Download - IEC 909-3 (1995-09)
NORME INTERNATIONALE INTERNATIONAL STANDARD
CE1 IEC
90913 Première édition
First edition 1995-09
Calcul des courants de court-circuit dans les réseaux triphasés à courant alternatif - Partie 3: Courants durant deux court-circuits monophasés simultanés séparés à la terre et courants de court-circuit partiels s’écoulant à travers la terre
Short-circuit cu rre n t calculation in three-phase a.c. systems - Part 3: Currents during two separate simultaneous single phase line-to-earth short circuits and partial short-circuit currents flowing through earth
Numéro de référence Reference number
CEVIEC 909-3: 1995
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4 8 4 4 8 9 3 ObOLBL5 770
Validité de la présente publication
Le contenu technique des publications de la CE1 est cons- tamment revu par la CE1 afin qu'il reflète l'état actuel de la technique.
Des renseignements relatifs à la date de reconfirmation de la publication sont disponibles auprès du Bureau Central de la CEI.
Les renseignements relatifs à ces révisions, à l'établis- sement des éditions révisées et aux amendements peuvent être obtenus auprès des Comités nationaux de la CE1 et dans les documents ci-dessous:
Bulletin de ia CE1
Annuaire de la CE1 Publié annuellement Catalogue des publications de la CE1 Publié annuellement et mis à jour régulièrement
Terminologie
En ce qui concerne la terminologie générale, le lecteur se reportera à la CE1 50: Vocabulaire Electrotechnique Inter- national (VEI), qui se présente sous forme de chapitres séparés traitant chacun d'un sujet défini. Des détails complets sur le VE1 peuvent être obtenus sur demande. Voir également le dictionnaire multilingue de la CEI.
Les termes et définitions figurant dans la présente publi- cation ont été soit tirés du VEI. soit spécifiquement approuvés aux fins de cette publication.
Symboles graphiques et littéraux
Pour les symboles graphiques. les symboles littéraux et les signes d'usage général approuvés par la CEI, le lecteur consultera:
- technique;
- la CE1 417: Symboles graphiques utilisables sur le matériel. Index, relevé et compilation des feuilles individuelles;
- la CE1 617: Symboles graphiques pour schémas:
la CE1 27: Symboles littéraux à utiliser en électro-
et pour les appareils électromédicaux,
- la CE1 878: Symboles graphiques pour équipements électriques en pratique médicale.
Les symboles et signes contenus dans la présente publi- cation ont été soit tirés de la CE1 27. de la CE1 417. de la CE1 617 et/ou de la CE1 878, soit spécifiquement approuvés aux fins de cette publication.
Publications de la CE1 établies par le même comité d'études
L'attention du lecteur est attirée sur les listes figurant à la fin de cette publication, qui énumèrent les publications de la CE1 préparées par le comité d'études qui a établi la présente publication.
Validity of this publication
The technical content of IEC publications is kept under constant review by the IEC, thus ensuring that the content reflects current technology.
Information relating to the date of the reconfirmation of the publication is available from tht IEC Central Office.
Information on the revision work, the issue of revised editions and amendments may be obtained from IEC National Committees and from the following IEC sources:
IEC Bulletin
IEC Yearbook
Catalogue of IEC publications Published yearly
Published yearly with regular updates
Terminology
For general terminology, readers are referred to IEC 50: International Electrotechnical Vocabulary (IEV), which is issued in the form of separate chapters each dealing with a specific field. Full details of the IEV will be supplied on request. See also the IEC Multilingual Dictionary.
The terms and definitions contained in the present publi- cation have either been taken from the IEV or have been specifically approved for the purpose of this publication.
Graphical and letter symbols
For graphical symbols, and letter symbols and signs approved by the IEC for general use, readers are referred to publications:
- IEC 27: Leiter symbols to be used in electrical technology;
- IEC 417: Graphical symbols for use on equip- ment. Index. survey and compilation of the single sheets:
- IEC 617: Graphical symbols for diagrams;
and for medical electrical equipment,
- equipment in medical practice.
IEC 878: Graphical symbols for electromedical
The symbols and signs contained in the present publi- cation have either been taken from IEC 27, IEC 417, IEC 617 and/or IEC 878, or have been specifically appro- ved for the purpose of this publication.
IEC publications prepared by the same technical committee
The attention of readers is drawn to the end pages of this publication which list the IEC publications issued by the technical committee which has prepared the present publication.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
NORME INTERNATIONALE INTERNATIONAL STANDARD
CE1 IEC
90913 Première édition
First edition 1995-09
Calcul des courants de court-circuit dans les réseaux triphasés à courant alternatif - Partie 3: Courants durant deux court-circuits monophasés simultanés séparés à ia terre et courants de court-circuit partiels s'écoulant à travers ia terre
Short-circuit current calculation in three-phase a.c. systems - Part 3: Currents during two separate simultaneous single phase line-to-earth short circuits and partial short-circuit currents flowing through earth
U Commission Electrotechnique Internationale C O D E P R I X international Electrotechnical Commission P R I C E CODE Merrmywaporucaa 3 n e m p o ~ e x w ~ Houncaca
Pow prix. voir cætilogue M ~ U a W
For price, we wmni atabgue
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 Ob01817 543 = -2 - 909-3 O CE111995
SOMMAIRE
AVANT-PROPOS ...................................................................................................................... 4
Articles
Section 1: Généralités
1.1 Domaine d’application ............................................................................................ 1.2 Références normatives ........................................................................................... 1.3 Définitions ...............................................................................................................
1.3.1 1.3.2
1.3.3 1.3.4 1.3.5
Deux court-circuits monophasés simultanés séparés à la terre ...........
séparés à la terre ~ E E ................................................................................. Courant à la terre total LEt0 à l’emplacement du court-circuit ........... Courant de court-circuit partiel à travers la terre 134, ) ......................
1.3.6 Impédance d’entrée 2, .............................................................................
Courant initial durant deux court-circuits monophasés simultanés
Facteur de réduction d’une ligne L .........................................................
1.4 Symboles ................................................................................................................. Section 2: Courants durant deux court-circuits monophasés simultanés
séparés à la terre
8 8
10 10 10 12
2.1 Méthode de calcul .................................................................................................. 14 2.1.1 Courant de court-circuit symétrique initial ........................................... 14 2.1.2
2.1.3
Section 3: Courants de court-circuit partiels s’écoulant à travers la terre
Valeur de Crete du courant de court.circuit. courant de court-circuit
Répartition des courants de court-circuits à la terre pendant deux courants symétrique coupé et courant de court-circuit permanent .................... 18
de court-circuits monophasés simultanés séparés à la terre ......................... 20
dans le cas d’un court-circuit déséquilibré
3.1 Méthode de calcul .................................................................................................. 22 3.1.1 Généralités ................................................................................................. 22 3.1.2 Court-circuit monophasé à la terre dans un poste ................................ 22 3.1.3 26 3.1.4 28
Court-circuit monophasé à la terre en dehors d’un poste .................... Facteur de réduction des lignes aériennes et des câbles .......................
Annexes
A Exemple de calcul de deux court-circuits monophasés simultanés séparés à la t em ....... 34 A.l D ~ N I ~ ~ s .......................................... : .......................................................................... 34 A.2 Calculs ....................................................................................................................... 36
B Exemples de calcul de courants de court-circuit partiels à travers la terre ......................... 40 B.l Données ..................................................................................................................... 40 B.2 Premier cas: Calcul d’un courant de court-circuit monophasé à la t em
B.3 Deuxième cas: Calcul d’un courant de court-circuit monophasé à la terre en dehors d’un poste ...................................................................................................
dans un poste .............................................................................................................. 42
48
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
Page
FOREWORD ............................................................................................................................... 5
Section 1: General
1.1 Scope ......................................................................................................................... 7 1.2 Normative references .............................................................................................. 9 1.3 Definitions .............................................................................................................. 9
9
9 9
1.3.1 1.3.2
1.3.3
Two separate simultaneous single phase line-to-earth short circuits ... Initial short-circuits currents during two separate simultaneous single phase line-to-earth short circuits CEE ..................................................... Total earth current lEtot at the short-circuit location ..............................
1.3.4 Partial short-circuit current through earth 1 3q0> .................................. 11 1.3.5 Reduction factor of line L .......................................................................... 11 1.3.6 Driving point impedance Zp ...................................................................... 11
1.4 Symbols .................................................................................................................... 13
Section 2: Currents during two separate simultaneous single phase line-to-earth short circuits
2.1 Calculation method ................................................................................................ 15 2.1.1 Initial symmetrical short-circuit current .................................................. 15 2.1.2 Peak short-circuit current. symmetrical short-circuit breaking current
19 2.1.3 Distribution of line-to-earth short-circuit currents during
21
Section 3: Partial short-circuit currents flowing through earth in the case
and steady-state short-circuit current ......................................................
two separate simultaneous single phase line-to-earth short circuits ...
of an unbalanced short circuit
3.1 Calculation method ................................................................................................ 23 3.1.1 General ........................................................................................................ 23 3.1.2 Line-to-earth short circuit in a station .................................................... 23 3.1.3 Line-to-earth short circuit outside a station ........................................... 27 3.1.4 Reduction factor for overhead lines and cables ....................................... 29
Annexes A Example for the calculation of two separate simultaneous single-phase line-to-earth
short-circuit currents .......................................................................................................... 35 A.l Data ..................... .. ..................................................................................................... 35 A.2 Calculations ............................................................................................................... 37
B Examples for the calculation of pariilal short-circuit currents through earth ..................... 41 B.l Data ............................................................................................................................ 41 B.2 Case 1: Calculation of line-to-earth short-circuit current in a station ........................ 43 B.3 Case 2: Calculation of line-to-earth short-circuit current outside a station ............... 49
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 ObOL819 3 L b
DIS
73PlPIS
-4 - 909-3 O CEI: 1995
Rapport de vote
73P8IRVD
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
CALCULS DES COURANTS DE COURT-CIRCUIT DANS LES RESEAUX TRIPHASÉS À COURANT ALTERNATIF
PARTIE 3: COURANTS DURANT DEUX COURT-CIRCUITS MONOPHASES SIMULTANES SEPARES À LA TERRE ET
COURANTS DE COURT-CIRCUIT PARTIELS SECOULANT À TRAVERS LA TERRE
AVANT-PROPOS
La CE1 (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée de l’ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CE1 a pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de l’électricité et de l’électronique. A cet effet, la CEI, entre autres activités, publie des Normes internationales. Leur élaboration est confiée à des comités d’études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent également aux travaux. La CE1 collabore étroitement avec l’organisation Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
Les décisions ou accords officiels de la CE1 en ce qui concerne les questions techniques, préparés par les comités d’études où sont représentés tous les Comités nationaux s’intéressant à ces questions, expriment dans la plus grande mesure possible un accord international sur les sujets examinés.
Ces décisions constituent des recommandations internationales publiées sous forme de normes, de rapports techniques ou de guides et agréées comme telles par les Comités nationaux.
Dans le but d’encourager l’unification internationale, les Comités nationaux de la CE1 s’engagent à appliquer de façon transparente, dans toute la mesure possible, les Normes internationales de la CE1 dans leurs normes nationales et régionales. Toute divergence entre la norme de la CE1 et la norme nationale ou régionale correspondante doit être indiquée en termes clairs dans cette dernière.
