Motor Controls
EETE 2 Technical Elective 2
![Page 2: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/2.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 2/45
OUTLINE
• Symbols: NEMA vs IEC
• Pilot Devices
•
Wiring vs Schematic Diagrams• Overcurrent vs Overload Protection
• Low Voltage Release vs Low Voltage
Protection
![Page 3: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/3.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 3/45
SYMBOLS
![Page 4: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/4.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 4/45
Symbols
•
Motor control language consists of symbols toform a circuit diagram.
• Contactors and motor starters are ratedaccording to size and type of load they are
designed to handle.• The National Electrical Manufacturers Association
(NEMA) and the International ElectrotechnicalCommission (IEC) are two organizations that rate
contactors and motor starters.
• Each organization has its own set of symbols.
![Page 5: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/5.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 5/45
NEMA
•
NEMA Contactors and Starters are designed instandardized sizes from 00 to 9.
• Each of these sizes has a defined current, and
a resultant voltage and frequency dependent
horsepower rating.
• No matter who manufactures the device, the
current and horsepower rating will be
identical for a given size.
![Page 6: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/6.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 6/45
NEMA
•
If a standard motor is being used, once itshorsepower rating is selected, the Contactor
or Starter horsepower rating is simply
matched to that of the motor.
• The nameplate of the Contactor or Starter is
labeled with the NEMA size, the various
horsepower and voltage ratings assigned to
the size, and its continuous current capabilityat which the NEMA Standard temperature rise
will not be exceeded.
![Page 7: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/7.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 7/45
NEMA• NEMA motor-control devices have generally become
known for their very rugged, heavy-duty construction.• Because of their rugged design, NEMA devices are
physically larger than IEC devices.
![Page 8: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/8.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 8/45
IEC
•
IEC Contactors and Starters are not designedto a standardized size.
• Instead a manufacturer certifies that he/she
has designed the device to meet a number of defined applications referred to as Utilization
Categories.
![Page 9: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/9.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 9/45
IEC
•
To properly match the IEC Contactor or Starterto the application requirements, the user
must know both the application requirements
and the capability of the Contactor or Starter
being selected.
• If the Contactor or Starter will not provide a
reasonable operational life in the application,
a larger device would need to be selected.
![Page 10: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/10.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 10/45
IEC• Not all applications require a heavy-duty industrial
starter.• In applications where space is more limited and the
duty cycle is not severe, IEC devices represent a cost-effective solution.
![Page 11: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/11.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 11/45
NEMA and IEC
Ratings Comparison
• NEMA Contactors and Starters can beapplied to AC-3 applications.
• They may also be applied at their normalstandardized ratings to AC-4 applicationswhere there will be no more than fiveopenings per minute and no more than 10openings during a 10-minute period.
• Beyond this level, NEMA provides a plugreversing and jogging duty table withmodified ratings for improved operating life.
• Many IEC devices also have a NEMA rating.
![Page 12: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/12.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 12/45
Additional Comparisons
![Page 13: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/13.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 13/45
Other Organizations
• There are several other organizations that havedeveloped standards and tests for electricalequipment.
•For example, contactors are tested byUnderwriters Laboratory (UL) using testprocedure UL508, which specifies a maximumhorsepower rating for which a contactor can be
used.• Deutsches Institut für Normung (DIN), the
German national standards organization
![Page 14: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/14.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 14/45
NEMA vs IEC
• The following comparison of circuit symbols is
based upon the following
international/national specifications:
• IEC 60617 graphic symbol database
(DIN EN 60617-2 to DIN EN 60617-12)
• NEMA ICS 19-2002, ANSI Y32.2/
IEEE 315/315 A, CSA Z99
![Page 15: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/15.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 15/45
NEMA vs IEC
![Page 16: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/16.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 16/45
NEMA vs IEC
![Page 17: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/17.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 17/45
NEMA vs IEC
![Page 18: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/18.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 18/45
NEMA vs IEC
![Page 19: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/19.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 19/45
NEMA and IEC Terminal Markings
NEMA d IEC C t ll M ki
![Page 20: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/20.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 20/45
NEMA and IEC Controller Markings
and Elementary Diagrams
![Page 21: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/21.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 21/45
PILOT DEVICES
![Page 22: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/22.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 22/45
Pilot Devices:Pushbuttons
• A pushbutton is a control device used to
manually open and close a set of contacts.
• Pushbuttons are available in a flush mount,
extended mount, with a mushroom head,
illuminated, or non-illuminated.
• Pushbuttons come with either normally
open, normally closed, or a combination
contact block.
![Page 23: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/23.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 23/45
Pilot Devices: Selector switches
• Selector switches are also used to manually
open and close contacts. Selector switchescan be maintained, spring return, or key
operated.
• Selector switches are available in 2-, 3-, and4-position types.
![Page 24: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/24.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 24/45
Pilot Devices: Pilot lights
• Pilot lights provide visual information of the
circuit’s operating condition.
• Pilot lights are normally used for ON/OFF
indication, caution, changing conditions, and
alarm signaling.
• Pilot lights are available with a variety of lens
colors, such as red, green, amber, blue, white,
or clear.
