OUTSULATION® An Exterior Wall Insulation and Finish System
Outsulation System Installation Details
EPS INSULATION
The architecture, engineering and design of the project using the
08/0611DAW
DATE:REV:APPROVED BY:
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER® MESH PRIOR TO
STANDARD MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
does not violate Dryvit's warranty. This detail is subject to change
®
version.
without notice. Contact Dryvit to insure you have the most recent
1.
NOTE:
and Dryvit specifically disclaims any liability for the use of this
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
detail and for the architecture, design, engineering or workmanship of
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
Dryvit products is the responsibility of the project's design
DRYVIT FINISH
Outsulation System®Outsulation System
DRYVIT OUTSULATION SYSTEM
BY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
HIGH
IMPACT
DRYVIT BASE COAT
PANZER 15 OR 20 REINFORCING
MESH EMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
SUBSTRATE
DRYVIT FINISH
SUBSTRATE
DRYVIT ADHESIVE
DRYVIT OUTSULATION SYSTEM
BY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COATNORMAL
IMPACT
DRYVIT BASE COAT
EPS INSULATION
DRYVIT ADHESIVE
OS 0.0.01
version.
without notice. Contact Dryvit to insure you have the most recent
detail and for the architecture, design, engineering or workmanship of
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
any project. The project design professional determines, in its sole
1.professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
Dryvit products is the responsibility of the project's design
®Outsulation System Grade Level - Termination At Concrete Curb
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE TO RECEIVE SEALANT
19 MM (3/4") MIN.
WRAP DRYVIT DETAIL MESH® 51 MM (2")
MINIMUM AT UNDERSIDE OF EPS
DRYVIT FINISH
FRAMING
DRYVIT ADHESIVE
EPS INSULATION
SUBSTRATE
BY OTHERS DRYVIT OUTSULATION SYSTEM
OS 0.0.02
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER® MESH PRIOR TO
STANDARD MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
does not violate Dryvit's warranty. This detail is subject to change
®
NOTE:The architecture, engineering and design of the project using the
DAW
APPROVED BY:
10/0612
DATE:REV:
610 MM (2'-0") Max
(SEE NOTE 2)
NOTE:The architecture, engineering and design of the project using the
08/0611DAW
DATE:REV:APPROVED BY:
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
1.
STOP FINISH APPROXIMATELY 51 MM (2")
BELOW GRADE.does not violate Dryvit's warranty. This detail is subject to change
®
without notice. Contact Dryvit to insure you have the most recent
version.
EXPANSION JOINT IS REQUIRED ALONG TOP
OF FOUNDATION IF 610 MM (2'-0") DIMENSION
IS EXCEEDED. and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
3. SLOPE GRADE AWAY FROM WALL.
4.
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
2.
Outsulation System Foundation - Termination Above Grade®
203 MM (8") MIN. ABOVE
FINISHED GRADE OR AS
REQUIRED BY LOCAL CODE
DRYVIT DRYFLEX™ WATER
RESISTANT BASE COAT
AND DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WRAP DRYVIT DETAIL MESH®
51 MM (2") MINIMUM AT
UNDERSIDE OF EPS
DRYVIT COMPATIBLE
SEALANT WITH BOND
BREAKER, BY OTHERS
DRYVIT FINISH
DRYVIT ADHESIVE
EPS INSULATION
SUBSTRATE
FRAMING
BY OTHERS DRYVIT OUTSULATION SYSTEM
OS 0.0.03
NOTE:
Outsulation® SystemThe architecture, engineering and design of the project using the
05/063RS
APPROVED BY: REV: DATE:
does not violate Dryvit's warranty. This detail is subject to change
®
version.
without notice. Contact Dryvit to insure you have the most recent
DRYVIT AQUAFLASH SHALL EXTEND TO
INTERIOR FACE OF FRAMING.
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF
AQUAFLASH SYSTEM.REFER TO OS 0.0.05, 0.0.06 FOR
INTEGRATION OF SILL FLASHING.
2.
1. 3.
and Dryvit specifically disclaims any liability for the use of this
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
Dryvit products is the responsibility of the project's design
Rough Opening Preparation
STEP #3
APPLY DRYVIT AQUAFLASH
SYSTEM AT HEAD LAPPING
OVER JAMB APPLICATION
(SEE NOTE 3)
APPLY DRYVIT AQUAFLASH
SYSTEM AT JAMBS LAPPING
OVER SILL APPLICATION
(SEE NOTE 3)
APPLY DRYVIT AQUAFLASH® SYSTEM
AT SILL, EXTENDING UP JAMBS
MINIMUM 64 MM (2 12") AND INSTALL
CORNER SPLICES (SEE NOTE 3)
STEP #1 STEP #2
OS 0.0.04
Outsulation® System
APPROVED BY:
RS 05/064
DATE:REV:
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
DRYVIT FLASHING TAPE SURFACE CONDITIONER™
AND DRYVIT FLASHING TAPE™ MAY BE USED IN
LIEU OF AQUAFLASH SYSTEM.
3.
®
PAN FLASHING SHOULD OVERLAP EIFS MIN. 2 1/2"
MEASURED FROM THE TOP OF THE EPS
PAN FLASHING MUST HAVE WATERTIGHT SEAMS2.
NOTES
1.