La Nonne internationale CE1 909-3 a été établie par le comité d’études 73 de la CEI: Cou- rants de court-circuit.
Le texte de cette norme est issu des documents suivants:
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant abouti à l’approbation de cette norme.
Les annexes A et B sont données uniquement titre d’information.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
~~ ~
m 4844893 Ob03820 038 W
73171/DIS
909-3 O IEC: 1995 - 5 -
73/78/RVD
INTERNATIONAL ELECTROTECHNICAL COMMISSION
SHORT-CIRCUIT CURRENT CALCULATION IN THREE-PHASE A.C. SYSTEMS
PART 3: CURRENTS DURING TWO SEPARATE SIMULTANEOUS SINGLE PHASE LINE-TO-EARTH SHORT CIRCUITS
AND PARTIAL SHORT-CIRCUIT CURRENTS FLOWING THROUGH EARTH
FOREWORD
The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote international cooperation on all questions concerning standardization in the electrical and electronic fields. To this end and in addition to other activities, the IEC publishes International Standards. Their preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with may participate in this preparatory work. International, governmental and non-governmental organizations liaising with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization for Standardization (KO) in accordance with conditions determined by agreement between the two organizations.
The formal decisions or agreements of the IEC on technical matters, prepared by technical committees on which all the National Committees having a special interest therein are represented, express, as nearly as possible, an international consensus of opinion on the subjects dealt with.
They have the form of recommendations for international use published in the form of standards, technical reports or guides and they are accepted by the National Committees in that sense.
In order to promote international unification, IEC National Committees undertake to apply IEC International Standards transparently to the maximum extent possible in their national and regional standards. Any divergence between the IEC Standard and the corresponding national or regional standard shall be clearly indicated in the latter.
International Standard IEC 909-3 has been prepared by IEC technical committee 73: Short- circuit currents.
The text of this standard is based on the following documents:
DIS I Report on voting I
Full information on the voting for the approval of this standard can be found in the report on voting indicated in the above table.
Annexes A and B are for information only.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
~ ~
D 4844893 Ob03823 Ti4
- 6 - 909-3 O CEI:1995
CALCULS DES COURANTS DE COURT-CIRCUIT DANS LES RESEAUX TRIPHASÉS A COURANT ALTERNATIF
PARTIE 3: COURANTS DURANT DEUX COURT-CIRCUITS MONOPHASES SIMULTANES SEPARES À LA TERRE ET
COURANTS DE COURT-CIRCUIT PARTIELS S’ÉCOULANT À TRAVERS LA TERRE
Section 1: Généralités
1.1 Domaine d’application
La présente norme internationale spécifie les procédures applicables au calcul des valeurs présumées des courants de court-circuit lors d’un court-circuit déséquilibré dans les réseaux triphasés aériens à haute tension à courant alternatif fonctionnant à une fréquence nomi- nale de 50 ou 60 Hz, c’est à dire:
a) courants durant deux court-circuits monophasés simultanés séparés à la terre dans les réseaux à neutre isolé ou mis à la terre par une bobine d’extinction; b) courants de court-circuit partiels s’écoulant à travers la terre, dans le cas d’un seul défaut monophasé à la terre dans les réseaux à neutre mis à la terre directement ou par une faible impédance.
Les courants calculés suivant ces procédures doivent être utilisés pour la détermination des tensions induites ou des tensions de contact ou de pas, et la montée du potentiel de terre dans un poste.
La présente norme ne couvre pas:
a) les courants de court-circuit provoqués délibérément de façon contrôlée, comme dans les stations d’essai en court-circuit;
b) les courants de court-circuit dans les installations électriques à bord des navires ou des avions;
c) les simples défauts monophasés à la terre dans les réseaux à neutre isolé ou mis à la terre par une bobine d’extinction.
L’objet de la présente norme est d’établir des procédures pratiques et concises pour le calcul des courants de court-circuit à la terre durant deux ’court-circuits monophasés simultanés séparés à la terre et des courants de court-circuit partiels s’écoulant à travers la terre, dans les installations électriques, donnant des résultats sûrs et d’une précision suffisante. Dans ce but, le courant est déterminé en utilisant une source de tension équiva- lente appliquée à l’emplacement du court-circuit. toutes les autres sources étant mises à zéro. La procédure est applicable à une détermination par des méthodes manuelles, par des simulations analogiques ou par calcul numérique.
La présente norme constitue un complément à la CE1 909. Pour les définitions, les sym- boles et les hypothèses de calcul en général, se reporter à cette publication. Seuls des éléments particuliers sont définis ou spécifiés dans le présent document. Ceci n’exclue pas l’utilisation de méthodes particulières, par exemple la méthode de superposition, adaptées à des circonstances particulières, si elles donnent au moins la même précision.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03822 900 M
909-3 O LEC1995 -7-
SHORT-CIRCUIT CURRENT CALCULATION IN THREE-PHASE A.C. SYSTEMS
PART 3: CURRENTS DURING TWO SEPARATE SIMULTANEOUS SINGLE PHASE LINE-TO-EARTH SHORT CIRCUITS
AND PARTIAL SHORT-CIRCUIT CURRENTS FLOWING THROUGH EARTH
Section 1: General
1.1 Scope
This International Standard specifies procedures for calculation of the prospective short- circuit currents with an unbalanced short circuit in high-voltage three-phase a.c. systems operating at nominal frequency 50 Hz or 60 Hz, Le.
a) currents during two separate simultaneous single phase line-to-earth short circuits in isolated neutral or resonant earthed neutral systems; b) partial short-circuit currents flowing through earth in case of single line-to-earth fault in solidly earthed or low-impedance earthed neutral systems.
The currents calculated by these procedures are to be used when determining induced voltages or touch or step voltages and rise of earth potential at a substation.
This standard does not cover:
a) short-circuit currents deliberately created under controlled conditions as in short- circuit testing stations, or
b) short-circuit currents in the electrical installations on board ships or aeroplanes, or
c) single line-to-earth faults in isolated or resonant earthed systems.
The object of this standard is to establish practical and concise procedures for the calculation of line-to-earth short-circuit currents during two separate simultaneous single phase short circuit and partial short-circuit currents through earth from electrical installa- tions, leading to conservative results with sufficient accuracy. For this purpose, the current is determined by considering an equivalent voltage source applied at the short-circuit loca- tion with all other sources set to zero. The procedure is suitable for determination by man- ual methods, analogue simulations or digital computation.
This standard is an addition to IEC 909. General definitions, symbols and calculation assumptions refer to that publication. Special items only are defined or specified in this document. This does not exclude the use of special methods, for example the superposition method, adjusted to particular circumstances. if they give at least the same precision.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
D 4844893 Ob01823 847
- 8 - 909-3 O CEk1995
Comme indiqué dans la CE1 909, les courants de court-circuit et leurs paramètres peuvent aussi &re déterminés par des essais du réseau, par des mesures sur un analyseur de réseau ou avec un calculateur numérique.
Le calcul des paramètres du court-circuit sur la base des caractéristiques assignées du matériel électrique et de la disposition topologique du réseau présente l’avantage d’être possible aussi bien pour les réseaux existants que pour les réseaux au stade de la conception.
1.2 Références normatives
Le document normatif suivant contient des dispositions qui, par suite de la référence qui en est faite, constituent des dispositions valables pour la présente norme internationale. Au moment de la publication, l’édition indiquée était en vigueur. Tout document normatif est sujet à révision, et les parties prenantes des accords fondés sur la présente norme interna- tionale sont invitées à rechercher la possibilité d’appliquer l’édition la plus récente du document normatif indiqué ci-après. Les membres de la CE1 et de I’ISO possèdent le registre des Normes internationales en vigueur à un moment donné.
CE1 909: 1988, Calcul des courants de court-circuit dans les réseaux triphasés à courant alternatif.
CE1 909-1: 1991, Calcul des courants de court-circuit dans les réseaux triphasés à cou- rant alternatif - Partie 1: Facteurs pour le calcul des courants de court-circuit dans les réseaux alternatifs triphasés conformément à la CEI 909.
CE1 909-2: 1992, Calcul des courants de court-circuit dans les réseaux triphasés à courant alternatif - Matériel électrique - Données pour le calcul des courants de court- circuit conformément à la CEI 909 (1988).
1.3 Définitions
Pour les besoins de la présente norme, les définitions suivantes s’appliquent.
1.3.1 Deux court-circuits monophasés simultanés séparés à la terre
Court-circuits monophasés à la terre se produisant simultanément en des emplacements distincts et sur des phases distinctes d’un réseau triphasé à courant alternatif dont le neutre est isolé ou est mis à la terre par une bobine d’extinction.
1.3.2 Courant initial durant deux court-circuits monophasés simultanés séparés à la terre G E E
Valeur efficace du courant de court-circuit initial circulant avec la même amplitude aux deux emplacements, au moment des deux court-circuits monophasés simultanés séparés à la terre.
1.3.3 Courant à la terre total l,,,, à l’emplacement du court-circuit
Valeur efficace du courant total s’écoulant par le réseau de terre d’un poste (centrale, poste de transformation ou de couplage) ou par l’impédance de pied d’un pylône de ligne aérienne et par des conducteurs mis à la terre. De tels conducteurs peuvent être des câbles de garde de ligne aérienne ou bien des gaines, écrans ou armures de câbles.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03824 783 9
909-3 O IEC1995 - 9 -
As stated in IEC 909, short-circuit currents and their parameters may also be determined by system tests, by measurement on a network analyzer, or with a digital computer.
The calculation of the short-circuit parameters based on the rated data of the electrical equipment and the topological arrangement of the system has the advantage of being possi- ble both for existing systems and for systems at the planning stage.
1.2 Normative references
The following nonnative document contains provisions which, through reference in this text, constitute provisions of this International Standard. At the time of publication, the edition indicated was valid. All normative documents are subject to revision, and parties to agreement based on this International Standard are encouraged to investigate the possi- bility of applying the most recent edition of the normative documents indicated below. Members of IEC and IS0 maintain registers of currently valid International Standards.
IEC 909: 1988, Short-circuit current calculation in three-phase a.c. systems.
IEC 909-1: 1991, Short-circuit current calculation in three-phase a.c. systems - Part 1 : Factors for the calculation of short-circuit currents in three-phase a.c. systems according to IEC 909.
IEC 909-2: 1991, Short-circuit current calculation in three-phase a.c. systems - Electri- cal equipment - Data for short-circuit current calculations in accordance with IEC 909 (1988).
1.3 Definitions
For the purpose of this standard, the following definitions apply.
1.3.1
Line-to-earth short circuits at different locations at the same time in different phases of a three-phase a.c. system having a resonant earthed or an isolated neutral.
Two separate simirltaneous single phase line-to-earth short circuits
1.3.2 Initial short-circuits currents during two separate simultaneous single phase line-to-earth short circuits CEE
The r.m.s. value of the initial short-circuit currents flowing with the same magnitude at both locations at the instant of the two separate simultaneous line-to-earth short circuits.
