BW4BW5
Installation Instructions
Oil---Fired Cast IronHot Water Boilers
Sizes 140,000 through 280,000
NOTE: Read the entire instruction manual before starting theinstallation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1. . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explanation of Model Numbers and Rating Plate 3. . . . . . . . .
General Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locating the Boiler 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fresh Air for combustion 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boilers with Tankless Heater Coil 7. . . . . . . . . . . . . . . . . . . . .
Installation System Piping 8. . . . . . . . . . . . . . . . . . . . . . . . . . .
Chimney and Chimney Connection 10. . . . . . . . . . . . . . . . . . .
Electrical Wiring 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Equipment and Optional Accessories 10. . . . . . . . . . . . . . . . . .
Filling Boiler 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATING BOILER 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
To Start 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel Units and Oil Lines 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Supply for Combustion 13. . . . . . . . . . . . . . . . . . . . . . . . .
Draft Regulators 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Nozzles 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Final Burner Adjustments 13. . . . . . . . . . . . . . . . . . . . . . . . . .
Oil Burner Maintenance 15. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking and Adjusting Controls 16. . . . . . . . . . . . . . . . . . . .
MAINTENANCE 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relief Valve 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventional Expansion Tank 16. . . . . . . . . . . . . . . . . . . . . . .
Diaphragm Expansion Tank 16. . . . . . . . . . . . . . . . . . . . . . . . .
Water System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tankless Coil (or Cover Plate Gasket) 16. . . . . . . . . . . . . . . . .
Oil Boiler/Burner Cleaning Instructions 17. . . . . . . . . . . . . . . .
Sequence of Operation 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Hints 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASMEama
®
SAFETY CONSIDERATIONSInstalling and servicing heating equipment can be hazardous dueto oil and electrical components. Only trained and qualifiedpersonnel should install, repair, or service heating equipment.Untrained personnel can perform basic maintenance functionssuch as maintaining water level. All other operations must beperformed by trained service personnel. When working onheating equipment, observe precautions in literature, on tags, andon labels attached to or shipped with unit and other safetyprecautions that may apply. Recognize safety information. This isthe safety--alert symbol . When you see this symbol on unit or ininstructions and manuals, be alert to potential for personal injury.Understand the signal words DANGER, WARNING,CAUTION, and NOTE. These words are used with thesafety--alert symbol. DANGER identifies the most serioushazards which will result in severe personal injury or death.WARNING signifies hazards which could result in personalinjury or death. CAUTION is used to identify unsafe practiceswhich may result in minor personal injury or product andproperty damage. NOTE is used to highlight suggestions whichwill result in enhanced installation, reliability, or operation. Readand obey the following rules to ensure safe installation andoperation:
1. Read the Owner’s Manual carefully for safe operation.Failure to follow the rules of safe operation and theinstructions can cause amalfunction of the boiler and result in death, seriousbodily injury, and/or property damage.
2. Check local codes and utility requirements beforeinstallation. The installation must be in accordance withtheir directives, or follow NFPA 31–Installation of OilBurning Equipment, latest revision.
3. Before servicing, allow boiler to cool. Always shut off anyelectricity and oil to boiler when working on it. Thisprevents any electrical shocks or burns.
4. Inspect oil line and connections for leaks.
5. Be certain oil burner nozzle is size required. Overfiringwill result in early failure of boiler sections. This causesdangerous operation.
6. Never vent this boiler into an enclosed space. Always ventto the outside. Never vent to another room or inside abuilding.
2
A02217
Fig. 1 -- Model BW4/BW5
7. Be sure there is adequate air supply for completecombustion.
8. Follow a regular service and maintenance schedule forefficient and safe operation.
9. Keep boiler area clean and free from combustiblematerials, gasoline, and other flammable vapors andliquids.
10. Oil Burners are not do--it yourself items. This boiler mustbe installed and serviced by qualified professionals usingcombustion test instruments.
11. Be aware when piping the relief valve that if the systempressure exceeds the safe limit of 30 pounds per squareinch, the relief valve will automatically lift open. Lifting ofthe relief valve can discharge large quantities of steam andhot water, which may damage the surroundings. Beforeinstalling the relief valve read the manufacturer’sinstructions and maintenance section of the manual onrelief valves.
12. Installation and sizing of the expansion tank must considerthe heating systems total water volume, temperature, boilerinitial fill pressure, and system arrangement. Animproperly installed and sized expansion tank may resultin frequent lifting of the relief valve or other heatingsystem problems. For proper installation, sizing, andmaintenance of the expansion tank follow the guidelinesestablished by the boiler manufacturer and the expansiontank manufacturer.
13. Expansion tank performance and life expectancy can behindered by overfilling the boiler. An initial fill pressure of10.12 psig is recommended. For higher fill pressures theexpansion tank’s air charge will need to be increased tomatch the fill pressure. Consult the manufacturer’sguidelines for sizing and selection.
14. Purging the heating system of air and gases when firstputting the boiler into service is critical for propercirculation and quiet performance. Once the air and gases
are purged, for boiler installations using float type vents,the air vents should be closed for normal operation. If airis heard or noticed by loss of heat, purge the system andopen the vents for a short period of time.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury, death and or property damage.
Use only number 1 or number 2 fuel oil having commercialstandard grade CS 12--48. Do not use gasoline, kerosene,crankcase oil, or any oil containing gasoline.
! WARNING
OPERATION ANDWARRANTY HAZARD
Failure to follow this warning could result in personalinjury, death and or property damage.
This boiler has been designed for residential installations. Ifused for commercial applications, all jurisdictionalrequirements must be met. This may require wiring and/orpiping modifications. The manufacturer is not responsiblefor any changes to original design.
! WARNING
BW4/BW5
3
A 19 5/8″
GAGE
36″1 1/4 IN. RETURN
1 1/4 IN. SUPPLY
AQUASTATCONTROL(WITHOUT COIL)
AQUASTATCONTROL(WITH COIL) TANKLESS
HEATER1/2 IN. N.P.T.
9″
C B
3/4 IN.ASMERELIEF VALVE
FRONT SIDE REAR
A96152
Fig. 2 -- Dimensional Drawing (See Table 1 for additional information)
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury, death and or property damage
DO NOT USE GASOLINE CRANKCASE DRAININGSOR ANY OIL CONTAINING GASOLINE.
! WARNING
INTRODUCTIONCheck to be sure boiler size is correct before starting installation.See rating and capacity table shown in Fig. 2 and Table 1a and1b. Check rating plate on right side of boiler.
The boiler must be supplied with the proper oil, fresh air forcombustion, and a suitable electrical supply. Boiler must also beconnected to a suitable venting system and an adequate pipingsystem. Finally, a properly located thermostat is needed forcontrol of heating system. If there are any doubts as to the variousrequirements, check with local authorities and obtain professionalhelp where needed. The Operating Boiler Instructions and FinalChecks and Adjustments sections later in this document are vitalto the proper and safe operation of the heating system. Take timeto be sure they are all done.
The following steps are all necessary for proper installation andsafe operation of boiler:
1. LOCATING THE BOILER
2. OIL SUPPLY AND PIPING
3. FRESH AIR FOR COMBUSTION
4. PIPING CONNECTIONS
5. CHIMNEY AND VENT PIPE CONNECTIONS
6. ELECTRICAL WIRING
7. THERMOSTAT LOCATION
8. CHECKING AND ADJUSTING
9. MAINTENANCE
FIRE, EXPLOSION, ELECTRICAL, CARBONMONOXIDE POISONING HAZARD
Failure to follow this warning could result in propertydamage, personal injury, or death.
Improper installation, adjustment, alteration, servicemaintenance, or use can cause carbon monoxide poisoning,explosion, fire, electrical shock, or other conditions whichmay cause personal injury or property damage. Consult aqualified installer, service agency, fuel oil supplier, or yourdistributor or branch for information or assistance. Thequalified installer or agency must use onlyfactory--authorized and listed kits or accessories whenmodifying this product.
! WARNING
Explanation of Model Numbers and Rating Plate
Each model number except for the BW4(5)RAH280ABAA has 3possible firing rates depending on which nozzle or burner isinstalled. The model number represents the burner installed in theboiler and the largest possible input for the boiler. TheBW4(5)RAH280ABAA can only be fired at an input of 280,000Btuh or 245,000 Btuh.
For example, a BW4BAH000140ABAA has a Beckett burnerand a maximum input of 140,000 Btuh. A BW4RAH000140 hasa Riello burner and a maximum input of 140,000 Btuh. Therating plate for each model shows the possible firing rates. Boilerscome shipped with the largest nozzle installed. By changingnozzles, the BW4BAH000140ABAA firing rate can be changedto 91,000 or 105,000 Btuh input.
For BW4BAH models equipped with Beckett burners:
The BW4BAH000280ABAA is shipped with 2 additionalnozzles to fire the Beckett burner at the alternate inputs listed onthe rating plate. The BW4BAH000210ABAA andBW4BAH000140ABAA are shipped with one additional nozzleeach, to fire the Beckett burner at the next lowest inputs listed onthe rating plate. To fire the BW4BAH000210ABAA andBW4BAH000140ABAA at the lowest inputs listed on the ratingplate, an accessory low--fire kit for each boiler, not included withthe boiler, is required. The low--fire kits include the alternate sizenozzle and the alternate burner end cone to fire the burners onthese models at the lowest inputs for those models.
BW4/BW5
4
For BW4RAH models equipped with Riello burners:
There are two different Riello burners used on the BW4RAHboilers, the F5 and F10 burner. The BW4RAH000280AAAA isshipped with one additional nozzles to fire the F10 burner at thenext alternate lower input listed on the rating plate. TheBW4RAH000210AAAA and BW4RAH000140AAAA areequipped with F5 burners and shipped with two additionalnozzles to fire the boilers at the next lowest inputs listed on therating plate.
