Transcript
Page 1: FUSION MEDICAL AESTHETICS WHEELHOUSE IIjrj-projects.gswconst.biz/JustinSummarell/2018-02-01 (Thur) Fusion... · 1/2/2018  · exit light fixtures emergency/night light pendant mounted

VITREOUS CHINALAVATORYLADENAK-2214

72" U

U

UUUU

UUU

+42"

+42"

+42"

+42"

+42"

72"

+48"+48"+48"

PANEL 'E'

EXISTING RTU-2ON ROOF ABOVE

E-2,4

E-5

E-7E-8E-9E-10 E-12

E-11

E-13

E-15 E-14

E-16

WH-1

IWH-1

E-6

E-21,23

E-22,24WITH #8

72"72"

103B

PATIENT ROOM

103C

PATIENT ROOM

103D

PATIENT ROOM

103A

STORAGE

103G

RECEPTION

103E

LAB

103F

PATIENT ROOM

WITH#10

MIC

ICE

DW

VITREOUS CHINALAVATORYLADENAK-2214

F

E E E

E

E

E E E E E E E

E

E

E E

E

J

J

EE

E E

E

E

E

EEE

K

E

L

M

E

E

E

E

E

E

E

E

E

(R)

E-17

E-19

LV LV LV103B

PATIENT ROOM

103C

PATIENT ROOM

103D

PATIENT ROOM

103A

STORAGE

103G

RECEPTION

103E

LAB

103F

PATIENT ROOM

VS

LV

LV

1

E-181

1

Drawn

Approved

Project No.

Date

17211.00

28

08

F

airm

ou

nt S

tre

et, S

uite

3

00

Da

lla

s, T

exa

s 7

52

01

| 2

14

.3

03

.1

50

0

33

00

W

est 7

th

S

tre

et, S

uite

1

10

Fo

rt W

orth

, T

exa

s 7

61

07

| 8

17

.3

03

.1

50

0

RevisionDateNo.

FU

SIO

N M

ED

IC

AL

A

ES

TH

ET

IC

S

WH

EE

LH

OU

SE

II

2625 W

HIT

MO

RE

S

TR

EE

T

FO

RT

W

OR

TH

, T

X 76107

BHB PROJECT #

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116

[email protected] • 817.338.1277 • bhbinc.com

TBPE Firm #44 • TBPLS FIRM #10011300

2017.013.095

01

POWER PLAN

SCALE: 1/8" = 1'-0"

PLAN NORTHTRUE NORTH

02

LIGHTING PLAN

SCALE: 1/8" = 1'-0"

PLAN NORTHTRUE NORTH

MSBPANEL "E"

NF NON-FUSIBLE (DISCONNECT)

30/3/25 DISCONNECT SIZE / POLES / FUSE SIZE

MC MECHANICAL CONTRACTOR

EC ELECTRICAL CONTRACTOR

1.2.3.4. SOME OF THESE SYMBOLS AND ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.

GROUND FAULT CIRCUIT INTERRUPTING

ABOVE FINISHED FLOORAFF

GFI

ALL LIGHT FIXTURES ON LIGHTING PLANS ARE TYPE 'A' UNLESS NOTED OTHERWISE.

CONDUIT W/ ONE PHASE, ONE NEUTRAL AND ONE GROUND

WHEN NO HASH MARKS ARE SHOWN, PROVIDE ONE PHASE, ONE NEUTRAL AND ONE GROUND CONDUCTOR.LETTER ADJACENT TO FIXTURE DENOTES FIXTURE TYPE. REFER TO FIXTURE SCHEDULE.

NOTES:

WP

*

ELECTRICAL SYMBOL LIST

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

WEATHERPROOF

CEILING MOUNTED VACANCY SENSOR

CEILING MOUNTED OCCUPANCY SENSOR

DATA OUTLET/POINT OF SALE OUTLET WITH 3/4" C STUBBED INTO CLG

TELEPHONE OUTLET WITH 3/4" C STUBBED INTO CLG

JUNCTION BOX

SPECIAL PURPOSE RECEPTACLE

GFI RECEPTACLE, WP FOR ALL OUTDOOR LOCATIONS

DUPLEX RECEPTACLE

MOUNTED ABOVE COUNTER

NON-FUSED DISCONNECT SWITCH

MOTOR

GROUND

CONDUIT W/ ONE GROUND, 3 PHASE & ONE NEUTRAL

CONDUIT AND HOMERUN TO PANEL - NOTE 2

208/120 V PANELBOARD

MOTOR RATED SWITCH

LOW VOLTAGE SWITCH

THREE WAY SWITCH

SINGLE POLE SWITCH

EMERGENCY LIGHTING UNIT WITH 2 LAMPS

EXIT LIGHT FIXTURES

EMERGENCY/NIGHT LIGHT

PENDANT MOUNTED LIGHT FIXTURE

TRACK LIGHT FIXTURE

LED LIGHT FIXTURE - REFER TO NOTE 1

FUSED DISCONNECT SWITCH

03

RISER DIAGRAM

SCALE: NTS

ELECTRICAL SPECIFICATIONS:1. PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL CODES AND CODE AUTHORITIES.