1.3.3
"he r.m.s. value of the total current flowing through the earthing system of a station (power station, transformer or switching station) or the footing impedance of an overhead line tower and through earthed conductors to earth. Such conductors may be earth wires of overhead lines or sheaths, shielding or armouring of cables.
Total earth current LE,,, at the short-circuit location
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
- 10- 909-3 O CEIz1995
1.3.4 Courant de court-circuit partiel à travers la terre 34,,
Amplitude de la fraction du courant total s’écoulant à la terre à une certaine distance de l’emplacement du court-circuit et du réseau de terre d’un poste, où la répartition du cou- rant total entre les conducteurs mis à la terre et la terre est presque constante. Son ampli- tude dépend du facteur de réduction L.
1.3.5 Facteur de réduction d’une ligne
Facteur qui détermine la fraction du courant homopolaire s’écoulant par la terre à une certaine distance de l’emplacement du court-circuit et du réseau de terre d’un poste.
1.3.6 Impédance d‘entrée Zp
Dans le cas d’une ligne aérienne, impédance constituée de l’impédance du câble de garde Zw entre deux pylônes avec retour par la terre, et de la résistance de pied de pylône R,. L’impédance d’entrée est définie pour une direction par
avec 2, = z’, dT
Figure 1 - Chaîne infinie constituée par l’impédance du câble de garde Zw et la résistance de pied des pylônes RT, séparées par des distances identiques dT
NOTE - L’impédance d’entrée &, peut être supposée constante à une distance de l’emplacement du court-circuit, F, supérieure à la distance “loin du poste” D, définie par l’équation (16).
Dans le cas d’un câble d’énergie, une approche similaire peut être utilisée, mais des précautions particulières sont nécessaires.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
W 4844893 Ob03826 55b W
909-3 O IEC1995 - 11 -
1.3.4
The magnitude of the part of the total current flowing through earth remote from the short- circuit location and the earthing system of a station, where the distribution of the total current between earthed conductors and earth is nearly constant. Its magnitude depends on the reduction factor L.
Partial short-circuit current through earth L 34,)
1.3.5 Reduction factor of line L
The factor which determines the part of the zero-sequence current flowing through earth remote from the short-circuit location and the earthing system of a station.
1.3.6 Driving point impedance Zp
In the case of an overhead line, the driving point impedance is composed of the earth-wire impedance & between two towers with earth return, and the tower footing resistance R,. The driving point impedance is defined for one direction by:
Figure 1 -Infinite chain composed by the earth-wire impedance -&, and the footing resistance RT of towers separated with equal distances dT
NOTE - The driving point impedance 2, can be assumed constant at a distance from the short-circuit point F. longer than the far-from-station distance D, defined by equation (16).
In the case of a power cable, a similar approach may be used, but special considerations are necessary.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03827 Y92
- 12- 909-3 O E I : 1995
1.4 Symboles
Toutes les équations données sont des équations quantitatives dans lesquelles les symboles représentent des grandeurs physiques comportant à la fois des valeurs numériques et des dimen- sions. Les symboles des grandeurs complexes sont soulignés, par exemple e.g. Z = R + jX. C Facteur de tension selon le tableau I de la CE1 909
cün/G Source de tension équivalente (valeur efficace), voir CE1 909
DF Distance "loin du poste"
*T
IbEE
IEtot
lt, I"
LtE2E
ipEE
q,,, R'S
R E
R T
- r Facteur de réduction
L 3k0, q I ) A ' q 1 ) B
S(2)A' 4 2 ) B
&o)
Distance entre pylônes, voir fig. 1 Courant de court-circuit coupé (valeur efficace) Courant de terre total à l'emplacement du court-circuit (valeur efficace) Courant de court-circuit monophasé à la terre initial (valeur efficace)
séparés à la terre (valeur efficace) Courant de court-circuit initial (valeur efficace) s'écoulant par la terre dans le cas d'un court-circuit biphasé à la terre, voir la CE1 909 Valeur de Crete du courant de court-circuit
Courant de court-circuit initial durant deux court-circuits monophasés simultanés
Impédance de couplage du système respectivement directe et inverse Composante résistive linéique de l'impédance propre d'une gaine à la terre Résistance du réseau de terre Résistance de pied d'un pylône de ligne aérienne
Courant de court-circuit partiel à travers la terre à une distance supérieure à DF Impédance de court-circuit directe du réseau triphasé à courant alternatif aux emplacements de court-circuit A et B
Impédance de court-circuit inverse du réseau triphasé à courant alternatif aux emplacements de court-circuit A et B
Impédance de court-circuit homopolaire du réseau complet entre les emplace- ments de court-circuit A et B (les admittances entre phases et terre sont nég 1 igées) Impédance linéique d'une gaine à la terre Impédance totale de terre dans une station Impédance d'entrée selon l'équation (1) et la figure 1
Impédance totale de terre du pylône OU se situe le court-circuit Impédance d'entrée des gaines, écrans ou armures de câble
Z'S 2, ZP &- ZU - Zw = &.dT Impédance du cable de garde avec retour par la terre entre deux pylônes
z'w -wL
6 P Résistivité du sol
Impédance linéique du câble de garde avec retour par la terre Impédance mutuelle linéique entre le câble de garde et les conducteurs de phase paralleles, avec retour commun par la terre Profondeur équivalente de pénétration dans la terre
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 0601828 329
909-3 O IEC: 1995 - 13-
1.4 Symbols
All equations are written as quantity equations, in which the symbols represent physical quantities possessing both numerical values and dimensions. Symbols of complex quantities are underlined, e.g. Z = R + jX.
C
c ü J 6 Equivalent voltage source (r.m.s.), see IEC 909
DF Far-from-station distance
dT ZbEE Short-circuit breaking current (r.m.s.)
ZEtot
L'k,
Voltage factor according to table I of IEC 909
Distance between towers, see fig. 1.
Total earth current at the short-circuit location (r.m.s.) Initial line-to-earth short-circuit current (r.m.s.)
I" Initial short-circuit current during two separate simultaneous s.&igle-phase earth short circuit (r.m.s.)
ne-to-
L!&
$EE Peak short-circuit current
ql), 4) R's RE Resistance of earth grid
RT - r Reduction factor
Initial short-circuit current (r.m.s) flowing to earth in the case of a line-to-line short circuit with earth connection, see IEC 909.
Coupling impedance, in the positive- resp. negative-sequence system Resistive component of the sheath to earth self impedance per unit length
Footing resistance of an overhead line tower
3k0, Partial short-circuit current through earth at a distance larger than D ,
q 1 ) A ' 4 l ) B
q Z ) A * 42)B
Go,
Z's ZE ZET
2, Z U - 2, = &dT Earth-wire impedance with earth return between two towers
z'w Per unit length earth-wire impedance with earth return zk, Per unit length mutual impedance between earth wires and the line conductors
with common earth return 6 Equivalent earth penetration depth P Soil resistivity
Positive-sequence short-circuit impedance of the three-phase a.c. system at the short-circuit locations A and B
Negative-sequence short-circuit impedance of the three-phase a.c. system at the short-circuit locations A and B
Zero-sequence short-circuit impedance of the entire network between the short- circuit locations A and B (admittances between phases and earth are disregarded) Sheath to earth impedance per unit length Total earth impedance in a station
Total earth impedance of the short-circuited tower Driving point impedance according to equation (1) and fig. 1.
Input impedance of sheaths, shielding or armouring of cables
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
41344893 0601829 265 D
- 14- 909-3 O CEI~1995
Section 2: Courants durant deux court-circuits monophasés simultanés séparés à la terre
2.1 Méthode de calcul
2.1.1
La figure 2 montre les courants de court-circuit IrEE dans le cas de deux court-circuits monophasés simultanés séparés à la terre dans des phases distinctes aux emplacements A et B séparés par une distance non nulle.
Courant de court-circuit symétrique initial
Dirtance+O
A B L1
t t I I
/ / / / / / / / / / / / / / / / / / / / / / / / / ’
+ La direction des fleches de courant est choisie arbitrainment
Cu 816m
Figure 2 - Représentation de deux court-circuits monophasés simultanés séparés à la terre et du courant IyEE
Dans les réseaux avec neutre isolé ou mis à la terre par une bobine d’extinction, le courant de court-circuit symétrique initial IrEE est calculé à l’aide de
Dans le cas d’un court-circuit éloigné d’un alternateur, pour lequel q1, = s(2) et hl1 = GI, le courant de court-circuit initial devient
Pour le calcul du courant de court-circuit maximal conformément à la CE1 909, d’impédance totale de terre ZE peut être négligée pour un court-circuit avec mise à la terre dans une station ou sur un pylône, équations (14) et (19).
NOTE - Pour la résolution de l’équation (2) voir les Directives du CCITT, UIT Genève, volume V. Chapitre 5 .
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
m 4844873 Ob03830 T87 m
909-3 O JEC1995 - 15-
Section 2: Currents during two separate simultaneous single phase ¡¡ne-to-earth short circuits
2.1 Calculation method
2.1.1 ' Initial symmetrical short-circuit current
Figure 2 shows the short-circuit current IrEE during two separate simultaneous single phase line-to-earth short circuits in different phases at the locations A and B with a distance between them # O.
I- 1 Distiacc+O
A B L1
I t L-=E / / / / / / / / / / / / / / / / / / / / / / / / /
+ The directioo of current arrows is chosen arbitrarily
IEC 616M
Figure 2 - Characterization of two separate simultaneous single phase line-to-earth short circuits and the current I t E E
In systems with isolated neutral or with resonant earthed neutral the initial symmetrical short-circuit current I&E is calculated using
In the case of a far-from-generator short circuit, where Gil = q2) and short-circuit current becomes
= the initial
For calculation of the maximum short-circuit current according to IEC 909, the total earth impedance Z, is to be disregarded for a short circuit with earth connection in a station or at a tower, equations (14) and (19).
NOTE - For derivation of equation (2) see CCITT-Directives, ITU Geneva, volume V, Chapter 5 .
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 ObOL833 913
909-3 0 CEI: 1995 - 16-
2.1.1.1
Les impédances de couplage, directe et inverse, &l) et 42) sont déterminées comme indiqué ci-après:
Détermination de $1) et 4)
Une source de tension UA est introduite à l’emplacement du court-circuit A comme la seule tension active du réseau. Si 41)A et 42)4 sont les courants dus à cette source de ten- sion dans les systèmes direct et inverse au point de court-circuit A et si qlIB et 42)B sont les tensions résultantes dans les systèmes direct et inverse au point B, alors
Les impédances de couplage circuit B au lieu du point A à l’aide de
et F2) peuvent aussi être déterminées au point de court-
2.1.1.2 Exemples simples de deux court-circuits monophasés simultanés séparés à la terre
Dans des cas simples les courants de deux court-circuits monophasés simultanés séparés à la terre peuvent être calculés comme indiqué dans le tableau 1, à condition d’admettre que
= &2). Avec cette hypothèse, les équations (6) à (8), données dans le tableau 1, sont déduites de l’équation (2). Les indices des équations (6) à (8) se rappor- tent aux impédances appropriées dans les circuits correspondants.