The BW5B and BW5R models are the same as the BW4B andBW5B models, except the tankless water heater is factoryinstalled.
Refer to Tables 1 and 7 (Beckett) or Table 8 (Riello) foradditional oil burner information. Refer to the boiler product datasheet for the correct accessory low--fire kit.
General InformationBoilers with the same number of sections are identical to eachother except for their firing rate and/or type of burner. The firingrate is determined by the nozzle size used in the oil burner and theoil pressure at the nozzle. For example, models BW4RAH091,BW4RAH105, and BW4RAH140 are the same boiler, without atankless coil. They all have a Riello oil burner fired at a differentinput rate. Models BW5RAH245 and BW4RAH280 are the sameboiler, with a tankless coil. They both have a Riello oil burnerfired at a different input rate.
1. Check to be sure you have selected the right size boilerwith the proper capacity. The I=B=R rating of the boilerselected should be greater than or equal to the calculatedpeak heating load (heat loss) for the building or area(s)served by the boiler and associated hot water heatingsystems. (See Table 1.) Any heat loss calculations usedshould be based on approved methods.
2. Boiler must be supplied with the proper oil supply and oilpiping, sufficient fresh combustion air, and a suitableelectrical supply.
3. Boiler must be connected to a suitable venting system anda piping system adequate to distribute the heating load.
4. A thermostat must be properly located and installed forcontrol of the heating system.
If there are any doubts as to the various requirements, check withlocal authorities and obtain professional help where needed. TheOperation Instructions, Final Checks and Adjustments andMaintenance sections in this manual are vital to the proper andsafe operation of the heating system. Take the time to be sure theyare all done.
Locating the BoilerIf boiler is part of a planned heating system, locate it as close aspossible to where it is shown on plan. If boiler is to be part of anexisting system, it is usually best to put it where the old one was.
If location is to be changed, additional materials as well as anadequate base will be required. The following rules apply:
1. The boiler must be level.
2. Use a raised base if floor can become wet or damp.
3. These boilers must have a non--combustible base ifinstalled on a combustible floor. Two inch concrete patioblocks or a 2--in. Cladlite--pad may be used.
4. The vent pipe connection should be as short as possible.
5. Maintain clearances for fire safety as well as servicing.Refer to Fig. 3 for minimum clearances. An 18--in.clearance must be maintained at a side where passage isrequired to access another side for cleaning, servicing,inspection, or replacement of any parts that normally mayrequire such attention. Boilers must be installed at least6--in. from combustible materials on all sides and above.Allow at least 24--in. front clearance for servicing. Allowat least 18--in. right--side clearance for servicing boilersequipped with a tankless coil.
6. Fresh air for combustion must be available at front ofboiler. Fresh air for ventilation must be available to frontAND rear of boiler. Air passages must be free ofobstructions at all times. Ventilating and combustion airmust enter boiler room without restrictions.
7. Be sure installation is in accordance with the requirementsof local authorities having jurisdiction. Compliance withthese regulations is required. In the absence of local codes,follow NFPA 31--Installation of Oil Burning Equipment.
INSTALLATIONInstallation RequirementsRefer to Fig. 4 for the basic requirements of a typical installation.
NOTE: Always keep manual fuel supply valve shut off if burneris shut down for an extended period of time.
Fresh Air for Combustion
���������������
24″ MIN 6″
6″ MIN
6″ MIN�18″ WITH COIL
BOILER�FRONT
A95592
Fig. 3 -- Minimum Clearance Dimensions
BW4/BW5
5
TO OUTSIDE
OILFILTER
SHUTOFFVALVE
OILTANK
VENT PIPE
OIL BURNER
OIL LINES
VENT PIPEMINIMUM 2 IN. ID
2 IN. FILL PIPE
AUTOMATICFILL VALVEAND SHUTOFF
DIAPHRAGMEXPANSION TANK
DRAFTREGULATOR
FOUNDATIONS
ELECTRIC LINESERVICE LINE
ENTRANCESWITCH
OVERCURRENTPROTECTEDSAFETY SWITCH
LINES TO OTHERAPPLIANCES
CHIMNEY
FROM RADIATION
RELIEF VALVE
TO RADIATION
CIRCULATING PUMPIN SUPPLY LINES
A02230
Fig. 4 -- General Principal Requirements for a Typical Installation
Table 1 – Boiler Ratings and Capacities
WITHOUTTANKLESSCOIL
NO.SEC
INPUT*MBH
**HEATINGCAPACITY*MBH
NETI=B=RRATING*MBH
FIRINGRATEGPH
A.F.U.E.MIN.
CHIMNEYSIZE/HEIGHT
DIMENSIONS--- INSHIPPINGWEIGHT
TANKLESSHEATERG.P.M.H W D
BW4BAH140BW4RAH140
3 91 80 70 0.65 #86.3 8” X8” X15’ 14 1/2 6 8 460 N/A3 105 92 80 0.75 #85.2 8” X8” X15’ 14 1/2 6 8 460 N/A3 140 119 103 1.00 83.4 8” X8” X15’ 14 1/2 6 8 460 N/A
BW4BAH210BW4RAH210
4 126 111 97 0.90 #86.0 8” X8” X15’ 17 3/4 6 9 5/8 533 N/A4 175 150 130 1.25 83.9 8” X8” X15’ 17 3/4 6 9 5/8 533 N/A4 210 178 155 1.50 82.4 8” X8” X15’ 17 3/4 6 9 5/8 533 N/A
BW4BAH280BW4RAH280
5 }168 147 128 1.20 #86.5 8” X8” X15’ 21 6 11 1/2 620 N/A5 245 209 182 1.75 83.6 8” X8” X15’ 21 6 11 1/2 620 N/A5 280 236 205 2.00 82.0 8” X8” X20’ 21 6 11 1/2 620 N/A
Shaded areas are as shipped. Alternate inputs require a field---installed alternate oil nozzle supplied with base model.* MBH = 1,000 BTU per hour/BTU=British Thermal Unit** Heating Capacity is based on a 13 percent CO2 with a ---0.02 in. wc draft over fire and a #1 smoke or less. Testing was done in accordance with the D.O.E.(Departmentof Energy) test procedure.+ GPH = Gallons per hour of oil at 140,000 BTU per gallon++ A.F.U.E. = Annual Fuel Utilization Efficiency based upon D.O.E. test procedure# As an Energy Star Partner, the manufacturer has determined that this product meets Energy Star guidelines for Energy Efficiency} The 168,000 Btuh input is only available with a Beckett burner.
BW4/BW5
6
Table 1 -- Boiler Ratings and Capacities (Cont.)
WITH TANK-LESS COIL
NO.SEC
INPUT*MBH
**HEATINGCAPACITY*MBH
NETI=B=RRATING*MBH
FIRINGRATEGPH
A.F.U.EMIN.
CHIMNEYSIZE/HEIGHT
DIMENSIONS--- INSHIPPINGWEIGHT
TANKLESSHEATER##G.P.M.H W D
BW5BAH140BW5RAH140
3 91 80 70 0.65 #86.3 8” X8” X15’ 14 1/2 6 8 470 2.903 105 92 80 0.75 #85.2 8” X8” X15’ 14 1/2 6 8 470 3.003 140 119 103 1.00 83.4 8” X8” X15’ 14 1/2 6 8 470 3.25
BW5BAH210BW5RAH210
4 126 111 97 0.90 #86.0 8” X8” X15’ 17 3/4 6 9 5/8 545 3.154 175 150 130 1.25 83.9 8” X8” X15’ 17 3/4 6 9 5/8 545 3.504 210 178 155 1.50 82.4 8” X8” X15’ 17 3/4 6 9 5/8 545 3.75
BW5BAH280BW5RAH280
5 }168 147 128 1.20 #86.5 8” X8” X15’ 21 6 11 1/2 620 N/A5 245 209 182 1.75 83.6 8” X8” X15’ 21 6 11 1/2 630 4.005 280 236 205 2.00 82.0 8” X8” X20’ 21 6 11 1/2 630 4.25
Shaded areas are as shipped. Alternate inputs require a field---installed alternate oil nozzle supplied with base model.* MBH = 1,000 BTU per hour/BTU=British Thermal Unit** Heating Capacity is based on a 13 percent CO2 with a ---0.02 in. wc draft over fire and a #1 smoke or less. Testing was done in accordance with the D.O.E.(Departmentof Energy) test procedure.+ GPH = Gallons per hour of oil at 140,000 BTU per gallon++ A.F.U.E. = Annual Fuel Utilization Efficiency based upon D.O.E. test procedure# As an Energy Star Partner, the manufacturer has determined that this product meets Energy Star guidelines for Energy Efficiency# # Gallons of water per minute, heated from 40˚F to 140˚F, with 200˚F boiler water temperature, intermittent draw.} The 168,000 Btuh input is only available with a Beckett burner.
Table 2 – Fresh Air Duct for Tightly Sealed House
FRESH AIR DUCT SIZE (IN.) 1/4–IN. MESH SCREEN (BTUH) WOOD LOUVERS (BTUH) METAL LOUVERS(BTUH)
3---1/2 X 12 144,000 36,000 108,0008X8 256,000 64,000 192,0008X12 384,000 96,000 288,0008X16 512,000 128,000 384,000
FIRE AND CARBON MONOXIDE POISONINGHAZARD
Failure to follow this warning can cause personal injury ordeath.
Be sure to provide enough fresh air for combustion.Enough air ensures proper combustion and ASSURESTHAT NO HAZARD WILL DEVELOP DUE TO LACKOF OXYGEN.
! WARNING
UNIT LIFE REDUCTION HAZARD
Failure to follow this warning could result in personalinjury, death and or property damage.
