Page 1: North - B.R. Miller and Company, Inc.brmillercompany.com/wp-content/uploads/2016/01/019M0.01.pdfprovide opposed-blade volume dampers at each air terminal device. 14. coordinate location

123456789101112131415

123456789101112131415

A

B

C

D

E

F

G

H

I

J

K

LC

OP

YR

IGH

T 2

01

1 -

AL

L R

IGH

TS

RE

SE

RV

ED

- N

O P

OR

TIO

N(S

) M

AY

BE

RE

PR

OD

UC

ED

WIT

HO

UT

EX

PR

ES

SE

D W

RIT

TE

N C

ON

SE

NT

OF

J H

OL

ME

S A

RC

HIT

EC

TU

RE

, P

LL

C

16

16

PROJ. NO.:

DATE:

938 First Avenue

North

Nashville, TN 37201

615.796.0256

I.C. Thomasson Associates, Inc.

CONSULTING ENGINEERS

2950 KRAFT DRIVE, SUITE 500

NASHVILLE, TN. 37204

PHONE (615) 346-3400

FAX (615) 346-3550

www.icthomasson.com

ICT PROJECT No. 120376.41

2012003.00

TC

AT

Cla

rksvil

le R

enovati

ons

135 I

nte

rnati

onal

Blv

d, C

lark

svil

le, T

N 3

7040

Ten

nessee B

oard

of

Reg

en

ts

10-23-2015

SB

C# 1

66/0

46-0

1-2

010E

A

1

2

MINI-SPLIT SYSTEM UNIT SCHEDULE

1 2 1 2 1

A

MARK

BASIS OF DESIGN

MODEL NUMBER

TYPE

AREA SERVED

TOTAL CFM

ESP (IN WG)

ELECTRICAL

VOLTAGE

MCA INDOOR/OUTDOOR

MOCP

MOTOR INDOOR/OUTDOOR

COOLING

TOTAL CAPCITY (MBH)

SENSIBLE CAPACITY (MBH)

HEATING

TOTAL CAPACITY (MBH)

SOUND (dBA) INDOOR/OUTDOOR

INDOOR UNIT DIMENSIONS WxDxH (IN)

INDOOR UNIT WEIGHT (LBS)

ASSOCIATED CONDENSING UNIT (CU)

CONDENSING UNIT DIMENSIONS WxDxH (IN.)

CONDENSING UNIT WEIGHT (LBS.)

MODEL NUMBER

SEER

NOTES

A A

2

MECHANICAL GENERAL NOTES:

1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL

ARRANGEMENT OF SYSTEMS. DRAWINGS SHALL NOT BE SCALED.

2. THE CONTRACTOR IS REQUIRED TO VISIT THE SITE AND BECOME

FAMILIAR WITH EXISTING CONDITIONS PRIOR TO SUBMITTING A BID.

3. THE DRAWINGS MAY NOT SHOW ALL EXISTING ITEMS OR

CONDITIONS. CONTRACTOR SHALL NOT RECEIVE EXTRA PAYMENT

FOR REQUIREMENTS WHICH CAN BE INFERRED THROUGH

OBSERVATION OF EXISTING CONDITIONS AT THE SITE. IN THE

EVENT CONCEALED CONDITIONS ARE ENCOUNTERED WHICH MAY

VARY SIGNIFICANTLY FROM THOSE INDICATED ON THE DRAWINGS,

NOTIFY THE DESIGNER BEFORE PROCEEDING WITH WORK.

4. CONTRACTOR SHALL FIELD VERIFY BY MEASUREMENT THE EXACT

LOCATION OF EQUIPMENT, DUCTWORK, PIPING, STRUCTURE, AND

OTHER CONDITIONS WHICH WILL AFFECT INSTALLATION.

CONTRACTOR SHALL LOCATE EQUIPMENT AND ROUTE DUCTWORK

AND PIPING TO AVOID CONFLICTS AND INTERFERENCES WITH FIELD

CONDITIONS.

5. PRIOR TO ANY INSTALLATION, CLOSELY COORDINATE ALL

MECHANICAL WORK WITH PLUMBING, FIRE PROTECTION,

ELECTRICAL, ARCHITECTURAL, AND STRUCTURAL WORK.

CONTRACTOR TO ENSURE ALL EQUIPMENT AND SERVICES WILL FIT

IN AVAILABLE SPACES ALLOWING CEILING HEIGHTS INDICATED ON

ARCHITECTURAL PLANS. INSTALL EQUIPMENT SO AS TO PROVIDE

CLEARANCES SHOWN ON DRAWINGS AND AS RECOMMENDED BY

MANUFACTURER FOR AIRFLOW, SERVICE, MAINTENANCE, AND

FILTER REMOVAL AS APPLICABLE.