= &,, et que
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844871 ObOL832 85T
909-3 O IEC1995 - 17-
2.1.1.1 Determination of and ,42) The positive- and negative-sequence coupling impedances, follows:
and 42) are determined as
A voltage source UA is introduced at the short-circuit location A as the only active voltage of the system. If hlIA and are the currents due to this voltage source in the positive- and negative- sequence systems at the short-circuit location A and if qIIB and 4 2 ) B are the resulting voltages in the positive- and negative-sequence systems at the location B, then
&2)= - b (4)
The coupling impedances tion B instead of the location A by using
and &2, may also be determined at the short-circuit loca-
2.1.1.2 Simple cases of two separate siniultaneous single phase line-to-earth short circuits
In simple cases the two separate simultaneous single phase line-to-earth short-circuit cur- rents can be calculated as shown in table l provided it is presumed that Gl) = &) and
= &2). With this presumption equation (6) to (S), shown in table 1, are denved from equation (2). The indices in equation (6) to (8) refer to the relevant impedances in the re- spective circuits.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03833 796
- 18- 909-3 O CEt1995
Tableau 1 - Calcul des courants initiaux de court-circuits monophasés h la terre dans des cas simples
LI U u
LI u L3
LI u: u
ligne alimentée en antenne
deux lignes alimentées en antenne
3cun (7)
ligne à double alimentation
Pour &o), la remarque à la suite de l'équation (3) doit être prise en considération. Le facteur de tension c doit être pris dans le tableau I de la CE1 909.
2.1.2 Valeur de crête du courant de court-circuit, courant de court-circuit symétrique coupé et courant de court-circuit permanent
La valeur de crête du courant de court-circuit est calculée conformément h la CE1 909 à l'aide de
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03834 b22
909-3 O IECz1995 - 19-
Table 1 - Calculation of initial line-to-earth currents in a simple case
I-'-I-'l LI L2 U
LI L2 I3
LI u. u
single-fed radial line
3cun (6:
two single-fed radial lines
3cu- (7)
double-fed single lines
For The voltage factor c shall be taken from table I of IEC 909.
the remark after equation ( 3 ) shall be considered.
2.1.2 Peak short-circuit current, synrnietrical short-circuit breaking current and steady-state short-circuit current
The peak short-circuit current is calculated according to IEC 909 using
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
W 4844871 Ob03835 567 W
909-3 O CEI:1995 - 20-
Pour le facteur K, la valeur à utiliser est la même que dans le cas d'un court-circuit tri- phasé aux emplacements A ou B, en prenant la valeur la plus élevée.
Si les court-circuits monophasés à la terre peuvent être assimilés à un court-circuit éloigné d'un alternateur, alors
- 1'' IkEE = IbEE - kEE
2.1.3 Répartition des courants de court-circuits à la terre pendant deux courants de court-circuits monophasés simultanés séparés à la terre
Si deux court-circuits monophasés à la terre se produisent aux emplacements A et B, la réparti- tion du courant à travers la terre peut être calculée en admettant que I 3q0) = 1 L'&E est la seule source active de courant alimentant le système homopolaire en A et B; toutes les autres sources sont négligées.
Par exemple, dans le cas de deux court-circuits monophasés à la terre sur les pylônes A et B d'une ligne aérienne, le courant à la terre IT du pylône considéré sur la figure 3 devient
Z P
OU
L R, est la résistance de pied de pylône;
&,
est le facteur de réduction de la ligne aérienne, selon 3.1.4:
est l'impédance d'entrée selon 1.3.6.
CU 817M
Figure 3 - Répartition du courant de court-circuit partiel à travers la terre L. 3q0, sur les pylônes A et B
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4 8 4 4 8 9 3 Ob03836 4T5
909-3 O IEC: 1995 -21 -
For the factor IC, the same value is used as in the case of a three-phase short circuit at the location A or B. whichever is the largest.
If the line-to-earth short circuits can be assumed as far-from-generator short circuits, then
'kEE = 'LEE = "LEE
2.1.3 Distribution of fine-to-earth short-circuit currents during two separate simultaneous single phase fine-to-earth short circuits
If two separate line-to-earth short circuits occur at the locations A and B, the current distri- bution through earth can be calculated assuming L 3r(o, = L as the only active current source feeding the zero-sequence system in A and B; all other sources are disregarded.
For example, in the case of two line-to-earth short circuits at the towers A and B of an overhead line, the current rT of the respective tower to earth in figure 3 becomes
z, - - --LEE r I"
s p + 2 ~ ~
where
L R, is the footing resistance of the tower;
&, is the driving point impedance according to 1.3.6.
is the reduction factor of the overhead line according to 3.1.4;
Figure 3 - Distribution of the partial short-circuit current p 3qO1 through earth on the towers A and B
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
H 4844893 Ob03837 331
909-3 O CEI: 1995 -22-
Section 3: Courants de court-circuit partiels s'écoulant travers la terre dans le cas d'un court-circuit déséquilibré
3.1 Méthode de calcul
3.1.1 Généralités
Les paragraphes 3.1.2 et 3.1.3 traitent des courants de court-circuit partiels s'écoulant à travers la terre et dans les conducteurs mis à la terre (par exemple réseaux de terre, câbles de garde de lignes aériennes ou gaines conductrices, écrans et armures de câbles), dans le cas de courts-circuits monophasés à la terre. Ce type de court-circuit est le défaut se produ- isant le plus fréquemment dans les réseaux haute-tension mis directement à la terre. Il conduit aux courants de court-circuit partiels à la terre les plus élevés si Z(o, est supérieur à Z(i,.
Lorsque Z(*> est inférieur à Z(li et dans le cas d'un court-circuit biphasé à la tem, le courant à travers la tem CEE doit être pris en considération conformément à la CE1 909.
De plus les postes A, B et C sont supposés &re séparés par plus que deux fois la distance "loin du poste" D, selon 1 'équation (16).
Pour le calcul du courant de court-circuit maximal conformément à la CE1 909, les impédances des pylônes, avec ou sans câble de garde, et les impédances des réseaux de terre et des autres connections à la terre peuvent &re négligées.
La procédure de calcul sera considérée avec un réseau simplifié constitué de trois postes A, B et C et de lignes aériennes avec un seul circuit et un seul câble de garde.
3.1.2 Court-circuit monophasé d la terre duns un poste I
La figure 4 représente un poste de transformation B avec des arrivées venant des postes adjacents A et C.
LWA Lwc CPble de garde .-...-..o- ...-.
....-e- . . * . .. *-(--.. . ~ ~ 3 4 0 ) ~ rc3k0)~ Terre de référence
CU 81865
Figure 4 - Courants de court-circuit partiels dans le cas d'un court-circuit monophasé à la terre dans le poste B
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03838 278 = 909-3 O EC1995 -23-
Section 3: Partial short-circuit currents flowing through earth in the case of an unbalanced short circuit
3.1 Calculation method
3.1.1 General
Subclauses 3.1.2 and 3.1.3 deal with partial short-circuit currents flowing through earth and earthed conductors (e.g. earthing systems, earth wires of overhead lines resp. conductive sheaths, shieldings and armouring of cables) in the case of line-to-earth short circuits. This type of short circuit in solidly earthed high-voltage systems is the most frequently occuring system fault. It leads to the greatest partial earth short-circuit currents ifZ(0) ’ Z(1).
For 2 e Z(i) in the case of a line-to-line short circuit with earth connection, the current to earth (9 shall be considered according to IEC 909.
Moreover it is assumed that stations A, B and C are separated by more than twice the far- from-station distance D, according to equation (16).
For calculation of the maximum short-circuit current according to IEC 909, the tower impedances with or without earth wire and the earth-grid impedances and other connections to earth may be disregarded.
The calculation procedure will be considered on a simplified network consisting of three stations A, B and C, and overhead lines with a single circuit and one earth wire.
3.1.2 Line-to-earth short circuit in a station
Figure 4 shows a transformer station B with feeders coming in from adjacent stations A and C.
1WA Lwc Earth wire
t e- --Q- . - . . . ...-. - ...-. -. t - - - - * -*
.-.v... . . . .-=-. . . . Reference earth ~ ~ 3 4 0 ) ~ r c 3 4 0 ~
IEC 8 I 8 m
Figure 4 - Partial short-circuit currents in the case of a line-to-earth short circuit inside the station B
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob03839 L O 4 = - 24- 909-3 O CEIc1995
Un ou plusieurs des transformateurs du poste B sont directement mis à la terre. Le courant de court-circuit monophasé à la terre LE1 est égal à trois fois le courant homopolaire circu- lant au point de court-circuit F
Le courant total à travers la terre au point de court-circuit F dans un poste éloigné des autres postes auxquels il est raccordé, est:
c’est-à-dire selon la figure 4
L’impédance de mise à la terre d’un poste est
1 - 2, = 1 - 1 - 1 -+L- +L- RE ZP Z U
OU
RE est la résistance du réseau de terre;
&, est l’impédance d’entrée selon 1.3.6; Z, est l’impédance d’entrée des gaines, écrans et armures des câbles.
Le potentiel de la terre au poste B est
Les équations (13a) et (13b) supposent que la distance entre le poste B et les postes A et C est supérieure à la distance “loin du poste” D, avec
OU
RT est Ia résistance de pied des pylônes;
dT est la distance entre pylônes; R e { a w ) est ia partie réeiie de ia racine d e de l’impédance du câble de garde de & = & a$ avec zw selon l’équation (24).
Autrement le courant total à la terre i,,, est réduit par une fraction trop importante du courant de double court-circuit monophasé à la terre s’écoulant vers le poste le plus proche A ou C par les câbles de garde. La répartition des courants de court-circuit entre les cables de garde et la terre comme indiqué à la figure 4 est déterminée par les facteurs de réduction des cables de garde rA et r, des lignes aériennes AB et BC. Dans le cas des câbles, le facteur de réduction dépend des gaines conductrices, des armures et de leurs mises à la terre.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
909-3 O IEC: 1995 -25-
One or more of the transfomers in station B are directly earthed. The line-to-earth short- circuit current Lrl is equal to three times the zero-sequence current flowing to the short- circuit location F:
The total current through earth at the short-circuit location F at a station remote from other stations to which it is connected, is:
i.e. in figure 4
The earthing impedance of a station is
1
where
RE is the resistance of earth grid;
Z, Z, is the input impedance of sheaths, shielding or armouring of cables.
is the driving point impedance according to 1.3.6;
The earth potential at the station B is:
Equations (13a) and (13b) suppose, that the distance from the station B to the stations A and C is longer than the far-from-station distance D, with
where
R, is the tower footing resistance;
dT is the tower distance;
R e ( c w ) is the real part of the square root of the earth-wire impedance & = Zw dT with zw according
to equation (24).
Otherwise the total earth current b,,, is reduced by an excessive part of the line-to-earth short-circuit current flowing back to the nearest station A or C via earth wires. The divi- sion of the short-circuit currents between the earth wires and the earth as shown in figure 4 is determined by the earth wire reduction factors q, and Q of the overhead lines AB and BC. For cables, the reduction factor depends on the conductive sheaths, armourings and their earthing.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob01843 8b2
- 2 6 - 909-3 O CEI: 1995
Les courants dans les câbles de garde des lignes aériennes de la figure 4, loin des postes A, B et C, sont donnés par
NOTE - Des précautions particulières peuvent être nécessaires dans le cas de lignes à double circuit ou de lignes parallèles avec des systèmes homopolaires couplés.
