Final Geotechnical Exploration and
Evaluation Report
Gymnastic and Meeting Building
Florida
Date:- _____________
Prepared For
The Parks and Recreation Department of Relax City, Florida
-
8/10/2019 Geotechnical Report 02 Revised
2/20
Page | 1
The Parks & Recreation Department, Our Ref:
Relax City, Date:
Florida
Attn: The Manager
SUB: Final Geotechnical Exploration and Evaluation Report of Gymnastic and
Meeting Building, Near City Hall, Florida
Dear Sir,
We have the pleasure to submit our site investigation report on your proposed project at the
above site. This report includes field and laboratory test results in addition to our conclusions
and recommendations for design and type of foundation
We are happy to render our services upon your request and would like to thank you for your
confidence. Please do not hesitate to call on us for any assistance whenever needed.
Yours Faithfully,
(Student Name)
-
8/10/2019 Geotechnical Report 02 Revised
3/20
Page | 2
Table of Contents
1. INTRODUCTION 3
2. PURPOSE OF INVESTIGATION 3
3. SCOPE OF WORK 3
4. SITE DESCRIPTION 3
5. SUBSOIL CONDITIONS AND DESCRIPTION 4
6. FIELD TEST 4
7. DISCUSSION 5
8. FOUNDATION DESIGN CONSIDERATION 5
10. SUMMARY OF RECOMMENDATIONS 8
11. APPENDIX 8
-
8/10/2019 Geotechnical Report 02 Revised
4/20
Page | 3
1. INTRODUCTION
This report presents the field work and test results of geotechnical investigation of the proposed
site with the following information.
Client : The Parks and Recreation Department of Relax City Site area : 4,877 m
2
Project : Gymnastic and Meeting Building
Location : Florida
Height of building : 13.7 m
2. PURPOSE OF INVESTIGATION
The main purpose of this study is to determine the surface and subsurface conditions at the
proposed site and to define physical and mechanical properties of the foundation materials inaddition to specifying other engineering characteristics of the encountered strata. This is in
order to guide the designer to achieve an adequate and economic design of the foundation type,
shape and size.
3. SCOPE OF WORK
Geotechnical Investigation was made at the proposed site by drilling 05 (five) boreholes
numbered as given in the borehole location plan given in figure 01. The location of the site is
given on Location Plan.
Boreholes of 50 mm diameter were drilled down to 7.62 m from, the respective borehole levels,
using 63.5 kg weight. Drilling in soils was carried out by the Cable Tool Percussion method.
Sampling and subsequent laboratory testing were used to classify various soil strata.
Fieldwork was commenced on 16/03/2009 and was completed on 16/03/2009.
4. SITE DESCRIPTION
The proposed site covers an area of 4877 sq. meter. It is bordered three sides from buildings and
in front with existing roads. At the time of investigation, the site was highly undulating and was
vacant. There were not such differences among the ground levels at certain locations.
-
8/10/2019 Geotechnical Report 02 Revised
5/20
Page | 4
5. SUBSOIL CONDITIONS AND DESCRIPTION
The nature of subsurface as encountered by borehole drilling, described in accordance with
ASTM, is summarized below. A section through boreholes is presented on the borehole
correlation chart in appendix B figure 03 to 07.
Depth
Range (m)"N" Range Description
0.03 12-45 Brown silica sand with fragmented limestone
37 14 - 45 Fragmented limestone
Stratum # 1:In general the top stratum starts off below a thick cover of dense dark brown silica
sand consisting of sand mixed with fragmented limestone. The soil can in general be classified
as SP.
Stratum # 2: This stratum underlying stratum # 2 consists of tan fragmented limestone and
extends to the final depth explored. In borehole No 01 & 03, again tan sand with fragmented
limestone of depth 1.5 m is encountered. This stratum is rock and exists in a soft to medium
dense condition of compactness with SPT value ranging 14 to 40.
Groundwater: Ground water was encountered at depths ranging from 1.98-2.1 m below the
investigated ground level. Measurements of ground water levels were taken on the day
following the completion of fieldwork-
6. FIELD TEST
6.1. STANDARD FENETRATION TESTS
Standard penetration tests (SPT's) were conducted regularly at 15 cm intervals up to the
investigated depth in accordance with the drilling procedure specified in ASTM D-1586.