INSTALL WINDOW UNIT AND ASSOCIATED
HEAD FLASHING. (SEE DETAIL 0.0.09)
INSTALL EIFS AND APPLY BACKER
ROD AND SEALANT ALONG JAMBS
AND AT SYSTEM TERMINATIONS,
ALSO ALONG EDGES OF FLASHING.
Preparation of Opening for Storefront Window
STEP 3: STEP 4:
64 MM
(2 12") MIN.
PREPARE OPENING AS PER OS 0.0.04. INSTALL
SILL PAN FLASHING AND SECURE TO FRAMING AND
BLOCKING. SHIM UNDERSIDE OF FLASHING TO
ENSURE INCIDENTAL MOISTURE IS DIRECTED TO
THE EXTERIOR FACE OF THE WALL.
(SEE NOTES 1,2 AND 3)
APPLY DRYVIT AQUAFLASH® SYSTEM
SPLICES OVER UPTURNED LEGS OF PAN
FLASHING (SEE NOTE 3)
STEP 1: STEP 2:
(SEE NOTES 1 AND 2)
51 MM (2") MIN.
OS 0.0.05
(SEE NOTES 1,2 AND 5)
51 MM (2") MIN.
APPLY DRYVIT AQUAFLASH®
SYSTEM AT SILL PER OS 0.0.04
AND SECURE FLASHING TO
FRAMING
(SEE NOTES 1,2,5 AND 7)
INSTALL SILL PAN FLASHING. SHIM
UNDERSIDE OF PAN FLASHING TO
ENSURE WATER RUN OFF
(SEE NOTE 2)
STEP 1: STEP 2:
64 MM
(2 12") MIN.
OS 0.0.06
DATE:APPROVED BY: REV:
RS 4 05/06
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
ADHESIVE ONLY APPLICATION IS
ACCEPTABLE WHEN USING THE
AQUAFLASH SYSTEM
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF
AQUAFLASH SYSTEM. ®
7.
APPLY DRYVIT AQUAFLASH SYSTEM AT
SILL. (SEE DETAIL OS 0.0.04)
6.
5.
INSTALL EIFS AND APPLY BACKER ROD AND
SEALANT ALONG JAMBS AND AT SYSTEM
TERMINATIONS, ALSO ALONG EDGES OF
FLASHING (SEE NOTES 3,4,5 AND 6)
APPLY DRYVIT AQUAFLASH SYSTEM
OVER METAL FLASHING TRANSITION
AND AT JAMBS LAPPING OVER
UPTURNED LEGS OF PAN FLASHING (SEE
NOTES 1,2,5 AND 7)
Preparation of Opening for Nail-On Window
INSTALL WINDOW UNIT AND
ASSOCIATED HEAD FLASHING.
STEP 4: STEP 5:
Outsulation® System
PAN FLASHING SHOULD OVERLAP EIFS MIN. 64
MM (2 1/2") MEASURED FROM THE TOP OF THE
EPS
PAN FLASHING MUST HAVE WATER
TIGHT SEAMS
STEP 3:
MECHANICAL FASTENERS SHOULD BE USED TO
ATTACH SILL TRIM PIECE
EIFS AT SILL SHALL BE SLOPED FOR DRAINAGE.
NOTES
4.
3.
2.
1.
DRYVIT ADHESIVE
NOTE:The architecture, engineering and design of the project using the
APPROVED BY: REV: DATE:
08/0614RS
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
does not violate Dryvit's warranty. This detail is subject to change
®
version.
without notice. Contact Dryvit to insure you have the most recent
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF
AQUAFLASH SYSTEM.
2.1.
detail and for the architecture, design, engineering or workmanship of
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
any project. The project design professional determines, in its sole
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
Dryvit products is the responsibility of the project's design
64MM
(2-1/2") MIN.
SILL PAN FLASHING
DETAIL
Outsulation System®
Termination at Sill
12.7MM (1/2")
DRYVIT OUTSULATION SYSTEMBY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
AIR SEAL PER WINDOW MANUFACTURES
REQUIREMENT, BY OTHERS
FRAMING
SUBSTRATE
DRYVIT-COMPATIBLE SEALANT
WITH BOND BREAKER, BY OTHERS
64MM (2 12") MIN.
WRAP DRYVIT DETAIL MESH® 51 MM (2")
MINIMUM AT UNDERSIDE OF EPS.
CONTINUOUS FLASHING, BY OTHERS.
TURN UP 12.7MM (12") MIN. AT JAMBS
(SEE INSET)
DRYVIT AQUAFLASH® SYSTEM
(SEE NOTE 2)
WINDOW SYSTEM
AND SHIMS
OS 0.0.07
DRYVIT ADHESIVE
DRYVIT OUTSULATION SYSTEM
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
DRYVIT AQUAFLASH® SYSTEM
(SEE NOTE 3)
NOTE:The architecture, engineering and design of the project using the
APPROVED BY: REV: DATE:
08/0613RS
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING TAPE™
MAY BE USED IN LIEU OF AQUAFLASH
SYSTEM.
