Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 1
Department of Science and Technology, Government of Gujarat
Responses to Pre- Bid Queries- II(B)
Engagement of Construction and Maintenance Agency (CMA)
for
Regional Science Museum at Patan,
Gujarat Council on Science and Technology
Department of Science & Technology, Govt. of Gujarat
Block B, 7th Floor, M.S Building, Sector 11, Gandhinagar – 382 011
Gujarat, India
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 2
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
1 94 Voulme II -
Schedule 11
I. SEWAGE
TREATMEN
T PLANT
We request authority to clarify the scope of Civil Works
and MEP for Sewage Treatment Plant This will be in Contractor’s scope.
2 Voulme II -
Schedule 11
Sec - C ,
SL.No 5
We request you to confirm the type of stone to be used
for making of facia. Kindly confirm.
Kindly refer Architectural BOQ for the
description mentions Marble/ Granite.
3 Schedule 2 Scope of
Works
We request Authority to Take Permission from all such
Concern department.
Please refer Schedule 2 and Schedule 9 for
all approvals to be taken by DTA and CMA
4 General Reinforceme
nt Details
We request Authority to provide reinforcement details
for Building for calculating quantities.
Reinforcement details shall be provided
during execution stage.
5 General
We request Authority to Provide BOQ in Excel Format No change
6 2
Scope of
Works
We request Authority that kindly Considered the
Tapping/outfall point 1 m Outside the Boundary of
RSM.
Kindly refer schedule 2 & schedule 3,
7 Autocad
Drawing
Autocad
Drawing Kindly Provide Details of D5 - Door type
Please refer description mentioned in BOQ,
3.1 & 3.2 of internal partition and false
ceiling
8
Autocad
Drawing
Autocad
Drawing We Consider it to Single leaf Aluminium glazed Door in
the same area.
Please refer Door Window Schedule in
drawing sheet no. 10741A-AC-1013-AC-
10101
9
Autocad
Drawing
Autocad
Drawing We request authority to kindly provide details/Schedule
of Ventilator
The ventilator details are Width – 1000mm,
Height-1200mm, Cill-1000mm, Lintel –
2250mm
10
Autocad
Drawing
Autocad
Drawing We request Authority to provide Finishing Details at
Ground floor Auditorium Central lobby.
Finishing Details will be same as that of the
corridor.
11
Autocad
Drawing
Autocad
Drawing We request Authority to provide Finishing Details at
ground Floor Room For Services
Finishing Details will be same as that of
AHU.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 3
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
12
Autocad
Drawing
Autocad
Drawing We request Authority to provide details for Double
Height Entrance Lobby with Cutout Above
Please refer finishing details of double
height atrium in drawing sheet no.
TCE.10741A-AC-1013-AF-10003.
13
Autocad
Drawing
Autocad
Drawing
We request Authority to Kindly provide Finishing
Details for Given Areas for Ground Floor -
1.IBMS ROOM
2. Circulation And Fire Exit Lobby - Grid 3-4 &A-B
3. Circulation And Fire Exit Lobby - Grid 11-12 &A-B
4. Jurassic Theatre
1. Finishing details of IBMS room is same
as that of the control room.
2. Finishing details of Circulation And Fire
Exit Lobby - Grid 3-4 &A-B is same as that
of corridors.
3. Finishing details of Circulation And Fire
Exit Lobby - Grid 11-12 &A-B
Will be same as that of corridors.
4. Finishing details of Jurassic Theater will
be same as that of short documentary
theater.
14
Autocad
Drawing
Autocad
Drawing
Near Office and Central Exhibit Area: Partition Wall of
Various Lenghts have been showed in CAD Drawing,
We request Authority to Kindly Clarify Details such as
Section and Relevant BOQ item to be referred.
Please refer sl. No. 1 of internal partition &
false ceiling for the partitions in central
exhibit area and sl.no.1 & 2 of internal
partition & false ceiling for office area
partition
15
3 Technical
Specification
s 5.2.2 We request you to kindly follow IS 456. IS 10262 can be followed alongwith IS 456.
