Adding Valueby
Establishing andMaintaining a
Continuous SteamTrap
Management Program
1
![Page 2: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/2.jpg)
Value ofContinuous Steam TrapManagement Program
•Energy Savings
•Improved Productivity andProduct Quality
•Lowered Maintenance Costs
2
![Page 3: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/3.jpg)
Energy Savings•Systems that have not beenmaintained and evaluated in 3-5 years produce 15-30% trapfailure
•Most traps fail open, whichcauses escape of live steam tothe condensate system and inmost cases to the atmosphere,resulting in significant steamloss
3
![Page 4: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/4.jpg)
Possible Steam Loss through25% Failed Traps
@ $12 per 1000# steam
# of Traps inSystem
# of FailedTraps
Calculatedw/ 1/8”Orifice
$ LossPer Hour
Annually@ 2080 hours
100 traps 25 1895 #phrloss $22.74 $47,299
150 traps 37 2804 #phrloss $33.65 $69,992
300 traps 75 5685 #phrloss $68.22 $141,897
4
![Page 5: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/5.jpg)
Production and ProductQuality Improvement
•What is the value ofcontrolling condensate systemsto improve productivity?
•Can we improve product qualityby managing condensate andsteam systems?
5
![Page 6: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/6.jpg)
6
![Page 7: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/7.jpg)
May May MayBeforeEvaluation
AfterEvaluation
7
![Page 8: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/8.jpg)
Starting Temp = 98.6°Ending Temp = 186.5°Temp Rise = 87.9°
Minutes to Set Point = 8 minutes
Rate of rise = 10.99° per min
Starting Temp = 111.3°Ending Temp = 199.1°Temp Rise = 87.75°
Minutes to Set Point = 14 minutes
Rate of rise = 6.26° per min
Objectives of #6 (before) and #9 (after) wereto ramp to set point as quickly as possible
May MayBeforeEvaluation
AfterEvaluation
8
![Page 9: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/9.jpg)
Starting Temp= 134.6°Ending Temp = 151.1°Temp Rise = 16.5°
Rate of rise = 2.08° per min
Starting Temp= 122.3°Ending Temp = 139.9°Temp Rise = 17.7°
Rate of rise = 1.6° per min
Objectives of #1 (before) & #4 (after) were tocontrol a ramp of 2° per minute to the set point
May MayBeforeEvaluation
AfterEvaluation
°
9
![Page 10: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/10.jpg)
Elements ofContinuous Steam TrapManagement Program
•Knowledge of Basic SteamPrinciples
•Knowledge of the BasicSteam System Conditions
•Tracking and ReportingEvaluations
10
![Page 11: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/11.jpg)
Elements ofContinuous Steam TrapManagement Program
•Understanding SteamPrinciples
•Understanding the SteamSystem
•Tracking and ReportingEvaluations
11
![Page 12: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/12.jpg)
Commitment to a Continuous Education ofSteam Principles and Application of Steam
Products• Training
• Department of Energy
• www.energy.gov
• UE Systems
• http://www.uesystems.com/
• Armstrong International
• www.armstronginternational.com/armstrong-university
• Spirax Sarco
• www.spiraxsarco.com/resources/steam-engineering-tutorials.asp
• Watson McDaniel
• www.watsonmcdaniel.com
• Available literature and website sizing
12
![Page 13: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/13.jpg)
Steam TablesThis table states the heat values and the
pressure/temperature relationships of saturatedsteam. It contains valuable information forcalculating steam and condensate loads, steamand condensate pipe sizing, and determiningflash rates in steam/condensate applications.
This table discloses thePressure/Temperature Relationships.
At a stated pressure, the related temperature is shown. Insaturated steam, pressure and temperature arecorresponding values.
Example:
From Column 1: From Column 3:100.3 psig (gauge pressure) = 338° F (related temperature)
Pressure TemperatureRelationship
Amount of BTU per #of Steam @ this
pressure
Volume of Steam@ each Pressure
13
![Page 14: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/14.jpg)
Flash Steam
What is flash steam?When pressurized hot condensate or boilerwater is released to a lower pressure, part of itis re-evaporated, becoming what is known asflash steam.
How does it affect my trap performance?The percentage of flash that occurs is basedon the upstream pressure before the steamtrap and the downstream pressure on thedischarge side of the trap.Flash steam can cause back pressure thataffects the performance of a steam trap andcan affect how we determine the operationalstatus of a trap.