Air for combustion must not be contaminated by halogencompounds, which include fluoride, chloride,bromide, andiodide. These elements are found in aerosol sprays,detergents, bleaches, cleaning solvents, salts, air fresheners,and other household products.
! WARNING
Enough fresh air must be provided to assure proper combustion.The fire in the boiler uses oxygen. It must have a continuoussupply. The air in a house contains only enough oxygen to supplythe burner for a short time. Outside air must enter the house toreplace that used by the burner. The exact fresh air requirementsdepend on whether the boiler is located in an unconfined orconfined space.
CARBON MONOXIDE POISONING AND UNITOPERATION HAZARD
Failure to follow this warning could result in personalinjury, death and or property damage.
If a fireplace or a kitchen or bathroom exhaust fan is used,an outside air intake should be installed. These devices robthe boiler and water heater of combustion air.
! WARNING
A. Boiler Located in Unconfined SpaceAn unconfined space is defined as a space with volume not lessthan 50 cu ft.. per 1000 Btuh of total input rating of all appliancesinstalled in that space.
If boiler is in an open area (unpartitioned basement) in aconventional house, air that leaks through cracks around doorsand windows will usually be adequate to provide air forcombustion. The doors should not fit tightly. Cracks aroundwindows should not be caulked.
B. Boiler Located in Confined SpaceALL AIR FROM INSIDE BUILDING
The confined space shall be provided with 2 permanent openingscommunicating directly with an additional room(s) of sufficientvolume so that the combined volume of all spaces meets thecriteria for an unconfined space. The total input of all combustionequipment installed in the combined space shall be considered inmaking this determination. Each opening shall have a minimumfree area of 1 sq.. in. per 1000 Btuh of total input rating for allcombustion equipment in the confined space, but not less than100 sq. in. One opening shall be within 12 in. of the top and 1within 12 in. of the bottom of the enclosure. (See Fig. 5.)
BW4/BW5
7
VENTILATING�GRILLE
COMBUSTION�AIR GRILLE
A95594
Fig. 5 -- Air Openings for Closet or UtilityRoom Installations
BOILER
FRESH AIR�DUCT
A95595
Fig. 6 -- Fresh Air Duct for Tightly Sealed House
Example: The boiler is rated at 100,000 Btuh. The water heater israted at 30,000 Btuh. The total is 130,000 Btuh. Two grilles areneeded, each with 130 sq. in. of FREE opening. Metal grilleshave about 60 percent FREE area. To find the louvered areaneeded, multiply the FREE area required by 1.7 (130 X 1.7 =221.0 sq. in. louvered area). In this example, 2 grilles each havingan 8 in. X 30 in. (240 sq. in.) louvered area would be used. Fig. 5shows grille locations.ALL AIR FROM OUTDOORSThe confined space shall be provided with 2 permanent openings,1 commencing within 12--in. of the top and 1 commencing within12--in. of the bottom of the enclosure. The openings shallcommunicate directly, or by ducts, with the outdoors or spaces(crawl or attic) that freely communicate with the outdoors. SeeTable 2 and Fig. 5 or 6.
1. When directly communicating with the outdoors, eachopening shall have a minimum free area of 1 sq. in. per4000 Btuh of total input rating of all equipment in theenclosure.
2. When communicating with the outdoors through verticalducts, each opening shall have a minimum free area of 1sq. in. per 4000 Btuh of total input rating of all equipmentin the enclosure.
3. When communicating with the outdoors throughhorizontal ducts, each opening shall have a minimum freearea of 1 sq. in. per 2000 Btuh of total input rating of allequipment in the enclosure.
4. When ducts are used, they shall be of the samecross--sectional area as the free area of the openings towhich they connect. The minimum dimension ofrectangular air ducts shall not be less than 3--in.
Boilers With Tankless Heater CoilBoilers may be factory packaged with a tankless heater coil. Theuse of this coil eliminates the need for a hot water storage tank.Instantaneous heating of water in the coil provides a flow of hotwater for domestic use if proper burner and water supply linecontrols are used. Tankless coils are meant to provide domestichot water for intermittent draws, not continuous flows.
IMPORTANT: Do not use a tankless coil if water isexcessively hard with lime or other deposits which willaccumulate inside coil.
C. Mounting Aquastat ControlThe control configuration on this boiler has been set up so thatthe Honeywell L8124C Combination Hi/Low Limit AquastatRelay mounts on the tankless coil. This maximizes tankless coilperformance by making the burner respond more quickly to a callfor domestic hot water. The boiler is completely wired accordingto schematic wiring diagram. (See Fig. 14.) The installer mustmount the L8124C Aquastat on control well in 3/4--in. tappingon tankless coil. (See Fig. 7.)
IN
�1⁄2 IN. NPT�
3⁄4 IN. NPT
CONTROL WELL
A95596
Fig. 7 -- Tankless Heater Coil
D. Tankless Coil PipingPiping is as shown in Fig. 8. A tempering valve (mixing valve) isrecommended. A flow restrictor may be required on tankless coilinlet piping so that flow rates are matched to boiler heat input.See Table 3.
BW4/BW5
8
Table 3 – Boiler Rating Information
BOILER MODEL BURNER FIRING RATE INPUT (MBH) TANKLESS RATING (GPM)
BW4BAH091BW4RAH091
BW5BAH091BW5RAH091 0.65 91 2.90
BW4BAH105BW4RAH105
BW5BAH105BW5RAH105 0.75 105 3.00
BW4BAH140BW4RAH140
BW5BAH140BW5RAH140 1.00 140 3.25
BW4BAH126BW4RAH126
BW5BAH126BW5RAH126 0.90 126 3.15
BW4BAH175BW4RAH175
BW5BAH175BW5RAH175 1.25 175 3.50
BW4RAH210BW4BAH210
BW5RAH210BW5BAH210 1.50 210 3.75
BW4BAH168 BW5BAH168 1.20 168 3.45
BW4BAH245BW4RAH245
BW5BAH245BW5RAH245 1.75 245 4.00
BW4BAH280BW4RAH280
BW5BAH280BW5RAH280 2.00 280 4.25
* Gallon of water per minute heated from 40_ F to 140_ F with 200_ F boiler water, intermittent draw. Tankless heater is factory installed on BW5 models, fieldinstalled accessory on BW4 models.
TEMPEREDHOT WATER
UNTEMPEREDHOT WATER
(TO AUTOMATICDISHWASHER, ETC.)
SHUTOFFVALVE
COLD WATERINLET
IN
OUTTANKLESS COIL
LIMIT CONTROL
CENTER LINEOF COLD TAP
8 IN. TO 12 IN.
TEMPERINGVALVE
A98269
Fig. 8 -- Recommended Piping with Tankless Heater Coil
Installation System Piping1. Place boiler in selected location as close to flue aspossible. (See Fig. 4.) Boiler is shipped assembled. Onlythe factory--supplied relief valve needs be installed.
2. Install relief valve in rear section on 3/4--in. nipple andstreet ell. Do not connect directly to a drain, but leave anair gap. No shutoff of any description shall be placedbetween safety relief valve and boiler, or on dischargepipes between such safety valves and the atmosphere.Installation of safety relief valve shall conform torequirements of the ANSI/ASME Boiler and PressureVessel Code, Section IV. The manufacturer is not
responsible for any water damage. Connect a drain line ofthe same pipe size (3/4--in.) to carry any water away to adrain.
3. Connect the 1 1/4--in. NPT supply and return lines toboiler. Both supply and return lines should be piped to thefront section or both to the rear section. The boiler shouldNOT be piped return line to the front, supply line to therear, or vice versa, as this will cause boiler water to shortcircuit heat exchanger. The connections may requirecertain additional fittings and parts as shown on diagrams.(See Fig. 9, 10, and 11.)
If installing an entire new heating system, first install all radiationunits (panels, radiators, or cabinets) and supply and return mains,then make connections to boiler.
In connecting cold water supply to reducing valve, make sure thata clean water supply is available. When water supply is from awell or pump, a sand stainer should be installed at pump.
When boiler is used in connection with refrigeration systems, itshall be installed so that chilled medium is piped in parallel withthe heating boiler with appropriate valves to prevent chilledmedium from entering the heating boiler.
The minimum boiler supply water temperature setting on theaquastat is 140_F. If the boiler is used in a heating system wheresupply water temperatures below 140_F are desired, a suitablemethod, such as, the use of bypass piping shown in the figure 10,a 3 way or 4 way mixing valve, or some other means needs to beused to ensure return water temperatures to the boiler are no lessthan 120_F. When the boiler is operated with return watertemperatures less than 120_F, condensation may form in theboiler and venting. This condensation is corrosive and caneventually cause severe damage to the boiler and venting system.Antifreeze added to boilers must be non--toxic and must be of atype specifically intended for use in closed hydronic heatingsystems. Under no circumstances should automotive antifreeze beused. Antifreeze used in any boiler may reduce capacity by 10percent or more and increase fuel consumption. Tankless coilperformance will fall as concentration of antifreeze is increased.Refer to boiler and piping water volumes tables on next page.
BW4/BW5
9
FILTROL WITHAIR PURGER
AUTOMATICFILL VALVE
SUPPLY TOSYSTEM
MAIN SHUTOFFVALVE
DRAIN VALVEFOR POWERPURGING
SHUTOFF VALVEBOILER SERVICE
FILL LINE WITH SHUT OFF VALVE
RETURN FROM SYSTEM
BOILERDRAINVALVE
R
AQUASTAT
S
A01032
Fig. 9 -- Circulator on Supply Pumping Away
FILTROL WITHAIR PURGER
AUTOMATICFILL VALVE
SUPPLY TOSYSTEM
DRAIN VALVEFOR POWER PURGING
SHUTOFF VALVEBOILER SERVICE
FILL LINE WITH SHUT OFF VALVE
RETURN FROM SYSTEM
BOILERDRAINVALVE
ISOLATION VALVES
THROTTLING VALVE
THROTTLING VALVE
CIRCULATORPUMP
AQUASTATS
R
MAIN SHUTOFFVALVE
ADJUST THE TWO THROTTLINE VALVES TOMAINTAIN AT LEAST 120 OF IN THEBOILER RETURN. THE THROTTLING VALVESARE USED FOR BYPASS PIPING, IF REQUIRED.