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
does not violate Dryvit's warranty. This detail is subject to change
®
version.
without notice. Contact Dryvit to insure you have the most recent
SEALANT SHOULD NOT BE IN DIRECT
CONTACT WITH FLASHING TAPE ADHESIVE;
STAINING COULD OCCUR.detail and for the architecture, design, engineering or workmanship of
3.discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
any project. The project design professional determines, in its sole
1. 2.and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
DRYVIT DEMANDIT® OR
COLOR PRIME™ ON SURFACE
TO RECEIVE SEALANT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
Outsulation System®Termination at Jamb
DRYVIT-COMPATIBLE SEALANT
WITH CLOSED CELL BACKER ROD
BY OTHERS (SEE NOTE 2)
19 MM (3/4") MIN
EPS INSULATION
WINDOW SYSTEM
AND SHIMS
AIR SEAL PER WINDOW
MANUFACTURES
REQUIREMENT, BY OTHERS
SUBSTRATE
BY OTHERS
FRAMING
OS 0.0.08
NOTE:
APPROVED BY: REV: DATE:
14RS 08/06
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
1.
does not violate Dryvit's warranty. This detail is subject to change
®
without notice. Contact Dryvit to insure you have the most recent
version.
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF
AQUAFLASH SYSTEM.
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
2.
AIR SEAL PER WINDOW
MANUFACTURES
REQUIREMENT, BY OTHERS
Outsulation SystemThe architecture, engineering and design of the project using the
Termination at Head®
WINDOW SYSTEM
AND SHIMS
CONTINUOUS FLASHING AND
SEALANT (BY OTHERS)
19 MM (3/4") MIN.
SUBSTRATE
APPLY DRYVIT AQUAFLASH® SYSTEM
OVER LEG OF HEAD FLASHING
(SEE NOTE 2)
DRYVIT AQUAFLASH SYSTEM
(SEE NOTE 2)
DRYVIT DEMANDIT® OR COLOR PRIME™ ON
SURFACE TO RECEIVE SEALANT
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
DRYVIT ADHESIVE
OS 0.0.09
DRYVIT OUTSULATION SYSTEMBY OTHERS
FRAMING
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE TO RECEIVE SEALANT
DRYVIT AQUAFLASH SYSTEM
(SEE NOTE 2)
NOTE: Dryvit products is the responsibility of the project's design
DATE:APPROVED BY: REV:
12DAW 08/06
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
®
version.
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF
AQUAFLASH SYSTEM.
1.2.
detail and for the architecture, design, engineering or workmanship of
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
any project. The project design professional determines, in its sole
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
WINDOW SYSTEM
AND BLOCKING
AIR SEAL PER WINDOW
MANUFACTURES
REQUIREMENT, BY OTHERS
®Outsulation SystemThe architecture, engineering and design of the project using the
Termination at Head-Solid Substrate
CONTINUOUS FLASHING AND
SEALANT, BY OTHERS
19 MM (3/4") MIN.
SOLID SUBSTRATE
DRYVIT AQUAFLASH® SYSTEM
OVER LEG OF HEAD FLASHING
(SEE NOTE 2)
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
DRYVIT ADHESIVE
OS 0.0.10
DRYVIT OUTSULATION SYSTEMBY OTHERS
version.
detail and for the architecture, design, engineering or workmanship of
LOCATE INSULATION BOARDS SUCH THAT
BOARD EDGES DO NOT ALIGN WITH CORNERS
OF PENETRATION.
2.discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
any project. The project design professional determines, in its sole
1. standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
®Outsulation System EPS Preparation at Wall Penetrations
The architecture, engineering and design of the project using the
DRYVIT DETAIL MESH
241 MM (9 1/2") X 305 MM (12") (TYP.)
(SEE NOTE 2)
BACK WRAP INSULATION BOARD
WITH DRYVIT DETAIL MESH®
EPS INSULATION (SEE NOTE 1)
OS 0.0.11
Dryvit products is the responsibility of the project's designNOTES:
DATE:REV:APPROVED BY:
05/06DAW 11
without notice. Contact Dryvit to insure you have the most recent
APPLY A PIECE OF 241 MM (9 1/2") X 305 MM
(12") DETAIL REINFORCING MESH DIAGONALLY
AT EACH CORNER.
®
version.
EXPANSION JOINT IS INTENDED TO
ACCOMMODATE CROSS GRAIN SHRINKAGE
OF FLOOR BEAMS. detail and for the architecture, design, engineering or workmanship of
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
does not violate Dryvit's warranty. This detail is subject to change
3. LOCATE EXTERNAL SEALANT JOINT WITHIN
51 MM (2") BELOW BREAK IN SHEATHING.
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and2.1.
®Outsulation System Wood Framing - Expansion Joint At Floor Line
The architecture, engineering and design of the project using the
WOOD FRAMING
SUBSTRATE
DRYVIT ADHESIVE
SEE NOTE 3
DRYVIT COMPATIBLE SEALANT
WITH CLOSED CELL BACKER ROD,
BY OTHERS
DRYVIT DEMANDIT® OR
COLOR PRIME™ ON SURFACES
TO RECEIVE SEALANT
SLOPE BOTTOM SURFACE
1/5 MIN. OUTWARD TO DRAIN
19 MM (3/4") MIN.
DRYVIT FINISH
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
OS 0.0.12
DRYVIT OUTSULATION SYSTEMBY OTHERS
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE
OF EPS
NOTE: Dryvit products is the responsibility of the project's design
DATE:REV:APPROVED BY:
DAW 08/0611
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
®
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
SLIP TYPE
CONNECTION
19 MM (3/4") MIN.
NOTE: Dryvit products is the responsibility of the project's design
11DAW 08/06
LOCATE EXTERNAL SEALANT JOINT WITHIN
51 MM (2") BELOW BREAK IN SHEATHING.
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
REV:APPROVED BY:
®
DATE:
version.
