Download - WattMaster VAV Component & System Wiring - … VAV Component & System Wiring - Technical Guide
WattMaster VAV
Component & System
Wiring - Technical Guide
www.wattmaster.com
Table Of Contents
System Configurations Installation & Commissioning .................................................................................. 5Networked Single Loop System ........................................................................................................................................................................... 6Networked Single Loop - Computer Connection With Remote Link .................................................................................................................... 7Networked Single Loop - Computer Connection With IP-Link ............................................................................................................................. 8Networked Multiple Loop System ......................................................................................................................................................................... 9Networked Multiple Loop - Computer Connection With Remote Link ................................................................................................................ 10Networked Multiple Loop - Computer Connection With IP-Link ......................................................................................................................... 11Systems Overview .............................................................................................................................................................................................. 12General Information ............................................................................................................................................................................................ 12Installation Procedures ....................................................................................................................................................................................... 12System Commisioning ........................................................................................................................................................................................ 15Transformer & Wire Sizing ................................................................................................................................................................................. 16
WMVAV Controller Wiring .............................................................................................................................. 17WMVAV Controller Wiring .................................................................................................................................................................................. 18WMVAV Controller Addressing ........................................................................................................................................................................... 19Space Sensor Wiring .......................................................................................................................................................................................... 20Supply & Return Sensor Wiring .......................................................................................................................................................................... 21Outside Air Sensor Wiring .................................................................................................................................................................................. 22Remote Occupied Contact To WMVAV Wiring ................................................................................................................................................... 23Humidity Sensor Wiring ...................................................................................................................................................................................... 24Supply Fan VFD Wiring ...................................................................................................................................................................................... 25Bypass Damper Actuator Wiring ........................................................................................................................................................................ 262 Slot Expansion Base Board Wiring ................................................................................................................................................................. 274 Slot Expansion Base Board Wiring ................................................................................................................................................................. 284 Analog Input 1 Analog Output Expansion Board Wiring .................................................................................................................................. 294 Analog Input 1 Analog Output Expansion Board Wiring (Cont’d) .................................................................................................................... 304 Analog Input 1 Analog Output Expansion Board Wiring (Cont’d) .................................................................................................................... 314 Binary Input Expansion Board Wiring .............................................................................................................................................................. 324 Relay Output Expansion Board Wiring ............................................................................................................................................................ 33
VAVBOX Controller Diagrams ....................................................................................................................... 35VAVBOX Controller Wiring ................................................................................................................................................................................. 363 Relay Output Expansion Board Wiring ............................................................................................................................................................ 373 Relay Output Expansion Board Wiring (Cont’d) .............................................................................................................................................. 383 Relay Output Expansion Board Wiring (Cont’d) .............................................................................................................................................. 39
Communication Devices Diagrams ............................................................................................................... 41System Manager Modular Cable Pigtail - Wiring Schematic ............................................................................................................................. 42System Manager Modular Cable Pigtail - Wiring Detail ..................................................................................................................................... 43Modular Service Tool Connections ..................................................................................................................................................................... 44CommLink II Wiring & Cabling Connections ...................................................................................................................................................... 45MiniLink Polling Device Wiring Using Wire Terminals ........................................................................................................................................ 46RS-232 Serial Port To USB Port Converter ........................................................................................................................................................ 47
WattMaster Controls Inc.8500 NW River Park Drive · Parkville , MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.wattmaster.comForm: WM-VAVWIRE-TGD-01C Copyright 2008 WattMaster Controls, Inc.WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.This document is subject to change without notice.
Component & System Wiring 3
Add-On Devices Diagrams............................................................................................................................. 49Lighting Panel Wiring For Standard Lighting Contactors ................................................................................................................................... 50Lighting Panel Wiring For GE® Latching Relay Lighting Contactors ................................................................................................................. 51Optimal Start Scheduler Wiring .......................................................................................................................................................................... 52GPC Wiring ......................................................................................................................................................................................................... 53GPC-17 Wiring ................................................................................................................................................................................................... 54
Miscellaneous Diagrams & Technical Information ...................................................................................... 55Over Voltage Board Wiring ................................................................................................................................................................................. 56Chip Locations .................................................................................................................................................................................................... 57Chip Locations (Cont’d) ...................................................................................................................................................................................... 58Chip Installation Procedures ............................................................................................................................................................................... 59Temperature & Humidity Sensor Voltage-Resistance Tables ............................................................................................................................. 60Pressure Sensors Voltage-Resistance Tables ................................................................................................................................................... 61Notes .................................................................................................................................................................................................................. 62Notes .................................................................................................................................................................................................................. 63
Table Of Contents
Component & System Wiring4
Component & System Wiring 5
System Configurations
Installation &
Commissioning
Component & System Wiring6
Networked Single Loop System
EP
RO
M
U3
U5
RA
M
CX2
1
U2
R1
C3
U4
CX
3
CX
4
YS
101818P
552
PR
OC
ES
SO
RP
BO
AR
D
CX
5C
1
U1
R2
CX
1
CX
6
WD
OG
U6
PH
ILIP
S
D1
P1
X1
C2
C4
0-1
0V
4-2
0m
A
TH
ER
M
R27
R31
D4
GND
24VAC
TB1
D5
C11
U1
2
LE
D2
PO
WE
R
V1
R25
R26
C7
CX15
CX13
PR
OC
.D
RIV
ER
LO
OP
DR
IVE
R
LO
CA
LL
OO
P
GND
AIN2
AIN1
+5V
TB2
P4
OF
F=
0-5
VAIN
2A
IN1
0-1
0V
4-2
0m
A
TH
ER
M
TB3
U15
LD
5L
D6
U13
C8
LE
D1RV
1
R4VREF
CX2
U11
YS
10
19
00
PM
INIL
INK
PO
LL
ING
DE
VIC
ER
EV
.1
OF
F
12481632
CX14
NE
TW
OR
KD
RIV
ER
RN
3
SHLD
SHLD
T
T
TB4
R
R
U14
NE
TW
OR
KL
OO
P
P5
ADD
P3
R24
LD
4
C9
U1
0
RN
2
SW
1R3
0
X2
R2
9
R2
8
C1
0
U6
CX6CX1
U7
U1
X1
C3
C1
R3
CX
7
Lin
eV
olt
ag
e
Lin
eV
olt
ag
e
Netw
ork
Lo
cal
Lo
cal
24
VA
C(8
VA
)
24
VA
C(6
VA
)
24
VA
C(6
VA
)
Back
Vie
wo
fC
om
mL
ink
Fro
nt
Vie
wo
fC
om
mL
ink
CL
IIom
min
k
LOOP
24V
TG
R
GND
RE
MO
TE
LIN
K(D
TE
)C
OM
PU
TE
R(D
CE
)
485LOOP
STA
TU
S
POWER
COMP
RLINK
SE
RIA
L#
CO
NT
RO
LS
110
VA
CTo
24
VA
CP
ow
er
Pack
Co
mm
Lin
k
Min
iLin
kP
DL
oo
p1
VA
VB
OX
Co
ntr
oll
er
VA
VB
OX
Co
ntr
oll
er
VA
VB
OX
Co
ntr
oll
er
WM
VA
VC
on
tro
lle
r
(1M
EG
)
TB
1
Co
nn
ectTo
Mo
du
lar
I/O
Co
nn
ecto
rsL
oca
ted
On
Ba
ck
OfT
he
Syste
mM
an
ag
er
ENTE
R
CLEA
RES
C
PREV
NEXT
DOW
N
UP
65
4 DEC7
08
13
2
9
MIN
US -
STAT
US
SETP
OINT
S
SCHE
DULE
S
ALAR
MS
OVER
RIDE
S
Mo
du
lar
Syste
mM
an
ag
er
No
te:
AM
odula
rS
yste
mM
anager,
AM
odula
rS
erv
ice
ToolO
rA
PC
With
Prism
Softw
are
Insta
lled
Can
Be
Used
To
Pro
gra
mA
nd
Configure
TheW
attM
aste
rV
AV
Syste
m.
No
te:
See
Page
2O
fT
his
Dra
win
gF
or
OptionalC
om
pute
rA
nd
Rem
ote
Lin
kC
onnection
Dia
gra
m.
11
10
00
Mo
du
lar
Se
rvic
eTo
ol
Mod
eSe
lect
ion
ENTE
R
CLEA
RES
C
PREV
NEXT
DOW
N
UP
65
4 DEC7
08
13
2
9
MIN
US -
STAT
US
SETP
OINT
S
SCHE
DULE
S
CONF
IGUR
ATIO
N
ALAR
MS
ON
OVER
RIDE
S
BALA
NCE-
TEST
ConnectTo
Next
VA
VB
OX
Contr
olle
rLocalLoop
SH
LD
T R
Typ
icalTerm
inalB
locks.A
llW
irin
gTo
Be
TTo
T,S
HL
D(G
)To
SH
LD
(G)
&R
To
R
TG
R
485LOOP
Typic
alS
ing
leLoop
Netw
orked
Syste
m
05
/12
/04
VA
V-N
etw
ork
-Sin
gle
Loop1B
.CD
R
Ne
two
rkS
yste
m-
Sin
gle
Lo
op
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
Wirin
g&
Co
nn
ectio
nD
iag
ram
JO
BN
AM
E
1o
f3
WH
ITE
(T)
DR
AIN
WIR
E(S
HL
D)
BL
AC
K(R
)
RE
D(2
4V
AC
)
Lin
eV
olt
ag
e
24
VA
C(6
VA
Min
.)
BR
OW
N(G
ND
)
GR
EE
N(G
ND
)
CX
6
SW
1
U1
0
75
17
6
EX
PA
NS
ION
Q3
Q2
D3
VR
17
82
4
GND
R
SHLD
GND
GND
AUX2
AUX1
AUX+VS
TMP
T
24VAC
R1
7
R1
6
U7
C7
R1
5
PO
WE
RR
21
R3
5
YS
10
1562
RE
V3
D4
R26
LD3
L1
SCANREC
R1
2
C6
R11
TOKEN
NET
LD
2
32
R1
4
R1
3
R1
00
LD
1
C5
D1
K1
V2
V3
K2
D2
AC
TU
AT
OR
R1
0
R9
PJ2
V1
C4
EPROM
VR
EF
AD
J
R23
C1
0
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STAT
U11
C1
5
R20
C11
R24
8
16
2
4
ADDRESS
ADD
1U6
U5
R19
U9CX9
R32
D5
C1
4
P.U.
R22
C1
3
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1
U2
R1
R2
R3
CX2
Q1
16L8
R3
4 FLOW
U8
1
RN1
CX8U4
R1
8CX4
U3
CX3
U1
PA
L
CX1
CX
6
SW
1
U1
0
75
17
6
EX
PA
NS
ION
Q3
Q2
D3
VR
17824
GND
R
SHLD
GND
GND
AUX2
AUX1
AUX+VS
TMP
T
24VAC
R1
7
R1
6
U7
C7
R1
5
PO
WE
RR
21
R3
5
YS
10
1562
RE
V3
D4
R26
LD3
L1
SCANREC
R1
2
C6
R11
TOKEN
NET
LD
2
32
R1
4
R1
3
R1
00
LD
1
C5
D1
K1
V2
V3
K2
D2
AC
TU
AT
OR
R1
0
R9
PJ2
V1
C4
EPROM
VR
EF
AD
J
R23
C1
0
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STAT
U11
C1
5
R20
C11
R24
8
16
2
4
ADDRESS
ADD
1U6
U5
R19
U9CX9
R32
D5
C1
4
P.U.