3.1.3 Court-circuit monophasé à la terre en dehors d u n poste
Un court-circuit monophasé à la terre sur un pylône d’une ligne aérienne est représenté sur la figure 5. Le court-circuit est supposé se produire loin des postes.
LWA LWA + [WB Lwc Cfble de garde . ...-=-, ... ... ... . -* - -..
...~-:- ... ... .+ ... ... -9% ... f ~ 3 4 ~ ) ~ Terre de référence ~ ~ 3 4 0 ) ~ rc ( 3 4 ~ ~ + 3401,)
CEI 8IMS
Figure 5 -Courants de court-circuit partiels dans le cas d’un court-circuit monophasé à la terre sur un pylône d’une ligne aérienne
Le courant de court-circuit monophasé à la terre L:l est donné par
L’impédance totale de terre du pylône où se situe le court-circuit, raccordé aux câbles de garde de la ligne aérienne à l’emplacement du défaut, est donnée par
1
1 2 - ET - (19)
OU
R, est la résistance de pied de pylône;
&, est l’impédance d’entrée de la ligne selon 1.3.6.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 0601842 7Tî D
909-3 O IEC: 1995 -27-
The currents in the overhead line earth wires of figure 4 remote from the stations A, B and C are given by
NOTE - Special considerations may be necessary in the case of double-circuit lines or parallel lines with coupled zero-sequence systems.
3.1.3 Line-to-earth short circuit outside a station
A line-to-earth short circuit at a tower of an overhead line is shown in figure 5. The short circuit is assumed to occur remote from the stations.
Earth wire l W A LWA + ¿WB ¿wc .-<- . . - . .. .-s-, . . . .-. -
... - .-. ...A... ... A...
Figure 5 - Partial short-circuit currents in the case of a line-to-earth short circuit at a tower of an overhead line
The line-to-earth short-circuit current is given by
The total earth impedance of the short-circuited tower connected to an overhead earth wire at the fault location is given by
1 - 1 2 SET -
where
R, is the footing resistance of the tower;
Z, is the driving point impedance of the overhead line according to 1.3.6.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 Ob01843 635
-28- 909-3 o cEI:1995
Lors d'un court-circuit sur un pylône T éloigné des postes A, B et C, le courant total de terre est donné par
Le potentiel de terre du pylône OU se produit le court-circuit est
Si sur une ligne comportant un câble de garde, un court-circuit monophasé à ia terre se produit sur un pylône dans le voisinage d'un poste, une grande partie du courant de court- circuit monophasé à la terre peut revenir au poste par le câble de garde. La partie du cou- rant s'écoulant par la terre peut, dans ce cas, &re inférieure à celle calculée à l'aide de l'équation (20). Le calcul nécessite une attention particulière lorsque ia distance entre le poste B et le pylône où se situe le court-circuit est faible, par rapport à la distance. "loin du poste" D,.
Le courant à travers ia terre au poste B dans le cas d'un court circuit à ia terre en F est obtenu, à partir de ia figure 5 , par
Le courant de terre LEB résultant d'un court-circuit monophasé à la terre se produisant sur la ligne aérienne peut être supérieur à celui résultant d'un court-circuit monophasé a la terre à l'intérieur du poste B.
3.1.4 Facteur de réduction des lignes aériennes et des cables
Les équations suivantes s'appliquent aux lignes aériennes avec câbles de garde. Elles sont également valables pour des câbles avec des gaines métalliques, des écrans ou des armures mis a ia terre à chaque extrémité. Le facteur de réduction dans le cas d'un câble de garde est donné par
Z'w et z'w dépendent de la résistivité du sol p. de la distance entre les cables de garde et les conducteurs de phase et du rayon équivalent du conducteur rww pour un ou plusieurs conducteurs.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 Ob01844 571
909-3 O IEC: 1995 -29-
For a short circuit at a tower T remote from the stations A, B and C, the total earth current is given by:
The earth potential at the tower at which the short circuit occurs is given by
If on a line with an earth wire, a line-to-earth short circuit occurs on a tower in the vicinity of a station, a large fraction of the line-to-earth short-circuit current may flow back to the station via the earth wire. The fraction flowing through the earth, in this case, may be smaller than that, calculated from equation (20). Determination needs special consideration, when the distance between the station B and the short-circuited tower T is small, compared with the far-from-station distance D,.
The current through earth in station B in the case of a line-to-earth short circuit in F is found from figure 5 as
The earth current kB for a line-to-earth short circuit occuring on the overhead line may be greater than for a line-to-earth short circuit inside the station B.
3.1.4 Reduction factor for overhead lines and cables
The following equations are given for overhead lines with earth wires. They are valid also for cables with metallic sheaths, shielding or armouring earthed at both ends. The reduc- tion factor for an earth wire is given by
ZtWL and ZfW are dependent on soil resistivity p, distance between the earth wire and the line conductors and equivalent conductor radius rww for one or more conductors.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 Oh01845 408 =
, >8 500 4 650 ... 8 500 2 690 ... 4 650 1 200 ... 2 940 710 ... 1 200 600 ... 850 270 ... 600 <380
- 30- 909-3 o cEI:1!395
Tableau 2 - Résistivité p et profondeur équivalente de pénétration dans la terre 6 pour différents types de sol
Types de sol Résistivité p en Qm
Granit Rochers Sol pierreux Cailloux, sable sec Sol calcaire, sable humide Terre agricole Argile, glaise Sol marécageux
>10 o00 3 o00 ... 10 000 1 000 ... 3 o00 200 ... 1 200
70 ... 200 50 ... 100 10 ... 50
<20
Profondeur équivalente de pénétration dans la terre 6 en m
à 50 Hz I B 60 Hz
>9 300 5 100 ... 9 300 2 940 ... 5 100 1 320 ... 3 220 780 ... 1320 660 .. 930 295 ... 660
<415
Le facteur de réduction peut &re évalué à partir de la figure 6 en utilisant le tableau 2. Les équations ci-après peuvent être utilisées pour un calcul détaillé du facteur de réduction.
L’impédance linéique du câble de garde est
z& = RW+ - 8 2x
avec 0’05 Cl/km pour 50 Hz
0.06 n/km pour 60 Hz 8
et l’impédance mutuelle linéique entre le câble de garde et les conducteurs de phase parallèles, avec retour commun par la terre
avec la profondeur équivalente de pénétration dans la terre conformément au tableau 2 1,85 6 = I
Les définitions suivantes s’appliquent:
RW ‘W
d W
rww
Résistance linéique du câble de garde Rayon du cable de garde Distance entre les cables de garde Rayon équivalent du câble de garde pour un cable de garde: rww = rw
pour deux cables de garde: rww = drw - dw
n Nornbre.de câbles de garde
dWL Distance moyenne géométrique entre le cable de garde et les conducteurs de phase L1, L2 et L3
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
909-3 O EC1995
4 8 4 4 8 9 3 Ob03846 344
- 3 1 -
Table 2 - Resistivity p and equivalent earth penetration depth 6 for different soil types
Soil types
Granite Rocks Stony soil Pebbles, dry sand Calcareous soil, wet sani Farm land Clay, loam Marshy soil
Resistivity p in Rm
>10 o00 3 o00 ... 10 000 1 O00 ... 3 o00 200 ... 1 200 70 ... 200 50 ... 100 10 ... 50 <20
Equivalent earth penetration depth 6 in m
for 50 Hz
>9 300 5 100 ... 9 300 2 940 ... 5 100 1 320 ... 3 220 780 ... 1320 660 .. 930 295 ... 660
<415
for 60 Hz
>8 500 4 650 ... 8 500 2 690 ... 4 650 1 200 ... 2 940 710 ... 1 200 600 ... 850 270 ... 600 <380
The reduction factor can be estimated from figure 6 using table 2. For detailed calcula- tions of the reduction factor the following equations can be used.
The earth wire impedance per unit length is
with 0.05 f2bn for 50 Hz
8 0.06 n/km for 60 Hz
and the mutual impedance per unit length between the earth conductors with common earth return
~ ' ~ ~ = W p o +ja& in - 6 8 2lc dWL
with the equivalent earth penetration depth according to table 2 1-85 6 =
The following definitions apply
ru, 'W Earth wire radius dW Distance between earth wires rw Equivalent earth wire radius
Earth wire resistance per unit length
for 1 earth wire: rww = rw
wire and the parallel line
(25)
for 2 earth wires: rww = drw dw n Number of earth wires
dWL Geometric mean distance between the earth wire and and L3
the line conductors L1, L2
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
~~~~
m 4844893 Ob03847 280
pour un
- 32- 909-3 O CEIz1995
6 pour deux cables de garde: dwL = \I dwlL1- LIwlL2 - dwlL3 dw2L1 - dw2L2 . dw2L3
Constante magnétique: po = 4 ~ . 1 0 ’ ~ Vs/Am Perméabilité relative du cable de garde Câbles aluminium-acier (Al-Ac) avec une couche d’aluminium: p, = 5 ... 10 Autres câbles Ai-Ac: p, = 1 Cables d’acier: pr= 75 Résistivité du sol selon le tableau 2
o milsation: o = 2nf
PO
Pr
P D’après les équations (23) à (25). la facteur de réduction des cables de garde Al-Ac usuels dépend de la résistivité du sol. La figure 6 montre par exemple la valeur du facteur de réduction du câble de garde pour des cables de garde non magnétiques et pour différents types de lignes aériennes de tension nominale 60 kV à 220 kV. Dans le cas de lignes aériennes comportant un ou deux cables de garde en acier, la valeur du facteur de réduc- tion devient respectivement d’environ 0’95 et 0,90.
10 2 4 6 8100 2 4 6 8 1 0 0 0 2 4 6 810000
p -am Cu 8 r n
Figure 6 - Valeur absolue I L I du facteur de réduction pour des câbles de garde non magnétiques en fonction de la résistivité p du sol
Dans le cas de câbles d’énergie, le facteur de réduction dépend également du type et des dimensions de la gaine, de l’écran et de l’armure, conformément aux pratiques et aux nor- mes nationales. Des indications peuvent être trouvées dans les manuels des fabricants.
Pour des câbles unipolaires, le. facteur de réduction E est donné par
R‘, et Z’, dépendent du métal de la gaine, des armures et du diamètre du conducteur. La calculation de Z’, est à l’étude.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
= 4844871 Ob01848 117
909-3 O IEC1995 - 33-
o
PO pr
Angular frequency: o = 2zf Magnetic constant: po = 4x~lO-~ Vs/Am Relative permeability of earth wire Aluminium core steel reinforced (ACSR) wires with one layer of aluminium:
Other ACSR wires: pr= 1 Steel wires: p, = 75 Soil resistivity according to table 2
pr= 5 ... 10
P
According to equation (23) to (25). the reduction factor of usual ACSR earth wires de- pends on earth resistivity. As example, figure 6 shows the magnitude of earth-wire reduc- tion factors for non magnetic earth wire for different types of overhead lines with nominal voltages 60 kV to 220 kV. In case of overhead lines with 1 and 2 earth wires of steel, the magnitude of the reduction factor becomes about 0.95 and 0,90 respectively.
