PROJECT
LOCATION/TYPE
WA-300 Dual Relay Automatic Wall Switch
Light level sensor holds lightsoff on secondary relay whenenough daylight is present
Optional walk-throughmode for increasedsavings
Dual switch buttons; eachcontrols a separate relay
Contains two relays for controlling two indepen-dent lighting loads or circuits; secondary relay isisolated
Advanced control logic based on RISC microcon-troller provides:
Detection Signature Processing eliminates falsetriggers and provides immunity to RFI and EMI
SmartSet automatically adjusts sensitivity andtime delay settings to fit occupant patterns
Walk-through mode turns lights off 3 minutesafter the area is initially occupied if no move-ment is detected within 30 seconds
One-step light level control set-up learnsdesired hold-OFF level
The WA-300 passive infrared automatic wall switchturns lighting on and off based on occupancy.These switches contain two relays for controllingtwo independent lighting loads or circuits.
Bi-level Control
Applications
Achieving bi-level lighting control greatly enhancesenergy savings in building areas such as officesand conference rooms. For exhaust fan applica-tions, the sensor can shutoff the exhaust fan relay10 minutes after the lighting relay is shutoff. Inaddition, the sensors hard lens enables it to beused in public spaces susceptible to vandalism.
Operation
The WA-300 replaces existing wall switches andoperates between 100 and 300 volts. The sensoruses advanced passive infrared technology todetect occupancy. It detects the differencebetween infrared energy from a human body inmotion and the background space. Each of the WA-300s relays can simultaneously control a separatelighting load and each can be set for either auto-matic or manual on. Dual ON/OFF buttons allowthe user to manually turn on and off each of theloads. After a period of time when no occupancy isdetected, lighting automatically switches off.
Two relays for control oftwo separate lightingloads or circuits
DescriptionProductOverview
Features Zero-cross relay guarantees reliable operationwith non-linear loads even with temperaturechanges and product aging
Choice of automatic-ON or manual-ON opera-tion; selectable for each relay
Built-in light level sensor in the second relayholds lights off until natural light levels drop
Optional audible alert for impending shutoff
For safety, there is no leakage to load in theOFF mode and sensor is safety grounded
Hard lens makes sensor resistant to vandalism
Units are tamper resistant
LED indicates occupancy detection
SmartSet technology automatically selects optimalsettings for each space
The WA-300 features a built-in light level sensorthat affects the second (secondary) relay. If ade-quate daylight is present, the sensor will holdsecondary lights off until daylight levels drop, pro-viding increased energy savings. The WA-300satisfies energy codes requiring bi-level or daylightcontrol switching. The two relays in the sensor giveit the unique ability to control two lighting loadsindependently. This provides A/B switching wherethe user can achieve half-lighting (or anotherdesired portion) from a single switch.
O c c u p a n c y S e n s o r s
www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5
-
Controls & Installation
Wiring
Coverage &Settings
Watt Stopper/Legrand
Pub. No. 17104
OrderingInformation
Specifications Universal 120/230/277 VAC; 50/60 Hz operation Coverage of 180 degrees, maximum 300 ft2, 150
ft2 for desktop activity Time delays: SmartSet (automatic), fixed (5, 10,
15, 20, 20 + 10, or 30 minutes), walk-through,test-mode
Sensitivity adjustment: SmartSet (automatic) orreduced sensitivity
1.0 mm hard, poly IR 2 lens; 2 level lens forsuperior desktop detection
Built-in light level sensor, works from 8 to 180footcandles (86 to 1,937 lux), on secondary relay
Compatible with all electronic ballasts and PLlamp ballast systems
Dimensions: 2.6" x 1.7" x 1.9"(67mm x 43mm x 49mm) L x W x D
UL and CUL listed; 5 year warranty
WA-300 Technical Information
Product Controls Installation
Bi-level Wiring
Coverage
2 Circuit Wiring
DIP Switch Settings
O c c u p a n c y S e n s o r s
WA-300-W
WA-300-A
WA-300-I
WA-300-G
WA-300-B
White
Lt. Almond
Ivory
Grey
Black
120 VAC; 50/60 Hz
or
230/277 VAC; 50/60 Hz
Catalog No. Color Voltage Load Requirement Coverage
One ASP-211 single-gang cover plate included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover platewith switch option (specify color).
0-800 Watt Ballast,1/4 hp
or0-1200 Watt Ballast,1/4 hp
180, 300 ft2 (27.9 m2)
25'(7.6m)
10'(3.1m)
4.0'(1.2m)
25'(7.6m)
floor
The 2-level lens providessuperior coverage at a desk-top level by allowing thesensor to detect vertical aswell as horizontal motion
12345678
ON/OFF ButtonsRelay 1Relay 2
DIPSwitches
LED
Lens
Neutral
Ground
Blue
Line Black
SecondaryLoad
Brown
PrimaryLoad
Red
White
Blue
Ground
PrimaryLoad
SecondaryLoad
Neutral White
Red
BrownLine 2
Line 1 Black
Neutral White
5
Auto OnManual On
Relay 1 ON Mode
SmartSet/Test
10 minutes15 minutes20 minutes
20 + 10* minutes30 minutes
override
5 minutes
1 2 3Time Delay
DIP Switch #s:
=ON =OFF
6
Auto OnManual On
Relay 2 ON Mode
4
DisabledEnabled
Walk Through 1 2 3 4 5 6 7 8
Time Delay
FACTORYPRESETS
Walk Through
ON
Relay 1 On Mode
Relay 2 On Mode
Audible Alerts
Sensitivity
Factory Settings
7
DisabledEnabled
Audible Alerts
DIP Switch #
DIP Switch #
8
HighLow, 50%
Sensitivity
DIP Switch #
DIP Switch #
DIP Switch #
*Relay 2 shuts off 10 min. after relay 1 Bypass occupancy & light level functions. Loads manually controlled with WA-300 buttons.
Project: Location: WA300W: WA300A: WA300I: WA300B: WA300G: