible metallic tubing,flexible metal conduit, electrical nonmetallic tubing, elec-trical metallic tubing, underfloor raceways, cellular con-crete floor raceways, cellular metal floor raceways, surfaceraceways, wireways, and busways.
Rainproof. Constructed, protected, or treated so as to pre-vent rain from interfering with the successful operation ofthe apparatus under specified test conditions.
Raintight. Constructed or protected so that exposure to abeating rain will not result in the entrance of water underspecified test conditions.
Receptacle. A receptacle is a contact device installed atthe outlet for the connection of an attachment plug. A singlereceptacle is a single contact device with no other contactdevice on the same yoke. A multiple receptacle is two ormore contact devices on the same yoke.
Receptacle Outlet. An outlet where one or more recep-tacles are installed.
Remote-Control Circuit. Any electric circuit that con-trols any other circuit through a relay or an equivalent de-vice.
Sealable Equipment. Equipment enclosed in a case orcabinet that is provided with a means of sealing or lockingso that live parts cannot be made accessible without open-ing the enclosure. The equipment may or may not be oper-able without opening the enclosure.
Separately Derived System. A premises wiring systemwhose power is derived from a source of electric energyother than a service. Such systems have no direct electricalconnection, including a solidly connected grounded circuitconductor, to supply conductors originating in another sys-tem. [ROP 1–132]
Service. The conductors and equipment for deliveringelectric energy from the serving utility to the wiring systemof the premises served.
Service Cable. Service conductors made up in the formof a cable.
Service Conductors. The conductors from the servicepoint to the service disconnecting means.
Service Drop. The overhead service conductors from thelast pole or other aerial support to and including the splices,if any, connecting to the service-entrance conductors at thebuilding or other structure.
Service-Entrance Conductors, Overhead System. Theservice conductors between the terminals of the serviceequipment and a point usually outside the building, clear ofbuilding walls, where joined by tap or splice to the servicedrop.
Service-Entrance Conductors, Underground System.The service conductors between the terminals of the serviceequipment and the point of connection to the service lateral.
FPN: Where service equipment is located outside thebuilding walls, there may be no service-entrance conduc-tors, or they may be entirely outside the building.
Service Equipment. The necessary equipment, usuallyconsisting of a circuit breaker(s) or switch(es) and fuse(s)and their accessories, connected to the load end of serviceconductors to a building or other structure, or an otherwisedesignated area, and intended to constitute the main controland cutoff of the supply.
Service Lateral. The underground service conductors be-tween the street main, including any risers at a pole or otherstructure or from transformers, and the first point of con-nection to the service-entrance conductors in a terminal boxor meter or other enclosure, inside or outside the buildingwall. Where there is no terminal box, meter, or other enclo-sure, the point of connection is considered to be the point ofentrance of the service conductors into the building.
Service Point. The point of connection between the fa-cilities of the serving utility and the premises wiring.
Show Window. Any window used or designed to be usedfor the display of goods or advertising material, whether itis fully or partly enclosed or entirely open at the rear andwhether or not it has a platform raised higher than the streetfloor level.
Signaling Circuit. Any electric circuit that energizes sig-naling equipment.
Solar Photovoltaic System. The total components andsubsystems that, in combination, convert solar energy intoelectrical energy suitable for connection to a utilizationload.
Special Permission. The written consent of the authorityhaving jurisdiction.
70-9ARTICLE 100 DEFINITIONS
2005 EditionNATIONAL ELECTRICAL CODE
DRAF
T
-
Structure. That which is built or constructed.
Supplementary Overcurrent Protective Device. A de-vice intended to provide limited overcurrent protection forspecific applications and utilization equipment such as lu-minaires (lighting fixtures) and appliances. This limitedprotection is in addition to the protection provided in therequired branch circuit by the branch circuit overcurrentprotective device. [ROP 1–138]
Switch, Bypass Isolation. A manually operated deviceused