Controlling Sutardja Dai Hall
Andrew KrioukovStephen Dawson-Haggerty, Jay Taneja
David Culler
![Page 2: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/2.jpg)
Buildings
40% of US electricity42% of greenhouse gas footprint
• Want:– Energy Efficiency– Flexible Load
![Page 3: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/3.jpg)
Building Power Consumption
11%
1MW883 kW
![Page 4: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/4.jpg)
Sutardja Dai Hall
3 years old
7 floors, 140k sq. feet
Collaboratories, offices, classrooms, auditorium & nanofab
Siemens Controls, WattStopper> 6000 sensors & actuators
![Page 5: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/5.jpg)
Building Control NetworkSensors,Actuators Controllers
WattStopperServer
Modem
Internet
sMAP/HTTP
Readings& Actuation
BACnet/IPGateway
Modem
Siemens P2over RS-485
SiemensServer
![Page 6: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/6.jpg)
Cooling Tower
Chiller
Economizer Air Handler
Hot Water
VAV VAV VAV
![Page 7: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/7.jpg)
Problems
1. Oblivious control loops– Increasing thermostat on warm day wastes energy– Conflicting controls
2. Oversizing – Excess ventilation– Oversized chiller
Inefficient, Inflexible Control
![Page 8: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/8.jpg)
Why?Modular Building ControllerMotorola 68302 16.67 MHz Processor3MB RAMRS-485 @ 300 - 115.2K bps60 day battery backup
• Hardware:– Resource limited– Reliability is the goal– Supports independent operation
• Generic control logic:Oversizing ensures comfortable operation in most buildings with less effort
• Historic:Replacing pneumatic/analog controls
![Page 9: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/9.jpg)
Goal
Globally-aware control with the same reliability.
• What is the architecture?– How to ensure: robustness, security and safety?
• What is the control policy?
![Page 10: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/10.jpg)
Building Control Architecture
Internet
Weather,Energy Prices
Low-levelControl
Sensors & Actuators
High-levelControl
Set points,PID parameters
Valve pos,Damper pos,
Fan speed
Building-wide optimization
PID Loops
How to do “atomic” building configuration changes?Security model?Enforcing safety constraints.
![Page 11: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/11.jpg)
Policy Components
• Supply air temp• Airflow• Room set points• Cold water pumps• Chiller• Hot water pumps
![Page 12: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/12.jpg)
Variable Air Volume (VAV) Box
• Ventilation• Maintain temperature
100%
0%
Cold AirflowHeating Valve
Setpoint Too HotToo Cold
Min airflow
![Page 13: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/13.jpg)
VAV Control100% Cooling
100% Heating
Dead band
![Page 14: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/14.jpg)
Conflicting VAVsMax Cooling• S1-1 – Boiler room• S4-4 – Floor 4 open office• S5-8 - Floor 5 office• S5-10 - Floor 5 open office • S7-13 - Floor 7 open office• S7-10 - Floor 7 open office• S7-1 - Floor 7 open office
Max heating• S1-9 - Mechanical Room• S4-20 - Floor 4 open office• S5-9 - Floor 5 hallway • S5-21 - Floor 5 open office• S5-4 - Floor 5 open office• S7-9 - Floor 7 open office• S7-3 - Floor 7 open office
![Page 15: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/15.jpg)
Ventilation
• TITLE 24: – 15 CFM per person of fresh air– 900 – 1100 PPM CO2
• VAVs have static minimum airflow base on:– Maximum occupancy– Minimum fresh air intake
![Page 16: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/16.jpg)
Fresh Air Intake
![Page 17: Controlling Sutardja Dai Hall](https://reader035.vdocument.in/reader035/viewer/2022062410/56816413550346895dd5c2a0/html5/thumbnails/17.jpg)
Questions?