R22
C1
3
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1
U2
R1
R2
R3
CX2
Q1
16L8
R3
4 FLOW
U8
1
RN1
CX8U4
R1
8CX4
U3
CX3
U1
PA
L
CX1
CX
6
SW
1
U1
0
75
17
6
EX
PA
NS
ION
Q3
Q2
D3
VR
17
82
4
GND
R
SHLD
GND
GND
AUX2
AUX1
AUX+VS
TMP
T
24VAC
R1
7
R1
6
U7
C7
R1
5
PO
WE
RR
21
R3
5
YS
10
1562
RE
V3
D4
R26
LD3
L1
SCANREC
R1
2
C6
R11
TOKEN
NET
LD
2
32
R1
4
R1
3
R1
00
LD
1
C5
D1
K1
V2
V3
K2
D2
AC
TU
AT
OR
R1
0
R9
PJ2
V1
C4
EPROM
VR
EF
AD
J
R23
C1
0
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STAT
U11
C1
5
R20
C11
R24
8
16
2
4
ADDRESS
ADD
1U6
U5
R19
U9CX9
R32
D5
C1
4
P.U.
R22
C1
3
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1
U2
R1
R2
R3
CX2
Q1
16L8
R3
4 FLOW
U8
1
RN1
CX8U4
R1
8CX4
U3
CX3
U1
PA
L
CX1
Lin
eV
olt
ag
eL
ine
Vo
ltag
e
24
VA
C(6
VA
Min
.)24
VA
C(6
VA
Min
.)
Component & System Wiring 7
Networked Single Loop - Computer Connection With Remote Link
VA
V-N
etw
ork
-Sin
gle
Loop1B
.CD
R
9P
inF
em
ale
En
d
Tele
ph
on
eC
ab
leA
ssem
bly
9P
inF
em
ale
Co
nn
ecto
r9
Pin
Fem
ale
Co
nn
ecto
r
Mo
lded
Cab
leA
ssem
bly
25
Pin
Male
En
d
25
Pin
Fem
ale
Co
nn
ecto
r(I
fR
eq
d)
Co
nn
ect
To
Co
mp
ute
rS
eri
alP
ort
Pers
on
alC
om
pu
ter
(By
Oth
ers
)
Ded
icate
dTele
ph
on
eO
utl
et
(By
Oth
ers
)
Back
Vie
wo
fC
om
mL
ink
Back
Vie
wo
fR
em
ote
Lin
k
Fro
nt
Vie
wo
fC
om
mL
ink
No
te:
IfD
ire
ct
Co
mp
ute
rC
on
ne
ctio
nIs
Re
qu
ire
d,
Co
nn
ectTo
PC
As
Sh
ow
n.
Re
mo
teL
ink
IsO
nly
Re
qu
ire
dIf
Ala
rmC
allo
ut
Or
Re
mo
teC
om
pu
ter
Co
nn
ectio
nIs
Re
qu
ire
d.
Fro
nt
Vie
wo
fR
em
ote
Lin
k
CL
IIom
min
k
LOOP
24V
TG
R
GND
RE
MO
TE
LIN
K(D
TE
)C
OM
PU
TE
R(D
CE
)
485LOOP
STA
TU
S
POWER
COMP
RLINK
SE
RIA
L#
CO
NT
RO
LS
RL
em
ote
ink
SIG
TE
LC
OL
INE
TE
LC
OL
INE
SE
RIA
LD
ATA
DET
RDY
SND
REC
PWR
SE
RIA
L#
CO
NT
RO
LS
8C
on
du
cto
rM
od
ula
rC
ab
leA
ssem
bly
110
VA
CTo
9V
DC
Po
wer
Pack
110
VA
CTo
24
VA
CP
ow
er
Pack
Co
mm
Lin
k
Re
mo
teL
ink
(Op
tio
na
l)
ConnectTo
Min
iLin
kP
DN
etw
ork
Term
inals
See
Page
1O
fT
his
Dra
win
g
PO
WE
R9V
DC
@500m
A
SH
LD
T R
Typ
icalTerm
inalB
locks.A
llW
irin
gTo
Be
TTo
T,S
HL
D(G
)To
SH
LD
(G)
&R
To
R
TG
R
485LOOP
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
Wirin
g&
Co
nn
ectio
nD
iag
ram
JO
BN
AM
E
2o
f3
Ne
two
rkS
yste
m-
Sin
gle
Lo
op
03
/24
/04
Opti
onalC
om
pute
rC
onnecti
on
Dia
gra
m
Usin
gR
em
ote
Lin
kFor
Rem
ote
Connecti
on
Component & System Wiring8
Networked Single Loop - Computer Connection With IP-Link
9P
inF
em
ale
En
d
Co
nn
ec
tE
the
rne
tR
J4
5C
ab
leA
ss
em
bly
To
10
Ba
se
TP
ort
On
IP-L
ink
9P
inF
em
ale
Co
nn
ec
tor
9P
inF
em
ale
Co
nn
ec
tor
Mo
lde
dC
ab
leA
ss
em
bly
Su
pp
lie
dW
ith
IP-L
ink
Kit
9P
inM
ale
En
dC
on
ne
ct
To
Se
ria
lP
ort
On
IP-L
ink
25
Pin
Fe
ma
leC
on
ne
cto
r(I
fR
eq
d)
Co
nn
ec
tTo
Co
mp
ute
rS
eri
al
Po
rt
Pe
rso
na
lC
om
pu
ter
(By
Oth
ers
)
Co
nn
ec
tE
the
rne
tR
J4
5C
ab
leA
ss
em
bly
(By
Oth
ers
)To
10
Ba
se
TC
on
ne
cti
on
On
Eth
ern
et
Ro
ute
rO
rM
od
em
(By
Oth
ers
)
Ba
ck
Vie
wo
fC
om
mL
ink
Ba
ck
Vie
wo
fIP
-Lin
k
No
te:
IfD
ire
ct
Co
mp
ute
rC
on
ne
ctio
nIs
Re
qu
ire
d,
Co
nn
ectTo
PC
As
Sh
ow
n.
IP-L
ink
IsO
nly
Re
qu
ire
dIf
E-m
ail
Ala
rmN
otifica
tio
nO
rR
em
ote
Co
mp
ute
rC
on
ne
ctio
nIs
Re
qu
ire
d.
Fro
nt
Vie
wo
fIP
-L
ink
CL
IIom
min
k
LOOP
24V
TG
R
GND
RE
MO
TE
LIN
K(D
TE
)C
OM
PU
TE
R(D
CE
)
485LOOP
STA
TU
S
POWER
COMP
RLINK
SE
RIA
L#
CO
NT
RO
LS
8C
on
du
cto
rM
od
ula
rC
ab
leA
ss
em
bly
11
0V
AC
To
9V
DC
Po
we
rP
ac
k
11
0V
AC
To
24
VA
CP
ow
er
Pa
ck
IP-L
ink
(Op
tio
na
l)
SH
LD
T R
Ty
pic
al
Te
rmin
al
Blo
ck
s.A
llW
irin
gTo
Be
TTo
T,
SH
LD
(G)
To
SH
LD
(G)
&R
To
R
TG
R
485LOOP
Opti
onalC
om
pute
rC
onnecti
on
Dia
gra
m
Usin
gIP
-Lin
kFor
Rem
ote
Connecti
on
Fro
nt
Vie
wo
fC
om
mL
ink
Co
mm
Lin
k
No
te:
1.S
et
Co
mm
Lin
kIn
tern
alS
witch
To
”Mu
lti”
2.
Re
pla
ce
Co
mm
Lin
kE
PR
OM
With
IP-L
ink
EP
RO
MS
up
plie
dW
ith
IP-L
ink
Kit
9V
DC
10B
aseT
Seri
al
Mo
de
PW
R
SER
RCV
LNK
ACT
Connect
ne
VA
V-N
etw
ork
-Sin
gle
Loop1B
.CD
R
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
Wirin
g&
Co
nn
ectio
nD
iag
ram
JO
BN
AM
E
3o
f3
Ne
two
rkS
yste
m-
Sin
gle
Lo
op
03
/24
/04
Co
nn
ectTo
Min
iLin
kP
DN
etw
ork
Te
rmin
als
Se
eP
ag
e1
OfT
his
Dra
win
g
Component & System Wiring 9
EP
RO
M
U3
U5
RA
M
CX2
1
U2
R1
C3
U4
CX
3
CX
4
YS
101818P
552
PR
OC
ES
SO
RP
BO
AR
D
CX
5C
1
U1
R2
CX
1
CX
6
WD
OG
U6
PH
ILIP
S
D1
P1
X1
C2
C4
0-1
0V
4-2
0m
A
TH
ER
M
R27
R31
D4
GND
24VAC
TB1
D5
C11
U1
2
LE
D2
PO
WE
R
V1
R25
R26
C7
CX15
CX13
PR
OC
.D
RIV
ER
LO
OP
DR
IVE
R
LO
CA
LLO
OP
GND
AIN2
AIN1
+5V
TB2
P4
OF
F=
0-5
VAIN
2A
IN1
0-1
0V
4-2
0m
A
TH
ER
M
TB3
U15
LD
5LD
6
U13
C8
LE
D1RV
1
R4VREF
CX2
U11
YS
10
19
00
PM
INIL
INK
PO
LL
ING
DE
VIC
ER
EV
.1
OF
F
12481632
CX14
NE
TW
OR
KD
RIV
ER
RN
3
SHLD
SHLD
T
T
TB4
R
R
U14
NE
TW
OR
KLO
OP
P5
ADD
P3
R24
LD
4
C9
U1
0
RN
2
SW
1R3
0
X2
R2
9
R2
8
C1
0
U6
CX6CX1
U7
U1
X1
C3
C1
R3
CX
7
EP
RO
M
U3
U5
RA
MCX2
1
U2
R1
C3
U4
CX
3
CX
4
YS
101818P
552
PR
OC
ES
SO
RP
BO
AR
D
CX
5C
1
U1
R2
CX
1
CX
6
WD
OG
U6
PH
ILIP
S
D1
P1
X1
C2
C4
0-1
0V
4-2
0m
A
TH
ER
M
R27
R31
D4
GND
24VAC
TB1
D5
C11
U1
2
LE
D2
PO
WE
R
V1
R25
R26
C7
CX15
CX13
PR
OC
.D
RIV
ER
LO
OP
DR
IVE
R
LO
CA
LLO
OP
GND
AIN2
AIN1
+5V
TB2
P4
OF
F=
0-5
VAIN
2A
IN1
0-1
0V
4-2
0m
A
TH
ER
M
TB3
U15
LD
5LD
6
U13
C8
LE
D1RV
1
R4VREF
CX2
U11
YS
10
19
00
PM
INIL
INK
PO
LL
ING
DE
VIC
ER
EV
.1
OF
F
12481632
CX14
NE
TW
OR
KD
RIV
ER
RN
3
SHLD
SHLD
T
T
TB4
R
R
U14
NE
TW
OR
KLO
OP
P5
ADD
P3
R24
LD
4
C9
U1
0
RN
2
SW
1R3
0
X2
R2
9
R2
8
C1
0
U6
CX6CX1
U7
U1
X1
C3
C1
R3
CX
7
Lin
eV
olt
ag
e
Lin
eV
olt
ag
e
Ne
two
rk
Ne
two
rk
Network
Lo
ca
l
Lo
ca
l
Lo
ca
l
24
VA
C(8
VA
)
24
VA
C(6
VA
)
24
VA
C(6
VA
)
24
VA
C(6
VA
)
Ba
ck
Vie
wo
fC
om
mL
ink
Fro
nt
Vie
wo
fC
om
mL
ink
CL
IIom
min
k
LOOP
24V
TG
R
GND
RE
MO
TE
LIN
K(D
TE
)C
OM
PU
TE
R(D
CE
)
485LOOP
STA
TU
S
POWER
COMP
RLINK
SE
RIA
L#
CO
NT
RO
LS
11
0V
AC
To
24
VA
CP
ow
er
Pa
ck
Co
mm
Lin
k
Min
iLin
kP
DL
oo
p1
Min
iLin
kP
DL
oo
p2
VA
VB
OX
Co
ntr
oll
er
VA
VB
OX
Co
ntr
oll
er
VA
VB
OX
Co
ntr
oll
er
WM
VA
VC
on
tro
ller
(1M
EG
)
TB
1
ConnectTo
Modula
rI/O
Connecto
rsLocate
dO
nB
ack
OfT
he
Syste
mM
anager
ENTE
R
CLEA
RES
C
PREV
NEXT
DOW
N
UP
65
4 DEC7
08
13
2
9
MIN
US -
STAT
US
SETP
OINT
S
SCHE
DULE
S
ALAR
MS
OVER
RIDE
S
Mo
du
lar
Sy
ste
mM
an
ag
er
No
te:
AM
od
ula
rS
yste
mM
an
ag
er,
AM
od
ula
rS
erv
ice
To
olO
rA
PC
With
Prism
So
ftw
are
Insta
lled
Ca
nB
eU
se
dTo
Pro
gra
mA
nd
Co
nfig
ure
Th
eW
att
Ma
ste
rV
AV
Syste
m.