![Page 25: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/25.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 25/45
WIRING VS SCHEMATIC DIAGRAMS
![Page 26: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/26.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 26/45
WIRING DIAGRAM• A wiring diagram shows, as closely as possible,
the actual location of all component parts of the device.
• The open terminals (marked by an open circle)
and arrows represent connections made bythe user.
• Since wiring connections and terminalmarkings are shown, this type of diagram is
helpful when wiring the device or tracingwires when troubleshooting.
![Page 27: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/27.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 27/45
WIRING DIAGRAM
• Bold lines denote the power circuit and thin
lines are used to show the control circuit.Black wires are conventionally used in power
circuits and red wire in control circuits for AC
magnetic equipment.
![Page 28: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/28.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 28/45
SCHEMATIC DIAGRAM
• An elementary diagram is a simplified circuit
illustration.
• Devices and components are not shown in
their actual positions.
• All control circuit components are shown as
directly as possible, between a pair of vertical
lines representing the control power supply.
![Page 29: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/29.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 29/45
SCHEMATIC DIAGRAM• Components are arranged to show the
sequence of operation of the devices and howthe device operates.
• The effect of operating various auxiliary
contacts and control devices can be readilyseen.
• This helps in troubleshooting, particularly withthe more complex controllers.
• This form of electrical diagram is sometimesreferred to as a “schematic” or “line” diagram.
![Page 30: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/30.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 30/45
OVERCURRENT VS OVERLOADPROTECTION
![Page 31: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/31.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 31/45
OVERCURRENT PROTECTION
•
Overcurrent protection devices are installed inthe power circuit to protect the conductors
and may exist in the form of fuses or circuit
breakers
![Page 32: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/32.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 32/45
![Page 33: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/33.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 33/45
OVERLOAD PROTECTION
•
If one overload contact is used, an overloadon any line will cause the overload contact to
open.
• When three overload contacts are used, the
overload contacts are connected is series.
Each contact is controlled by the adjacent
overload heater.
![Page 34: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/34.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 34/45
TYPES OF CONTROL CIRCUITS
![Page 35: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/35.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 35/45
Low Voltage Release
•
The following terms are generally accepted as havingthe same meaning:A. Under voltage release (UVR)
B. Low voltage release (LVR)
C. No Voltage release (NVR)
Operation:The motor will stop when there is supply voltage failure andwill restart automatically when the supply voltage isrestored.
• The term “two-wire” control is given to this type of circuit.
• Pilot devices such as float switches, limit switches, andtemperature controls are single contact devicesrequiring two conductors.
![Page 36: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/36.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 36/45
Low Voltage Release
![Page 37: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/37.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 37/45
Low Voltage Release• The term “2-wire” control is derived from
the fact that in the basic circuit, only two
wires are required to connect the pilotdevice to the starter.
![Page 38: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/38.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 38/45
Low Voltage Protection
•
The following terms are generally accepted as havingthe same meaning:A. Under voltage protection (UVP)
B. Low voltage protection (LVP)
C. No Voltage protection (NVP)
Operation:The motor will stop when there is supply voltage failure and will NOT restart automatically when the supply voltage isrestored.
• The term “three-wire” control is given to this type of circuit.
• An auxiliary contact is connected in parallel with the startbutton. The auxiliary contacts seal in the circuit to keep thecoil energized after the start push button is released.
![Page 39: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/39.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 39/45
Low Voltage Protection
![Page 40: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/40.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 40/45
Low Voltage Protection• The term “3-wire” control is derived from
the fact that in the basic circuit, at least
three wires are required to connect thepilot devices to the starter.
![Page 41: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/41.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 41/45
Example
•A three phase, 575 V, 60 Hz, 40 Hp SquirrelCage Induction Motor is to be connected for
full-voltage starting. It has a service factor of
1.15. Ambient Temperature is 28˚C.
Nameplate current is 38 A.
• Determine:
1. FLC of the motor
2. NEMA Starter Size
3. FLA of the motor
![Page 42: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/42.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 42/45
Example 1• Solution:
1. FLC of the motorSee Table 430.250 NEC 2011 or Table 4.30.14.4 PEC
2002
Nameplate values: three phase ,575 V, 60 Hz, 40 HpFLC = 41 A
2. NEMA Starter Size:
See NEMA Motor Starter Sizing Chart
Use: NEMA Size 3
3. FLA = Nameplate Value
FLA = 38 A
![Page 43: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/43.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 43/45
Example 2
•A 3 phase, 460 V, 60 Hz, 10 Hp Squirrel CageInduction Motor is to be connected for full-
voltage starting. It has a service factor of 1.15.
Ambient Temperature is 28˚C.
Nameplatecurrent is 12 A.
• Determine:
1. FLC of the motor
2. NEMA Starter Size
3. FLA of the motor
![Page 44: NEMA IEC and Pilot Device Presentation](https://reader030.vdocument.in/reader030/viewer/2022021303/577cdae81a28ab9e78a6dd9c/html5/thumbnails/44.jpg)
7/28/2019 NEMA IEC and Pilot Device Presentation
http://slidepdf.com/reader/full/nema-iec-and-pilot-device-presentation 44/45
Example