EXPANSION JOINT IS INTENDED TO
ACCOMMODATE MOVEMENT AT SLIP
CONNECTION.
3.
2.1.
detail and for the architecture, design, engineering or workmanship of
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
®Outsulation SystemThe architecture, engineering and design of the project using the
Light Gauge Framing - Expansion Joint At Floor Line
SLOPE BOTTOM SURFACE 1/5 MIN.
OUTWARD TO DRAIN
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
DRYVIT FINISH
SEE NOTE 3
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
DRYVIT ADHESIVE
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
SUBSTRATE
OS 0.0.13
BY OTHERS DRYVIT OUTSULATION SYSTEM
OS 0.0.14
version.
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
1. standards. This detail is for general information and guidance only2.
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
DRYVIT OUTSULATION SYSTEMBY OTHERS
Termination at Parapet-Cap Flashing®Outsulation System
The architecture, engineering and design of the project using the
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
EPS INSULATION
PARAPET COPING ASSEMBLY,
BY OTHERS
DRYVIT COMPATIBLE SEALANT WITH
BOND BREAKER, BY OTHERS
WRAP DRYVIT REINFORCING MESH
AND BASE COAT OVER TOP OF FRAMING
(SEE NOTE 2)
FRAMING
ROOF
ASSEMBLY
SUBSTRATE
64 MM (2 1/2") MIN.
NOTE: Dryvit products is the responsibility of the project's design
08/0612DAW
detail and for the architecture, design, engineering or workmanship of
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
AS AN OPTION, DRYVIT AQUAFLASH®
SYSTEM OR DRYVIT FLASHING TAPE
SURFACE CONDITIONER™ AND DRYVIT
FLASHING TAPE™ MAY BE USED TO
PROVIDE ADDITIONAL PROTECTION AT THE
TOP OF A PARAPET WALL.
®
DATE:REV:APPROVED BY:
DRYVIT ADHESIVE
DRYVIT REINFORCING
MESH EMBEDDED IN
DRYVIT BASE COAT
203 MM (8") MIN.
NOTE:Dryvit products is the responsibility of the project's design
RS 08/0714
AS AN OPTION, DRYVIT AQUAFLASH®
SYSTEM OR DRYVIT FLASHING TAPE
SURFACE CONDITIONER™ AND DRYVIT
FLASHING TAPE™ MAY BE USED TO
PROVIDE ADDITIONAL PROTECTION AT THE
TOP OF A PARAPET WALL.
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
any project. The project design professional determines, in its sole
does not violate Dryvit's warranty. This detail is subject to change
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
detail and for the architecture, design, engineering or workmanship of
2.1.
®Outsulation System Termination at Parapet - Solid Substrate
The architecture, engineering and design of the project using the
DRYVIT OUTSULATION SYSTEMBY OTHERS
DRYVIT FINISH
PARAPET COPING ASSEMBLY,
BY OTHERS WRAP DRYVIT DETAIL
MESH 51 MM (2") MIN.
AT UNDERSIDE OF EPS
(SEE NOTE 2)
WRAP DRYVIT REINFORCING MESH
AND BASE COAT OVER TOP OF
FRAMING (SEE NOTE 2)
DRYVIT COMPATIBLE
SEALANT, BY OTHERS
DRYVIT COMPATIBLE
SEALANT WITH BOND
BREAKER, BY OTHERS
SOLID SUBSTRATE
ROOF FLASHING AND COUNTER
FLASHING BY OTHERS
ROOF ASSEMBLY
EPS INSULATION
DRYVIT ADHESIVE
64 MM (2 1/2") MIN.
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
OS 0.0.15
without notice. Contact Dryvit to insure you have the most recent
®
APPROVED BY: REV: DATE:
EDGE/REGLET DETAIL SHOWN
IN ENLARGED SECTION VIEW
ROOFING SYSTEM
NOTE: Dryvit products is the responsibility of the project's design
05/067RS
without notice. Contact Dryvit to insure you have the most recent
REV:APPROVED BY: DATE:
version.
2. FLASHINGS SHALL BE CONFIGURED AND
INSTALLED IN A WATER TIGHT FASHION
PRIOR TO OUTSULATION INSTALLATION
APPLY AQUAFLASH® SYSTEM OR FLASHING
TAPE™ AT WALL/SLEEVE TRANSITION.
1.
any project. The project design professional determines, in its sole
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
discretion, whether this detail or a functionally equivalent alternative
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
ROOF FLASHING AND COUNTER
FLASHING, BY OTHERS
DRYVIT COMPATIBLE SEALANT
W/CLOSED CELL BACKER ROD,
BY OTHERS
Outsulation® System Parapet/Wall Termination
The architecture, engineering and design of the project using the
DRYVIT FINISH
OUTSULATION SYSTEM
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
FLASHING SLEEVE SHOWN
IN EXPLODED VIEW
METAL COPING FLASHING
AT PARAPET WALL
DRYVIT OUTSULATION SYSTEM
ALUMINUM REGLET
OS 0.0.16
APPROVED BY: REV: DATE:
OS 0.0.17
The architecture, engineering and design of the project using the
Soffit With Fascia Extended Drip
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
does not violate Dryvit's warranty. This detail is subject to change
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
detail and for the architecture, design, engineering or workmanship of
without notice. Contact Dryvit to insure you have the most recent
NOTE:Dryvit products is the responsibility of the project's design
08/0612DAW
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS. ®
version.