No
te:
Se
eP
ag
e2
an
d3
OfT
his
Dra
win
gF
or
Op
tio
na
lC
om
pu
ter
To
Re
mo
teL
ink
or
IP-L
inkC
on
ne
ctio
ns
11
10
00
Mo
du
lar
Se
rvic
eTo
ol
Mod
eSe
lect
ion
ENTE
R
CLEA
RES
C
PREV
NEXT
DOW
N
UP
65
4 DEC7
08
13
2
9
MIN
US -
STAT
US
SETP
OINT
S
SCHE
DULE
S
CONF
IGUR
ATIO
N
ALAR
MS
ON
OVER
RIDE
S
BALA
NCE-
TEST Co
nn
ectTo
Ne
xt
VA
VB
OX
Co
ntr
olle
rO
nL
oo
p1
Co
nn
ectTo
Min
iLin
kP
olli
ng
De
vic
eL
oo
p3
Co
nn
ectTo
Lo
op
2V
AV
BO
XC
on
tro
ller
Or
WM
VA
VC
on
tro
ller
SH
LD
T R
Ty
pic
al
Te
rmin
al
Blo
ck
s.A
llW
irin
gTo
Be
TTo
T,
SH
LD
(G)
To
SH
LD
(G)
&R
To
R
TG
R
485LOOP
Typic
alM
ult
iple
Loop
Netw
orked
Syste
m
05/1
2/0
4
VA
V-N
etw
ork
-MultLoop1B
.CD
R
Ne
two
rkS
yste
m-
Mu
ltip
leL
oo
p
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
Wirin
g&
Co
nn
ectio
nD
iag
ram
JO
BN
AM
E
1o
f3
WH
ITE
(T)
DR
AIN
WIR
E(S
HL
D)
BL
AC
K(R
)
RE
D(2
4V
AC
)
Lin
eV
olt
ag
e
24
VA
C(6
VA
Min
.)
GR
EE
N(G
ND
)
CX
6
SW
1
U1
0
75
17
6
EX
PA
NS
ION
Q3
Q2
D3
VR
17
82
4
GND
R
SHLD
GND
GND
AUX2
AUX1
AUX+VS
TMP
T
24VAC
R1
7
R1
6
U7
C7
R1
5
PO
WE
RR
21
R3
5
YS
10
15
62
RE
V3
D4
R26
LD3
L1
SCANREC
R1
2
C6
R11
TOKEN
NET
LD
2
32
R1
4
R1
3
R1
00
LD
1
C5
D1
K1
V2
V3
K2
D2
AC
TU
AT
OR
R1
0
R9
PJ2
V1
C4
EPROM
VR
EF
AD
J
R23
C1
0
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STAT
U11
C1
5
R20
C11
R24
8
16
2
4
ADDRESS
ADD
1U6
U5
R19
U9CX9
R32
D5
C1
4
P.U.
R22
C1
3
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1
U2
R1
R2
R3
CX2
Q1
16L8
R3
4 FLOW
U8
1
RN1
CX8U4
R1
8CX4
U3
CX3
U1
PA
L
CX1
CX
6
SW
1
U1
0
75
17
6
EX
PA
NS
ION
Q3
Q2
D3
VR
17
82
4
GND
R
SHLD
GND
GND
AUX2
AUX1
AUX+VS
TMP
T
24VAC
R1
7
R1
6
U7
C7
R1
5
PO
WE
RR
21
R3
5
YS
10
15
62
RE
V3
D4
R26
LD3
L1
SCANREC
R1
2
C6
R11
TOKEN
NET
LD
2
32
R1
4
R1
3
R1
00
LD
1
C5
D1
K1
V2
V3
K2
D2
AC
TU
AT
OR
R1
0
R9
PJ2
V1
C4
EPROM
VR
EF
AD
J
R23
C1
0
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STAT
U11
C1
5
R20
C11
R24
8
16
2
4
ADDRESS
ADD
1U6
U5
R1
9
U9CX9
R32
D5
C1
4
P.U.
R22
C1
3
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1
U2
R1
R2
R3
CX2
Q1
16L8
R3
4 FLOW
U8
1
RN1
CX8U4
R1
8CX4
U3
CX3
U1
PA
L
CX1
CX
6
SW
1
U1
0
75
17
6
EX
PA
NS
ION
Q3
Q2
D3
VR
17
82
4
GND
R
SHLD
GND
GND
AUX2
AUX1
AUX+VS
TMP
T
24VAC
R1
7
R1
6
U7
C7
R1
5
PO
WE
RR
21
R3
5
YS
10
15
62
RE
V3
D4
R26
LD3
L1
SCANREC
R1
2
C6
R11
TOKEN
NET
LD
2
32
R1
4
R1
3
R1
00
LD
1
C5
D1
K1
V2
V3
K2
D2
AC
TU
AT
OR
R1
0
R9
PJ2
V1
C4
EPROM
VR
EF
AD
J
R23
C1
0
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STAT
U11
C1
5
R20
C11
R24
8
16
2
4
ADDRESS
ADD
1U6
U5
R19
U9CX9
R32
D5
C1
4
P.U.
R22
C1
3
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1
U2
R1
R2
R3
CX2
Q1
16L8
R3
4 FLOW
U8
1
RN1
CX8U4
R1
8CX4
U3
CX3
U1
PA
L
CX1
Lin
eV
olt
ag
eL
ine
Vo
lta
ge
24
VA
C(6
VA
Min
.)2
4V
AC
(6V
AM
in.)
BR
OW
N(G
ND
)
Networked Multiple Loop System
Component & System Wiring10
Networked Multiple Loop - Computer Connection With Remote Link
03
/24
/04
VA
V-N
etw
ork
-MultLoop1B
.CD
R
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
Wirin
g&
Co
nn
ectio
nD
iag
ram
JO
BN
AM
E
2o
f3
Ne
two
rkS
yste
m-
Mu
ltip
leL
oo
p
9P
inF
em
ale
En
d
Tele
ph
on
eC
ab
leA
ssem
bly
9P
inF
em
ale
Co
nn
ecto
r9
Pin
Fem
ale
Co
nn
ecto
r
Mo
lded
Cab
leA
ssem
bly
25
Pin
Male
En
d
25
Pin
Fem
ale
Co
nn
ecto
r(I
fR
eq
d)
Co
nn
ect
To
Co
mp
ute
rS
eri
alP
ort
Pers
on
alC
om
pu
ter
(By
Oth
ers
)
Ded
icate
dTele
ph
on
eO
utl
et
(By
Oth
ers
)
Back
Vie
wo
fC
om
mL
ink
Back
Vie
wo
fR
em
ote
Lin
k
Fro
nt
Vie
wo
fC
om
mL
ink
No
te:
IfD
ire
ct
Co
mp
ute
rC
on
ne
ctio
nIs
Re
qu
ire
d,
Co
nn
ectTo
PC
As
Sh
ow
n.
Re
mo
teL
ink
IsO
nly
Re
qu
ire
dIf
Ala
rmC
allo
ut
Or
Re
mo
teC
om
pu
ter
Co
nn
ectio
nIs
Re
qu
ire
d.
Fro
nt
Vie
wo
fR
em
ote
Lin
k
CL
IIom
min
k
LOOP
24V
TG
R
GND
RE
MO
TE
LIN
K(D
TE
)C
OM
PU
TE
R(D
CE
)
485LOOP
STA
TU
S
POWER
COMP
RLINK
SE
RIA
L#
CO
NT
RO
LS
RL
em
ote
ink
SIG
TE
LC
OL
INE
TE
LC
OL
INE
SE
RIA
LD
ATA
DET
RDY
SND
REC
PWR
SE
RIA
L#
CO
NT
RO
LS
8C
on
du
cto
rM
od
ula
rC
ab
leA
ssem
bly
110
VA
CTo
9V
DC
Po
wer
Pack
110
VA
CTo
24
VA
CP
ow
er
Pack
Co
mm
Lin
k
Re
mo
teL
ink
(Op
tio
na
l)
ConnectTo
Min
iLin
kP
DN
etw
ork
Term
inals
See
Page
1O
fT
his
Dra
win
g
PO
WE
R9V
DC
@500m
A
SH
LD
T R
Typ
icalTerm
inalB
locks.A
llW
irin
gTo
Be
TTo
T,S
HL
D(G
)To
SH
LD
(G)
&R
To
R
TG
R
485LOOP
Opti
onalC
om
pute
rC
onnecti
on
Dia
gra
m
Usin
gR
em
ote
Lin
kFor
Rem
ote
Connecti
on
Component & System Wiring 11
03/2
4/0
4
VA
V-N
etw
ork
-MultLoop1B
.CD
R
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
Wirin
g&
Co
nn
ectio
nD
iag
ram
JO
BN
AM
E
3o
f3
Ne
two
rkS
yste
m-
Mu
ltip
leL
oo
p
9P
inF
em
ale
En
d
Co
nn
ect
Eth
ern
et
RJ45
Cab
leA
ssem
bly
To
10B
aseT
Po
rtO
nIP
-Lin
k
9P
inF
em
ale
Co
nn
ecto
r9
Pin
Fem
ale
Co
nn
ecto
r
Mo
lded
Cab
leA
ssem
bly
Su
pp
lied
Wit
hIP
-Lin
kK
it
9P
inM
ale
En
dC
on
nect
To
Seri
al
Po
rtO
nIP
-Lin
k
25
Pin
Fem
ale
Co
nn
ecto
r(I
fR
eq
d)
Co
nn
ect
To
Co
mp
ute
rS
eri
alP
ort
Pers
on
alC
om
pu
ter
(By
Oth
ers
)
Co
nn
ect
Eth
ern
et
RJ45
Cab
leA
ssem
bly
(By
Oth
ers
)To
10
BaseT
Co
nn
ecti
on
On
Eth
ern
et
Ro
ute
rO
rM
od
em
(By
Oth
ers
)
Back
Vie
wo
fC
om
mL
ink
Back
Vie
wo
fIP
-Lin
k
No
te:
IfD
irectC
om
pute
rC
onnection
IsR
equired,C
onnectTo
PC
As
Show
n.