16
42 Technical
Specification
s 11.5.1
We Request Authority to follow IS code for removal of
formwork. No change
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 4
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
17
44 Technical
Specification
s 13.5 We request authority to Consider as per IS Code No change
18
49-51 Technical
Specification
s
14.8.1,
14.8.2 We request Authority to kindly Follow IS 383-2016. IS 383-2016 can be followed
19
Autocad
Drawing
Autocad
Drawing
We request Authority to Provide footing Layout and
Footing Section for main Building and Boundary Wall
for Quantity Calculation
The details of the same will be provided
during execution stage.
20
In Gujarat state cement used is Abuja, Ultratech, saghi,
JK Lakshmi, sidhee and Hathi brand,but in list of
Approved Makes only Ultratech is given. All these brands
are I.S.I approved makes, hence it is desirable that above
said brands may be added in approved make list please.
A.C.C. and Ultratech are already part of
approved make list. In addition to the brands
mentioned in approved make list, Ambuja,
Ultratech, Sanghi and JK Lakshmi cement
are included
21 NA
TCE
10741A-EL-
4000-AU-
40001
Drawing
40 KVA UPS with ACDB is shown but the UPS panel is
missing. Kindly Calrify is the UPS Panel needs to be
consider or not? If Needs to Consider, Kindly Provide
the SLD for the same.
UPS along with distribution board already
been shown in SLD. Please refer
TCE.10741A-EL-4000-AU-40001 sheet 3
of 3
22 NA
TCE
10741A-EL-
4000-AU-
40001
Drawing SLD for Fire Panel, WTP Panel is not Shown in SLD.
Kindly Confirm the consideration.
Fire Panel and WTP Panel shall be as per
Package requirements. In present scheme,
only SINGLE POINT supply to these panels
considered.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 5
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
23 NA
TCE 10741A-
EL-4000-AU-
40001 Drawing
SLD for HVAC Panel is not Shown in SLD. Kindly
Confirm the consideration.
HVAC Panel shall be as per Package
requirements. Only SINGLE POINT supply
is considered in Electrical Single Line
Diagrams.
24 NA
TCE 10741A-
EL-4000-AU-
40001 Drawing
Kindly Clarify the Purpose of 12 Nos 40A FP MCB &
10 Nos 16A DP MCB shown at the outgoing terminal of
UPS and also the Size of cable to be used for the same.
40A, 4P MCBs will feed downstream
Emergency Lighting Distribution Boards.
Other DP MCBs will be used to supply UPS
power to various requirments during
detailing. (like BMS, exhibit, Workstation
etc. )
Cable Sizes: 40A 4P MCB - 4C X 25
sq.mm. Cable, DP MCB's - Upto 16 sq.mm.
25 NA General
NA Kindly Provide the Details of DB to be Provided for Lift
Purpose.
Lift Panel (DB) shall be as per Lift's
requirement. Only Single point supply
considered for Lift Panel.
26 NA General
NA Light Fixture for Lift is missing in Drg, Kindly confirm
the consideration. Light Fixture in Lift, will be part of lift car.
27 NA General
NA
Kindly Provide the Size of Wire/Cables used for 70W
Flood Lights, 50W Down Lighters, Up Lighters, Object
Focus Lights, 22W Down Lighters, Special Light
Fixtures
For Flood Lights - upto 6 sq.mm. Wire /
cable. For others 2.5 / 4 sq.mm. wires.
28 NA
TCE 10741A-
EL-4000-AU-
40003 Drawing
Please Provide the Specification/Model Cat Ref for
Below Mentioned Lights
1. Down Lightes
2. Ceiling Suspension Lights
3. Uplighters, Floor/Base Mounting
4. Object Focus Lights (Ceiling Mounted)
For these items, refer description mentioned
in Architecture BOQ for Lighting fixtures. It
is clearly mentions the suggested vendors
for the same. These are general lighting and
there cannot be particular specifications for
the same. Model/ Cat Ref no are vendor
specific and depends on vendor to vendor.
29 NA
BOQ,
Schedule 11
15.1.6, 16.1,
16.2, 16.4,
16.6, 16.7
Please Provide the Use of Following Items.
