DESIGN OF A MULTI-STOREY STEEL STRUCTURE
Computation run on an un-braced frame with 3 spans and 6 storey, the loads beingpresented in the table below:
-
7/27/2019 Design of a Multi-storey Steel Structure
2/15
Calculus of the structural imperfections
This evaluation is made by considering an equivalent geometric imperfection, expressed bythe initial bow:
Where :
but:
Initial bow may be replaced by a system of horizontal equivalent forces at every level.Total load at every level is: 60kN/m6m3=1080 kN.Horizontal equivalent force is: 0.00261080=2.81 kN.
-
7/27/2019 Design of a Multi-storey Steel Structure
3/15
DESIGN OF THE STRUCTURAL CONNECTIONS: BEAMS TO COLUMNS JOINTS
End plates 25 mm and high strength M24, gr.10.9 bolts, not preloaded. Weak component of the connection: web panel of the column. The joint is considered a rigid one having a full strength by most of the engineers but its
characteristics places it in the semi-rigid connections area, with partial strength. Increasing the strength of the web may be done:
A- use a HEM section with a stronger web or a build-up section ( plate girder) increase thesteel consumption;
B- strengthen the web with supplementary steel plates welding increase the costs of theexecution and it induces a fragile behaviour under repeated loading (dynamic actions).
Supplementary web plates, ENV 1993-1-8
-
7/27/2019 Design of a Multi-storey Steel Structure
4/15
DESIGN OF THE BEAM TO COLUMN CONNECTION
Ed
cr cr
F
F
-
7/27/2019 Design of a Multi-storey Steel Structure
5/15
OSERVATIONS:Strength of the joint almost equal with the strength of the beam de (89% from the plastic
resistance of the beam and the stiffness of the joint with respect to the stiffness of the beam
is 13.2, that is smaller than 25, whic makes a joint to be considered fully rigid in an un-braced frame.Due to the fact that the external bending moment, M j,Ed is smaller than 2/3 from the
resistance of the joint, M j,Rd, the stiffness of the joint S j is equal withthe initial sitffness S j,ini. In this case both the situations will be considered in the design:1) the joint is fully rigid;2) The joint is semi-rigid, this behaviour being modelled.
The structural analysis must consider the sensitivity to lateral sway (I or II order) and alsothe plastic resistance of the structure (elastic or plastic).In this regard, a frame may be considered with fixed joints or the sway may be considered asdepending on the ratio between the vertical total force F Ed applied on the structure and thecritical elastic force F cr causing lateral instability (sway).
The structure with rigid connections, the buckling analysis shows a factor cr=11.1 > 10,then the structure is classified as with rigid connections. And normally according to ENV1993-1-1, an elastic I order analysis with global imperfections may be run .
Still, being close to the limit, an elastic II order analysis will be run also. For the semi-rigidconnections, the buckling analysis show a factor of cr= 8, 96 and because is a value under10, the structure will be considered with swaying connections and a II order elastic analysis isimposed.
-
7/27/2019 Design of a Multi-storey Steel Structure
6/15
Buckling analysis with SAP 2000
-
7/27/2019 Design of a Multi-storey Steel Structure
7/15
First buckling shape for the structure: a) with fully rigid connections; ) with semi-rigid connections
-
7/27/2019 Design of a Multi-storey Steel Structure
8/15
I and II order analysis of the structure with SAP 2000
-
7/27/2019 Design of a Multi-storey Steel Structure
9/15
-
7/27/2019 Design of a Multi-storey Steel Structure
10/15
The reserve in the resistance of the structure up to a plastic hinge development, aplastic analysis must be run both for the rigid frame and for the sway frame. Plasticanalysis gives cr
-
7/27/2019 Design of a Multi-storey Steel Structure
11/15
Definition of plastic hingesfor columns (P-M)
-
7/27/2019 Design of a Multi-storey Steel Structure
12/15
-
7/27/2019 Design of a Multi-storey Steel Structure
13/15
Distribution of the bending moment on the beam in the stage of I plastic hinge
-
7/27/2019 Design of a Multi-storey Steel Structure
14/15
-
7/27/2019 Design of a Multi-storey Steel Structure
15/15