2. SUBMIT SHOP DRAWINGS FOR ALL MATERIAL FURNISHED UNDER THIS DIVISION OF WORK. PROVIDE A MINIMUM OF SIX COPIES.

3. SECURE AND PAY FOR ALL NECESSARY PERMITS, LICENSES AND INSPECTIONS REQUIRED BY LAW FOR THE COMPLETION OFTHE WORK. SECURE AND PAY FOR ALL CERTIFICATES OF APPROVAL THAT ARE REQUIRED AND DELIVER THEM TO THEARCHITECT BEFORE FINAL ACCEPTANCE OF THE WORK.

4. IDENTIFY ELECTRICAL EQUIPMENT USING LAMINATED THREE-PLY, ENGRAVED, PLASTIC NAMEPLATES WITH BLACK SURFACEAND WHITE INTERIOR CORE, AT LEAST 1/16 INCH THICK. ATTACH NAMEPLATES USING CHROMIUM PLATED SCREWS. PROVIDENAMEPLATES FOR PANELBOARDS, TRANSFORMERS AND DISCONNECT SWITCHES.

5. EXAMINE THE PROJECT SITE AND MAKE ALLOWANCES IN THE BID TO ACCOMMODATE EXISTING CONDITIONS.

6. ALL MATERIAL SHALL BE NEW, UL LISTED, AND FREE FROM DEFECTS, UNLESS EXISTING MATERIAL IS SPECIFICALLY SHOWN TOBE REUSED. INSTALL ALL MATERIAL IN ACCORDANCE WITH GOOD WORKMANSHIP STANDARDS.

7. SUBSTITUTIONS OF SPECIFIED MATERIAL SHALL BE APPROVED IN WRITING BY THE ARCHITECT PRIOR TO BIDDING.

8. PROVIDE FACTORY FINISH ON ALL MATERIAL FURNISHED TO THE JOBSITE AND TOUCH UP FINISHES WHICH HAVE BEENDAMAGED.

9. PROVIDE TYPEWRITTEN DIRECTORIES IN ALL NEW PANELBOARDS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR EXISTINGPANELBOARDS IN WHICH THE LOADS SERVED HAVE BEEN CHANGED BY THE SCOPE OF THIS PROJECT.

10. PROVIDE A COPY OF AS-BUILT PLANS TO THE OWNER UPON COMPLETION OF PROJECT.

11. MAINTAIN OPERATIONS OF ALL BUILDING SYSTEMS DURING CONSTRUCTION. COORDINATE ALL SHUTDOWNS OR SYSTEMDISRUPTIONS WITH OWNER SEVEN DAYS IN ADVANCE.

12. USE EMT CONDUIT WITH SET-SCREW TYPE FITTINGS AND INSULATED BUSHINGS, 3/4 INCH MINIMUM, FOR INTERIOR,CONCEALED WORK AND EXPOSED WORK ABOVE SWITCH HEIGHT.

13. USE RIGID GALVANIZED STEEL CONDUIT FOR EXPOSED WORK BELOW SWITCH HEIGHT.

14. USE SCHEDULE 40 PVC CONDUIT, 3/4 INCH MINIMUM, FOR ALL UNDERGROUND WORK. PROVIDE PVC COATED, RIGIDGALVANIZED STEEL BENDS.

15. USE 4" SQUARE (MINIMUM) GALVANIZED STEEL OUTLET BOXES.

16. USE COPPER CONDUCTORS, TYPE THHN INSULATION, OR APPROVED EQUAL. USE SOLID CONDUCTORS FOR #10 AWG ANDSMALLER AND STRANDED CONDUCTORS FOR #8 AWG AND LARGER. ALUMINUM CONDUCTORS ARE NOT ACCEPTABLE.

17. PROVIDE CONNECTIONS TO ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT AND BY OTHER DIVISIONS OF THE WORK.MAKE ALL CONNECTIONS AS RECOMMENDED BY THE MANUFACTURER AND AS REQUIRED BY APPLICABLE CODES.

18. CONNECT ALL MOTORS AND TRANSFORMERS WITH FLEXIBLE CONDUIT SUCH THAT VIBRATION IS NOT TRANSMITTED TO THESTRUCTURE. USE LIQUID TIGHT FLEXIBLE CONDUIT IN DAMP AND WET LOCATIONS.

19. MAKE SPLICES AND PROVIDE WORK AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO EXISTING DEVICES AND EQUIPMENTTO REMAIN IN SERVICE.

