GeneralSpecifications
GX60I/O Base Unit (Expandable I/O)GX90EXExpansion Module
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
GS 04L53B00-01EN
GS 04L53B00-01EN©Copyright April 2014
10th Edition May. 31, 2021
OVERVIEWGX60 I/O Base Unit (Expandable I/O)The GX60 provides a function to expand an I/O module for recording and controlling, when it is connected to the expansion module that is connected to the GX10/GX20/GP10/GP20/GM using a LAN cable via a private communication network.
● OneGX60caninstalluptosixI/Omodules.● Uptosixunitscanbeadditionallyconnectedto
the GX/GP/GM.● ThecommunicationdistancebetweentheGX/
GP/GM and GX60 or between GX60s can be extendedbyupto100musingaLANcable.
* WhenthemeasurementmodeontheGX/GP/GM is High speed, expandable I/O units cannot be installed in the GX/GP/GM.
GX90EX Expansion ModuleThe expansion module is installed in the GX10/GX20/GP10/GP20, GX60, GM main unit, and GM sub unit.[IfGX90EXexpansionmoduleisinstalledintheGX/GPor I/O base unit]
● Theexpansionmodule,whichissupportedbythe GX/GP and GX60, enables a connection betweenGX/GPandGX60oracommunicationbetween GX60s.
● AdistributedarrangementwiththedatatimesynchronizationsecuredisprovidedbyconnectingExpansionmodulesinstalledintheGX/GPmainunitandGX60usingaLANcable.
● Dataistransferredtothehigh-orderGX/GPviatheexpansionmodule.
[IfGX90EXexpansionmoduleisinstalledintheGMmainunit/subunit]
● Theexpansionmodule,whichissupportedbytheGMmainunitandsubunit,enablesaconnectionbetweenGMmainunitandsubunitoracommunicationbetweensubunits.
● AdistributedarrangementwiththedatatimesynchronizationsecuredisprovidedbyconnectingExpansionmodulesinstalledintheGMmainunitandsubunitusingaLANcable.
● Dataistransferredtothehigh-orderGM10viatheexpansionmodule.
GX90EX
GX60 Power inlet type
Power Screw type
-
2
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00
GX60 SPECIFICATIONSModule Installation
• I/Omodule:Max.6modules(Slots0to5) Modules that can be installed PleaserefertotheGeneralSpecificationsofthe
GX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YA I/O Modules (GS 04L53B01-01EN) and GX90UTPIDcControlModule(GS04L53B01-31EN).
Restrictions:Expansionmodule:1module(expansion
moduleslot“EXT”)Forotherlimitations,seetheGX10/GX20
Paperless Recorder (Panel Mount Type) GeneralSpecifications(GS04L51B01-01EN).
Names of Channels• ThemoduleinstalledintheGX60hasachannel
namethatconsistsoftheunitnumber,slotnumber,andchannelnumber.
012345
Channel name
Unit number
Slot number
Channel numberI/O modules
Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06Digital input/output: DI 01 to 08
DO 09 to 14
Slot number; 0 to 5Unit number; 1 to 6
Pulse input: 01 to 10 Analog output: 01 to 04PID control, input/output: 01 to 26
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
CSA-C22.2 No. 61010-2-030, CAN/CSA-C22.2 No.61010-2-201 *4, OvervoltageCategoryII *1,PollutionDegree2 *2, MeasurementCategory *3
• UL: UL 61010-1, UL Std. No. 61010-2-030, UL 61010-2-201 *4 (CSA NRTL/C),
OvervoltageCategoryII *1,PollutionDegree2 *2, MeasurementCategory *3
• CE/EMCdirective: EN 61326-1 Class A Table 2 (For use in
industriallocations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective: EN 61010-1, EN 61010-2-030,
EN IEC 61010-2-201 *4 compliant OvervoltageCategoryII *1,PollutionDegree2 *2,
MeasurementCategory *3• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategoryII: Describesanumberwhichdefinesatransient
overvoltagecondition. Impliestheregulationforimpulsewithstand
voltage. “II”appliestoelectricalequipmentwhich
issuppliedfromthefixedinstallationlikeadistribution board.
