Electrical Failure
InvestigationsPresented byPresented by
Ashley HarknessAshley Harkness
![Page 2: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/2.jpg)
Forensics, the Mystery
• Our Forensics Work
• Project Examples
![Page 3: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/3.jpg)
Why Do Things Fail?
![Page 4: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/4.jpg)
Because of...• Installation
• Application
• Operation
• Maintenance
![Page 5: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/5.jpg)
What we will look at...
• When the installer does it wrong…
• When the unexpected happens...
• When the design has problems...
• When People get involved…
![Page 6: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/6.jpg)
Poor Installation...
First:
![Page 7: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/7.jpg)
A High Voltage Bushing
• 27 KV bushing installed on a commuter train system.
• Steamed and Smoked when energized.
• Client wanted to know: What happened.
![Page 8: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/8.jpg)
Manufacturer’s Information
• Cut the Cable• Strip off insulation• Strip away insulation
shield• Wrap tape stress cone• Attach top connector• Assemble components• Fill with sealant
![Page 9: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/9.jpg)
The first step: X-ray the Sample
![Page 10: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/10.jpg)
What the X-ray revealed:
• The connector had not been properly soldered.
• The conductor strands were clearly visible.
![Page 11: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/11.jpg)
![Page 12: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/12.jpg)
How bad was the connection?
![Page 13: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/13.jpg)
It was not the only problem!
• Question: Where did the steam come from?
• Further investigation showed a second problem.
![Page 14: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/14.jpg)
The cable seal was improper.
The seal is in the wrong place.
![Page 15: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/15.jpg)
The Correct Seal Position
The seal is against the outer jacket material.
![Page 16: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/16.jpg)
The Report:
• The poor connection caused heat and steam.• The improper seal allowed water to
penetrate the bushing.• This was caused by poor workmanship.
![Page 17: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/17.jpg)
Next Example:
Contractor: “It’s bad equipment!”
Manufacturer: “Poor workmanship!”
Owner: “Help!”
![Page 18: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/18.jpg)
![Page 19: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/19.jpg)
Arcing between phases
![Page 20: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/20.jpg)
Mfg. Limits:
![Page 21: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/21.jpg)
Conclusion:
• Improper installation
![Page 22: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/22.jpg)
“Well, we had a limited budget…”
Let’s take another example..
![Page 23: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/23.jpg)
![Page 24: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/24.jpg)
![Page 25: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/25.jpg)
![Page 26: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/26.jpg)
![Page 27: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/27.jpg)
![Page 28: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/28.jpg)
Conclusion:
• Mismatch of equipment• Poor installation
![Page 29: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/29.jpg)
Something “Off the Wall”...
Weird ones:
![Page 30: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/30.jpg)
An Airport Maintenance Facility in Texas
![Page 31: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/31.jpg)
The Problem:
• Blow-outs between A Phase and Ground• Several in the first months of installation.• No previous history of such faults.• Was it bad product?• Was it bad installation?• What was the cause?
![Page 32: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/32.jpg)
Power Bus Duct
• Reduced impedance.
• Reduced cost.• Increased inherent
strength.• Manufacturing
simplicity.• Reliable.
![Page 33: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/33.jpg)
Buss Duct End View
![Page 34: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/34.jpg)
Fault Tree
![Page 35: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/35.jpg)
Insulation Porosity
![Page 36: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/36.jpg)
The Report:
• Rain water entered the product.• Insulation porosity was present.• The installation was correct.• The product was properly produced.• The transportation was incorrect.
![Page 37: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/37.jpg)
A defective product.
Undetected, until suspicions were aroused
Another weird one:
![Page 38: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/38.jpg)
The Problem:
• The installing splicersdid not like the cable.
• Client wanted it tested to Specifications.
![Page 39: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/39.jpg)
5 KV Cable Sample
![Page 40: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/40.jpg)
Suspicious gaps in the strand shield system.
![Page 41: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/41.jpg)
Close-up of the defect.
• The strand shield had separated during extrusion.
• The mark did not follow the strands.