A01034
Fig. 10 -- Bypass Piping Circulator on Supply
FILTROL WITHAIR PURGER
AUTOMATICFILL VALVE
SUPPLY TOSYSTEM
SHUTOFF VALVEBOILER SERVICE
FILL LINE WITHSHUT OFF VALVE
RETURN FROM SYSTEM
BOILERDRAINVALVE
ISOLATIONVALVES
CIRCULATORPUMP
AQUASTAT
SHUTOFF VALVEBOILER SERVICE
*
* LOCATE CIRCULATOR PUMP HERE WHEN SYSTEMPIPING USES ZONE VALVES. IF SYSTEM PIPINGUSES ZONE CIRCULATORS, USE THIS CIRCULATORAS A ZONE CIRCULATOR
A01035
Fig. 11 -- Piping Circulator on Supply Side
BW4/BW5
10
Table 4 – Recommended Minimum Chimney Sizes
FIRING RATE(GPH)
CHIMNEY HEIGHT(FT.)
NORMAL CHIMNEY AREA (IN.) ROUND LINER INSIDEDIAMETER (IN.)
SQUARE LINER INSIDEDIMENSIONS (IN.)
0.60 to 1.30 15 8 X 8 6 6---3/4 X 6---3/41.31 to 1.80 15 8 X 8 7 6---3/4 X 6---3/41.81 to 2.00 20 8 X 8 8 6---3/4 X 6---3/4
---For elevations above 2000 ft. above sea level, add 3 ft. to chimney heights. (See figure 12.)
Chimney and Chimney ConnectionFollow local codes. In the absence of local codes, followANSI/NFPA 31 Installation of Oil Burning Equipment, latestrevision.
A. Checking ChimneyThe chimney is a very important part of the heating system. Noboiler, however efficient its design, can perform satisfactorily ifthe chimney serving it is inadequate. Check chimney to makecertain it is the right size, properly constructed, and in soundcondition.
B. Chimney Connector and Draft RegulatorBoiler requires 6--in. diameter chimney connector pipe. The draftregulator shipped with boiler must also be used. When properlyinstalled, the regulator controls the draft automatically. It is best toinstall it in a horizontal section of the pipe, but it may be in anangled or vertical section. Make certain that the “top” is at top andthat the short pipe section which holds vane is horizontal. Installit as close as practicable to boiler. (See Fig. 12.)Install chimney connector as follows:
1. Start at boiler with a vertical pipe, at least 1 foot tall, andthen an elbow.
2. Install draft regulator making it horizontal.
3. When regulator is in place, start at chimney and work backto regulator.
4. Join the 2 sections with a drawband. The horizontal pipemust slope up toward chimney at least 1/4--in. per ft.. Itmust not leak and must be firmly supported.
5. Join sections with at least 3 sheet metal screws. Spaceevenly around the pipe.
6. Support every 5 feet with metal straps or stove pipe wire.
C. Minimum Vent Pipe ClearanceWood and other combustible materials must not be closer than18--in. from any surface of vent pipe.
Electrical WiringSee Fig. 14 for wiring diagrams for the various models.
A. Installing Thermostat (Not Provided)The 24--v thermostat location has an important effect onoperation of boiler system. BE SURE TO FOLLOWINSTRUCTIONS INCLUDED WITH THERMOSTAT.
B. GroundingPermanently ground boiler according to local codes and thecurrent edition of The National Electrical Code. Run a 14 gage orheavier copper wire from boiler to a grounded connection inservice panel or a properly driven and electrically groundedground rod.
C. Electrical Power Supply
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
Turn off electric power at fuse box before making any linevoltage connections. Follow local electric codes
! WARNING
All electrical work must conform to local codes as well as theNational Electrical Code. If not familiar with wiring and codes ingeneral, have a competent electrician do this job.
Boiler controls are all wired at the factory. All that is required isto connect a 115--v electric supply and thermostat wires toaquastat relay.
Run a separate circuit from a separate overcurrent protectivedevice in electrical service entrance panel. This should be a15--amp circuit. Locate a shutoff switch at boiler. It must beturned OFF during any maintenance. Solder and tape or securelyfasten these connections with wire nuts.
D. Connecting 115--V Electrical Wiring to BoilerConnect 115--v electric supply wires to terminals L1 and L2 onaquastat relay. (See Fig. 14.)
E. Thermostat ConnectionsThe 2 wires from thermostat connect to terminals T and T onL8148A and L8124C aquastat relay (See Fig. 14.)
F. Thermostat Heat Anticipator AdjustmentSet heat anticipator at 0.2 amps. Measure the AMP draw of thethermostat circuit and adjust the anticipator setting if necessary.
Equipment and OptionalAccessoriesA. Relief Valve (Required, Provided)Each low--pressure hot water heating boiler is provided with arelief valve for over--pressure protection of boiler and heatingsystem. The relief valve opens when pressure in boiler rises to 30psig. Each relief valve is provided with a lifting device for testingand should be tested monthly during heating season. Escapepiping should be provided from discharge side of relief valve soas to prevent scalding or other hazardous situations. The escapepiping must remain full size and end at a safe point of discharge.
B. Expansion Tank (Not Provided)In a properly assembled system, expanding water flows into anexpansion tank. This tank should be of the correct size.
The tank is filled with air. As the water expands, it compresses theair in tank to form an air pressure cushion. This “spring--like”cushion serves s to maintain correct operating water pressureregardless of water temperature. This assures a “full measure” ofwater even in the highest radiation unit of system. It also preventsblowing off the relief valve.
The air in tank in the beginning (with system filled with coldwater) is sufficient for proper operation. The tank also serves as atrap for excess s air in system. This air would cause gurgling inpipes and inefficient circulation in radiators if left in system.
BW4/BW5
11
It is possible for a tank to become “water--logged” (filled withwater). It can also become overfilled with air. This can happenafter filling system with new water. Fittings are provided on tankand in line to tank for bleeding off excess water or air.
When installing this tank, the following are important: :
1. Tank should be higher than boiler top.
2. Pipe to tank should continuously rise up to tank (so thatair can “bubble“ up through it).
C. Diaphragm--Type Expansion Tank (Not Provided)The diaphragm--type expansion tank takes the place of aconventional expansion tank. Read instructions packed with tankassembly carefully. The tank comes with a 10--12 psi air charge.This is the same as the pressure produced in system by automaticfill valve. When system is first filled, ,tank contains little or nowater. .As water is heated, its pressure increases. It expands intotank compressing the air in tank. This compressed air cushionpermits water in system m to expand as temperature changes. Thediaphragm--type expansion tank can be mounted on the air purgerfitting or at any other convenient place in the supply or returnline. It is recommended to locate the diaphragm type expansion
tank (a) in the supply line with the circulator located after theexpansion tank or (b) off the e3/4--in. tapping provided on the topof the rear casting with the circulator mounted directly off theboiler’s supply piping connection. This configuration allows thecirculator to “pump away” from the expansion tank for improvedair elimination and system performance. The air reliminatorfitting or air purger is not provided. The air eliminator fitting orair purger is used to help remove air from the system before itreaches the radiators. It should be installed in the supply line. Airleft in the system can cause noises in the pipes and inefficientcirculation in the radiators. .
D. Air Eliminating Fitting (Air Purger) (Not Provided)
Table 5 – Boiler Water VolumesNUMBER OF BOILER SECTIONS TOTAL VOLUME (GALLONS)
3 9.64 11.65 13.7
MUST BE REQUIRED MINIMUM�HEIGHT. MUST BE AT LEAST�3 FT HIGHER THAN HIGHEST�
PART OF PASSAGE THROUGH�ROOF. MUST BE AT LEAST 2 FT�
HIGHER THAN ANY NEIGHBORING�OBJECT. MUST HAVE AN �
UNOBSTRUCTED TOP OPENING.
MUST BE AT LEAST �4 IN. THICK AND BE TIGHT.
BALANCED�WEIGHT
CRIMPED�END
ALTERNATE POSITIONS
TOP
TOP
MUST SLOPE UP AT �LEAST 1/4 IN. PER FOOT�
OF HORIZONTAL RUN.
TIGHT CLEAN-OUT�DOOR
SEALED IN�THIMBLE
TIGHT, SMOOTH,�CORRECTLY SIZED.
DRAWBAND LAST�PIECE INSTALLED
DRAFT REGULATOR�VANE
A95601
Fig. 12 -- Typical Chimney Requirements
BW4/BW5
12
Table 6 – Piping Water VolumesPIPE SIZE COPPER PIPE FACTOR STEEL PIPE FACTOR
1/2--- IN. 82.5 63.5
3/4--- IN. 40.0 36.0
1--- IN. 23.3 22.2
1---1/4--- IN. 15.3 12.8
1---1/2--- IN. 10.8 9.5
2--- IN. 6.2 5.8
---Divide total length of piping in feet by appropriate factor in table to de-termine volume in gallons.An air purger is used to remove air from system. It is installed insupply line. It eliminates air from water before it reaches radiatorsand bleeds off this air.
E. Main Air Vent for Downflow Systems orDiaphragm--Type Expansion Tank (Not Provided)
Before a system is filled with water, there is air in pipes andradiation units. Some of it will be trapped as system fills. It ispossible to eliminate most of this air through air vents onradiation units. A main air vent speeds and simplifies this process.It should be installed on highest point in supply main when allradiation is below top of boiler.