1.and Dryvit specifically disclaims any liability for the use of this
25 MM (1") MAX.
®Outsulation System
DRYVIT ADHESIVE
DRYVIT REINFORCING
MESH EMBEDDED IN
DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
FRAMING
SUBSTRATE
BY OTHERS DRYVIT OUTSULATION SYSTEM
version.
any project. The project design professional determines, in its sole
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
1.
DRYVIT DETAIL
MESH® EMBEDDED
IN DRYVIT BASE COAT
OVERLAP 64 MM (2 1/2") MIN.
Soffit Router Cut Drip®Outsulation System
The architecture, engineering and design of the project using the
19 MM (3/4") MIN.
DRYVIT REINFORCING
MESH EMBEDDED IN
DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
DRYVIT ADHESIVE
SUBSTRATE
FRAMING
OS 0.0.18
DRYVIT OUTSULATION SYSTEMBY OTHERS
NOTE:Dryvit products is the responsibility of the project's design
08/0612DAW
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
®
APPROVED BY: DATE:REV:
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
NOTE:Dryvit products is the responsibility of the project's design
DATE:APPROVED BY: REV:
DAW 08/0612
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
®
version.
1.
detail and for the architecture, design, engineering or workmanship of
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
professional. All systems must comply with local building codes and
Outsulation System®Soffit With Expansion Joint
The architecture, engineering and design of the project using the
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
19 MM (3/4") MIN.
DRYVIT FINISH
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
SUBSTRATE
DRYVIT ADHESIVE
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
BY OTHERS DRYVIT OUTSULATION SYSTEM
OS 0.0.19
version.
3. REFER TO DRYVIT PUBLICATION DS 173, FOR
APPLICATION ON EXTERIOR SOFFITS.
1. SOFFITS WITHOUT EPS INSULATION REQUIRE
EXPANSION JOINTS EVERY 6.096 M (20 FT).
2.
Soffit - Uninsulated
The architecture, engineering and design of the project using the
Outsulation®System
DRYVIT FINISH
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
DRYVIT ADHESIVE
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
SUBSTRATE
OS 0.0.20
BY OTHERS DRYVIT OUTSULATION SYSTEM
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
detail and for the architecture, design, engineering or workmanship of
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS. ®
DATE:REV:APPROVED BY:
25 MM (1") MAX.
SUBSTRATE
DRYVIT COMPATIBLE SEALANT
WITH BOND BREAKER, BY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN BASE COAT
NOTE:Dryvit products is the responsibility of the project's design
08/0612DAW
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
any project. The project design professional determines, in its sole
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
®
DATE:REV:APPROVED BY:
203 MM (8") MIN.
SEE NOTES 2 AND 3
NOTE:
08/0612DAW
version.
3. DO NOT LAP REINFORCING MESH WITHIN
203 MM (8") OF A CORNER.
any project. The project design professional determines, in its sole
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
discretion, whether this detail or a functionally equivalent alternative
2. DOUBLE WRAP OUTSIDE CORNERS WITH
REINFORCING MESH OR USE CORNER MESH.1.
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Outside CornersROutsulation SystemDryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
203 MM (8") MIN.
SEE NOTES 2 AND 3
SUBSTRATE
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVE
EPS INSULATION
OS 0.0.21
DRYVIT OUTSULATION SYSTEMBY OTHERS
DRYVIT BASE COAT
NOTE:professional. All systems must comply with local building codes and
08/0612DAW
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
without notice. Contact Dryvit to insure you have the most recent
APPROVED BY:
®
REV: DATE:
version.
1.
any project. The project design professional determines, in its sole
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
discretion, whether this detail or a functionally equivalent alternative
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
203 MM (8") MIN.
Outsulation System® Outside Corner - High Impact
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DRYVIT FINISH
PANZER® 15 OR 20
REINFORCING MESH
DRYVIT STANDARD OR STANDARD
PLUS REINFORCING MESH OVERLAP
MIN. 203 MM (8") AT CORNER
DRYVIT CORNER MESH
DRYVIT ADHESIVE
EPS INSULATION
DRYVIT BASE COAT
SUBSTRATE
OS 0.0.22
DRYVIT OUTSULATION SYSTEM
BY OTHERS
OPTIONAL SECONDARY
SEAL, BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
WRAP DRYVIT DETAIL
MESH® 51 MM (2") MIN.
AT UNDERSIDE OF EPS
(SEE NOTE 2)
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
19 MM (3/4") MIN.
NOTE:professional. All systems must comply with local building codes and
detail and for the architecture, design, engineering or workmanship of
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
08/0613DAW
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
®
DATE:APPROVED BY: REV:
AS AN OPTION, THE REINFORCED
BASE COAT EDGE WRAP MAY BE
EXTENDED ONTO THE CONCRETE
EDGE AND/OR FRAMING.
1. 2.