IP-L
ink
IsO
nly
Required
IfE
Ala
rmN
otification
Or
Rem
ote
Com
pute
rC
onnection
IsR
equired.
Fro
nt
Vie
wo
fIP
-L
ink
CL
IIom
min
k
LOOP
24V
TG
R
GND
RE
MO
TE
LIN
K(D
TE
)C
OM
PU
TE
R(D
CE
)
485LOOP
STA
TU
S
POWER
COMP
RLINK
SE
RIA
L#
CO
NT
RO
LS
8C
on
du
cto
rM
od
ula
rC
ab
leA
ssem
bly
110
VA
CTo
9V
DC
Po
wer
Pack
110
VA
CTo
24
VA
CP
ow
er
Pack
IP-L
ink
(Op
tio
na
l)
SH
LD
T R
Typ
icalTerm
inalB
locks.A
llW
irin
gTo
Be
TTo
T,S
HL
D(G
)To
SH
LD
(G)
&R
To
R
TG
R
485LOOP
Opti
onalC
om
pute
rC
onnecti
on
Dia
gra
m
Usin
gIP
-Lin
kFor
Rem
ote
Connecti
on
Fro
nt
Vie
wo
fC
om
mL
ink
Co
mm
Lin
k
No
te:
1.S
etC
om
mLin
kIn
tern
alS
witch
To”M
ulti”
2.R
epla
ce
Com
mLin
kE
PR
OM
With
IP-L
ink
EP
RO
MS
upplie
dW
ith
IP-L
ink
Kit
9V
DC
10B
aseT
Seri
al
Mo
de
PW
R
SER
RCV
LNK
ACT
Connect
ne
ConnectTo
Min
iLin
kP
DN
etw
ork
Term
inals
See
Page
1O
fT
his
Dra
win
g
Networked Multiple Loop - Computer Connection With IP-Link
Component & System Wiring12
General Information
The WattMaster VAV system components can be configured into dif-ferent types of systems depending on the type and number of control-lers required. It is a good idea to become familiar with the types ofsystems and their architecture by reading the information in this sectionand looking at the configuration diagrams in the System Configura-tions Installation & Commissioning section of this manual. The infor-mation below is designed to help you understand how the system com-ponents integrate with each other and the available configuration op-tions.
System Types
Two different system configurations are available depending on the typeand number of controllers that you have on your system.
1. Networked Single Loop(See Pages 6 Through 8 For Connection Diagrams)
2. Networked Multiple Loop(See Pages 9 Through 11 For Connection Diagrams)
System Type Definitions
Networked Single LoopThe Networked Single Loop system, as its name implies, consists of asingle communications loop. The system can consist of the followingcontrollers and devices.
1. A single WMVAV controller used as a VAV controller andit’s associated VAVBOXcontrollers. Other WMVAVcontrollers used for constant volume units and/or and Add-on Devices may also be connected as long as the total of allcontrollers on the loop does not exceed 59. Only one VAVcontroller with it’s VAVBOX controllers can be installedper loop. If more than one VAV controller with VAVBOXcontrollers is required, you must have a separate loop foreach.
This system requires one CommLink communications interface andone MiniLink Polling Device. Programming and status monitoring areaccomplished by the following methods.
1. By using an operators interface. This can be either aModular System Manager, a Modular Service Tool or bothdevices. The System Manager or Modular Service Toolcan connect to any controller on the local loop.
2. A computer interface can also be used in conjunction withthe other operators interfaces listed above, or by itself. Thisrequires a personal computer with the Prism computer frontend software installed. The PC connects to the CommLinkvia a supplied cable.
Networked Multiple LoopThis Networked Multiple Loop System consists of two or more loops,each being called ‘Local Loops’, with one ‘Network Loop’ that ties the“Local Loops” together. Each of these local loops can consist of thefollowing controllers and devices.
1. A series of WMVAV controllers for constant volume unitsand/or Add-on devices without any VAVBOX controllers.Up to 59 controllers may be connected on the loop in thismanner.
2. A single WMVAV controller used as a VAV controller andits associated VAVBOX controllers. Other WMVAVcontrollers used for constant volume units and/or and Add-on Devices may also be connected as long as the total of allcontrollers on the loop does not exceed 59. Only one VAVcontroller with its VAVBOX controllers can be installedper local loop.
To form the Networked Multiple Loop System the following networkdevices are required.
1. A MiniLink Polling Device is required per loop (LocalLoop). This allows the controllers to share information thatis broadcast from one controller to all controllers on thatlocal loop and also provides alarming and trend loggingcapabilities.
2. One CommLink is required for the entire system. It resideson the Network Loop and allows for communicationsbetween all the local loops and provides for globalbroadcasts to all controllers on the entire system.
Programming and status monitoring are accomplished by one or moreof the following methods.
1. By using an operator interface. This can be either aModular System Manager, a Modular Service Tool or bothdevices. The System Manager or Modular Service Tool canconnect to any controller on any “Local Loop” on theentire system.
2. A computer interface can also be used in conjunction withthe other operators interfaces listed above, or by itself. Thisrequires a personal computer with the Prism computer frontend software installed. The PC connects to the CommLinkvia a supplied cable.
Network Communications Devices
MiniLink Polling Device1. This device is required for all Networked Single loop
systems.
2. One of these device is required on each local loop of allNetworked Multiple Loop systems
CommLink1. One CommLink is required on all Networked Single Loop
or Multiple Loop Systems
2. Up to 60 local loops can be connected to the CommLink
Installation Procedures
The installation procedures that follow are based on recommended meth-ods of wiring connection and controller installation. Installation proce-dures vary depending on the which Networked system you are install-ing. The system you are installing could be “Networked Single Loop”or a “Networked Multiple Loop” system. The Networked Systemsalso have installation variations based on the type of components youare installing for that system. The following information explains theprocedures for all of these systems. Please find the system and compo-nents that closely match your system and follow the outlined proce-dures.
Systems Overview
Component & System Wiring 13
Networked Single Loop Systems
See the “Networked System - Single Loop Wiring” on pages 6 through8 of this manual for detailed wiring information. Also see page 16 forwire and transformer sizing information. You should review these dia-grams before attempting connections or powering up the controller orinterface devices.
1. Connect all WMVAV or Add-on Device controllers in adaisy chain or star ring format by connecting from eachcontroller’s communication terminal block to the next using18 gauge, 2 conductor shielded cable. Install a separate 24VAC, transformer for each controller and wire from eachcontroller’s power terminal block to its transformer using18 gauge minimum, 2 wire cable for power. See Wire andTransformer Sizing section on page 16 for detailedtransformer and wire sizing information. Observe polarityon all board power wiring. Install a separate 24 VAC, 6 VAminimum, transformer for each VAVBOX controller on theloop and wire from each controller’s power terminal blockto its transformer using 18 gauge minimum, 2 wire cable.Observe polarity on all boards! As an alternative, a singletransformer that connects to all VAVBOX controllers mayalso be used. It must be sized to handle the minimum loadof 6 VA per VAVBOX controller connected to it. Whenusing this method, the polarity of all wiring between thetransformer and the VAVBOX controllers is extremelycritical and must be maintained to prevent damage toall boards connected! See the wire and transformer sizinginformation on page 16 of this manual for completewire and transformer sizing information.
Warning: If polarity between controllers is not maintained,severe damage to the controllers may result.WattMaster recommends using a separate transformerfor each controller in order to eliminate the potentialfor damaging controllers due to incorrect polarity.
2. Using 18 gauge 2 conductor shielded cable, connect fromthe WMVAV controller’s 3 wire communicationsconnector to the MiniLink PD’s 3 wire communicationsconnector marked “Local Loop”.
3. Connect 2 conductor shielded cable from theMiniLink PD’s 3 wire communications terminal blockslabeled “Network Loop” to the CommLink’s 3 wirecommunications terminal block located on the back of theCommLink. Find the 110 VAC/24 VAC power supplyfurnished with the CommLink and connect the 2 strippedwire leads to the 24 VAC terminals on the back of theCommLink. The CommLink’s internal jumper must be setto “Multiple” for all WattMaster VAV systems. See page 45of this manual for complete CommLink wiring and jumpersetting information. After determining all wiring andjumper settings are correct, connect the power supply plug-in transformer to a 110 V receptacle.
4. Install a 24 VAC, 6 VA minimum, transformer for theMiniLink PD and wire it to the 24 VAC power terminalblock on the MiniLink PD using 18 gauge minimum, 2wire cable. See page 46 of this manual for completeMiniLink PD wiring diagrams and instructions.
5. When the Modular Service Tool is to be used forprogramming and monitoring of the controllers it can beconnected to the WMVAV controllers using the suppliedcable with DIN connectors on both ends. The DINconnector on the WMVAV controller is located near thecommunications terminals. To connect the Modular ServiceTool to a VAVBOX controller first unplug the 3 wirecommunication terminal block from the VAVBOXcontroller. Connect the DIN to terminal adapter terminalend to the communication terminals block socket on theVAVBOX controller then connect the DIN connector sideof the adapter to the Modular Service Tool cable DINconnector. See page 44 of this manual for completeModular Service Tool connection diagrams andinstructions.
6. The Modular System Manager comes supplied with a 12foot modular cable pigtail with a modular connector on oneend and stripped wires on the other. Plug the modularconnector end into the System Manager modular connector.Run 18 gauge, 2 conductor shielded cable forcommunications from the MiniLink PD or any controlleron the local loop by connecting one end of the controller’sor MiniLink PD’s 3 wire “Local Loop” communicationsterminal block to a junction box located within 12 feet ofthe System Manager. Run 18 gauge, 2 wire, power wiressupplied by a separate 24 VAC, 6 VA minimum transformerinto the junction box. Splice the stripped modular cableends from the System Manager to the communications andpower wire inside of the junction box using solidconnections made with wire nuts or butt-splice connectors.See Modular System Manager wiring on pages 42 and 43of this manual for wiring color coding and complete wiringinstructions. The Modular System Manager MUST alwaysbe connected on the “Local Loop”, never the “NetworkLoop”.
Networked Multiple Loop Systems
See the “Networked System - Multiple Loop Wiring” on pages 9 through11 of this manual for detailed wiring diagrams. Also see page 16 forwire and transformer sizing information. You should review these dia-grams before attempting connections or powering up the controller orinterface devices.
Loop(s) with WMVAV Controllers without VAVBOX Controllers1. For each local loop on the system, connect all controllers in
a daisy chain or star ring format by connecting from eachcontrollers communication terminal block to the next using18 gauge, 2 conductor shielded cable. Install a separate 24VAC, 8 VA minimum, transformer for each controller andwire from each controller’s power terminal block to itstransformer using 18 gauge minimum, 2 wire cable forpower. Observe polarity on all boards.
2. Select one of the local loops and connect 2 conductorshielded cable from one of its WMVAV controller’s 3 wirecommunications terminal blocks to it’s associatedMiniLinkPD’s 3 wire communications terminal block marked “LocalLoop”. Repeat this procedure for all loops on the entiresystem.
Component & System Wiring14
3. Connect 2 conductor shielded cable from one of thesystems MiniLink PD’s 3 wire communications terminalblocks labeled “Network Loop” to the CommLink’s 3 wirecommunications terminal block located on the back of theCommLink. Find the 110 VAC/24 VAC power supplyfurnished with the CommLink and connect the 2stripped wire leads to the 24 VAC terminals on the back ofthe CommLink. The CommLink’s internal jumper must beset to “Multiple” for all WattMaster VAV systems. See page45 of this manual for complete CommLink wiring andjumper setting information. After determining all wiringand jumper settings are correct, connect the power supplyplug-in transformer to a 110 V receptacle.