6. COORDINATE DUCT, PIPING, AND EQUIPMENT LOCATIONS WITH

ELECTRICAL PANEL LOCATIONS. DO NOT PASS ANY MECHANICAL

OR PLUMBING ITEMS DIRECTLY OVER ELECTRICAL PANELS. SEE

ELECTRICAL DRAWINGS FOR EXACT PANEL LOCATIONS.

7. ALL CUTTING AND PATCHING SHALL BE COORDINATED WITH THE

GENERAL CONTRACTOR. ALL PATCHING SHALL RESTORE EACH

DAMAGED SURFACE TO ITS ORIGINAL FINISH.

8. CEILING DIFFUSER AND REGISTER LOCATIONS ARE APPROXIMATE

ONLY. EXACT LOCATIONS TO BE DETERMINED BY ARCHITECTURAL

REFLECTED CEILING PLANS. CLOSELY COORDINATE DUCT AND PIPE

ROUTING WITH ARCHITECTURAL REFLECTED CEILING PLANS.

9. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE INSIDE CLEAR.

ALLOWANCE MUST BE MADE IN SHEET METAL SIZE WHERE DUCT

LINER IS SPECIFIED.

10. LOW-PRESSURE DUCT RUNOUTS TO DIFFUSERS AND REGISTERS TO

BE AS SCHEDULED UNLESS OTHERWISE INDICATED ON PLANS.

CONTRACTOR TO PROVIDE A TRANSITION AT NECK OF EACH AIR

TERMINAL DEVICE AS NECESSARY.

13. WHERE BRANCH TAPS OCCUR, PROVIDE INDIVIDUAL SPIN-IN

FITTINGS WITH MANUAL-VOLUME DAMPERS FOR BALANCING. DO

NOT USE TYPE WITH AIR SCOOP/EXTRACTOR. ADDITIONALLY,

PROVIDE OPPOSED-BLADE VOLUME DAMPERS AT EACH AIR

TERMINAL DEVICE.

14. COORDINATE LOCATION AND PROVIDE DUCT ACCESS DOORS FOR

ACCESS TO ALL FIRE DAMPERS. DUCT ACCESS DOORS MAY BE

OMITTED WHERE TYPE "A" FIRE DAMPERS ARE ACCESSIBLE

THROUGH SIDEWALL REGISTER FACE. INSURE DUCT ACCESS DOORS

AND DAMPERS ARE ACCESSIBLE THROUGH CEILINGS AND WALLS.

LOCATE DUCT ACCESS DOORS ABOVE SPACES WITH LAY-IN CEILINGS

OR EXPOSED CEILINGS WHERE POSSIBLE. REFER TO

ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING TYPES.

15. ALL EXPOSED DUCTWORK, PIPING, AND EQUIPMENT IN FINISHED

SPACES TO BE INSTALLED AS HIGH AS POSSIBLE ABOVE FINISHED

FLOOR.

SURROUNDING SURFACES IN ACCORDANCE WITH ARCHITECT’S

INSTRUCTIONS.

16. ALL MOISTURE CONDENSATE DRAIN (MCD) LINES SHALL BE

PLENUM USE WHEN ROUTED INDOORS. LINES SHALL BE "DWV"

17. PATCH ALL RATED FLOOR AND RATED WALL PENETRATIONS WITH

18. PAINT ROOF FANS, GAS VENTS, ETC., TO MATCH

OF ALL RATED WALLS & SMOKE PARTITIONS. SEE DETAILS.

19. FIRESTOP/DRAFTSTOP ALL DUCT AND PIPING PENETRATIONS

INSULATED WITH 1" ARMAFLEX AP TYPE INSULATION RATED FOR

U.L. APPROVED ASSEMBLIES IN ACCORDANCE WITH IBC REQUIREMENTS.

COPPER WITH 95-5 SOLDER JOINTS WITH APPROPRIATE FLUX.

ALL FITTINGS SHALL BE DRAINAGE PATTERN MINIMUM 1/8 "

PER FOOT TOWARD DRAIN. PROVIDE LINE SIZE CLEANOUTS

SPACED MAXIMUM 50’-0" ON CENTER. SEE PLUMBING DRAWINGS

FOR EXACT LOCATION OF FLOOR DRAINS, HUB DRAINS AND SINK

P-TRAP CONNECTIONS FOR MCD DISCHARGE.