Structural Expansion Joint
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
®Outsulation System
EPS INSULATION
DRYVIT ADHESIVE
FRAMING
SUBSTRATE
DRYVIT
OUTSULATION
SYSTEM
DRYVIT FINISH
BY OTHERS
SOLID SUBSTRATE
OS 0.0.23
any project. The project design professional determines, in its sole
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
discretion, whether this detail or a functionally equivalent alternative
1.and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
®Outsulation System Outsulation Expansion Joint - Dissimilar Substrates
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
DRYVIT COMPATIBLE SEALANT WITH
CLOSED-CELL BACKER ROD, BY OTHERS
19 MM (3/4") MIN.
DRYVIT FINISH
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
SUBSTRATE
BY OTHERS
FRAMINGSOLID SUBSTRATE
OS 0.0.24
DRYVIT ADHESIVE
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COATWRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
EPS INSULATION
DRYVIT
OUTSULATION
SYSTEM
NOTE:professional. All systems must comply with local building codes and
08/0612DAW
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
®
APPROVED BY: REV: DATE:
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
DRYVIT ADHESIVE
NOTE: professional. All systems must comply with local building codes and
08/0614RS
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
APPROVED BY:
®
REV: DATE:
2. AS AN OPTION, THE REINFORCED BASE
COAT EDGE WRAP MAY BE EXTENDED ONTO
THE FRAMING.
1.
any project. The project design professional determines, in its sole
is best suited for the project. Use of a functionally equivalent detail
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
discretion, whether this detail or a functionally equivalent alternative
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
Outsulation System®Structural Expansion Joint - Inside Corner
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
FRAMING
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
(SEE NOTE 2)
19 MM (3/4") MIN.
OPTIONAL SECONDARY
SEAL, BY OTHERS
DRYVIT-COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
DRYVIT ADHESIVE
SUBSTRATE
OS 0.0.25
DRYVIT OUTSULATION SYSTEM BY OTHERS
REV:APPROVED BY: DATE:
1. 2. AS AN OPTION, THE REINFORCED BASE
COAT EDGE WRAP MAY BE EXTENDED
ONTO THE FRAMING.
NOTE: professional. All systems must comply with local building codes and
08/0613RS
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
detail and for the architecture, design, engineering or workmanship of
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
®
The architecture, engineering and design of the project using the
Structural Expansion Joint - Outside Corner
Dryvit products is the responsibility of the project's design
Outsulation System®
DRYVIT OUTSULATION SYSTEMBY OTHERS
DRYVIT REINFORCING MESH
EMBEDDED IN BASE COAT
EPS INSULATION
DRYVIT FINISH
DRYVIT ADHESIVE
OPTIONAL SECONDARY
SEAL, BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
(SEE NOTE 2)
19 MM (3/4") MIN.
DRYVIT COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
SUBSTRATE
OS 0.0.26
AS AN OPTION, THE REINFORCED BASE
COAT EDGE WRAP MAY BE EXTENDED ONTO
THE FRAMING. any project. The project design professional determines, in its sole
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
1. 2.and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
PenetrationsOutsulation SystemThe architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
®
DRYVIT FINISH
DRYVIT ADHESIVE
DRYVIT DEMANDIT OR COLOR PRIME
ON SURFACES TO RECEIVE SEALANT
SUBSTRATE
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT UNDERSIDE OF EPS
(SEE NOTE 2)
OPTIONAL SECONDARY SEAL,
BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
DRYVIT-COMPATIBLE SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
19 MM (3/4") MIN.
OS 0.0.27
DRYVIT OUTSULATION SYSTEMBY OTHERS
OPTIONAL SECONDARY SEAL
19 MM (3/4") MIN.
NOTE: professional. All systems must comply with local building codes and
08/0612DAW
DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
®
DATE:REV:APPROVED BY:
discretion, whether this detail or a functionally equivalent alternative
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
is best suited for the project. Use of a functionally equivalent detail
and Dryvit specifically disclaims any liability for the use of this
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
Outsulation System®Sign Attachment
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
12.7 MM (12") MIN.
DRYVIT REINFORCING
MESH EMBEDDED IN
DRYVIT BASE COAT
DRYVIT FINISH
SIGN FIXTURE
FRAMING
PIPE SLEEVE SET IN SEALANT
SCREW OR BOLT ATTACHMENT
TO BUILDING FRAMING OR
STRUCTURAL SUBSTRATE
BEARING WASHER
professional. All systems must comply with local building codes andPERIMETER OF PIPE SLEEVE IS CAULKED TO
PREVENT WATER ENTRY INTO WALL.
NOTE:
1.
05/0612DAW
version.
APPROVED BY:
®
DATE:REV:
DRYVIT-COMPATIBLE
SEALANT AND BOND
BREAKER TAPE, BY OTHERS
EPS INSULATION
BLOCKING OR STRUCTURAL
SUBSTRATE AS REQUIRED
DRYVIT ADHESIVE
SUBSTRATE
OS 0.0.28
DRYVIT
OUTSULATION
SYSTEMBY OTHERS
BY OTHERS
OS 0.0.29
1.4 KG/M² (2.5 LBS/YD²) OR 1.8 KG/M²
(3.4 LBS/YD²) GALVANIZED EXPANDED
METAL LATH (BY OTHERS)
ATTACH METAL LATH TO STRUCTURAL
FRAMING USING APPROPRIATE
FASTENERS (BY OTHERS)
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVE (KEYED INTO LATH)
SUBSTRATE
EPS INSULATION
BY OTHERS DRYVIT OUTSULATION SYSTEM
DRYVIT FINISH
METAL OR
WOOD STUDS
DRYVIT ADHESIVE (KEYED INTO LATH)
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
1.4 KG/M² (2.5 LBS/YD²) OR 1.8 KG/M²
(3.4 LBS/YD²) GALVANIZED EXPANDED
METAL LATH (BY OTHERS)
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
The architecture, engineering and design of the project using the
Outsulation Applied Over Metal Lath
1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
version.