*2 PollutionDegree2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 MeasurementCategory: Dependsonthespecificationofeachmodules.*4 Thisproductisdesignedasopenequipment
undertherelevantstandard,installitasfollows: • Install the GX60 in a panel with a door. •Theinstrumentationpanelorpanelusedfor
supportmustcomplywithCSA/UL/EN61010-2-201ormustbeatleastIP1X(degreesofprotection) and at least IK09.
-
3
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material:Polycarbonate,aluminumalloy• Color;
Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:412.5mm(W)x164.7mm(H)x127.8mm(D)
• Weight:Approx.3.2kg(installing6modules)
Power Supply• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,
180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Powerconsumption:
Supply voltage Normal operation *
Maximum
100VAC 20VA 40VA
240VAC 30VA 55VA
* Whenusing6analoginputmodules.• Allowableinterruptiontime:Lessthan1cycleof
thepowersupplyfrequency
Isolation• Insulationresistance:Betweeneachinsulation
terminals,andearth:20MΩorgreaterat500VDC
• Withstandvoltage: Betweenthepowerterminalandearth:3000VACat50/60Hzforoneminute
Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.
• Grounding:Besuretosetalowgroundingresistance.
• Isolation:
Power terminal
The circuits divided by lines are insulated mutually.
Internal circuit
Input and output module terminal
Input and output module internal circuitEarth (PE) terminal
External DimensionsPowerscrewterminaltype
127.8 (5.03)
148
(5.8
3)
412.5 (16.2)162 (6.38)48 156 (6.14)
164.
7 (6
.48)
6-Φ5 hole(1.89)
8.7
(0.3
4)
(6-Φ0.2) hole
Power inlet type
127.8 (5.03)
148
(5.8
3)
412.5 (16.2)162 (6.38)48 156 (6.14)
8.7
(0.3
4)
164.
7 (6
.48)
6-Φ5 hole(1.89)(6-Φ0.2) hole
Withmodules
147 (5.79)
48(1.89)
412.5 (16.2)162 (6.38)156 (6.14)
6-Φ5 hole(6-Φ0.2) hole
148
(5.8
3)
164.
7 (6
.48)
8.7
(0.3
4)
-
4
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00
185±
0.4
(7.2
8±0.
0157
)
162±0.2(6.38±0.0078)
156±0.2(6.14±0.0078)
6-Φ4.5 hole or M4
Dimensions of fixing hole
(0.24-Φ0.18) hole or M4
148±
0.4
(5.8
3±0.
0157
)
Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).
Normal Operating Conditions• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(However,less
thanmoisturecontentof40°C80%RHat40°Cormore),Nocondensation
• Magneticfield:400A/morless(DCand50/60Hz)
• Vibration: 5≤f<8.4Hzamplitude3.5mm(peak)
8.4≤f≤160Hzacceleration9.8m/s2 or less• Shock(IEC-60068-2-27):
Non-energization,500m/s2orless,approximate10ms,6directions(±X,±Y,±Z)
• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontalwheninstallingthepanelmountandwallmount.
• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower
on
Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged
condition)
Effects of Operating Conditions• Powersupplyvariation:Shallsatisfythe
accuracyspecificationintherangeof90to132VACor180to250VAC(frequency:50/60Hz).Powersupplyfrequencyfluctuation:Shallsatisfytheaccuracyspecificationintherangeofratedsupplyfrequency+/-2Hz(power-supplyvoltage:100VAC).
GX90EX SPECIFICATIONSCommunication Functions CommunicationbetweenGX/GPandGX60,
betweenGX60s,betweenGMmainunitandsubunit,betweenGMsubunitsviadedicatedcommunicationnetwork.• Baudrate:10Base-T/100Base-TX(Auto)*1• Numberofports:2• Connectioncable:STPcable,CAT5orgreater• Inter-moduleconnection:Cascadeconnection
(Ring connection is disabled.)• Maximumcommunicationdistance:100m*2• Connector:RJ-45*1Canbefixedto10Base-TbyDIPswitchsettings.*2DistanceextensionthroughHUBconnectionor
LAN repeaters is not possible.