AC-3/AC-4

MITSUBISHI

MSZ-GE09NA

OFFICE

235

0.2

208/1/60

1/15

20

50W/40W

12.2

10.1

10.9

31/46

36x10x12

55

CU-3

31x12x28

130

MXZ-2B20NA

18.0

AC-1

MITSUBISHI

PKA-A18

IT ROOM

370

0.2

208/1/60

1/13

20

30W/40W

18

9.72

19

43/46

36x10x12

35

CU-1

31x12x24

105

PUZ-A18

15.2

SYMBOL NECK FACE CFM SP RUNOUT

RA/EA

RB/EB

RC/EC

RD/ED

RE/EE

RF/EF

6" SQ

8" SQ

10" SQ

12" SQ

14" SQ

8"x8"

10"x10"

12"x12"

14"x14" 500

700

8"x4"/6"

10"x6"/8"

14"x6"/10"

16"x8"/12"

18"x8"/14"

.06

.06

.06

.06

.06

200

350

25

24"x10"/18".06

16"x16"

18"x18"16" SQ 1000 .06 20"x10"/16"

RG/EG

22" SQ 24"x24" 1750 .06 24"x12"/18"

18" SQ

PERFORMANCE BASIS:

20"x20" 1250

RH/EH

CEILING GRILLES & REGISTERS

PERFORMANCE BASIS:

SA

SYMBOLADAPTOR/ FACE MAX MAX MAX

THROW RUNOUT SIZENECK SIZE SIZE CFM

SB

SC

SD

SE

24"x24"

24"x24"

SP NC

6"

8"

10"

12"

14"

24"x24"

24"x24"

24"x24"

350

4-WAY

4-WAY

4-WAY

4-WAY

4-WAY

UNLESS OTHERWISE INDICATED ON PLANS.

500

700

0.05

0.05

0.05

0.05

0.05

20

20

20

20

20

10"x7"/8"

12"x8"/10"

14"x9"/12"

100

200

CEILING DIFFUSER SCHEDULE

2.

25

25

25

25

25

25

25

100

MAX NC

8"x5"/6"

16"x10"/14"

1.

1.

2.

TITUS MODEL 50-F OR APPROVED EQUAL WITH 1/2 "x 1/2 " EGG-CRATE CORE.

COORDINATE W/ARCHITECT FOR DIFFUSER & GRILLE COLOR

SELECTION.

TITUS OMNI OR APPROVED EQUAL FOR DIFFUSERS SA THRU SE AND SSA THRU SSD.

COORDINATE W/ARCHITECT FOR DIFFUSER & GRILLE COLOR

SELECTION.

RECTANGULAR DUCT TURNING DOWN

ROUND DUCT TURNING DOWN

DOUBLE LINE TO SINGLE

BRANCH TAP OFF MAIN W/45^

W/DAMPER (LOW PRESSURE)

TRANSITION IN DUCT (NOT

DIRECTION OF AIRFLOW)

REGISTER TAPPING INTO

BOTTOM OF DUCT

DUCT TERMINATION

45 FULL RADIUS TURN

FULL RADIUS TURN

SB INDICATES A SIZE "B" SUPPLY

RB

100

INDICATES A SIZE "B" RETURN

REGISTER SET FOR 100 CFM

SQUARE ELBOW

W/TURNING VANES

FIRE DAMPER

FIRE/SMOKE DAMPER

LINE DUCTWORK

150 DIFFUSER SET FOR 150 CFM

BOOT FITTING OR SPIN-IN FITTING

FD

FSD

EA INDICATES A SIZE "A" EXHAUST

REGISTER SET FOR 50 CFM50

CEILING RETURN/EXHAUST

GRILLE/REGISTER

CEILING SUPPLY DIFFUSER

EQUIPMENT ID TAG

EQUIPMENT NUMBER

T THERMOSTAT OR SPACE TEMP SENSOR

SD

SMOKE DAMPER

MCDTEE

PIPE TURNING UP

PIPE TURNING DOWNRSL

RLL

DIRECTION OF WATER FLOW

UNLESS OTHERWISE NOTED

MOISTURE CONDENSATE DRAIN

UON

1

AHU

PIPING LEGEND

DUCTWORK LEGEND

REFRIGERANT LIQUID LINES

REFRIGERANT SUCTION LINES

3

3 3 3

MECHANICAL

LEGEND &

SCHEDULES

M

0.01

WALL MOUNTED

WALL MOUNTED THERMOSTAT; CONDENSATE PUMP; LOW AMBIENT KIT.

INDOOR UNIT IS POWERED FROM CONDENSING UNIT.

PROVIDE 6" CONCRETE PAD FOR CONDENING UNIT (CU-X).

PROVIDE 5 YEAR WARRENTY ON COMPRESSOR.4

4 4 4 1

A

2

AC-5

MITSUBISHI

PKA-A24

IT ROOM

635

0.2

208/1/60

1/13

15

56W/75W

24

21

----

43/46

36x10x12

35

CU-5

31x12x24

170

PUY-A24

17.0

3 4

AC-2

MITSUBISHI

PKA-A24

OFFICE

635

0.2

208/1/60

1/13

15

56W/75W

24

21

26

43/46

36x10x12

35

CU-2

31x12x24

170

PUZ-A24

17.0