DATE:REV:APPROVED BY:
12DAW 08/06
DRYVIT FINISH
Outsulation System
NOTE:
®
BRICK, MASONRY
OR CONCRETE
CONSTRUCTION
EPS INSULATION
®
ATTACH METAL LATH TO SUBSTRATE
USING APPROPRIATE FASTENERS OR
ANCHORS (BY OTHERS)
12
2. SLOPE BOTTOM EDGE OF REVEAL FOR
POSITIVE DRAINAGE.
1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD
MESH™ OR STANDARD PLUS MESH™.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
professional. All systems must comply with local building codes and
DAW
version.
®
DATE:REV:APPROVED BY:
08/06
discretion, whether this detail or a functionally equivalent alternative
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
is best suited for the project. Use of a functionally equivalent detail
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
Aesthetic RevealsOutsulation System
NOTE:
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
®
DRYVIT DETAIL MESH®
EMBEDDED IN DRYVIT BASE COAT
19 MM (3/4") MIN.
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT OUTSULATION SYSTEMBY OTHERS
DRYVIT FINISH
FRAMING MEMBER
DRYVIT ADHESIVE
SUBSTRATE
OVERLAP 64 MM (2 1/2")
OS 0.0.30
BY OTHERS
1. MAXIMUM THICKNESS OF EPS BUILT OUT
SHAPES SHALL NOT EXCEED 305 MM (12
INCHES) AT ANY POINT MEASURED FROM THE
SUBSTRATE
version.
PERCENTAGE OF WALL AREA COVERED BY
EPS FOAM SHAPES IN EXCESS OF 102 MM (4
IN.) IN THICKNESS SHALL NOT EXCEED 15%
®
REV: DATE:APPROVED BY:
05/0612DAW
2.discretion, whether this detail or a functionally equivalent alternative
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
is best suited for the project. Use of a functionally equivalent detail
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
EPS INSULATION
DRYVIT FINISH
DRYVIT ADHESIVE
OVERLAP 64 MM (2 1/2")
Outsulation SystemNOTE:
® Projecting Graphics
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
DRYVIT REINFORCING MESH
LAPPED 64 MM (2 1/2") MIN.
SUBSTRATE
DRYVIT
OUTSULATION
SYSTEM
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
EPS INSULATION
DRYVIT ADHESIVE
SUBSTRATE
OS 0.0.31
SUBSTRATE
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
Recessed Graphics
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DRYVIT REINFORCING MESH
LAPPED 64 MM (2 1/2") MIN.
Outsulation SystemNOTES:
®
DRYVIT ADHESIVEEPS INSULATION
BY OTHERS
DRYVIT
OUTSULATION
SYSTEM
OVERLAP 64 MM (2 1/2") MIN.
19 MM (3/4") MIN.
DRYVIT FINISH
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
EPS INSULATION
DRYVIT ADHESIVE
SUBSTRATE
OS 0.0.32
standards. This detail is for general information and guidance only1. SLOPE BOTTOM EDGE OF HORIZONTAL
RECESSES FOR POSITIVE DRAINAGE
detail and for the architecture, design, engineering or workmanship of
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
any project. The project design professional determines, in its sole
and Dryvit specifically disclaims any liability for the use of this
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
version.
DATE:REV:APPROVED BY:
11DAW 05/06
®
FLASHING NO. 1, BY OTHERS,
EXTEND UP BEHIND FLASHING
NO. 2 76 MM (3") MIN.
REFER TO OS 0.0.34 FOR DECK
CUTAWAY DETAIL.
THESE DETAILS DO NOT APPLY TO
CANTILEVERED DECKS. CANTILEVERED DECKS
REQUIRE JOB SPECIFIC FLASHING DETAILS.
professional. All systems must comply with local building codes and
version.
DATE:APPROVED BY: REV:
05/066DAW
®
2. WHEN FLASHING NUMBER 1 IS IN PLACE, EPS
WILL NEED TO BE PRE WRAPPED WITH BASE
COAT AND MESH.
of any project. The project design professional determines, in its sole
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
discretion, whether this detail or a functionally equivalent alternative
and Dryvit specifically disclaims any liability for the use of
this detail and for the architecture, design, engineering or workmanship
standards. This detail is for general information and guidance only
WRAP DRYVIT DETAIL MESH® 51 MM
(2") MIN. AT BACKSIDE OF EPS BOARD
SUBSTRATE
Outsulation® SystemNOTE:
1. 3.The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
Termination at Deck - Section
64 MM (2-1/2") MIN.
DRYVIT COMPATIBLE SEALANT
WITH BOND BREAKER, BY OTHERS
25 MM (1") MIN.
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
FLASHING NO. 3, BY OTHERS, EXTEND UP
BEHIND EPS INSULATION 76 MM (3")
WOOD SUPPORT STRIP
WOOD DECK FRAMING
FLASHING NO. 2, BY OTHERS, EXTEND UP
BEHIND FLASHING NO. 3 76 MM (3") MIN.