20. REMOVE ALL EXISTING CONDUCTORS, CABLES AND EXPOSED CONDUIT RENDERED UNUSED BY THE SCOPE OF THIS PROJECTBACK TO THE SOURCE OF SUPPLY.

21. PROVIDE SPECIFICATION GRADE WIRING DEVICES EQUAL TO HUBBELL 1221 FOR SWITCHES AND HUBBELL 5262 FORRECEPTACLES. PROVIDE COVERPLATES FOR ALL WIRING DEVICES AND COMMUNICATIONS OUTLETS. INSTALL RECEPTACLESAT +18 INCHES AND SWITCHES AT +48" UNLESS NOTED OTHERWISE. INSTALL DEVICES IDENTIFIED WITH AN "*" SIX INCHESABOVE THE COUNTER BACKSPLASH.

22. PROVIDE FUSIBLE CLASS "R" DISCONNECT SWITCHES OF AMPERE RATING AS REQUIRED OR AS NOTED ON THE DRAWINGS.FURNISH HEAVY DUTY, QUICK MAKE, QUICK BREAK, THREE PHASE, THREE POLE SWITCHES. USE NEMA 1 ENCLOSURESINDOORS AND NEMA 3R ENCLOSURES OUTDOORS. DISCONNECT SWITCHES SHALL BE OF THE SAME MANUFACTURER AS THEPANELBOARDS.

23. FUSES SHALL BE CURRENT LIMITING, WITH 200,000 R.M.S. SYMMETRICAL AMPERES INTERRUPTING RATING AND SHALL BE ULLISTED. ALL FUSES SHALL BE OF THE SAME MANUFACTURER. FUSES 600 AMPERES AND SMALLER SHALL BE CLASS RK1, DUALELEMENT EQUAL TO BUSSMANN LPS-RK. FUSES IN MOTOR CIRCUITS SHALL BE SIZED AS FOLLOWS: FUSES FOR NOT LESSTHAN 1.15 SERVICE FACTOR MOTORS SHALL HAVE AN AMPERE RATING 125 PERCENT OF MOTOR FULL LOAD CURRENT ORNEXT HIGHER FUSE RATING. FUSES FOR 1.0 SERVICE FACTOR MOTORS SHALL HAVE AN AMPERE RATING 115 PERCENT OFMOTOR FULL LOAD CURRENT OF NEXT HIGHER FUSE RATING.

24. CIRCUIT BREAKERS SHALL BE BOLT-ON THERMAL MAGNETIC TYPE WITH NUMBER OF POLES AND AMPERE RATING AS SHOWNON PLANS. CIRCUIT BREAKERS SHALL BE CAPABLE OF INTERRUPTING THE FAULT CURRENT AVAILABLE TO THEM WITHOUTTHE USE OF SERIES CONNECTED RATINGS WITH UPSTREAM CIRCUIT BREAKERS.

25. PROVIDE A GROUND SYSTEM THAT INCLUDES ALL CONNECTIONS AND TESTING OF: GROUND RODS, GROUND CABLES,GROUND BUSES, CONDUITS, FITTINGS, ANCHORS, SUPPORTS, AND OTHER MATERIALS AS REQUIRED FOR A COMPLETEINSTALLATION.

26. ALL TELEPHONE AND DATA SYSTEMS CONDUITS ARE ONE INCH UNLESS NOTED OTHERWISE.

27. PROVIDE PANELBOARDS WITH FLUSH ENCLOSURE, HINGED LOCKABLE DOOR, COPPER BUSING, FULL SIZE NEUTRAL BUS ANDA GROUND BUS. PROVIDE PANELBOARDS WITH AN INTERRUPTING RATING AS INDICATED ON PLANS. PROVIDE CIRCUITBREAKERS WHICH SIMULTANEOUSLY OPEN ALL POLES ON DOUBLE AND THREE POLE CIRCUIT BREAKERS. PROVIDE SINGLEPOLE CIRCUIT BREAKERS SERVING FLUORESCENT LIGHTING LOADS WITH SWD MARKING. PROVIDE PANELBOARDS ASMANUFACTURED BY GENERAL ELECTRIC, SIEMENS OR SQUARE D.

VACANCY SENSOR SWITCH

CEILING MOUNTED DAYLIGHT SENSOR

CEILING MOUNTED POWER PACK

DUPLEX RECEPTACLE WITH USB PORTU

UNDERCABINET LED LIGHTING

CEILING MOUNTED SPEAKER

3#4/0,1#4G.,2 1/2"C.

NOTES BY SYMBOL " " 1. PROVIDE CIRCUIT WITH 500W CURRENT LIMITER.

2. PROVIDE A NEW 225/2 CIRCUIT BREAKER IN EXISTING MAIN PANELTO SERVE PANEL "E".

(EXISTING)

01.15.2018

FLOOR PLANS

ELECTRICAL

E1.0

MA

CP

01/15/2018

Top Related