F. Aquastat Relay Control (Provided)The water temperature limit control in aquastat relay is adjustableand may be set as necessary. It may be set as low as 140_F or ashigh as 240_F. This depends on type and amount of radiationinvolved and weather conditions.
G. Automatic Fill Valve (Not Provided)For safe, efficient operation, a hot water system must be filledwith water. Adding new water when needed can be donemanually (by use of a hand valve in water supply line). Thisrequires regular attention to system’s needs. An automatic fillvalve accomplishes this without attention. It is installed in supplyline on hot water boilers only. The valve operates through waterpressure differentials. It does not require electrical connection.
H. Drain Valve (Provided)This manual valve provides a means of draining all water fromboiler and system. It is installed in a tee where return line entersboiler.
I. Circulating Pump (Provided)Every forced hot water system requires a circulating pump. Aseparate pump or zone valve is required for each zone if there are2 or more zones. The circulator must have the capacity to providethe circulation required by the heating system. The circulatorshould be connected to the supply main and must be wired intothe boiler’s electrical system. See the prior pages of installationsection for piping configurations with the circulator located onthe supply main piping using zone circulators or zone valves.When the piping is arranged with zone circulators and no bypasspiping, the circulator provided with the boiler may be used as azone circulator. Both piping arrangements allow the circulator topump away from the expansion tank and show how the pipingshould be arranged to allow the heating system to be easilypurged of air.
J. Oil Solenoid ValveThe Beckett oil burner uses a standard solenoid valve. Uponburner shutdown, a standard solenoid valve stops the flow of oilto the nozzle. Without the solenoid valve, the oil pump continuesto pump oil to the burner nozzle until the motor winds downbelow the pump cut--off speed. The Riello oil burner has a delayoil solenoid valve. The delay solenoid valve provides the sameshut down action of the standard solenoid valve, plus on burnerstart--up, the delay solenoid valve remains closed for anadditional 15 seconds. This allows the burner fan motor to
pre--purge the combustion chamber and the oil pump to bring thesupply oil pressure up to its set point helping to provide a cleanlight off.
Filling BoilerOPTION #1
A. How a Hot Water System OperatesThe entire heating system (boiler, piping, and radiation units) isfilled with water. As water in boiler is heated, it is pumped fromtop of boiler through supply main to radiation units. The coolerwater in them flows back through return main to boiler. Thisprovides positive and rapid response to thermostat.
B. Filling System With Watera. Close the main shutoff valve, isolation valves, andzone valves (if applicable). If bypass piping isinstalled, also close the two throttling valves. Leavethe boiler service shutoff valve (if installed) and thebalancing valves to each heating zone fully open.
b. Open the following valves in order: the drain valve forpower purging, isolating valves before and after theboiler circulator (if applicable), both throttling valves(if applicable), and then open the fill line shutoffvalve. Water will fill the bypass piping and push airthrough the piping and out the power purging drainvalve. When the power purging drain valve runs airfree, close the bypass throttling valve (leaving thethrottling valve to the supply piping fully open)
c. Next, open the isolation valve (or zone valve) to thefirst zone. Water will fill the piping and push any airout the power purging drain valve. When the powerpurging drain valve runs air free, close the isolationvalve or zone valve. Repeat this procedure for theremaining heating zones.
d. Once all of the zones are filled with water and purgedof air, close the power purging drain valve and fill lineshut off valve, open the main shutoff valve, and adjustthe throttling valves and balancing valves as required.
OPTION #2
1. Close air vents on all radiation units. Open valves to theseunits.
2. Make sure boiler and expansion tank drain cocks areclosed. The air bleed screw on tank drain fitting should beclosed.
3. Open valve in line from boiler to expansion tank.
4. Open water inlet to boiler and leave it open.
5. Start with the LOWEST radiation unit. Open the air venton this radiation unit. When all air has escaped and waterstarts to flow from vent, close air vent.
6. Proceed to next lowest radiation unit and repeat processoutlined in item 5. Repeat until every radiation unit insystem has been covered. End with the highest unit insystem.
If units have automatic vents, this manual venting is unnecessarybut will speed up proper filling of system.
If system is a closed expansion tank system, there should be anautomatic fill valve. It may be left open to refill systemautomatically as needed.
Check temperature--pressure gage. Note position of handindicating pressure. This should be between 10 and 15 psi. Anylowering of this movable hand below 10 psi indicates loss ofwater due to leakage. The automatic fill valve should compensatefor this. If it does not, manually open this valve to refill system
BW4/BW5
13
until hand is again pointing to same pressure reading. Instructionsare packaged with valve.
OPERATING BOILER
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personalinjury, death and or property damage.
Do not tamper with unit or controls.
! WARNING
IMPORTANT: Follow these instructions carefully.
To StartFill entire system with water. Vent all air from system. Refer toinstructions included with oil burner.
Fuel Units and Oil LinesInstall oil line(s) to the oil burner. Recommend using heavy wallcopper tubing and flared fittings, not compression fittings. Allconnections and joints must be absolutely airtight. Use anappropriate non--hardening thread sealing compound on thethreaded connections, not Teflon tape. See fuel unit data sheetfurnished with the burner for sizing, lift, and length of tubingrecommendations.The original equipment oil burner (when furnished) is equippedwith a single--stage fuel unit with the by--pass plug removed forsingle pipe installation. This is satisfactory where the fuel supplyis on the same level as, or above the burner, permitting gravityflow of oil. Per NFPA--31 requirements, never exceed 3 psigpressure to the inlet side of the fuel unit. When it is necessary tolift the oil to the burner, a two--pipe installation is required. Runa return line between the fuel unit and the oil supply. When atwo--pipe installation is used, the by--pass plug (furnished withthe burner) must be installed in the fuel unit. Refer to the fuelunit instructions furnished with the burner for specificinstructions on installing the by--pass plug. Do not exceed thefuel unit manufacturer’s recommendations for running vacuum.(Note: If lift exceeds 14 feet for Beckett or Carlin burners or 11feet for Riello burners, a two--stage fuel unit is required with areturn line.)Install an oil filter of adequate size inside the building betweentank shutoff valve and the oil burner. For ease of servicing, locatethe shutoff valve and filter near the oil burner.
Air Supply for CombustionDo not install in rooms with insufficient air to supplycombustion. Occasionally, it is necessary to install windows orcut holes in a door to these rooms to obtain sufficient air and toprevent less than atmospheric air pressure in the room. If there isa lack of combustion air, the burner flame will be yellow andformation of soot will occur in heating unit. In buildings ofconventional frame, brick, or stone construction without utilityrooms, basement windows, or stair doors, infiltration is normallyadequate to provide air for combustion and operation ofbarometric draft control. The room should be isolated from anyarea served by exhaust fans. Do not install exhaust fans in thisroom. See Fresh Air for Combustion section earlier in thisdocument.
Draft Regulators (Provided)A draft regulator is required. It should preferably be mounted insmoke pipe. Use a draft gage to adjust to proper opening. Whenburner air supply and draft are properly adjusted, combustionchamber draft will be approximately --0.01 to --0.02 in. wc andstack draft will be --0.02 to --0.04 in. wc. The larger theinstallation, the greater the draft required at stack to obtain --0.01to --0.02 in. wc at combustion chamber.
Nozzles (Provided)Use the proper size, type, and spray pattern nozzle, refer to Table6. To install nozzle, loosen clamping screw on retention ringassembly and slide assembly off adapter. Install and tightennozzle in adapter. Be careful not to damage electrode insulators orbend electrodes. Replace retention ring assembly on adapter.Make sure clamp is tight against shoulder on adapter. Tightenclamping screw. Check electrode setting. (See Fig. 13--17.)
Final Burner AdjustmentsA final adjustment must be made with the use of aCOMBUSTION TEST KIT. Initial settings for burner are shownon label on top of ignition transformer and Table 7 for Beckettburners, Table 8 for Riello burners. Set burner accordingly. Afteroperating 10 minutes to warm unit up, a smoke tester should beused to take a smoke reading in flue pipe between boiler and draftregulator. Smoke should be zero (Shell Bacharach Scale). Attimes a new boiler requires more time than this to burn clean dueto oil film on a new heat exchanger. Check draft over the fire.This should be --0.01 to --0.02 in. wc as previously stated. Adjustdraft if necessary. Gradually close air shutter, and if necessary theair band, to obtain a smoke reading showing a trace of smoke.Measure CO2 at this point. Increase air sufficiently to reduce CO2by 0.5 to 1 percent as an insurance margin. Smoke should bezero. If a clean fire cannot be obtained, it will be necessary toverify head and electrode alignment. (See Fig. 15--17.) If fire isstill smoky, replace nozzle with a correct replacement. Recordnozzle size, oil pressure, combustion readings and air settingsthen place a tag or label on boiler or burner with this information.Units should be cycled several times to assure good operationwith no fluttering or rumbling. Check for oil leaks.