4. Connect 2 conductor shielded cable for networkcommunications between each MiniLink PD on the systemincluding the one that was just connected to theCommLink. This is accomplished by connecting betweeneach MiniLink PD’s 3 wire communications terminal blocklabeled “Network Loop” and the next MiniLink PD’scommunications terminal block labeled “Network Loop”.Install a 24 VAC, 6 VA minimum, transformer for each ofthe MiniLink PDs on the system and wire each transformerto the 24 VAC power terminal block for its respectiveMiniLink PD using 18 gauge minimum, 2 wire cable. Seepage 46 of this manual for complete MiniLink PD wiringdiagrams and instructions.
5. When the Modular Service Tool is to be used forprogramming and monitoring of the controllers it can beconnected to the WMVAV controllers using the suppliedcable with DIN connectors on both ends. The DINconnector on the WMVAV controller is located near thecommunications terminals. See page 44 of this manual forcomplete Modular Service Tool connection diagrams andinstructions.
6. The Modular System Manager comes supplied with a 12foot modular cable pigtail with a modular connector on oneend and stripped wires on the other. Plug the modularconnector end into the System Manager modular connector.Run 18 gauge, 2 conductor shielded cable forcommunications from the MiniLink PD or any controlleron the local loop by connecting one end the controller’s orMiniLink PD’s 3 wire “Local Loop” communicationsterminal block to a junction box located within 12 feet ofthe System Manager. Run 18 gauge, 2 wire, power wiressupplied by a separate 24 VAC, 6 VA minimum transformerinto the junction box. Splice the stripped modular cableends from the System Manager to the communications andpower wire inside of the junction box using solidconnections made with wire nuts or butt-splice connectors.See Modular System Manager wiring on pages 42 and 43of this manual for wiring color coding and complete wiringinstructions. The Modular System Manager MUST alwaysbe connected on the “Local Loop”, never the “NetworkLoop”.
Loop(s) with WMVAV and VAVBOX Controllers1. Select one of the local loops on your system. Connect all
WMVAV or Add-on Device controllers in a daisy chain orstar ring format by connecting from each controller’scommunication terminal block to the next using 18 gauge,2 conductor shielded cable. Install a separate 24 VAC,transformer for each controller and wire from eachcontroller’s power terminal block to its transformer using18 gauge minimum, 2 wire cable for power. See Wire andTransformer Sizing section on page 16 for detailedtransformer and wire sizing information. Observe polarityon all board power wiring. Install a separate 24 VAC, 8 VAminimum, transformer for each VAVBOX controller on theloop and wire from each controller’s power terminal blockto it’s transformer using 18 gauge minimum, 2 wire cable.Observe polarity on all boards! As an alternative, a singletransformer that connects to all VAVBOX controllers mayalso be used. It must be sized to handle the minimum loadof 6 VA per VAVBOX controller connected to it. Whenusing this method, the polarity of all wiring between thetransformer and the VAVBOX controllers is extremelycritical and must be maintained to prevent damage toall boards connected! See the wire and transformer sizinginformation on page 16 of this manual for complete wireand transformer sizing information. Repeat this procedurefor each loop with VAVBOX controllers on your system.
Warning: If polarity between controllers is not maintained,severe damage to the controllers may result.WattMaster recommends using a separate transformerfor each controller in order to eliminate the potentialfor damaging controllers due to incorrect polarity.
2. For each local loop on the system do the following. Using18 gauge 2 conductor shielded cable, connect fromone of the WMVAV controller’s on the loop, 3 wirecommunications connector to that loop’s MiniLink PD 3wire communications terminal block marked “Local Loop”.
3. To install the CommLink, connect 2 conductor shieldedcable from one of the system’s MiniLink PD’s 3 wirecommunications terminal blocks labeled “Network Loop”to the CommLink’s 3 wire communications terminal blocklocated on the back of the CommLink. Find the 110 VAC/24 VAC power supply furnished with the CommLink andconnect the 2 stripped wire leads to the 24 VAC terminalson the back of the CommLink. The CommLink’s internaljumper must be set to “Multiple” for all WattMaster VAVsystems. See page 45 of this manual for completeCommLink wiring and jumper setting information. Afterdetermining all wiring and jumper settings are correct,connect the power supply plug-in transformer to a 110 Vreceptacle.
4. The following procedure must be performed for eachMiniLink PD on your system. Install a 24 VAC, 6 VAminimum, transformer for theMiniLink PD and wire it tothe 24 VAC power terminal block on the MiniLink PDusing 18 gauge minimum, 2 wire cable. See page 46 of thismanual for complete MiniLink PD wiring diagrams andinstructions. Be sure that all MiniLink PDs on the entiresystem are wired as required.
System Installation
Component & System Wiring 15
5. When the Modular Service Tool is to be used forprogramming and monitoring of the controllers it can beconnected to the WMVAV controllers using the suppliedcable with DIN connectors on both ends. The DINconnector on the WMVAV controller is located near thecommunications terminals. To connect the Modular ServiceTool to a VAVBOX controller, first unplug the 3 wirecommunication terminal block from the VAVBOXcontroller. Connect the DIN to terminal adapter terminalend to the communication terminals block socket on theVAVBOX controller then connect the DIN connector sideof the adapter to the Modular Service Tool cable DINconnector. See page 44 of this manual for completeModular Service Tool connection diagrams andinstructions.
6. The Modular System Manager comes supplied with a 12-foot modular cable pigtail with a modular connector on oneend and stripped wires on the other. Plug the modularconnector end into the System Manager modular connector.Run 18 gauge, 2 conductor shielded cable forcommunications from the MiniLink PD or any controlleron the local loop by connecting one end the controller’s orMiniLink PD’s 3 wire “Local Loop” communicationsterminal block to a junction box located within 12 feet ofthe System Manager. Run 18 gauge, 2 wire, power wiressupplied by a separate 24 VAC, 6 VA minimum transformerinto the junction box. Splice the stripped modular cableends from the System Manager to the communications andpower wire inside of the junction box using solidconnections made with wire nuts or butt-splice connectors.See Modular System Managerl wiring on pages 42 and 43of this manual for wiring color coding and complete wiringinstructions. The Modular System Manager MUST alwaysbe connected on the “Local Loop”, never the “NetworkLoop”.
System Commissioning
The following information is a brief overview of the procedures re-quired to commission a typical WattMaster VAV System.
1. Address each MiniLink PD on the system with a uniqueaddress from 1 to 60.
2. On a loop of WMVAV controllers and/or Add-on Devices,without VAVBOX Controllers, address the controllers anddevices from 1 to 59.
3. On a loop which has VAVBOX controllers, addressthe VAVBOX controllers from 1 to 58. Address theWMVAV controller serving the VAVBOX controllers asaddress 59. Address all other controllers with addresses notalready used by other controllers on the loop.
4. Always apply power to the system in the following order.
WMVAV controllers or Add-on Devices, MiniLink PD(s),CommLink, VAVBOX controllers (if used).
5. After powering up verify diagnostics LED indicator forproper operation of all controllers. See the technical guidefor each specific controller for detailed information on thelocation of its diagnostic LED, and each controller’sstart-up sequence.
6. If a computer is used, install the Prism computer front endsoftware on it and connect it to the CommLink to accessall of the controllers on the entire system for programming.
7. If a computer is not used, and if a Modular System Mangeris not already connected on the local loop, connect aModular Service Tool to one of the controllers to performprogramming of all controllers on the entire system.
Component & System Wiring16
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
Wire & Transformer Sizing
JOB NAME
VAV-WIRSIZ1.CDR
WattMaster VAV
Component Power Requirements
GPC Controller .........................8VA
VAV/CAV Controller ..................8VA
VAVBOX Controller...................6VA
GPC-17 Controller ....................10VA
Lighting Panel Controller ..........10VA
MiniLink Polling Device............. 6VAOptimal Start Scheduler............10VA
1 of 1
05/12/04
24VAC Power - Transformer & Wire Sizing Considerations For VAVBOX Controllers
120 / 24VAC120 / 24VAC
Distance A to B cannot exceed 61.73 Ft.Distance from A to B cannot exceed 123.46 Ft.Distance from A to C cannot exceed 123.46 Ft.
Distance from A to B cannot exceed 230.40 Ft.Distance from A to C cannot exceed 308.64 Ft.Distance from A to D cannot exceed 308.64 Ft.Distance from A to E cannot exceed 308.64 Ft.Distance from A to F cannot exceed 308.64 Ft.
120 / 24VAC
Some installers like to use one large 24VAC transformer to power several devices. This is allowable as long as polarity is maintained to each device onthe transformer circuit.
Usingseparate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioningtransformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several devices, the followingtransformer and wire sizing information is presented to help the installer correctly supply 24VAC power to the devices.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.
Each VAVBOX Controller requires 6 VA @ 24VAC power. In the examples below we have a total of 10 VAV Controllers.
10 VAVBOX Controllers @ 6VA each................ 10 x 6VA =60VA.
The above calculation determines that our transformer will need to be sized for a minimum of 60VA if we are to use one transformer to power all thecontrollers. We will use a 75 VA transformer, as this is a readily available size that meets our VA load requirements.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has avoltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire16ga wire.................................0.00034 = voltage drop per 1’ length of wire14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.
Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 10 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 60VA controller load = Volts/Ft.
WattMaster VAVBOX controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts bythe number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 75 VA transformer with no morethan a 2 Volt drop at the farthest controller from the transformer..
2 (Volts total allowable voltage drop)= 61.73
0.0324 (Voltage drop per 1 ft. @ 60VA load)
Parallel circuiting of the wiring instead of wiring all 10 controllers in series allows for longer wire runs to be used with the same size wire (as shown inour examples below).
Warning: If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommendsusing a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity.
0.0324
feet
It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size,transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatorythat the farthest controller on the circuit is supplied with a minimum of 22 Volts and that the polarity is maintained to all controllers connected to thetransformer.
AA
A
B
C
D
E
F
B
B C
Transformer & Wire Sizing
Component & System Wiring 17
WMVAV Controller Wiring
Component & System Wiring18
WMVAV Controller Wiring
Notes:
1.)24 VAC Must Be Connected So ThatAll Ground Wires Remain Common.
4.)When Humidity Sensor Is To BeInstalled A 250 Ohm Resistor Must BeInstalled On The Ground Side Of TheSensor And Pull Up Resistor PU5Must Be Removed From TheController. See Humidity SensorWiring Diagram In The WMVAVsection of this manual.
5.)If The Slide Adjust Option Is Used OnThe Room Sensor , The AUXConnection Must Be Wired To AIN7.The Fan Proof Of Flow Switch,Which Normally Connects To AIN7, IsNot Available For Use When TheSlide Adjust Option Is Used.3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
05/12/04
VAV-WMVAVWIR1A.CDR
WMVAV Controller1 of 2
Line Voltage
All Comm Loop Wiring IsStraight Thru
24VAC
24VAC
GND
GND
Local Loop RS-4859600 Baud
Analog InputsSee Individual SensorWiring Diagrams For
Detailed Sensor Wiring
Connect To Next Controller,MiniLink PD Or System Manager
On Local Loop
G - Fan ON/OFF Only
R - 24VAC
Relay Output Dry ContactsR2 Thru R5 May Be User ConfiguredFor The Following:1 - Heating (Aux. Heating)Stages2 - Cooling (Compressor) Stages3 - Warm-up Mode Command For Boxes4 - Reversing Valve (Air To Air Heat Pumps)5 - Gas Reheat Control For Dehumidification6 - Exhaust Fan Interlock7 - Preheat Coil8 - Alarm Relay9 - Override10 - Occupied11 - Economizer
Note: Up To 16 More Relays Are Available ByAdding Relay Expansion Boards. AllExpansion Board Relay Outputs Are UserConfigurable As Listed Above.