In the case of power cables, the reduction factor also depends on the type and size of sheath, shielding and armouring in compliance with the national techniques and standards. Data may be taken from manufacturer's handbooks.
For single-core cables the reduction factor 1 is given by
R', and ZlS depend on sheath metal, armour, conductor diameter. Calculation of ZtS is under consideration.
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
m 4844891 Ob01849 053 m
-34-
Annexe A (informative)
909-3 O CEIz1995
Exemple de calcul de deux court-circuits monophasés s¡multant% séparés à la terre
Q
>,////,////// / I , /////////////
Figure A.l - Deux court-circuits monophasés simultanés séparés à la terre sur une ligne alimentée en antenne, voir tableau 1
A.1 Données
Tension nominale: U,, = 66 kV
Fréquence nominale: 50 Hz Neutres des transformateurs isolés ou mis à la terre par bobine d’extinction Impédance équivalente au point de raccordement de l’alimentation Q: Courant de court-circuit symétrique initial dans le poste d’alimentation (voir CE1 909)
= (1.5 + j 15) R
1.1 x 66 kV
cl15 + j 151 R IrQ = = 2’8 kA
Ligne aérienne: conducteurs câble de garde
3 x 1 x 166/88 mm2 Ai-Ac
1 x 49 mm2 Ac, diamètre 9 mm
distance moyenne géométrique entre le câble de garde et les conducteurs de phase impédance linéique de la ligne:
dwL= 6 m
qi1 = (0,17 + j 0.40) R / km
= (0,32 + j 1,40) R / km
directe homopolaire
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4 8 4 4 8 9 3 Ob03850 875
909-3 O IEC: 1995 -35-
Annex A (informative)
Example for the calculation of two separate simultaneous single-phase line-to-earth short-circuit currents
L1 L2 I3
Q A
' / Y / / / / / / / / / / / / / / / / / / / / / / / Y / /
IEC 821195
Figure A.l - Two separate simultaneous single phase line-to-earth short circuits on a single fed radial line, see table 1
A.l Data
Nominal voltage: U,= 66 kV
Nominal frequency: 50 Hz Transformer neutrals isolated or resonant earthed Equivalent impedance of the network at the feeder connection point Q: %= (1.5 + j 15) S2
Initial symmetrical short-circuit current in the feeding station (see IEC 909)
1.1 x 66 kV
611.5 + j 151 Q ILQ = = 2.8 kA
Overhead line: conductors earth wire
geometric mean distance between the earth wire and the line conductors line impedance per unit 1en;th:
positive-sequence zero-sequence
3 x 1 x 166/88 mm2 ACSR 1 x 49 mm2 steel, diameter 9 mm
* p, = 75 p=- 1 Q- mm2 7 m
d,,= 6 m
qll = (0,17 + j 0,40) Q / km Go, = (0,32 + j 1.40) Q /km
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 Ob01851 701
- 36-
0.05 + j 0,39
2.97 + j 2,02 r = l i -
909-3 O CEk1995
= 0,93
résistivité du sol rocheux profondeur équivalente de pénétration dans le sol
p = 1 O00 Rm 6 = 2 940 m, selon tableau 2
résistance de pied de pylône R,= 10R distance entre pylônes
A.2 Calculs
dT= 300 m
Impédance linéique du câble de garde par unité de longueur conformément a l'équation (24)
1 2 940 m
4,s mm
1000 Qmm* R
7x49 mm2km km Z& =- + 0.05 - + j 314 s-' x
a = (2.97 + j 2.02) -
km
Impédance mutuelle linéique entre le câble de garde et les conducteurs de phase parallèles, avec retour commun par la terre, conformément à l'équation (25)
R 45c. lo4 Rs 2 940 m R Z'WL = 0,05 - + j 314 s-l x - In = (0.05 + j 0'39) -
6 m km km 2 x km
Impédance d'entrée conformément à 1 'équation (1)
4 x l O R
(2,97 + j 2,02) W m x 0,3 km I = - x 0 , 3 k m x (2,97 + j 2.02) R
2 km & =
= (3.6 + j 1.3) R
Pour le calcul du courant maximal de deux court-circuits monophasés simultanés sépads à la terre, les impédances des pylônes sont négligées.
L'équation (6) du tableau I donne 3 x 1,l x 66 kV
(14.1 + 3,4 + 3.2) R + j (102 + 8 + 14) f¿ = (285 - j 1 709) A I" -
-kEE -
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
m 4844891 0601852 648 m
0.05 + j 0.39
2.97 + j 2,02 r = / i -
909-3 O IEC1995
= 0,93
-37-
stony soil resistivity equivalent earth penetration depth tower footing resistance tower distance
p = 1000 Rm 6 = 2 940 m from table 2
R T = 10 Sz
dT = 300 m
A.2 Calculations
Earth wire impedance per unit length according to equation (24)
1 2 940 m
4.5 mm
1000 Qmm* sz Z& =- + 0.05 - + j 314 s-' x
n = (2.97 + j 2.02) -
kin
7x49 m m * h km
Mutual impedance per unit length between the earth wire and the parallel line conductors with common earth return according to equation (25)
n 4 ~ . 1 0 - ~ ns 2 940 m R Z'w,= 0.05 - + j 314 s-' x - x in = (0,05 + j 0.39) -
km 2n km 6 m km
Driving point impedance according to equation (1)
4 x 1 0 n
(2,97 + j 2.02) Q/km x 0,3 km I = - -x0,3kmx (2.97 + j 2.02) C2
2 km
- z p -
= (3.6 + j 1.3) R
For calculation of the maximum two separate simultaneous single phase line-to-earth short-circuit current, the tower impedances are disregarded.
Equation (6) of table 1 gives 3 x 1.1 x 66 kV
(14.1 + 3.4 + 3.2) 52 + j (102 + 8 + 14) R -kEE I" - - = ( 2 8 5 - j 1709)A
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
~ ~~ ~
4844891 Ob01853 584
-38- 909-3 O CEI:1995
ou
64,,, = 6[(1,5 + j 15)
2 q I l r = 2 x 10 km (0.17 + j 0.40)- = (3,4 + j 8) $2
qoir
R + 5 km (0.17 + j 0.40) - ] = (14.1 + j 102) R km a
km n = 10 km (0,32 + j 1,4) - = (3.2 + j 14) R km
Le courant à la terre à travers les résistances du pied des pylônes aux points des court- circuits A et B est déterminé conformément à l’équation (1 1)
13,6+ j 1.31 i2
l(3.6 + j 1.3) $2 + 2 x 10 i21 1, = 0.93 x 1733 A x = 261 A
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
~
4844893 Ob01854 410
909-3 O IEC1995 - 39-
where
64,), = 6[(1,5 + j 15) f2 + 5 km(0.17 + j 0,40) -1 = (14.1 + j 102) R
R 2q1,, = 2 x 10 km (0,17 + j 0.40)- = (3.4 + j 8) R km
qo)r
R km
n km
= 10 km (0.32 + j 1,4) - = (3.2 + j 14)
The current to earth through the tower footing resistances at the short-circuit locations A and B is determined according to equation (1 1)
1, = 0.93 x 1733 A x 13.6 + j 131 n
((3.6 + j 1.3) i2 + 2 x 10 i21 = 261A
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 0601855 357
-40- 909-3 O CEIz1995
Annexe B (informative)
Exemples de calcul de courants de court-circuit partiels a travers la terre
Un réseau à 132 kV et à 50 Hz est figuré sur les figures B1 et B3. Les distances sont de 40 km entre les postes A et B et de 100 km entre les postes B et C.
B.l Données
Poste A:
impédance de court-circuit impédance homopolaire du transformateur
Poste B:
impédance de court-circuit impédance homopolaire du transformateur résistance du réseau de terre
Poste C:
impédance de court-circuit impédance homopolaire du transformateur
Ligne aérienne:
conducteurs de phase cable de garde 1 x 240/40 mm2 Al-Ac impédance directe linéique par phase impédance homopolaire linéique par phase résistivité du sol profondeur équivalente de pénétration dans le sol impédance linéique du cable de garde facteur de réduction du cable de garde résistance de pied de pylône
3 x 2 x 240/40 mm2 Al-Ac
- distance entre pylônes
2, = ( O + j 6,4) i2
Go), = (O + j 12) i2
2, = ( O + j 7,6) i2
qOlB = ( O + j 7 ) Q RE, = 5 Q
= (0,06 + j 0,298) Q/km = (0,272 + j 1,48) Q/km Gol
p =1000Qm 6 = 2 940 m, selon tableau 2
Z'w = (0,17 + j 0,801) Q/km I,= = k= = 0.6 - j 0,03 = 0,6 R,= 10 i2 dT=400m
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
~
4844873 ObOL85b 293
909-3 O IEC1995 -41 -
Annex B (informative)
Examples for the calculation of partial short-circuit currents through earth
A 132 kV, 50 Hz system is given as shown in figure B 1 and B3. The distances are 40 km between the stations A and B and 100 km between the stations B and C.
B.l Data
Station A:
short-circuit impedance zero-sequence impedance of the transformer
Station B :
short-circuit impedance
zero-sequence impedance of the transformer resistance of earth grid
Station C :
short-circuit impedance
zero-sequence impedance of the transformer
Overhead line:
line conductors 3 x 2 x 240/40 mm2 ACSR
earth wire 1 x 240/40 mm2 ACSR
positive-sequence line impedance per unit length zero-sequence line impedance per unit length soil resistivity equivalent earth penetration depth earth-wire impedance per unit length earth-wire reduction factor tower footing resistance tower distance
2, = ( O + j 7,6) Cl
= (0 + j 7) Q
RE, =5a
2, =(O+j21)hz
= ( O + j 2 0 3 Q
Z;,) Go) p = 1 0 0 0 n m 6 = 2 940 m from table 2
Z’w = ( 0 ~ 7 + j 0,801) R/km - rA= 4 = 5 = r = 0,6 - j 0.03 = 0,6
R , = 1 0 Q
d, = 4 0 0 m
= (0,06 + j 0,298) Rlkm = (0,272 + j 1,48) alkm
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4 8 4 4 8 9 1 O b 0 1 8 5 7 L 2 T
-42- 909-3 O CEI:1995
B.2 Premier cas: Calcul d’un courant de court-circuit monophasé it la terre dans un poste.
Un court-circuit monophasé à la terre se produit dans le poste B, comme indiqué sur la figure B1.
LWh Lwc Cible de garde . -...-.
f.. .- . . . ...-...
Figure B1 -Court-circuit monophasé à la terre dans le poste B. Schéma du réseau avec les postes A, B et C
F
CEi 82395
Figure B2 -Court-circuit monophasé à la terre dans le poste B. Systèmes direct, inverse et homopolaire avec les connections à l’emplacement F du court-circuit à l’intérieur du poste B
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844893 Ob01858
-43 -
B.2 Case 1: Calcul-tion of a line-to-earth short-circi
Obb
909-3 O IECz1995
t current in a s-ation
A line-to-earth short circuit occurs inside the station B as shown in figure B 1.