ELECTRODE
NOZZLE
DIMENSION "H"SEE ABOVE
DIMENSION "N"SEE ABOVE
L1 OR V1 HEAD
5/32GAP
5/16 ABOVE
BOILERMODEL
5EW
DIMENSION "N"(electrode to nozzle)
1/16"
DIMENSION "H"(head to nozzle)
7/32" - 9/32"
BECKETT AFG BURNER ELECTRODE ADJUSTMENTS VARIABLE (V1) HEADS
A06663
Fig. 13 -- Beckett Burner Electrode Adjustments
BW4/BW5
14
3-3/4" 1/32"
"Z"DIMENSION
LOCATION OF HEAD AT "D"POSITION ON ADJUSTING PLATE
"V1" ADJUSTABLE HEAD
AIR TUBE COMBINATION
HOLD DOWNSCREW
ACORN NUT/ LOCK WASHER
KNURLEDNUT
SECONDARYADJUSTING
PLATE
PRIMARYADJUSTING
PLATE
WITNESSMARK
BECKETT AFG VARIABLE (V1) HEAD ADJUSTMENTS AND SETTINGS
A06664
Fig. 14 -- Beckett Burner Setting Variable (V1) Head
5/32GAP
7/16 ABOVE
NOZZLEDIMENSION "N"
SEE ABOVE
BURNER F-HEAD MODEL
F0 THRU F31
DIMENSION "N" HEAD TO NOZZLE
1/16"
BECKETT AFG BURNER ELECTRODE ADJUSTMENTS F-HEADS
A06665
Fig. 15 -- Beckett Burner Setting Fixed (F) Head -- 140, 210
A06506
Fig. 16 -- Riello 40--F5 Burner Electrode Adjustments
BW4/BW5
15
A06507
Fig. 17 -- Riello 40--F10 Burner Electrode Adjustments
Oil Burner MaintenanceThe following preventative maintenance items should beperformed annually, preferably prior to the heating season.
A. Oil Burner MotorAdd 2--3 drops of non--detergent electric motor oil to each oil cuplocated at front and rear of motor. Excessive oiling will shortenthe life expectancy of motor.
B. Fuel FilterThis should be replaced so as to prevent contaminated fuel fromreaching the nozzle. A partially blocked fuel filter can causepremature failure of fuel pump unit.
C. Fuel Pump UnitReplace pump screen and clean pump unit to maintain reliablefuel delivery to nozzle.
D. Ignition Electrods
Clean and adjust as per manufacturer’s recommendations so as tomaintain reliable ignition of oil.
E. NozzleReplace so as to maintain safe and reliable combustion efficiency.Always replace with the exact nozzle as required in Table 7.
These must be kept clean and free of dirt, lint, and oil so as tomaintain proper amount of air the fuel requires to burn.
NOTE: If any component parts must be replaced, always useparts recommended by burner manufacturer.
F. Fan and Blower HousingCheck burner blower wheel for dirt, grease and grime. Clean asnecessary. Check motor is attached to burner housing and wheelis attached tightly to motor shaft. Check pump coupling for wearand damage.
Table 7 – Beckett Oil Burner Specifications
BASEMODEL
BOILER IN-PUT (BTUH)
DELEVAN OILNOZZLE
FIRINGRATE(GPM)
HEAD---ADJUSTMENTOR SETTING
LOW FIREBAFFLE
AIR SHUTTERAIRBAND
STATICPLATE (IN.)
PUMP PRESSURE
140
91,000* 0.50–80 B 0.65 F0 1---1/8 YES 10 0 3---5/8 175 PSIG
105,000 0.65–70 B 0.75 F3 1---1/8 YES 10 0 3---1/2 140 PSIG
140,000 0.85–70 B 1 F3 1---1/8 NO 10 2 3---1/2 140 PSIG
210
126,000* 0.75–80 A 0.9 F3 1---1/8 NO 8 0 3---1/2 140 PSIG
175,000 1.00–80 A 1.25 F6 1---1/8 NO 10 0 3---3/8 140 PSIG
210,000 1.25–80 A 1.5 F6 1---1/8 NO 10 2 3---3/8 140 PSIG
280
168,000 1.00–60 B 1.2 V1---0 NO 10 1.5 2---3/4 140 PSIG
245,000 1.50–45 B 1.75 V1---2 NO 10 4 2---3/4 140 PSIG
280,000 1.65–60 B 2 V1---4 NO 10 5 2---3/4 140 PSIG
BW4/BW5
16
Table 8 – Riello Oil Burner SpecificationsBASEMODEL
BOILERINPUT (BTUH)
DELEVANOIL NOZZLE
FIRINGRATE (GPM)
TURBULATOR/AIRSHUTTER SETTING
OIL PUMP PRESSURE(PSIG)
OILBURNER
140
91,000 0.50---70ºW 0.65 0.5 / 2.0 155 F5
105,000 0.65---70ºW 0.75 2.0 / 2.2 150 F5
140,000 0.85---70ºW 1.00 2.0 / 3.2 170 F5
210
126,000 0.75---70ºW 0.9 1.5 / 2.6 160 F5
175,000 1.00---70ºW 1.25 2.5 / 3.8 170 F5
210,000 1.25---70ºW 1.5 4.0 / 7.0 175 F5
280245,000 1.50---70ºW 1.75 2.0 / 3.8 155 F10
280,000 1.75---70ºW 2.00 2.5 / 4.1 155 F10
Note: All Riello 40 F5 and F10 oil burners are factory preset at 145 psig.
Checking and Adjusting Controls
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury or death.
Do not attempt to start the burner when excess oil hasaccumulated, when unit if full of vapor, or when thecombustion chamber is very hot.
! WARNING
IMPORTANT: These instructions must be followed carefully.
A. Adjusting Operating ControlsInstructions for each control are included. Refer to Table 8 forrecommended settings for the first adjustment:
These settings can be changed after gaining familiarity with howsystem responds. If system does not give quite enough heat invery cold weather, ,the high limit setting can be raised to 220_F.If more domestic hot water is required, the low limit setting canalso be raised
B. Checking Thermostat OpeationWhen set above temperature indicated on thermometer, boilerburner should start. Make certain thermostat shuts boiler downwhen room temperature reaches selected setting and starts boileroperating when room temperature falls a few degrees.
NOTE: Do not start burner unless all cleanout doors are securedin place.
MAINTENANCETo assure trouble--free operation, we recommend that fluepassages, burner, combustion chamber area (target wall and firedoor insulation), burner adjustment, operation of controls, andboiler seals (door gasket or silicone seal, cast iron seals and fluecollector) be checked ONCE EACH YEAR by a competentservice technician.
BEFORE THE START OF EACH SEASON (or wheneversystem has been shut down for some time), recheck the wholesystem for leaks and recheck boiler and vent pipe for leaks.Replace or patch any boiler seals that are faulty.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury or death.
Never burn garbage or paper in the unit, and never leavecombustible material around it.
! WARNING
Relief ValveThis valve should open automatically when system pressureexceeds the safe limit (30 psi). Should it ever fail to open underthis condition, shut system down. Drain it until pressure isreduced below safe limit, then have valve replaced immediately.The relief valve should be tested monthly during heating season.Prior to testing, make certain a discharge pipe is properlyconnected to the valve outlet and arranged so as to contain andsafely dispose of boiler discharge. Hold the trip lever fully openfor at least five seconds in order to flush free any sediment thatmay lodge on the valve seat. Then permit the valve to snap shut.
Conventional Expansion TankAs previously noted, this tank may become waterlogged or mayreceive an excess of air. Frequent automatic opening of reliefvalve indicates waterlogging. A high boiler temperatureaccompanied by unusually low radiation unit temperature (and“knocking”) indicates excess air in tank. To correct eithercondition, close valve between boiler and tank. Drain tank until itis empty. Check all tank plugs and fittings. Tighten as necessary.Open valve between boiler and tank. Water will rise to normalheight in tank if automatic fill valve is installed, otherwise,manually refill system.
Diaphragm Expansion TankAs previously noted, this tank may become waterlogged or mayreceive an excess of air. Frequent automatic opening of reliefvalve indicates waterlogging. A high boiler temperatureaccompanied by unusually low radiation unit temperature (and“knocking”) indicates excess air in tank. To correct this condition,replace the diaphragm expansion tank.
Water SystemIf system is to remain out of service during freezing weather,always DRAIN IT completely. Water left in to freeze will crackpipes and/or boiler.
Tankless Coil (or Cover Plate Gasket)The tankless coil gasket should be checked at least twice a yearfor leakage and replaced if necessary.
BW4/BW5
17
Oil Boiler/Burner Cleaning InstructionsOIL BOILER CLEANING
1. Shut off all electrical power to the boiler/burner and shutoff fuel oil supply.
2. Remove the vent pipe from the top of the boiler. Inspectthe pipe and chimney for signs of corrosion anddeterioration. Clean out the base of the chimney. If thevent pipe shows any signs of corrosion or deterioration,replace it immediately. If chimney damage or deteriorationis discovered, contact a competent professional.
3. Remove the top jacket panel screws (5), the brass wingnuts (2) holding the flue collector top, and then the fluecollector top. Inspect the gasket on the underside of theflue collector and replace as necessary.
4. Before beginning to clean the flue passageways, ensurethat the combustion chamber blanket is covered. If theblanket is not covered prior to cleaning, replace theblanket once cleaning is complete.
5. Now with access to the flue passageways, remove the sootfrom the fireside surfaces by brushing diagonally throughthe flue passages (See Fig. 18). Brushing can be madeeasier by cutting the end of the flue brush off and insertingit into a drill. When brushing, care should be taken so asnot to damage the target wall with the flue brush.
6. Carefully vacuum the soot accumulations from thecombustion chamber area, being particularly careful to notdamage any of the refractory or blanket insulation. To gainaccess to the combustion chamber first double check thatthe shut off valve on the fuel line is closed and thendisconnect the fuel oil line. Then open the swing door bysimply removing the whiz lock nut holding the door shut.
7. Now inspect the target wall, fire door refractory, andcombustion chamber blanket (when included) for crackingand deterioration. If there is any signs of cracking ordeterioration, replace the refractory or blanket beforereassembling the burner/front plate.
8. Inspect the door’s braided gasket for wear and damage.Replace when necessary with braided gasket of the samematerial and size. See repairs parts section of this manual.
9. Now inspect and clean the oil burner.
A95609
Fig. 18 -- Removing Soot
OIL BOILER CLEANINGNOTE: These are general instructions for cleaning an oil burner.For specifics, consult the burner manufacturer’s instructions
1. Make sure all electrical power to the boiler/burner and thefuel supply to the burner are shut off.
2. With the swing door open, clean any soot accumulationsfrom the end of the burner and if applicable burner head.
3. Remove the burner drawer assembly, clean the electrodesand then reset the electrode spark gap per themanufacturer’s recommendations.
