Growatt PCS500
Features
Growatt PCS500 battery inverter is designed forlarge volume storage system to
Bidirectional Battery Charger/Inverter
Touch Screen LCD
Flexible Battery Type(li-ion,lead-acid)
Comprehensive Protection for Inverter and Battery
Multiple Working Mode Presetable
Battery Forecast (discharge time, capacity, etc)
CAN and RS485 Communication Interface, Modbus Protocol
Seamless transfer between on and off grid(with optional ATS cabinet)
Flexible design, multiple inverters parallelable
GROWATT NEW ENERGY TECHNOLOGY Co.,LTD
A: No.28 Guangming Road, Longteng Community, Shiyan, Baoan District, Shenzhen, P.R.China.
T: + 86 755 2747 1900 F: + 86 755 2749 1460E: [email protected]
1.Firm unstable solar power to increase grid power quality
2.Increase the usage of solar energy and reduce grid electricity cost
3.Serve as back up power supply for local electrical equipments during grid power outage
4.Serve as temporary power supply for remote area or certain events
AC(Grid-connected)
Rated power
Voltage range
Rated frequency
Rated voltage
Output from
PF
THDI
Frequency range
Datasheet
500KVA
250V - 362V
50/60Hz
315V
3/N/PE
0.9lagging~0.9leading
<3%
47~51.5/57~61.5Hz
Growatt PCS500
DC(battery)
AC(off-grid)
Max power
Current regulation
Voltage regulation
Voltage range
Rated current
Voltage ripple
Current ripple
Max current
Input numbers
Rated voltage
Rated frequency
Overload capability
THDU
Datasheet
Rated voltage
550KW
500-820V
920A
<3%
<2%
1100A
1
315Vac
50/60Hz
110%-10 mins120%-1 min
Growatt PCS500
600V
≤1%linear
±1%
±1%
Communication
Display
Communication interface
Touch screen LCD
RS485/CAN
General Information
Maximum efficiency
Environment compatibility
Noise
Altitude
Environment temperature
Cooling
Dimension (W/H/ )D
Weight
Humidity
97.5%
<65dB
5000m(derated above 3000m)
-25 °C ... +55 °C
Air Forced
2000/2180/850mm
1620KG
0 ~95% non-condensing
Transfer between on/off grid Manual(default)
Automatic(optional)≤20ms
IP 20
Peak-shaving Mode
Typical Application
Grid export limit
Load power
www.ginverter.com
Energy flow
Communication
Power cable
Diesel generator
Mode 2
In the morning,
solar power is
not enough, grid
and solar supply
local load together
Diesel generator
Mode 3
Solar power is
higher than load
power, it supplies
local load, charges
battery at the
same time
Diesel generator
Mode 4
Solar power
decreases to below
load power, battery
discharges to
supply local load at
the same time
Diesel generator
Mode 1
At night, battery
is fully discharged,
grid supplies local
load
bypass cabinet (optional)
bypass cabinet (optional)
bypass cabinet (optional)
bypass cabinet (optional)
Transformer
Transformer
Transformer
Transformer
www.ginverter.com
NOTE:
1.Output power of inverter and PCS can be controled by the feedback information from power sensor.value ajustable
2.LPC stands for power control unit
Typical Application
Back-up Mode
Energy flow
Communication
Power cable
bypass cabinet (optional)
Diesel generator
Transformer
bypass cabinet (optional)
Diesel generator
Transformer
Mode 2
Mode 1
When grid is absent,
bypass cabinet disconnects grid automatically,battery discharges to supply local load together with solar when Diesel generator is starting up
When diesel generator is started, ATS connects diesel generator automatically to supply local load together with battery and solar