Lwc Earth wire
. . . .-e-, . . . . .. -2- - - . Q ~ O M r c 3 4 0 ~ Reference earth
Figure B 1 - Line-to-earth short circuit inside the station B. System diagram for stations A, B and C
P
Zero-sequence system
1 Figure B2 - Line-to-earth short circuit inside the station B. Positive-,
negative- and zero-sequence systems with connections at the short-circuit location F within the station B
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
= 4844891 Ob01859 T T 2 = -44- 909-3 O CEk1995
Le courant de court-circuit initial LFI peut être calculé d’après l’équation (29) de la CE1 909 à l’aide de la figure B 1 : -
e x 1’1 x 132 k V
2 - (0,222 + j 4,876) f2 + (0,115 + j 6,157) f2 L i I = = (555 - j 15789) A
OU
= q, = (0,222 + j 4,876) R
qo, = (0,115 + j 6,157) R
La composante homopolaire est donnée par
1 = I:, = (185 - j 5263) A
4,,, est la somme des courants de court-circuit partiels et
OU
qow = (75 - j 444) A = 450 A e-jsOp0
= (76 - j 4632) A = 4633 A e-jS9*l0
= (34 - j 187) A = 190 A e-jsO*Oo
Le courant total à travers la terre à l’emplacement F du court-circuit est, conformément aux équations (13a) et (13b)
IEtot= 3 - 0’6 - (109 - j 631) A = 1153 A e-jSo3O
La distance “loin du poste” DF est, conformément à l’équation (16)
400 m D F = 3 x f i x = 834 km
Re { (0,068 + j 0,320)Q )
Loin des postes, c’est à dire à une distance supérieure à Ia distance “loin du poste” DF, les courants dans le câble de garde des lignes aériennes sont, conformément aux équa- tions (17a) et (17b)
LwA = 0.4 x 3 x (75 - j 444) A = (90 - j 533) A = 541 A e-j*0940
0,4 x 3 x (34 - j 187) A = (41 - j 224) A = 228 A Lwc =
Les courants maximaux à travers la terre aux postes A et C sont
I,, = O,6 X 3 x 450 A = 810 A IEC= 0 , 6 X 3 X 190A = 342 A
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4844891 0601860 714 m
909-3 O IEC1995 -45 -
The initiai short-circuit current Ly, can be calculated according to IEC 909 equation (29) using figure B2.
6 x 1.1 x 132 k V
2 x (0,222 + j 4,876) i2 + (0,115 + j 6,157) R LZi = = (555 - j 15789) A
where = = (0,222 + j 4,876) R
&o) = (0.1 15 + j 6,157) !2
The zero-sequence component is given by
1 q0) = - 3
= (185 - j 5263) A
hol is the sum of the partial short-circuit currents and hOK where
= (75 - j 444) A = 450 A e-jso.40
kOm = (76 - j 4632) A = 4633 A e-fi9*lo
kor = (34 - j 187) A = 190 A e-J80*oo
The total current through earth at the short-circuit location F according to equations (1 3a) and (13b):
LEEtot = 3 x 0.6 x (109 - j 631) A = 1153 A e-j8'*'O
The far-from-station distance D, according to equation (1 6)
400 m
Re { \I (0,068 + J 0,320)Q ) D,= 3x 6 x = 8,54 km
Remote from the stations, Le. at a distance longer than the far-from-station distance D,, the currents in the earth wire of the overhead lines according to equations (17a) and (17b)
LWA - - 0,4 x 3 x (75 - j 444) A = (90 - j 533) A = 541 A e-j80*40
- 0,4 x 3 x (34 - j 187) A = (41 - j 224) A = 228 A e-j79*60 Lwc -
The maximum currents through earth in the stations A and C are
ìEA= 0,6 x 3 ~ 4 5 0 A = 810 A íEc= 0,6 x 3 x 190 A = 342 A
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
-46- 909-3 0 CEI: 1995
L’impédance d’entrée d’une ligne aérienne est, conformément à l’équation (1)
r 1 4 x loa
(0,068 + j 0,320) i2 z p = (0,068 + j 0,320) R ++\Il+
2
= (1,436 + j 1,305) R = 1,940 R d42*30
Les lignes aériennes venant des postes A et B sont raccordées aux barres lorsque le court- circuit se produit. L’impédance de mise à la terre du poste B est, conformément à l’équation (14)
1 = (0,684 + j 0,493) R = 0,843 S2 d35*80 -
2 ~ E B - + -
5 R (1,436 + j 1,305) R
et le potentiel de la terre est, conformément à l’équation (15)
aEB = 3 x 0.6 x (109 - j 631) A X (0,684 + j 0,493) R = 972 V e-j4*40
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
W 4844891 0603862 597 W
909-3 O IEC:1995 -47-
The driving point impedance of one overhead line according to equation (1)
r I 4 x 10R
(0,068 + j 0,320) C2 (0,068 + j 0,320) R
2 2, =
= (1,436 + j 1,305) R = 1,940 R d42*30
The overhead lines from stations A and C are connected to the bus where the short circuit occurs. The earth impedance of station B is according to equation (14):
1 ZEB = = (0,684 + j 0,493) R = 0,843 R d35*80
1 2 + - 5 R (1,436 + j 1,305) R
and the earth potential according to equation (15)
&B = 3 x 0,6 x (109 - j 631) A x (0,684 + j 0,493) R = 972 V
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
- 4 8 - 909-3 O CEI:1995
B 3 Deuxième cas: Calcul d’un courant de court-circuit monophasé à la terre en dehors d’un poste
Un court-circuit monophasé à la terre se produit en dehors des postes, sur un pylône T entre les postes B et C, à une distance de 60 km du poste B, comme indiqué sur la figure B3.
Câble de garde .-.- LWA LWA + LWB Lwc ,-<- . * . * ..<-e-. . ..
...A?-. ... . * .,-e-. . . . ... <-=-. ... ~ 3 4 ~ ) ~ Terre de rCfCrence Lc ( 3 4 0 ) ~ + 340)~)
Figure B3 - Court-circuit monophasé à la terre en dehors des postes A, B et C, sur le pylône T d’une ligne aérienne. Schéma du réseau pour les postes A, B et C
P
Ch’ 8 I W S
A
Système direct
Système invene
CU 8î3¡’35
Figure B4 - Court-circuit monophasé à la terre en dehors des postes A, B et C, sur le pylône T d’une ligne aérienne. Systèmes direct, inverse et homopolaire avec les connections à l’emplacement F du court-circuit
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
909-3 O IEC1995
rn 4844891 ObOLBb4 3bT rn
-49-
B.3 Case 2: Calculation of a line-to-earth short-circuit current outside a station
A line-to-earth short circuit occurs outside the stations at a tower T between station B and C, 60 km distant from station B as shown in figure B3.
Figure B3 -Line-to-earth short circuit outside the stations A, B and C at the tower T of an overhead line. System diagram for stations A, B and C -
P
IEC 819M *
41, =&, = 40, = 3 1 ~ " k l
I B kW Zero-sequence system
I
Figure B4 -Line-to-earth short circuit outside the stations A, B and C at the tower T of an overhead line. Positive-, negative- and zero-sequence systems with connections at the short-circuit location F
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
-50- 909-3 O CE111995
Le courant de court-circuit initial [yl peut &re calculé conformément à l'équation (29) de la CE1 909 à l'aide de la figure B4.
6 x 1,l x 132 kV
2 x (1.7 15 + j 13,660) R + (6,626 + j 43,332) R = = (500 - j 3489) A
OU
= z(zi = (1,715 + j 13,660) R
Go) = (6.626 + j 43,332) R
La composante homopolaire est plus petite que dans le premier cas
1 ko)= 7 cl = (167-j 1163)A
ho, est la somme des courants de court-circuit partiels kola et droit du pylône T sur la figure 4
sur les côtés gauche et
hola est la somme des courants de court-circuit partiels
I<o>A = (14 - j 45) A = 47 A
qolB = (72 -j 481) A = 486 A e-j81*50
Les courants à travers la terre dans les postes A, B et C sont
I,, = 0.6 x 3 x 47 A I,, = 0-6 X 3 X 486 A = 875 A
= 85 A
IEc= 0,6 X 3 X 642 A = 1156 A
Le courant total à travers la terre à l'emplacement F du court-circuit est, conformément à l'équation (20)
-j81.S0 lE,, = 0,6 x (500 - j 3489) A = (300 - j 2093) A = 21 14 A e
Les courants dans les câbles de garde des lignes aériennes, a une certaine distance des postes A, B et C et du Pylone T. sont
LW* = (1-r> 3kOlA = 0,4 x 3 x (14 - j 45) A = (16,8 - j 54) A = 57 A e-J72*70
LWA,B = (1-d (3k0,, + 3q0,) = 0.4 x 3 x (86 - j 526) A = (103 - j 631) A = 640 A e-j80*70
Lwc = (1-L) 3koIc = 0,4 x 3 x (81 - j 637) A = (97,2 - j 764) A = 770 A e-j*2*70
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
909-3 O IEC~1995 -51 -
The initial short-circuit current Ltl can be calculated according to equation (29) of IEC 909 using figure B4.
6 x 1.1 x 132 k V
2 x (1,715 + j 13,660) i 2 + (6,626 + j 43,332) Q Ly1 = = (500 - j 3489) A
where
= z(z, = (1,715 + j 13,660) R
&) = (6,626 + j 43,332) R
The zero-sequence component is smaller than that in case 1:
Ly, = (167-j 1163)A 1 &o>= 3
bo, is the sum of the partial short-circuit currents the tower T in figure B4.
and on the left and right side of
4,,b=40K= (81 - j 637) A = 642 A e -j82.8O
qoh= (86 - j 526) A = 533 A e-j80*70
I -(Ob is the sum of the partial short-circuit currents
The currents through earth in the station A, B and C are
I, , = 0.6 X 3 X 47 A = 85 A IEB = 0.6 x 3 x 486 A = 875 A I,,=0,6 X 3 x 642 A = 1156 A
The total current through earth at the short-circuit location F according to equation (20):
[E!Etot = 0,6 x (500 - j 3489) A = (300 - j 2093) A = 21 14 A e-J81v80
The currents in the earth wires of the overhead lines at some distance from stations A, B and C and tower T are:
LWA = (1-L) 3kOlA = 0,4 x 3 x (14 - j 45) A = (16,8 - j 54) A = 57 A e-j72*70
LWAB = (1-rJ (340)~ + 3qOlB) = 0.4 x 3 x (86 - j 526) A = (103 - j 631) A = 640 A e-J80*70
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
-52- 909-3 O CEI: 1995
Compte tenu de l’impédance d’entrée Z,, calculée comme dans le premier cas, et de l’impédance de pied du pylône RT, l’impédance totale de mise à la terre du pylône OU se produit le court-circuit devient, confonnément à l’équation (19)
1 - ET - = (0,704 + j 0,566) ZZ = 0,903 ZZ d38*80 1 2
10 SZ (1,436 + j 1,305) SZ
Le potentiel de la terre à l’emplacement F du court-circuit est, conformément à l’équation (21)
bT= (300 - j 2093) A x (0,704 + j 0,566) SL = (1396 - j 1304) V = 1910 V e-j43*00
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
9 Y 8 4 4 8 9 1 O b O L 8 b 8 TO5
909-3 o IEC: 1995 -53-
With the driving point impedance Z, as calculated in case 1 , and the tower footing impedance i?,, the total earth impedance of the short-circuit tower according to equation (19) becomes:
1 = (0,704 + j 0,566) R = 0,903 R &38*8a -
1 2 ET - + -
10 R (1,436 + j 1,305) R
The earth potential at the short-circuit location F according to equation (21)
bT= (300 - j 2093) A x (0,704+ j 0,566) R = (1396 - J 1304) V = 1910 V e -j43.0°
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
m 4 8 4 4 8 9 3 ObOL869 941
We at the IEC want to know how our standards are used once they are published. I The answers to this survey will help us to improve IEC standards and standard related
information to meet your future needs.