The test was carried out using a manual drop hammer assembly, which utilizes a manual trip
mechanism to release the weight all in accordance with ASTM D-1586. Results are presented
on borehole logs appendix B figure 03 to figure 09.
-
8/10/2019 Geotechnical Report 02 Revised
6/20
Page | 5
7. DISCUSSION
The proposed construction is Gymnastic and Meeting Building with approximate 13.7 m height.
Based on the type of structure and the soil conditions encountered, shallow foundations are
recommended.
The level survey reveals the following points;
The site was not so undulating and there were no significant differences among the existing
ground levels at certain locations as the ground levels.
There were zero differences of among the borehole levels as their levels of all the bore holes
depth are 7.62 m.
At the time of investigation, the following facts were observed:
In one of the boreholes drilled, the subsoil strata show presence of loose to medium dense
silica sand and gray concrete fill layers up to 0.61m below the investigated ground level.
These SPT values are coming within the load influence zone of shallow foundations and
limiting the bearing pressure values (which are evaluated based on both shear and settlement
criteria).
The ground water table was encountered at depths ranging from 1.98~2.1 m below the
investigated ground level.
8. FOUNDATION DESIGN CONSIDERATION
8.1. ALLOWABLE BEARING CAPACITY
There are many methods to calculate the allowable bearing pressures of the soil and there are
considerable variations in the values obtained by different methods and hence it is practically
impossible to fix a single value for a particular site for a given breadth and type of foundations
even after considering the same magnitude for factor of safety. This is because of the many
uncertainties in determining the allowable bearing pressure values. Based on our experience we
may be assigning different values for factor of safety for different areas and this will be a
minimum of 3.0 for shallow foundations.
-
8/10/2019 Geotechnical Report 02 Revised
7/20
Page | 6
Meyerhof Bearing Capacity Theory Based on Standard Penetration Test Values
Qu= 31.417(NB + ND) (kN/m2) (metric)
For footing widths of 1.2 meters or less
Qa= 11,970N (kN/m
2
) (metric)
For footing widths of 3 meters or more
Qa= 9,576N (kN/m2) (metric)
Where:
N = N value derived from Standard Penetration Test (SPT)
D = depth of footing (m) (ft), and
B = width of footing (m) (ft).
Taking into consideration the above described criteria the net allowable bearing pressure has
been calculated at 1 m depth below the existing ground surface. The recommended allowable
bearing pressure values in general are as follows:
Depth of
Foundation
Type of
Foundation
Least lateral
Dimension of
Foundation
Net Allowable
Bearing
Pressure
1 m Shallow Square 1.25 m 565 kN/m
The actual net bearing pressure value for any particular Isolated Square foundation can be seen
from Table 02.
9. ENGINEERING RECOMMENDATIONS
9.1. SHALLOW FOUNDATIONS CONSIDERING GROUND IMPROVEMENTS
The following lines shall be considered prior to placing shallow foundations:
http://www.geotechnicalinfo.com/geotechnical_glossary.htmlhttp://www.geotechnicalinfo.com/geotechnical_glossary.htmlhttp://www.geotechnicalinfo.com/geotechnical_glossary.htmlhttp://www.geotechnicalinfo.com/geotechnical_glossary.html -
8/10/2019 Geotechnical Report 02 Revised
8/20
Page | 7
Excavate the construction area up to a level 1 m and compact the excavated surface to not less
than 95% of the maximum dry density of the soil using a heavy vibratory roller.
Compaction tests shall be carried out for each compacted layer to confirm the
aforementioned percentages of compaction. Since excavation exceeds 1 m below the natural ground level, suitable side protection has to
be ensured during excavations, ground improvements and foundation placement works.
Since the ground water table was encountered at levels 2.1 m, dewatering may not be
necessary to be carried out to below the aforementioned excavation level.
Based on the above, allowable bearing pressures as given in table may be used for isolated
square footings of width 1.25 m, at 1 m above excavated and backfill compacted level.