Percentage Flash SteamSteam
PressurePSIG
Flash Tank Pressure
0 2 5 10 15 20 50 75 100
5 1.7 0.9 0.0
10 2.9 2.2 1.3 0.0
15 4.0 3.2 2.4 1.1 0.0
20 4.9 4.2 3.3 2.0 1.0 0.0
30 6.5 5.8 4.9 3.7 2.6 1.6
40 7.9 7.1 6.3 5.0 4.0 3.0
50 9.0 8.3 7.4 6.2 5.1 4.2 0.0
75 11.4 10.7 9.8 8.6 7.6 6.7 2.5 0.0
100 13.3 12.6 11.8 10.6 9.6 8.7 4.6 2.1 0.0
125 14.9 14.2 13.4 12.2 11.2 10.3 6.3 3.8 1.8
150 16.3 15.6 14.8 13.7 12.7 11.8 7.8 5.4 3.3
210 19.2 18.5 17.7 16.6 15.6 14.7 10.8 8.5 6.5
335 23.7 23.0 22.3 21.2 20.2 19.4 15.6 13.3 11.5
14
![Page 15: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/15.jpg)
Percentage Flash SteamSteam
PressurePSIG
Flash Tank Pressure
0 2 5 10 15 20 50 75 100
5 1.7 0.9 0.0
10 2.9 2.2 1.3 0.0
15 4.0 3.2 2.4 1.1 0.0
20 4.9 4.2 3.3 2.0 1.0 0.0
30 6.5 5.8 4.9 3.7 2.6 1.6
40 7.9 7.1 6.3 5.0 4.0 3.0
50 9.0 8.3 7.4 6.2 5.1 4.2 0.0
75 11.4 10.7 9.8 8.6 7.6 6.7 2.5 0.0
100 13.3 12.6 11.8 10.6 9.6 8.7 4.6 2.1 0.0
125 14.9 14.2 13.4 12.2 11.2 10.3 6.3 3.8 1.8
150 16.3 15.6 14.8 13.7 12.7 11.8 7.8 5.4 3.3
210 19.2 18.5 17.7 16.6 15.6 14.7 10.8 8.5 6.5
335 23.7 23.0 22.3 21.2 20.2 19.4 15.6 13.3 11.5
Calculating Flash Steam Rate
% Flash Steam = SH-SL x 100H
SH = Sensible heat in the condensateat the higher pressure before inletof trapSL = Sensible heat in the condensateat the lower pressure below outletof trapH = Latent heat in the steam at thelower pressure to which thecondensate is being discharged
Example:
125.3 psig upstream, dischargingto0 psig downstream condensate line
From the steam table:
324.74-180. X100= 14.9% Flash970.2
15
![Page 16: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/16.jpg)
Elements ofContinuous Steam TrapManagement Program
•Understanding SteamPrinciples
•Understanding the SteamSystem
•Tracking and ReportingEvaluations
16
![Page 17: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/17.jpg)
Things are not always asthey appear!
17
![Page 18: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/18.jpg)
How much steam pressuredo you have?
Things are not always asthey appear!
18
![Page 19: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/19.jpg)
This plant stated thatthey had 90 to 100 psig
steam pressure atall times.
Looks likemin pressure
approx. 64.5 psig
Steam PressureSupply Line
May 12th
Looks likemax pressure
approx. 87 psig
BeforeEvaluation
19
PRESSURE
![Page 20: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/20.jpg)
Things are not always asthey appear!
Stall in a heat exchanger,causing trap to appear
failed closed
Does it affectproductivity and quality?
20
![Page 21: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/21.jpg)
T2
T1
Liquid IN
Liquid OUT
Steam In
Steam Trap
Recirculatingwater through
the heatexchanger
Controlvalve
responding tohigh set point
Condensatereturn lifting
about 15’
21
![Page 22: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/22.jpg)
Unstableheat transfer
acrossheat exchanger
TEMPERATURE
BeforeEvaluation
22
![Page 23: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/23.jpg)
Unstableheat transfer
acrossheat exchanger
May 12thRATE OF RISEBefore
Evaluation
23
TEMPERATURE
![Page 24: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/24.jpg)
May 18thMEDIA TEMPERATURES
AfterEvaluation
24
TEMPERATURE
![Page 25: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/25.jpg)
May 18thMEDIA TEMPERATURES After
Evaluation
25
TEMPERATURE
![Page 26: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/26.jpg)
P3P2CVP4
PRESSURE
May 12thMay 12th
BeforeEvaluation
26
![Page 27: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/27.jpg)
T2
T1
Liquid IN
Liquid OUT
Steam In
Steam Trap
Recirculatingwater through
the heatexchanger
Controlvalve
responding tohigh set point
Condensatereturn lifting
about 15’
27
![Page 28: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/28.jpg)
May 18thCONDITION INHEAT EXCHANGER
AfterEvaluation
28
PRESSURE
![Page 29: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/29.jpg)
May 18thMEDIA TEMPERATURES
AfterEvaluation
29
TEMPERATURE
![Page 30: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/30.jpg)
ControlValve
100% Open
Back pressurein excess of 25 psig
30
![Page 31: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/31.jpg)
Preheat Coil Trap-control valve 100% open
-high load
Trap discharge lineinto condensatecollection line
263° F approximately22.55 psig back pressure inreturn line downstream of
steam trap
31
![Page 32: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/32.jpg)
Steam TablesThis table states the heat values and the
pressure/temperature relationships of saturatedsteam. It contains valuable information forcalculating steam and condensate loads, steamand condensate pipe sizing, and determiningflash rates in steam/condensate applications.
