3LOW VOLTAGE ELECTRICAL INSTALLATIONS:Methods of installation and current-carrying capacities
based on IEC 60364-5-52 Ed.3
![Page 2: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/2.jpg)
SUMMARY Methods of installation:
Table A.52.3 Examples of methods of installation providing instructions for obtaining current-carrying capacity
Current-carrying capacities:
Table B.52.1 Installation reference methods forming basis of tabulated current-carrying capacities
Table B.52.2 Current-carrying capacities in amperes for methods of installation in Table B.52.1 :
- PVC insulation/two loaded conductors, copper or aluminium
- Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Table B.52.3 Current-carrying capacities in amperes for methods of installation in Table B.52.1 :
- XLPE or EPR insulation, two loaded conductors/copper or aluminium
- Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Table B.52.4 Current-carrying capacities in amperes for methods of installation in Table B.52.1:
- PVC insulation, three loaded conductors/copper or aluminium
- Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Table B.52.5 Current-carrying capacities in amperes for methods of installation in Table B.52.1 :
- XLPE or EPR insulation, three loaded conductors/copper or aluminium
- Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Table B.52.6 Current-carrying capacities in amperes for installation method C of Table B.52.1 :
- Mineral insulation, copper conductors and sheath - PVC covered or bare exposed to touch
- Metallic sheath temperature: 70 °C, reference ambient temperature: 30 °C
Table B.52.7 Current-carrying capacities in amperes for installation method C of Table B.52.1 :
- Mineral insulation, copper conductors and sheath
- Bare cable not exposed to touch and not in contact with combustible material
- Metallic sheath temperature: 105 °C, reference ambient temperature: 30 °C
Table B.52.8 Current-carrying capacities in amperes for installation methods E, F and G of Table B.52.1 :
- Mineral insulation, copper conductors and sheath/PVC covered or bare exposed to touch
- Metallic sheath temperature: 70 °C, reference ambient temperature: 30 °C
Table B.52.9 Current-carrying capacities in amperes for installation methods E, F and G of Table B.52.1 :
- Mineral insulation, copper conductors and sheath – Bare cable not exposed to touch
- Metallic sheath temperature: 105 °C, reference ambient temperature: 30 °C
Table B.52.10 Current-carrying capacities in amperes for installation methods E, F and G of Table B.52.1 :
- PVC insulation, copper conductors
- Conductor temperature: 70 °C, reference ambient temperature: 30 °C
Table B.52.11 Current-carrying capacities in amperes for installation methods E, F and G of Table B.52.1 :
- PVC insulation, aluminium conductors
- Conductor temperature: 70 °C, reference ambient temperature: 30 °C
page
3-9
10
11
12
13
14
15
16
17
18
19
20
1Methods of installation and current-carrying capacities based on IEC 60364-5-52 Ed.3
![Page 3: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/3.jpg)
2Methods of installation and current-carrying capacities based on IEC 60364-5-52 Ed.3
SUMMARY
Table B.52.12 Current-carrying capacities in amperes for installation methods E, F and G of Table B.52.1 :
- XLPE or EPR insulation, copper conductors
- Conductor temperature: 90 °C, reference ambient temperature: 30 °C
Table B.52.13 Current-carrying capacities in amperes for installation methods E, F and G of Table B.52.1 :
- XLPE or EPR insulation. aluminium conductors
- Conductor temperature: 90 °C, reference ambient temperature: 30 °C
Table B.52.14 Correction factor for ambient air temperatures other than 30 °C to be applied to
the current-carrying capacities for cables in the air
Table B.52.15 Correction factors for ambient ground temperatures other than 20 °C to be applied to
the current-carrying capacities for cables in ducts in the ground
Table B.52.17 Reduction factors for one circuit or one multi-core cable or for a group of more than one circuit,
or more than one multi-core cable, to be used with current-carrying capacities of Tables
B.52.2 to B.52.13
Table B.52.18 Reduction factors for more than one circuit, cables laid directly in the ground
- Installation method D2 in Tables B.52.2 to B.52.5 - Single-core or multi-core cables
Table B.52.19 Reduction factors for more than one circuit, cables laid in ducts in the ground
- Installation method D1 in Tables B.52.2 to B.52.5
page
21
22
23
24
25
26
27-28
![Page 4: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/4.jpg)
3METHODS OF INSTALLATION
![Page 5: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/5.jpg)
4METHODS OF INSTALLATION
![Page 6: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/6.jpg)
5METHODS OF INSTALLATION
![Page 7: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/7.jpg)
6METHODS OF INSTALLATION
![Page 8: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/8.jpg)
7METHODS OF INSTALLATION
![Page 9: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/9.jpg)
8METHODS OF INSTALLATION
![Page 10: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/10.jpg)
9METHODS OF INSTALLATION
![Page 11: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/11.jpg)
10CURRENT-CARRYING CAPACITIES
![Page 12: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/12.jpg)
11CURRENT-CARRYING CAPACITIES
![Page 13: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/13.jpg)
12CURRENT-CARRYING CAPACITIES
![Page 14: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/14.jpg)
13CURRENT-CARRYING CAPACITIES
![Page 15: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/15.jpg)
14CURRENT-CARRYING CAPACITIES
![Page 16: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/16.jpg)
15CURRENT-CARRYING CAPACITIES
![Page 17: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/17.jpg)
16CURRENT-CARRYING CAPACITIES
![Page 18: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/18.jpg)
17CURRENT-CARRYING CAPACITIES
![Page 19: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/19.jpg)
18CURRENT-CARRYING CAPACITIES
![Page 20: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/20.jpg)
19CURRENT-CARRYING CAPACITIES
![Page 21: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/21.jpg)
20CURRENT-CARRYING CAPACITIES
![Page 22: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/22.jpg)
21CURRENT-CARRYING CAPACITIES
![Page 23: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/23.jpg)
22CURRENT-CARRYING CAPACITIES
![Page 24: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/24.jpg)
23CURRENT-CARRYING CAPACITIES
![Page 25: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/25.jpg)
24CURRENT-CARRYING CAPACITIES
![Page 26: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/26.jpg)
25CURRENT-CARRYING CAPACITIES
![Page 27: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/27.jpg)
26CURRENT-CARRYING CAPACITIES
![Page 28: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/28.jpg)
27CURRENT-CARRYING CAPACITIES
![Page 29: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/29.jpg)
28CURRENT-CARRYING CAPACITIES
![Page 30: LOW VOLTAGE ELECTRICAL INSTALLATIONS:3 - Top Cable · - Bare cable not exposed to touch and not in contact with combustible material - Metallic sheath temperature: 105 °C, reference](https://reader033.vdocument.in/reader033/viewer/2022052805/605ccbd7c2cfdc0c9d753c9b/html5/thumbnails/30.jpg)
29
Top Cable InternationalParc d’Activitats Econòmiques Can Sant JoanCamí Vell de Sant Cugat s/n08191 Rubí (Barcelona) SPAINTel +34 935 880 911 / +34 935 882 800Fax +34 935 883 [email protected]
SCANKAB Cables A/SMalervae nget 3DK-5560 AarupTel +45 70 20 34 55Fax +45 64 43 37 [email protected]
www.topcable.com
Top Cable SingaporeTel +65 626 211 61Fax +65 626 211 [email protected]
Top Cable South AfricaTel +27 11 397 35 54Fax +27 11 397 [email protected]
TOP CABLE