Item 15.1.6, 16.1, 16.2, 16.4, 16.6, 16.7
15.1.6 - is EXIT Light. Already shown in
Lighting Layout.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 6
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
16.1 to 16.7 are Street Lighting items. -
They are shown in Drawing Number
TCE.10741A-EL-4000-GL-40013
30 NA General
Please Provide Drg for Special Light Fixtures
Please refer TCE.10741A-EL-4000-GL-
40002-03-04-05-06 - LIGHTING LAYOUT
provided in tender drawings.
31 NA
Technical
Specification
& BOQ NA
The BOQ Items shows the capacity of DO Fuse to be
install is 11KKKV but as per technical specs it is 33 KV,
Please confirm the size of fuse to be considered.
Kindly note that electrical system is 11kV
system so all equipment shall be 11kV rated
only.
32 NA General
NA Kindly Provide the Details of DB to be Provided for Lift
Purpose. Refer response to query 25.
33 NA General
NA Light Fixture for Lift is missing in Drg, Kindly confirm
the consideration. Refer response to query 26.
34 NA
TCE-
10741A-EL-
4000-AU-
40001
Drawing
Kindly Clarify the Purpose of 12 Nos 40A FP MCB &
10 Nos 16A DP MCB shown at the out going terminal of
UPS and also the Size of cable to be used for the same.
Refer response to query 24.
35 NA General
NA Please Provide the Cable Route and Earthling Route, for
Calculation of Quantities of Cable & Earthing Items.
Please refer TCE.10741A-EL-4000-SE-
40014 - FLOOR EARTHING &
LIGHTNING PROTECTION LAYOUT
provided in tender drawings.
36 NA
Technical
Specification Specificatio
n Kindly Provide the specification for Distribution Boards.
We believe you are referring to LDB /
PDBs. They shall be as per Manufacturer's
standard. List of approved makes already
given. Please refer it to schedule 3.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 7
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
37 NA
Technical
Specification
& BOQ
Specificatio
n
The Technical specification of BMS System is included
in Schedule 3 but the same is not consider in BOQ,
Kindly Confirm the consideration.
Please consider the specifications mentioned
in the Schedule 3 for BMS
38 NA
Technical
Specification
& BOQ
Specificatio
n
Please Provide Technical Specification of Ticket
Counter Software if any.
As such there are no technical specifications
for Ticketing software. Generally they have
data sheets which are vendor specific. Data
sheets from the vendor can be provided
which will be approved by Authority/DTA.
39
BOQ &
Drawing
DSR Item
No 4.6 In
Electrical &
TCE-
10739A-EL-
4026-GL-
40020
In Drg the height is mentionede as 75mm but in BOQ
item is of 50mm. Kindly confirm which size is to be
considered.
The dwg no. mentioned is not for RSM
Patan. Pls Clarify. Pls follow description
mentioned in BOQ for cable tray details.
40 BOQ
DSR Item
No. 17.1,
17.2, 17.3,
17.4, 17.5,
17.6
Kindly Provide the area where 3Cx2.5Sqmm Cu FR
PVC Insulated Cabel to be used and where
2x2.5+1x1.5Sqmm FRLS PVC Circuit is to be used.
3Cx2.5Sqmm Cu FR PVC- Primary Points-
Lighting
2x2.5+1x1.5Sqmm FRLS PVC- Secondary
points-Lighting
41 Annexure 5
Annexure 5 Themic Blue Lighting is not visible; Provide the Auto
cad Drg for the same.
Autocad dwgs will be provided against
submission of NDA. Please refer
TCE.10741A-EL-4000-GL-40002 for the
same.
42 General
General Please provide auto cad drawing for special lights
Autocad dwgs will be provided against
submission of NDA. Please refer
TCE.10741A-EL-4000-GL-40002 for the
same.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 8
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
43 Page no
51
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
BOQ-2.00-
Centrifugal
Pumps:
Shall we consider pump with thermal insulation with
cladding ? Please confirm
Yes, Pump shall have thermal insulation
with cladding as per the relevant piping
insulation thickness
44 Page no
51
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
BOQ- 3.0 -
Cooling
Tower
CTI Certified cooling tower Required or Not? Please
confirm. Not Required
45 Page no
52 to 55
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
BOQ- 4.0-
Canteen Air
Handling
Units:
BOQ- 5.0-
Kitchen Air
Handling
Unit (100%
Fresh Air):
BOQ- 6.0-
Ceiling
Suspended
Air
Handling
Unit
BOQ-
7.0,8.0-
Floor
Mentioned static pressure is Esp or TSP ?please confirm.
(ESP- External static pressure
TSP- Total Static pressure)
TSP.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 9
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
Mounted
Air
Handling
Units
46 Page no
55
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
BOQ- 9.0
Floor
Mounted
Heat
Recovery
AirHandling
Unitsfor
FreshAir:
Please provide the unit selection conditions :-
a) Fresh air condition for the summer and Monsoon.
B) return Air condition
Refer Technical Specification Clause No-5
for Outdoor Design Conditions And Clause
No-6.01 for Indoor Design Conditions
47 Page no
57
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
BOQ- 12.0
High Wall
Split AC
Units:
Hi wall units are inverter type or non inverter type ?
Please confirm Inverter Type
48 Page no
59
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
B) Ducting:
1.00 GSS
Factory
Fabricated
Ducting:
Ducting is 180 GSM or 120GSM ? Please confirm.
As per Technical Specification for Duct
work, Clause for Air Distribution Point No-
3.01-C & 4.01-C ,
The GSM Value shall be 120
49 Page no
59
5-RFP-
Volume-I-
Draft-
B) Ducting:
1.04
QTY shown for 18G is R/O but amount is shown. Please
confirm?
The quantity shown in item description is
Rate only. Refer Corrigendum V(b)
attached..
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 10
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
Contract-
Schedule-11
50 Page no
64
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
E)Insulation
Works
6.03(a)
6.04(c)
6.05(c)
Amount is not reflecting for the item.
The total amount for these items comes out
to be Rs. 21414. Refer Corrigendum V (b)
attached.. Please note that the BOQ is
indicative in nature and the project is
awarded on a lump sump basis.
51 Page no
21
5-RFP-
Volume-I-
Draft-
Contract-
Schedule-11
GRAND
TOTAL ACTUAL VALUE - 39960375.83
Please consider the actual value. Refer
Corrigendum V (b) attached
52 Schedule 3-
Exhibits
As per the discussion over the pre bid meeting, it is
suggested by the Authority to use the specified videos
from Youtube for the main content source for the
interactive exhibits as an edited version for the same.
We would like to know that who will take the ownership
for the copyrights of the same videos. Kindly clari
Refer Corrigendum V(b) attached for RFP
Volume II, Schedule 2 -Scope of Work
53 Schedule 3-
Exhibits
We would request to upload detailed design & AV BOQ
for three museums for our detailing of the appropriate
propositions
Please Refer Corrigendum V(b) Annexure 1
Exhibit report(Schedule 3- RFP Volume II).
AV design and BOQ is part of scope of
CMA
54 Schedule-3
Exhibit
Report
Chapter 8/7
– Theming
Lack of clarity/ text readability is an issue and hence
can’t comprehend what’s written
This section has been removed and detailed
3D views are attached as Annexure 1. Please
Refer Corrigendum V(b) Annexure 1
Exhibit report(Schedule 3- RFP Volume II)
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 11
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
55 Schedule-3
Exhibit
Report
Annexure 1: Titling of gallery is missing Please Refer Corrigendum V(b) Annexure 1
Exhibit report(Schedule 3- RFP Volume II)
56 Schedule-3
Exhibit
Report
Annexure 1: No details in Projector Room except make/brand of
Projector
Details of the projector room have been
updated in the exhibit list. Please Refer
Corrigendum V(b) Annexure 1 Exhibit
report(Schedule 3- RFP Volume II)
57 Schedule-3
Exhibit
Report
Detail brief of Video content required wherever video is
to be developed
Video content details have been updated.
Please Refer Corrigendum V(b) Annexure 1
Exhibit report(Schedule 3- RFP Volume II)
58 Schedule-3
Exhibit
Report
Simulator have been suggested at many places, details of
the same are missing
Simulators details have been updated. Please
Refer Corrigendum V(b) Annexure 1
Exhibit report(Schedule 3- RFP Volume II)
59 Schedule-3
Exhibit
Report
B10_EX 01 & 02: POP & FRP has been jointly
suggested – are you sure on this?