3
2
1
EconomizerActuator
(Belimo Shown)Consult Factory ForOther ManufacturersWiring Connections
Connect Tubing To High PressurePort (Bottom Tube) and Route To StaticPressure Pickup Probe Located In UnitDischarge. Leave Port Marked “Lo” OpenTo Atmosphere
S.P.Transducer
Splice If Req’d
Connect ToExpansion BoardBase (When Used)
Not UsedJumper MustBe In 0-5V PositionAs Shown
RLY
1
D1
D2
D3
D4
D5
RAM
C3
C2
U6
PH
ILIP
S
CX6
C1
CX2U2
PAL
CX4
U4
TUC-5R PLUS
YS101816 REV. 2
V1
V2
V3
V5
V4
TB2
4
NETWORK
TOKEN
16
32
8
SW1
ADD
2
1
ADDRESS
V6
PO
WE
R
GND
24VAC
L1
D1
6
R6
C9
SC1
R11
U11
MC34064A
D1
3
C16
9936
VR2
TB4
R2
7
C13
R1
0
VR1
C1
9
C1
8
NE5090NPB31920PS
U8
CX
8
U9
X1
R7
D1
0
R13D12
C7CX10
U10
CX12
U12
U14
CX14
PJ3
PJ2
PJ1
EXPANSION
PRESSURESENSOR
T'STAT
C17D15
R26
C20 R25
R24
R22
U15
CX13
U13
C15
R19
R15
C14
D1
8
D1
7
PU1
PU2
PU3
PU4
PU5
PU7
D6
D7
D8
D9
D11
D14
C12
C10
0-5
VD
C
0-1
VD
C
JP1
C11
X2
GNDTB3
INPUTS
GND
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AOUT1
AOUT2
AIN7
RN
4
1
RN5
RS-485
CX5
U5
R
TB1
SHLD
T
COMM
COMM
RN
3
1
RN1
U1
CX1
1
LD6
COMM
PWRLD7
LED1
LED2
LD9
LD8
R1
U7
RV1
VREF ADJ R28
+VREF
5.11V
TEST POINT
EWDOG
D19
RN
2
1
COM1-3
COM4-5
R5
R4
R3
R2
R1
RLY
2R
LY
3R
LY
4R
LY
5
CX15
(1 MEG)HH
P1
C2
1
CX
3
EPROM
U3
+
Supply FanVariable Frequency Drive
(By Others)
_
VFD 0-10VDC Input
GND
The VFD Unit Must BeConfigured For 0-10VDCInput. The Input ResistanceAt The VFD Must Not BeLess Than 1000 Ohms WhenMeasured At The VFDTerminals With All InputWires Removed.
Warning:24 VAC Must Be Connected So That All GroundWires Remain Common. Failure To Do So WillResult In Damage To The Controllers.
T to TR to R
SHLD to SHLD
Size Transformer ForCorrect Total Load. WMVAVController = 8 VA PowerConsumption. If EconomizerOption Is UsedThe Economizer ActuatorVA load Must Also BeConsidered When SizingThe Transformer.
Component & System Wiring 19
WMVAV Controller Addressing
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
2 of 2
4
NETWORK
TOKEN
16
32
8
SW1
ADD
2
1
ADDRESS
V6
PO
WE
R
GND
24VAC
L1
D1
6
R6
C9
SC1
R11
U11
D1
3
C16
VR2
TB4
R2
7
C13
R1
0
VR1
C1
9
C1
8
R7
D1
0
R13D12
C7CX10
U10
CX12
U12
U14
CX14
PJ3
PJ2
PJ1
EXPANSION
PRESSURESENSOR
C17D15
R26
C20 R25
R24
R22
U15
CX13
U13
C15
R19
R15
C14
D1
8
D1
7
PU1
PU2
PU3
PU4
PU5
PU7
D6
D7
D8
D9
D11
D14
C12
C10 0-5
VD
C
0-1
VD
C
JP1
C11
X2
GNDTB3
INPUTS
GND
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AOUT1
AOUT2
AIN7
RN5
D19
CX15
1632TOKEN
NETWORK
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Should BeIn The OFF PositionAs Shown
Note:The Power To The Controller Must Be Removed AndReconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect.
CautionDisconnect All Communication Loop Wiring From TheController Before Removing Power From The Controller.Reconnect Power And Then Reconnect CommunicationLoop Wiring.
ADDRESS ADD
ADDRESSADD
ADDRESSADD
The Address For Each ControllerMust Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
WMVAV Controller
05/12/04
VAV-WMVAVWIR1A.CDR
Component & System Wiring20
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
05/12/04
VAV-SpaceTempWire1.CDR
Space Temperature Sensor To1
GND
TMP
Space Temperature Sensor
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
NORMAL
OVR
RELO
C
REMR
O
AW
AUX (See Note)
Note:If The Slide Adjust Option Is Used OnThe Room Sensor The AUX TerminalMust Be Wired To AIN7. The Fan ProofOf Flow Switch, Which NormallyConnects To AIN7, Is Not Available ForUse When The Slide Adjust Option IsUsed.
Fan Proof OfFlow Switch(See Note)
WMVAV Controller Board
Space Temperature Sensor InformationThe Space Temperature Sensor is typically used for constant volume HVACunit applications controlling one zone. The Space Temperature Sensor is a10K Type III thermistor sensor. The Space Temperature Sensor should bemounted approximately 5 ft. above the floor in the space that is to becontrolled. The Space Temperature Sensor is available in a sensor only,sensor with override button, sensor with slide adjust and sensor with slideadjust and override configurations. If the Space Temperature Sensor withSlide Adjust option is to be used, the Fan Proof of Flow Switch cannot beused.
Space Sensor Wiring
Component & System Wiring 21
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
03/24/04
VAV-SupRetTempWire1.CDR
Supply & Return Air Temperature Sensor To1
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
Mount In HVACUnit Supply
Air Duct
Mount In HVACUnit Return
Air Duct
SupplyAir Temperature
Sensor
ReturnAir Temperature
Sensor
WMVAV Controller Board
Supply & Return Sensor InformationThe Supply and Return Air Temperature Sensors must be wired as shown in theillustration below for proper operation. The Supply and Return Air TemperatureSensors are 10K Type III thermistor sensors. The Supply Air Temperature Sensorshould be mounted in the unit discharge plenum or in the supply air duct. The ReturnAir Temperature Sensor should be mounted in the return air duct. If the system has abypass damper installed, be sure the return air sensor is located upstream of thebypass duct connection.
Supply & Return Sensor Wiring
Component & System Wiring22
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
05/12/04
VAV-OATempWire1.CDR
Outside Air Temperature Sensor To1
Outside AirTemperature SensorThe Outside Air Sensor must be wired as shown in the illustration above for properoperation. The Outside Air Temperature Sensor is a 10K Type III thermistor sensor.The sensor should be mounted in the upright position as shown, in an area that isprotected from the elements and direct sunlight. Be sure to make the wiring splicesinside of the OutsideAir Temperature Sensor weathertight enclosure.
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
OutdoorAir Temperature
Sensor
WMVAV Controller
Make Splice ConnectionsInside Sensor EnclosureAs Shown.
Caution: Be sure to mount the Outside Air Sensor in an area that is not exposed to direct sunlight. A
shaded area under the eve of the building or under the HVAC unit rainhood is normally a good
location. If sensor is not located as specified, erroneous outside air temperature readings will
result. Unused conduit opening(s) must have closure plugs installed and must be coated with a
sealing compound to provide raintight seal. Water can damage sensor!
Outside Air Sensor Wiring
Component & System Wiring 23
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
03/24/04
VAV-RemoteOccConWire1.CDR
Remote Occupied Contact To1
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
WMVAV Controller Board
Note:If Remote Occupied Contact Is RequiredWhen Humidity Sensor Is Used, TheRemote Occupied Contact Must BeRelocated To AIN2 On The 4 Analog Input1 Analog Output Expansion Board. SeeExpansion Board Wiring For DetailedWiring.
Remote OccupiedContact
(Relay By Others)
Remote Occupied Contact To WMVAV Wiring
Component & System Wiring24
4-2
0m
A4
-20
mA
VA
Cor
DC
VA
Cor
DC
GN
DG
ND
0-5
Vo
r0
-10
V0
-5V
or
0-1
0V
44
445566
ONON
ONON
33
33
22
22
11
11
ZeroZero
SpanSpan
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
02/21/08
VAV-HumidSensorWire1B.CDR
Humidity Sensor To1
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
OutdoorAir Humidity
Sensor - 4-20mA
WMVAV Controller Board
250 OhmResistor
(Shipped With Sensor)To be Installed Between
AIN5 and GND
Note:If Remote Occupied Contact IsRequired When HumiditySensor Is Used, The RemoteOccupied Contact Must BeRelocated To AIN2 On The 4Analog Input 1 Analog OutputExpansion Board.
The Pull-up Resistor (PU5)Must Be RemovedWhen Using A 4-20ma Device
Warning:
It is very important to be certain that all wiring
is correct as shown in the wiring diagram
below. Failure to observe the correct polarity
will result in damage to the Humidity Sensor or
controller.
Humidity Sensor Wiring
Component & System Wiring 25
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
03/24/04
VAV-SupplyVFDWR1.CDR
Supply Fan VFD To1
+
Supply FanVariable Frequency Drive
(By Others)
_
VFD 0-10VDC Input
GND
The VFD Unit Must Be Configured For 0-10VDC Input. TheInput Resistance At The VFD Must Not Be Less Than 1000Ohms When Measured At The VFD Terminals With AllInput Wires Removed.
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
WMVAV Unit Controller BoardCaution:
Variable Frequency Drive Units Can Cause Large
Transient Noise Spikes Which Can Cause
Interference To Be Propagated On Other
Electronic Equipment. Use Shielded Wire
Wherever Possible And Route All
Sensor/controller Wiring Away From The Variable
Frequency Drive And The Air Handling Unit
Electrical Wiring.
Supply Fan VFD Wiring
Component & System Wiring26
Bypass Damper Actuator Wiring
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
WMVAV Controller Wiring
JOB NAME
02/20/08
VAV-BypassActuatorWire1B.CDR
Bypass Damper Actuator To1
GND
INPUTS
GNDAOUT1
AOUT2
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AIN7
WMVAV Unit Controller Board
Transformer - 8 VA Minimum
OE281-04 Bypass Damper Actuator
10
1
1
2
2
3
1
0
3
Set Rotation Switch To Correct DamperOperating Rotation. StandardWattMaster Rotation IsCounterclockwise To Open (1) AsShown.
LINE24 VAC
GND
� Y�
Component & System Wiring 27
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
03/24/04
VAV-2SlotExpBase.CDR
2 Slot Expansion Base Board1 of 1
VR5
MC
7824CT
C6
TB2
VR3
7805ACT
R1
4
VR2
D3
7824CT
MC MC
VR4
7812CT
MC
GND
+24VDC-OUT
GND
24VAC-IN
TB1
CX3
R13PWRLD1
C1
PJ2
R11
C2 C3
U1
PJ1
R9
R7D2D1 R8
P1
R1CX1
R2
R3
JP1
2SLO
TM
OD
ULA
RI/O
2SLO
TM
OD
ULA
RI/O
VR6
7824CT
MC
LM3
58
N
YS1
01
78
0
C4 C5
U2
VR1
R12
R6
CX2R10
R4
R5
P2 JP2
Connect To Unit Controller Board
Transformer Load = 10VA
WARNING!!Observe Polarity! All boards must be wired with
GND-to-GND and 24VAC-to-24VAC.Failure to observe polarity will result in damageto one or more of the boards. Expansion Boardsmust be wired in such a way that power to both
the expansion boards and thecontroller are always powered together. Loss of
power to the expansion board will cause thecontroller to become inoperative until power is
restored to the expansion board.