Depth of
Foundation
Type of
Foundation
Least lateral
Dimension of
Foundation
Net Allowable
Bearing
Pressure
1 m Shallow Square 1.25 m 565 kN/m
These allowable bearing pressures are obtained using Meyerhof bearing capacity theory based
on "Estimating allowable bearing pressure for foundations in sand on basis of results of standard
penetration tests" and incorporates a factor of safety of at least 3 on the-ultimate bearing
pressure assuming ground water to rise to foundation level.
9.2. CONSTRUCTIONAL ASPECTS
We recommend the following measures for long-term stability of the structures.
As mentioned in the report the boreholes made were of 50.8 mm in diameter. The
information received from the limited number and the stipulated diameter of boreholes may
not represent the entire site and may not reveal all the weak layers or conditions especially
when they are localized. Hence no responsibilities can be born for conditions not revealed
by boreholes or trial pits made on the site. In case of any such findings we shall be contacted
immediately to arrange a site visit by our engineer to make an on-site study of such
conditions after which recommendations if it is deemed necessary will be revised.
-
8/10/2019 Geotechnical Report 02 Revised
9/20
Page | 8
In case ground improvements are necessary to be carried out, techniques suitable for any
particular site shall be selected in consultation with geotechnical engineer.
In case of any hard strata like the sandstone, siltstone or other rock types, use of special
excavators for excavations of such strata shall be considered.
Prior to providing foundation concrete, the foundation soil after excavation may be
thoroughly compacted before placing foundation concrete.
9.3. INSPECTION AND MONITORING
It is necessary that all the geotechnical aspects of foundation construction and earthwork be
monitored by competent construction supervision staff including qualified and experienced
engineers. For this purpose a comprehensive inspection and monitoring program should be
prepared.
10.SUMMARY OF RECOMMENDATIONS
10.1. TYPE OF FOUNDATION
Shallow foundation Isolated Square type with size 1.25 m x 1.25 m is selected and drawing is
attached
10.2. MINIMUM DEPTH OF FOUNDATION
Minimum depth of foundation should be 1 m below the existing ground level on well
compacted soil.
10.3. BEARING PRESSURE
The recommended allowable bearing pressure values in general are as follows:
Depth of
Foundation
Type of
Foundation
Least lateral
Dimension of
Foundation
Net Allowable
Bearing
Pressure
1 m Shallow Square 1.25 m 565 kN/m
11.APPENDIX
Tables
Bore Hole Logs figures
-
8/10/2019 Geotechnical Report 02 Revised
10/20
Page | 9
APPENDIX - A
TABLE-1
Empirical Values For , Qu, Drand Unit Weight Of Soils Based on The SPT
Soil Properties at depth 3 ft
Relative Density, Dr= 0.56
Standard Penetration Test value, N = 24
Approximate angle of internal friction, (degree) = 33.5
Approximate range of moist unit weight, y (pcf) = 124 Ib/ft3=1986 kg/m3
Submerged unit weight, sub= 67
-
8/10/2019 Geotechnical Report 02 Revised
11/20
Page | 10
Table-2
Calculation of Foundation Width
Let
B = 1.25 mD = 1 m
Meyerhof Bearing Capacity Theory Based on Standard Penetration Test Values
Qu= 31.417(NB + ND) (kN/m2) ------------(1) (metric)
Thus,
Qu= 31.417((24)(1.25) + (24)(1)) = 1696 kN/m2
Qa= QU =565 kN/m2 ----------(2)
F.S
Qa= 565 kN/m2
As column load for 1.25 m x 1.25 m square footing is 800 kN (180,000 lb) and stress applied is
800/1.62= 512 kN/m
2,thus Qa >565 lb/ft
2
-
8/10/2019 Geotechnical Report 02 Revised
12/20
Page | 11
APPENDIX - B
Figure -01
-
8/10/2019 Geotechnical Report 02 Revised
13/20
Page | 12
LEGENDS
Figure -02
-
8/10/2019 Geotechnical Report 02 Revised
14/20
-
8/10/2019 Geotechnical Report 02 Revised
15/20
Page | 14
Figure -04
-
8/10/2019 Geotechnical Report 02 Revised
16/20
Page | 15