Either of the two can be used.
60 Schedule-3
Exhibit
Report
B10_EX 13: Details required with ref to number of seats 4 seats
61 Schedule-3
Exhibit
Report
B10_EX 14: Clarity needed
12 models shall be placed
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 12
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
62 Schedule-3
Exhibit
Report
B10_EX 15: Number of Pods? Number of animals?
Should they be real or fabricated
Bottled animals shall be real. The count of
animals has been specified in the exhibit list
63 Schedule-3
Exhibit
Report
Touch Screen Kiosks - size and technical specifications
needed
17” touch screen kiosk shall be used.
64 Schedule-3
Exhibit
Report
Content Brief for Touch screen kiosk missing
Content brief has been specified at various
places
65 Schedule-3
Exhibit
Report
For installations/models/statics/hardware – certain
vendors are suggested, do we have to only source from
them/ is it compulsory to only buy from these identified
vendors? Or can we procure from elsewhere with
equivalent specs or customize our self
The exhibits shall be procured from the
suggested vendors only. In eventuality of
non-availability of specific exhibit with
suggested vendor, same shall be dealt on
case to case basis at the time of execution
with prior approval from Authority/DTA
66 Schedule-3
Exhibit
Report
Content/copy curation has to be done by the agency or the
content will be given by the consultant? In case the
content has to be curated by the agency who will be the
approving authority of the same and the timelines?
The theme of content shall be specified by
DTA. Actual development of content/ copy
curation shall be done by the CMA and it
shall be approved by DTA/Authority
67 RFP-Volume-
II, Schedule3 Tender Drawings No. TCE.10741A-1019-LP-16413,
Quantity of 60mm thick interlocking concrete pavers is
Please consider volume of 2025 sqm. Also
refer Annexure 3.0 for updated BOQ.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 13
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
2410 SQMT given whereas 2025 SQMT given in BOQ.
Please confirm.
68
RFP-Volume-
II
BOQ Item No. D3 and D4 in Landscape, Unpolished kota
tile (25mm thick) and Mirror kota in outdoor (40mm
thick) given whereas not given. Please provide the
location for the same on drawing.
This is shown in the drawing near the
sundial area, please check legend and
drawing.
69
RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-
10101, Door & Window schedule, Ref. RFP-Volume-I,
BOQ Item No. D15.1 pg no. 6. Please provide
specification and separate item in BOQ for all types of
fire rated door.
Please refer Annexure 3.0 for description in
BOQ. BOQ item no. D-15.1 shall be
applicable for all other fire doors.
70 RFP-Volume-
II, Schedule3
Tender Drawings, DRG no. TCE.10741A-AC-1013-DW-
10141 (Door and Window schedule) given in list. Please
provide the same.
Door window schedule is provided in Drg
no. TCE.10741A-AC-1013-AC-10101.
Hence no separate drawing for door window
schedule is required. Please ignore the Drg
No. provided in list.
71
RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-
10101, Door & Window schedule, Quantity of Automatic
Glazed sliding door (GD1) 14 No. Given whereas 13No.
given in BOQ Arch. Items No. D5. Please confirm.
Please refer Annexure 4.0 Drawings No.
TCE.10741A-AC-1013-AC-10101 for
revised drawing. Number of GD1 are 13 and
the same is incorporated in revised drawing.
72 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-
10101, Door & Window schedule, Quantity of FD4 is not
match on provided floor plan. Pease confirm.
Please refer Annexure 4.0 Drawings No.
TCE.10741A-AC-1013-AC-10101 for
revised drawing. Quantity of FD-4 has been
revised in drawing.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 14
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
73 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-10101
to 10104, 1000mm and 950+250mm High SS railing
given whereas same item given in kg in BOQ. Please
provide detail drawings of same item.
The item for SS railing is considered in kg.
Please refer Annexure 4.0 Drg No.
TCE.10741A-AC-1013-AC-10002 revised
for all types of railing. In the revised Tender
drawings different types of railings are
indicated. The length of the railing may be
calculated by bidder as per tender drawings.