Display Functions• SystemstatusLEDindicators: RDY(green):LightsupwhentheCPUisrunning
normally. MAIN(green):Turnsoninmastermodeandoff
inslavemode. FAIL(red):Lightsupwhenasystemerror
occurs.• 7-segmentLEDindicator:Indicatesaunit
numberoroperationerror.• EthernetstatusindicatorLED:LINKACT(green),
SPEED(orange)
Address Setting Functions Switchsettings:
Switch No. Descriptions1 Forunitnumbersetting
2
3
4
5 -
6 -
7 10 Mpbs/100 Mbps switching
8 MASTER/SLAVEswitching
Master / Slave FunctionsCanbesettomastermode(wheninstalledintheGX/GPorGMmainunit),orslavemode(wheninstalledintheGX60orGMsubunit)usingtheDIPswitches.
10 Mbps Fixed ModeCanbesettothe10MbpsfixedmodeusingtheDIPswitches.
MountingCanbemountedintheGX/GP,GX60,GMmainunit,and GM sub unit.• Mountingposition: GX10/GP10:Slot2 GX20/GP20:Slot9 GX60:EXTslot GMmainunit:Leftmostposition GMsubunit:Nexttothepowersupplymodule
-
5
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
OvervoltageCategoryIIorI *1,PollutionDegree2 *2• UL: UL 61010-1 (CSA NRTL/C),
OvervoltageCategoryIIorI *1,PollutionDegree2 *2• CE/EMCdirective: EN 61326-1 Class A Table 2 (For use in
industriallocations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective EN61010-1compliant,
OvervoltageCategoryIIorI *1,PollutionDegree2 *2• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategory: Describesanumberwhichdefinesatransient
overvoltagecondition. Impliestheregulationforimpulsewithstand
voltage. IIorIdependsonthepowersupplyspecification
oftheGX/GPmainunit,GMmainunitorsubunit.*2 PollutionDegree2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material:Polycarbonate• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:45.2mm(W)x111mm(H)x107.1mm(D)(D:includingterminalcover)
• Weight:Approx.0.18kg
Power Supply SuppyfromGX/GP,GX60expandableI/O,or
GM90PSpowersupplymodule.• Powerconsumption:1.8Worless
External DimensionsUnit: mm (approx. inch)
45.2(1.78)
107.
1
3(0.
12)
8(0.
31)1
00(3
.94)
31.9
82.1
(3.2
3)Normal Operating Conditions
Fornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):ThisGeneral
SpecificationsGMSpecifications:GS04L55B01-01EN
Transport and Storage Conditions• Ambienttemperature:–25to70°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged
condition)
Effects of Operating Conditions None
-
6
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00
MODEL AND SUFFIX CODESMODEL and SUFFIX Code (GX60)
Model Suffix Code DescriptionGX60 I/O Base UnitType -EX I/O ExpansionArea N GeneralPower supply 1 100VAC,240VACPower cord D Power cord UL/CSA standard
F PowercordVDEstandardR Power cord AS standardQ Power cord BS standardH Power cord GB standardN Power cord NBR standardW Screwterminal(M3)
*OneGX90EX(I/Oexpansionmodule)isprovided.MODEL and SUFFIX Code (GX90EX)
Model Suffix Code DescriptionGX90EX I/O Expansion ModulePort -02 2 portsType -TP1 Twisted Pair Cable- N Always NArea -N General
Standard AccessoriesProduct Qty
Power cord 1*
Stopper (Antiskid rubber) (A9088ZM) 2
* ExceptGX60powercordsuffixcode:W
Optional Accessories (Sold Separately)ThedummycoverisforemptyslotsonGX/GPandGX60.ThedummycoverisnotattachedtotheGX60whenshippedfromthefactory.Ifyouneedthedummycover,pleasepurchaseitseparately.
Product Part no.Dummycover B8740CZ
Test certificate (QIC, sold separately)When ordering the GX60, GX90EX gets its own QIC (one QIC per unit).Whenorderingtheexpansionmodulesseparately,eachmodulegetsitsownQIC(oneQICpermodule).
User's ManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL: www.smartdacplus.com/manual/en/Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.
•SMARTDAC+isregisteredtrademarksofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.