I Would you please take a minute to answer the survey on the other side and mail or fax to:
Customer Service Centre (CSC) International Electrotechnical Commission 3, rue de Varembé Case postale 131 121 1 Geneva 20 Switzerland
Fax to: CSC at +41 22 919 03 O0
Thank you for your contribution to the standards making process.
Nicht frankieren Ne pas affranchir
Non affrancare No stamp required
REPONSE PAYEE SUISSE
Customer Service Centre (CSC) International Electrotechnical Commission 3, rue de Varembé Case postale 131 121 1 Geneva 20 Switzerland
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
m 4844891 ObOL870 663 m
1.
No. of IEC standard:
........................ P.
Tell us why you have the standard. (check as many as apply). I am:
0 the buyer
0 the user a a librarian
0 a researcher
0 an engineer
0 a safety expert
0 involved in testing
0 with a government agency
0 in industry
0 other _ _ _ . _ _ _ _ . _ . ._._._ 3. This standard was purchased from:
......................... 4. This standard will be used (check as many as apply):
0 in a standards library
0 to develop a new product
0 to write specifications
0 to use in a tender
0 for educational purposes
0 for a lawsuit
0 for quality assessment
0 for cedification
0 for general information
0 for design purposes
0 fortesting
for reference
0 other ................ 5. This standard will be used in conjunction with (check as many as apply):
0 IEC
0 I S 0 a corporate
0 other (published by - - - - - . - - - . ) 0 other (published by ......... )
......... 0 other (published by 1
6. This standard meets my needs (check one):
0 not at ali a almost
fairly weil
0 exactly
~
7. Please rate the standard in the following areas as (1) bad. (2) below average, (3) average. (4) above average. (5) exceptional (O) not applicable:
0 clearly written
0 logically arranged
0 information given by tables
0 illustrations
a technical information
8. I would like to know how I can legally reproduce this standard for:
0 internai use
0 sales information
0 product demonstration
0 other .....................
13. If you said yes to 12 then how many volumes:
......................... 14. Which standards organizations published the standards in your library (e.9. ISO. DIN. ANSI, BSI. etc.):
......................... 15. My organization supports the standards- making process by (check as many as
0 buying standards aPPly):
using standards
0 membership in standards organizations
D sewing on standards development ~
9. committees In what medium of standard does your organization maintain most of its standards (Che& one): 0 other ..................
R paper
microíiim/microíiche
0 magtape
a CDROM
0 floppy disk
0 on line
SA. If your organization currently maintains part or all of its standards collection in electronic media please indicate the format(s).
0 raster image a iuii text
1 o. In what medium does your organization intend to maintain its standards collection in the future (check ail that apply):
0 microíiim/microíiche paper
Cb magtape
a CDROM
16. My organization uses (check one):
0 French text only
0 English text only
0 Both EnglisNFrench text
17. Other comments:
.............................
.............................
.............................
.............................
.............................
18. Please give us information about you and your company
name:.......
job title:
0 floppy disk
Cb on line
10A. For electronic media which format will be chosen ceimpany: - - . (check one):
0 raster image address: .......................
.................. .......................
0 fui1 text ..............................
11. My organization is in the following sector (ag. engineering, manufacturing) .............................. .................................. ..............................
12. Does your organization have a standards library:
r+ Yes
a No turnover/sales: ...................
No. employees at your location: .......
I I I I I I I I I I I I I I I I
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
4 8 4 4 8 9 3 0603873 5 T T
Enquête sur les normes
I -
a La CE1 se préocupe de savoir comment ses normes sont accueillies et utilisées. Les réponses que nous procurera cette enquête nous aideront tout à la fois à améliorer nos normes et les informations qui les concernent afin de toujours mieux répondre à votre attente.
Nous aimerions que vous nous consacriez une petite minute pour remplir le questionnaire joint que nous vous invitons à retourner au:
Centre du Service Clientèle (CSC) Commission Electrotechnique Internationale 3, rue de Varembé Case postale 131 CH1 21 1 - Genève 20 Suisse Télécopie: IEC/CSC +41 22 919 03 O0
Nous vous remercions de la contribution que vous voudrez bien apporter ainsi a
I I I I I I I a Norm ali sat i on I nt ern at i on ale.
I- 'I
Nicht frankieren Ne pas affranchir
Non affrancare No stamp required I
REPONSE PAYEE SUISSE
Centre du Service Clientèle (CSC) Commission Electrotechnique Internationale 3, rue de Varembé Case postale 131 CH1211 - Genève 20 Suisse
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
m 4844893 ObOitBï2 436 m
1.
Numéro de la Norme GEI:
.........................
2. Pourquoi possédez-vous cette norme? (plusieurs réponses possibles). Je suis:
l'acheteur
0 l'utilisateur
0 bibliothécaire
0 chercheur
0 ingénieur
0 chargé denectuer des essais
0 fonctionnaire &Etat
0 dans I'industrie
expert en sécurité
autres .................. -
3. Ou avez-vous acheté cette norme?
......................... 4.
Comment cette norme sera-î-elle utiliseo? (plusieurs réponsos possibles)
comme référence
dans une bibliothbque de normes
7. Nous vous demandons maintenant de donner une note A chacun des critères ci-dessous (1. mauvais; 2. en-dessous de Ia moyenne; 3. moyen: 4. au-dessus de la moyenne; 5. exceptionnel; O. sans objet)
clarté de la rédaction
0 logique de la disposition
0 tableaux informatls
0 illustrations 0 informations techniques
8. J'aimerais savoir comment je peux reproduire légalement cette norme pour: 0 usage interne
0 des démonstrations de produit
des renseignements commerciaux
0 autres .................... ~~ ~~
9. Quel support votre société utilise-l-elle pour garder la plupart des ses normes?
R papier
0 bandes magnétiques
0 CD-ROM
0 disquettes pour développer un produit nouveau 0 abonnement à un serveur électronique pour rédiger des spécifications
pour ut i ï i t ion dans une soumission
& des fins éducatives
pour un procès
pour une évaluation de la qualité
pour la certification
à titre d'information générale
pour une étude de conception
pour en ectuer des essais
pares. ................. 5. Cette norme est-elle appelée à être utilisée conjointement avec d'autres normes? Lesquelles? (plusieurs réponses possibles):
0 CE1
0 IS0
a autre (publiée par.. ........ 1 0 autre (publiée par. ......... 1
0 autre (publiée par.. ........ )
' 0 internes votre société
6.
Cette norme répond-elle à vos besoins?
0 pasdutout
0 àpeuprbs
0 asez bien
0 parfaitement
9A. Si votre société consewe en totalité ou en partie sa collection de normes sous forme électronique, indiquer la ou les formats:
0 format tramo (ou image bala* rine par i ¡ )
L b texte intégrai
10. Sur quels supports votre société prévoitslle de conserver sa collection de normes à I'avenir (plusieures réponses possibles):
a papier
0 microtiim/microfiche
a bande magnétique
0 CD-ROM
0 disquette
0 abonnement à un serveur électronique
î0A. Quel formal serait retenu pour un moyen électronique? (une seule réponse)
0 format tramé
0 texte intégrai
11. A quel secteur d'activité appartient votre société? (par ex. ingénierie. fabrication)
.................................. 12. Votre société possbde-1-elle une bibliothbque de normes? 0 oui
0 Non
13. En combien de volumes dans le cas affirmatif ?
......................... 14. Quelles organisations de normalisation ont publiées les normes de cette bibliothbque ? (ISO. DIN. ANSI, BSI. etc.):
......................... 15. Ma rocié10 apporle sa contribution & l'élaboration des normes par les moyens suivants (plusieurs réponses possibles):
0 en achetant des normes
Q en utilisant des normes
a en qualité de membre d'organisations
0 en qualité de membre de comités de
0 autres ..................
de normalisation
normalisation
16. Ma soCi616 utilise: (une seule réponse)
0 des normes en tranpis seulement
0 des normes en anglais seulement
0 des normes bilingues anghisnrançais
17. Autres observations:
................................
................................
................................
................................
................................
18. Pourriez-vous nous donner quelques informations sur vous-même et votre socWé?:
nom: ......................... fonction:. ......................
nom de la société:. ................
adresse: .......................
..............................
..............................
..............................
nombre d'employés:. ..............
chin re d'affaires: .................
I I I I I I I I I I I I I I I I
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
Publications de la CE1 préparées par le Comité d’Etudes no 73
781 (1989)
865: -Courants de cairt-circuit -Calcul des effets.
Guide d’appùcation pour le caicui des amrants de courtcirciiit dans les réseaux à basse tmsion radiaux.
M 4844873 Oh03873 372 =
865-1 (1993) 865-2 (1994) 909 (1988)
909-1 (1991)
909-2 (1992)
909-3 (1995)
Putie 1: Déhitiais et méthodes de dail Partie 2: Jkemples de dail Calad de-s courants de court-circuit dans les réaeaux triphasés i courant alternatif. Partie 1: F e u n pour le calcul des murants de court-ciraiit dans les réseaux alternatifs triphash donnément à la CEl W. Matériel éledique - Données pour le cald d e s anirants de court-cirnrit mnformánent à ia CE1 909 (1988). Pattie 3: Courants durant deux cuurt-circuits mono- phasés simultanés s6pa1-6~ à la terre et courants de court-circuit partiels s’écoulant à travers la terre.
IEC publications prepared by Technical Committee No. 73
781(1989)
865: - Shorttinwit currents - calculation of effects.
AlqAkatiai guide for calculation of shoa-cimit cunmts in low-voltage radial systems.
865-1 (1993) 865-2 (1994) 909 (1988)
909-1 (1991)
909-2 (1992)
909-3 (1995)
Part 1: Lkhitims and calculation methods. Pad 2: Examples of calallatial. Shortcimit current calailatiai in three-phase a.c. systcms.
Part 1: Factors for the calculation of short-cirarit cumts in three-phase ac systems amnimg to IEC 909. Eledncal equipment - Data for short-circuit cunmt calculations in accordana with iEC 909 (1988).
Pad 3: Currerils during two separate 8imultaneair single phase line-to-eaith short circuits and paitiai short-cimit currents flowing through earth.
Publication 909-3
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---
rn 4844893 ObO3Bï4 209 rn
Typeset and printed by the IEC Central Ofice GENEVA, SWITZERLAND
COPYRIGHT 2003; International Electrotechnical Commission
Document provided by IHS Licensee=/5902168001, User=, 06/28/2003 14:27:10 MDTQuestions or comments about this message: please call the Document PolicyManagement Group at 1-800-451-1584.
--`,,,````,``,,``,,````,,,`,-`-`,,`,,`,`,,`---