74
Please provide detail drawings of connecting bridge
Details of connecting bridge are already
given in Tender Drawing No. TCE.10741A-
CV-3000-RC-30059 & 30060.
75 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-10215
(Partition wall layout), vinyl wall paper mentioned
whereas same item not given in BOQ. Please provide
BOQ for the same.
All such partitions walls shall be “Gypsum
board partition” as per BOQ item no. F-1.1.
Vinyl wall paper is considered in BOQ of
‘Exhibits’
76
Please provide BOQ for Toilet cubical and location for
the same in drawing.
All the toilet partitions are made of masonry
wall, having tiles finish. Hence there is no
separate item for toilet cubicle.
77 RFP-Volume-
I BOQ
For Civil and Structural works, Grand total is not match
with actual amount. For Example: SOQ Item No. L 30
(Water Proofing), = 480 sqm x 505.90Rs/sqm =
2,42,832.00 Rs. Amount whereas 2,59,830.24 Rs given in
BOQ. Please correct arithmetic error.
Please consider the final amount in BOQ.
Contingencies are added in the final amount.
Kindly note that the estimates are only for
reference
78 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-
10103, L shaped sofa not shown but quantity is
considered in BOQ. Please confirm.
For sofa and all other furniture tender drg
no. TCE.10741A-AC-1013-IW-10201 to
10204 to be referred.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 15
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
79 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-
10101, 4 chair per table shown for canteen chair, hence
total NO. of chairs shall be 4x12= 48 No. while 96 No.
chairs are considered in BOQ. Please confirm.
For furniture, tender drg no. TCE.10741A-
AC-1013-IW-10201 to 10204 to be referred.
80 RFP-Volume-
I
BOQ of signage and furniture Item No.B5, B24 to B30,
Please provide the location else confirm whether quantity
to be executed as per BOQ.
Please refer tender drg no. TCE.10741A-
AC-1013-AC-10208 to 10211 for tentative
location of signage
81 RFP-Volume-
II, Schedule-2
Part A (Scope
of Work- D.
landscape
works)
Please provide BOQ, Specification and Details DRGs of
above mentioned scope.
Sr. No. 1 - Outdoor Furniture- We have used
brick and plastering and this quantity is
taken in the BOQ, location of the same will
be given in the GFC.
Sr. No. 2,3,4,8,10 - These are not there in
the design and thus not given BOQ, spec
and Drawing for the same.
Sr. No. 5 - Pump/Gardeners room will be
provided in the Utility Building and thus not
given separately.
Sr. No. 9 - Drip irrigation System- No drip
irrigation will be provided but manual
irrigation will be done on the site.
Sr. No. 6 & 7- Not Required.
Please note that the BOQ qualities are only
for reference
82 RFP-Volume-
II, Schedule3 Tender Drawings No. TCE.10741A-AC-1013-AC-
10102, Details No. 1.1 and 1.2 for terrace. Details shows
The coping item is already taken in the
BOQ. Please refer Sr. No. 17(b), 19(b) & 22
in the BOQ.
Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat
Page 16
S.
No
Page
No. Part of RFP Clause No. Clarification sought with justification, if any Response
RCC coping. Please provide the BOQ for the same item
in RNMT.
83 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-AC-1013-AC-10103
and 10104, Finishing Schedule, wall finish shows gypsum
plaster e.g. At lift lobby & corridor. The quantity is
mentioned in BOQ is 10 SQMT only. Please revise the
quantity in BOQ.
The gypsum plaster has been revised to
cement plaster and wall putty finish. The
revised finish schedule drawing to be
referred. A nominal quantity for gypsum
plaster is kept as alternative item.
84 RFP-Volume-
II, Schedule3
Tender Drawings No. TCE.10741A-CV-3000-RC-30001
(General Note), concrete note no. 8 shows HDPE sheet
applicable and mentioned in BOQ. Please provide the
BOQ for HDPE sheet.
HDPE sheet not required. Please ignore.
85 RFP-Volume-
II, Schedule3
Tender Drawings, reinforcement details are not provided
in all Structural drawings. Please provide the
reinforcement details for all structural members. No Change. Please refer schedule 2.