• A longitudinal impression was present.
![Page 42: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/42.jpg)
The Culprit
• A cut-off knife caused the gash in the conductor stranding.
![Page 43: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/43.jpg)
The Report:
• A manufacturing defect was found.• The life of the cable had been shortened. • The manufacturer offered the client an
extended warranty.
![Page 44: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/44.jpg)
There was no fault!
–A Different Type of Case:–A Critical Area—EDP–The Fuse Blew!–The mystery…
![Page 45: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/45.jpg)
![Page 46: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/46.jpg)
![Page 47: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/47.jpg)
Melted element
![Page 48: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/48.jpg)
Intact Elements
![Page 49: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/49.jpg)
Mechanical Fractures
![Page 50: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/50.jpg)
Hey, wait a minute...
• Earlier testing records noted this fuse--
• One fuse had high resistance
• Replacement had not been done
![Page 51: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/51.jpg)
Conclusion:
• Work hardened elements fractured• Fuse opened on less than full load
• Operation and Maintenance Issue• Preventable Outage
![Page 52: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/52.jpg)
TIME OUT!
How do you know that?
![Page 53: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/53.jpg)
The Forensic Process...
• Things we know:
• Arc Behavior• Fire Directions • Expected Performance
• Things we Learn:
• Circuit Loading• Environmental Factor• Discovery
– Inspection– Testing
![Page 54: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/54.jpg)
The Fault Tree
• Initiating Event• Failure Mechanism• Findings
– Test, inspections, measurements• Conclusion:
– Not Likely Cause– Most Probable Cause
![Page 55: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/55.jpg)
![Page 56: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/56.jpg)
A Design Problem:
•“Well, I’m not sure what the load is...”
![Page 57: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/57.jpg)
Why did it fail?
Better question:
What is it?
![Page 58: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/58.jpg)
![Page 59: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/59.jpg)
Conclusion:
• Bus Overload– 4000 Amp Bus– 5000 Amp Load!
– Application
![Page 60: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/60.jpg)
The Human Factor...
And then:
![Page 61: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/61.jpg)
What People will do...
• Working “Hot”
![Page 62: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/62.jpg)
“I don’t need no stinking safety procedures.”
“Hey, loan me your wiggie.”
![Page 63: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/63.jpg)
![Page 64: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/64.jpg)
![Page 65: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/65.jpg)
![Page 66: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/66.jpg)
![Page 67: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/67.jpg)
![Page 68: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/68.jpg)
Conclusion:
• Defective meter initiated fault• Poor Work Practices• Lack of Protective Equipment
![Page 69: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/69.jpg)
But we paid extra to
keep the power on !
(Human Factor)
![Page 70: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/70.jpg)
The Attorney's
Office
![Page 71: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/71.jpg)
480 Volt Generator
![Page 72: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/72.jpg)
![Page 73: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/73.jpg)
208 Volt Generator
![Page 74: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/74.jpg)
![Page 75: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/75.jpg)
Conclusion:
• Improper wiring of generator– No connected neutral or ground
– Metal Oxide Varistor could not withstand the voltage.
– Fire was result
![Page 76: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/76.jpg)
When maintenance goes wrong…”
“What’s this green wire for?”
“It’s only a street light!”
![Page 77: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/77.jpg)
![Page 78: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/78.jpg)
![Page 79: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/79.jpg)
![Page 80: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/80.jpg)
Conclusion:
• Poor Installation and Maintenance:– Water Damage– Pinched Wire– Not Grounded
• Child’s death:– She touched the energized light pole and a
grounded fence.
![Page 81: Electrical Failure Investigations · 2007. 4. 24. · Power Bus Duct • Reduced impedance. • Reduced cost. • Increased inherent strength. • Manufacturing simplicity. • Reliable](https://reader035.vdocument.in/reader035/viewer/2022071408/6100a74b8fd8bd34564d7b41/html5/thumbnails/81.jpg)
In Summary:
• Forensics finds the strangest things.– Poor Workmanship– Defective Product– Off-the-Wall Problems