Line Voltage
24VAC
GND
Jumpers Must Be SetAccording To Type OfExpansion Board UsedSee Expansion BoardSpecific Wiring ForJumper Settings
2 Slot Expansion Base Board Wiring
Component & System Wiring28
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications. FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
03/24/04
VAV-OE353-4SLOTEXP.CDR
OE353 - 4 Slot Expansion Base Board1
Connect To Unit Controller Board
Transformer Load = 14VA
WARNING!!Observe Polarity! All boards must be wired with
GND-to-GND and 24VAC-to-24VAC.Failure to observe polarity will result in damageto one or more of the boards. Expansion Boardsmust be wired in such a way that power to both
the expansion boards and thecontroller are always powered together. Loss of
power to the expansion board will cause thecontroller to become inoperative until power is
restored to the expansion board.
Line Voltage24VAC
GND
Jumpers Must Be SetAccording To Type OfExpansion Board UsedSee Expansion BoardSpecific Wiring ForJumper Settings
JP2
VR2
7824CT
R2
0
C8
TB2
D3
VR4
7812CT
VR3
7805ACT
VR5 VR6
7824CT7824CT
C1
PWRLD1
24VAC-IN
GND
GND
TB1R19
PJ2
+24VDC-OUT
R17
PJ1
R15 D1
D2 LM
35
8N
P8
2B7
15
P
C3C2
CX3
U1
C4 C5
U2
R3
R1
4
R1
3
CX1
R2
R1
P1 JP1
CX2
P2
7824CT
VR7
7824CT
4 SLOT MODULAR I/O BD.
VR8
YS101782
C6
R5R4 R6
P3
R9R8R7
JP3
C7
VR1
R18
R1
1
R16
R1
0
P4 JP4
R1
2
4 Slot Expansion Base Board Wiring
Component & System Wiring 29
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
03/24/04
VAV-OE354-4ANALOGIN1OUT.CDR
OE354 - 4 Analog Input 1 Analog Output Expansion Board1 of 3
Mount Expansion Board To Either The OE352 2 SlotOr OE353 4 Slot Expansion Base Board
JO3
JO4
JO2
JO1
CX
2
R10
AOUT1
AIN4
TB1
GND
AIN2
AIN3
AIN1
PU4
U2
D5
Q1
R8
R9
LM358
C5
C1
R7
R6
R5
PU3
C4
C3
C2
PU2
PU1
4 ANALOG IN MOD. I/O BD.
R3
PC
F8
59
1P
YS101784
D4
R4
D3
D1
D2
R2
R1 CX1
U1
P1
Jumper On = 0-10VDC Input Setting
For Proper Operation Pullup Resitors PU1,PU3 & PU4 Must Be Removed As Shown
Voltage Is Selectable For AIN1 Only
Jumper Must Be Off For AIN2 & 4Jumper Must Be ON For AIN3
Jumper Off = 0-5 VDC Input Setting
Output #3 - Relief Fan VFD Signal (0-10VDC)
Input #12 - Relief Pressure Sensor
Input #11 - Carbon Dioxide Sensor
Input #10 - Remote Occupied Contact
Input #9 - Supply Setpoint Reset
Analog Inputs
Analog Output
4 Analog Input 1 Analog Output Expansion Board Overview
Input #9 - Supply Setpoint Reset - Wiring
JO3
JO4
JO2
JO1
CX
2
R10
AOUT1
AIN4
TB1
GND
AIN2
AIN3
AIN1
+
PU4
U2
D5
Q1
R8
R9
LM358
C5
C1
R7
R6
R5
PU3
C4
C3
C2
PU2
PU1
4 ANALOG IN MOD. I/O BD.
R3
PC
F8
59
1P
YS101784
D4
R4
D3
D1
D2
R2
R1 CX1
U1
P1
Jumper J01 Must Be OnAs Shown For0-10VDC Operation
Jumper J01 Must Be RemovedFor 0-5VDC Operation
Pullup Resistor PU1 Must BeRemoved For Proper Operation
Other Device That IsSupplying Reset Signal
_
Supply Setpoint ResetSignal0-5VDC or 0-10VDC
GND
Address JumpersLocated On BaseBoard UnderExpansion Board
Ed
ge
of
Base
Bo
ard
4 Analog Input 1 Analog Output Expansion Board Wiring
Component & System Wiring30
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
OE354 - 4 Analog Input 1 Analog Output Expansion Board2 of 3
Input #11 - Carbon Dioxide Sensor - Wiring
Input #10 - Remote Occupied Contact - Wiring
JO3
JO3
JO4
JO4
JO2
JO2
JO1
JO1
CX
2C
X2
R10
R10
AOUT1
AOUT1
AIN4
AIN4
TB1
TB1
GND
GND
AIN2
AIN2
AIN3
AIN3
AIN1
AIN1
PU4
PU4
U2
U2
D5
D5
Q1
Q1
R8
R8
R9
R9
LM358
LM358
C5
C5
C1
C1
R7
R7
R6
R6
R5
R5
PU3
PU3
C4
C4
C3
C3
C2
C2
PU2
PU2
PU1
PU1
4 ANALOG IN MOD. I/O BD.
4 ANALOG IN MOD. I/O BD.
R3
R3PC
F8
59
1P
PC
F8
59
1P
YS101784
YS101784
D4
D4
R4
R4
D3
D3
D1
D1
D2
D2
R2
R2
R1
R1
CX1
CX1
U1
U1
P1
P1
Normally OpenDry Contact(By Others)
Input #10 - Remote Occupied Contact
Jumper Must Be Off For AIN2
Pullup Resistor PU2 Must BeInstalled
Pullup Resistor PU3 Must BeRemoved As Shown
CO Sensor
(0-10VDC Signal)2
1. -N
ot Used
2. -N
ot Used
4. Relay
Com
mon
5. Relay
Norm
Closed
6. 4-20mA
Output
3. Relay
Norm
Open
7.S
ign
al Gro
un
d8. 0-10V
Ou
tpu
t
Pin
Designations
Pin
Designations
1. AC
+/D
C+
2. AC
/GN
D
24V
AC
Line Voltage
GN
D
Warning:24 VAC Must Be Connected So That All GroundWires Remain Common. Failure To Do So WillResult In Damage To The Controllers.
Jumper J03 Must Be OnAs Shown For CO Sensor
With 0-10VDC SignalIf
Be Removed
2
CO Sensor With 0-5VDC
Signal Is Used It Must2
VAV/CAV Unit Controller Board
24VAC
GND
03/24/04
VAV-OE354-4ANALOGIN1OUT.CDR
4 Analog Input 1 Analog Output Expansion Board Wiring (Cont’d)
Component & System Wiring 31
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
OE354 - 4 Analog Input 1 Analog Output Expansion Board3 of 3
EXPANSION
SENSORPRESSURE
GND
7AIN
AOUT2
AOUT1
AIN
GND
GND5
AIN
AIN
AIN
4
3
2
AIN1
+VDC
INPUTS
HIG
H
LO
W
-+
+ +
VAV/CAV Unit Controller Board
Building Pressure Sensor
Tubing To BuildingPressure Sensing Location
Tubing To AtmosphericPressure Sensing Location
-
+
Jumper J04 Must Be OffAs Shown For Proper0-5VDC Operation
Warning:24 VAC Must Be Connected So That All GroundWires Remain Common. Failure To Do So WillResult In Damage To The Controllers.
Input #12 - Relief Pressure Sensor - Wiring
Output #3 - Relief Fan VFD Signal - Wiring
JO3
JO3
JO4
JO4
JO2
JO2
JO1
JO1
CX
2
CX
2
R10
R10
AOUT1
AOUT1
AIN4
AIN4
TB1
TB1
GND
GND
AIN2
AIN2
AIN3
AIN3
AIN1
AIN1
PU4
PU4
U2
U2
D5
D5
Q1
Q1
R8
R8
R9
R9
LM358
LM358
C5
C5
C1
C1
R7
R7
R6
R6
R5
R5
PU3
PU3
C4
C4
C3
C3
C2
C2
PU2
PU2
PU1
PU1
4 ANALOG IN MOD. I/O BD.
4 ANALOG IN MOD. I/O BD.
R3
R3
PC
F8
59
1P
PC
F8
59
1P
YS101784
YS101784
D4
D4
R4
R4
D3
D3
D1
D1
D2
D2
R2
R2
R1
R1
CX1
CX1
U1
U1
P1
P1
Pullup Resistor PU4 Must BeRemoved
+
Relief Fan Variable Frequency Drive(By Others)
_
VFD 0-10VDC Input
GND
Warning:The VFD Unit Must Be configured for 0-10VDC input.The input resistance at the VFD must not be less than1000 ohms when measured at the VFD terminals withall input wires removed. Higher voltages or lowerresistance will cause improper operation and couldresult in damage to circuit boards
03/24/04
VAV-OE354-4ANALOGIN1OUT.CDR
4 Analog Input 1 Analog Output Expansion Board Wiring (Cont’d)
Component & System Wiring32
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
03/24/04
VAV-OE356-4BINARYINPUT.CDR
OE356 4 Binary Input Expansion Board1 of 1
4 Binary Input Expansion Board
24VoltPowerOnly
Mount Expansion Board To Either The OE352 2 SlotOr OE353 4 Slot Expansion Base Board
R4
R3
R2
R1
YS101788
BIN 4BIN 4
BIN 3BIN 3
BIN 2BIN 2
BIN 1BIN 1
COM
TB1
OPTO2
R10
R12
4 DIG. IN MOD. I/O BD.4 DIG. IN MOD. I/O BD.
P2
50
6-2
R8
R6
R5
P2
50
6-2
OPTO1
74
HC
14
N
PC
F8
57
4P
U2C4
C3
U1
CX2
C2
C1 CX1
P1
OE265-06 Humidistat
Dirty Filter
Remote Forced Heat Mode
Remote Forced Cool Mode
Relay Contacts(By Others)
Address JumpersLocated On BaseBoard UnderExpansion Board
Ed
ge
of
Base
Bo
ard
RD
4 Binary Input Expansion Board Wiring
Component & System Wiring 33
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
05/12/04
VAV-OE357-4RELAYOUT.CDR
OE357 4 Relay Output Expansion Board1 of 1
Relay Output Dry ContactsR6 Through R21 May Be User Configured For TheFollowing:
Not UsedHeating (Aux. Heating)StagesCooling (Compressor) StagesWarm-up Mode Command For BoxesReversing Valve (Air To Air Heat Pumps)Gas Reheat Control For DehumidificationExhaust Fan InterlockPreheat Coil
Configure Relays By Utilizing The System Manager,Modular Service Tool or Prism Computer Front EndSoftware.
Alarm RelayOverrideOccupiedEconomizer
4 Relay Output Expansion Board
UL5A250VAC
G5L-114P-PSOMRON
CONTACT:24VDC
UL5A250VAC
G5L-114P-PSOMRON
CONTACT:24VDC
UL5A250VAC
G5L-114P-PSOMRON
CONTACT:24VDC
UL5A250VAC
G5L-114P-PSOMRON
CONTACT:24VDC
K3
K2
4RLY IO BD.4RLY IO BD.