This table discloses thePressure/Temperature Relationships.
At a stated pressure, the related temperature is shown. Insaturated steam, pressure and temperature are correspondingvalues.
Example:
From Column 3: From Column 1:263° F (related temperature) = 22.55 psig (gauge pressure)
Back Pressure in return condensate line
32
![Page 33: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/33.jpg)
260° F approximately20.72 psig pressure in
the steam trap
Inside of Trap
Preheat Coil Trap-control valve 100% open
-high load
33
![Page 34: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/34.jpg)
Trap Inlet233° F approximately
7.27 psig pressure at inletto the steam trap
Preheat Coil Trap-control valve 100% open
-high load
34
![Page 35: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/35.jpg)
Trap Outlet
260° F approximately20.72 psig back pressure
discharge outlet of thesteam trap
22.55 psig back pressure in return line20.72 psig pressure at discharge of trap20.72 psig pressure inside of trap
7.27 psig at inlet of trap
Trap cannot operate properly because of system conditions!
Preheat Coil Trap-control valve 100% open
-high load
35
![Page 36: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/36.jpg)
36
![Page 37: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/37.jpg)
Steam Table
Example:
15.3 inches of Vacuum = 180° F (relatedtemperature)
This table discloses thePressure/Temperature Relationships
Here in Inches of Vacuum
Heating airtemperatures to 180°F
Things are not always as they appear!
37
![Page 38: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/38.jpg)
Heating Airwith Steam
Incoming AirTemperature = 95.3°
F
38
![Page 39: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/39.jpg)
Heating Airwith Steam
Discharge AirTemperature =
147°F
39
![Page 40: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/40.jpg)
Heating Airwith Steam
Steam pressurebefore control
valve
Approximately 65psig
40
![Page 41: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/41.jpg)
Heating Airwith Steam
Steam Pressureafter
Control Valve
Approximately 40psig
With a 25 psig dropacross this valve, youwould be discharging
approximately2500 #phr of steam
41
![Page 42: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/42.jpg)
Steam Trap
From the steam tables217 deg f =
Approximately 1.5 psiBack Pressure
Heating Airwith Steam
Condensate LinePressure after
Steam Trap
Approximately 1.5psig
With a 1.5 pressuredifferential across this
trap,you would bedischarging
approximately 2500 #phrof condensate
42
![Page 43: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/43.jpg)
Inlet piping tosteam trap
From the steam tables206°F =
Approximately -1.6 psigor 3.0 inches Hg
Heating Airwith Steam
Condensate LinePressure Before
Steam Trap
Approximately 3.0inches Hg or
Vacuum
This means that theheat exchanger on the
steam side is in avacuum, trying todischarge into a
condensate line that is1.5 psig back
pressure.
43
![Page 44: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/44.jpg)
HotWater
HotWater
Heating Airwith Steam
(actually hot water)
258°F = 19.55 psig183°F = Hot Water176°F = Hot Water
44
![Page 45: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/45.jpg)
AfterSteam Trap
BeforeSteam Trap
Heating Airwith Steam
Condensate LinePressure Before
Steam Trap
Approximately 1.5psig
Was the trap blowing orwas it constantly
discharging condensateas it should?
45
![Page 46: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/46.jpg)
Elements ofContinuous Steam TrapManagement Program
•Understanding SteamPrinciples•Understanding the SteamSystem•Tracking and ReportingEvaluations
46
![Page 47: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/47.jpg)
Example ofComprehensive Report
47
![Page 48: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/48.jpg)
This analysis reveals a reduction in failedtraps to below 10% on average, and clearlydemonstrates the importance of intermediate
evaluation to the process application.
48
![Page 49: PC Steam Trap Management Presentation - UE Systems trap management program.pdf · Value of Continuous Steam Trap Management Program • Energy Savings • Improved Productivity and](https://reader033.vdocument.in/reader033/viewer/2022052709/5a84d3577f8b9a14748ba725/html5/thumbnails/49.jpg)
Web-basedSteam TrapEvaluationDatabase
49