Directional Airflow
What, Where, & When?
J. Paul Jennette, MS, PE, RBPDirector of Biocontainment OperationsCornell College of Veterinary Medicine
![Page 2: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/2.jpg)
The Purpose of Directional AirflowTo mitigate the risk of airborne contaminants being released from a high-containment laboratory, as a fundamental component of the laboratory’s (secondary) barrier function.
“mitigate”“secondary”
![Page 3: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/3.jpg)
What is Directional Airflow?Directional Airflow is *not*the same as Differential Pressure
![Page 4: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/4.jpg)
Airflow and DP
Q2
DP =(2610*A)2
DP = differential pressure (inches of water) Q = air flow (cfm) A = total leak area (square feet) 2610 = conversion factor
- ASHRAE Handbook of Fundamentals
![Page 5: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/5.jpg)
Where Can We Have Directional Airflow?
• Within Rooms• Between Rooms• Across the Whole
Facility
WHO Biosafety Manual 3rd Ed., 2004
![Page 6: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/6.jpg)
Where Can We Have Directional Airflow?
ante
support
culture
corridor
culture
![Page 7: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/7.jpg)
When Do We Need Directional Airflow?
(Note that “secondary barrier” implies the context for this question - that the lab is occupied, and that the directional airflow is not the first line of defense)
• Normal, steady state, conditions-?• Upset conditions-?
– External– Internal
![Page 8: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/8.jpg)
External Upset: Airflow Reversal• Power failure &
transition to backup generator
• Exhaust Fan failure & transition to backup fan
![Page 9: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/9.jpg)
External Upset: Airflow Reversal
![Page 10: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/10.jpg)
Airflow Reversal Testing
![Page 11: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/11.jpg)
Airflow Reversal – Before Tuning
![Page 12: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/12.jpg)
Airflow Reversal – After Tuning
![Page 13: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/13.jpg)
Internal Upset: Aerosol Release
• Equipment Failure
• Accident
• (Bad Behavior)
![Page 14: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/14.jpg)
Aerosol Release Testing, 1
![Page 15: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/15.jpg)
Aerosol Release Testing, 2
![Page 16: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/16.jpg)
Aerosol Release Testing, 3
ante
corridor
Xsupport
culture
![Page 17: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/17.jpg)
Coincident Events for High Risk
• External Upset:
Airflow Reversal + Internal Upset
• Internal Upset:
Internal Upset + Open Door
![Page 18: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/18.jpg)
Relative Probabilities
![Page 19: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/19.jpg)
• External Upset:
(Airflow Reversal) (Internal Upset)
• Internal Upset:
(Internal Upset) (Open Door)`
Relative Probabilities
![Page 20: Directional Airflow - The Eagleson Institute · 2019. 7. 25. · The Purpose of Directional Airflow To mitigate the risk of airborne contaminants being released from a high-containment](https://reader033.vdocument.in/reader033/viewer/2022060907/60a16a7d82f9a5003e5df9ed/html5/thumbnails/20.jpg)
ResponseAt Cornell, we:1. Design and control containment HVAC systems
based on airflow offsets at critical doorways2. Verify containment performance by using smoke or
fog to test directional airflow at critical doorways3. Include multiple door transitions in designs4. Train containment lab users to open doors
efficiently5. Avoid lead/lag fan redundancy6. Tune our HVAC systems to minimize reversals