4. Replace the oil nozzle with the exact same size and typerecommended for use on this boiler.
5. Reinstall the burner drawer assembly making sure thehead location (and size if applicable) are per themanufacturer’s recommendations. If the burner being usedhas a damaged head, replace the head with the exact samehead recommended for use on this boiler.
6. Inspect and clean the oil burner blower wheel.
7. Remove the oil pump cover and clean/replace the pumpscreen. Carefully reassemble ensuring the pump covermakes a good seal.
8. Securely fasten the swing door shut.
9. Replace the fuel filter (if applicable).
10. Reconnect the electrical and fuel supplies.
11. Fire the burner, checking for proper combustion usingcombustion test equipment and making adjustments asnecessary.
12. Ensure that all safety controls and operating controls arefunctionally properly.
IMPORTANT: KEEP BOILER AND AREA AROUND ITCLEAN. NEVER BURN REFUSE OR ANY MATERIALOTHER THAN THE SPECIFIED FUEL IN BOILER. HAVEBOILER CHECKED EACH YEAR BY A QUALIFIEDTECHNICIAN.
Sequence of OperationRefer to Fig. 19 and the wiring diagram shown in Fig. 14 whilereviewing sequence of operation.
A. Boiler with Tankless CoilHIGH LIMIT CONTROLLER
The high limit contacts open and turn burner off when boilerwater temperature reaches high limit set point. The high limitautomatically resets after boiler water temperature drops past setpoint and through fixed 10_ differential.
LOW LIMIT AND CIRCULATOR CONTROLLER
On a boiler water temperature rise, with the adjustable differentialset at the minimum setting of 10_, burner circuit contacts RBbreak and circulator circuit contacts RW make at low limit setpoint. On a boiler water temperature drop of 10_ below set point,the RB circuit makes and RW circuit breaks
At any differential setting greater than 10_, the RB make andRW break temperature remains the same (control setting minus10_). The RB break and RW make temperature is the set pointtemperature plus the difference between differential setting and10_.
The low limit control fires burner to maintain boiler watertemperature at low limit setting (set point plus adjustabledifferential setting minus 10_).
While boiler water temperature is below low limit setting,circulator is prevented from operating, giving preference todomestic hot water requirements. Once boiler water temperaturerises to low limit setting, thermostat controls firing of burner andoperation of circulator pump as follows:
BW4/BW5
18
TO115V
SUPPLY L1
N H 115V 60 CYCLESUPPLY
24 VOLTTHERMOSTAT
L2 T T
TO24VTHERM
AQUASTATRELAY
A95602
Fig. 19 -- Wiring Connections to Aquastat Relay
Table 9 – Recommended Operating Control Settings
OPERATING CONTROL CONTROLSETTING
High LimitStanding Radiators 180°FBaseboard andConvectors 200°F
Low Limit (When Used) 140°FDifferential (When Used) 10°F
1. Thermostat calls for heat completing circuit betweenterminals T and T on L8124C aquastat controllerenergizing the 1K relay coil.
2. With 1K relay coil energized, contacts 1K1 and 1K2 areclosed. Terminal B1 is energized providing power toR4184 oil burner primary control. This in turn powersignition coil and burner motor.
3. With R4184 primary control energized, burner operationstarts and burner remains running as long as cad cellsenses flame. In the event of a flame failure or if flame isnot fully proven within 45 sec of initial start--up, theR4184 primary control locks out and opens burner circuit.This requires a manual start--up of burner.
4. As long as flame is proven through cad cell relay, burnerremains on until circuit is interrupted by boiler watertemperature reaching high limit setting (opening high limitcontacts BR), or thermostat is satisfied breaking T--Tcircuit.
5. Circulator pump is powered through terminal C1 and runswhen boiler water temperature is above low limit setting.
6. If boiler water temperature reaches high limit setting, highlimit contacts BR open de--energizing terminal B1 and
shutting off burner. Circulator pump remains running aslong as thermostat calls for heat.
7. If boiler water temperature falls 10_ below high limitsetting, contacts BR close energizing burner.
8. Thermostat is satisfied terminating call for heat. Relay coil1K is de--energized opening 1K1 and 1K2 contacts. Bothburner and circulator pump cease operation.
NOTE: The high limit setting must be set a minimum of 20_higher than low limit setting.
B. Boiler Without Tankless CoilAQUASTAT HIGH LIMIT CONTROLLER
The aquastat control’s high limit contacts open and turn off theburner when the boiler water temperature reaches the control’shigh limit set point. The high limit contracts automatically resetafter the boiler water temperature drops past the set point by 10_F, which is a fixed differential. When the thermostat controls callfor domestic space heating, the sequence of operation for theburner and circulator is as follows:
1. Thermostat calls for heat, completing the circuit betweenterminals T and T on the aquastat controller, energizingthe 1K relay coil.
2. With the 1K relay coil energized, contacts 1K1 and 1K2are closed. Terminals C1 and C2 are energized providingpower to the circulator. Terminal B1 is energized,providing power to the oil burner primary control. This inturn powers the ignition coil and burner motor.
3. With the primary control energized, the burner operationstarts and remains running as long as the cad cell sensesflame. In the event of flame failure or the flame is not fullyproven within the trial for ignition period, the primarycontrol will lockout and open the burner circuit. This willrequire a manual startup of the burner.
4. As long as flame is proven through the cad cell relay, theburner will remain on unit the circuit is interrupted by theboiler water temperature reaching the aquastat’s high limitsetting (opening high limits contracts BR), or thethermostat is satisfied breaking the T—T circuit.
5. If the boiler water temperature reaches the aquastat’s highlimit setting, the high limit contact BR is de--energizedturning the burner off. However, the circulator pump willcontinue to run, as long as, the thermostat calls for heat.
6. After the high limit contact BR is de--energized, the boilerwater temperature must fall 10_ F below the aquastat’shigh limit setting for the high limit contacts BR to closeand energize the burner.
7. When the thermostat is satisfied, the call for domesticspace heating is ended. Relay coil 1K is de--energized,opening 1K1 and 1K2 contacts. Both the burner andcirculator pump operation stop.
BW4/BW5
19
L1
FIELD WIRING24 VOLT THERMOSTAT
L8124CAQUASTAT
NEUTHOT120V
POWERSUPPLY
OVERCURRENTPROTECTEDDISCONNECT
BK W
RBK
BK
WW
R
CIRCULATORPUMP
IGNITIONTRANSFORMER
OIL BURNERMOTOR
BK
BK
W
BK
O
R4184RELAY CAD CELL
Y
Y
120/60/1 OVERCURRENT PROTECTED DISCONNECT
BOILER WITHOUT TANKLESS HEATER COILBOILER WITH TANKLESS HEATER COIL
LINE
NEUTRAL
24 V THERMOSTAT
FIELD WIRING
OIL BURNERMOTOR
L8148AAQUASTAT
IGNTRANS
B
W
CIRCULATOR
B W
B
W
W
B
O
B
B
R4184DRELAY
Y
Y
CADCEL
IK1JUMPER
IK IK2
B2 C2
C1 ZC
FF
ZR B1
L2 T T
T T
G
GND
L1(HOT)
L2
L1
L2
B1
B2
C1
B
R
ZR
BRW
ZC
C2
HIGH LIMIT
1K2
LOW LIMIT/CIRCULATOR
COLOR CODE
BK=BLACKO=ORANGEY=YELLOWR=REDW=WHITE
1K1
1K
A
R
LINEVOLTAGECLASS II24 VOLTS
TTL2L1
3
F
F
B
3TT
C1
C2 B2 B1L2
L1
B
R
G
B2B1C2C1
COLOR CODE
B=BLACKW=WHITEO=ORANGEY=YELLOW
OILVALVE
OILVALVE
BW4B BW5B
A02231
Fig. 20 -- Wiring Diagrams for Boilers With and Without Tankless Heaters and Beckett BurnersBW4/BW5
20
A06504
Fig. 21 -- Boilers Without Tankless Coil and Honeywell L8148 Aquastat Control
BW4/BW5
21
F5 only
A06505
Fig. 22 -- Boilers With Tankless Coil and Honeywell L8124C Aquastat Control and Riello Burners
BW4/BW5
22
10 F (5.6 C)�DIFF
110 F (43 C)
240 F (116 C)
25 F (13.9 C)�DIFF
10 F (5.6 C)�DIFF
SWITCH BREAKS ON�RISE, TURNS BURNER�OFF. CIRCULATOR�OPERATES ON CALL�FOR HEAT.
SWITCH MAKES ON�FALL. BURNER�OPERATES ON�CALL FOR HEAT.
SWITCH MAKES R-B�ON FALL, BREAKS�R-W. BURNER ON,�CIRCULATOR OFF.
SWITCH MAKES R-W,�BREAKS R-B ON RISE�(25 F [13.9 C]�DIFFERENTIAL).
SWITCH MAKES R-W,�BREAKS R-B ON RISE�(10 F [5.6 C]�DIFFERENTIAL).
HI LIMIT�SETTING
LOW LIMIT�AND�
CIRCULATOR�SETTING
A95611
Fig. 23 -- Relationship of Set Points and Differential
Service HintsAvoid inconvenience and service calls by checking these pointsbefore calling for service.
have your service technician check any problem you areunable to correct.
Parts ListAll parts are listed in the following Parts Lists. Parts may beordered through nearest supplier When ordering parts, first obtainthe Model No. from the name plate on boiler, then determine thePart No. (not the Key No.) and the Description of each part fromthe following appropriate illustration and list. Parts for which noPart No. is given are standard items which can be procuredlocally. Be sure to give all this information: The Part No., ThePart Description, The Boiler Model No.
