Download - Grounding of Overhead Transmission Lines
![Page 1: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/1.jpg)
Experts Teaching from Practical Experience
Panel Paper 2010TD0683:
Grounding of
Overhead
Transmission Lines
William A. (Bill) Chisholm
Kinectrics / UQAC [email protected]
Emanuel Petrache, Kinectrics
Fabio Bologna, EPRI
2015 PES Annual Meeting
Lightning WG Meeting – Update to:
![Page 2: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/2.jpg)
Experts Teaching from Practical Experience
How Grounding
Affects Overhead
Groundwire
(OHGW) Protection
2010 IEEE T&D Expo
Panel Session on Lightning
Performance of Overhead Lines
![Page 3: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/3.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Dealing with Lightning Challenges
• Direct Stroke Termination
• Directly to the unshielded line
• To ground or an object near the line
• Grounding of the Stroke Current
• Into Normal Soil
• Across surface of High-Resistivity Soil
• Equalization of Potentials
• Electromagnetic coupling
• Surge arresters
![Page 4: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/4.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Stroke Incidence – Side View
![Page 5: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/5.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Stroke Incidence – Side View
OHGW Interception
![Page 6: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/6.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Stroke Incidence – Side View
V Ipk∙ Rf
Rf
Ipk
![Page 7: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/7.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Effectiveness of OHGW
W.A. Chisholm and J.G. Anderson, “Guide for Transmission Line Grounding: A Roadmap for Design, Testing, and Remediation”, EPRI, Palo Alto, CA:
2004. 1002021. Available: mydocs.epri.com/docs/public
![Page 8: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/8.jpg)
Experts Teaching from Practical Experience
Calculating
Low Frequency
Resistance Rf
using the “Chiz-
Whiz” Method
2010 IEEE T&D Expo
Panel Session on Lightning
Performance of Overhead Lines
![Page 9: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/9.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
Wire
ContactGeometricAF
A
LA
g
gRR ln
18.11ln
1
2
2
• Grounding of the Stroke Current
• Into Normal Soil of Resistivity (m)
• Split into “Geometric” and “Contact” Resistance
• Solid Disc, Ring have:
– SAME Geometric Resistance
– DIFFERENT Contact Resistance (Disc Rcontact 0)
![Page 10: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/10.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
Wire
ContactGeometricAF
A
LA
g
gRR ln
18.11ln
1
2
2
Resistivity (local soil near tower)
![Page 11: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/11.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
Wire
ContactGeometricAF
A
LA
g
gRR ln
18.11ln
1
2
2
Size (geometric radius)
![Page 12: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/12.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
Wire
ContactGeometricAF
A
LA
g
gRR ln
18.11ln
1
2
2
Shape Factor, pointy = larger
![Page 13: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/13.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
Wire
ContactGeometricAF
A
LA
g
gRR ln
18.11ln
1
2
2
Length of wire
![Page 14: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/14.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
Wire
ContactGeometricAF
A
LA
g
gRR ln
18.11ln
1
2
2
Fill Factor (F 2)
![Page 15: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/15.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
• Invited paper for Industry Applications, 2015
![Page 16: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/16.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Geometric and Contact Resistance
• Worked
example
shows
problem with
n rods in a
row formula
![Page 17: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/17.jpg)
Experts Teaching from Practical Experience
Changes in
Resistivity:
Region to Region,
Tower to Tower
2015 IEEE PES Annual Meeting
Lightning Working Group
![Page 18: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/18.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Rise Time Maps Ground Resistivity
![Page 19: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/19.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
FCC M3 Conductivity Map
2 mS/m = 500 m
4 mS/m = 250 m
8 mS/m = 125 m
15 mS/m = 67 m
![Page 20: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/20.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Soil Suitability for Ground Penetrating Radar
![Page 21: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/21.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Footing Resistance Statistics
• TVA carried out 10,600 measurements of
tower footing resistance in early 1990s.
500-kV towers had insulated overhead
groundwires.
For the most part, untreated with expectation
that Rf < 40 .
Analyzed with Pearson Classification.
![Page 22: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/22.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Pearson Classification, TVA Lines, Rf
![Page 23: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/23.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Pearson Classification, TVA Lines, ln Rf
![Page 24: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/24.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Recent Work in Portugal
• Campaign to test grounding of 150-kV, 220-
kV and 400-kV Footing Resistance
Made use of ABB 26-kHz meter
Summarized by Susana de Almeida de Graaff
![Page 25: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/25.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Portugal: REN Lines, ITU Conductivity (mS/m)
![Page 26: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/26.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Recent Comparison Work
• Measurements corrected for overhead
groundwire connection to adjacent structures
• TVA and REN data evaluated in similar ways
![Page 27: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/27.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Recent Comparison Work
• REN reported median 18.2 and ln Rf = 1.05
on a system-wide basis.
• TVA and REN data have similar (log-normal)
distributions of footing resistance with values of
standard deviation of ln(Rf) of 0.92 (TVA)
and 0.73 (REN), compared the same way on a
line-by-line basis.
• 2015 SIPDA XIII Invited Lecture has details
(28 September to 2 October 2015).
![Page 28: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/28.jpg)
Experts Teaching from Practical Experience
Conclusions
2015 IEEE PES Annual Meeting
Lightning WG Meeting
![Page 29: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/29.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Conclusions
• Footing resistance has an important effect on the performance of overhead groundwire protection.
• Simple formulas exist for relating the resistance of structures to the local soil resistivity.
• Several different ways exist to infer the soil resistivity in regions, but not on a tower-by-tower basis.
• Tower-by-tower variation of soil resistivity and footing resistance is very large.
![Page 30: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/30.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Conclusions
• Regions of similar size (TN, USA and Portugal), Similar numbers transmission of towers, Footing resistance data measured with earth resistance tester (TVA) or ABB 26-kHz meter (REN).
• On line-by-line basis, high skew and kurtosis, so data were not normally distributed.
• Transformation ln (Rf ) got rid skew and kurtosis.
• Footing resistance is log-normally distributed with wider value of standard deviation than peak current.
![Page 31: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/31.jpg)
Experts Teaching from Practical Experience
Questions
2015 IEEE PES Annual Meeting
Lightning WG Meeting
![Page 32: Grounding of Overhead Transmission Lines](https://reader034.vdocument.in/reader034/viewer/2022042503/586cb7081a28abc7348b59f5/html5/thumbnails/32.jpg)
IEEE PES Annual Meeting Denver CO Lightning WG Meeting [email protected] © 2015
Dr. William A. (Bill) Chisholm is a well-known expert in electric power reliability problems involving adverse weather including lightning, winter pollution and low wind conditions.
IEEE Fellow in 2007.
Led/leading IEEE Standards 1243 and 1410 for improving lightning protection of transmission and distribution lines.
Associate at Kinectrics (former Ontario Hydro Research Division) in Transmission and Distribution group.
Principal author of EPRI Transmission Line Reference (Red Book), 200 kV and Above, Chapter 6 (lightning protection) and main technical contributor to the upcoming Grey Book (lightning and grounding).
Spent 2007-2008 at the University of Quebec at Chicoutimi, co-writing a book for and teaching lightning protection.
Columnist (Transient Thoughts) for INMR Magazine.
About the Author