51 MM (2") MIN.
WOOD DECK BOARDS
DRYVIT FINISH
OS 0.0.33
DRYVIT ADHESIVE
EPS INSULATION
DECK BOARD
professional. All systems must comply with local building codes and
THESE DETAILS DO NOT APPLY TO
CANTILEVERED DECKS. CANTILEVERED
DECKS REQUIRE JOB SPECIFIC FLASHING
DETAILS.
version.
DATE:REV:APPROVED BY:
05/066DAW
®
51 MM
(2") MIN.
DRYVIT COMPATIBLE
SEALANT WITH BOND
BREAKER, BY OTHERS
OS 0.0.34
REFER TO OS 0.0.33 FOR DECK SECTION DETAIL.2.of any project. The project design professional determines, in its sole
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
and Dryvit specifically disclaims any liability for the use of
this detail and for the architecture, design, engineering or workmanship
standards. This detail is for general information and guidance only
Outsulation® SystemNOTES:
1.The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
Termination at Deck - Cut Away
END JOIST
FLASHING NO. 2,
BY OTHERS
FLASHING NO. 1,
BY OTHERS 51 MM (2") MIN.
FLASHING NO. 3, BY
OTHERS TURNED DOWN
OVER END JOIST
METAL FLASHINGS ARE 254 MM (10") X 51 MM
(2") LONGER THAN THE EXPOSED PORTION OF
THE ROOFING SHINGLE AND ARE BENT IN HALF
TO ALLOW FOR TWO 127 MM (5") LEGS.
ALTHOUGH NOT SHOWN, METAL FLASHINGS ARE
STEP FLASHED (INTERWOVEN) WITH ROOFING
SHINGLES.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
EXTEND DIVERTER FLASHING
(KICKOUT) A MINIMUM OF 25 MM
(1") BEYOND FACE OF SYSTEM.
3. EXTEND ROOFING UNDERLAYMENT
127 MM (5") UP VERTICAL WALL
BEHIND METAL FLASHING.
DAW 05/063
APPROVED BY: REV: DATE:
2. ROOF DIVERTER TO BE MADE FROM
CORROSION RESISTANT MATERIAL MIN.
24 GAGE WITH WATER TIGHT SEAMS.
®
ROOF DIVERTER FLASHING,
BY OTHERS (SEE NOTE 2)
ROOF STEP FLASHING,
BY OTHERS
ROOFING UNDERLAYMENT,
BY OTHERS (SEE NOTE 3)
Termination at Sloped Roof
GUTTER SYSTEM SLOPED
AWAY FROM WALL
(6")
Outsulation® SystemNOTE:
4.1.
(12")305 MM
152 MM
152 MM(6")
110
ROOF DIVERTER
(NOTE 2)
100
DRYVIT FINISH
ROOFING SHINGLES
51 MM (2") MIN.
EPS INSULATION
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
SUBSTRATE
FRAMING
OS 0.0.35
standards. This detail is for general information and guidance only
05/06
DATE:
1DAW
APPROVED BY: REV:
®
is best suited for the project. Use of a functionally equivalent detail
without notice. Contact Dryvit to insure you have the most recent
version.
does not violate Dryvit's warranty. This detail is subject to change
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
and Dryvit specifically disclaims any liability for the use of this
DRYVIT COMPATIBLE
SEALANT, BY OTHERS
Outsulation SystemDryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
The architecture, engineering and design of the project using the
®Termination at Roof Stop Flashing
ROOF SHINGLES
GLUED TO FLASHING
51 MM (2") MIN.
102 MM (4") MIN.
SHINGLES
ROOF STOP FLASHING,
BY OTHERS
ROOF/WALL FLASHING,
BY OTHERS
FASCIA BOARD
OS 0.0.36
WATER-RESISTIVE BARRIER
EXTENDED BEHIND FLASHING,
BY OTHERS
professional. All systems must comply with local building codes and
RS 0 05/08
version.
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
APPROVED BY: REV: DATE:
1.
discretion, whether this detail or a functionally equivalent alternative
DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED LIEU OF DRYVIT
AQUAFLASH SYSTEM.is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
any project. The project design professional determines, in its sole
standards. This detail is for general information and guidance only2.
NOTE:
Horizontal Joint At Stone Veneer
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
STONE VENEER SYSTEM, BY OTHERS
APPROVED SUBSTRATE
EPS INSULATION BOARD NOTCHED TO
ACCOMMODATE FLASHING
DRYVIT ADHESIVE
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
CONTINUOUS FLASHING, BY OTHERS
SEALANT WITH BOND
BREAKER, BY OTHERS
DRYVIT COMPATIBLE SEALANT WITH CLOSED
CELL BACKER ROD, BY OTHERS
19 MM (3/4") MIN.
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN BASE COAT
WRAP DRYVIT DETAIL MESH®
51 MM (2") MIN. AT BACKSIDE OF EPS
DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 2)
DRYVIT OUTSULATION SYSTEMBY OTHERS
OS 0.0.37
Outsulation® System