Table 10 – Service Hints
IF SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT. . .POSSIBLE CAUSE WHAT TO DO
Thermostat is not set correctly Reset thermostat above room temperature.Boiler and/or burner may be dirty Clean all flue passages and vent pipe. Have burner cleaned and readjusted.
Burner may not be firing at proper rate Check nozzle size it there is any doubt. Have burner adjusted.Burner may be short---cycling Short---cycling (too frequent off andon) of burner causes sooting. If boiler and/or burner becomes
Burner may be short---cycling dirty at frequent intervals, correct the .dirt condition,. then also correct the controlsetting (or other cause of short---cycling).
Check thermostat heat anticipator and correct setting, if neces---sary, per instruction sheet packed with thermostat.
No power to boiler Check overcurrent protection. Check to be sure power supply circuit is on.Controls out of adjustment Reset according to instructions packed with controls.Radiators not heating Open radiator vents to vent excess air. Check flow control valve (if used). It may
be in closed position.Circulator pump not running Check relay operation.Poor electrical contact Check all control terminals and wire joints.
IF BURNER IS NOISY. .POSSIBLE CAUSE WHAT TO DO
Oil burner fan wheel may be dirty Clean fan wheel with a stiff brush and cleaning solvent. Readjust oil burner.Draft regulator may be stuck Check to see if vane swings freely. Clean if vane is stuck.
IF RADIATORS ARE NOISY. . .POSSIBLE CAUSE WHAT TO DOAir in system Open radiator vents to vent air. Check expansion tank.
RELIEF VALVE LEAKING. . .POSSIBLE CAUSE WHAT TO DODirt on seat Open valve manually. Allow water to run and clear valve seat.
Waterlogged expansion tank Drain tank. See instructions.
BW4/BW5
23
12XXX
132
111
XXX10
XXX4
2XXX
XXX7
XXX5
142
31
9XXX
81
11
11
151
161
1810
1910
2010
A01039
ITEM DESCRIPTION PART NUMBER1 Section Machined Back 403---00---0082 Section Machined Middle 403---00---0073 Section Machined Front 403---00---0064 Nipple Machined 2--- in. --- (2--- in. cast iron push nipple) 433---00---976
5
Tie Rod 1/4X10 1/43 section 146---05---0024 section 146---05---0515 section 146---05---053
6 Nuts head (Hex) ZP (Zinc Plated) 1/4--- in. --- 20 HW---003.02
7 Cut Rope 5/18--- in. X 70---1/2--- in. (NORFAB 400 Serrated BraidedRope) 433---00---955
8 Target Wall (Gemcolite Vacuum Formed Ceramic Fiber 2300’) 146---19---003
9 Dura Blanket 3---8 # 1/2--- in. thickSize --- 3 section---8--- in. X 12--- in., 4 section --- 8--- in. X 20--- in. 5 146---30---031
10
Collector Base3 section 425---00---2794 section 425---00---2805 section 425---00---281
11 Tape Plym Collector insulation1--- in. X 1/16--- in. X 100 Included in Part # 425---00---279, 80, 81
12 Collector Top Included in part # 425---00---279, 80, 8113 Wing Nut 8/32 --- Brass 137---04---007
14 Screw #14 X 3/4 in. HWH SL S.M. SC.(Hex Washer Head, Slotted, Sheet Metal Screw) 146---95---109
15 Gasket PF---EV 5040---150A 146---03---06516 Coil 3.7 GPM (Gallons Per Minute) CDB 146---27---02017 Cover Plate (Not Shown) 146---19---00118 Stud 18---8St. St.(Stainless Steel) 3/8---16X1---1/2--- in. 146---95---11319 Washer Flat 18---8 St. St. (Stainless Steel) 3/8 146---95---11420 Nut Top Lock 18---8 St. St. (Stainless Steel) 3/8 146---95---11521 Plug Solid Black Square Head 1---1/4--- in. (Not Shown) 139500222 400_ Black Silicone Rubber Adhesive Sealant (Not Shown) 146---06---020
BW4/BW5
24
62
72
51
11
14
13 1
2
181
4
110
111
112
A01040
ITEM DESCRIPTION PART NUMBER1 Section Machined Front 403–00–0062 Stud TFL (Threaded Full Length) 3/8–16--in. X 2–1/2--in. 146–95–1253 Whizlok Nut ZP (Zinc Plated) 3/8 146–95–1264 Insulation Swing Door (Gemoclite Vacuum Formed Ceramic Fiber 2300°) 146–14–0145 Hinge Machined 403–00–0106 Rivet RD (Round) HD (Head) Separated Flange ZP 3/8--in. X 1--in. 146–95–1217 Bolt Hex (head) Separated Flange ZP (Zinc Plated) 1/4--in. X 2--in. 146–95–1248 Cut Rope FiberFrax Round Braid 3/8--in. X 48--in. 433–00–9059 Fire Door Wing Machined 403–00–00910 Observation Door Machined 403–00–01411 Washer Lock Plain 5/16--in. 146–95–12312 Bolt 5/16--in. X 3/8--in. Socket SH (Shoulder) BLT (Bolt) 1/4--in. 20 TH (Thread) 146–95–122
Fig. 24 -- Swing Fire Door Assembly
Table 11 – Beckett Oil Burner Service Parts
OIL BURNER REPAIR PARTS--BURNER NOT SHOWN PART NUMBERBurner Motor RP--015.00Fuel Pump RP04501
Oil Solenoid Valve RP04601Ignitor or Ignition Transformer RP02001Oil Primary Control 7184B RY00701
Electrodes for V1 Head (5 section only) 146–19–105Electrodes for F Head (3 and 4 section only) 146–19–104
Oil Burner Head, F--0 1050003Oil Burner Head, F--3 1050002Oil Burner Head, F--6 1050004Oil Burner Head, V--1 Not Stocked--Order from Beckett
Burner Mounting Gasket 14619106Cad Cell 14662085
Oil Burner, 3 section 146--19--355Oil Burner, 4 section 146--19--356Oil Burner, 5 section 146--19--357
BW4/BW5
25
Table 12 – Riello Oil Burner Service PartsRIELLO OIL BURNER REPAIR PARTS
Oil Burner Repair Parts---Burner Not Shown Part NumberBurner Motor 30A065101Fuel Pump * 30A065401
Oil Solenoid Coil * * 30A064901Oil Primary Control 530SE 30A064801
Electrodes 30A065301Photo Cell 30A065701
Oil Burner, 3 section 1050006Oil Burner, 4 section 1050006Oil Burner, 5 section 14619011O---Ring Pump Press 30A065601Electric Air Shutter C7001082Capacitor 12.5uF 30A065201Pump Drive Key 30A064701
84
3XXX
4XXX
21
51
64
721
9b4
1XXX
A01042
Item Description 3 SectionPart Number
4 SectionPart Number
5 SectionPart Number
Complete Jacket 42670289AB 42670290AB 42670291AB1 Panel Right Empire II 42570244AB 42570245AB 42570246AB2 Jacket Panel, Back 42570269AB 42570269AB 42570269AB3 Jacket Panel, Top 42570254AB 42570255AB 42570256AB4 Panel Left Empire II 42570264AB 42570265AB 42570266AB5 Panel Upper Front Empire II 42570267AB 42570267AB 42570267AB6 Acorn Nut --- 5/16” 146---95---042 146---95---042 146---95---0427 #14 Jacket Screw 146---95---074 146---95---074 146---95---0748 Stand---Off 146---95---103 146---95---103 146---95---1039 Panel, Lower Front Empire II 42570268AB 42570268AB 42570268AB
BW4/BW5
26
LEFT SIDE PANEL
BACK PANELRIGHT SIDE PANEL
JACKET SCREW
LOWER FRONT PANELSHOWN HERE FOR CLARITY
ACORN NUT
STAND_OFF
OPENING FOR OPTIONALEXPANSION TANK OR AIRELIMINATOR
TRIDICATOR OPENING
COLLECTOR OPENINGJACKET TOP
BOILER SUPPLYOPENING
FRONT PANEL
A01041
Fig. 25 -- Jacket Parts
4
2a(WITHOUTTANKLESSCOIL)
2b(WITHTANKLESSCOIL)5a, 5b
FRONT VIEW
WATEROUTLET
RIGHT SIDE VIEW
1
6
7
5OPTIONALTANKLESS
COILWATERHEATER
WITH 1/2” NPTCONNECTIONS
3a
A02216
ITEM DESCRIPTION 3 SECTION 4 SECTION 5 SECTION1 Beckett AFG F--Head oil Burner 1050036 1050037 ____1 Beckett AFG Variable Head Oil Burner ____ ____ 146--19--3571 Riello Oil Burner 1050006 1050006 146--19--0112a L8148A--1124 Aquastat Control (no tankless coil) 433--00--521 433--00--521 433--00--5212b L8124C--1094 Aquastat Control (with tankless coil) 146--62--022 146--62--022 146--62--0223a Taco 007 Circulator CI--001.03 CI--001.03 CI--001.033c Taco Circulator Gaskets 146--26--050 146--26--050 146--26--050____ 1--1/4” Flange set with gaskets, nuts, and bolts 146--26--049 146--26--049 146--26--0494 Temperature/Pressure Gauge 2” Stem 1260006 1260006 12600065a 1--1/4” x 2--1/2” Pipe Nipple 146--07--044 146--07--044 146--07--0445b 1--1/4” x 3/4” x 1--1/4” Reducing Tee 1510001 1510001 15100016 3/4” Drain Valve 146--22--000 146--22--000 146--22--0007 3/4” Relief Valve 146--22--011 146--22--011 146--22--011
Fig. 26 -- Repair Parts
Copyright 2006 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: IM---BW4R---02Replaces:IM--BW4R
Printed in U.S.A. Edition Date: 10/06
BW4/BW5