V4 K4 YS101790
TB1
V1
K1
K3
U2
K4
RN1
PCF8574P
U3
CX3
U1
ULN2803A/ ULN2803A/
K2
K174HC04N
P1
CX
2
CX
1
Relays 6-9
Relays 10-13
Relays 14-17
Relays 18-21
Address JumpersLocated On BaseBoard UnderExpansion Board
Typical Wiring For RelayOutputs - 6 Through 21
R1
R2
R3
R4
24VoltPower Mount Expansion Board To Either The OE352 2 Slot
Or OE353 4 Slot Expansion Base Board
Note:All Circuit Board Contacts Are N.O.All Contacts Are Rated For 2 Amps @24VAC Pilot Duty OnlyDo Not Apply Any Voltage Greater Than24VAC
�
�
�
Pilot Duty Relays(By Others)
Ed
ge
of
Base
Bo
ard
Ed
ge
of
Base
Bo
ard
Ed
ge
of
Base
Bo
ard
Ed
ge
of
Base
Bo
ard
4 Relay Output Expansion Board Wiring
Component & System Wiring34
Component & System Wiring 35
VAVBOX Controller
Diagrams
Component & System Wiring36
C O N T R O L S
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
VAVBOX Controller
See Note 1
R
SH
T
R
SH
T
R
SH
T
R
SH
T
All Comm Loop Wiring IsStraight Thru
Required VA For TransformerEach VAVBOX Controller = 6 VA Min.
(Includes Actuator)
24VAC
GND
GND
AUX
TMP
NORMAL
OVR
RELO
C
REMR
O
AW
1632TOKENNET
8421
Caution!VAVBOX Controllers Must Have Address Switches SetBetween 1 And 58
Room Sensor
Diagnostic Blink Code LED
VAVBOX Damper Actuator
Local LoopRS-485
9600 Baud
Airflow Sensor (Optional)Only Used For PressureIndependent Applications
Connect ToNext VAVBOX
ControllerAnd/Or WMVAV
Controller OnLocal Loop
Address Switch Shown IsSet For Address 9
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
Switches Labeled 32 AndToken Should Be In TheOFF Position As Shown
Note:The Power To The VAVBOX Controller Must BeRemoved And Reconnected After Changing TheAddress Switch Settings In Order For Any ChangesTo Take Effect.
Caution:Disconnect All Communication Loop WiringFrom The VAVBOX Controller Before Removing PowerFrom The VAVBOX Controller. Reconnect Power AndThen Reconnect Communication Loop Wiring.
ADDRESS ADD
ADDRESSADD
ADDRESSADD
Connection To AUXTerminal Required OnlyWhen Sensor Is SpecifiedWith Slide Adjust Option
JOB NAME
05/12/04
VAV-VAVBOXWire1.CDR
WattMaster VAV System
10
SHIELDR
T
HiLo
Airflow
Notes:
3.)The Supply Air Sensor is not required when the VAVBOX Controllers areconnected with WMVAV Unit Controller boards. A global supply airtemperature is broadcast by the one of the WMVAV Unit Controllers. TheSupply Air Sensor is only required if the VAVBOX Controller is required tooperate as a “Stand Alone” controller.
1.) All wiring to be in accordance with local and national electrical codesand specifications.
2.) All communication wiring to be 2 conductor twisted pair with shield.Use Belden #82760 or equivalent.
The Address For Each ControllerMust Be Between 1 And 58 And Be
Unique To The Other ControllersOn The Local Loop
1 of 1
(See Note 3)
CX4
R2
8 R24
78
24
GND
R1
7
R1
6
U7
PO
WE
R
R26
YS
10
15
62
RE
V.
3
24VAC
D4
VR
1
L1
C7
D3S
CA
NR2
1
RE
C
C6
R1
4
CX10
U11
COMM
C1
5
R25
SW
1
U1
0 1632
TOKEN
NET
4
8
2
1 U6
ADDRESS
EW
DO
G
C11
R2
0
R1
9
ADD
VR
EF
AD
J
T'STAT
R32
D6
C1
4C
13
R2
7
C8
R23
C1
0
P.U.
R22
CX9
C9
U9
U8
D5
RN
1
AIRFLOW
R3
4
R1
8
CX8U4
R1
5
Q3
D2
K2
V2
PJ2
R1
00
R1
2
R11
Q2
D1
K1
R9
R1
3 V1
AC
TU
AT
OR
C4
R8
CX
6
C5
C3
PJ1
CX
5
R6R7
R5
R4
C2
EX
PA
NS
ION
CX2
PA
L
X1
C1
EPROM
R1
R2R3
U2
Q1
CX1U3
CX3
U1
P.U.
O I
D7
R33
U5
P.U.
48
5D
R V
C16
V3
R3
5
PJ3
OF
F
VAVBOX Controller Wiring
Component & System Wiring 37
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted by Others
24VAC
COM
24 VAC Transformer Supplied& Wired by Others. Size ForRequired Contactor(s) Load.
Notes:
1.) All Wiring to be in Accordance With Local & National Electrical Codes& Specifications.
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
09/26/06
OE322 - 3 Relay -1 Analog Output Board1 of 3
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted by Others
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
24VAC
COM
Fan Relay
R1
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted & Wired by Others
24VAC
COM
C1
C1
Fan Relay
R1
1st Stage Heat Contactor
1st Stage Heat Contactor
2nd Stage Heat Contactor
2nd Stage Heat Contactor
3rd Stage Heat Contactor
3rd Stage Heat Contactor
C2
C2
C3
C3
Typical Wiring forSingle Duct Terminalwith Electric Heat
Typical Wiring forFan Terminal Unitwith Cooling Only
Typical Wiring forFan Terminal Unitwith Electric Heat
Note: 3 Stage Heating is Attained by Sizing All 3Heating Elements For Equal KW Output. EachElement Should be Sized for 1/3 of the Total KWOutput Required. To Achieve 3 Stage Heating theSystem would be Configured to EnergizeContactor C1 for First Stage Heat. For 2nd StageHeat the System Would be Configured to De-energize Contactor C1 and Energize Contactor C2& C3. For 3rd Stage Heat the System Would beConfigured to Leave Contactor C2 & C3 Energizedand also Energize Contactor C1.
Note: 3 Stage Heating is Attained by Sizing All 3 HeatingElements For Equal KW Output. Each Element Should beSized for 1/3 of the Total KW Output Required. To Achieve 3Stage Heating the System would be Configured to EnergizeContactor C1 for First Stage Heat. For 2nd Stage Heat theSystem Would be Configured to De-energize Contactor C1and Energize Contactor C2 & C3. For 3rd Stage Heat theSystem Would be Configured to Leave Contactor C2 & C3Energized and also Energize Contactor C1.
24 VAC Contactor(s)Supplied & InstalledBy Others. 2 AmpMax. Load Each.
24 VAC FanRelay &Contactor(s)Supplied &Installed ByOthers. 2Amp Max.Load Each.
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
24 VAC Transformer Supplied& Wired by Others. Size ForRequired Fan Relay Load.
24 VAC Transformer Supplied &Wired by Others. Size For RequiredFan Relay & Contactor(s) Load.
24 VAC Fan RelaySupplied & InstalledBy Others. 2 AmpMax. Load.
VAV-OE322-3RELAY1OUTBD.CDR
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
3 Relay Output Expansion Board Wiring
Component & System Wiring38
Notes:
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
Typical Wiring ForSingle Duct TerminalWith Modulating HotWater Heat
Typical Wiring ForFan Terminal UnitWith ModulatingHot Water Heat
OE322 - 3 Relay -1 Analog Output Board2 of 3
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted & Wired by Others
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted & Wired by Others
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
24 VAC Transformer Supplied &Wired by Others. Size For RequiredFan Relay Load.
24VAC
COM
Fan Relay
24 VAC Fan Relay Supplied andInstalled by Others. 2 Amp Max.Load For Fan Relay.
R1
HWV
HWV
0-10 VDC ModulatingHot Water Valve Supplied & Installed by Others
0-10 VDC ModulatingHot Water Valve Supplied & Installed by Others
0-10 VDC Signal
0-10 VDC Signal
Supply PowerOf Required Voltage
To Valve Motor(By Others)
24 VDC Power Only(12 Watts Max.)
Is Available From TB3Terminals (+V & GND)
Supply PowerOf Required Voltage
To Valve Motor(By Others)
24 VDC Power Only(12 Watts Max.)
Is Available From TB3Terminals (+V & GND)
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
09/26/06
1.) All Wiring to be in Accordance With Local & National Electrical Codes& Specifications.
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
VAV-OE322-3RELAY1OUTBD.CDR
3 Relay Output Expansion Board Wiring (Cont’d)
Component & System Wiring 39
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
OE322 - 3 Relay -1 Analog Output Board3 of 3
Typical Wiring forSingle Duct TerminalWith 2 Position HW Valve
Typical Wiring forFan TerminalWith 2 Position HW Valve
09/26/06
Notes:
1.) All Wiring to be in Accordance With Local & National Electrical Codes& Specifications.
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
Q3
R6
R3
R10
Q2
R9
R5
R2
Q1
R8
R4
R1
R7
D1
PJ1
C2C4
VR
2
C6
C1 U1
RLY3
D2
2RLY
D3
1RLY
D4
K1 2RAOUT BD.
YS101714REV. 3
V4
V3
K2
K3
V1C5
R12
R11
R13
VR1
R14
TB1 GND
OUTV5 +ANALOG
+V
GND
TB3
3
COM
1
2
TB2
LM358
C3
V2
7824C
T
M
IO S
ER
IAL
#
Q4
24VAC
24VAC
COM
COM
Fan Relay
24 VAC HW Valve Supplied andInstalled by Others. 2 Amp Max. Load.
24 VAC Fan Relay and HW Valve Supplied and Installed byOthers. 2 Amp Max. Load Each For HW Valve and Fan Relay.
24 VAC - Transformer Suppliedand Installed by Others. Size ForRequired HW Valve Load.
24 VAC - Transformer Suppliedand Installed by Others. Size ForRequired Fan Relay and HWValve Load.
HWV
R1
HWV
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
WattMaster Part # BK000047Snaptrack Supplied by WattMasterMounted by Others. Remove ControlBoard from Snaptrack & Mount Snaptrack on Box
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted & Wired by Others
WattMaster Part #OE322Relay Expansion Boardw/ Modular CableSupplied by WattMasterMounted & Wired by Others
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
Connect To VAVBOX ControllerUsing Modular Cable SuppliedBy WattMaster
VAV-OE322-3RELAY1OUTBD.CDR
3 Relay Output Expansion Board Wiring (Cont’d)
Component & System Wiring40
Component & System Wiring 41
Communication Devices
Diagrams
Component & System Wiring42
Use Supplied ModularCable With Stripped EndsFor Connection To TerminalBlock And Transformer
Modular System ManagerBack of Front Cover
P1
P2
VAR1
U1
3
RS-485PCOMM
R14
U6
V62C518256L-70P
CX
11
CX
12
U12
U11
CX7
PAL
EPRO
MRA
M
CX
13
75176
U8
74HC573
CX
8
RN1
SC1
YS101830PREV.YS101830PREV.2PMODULARPSYSTEM2PMODULARPSYSTEMMANAGER
PC
B8
0C
55
2-5
-16
WPP4
42
86
0=
2/5
PC
B8
0C
55
2-5
-16
WPP4
42
86
0=
2/5
PD
fD9
72
2V7
YPD
fD9
72
2V7
YC2
U7
X1
C1
R1
R4
EW
DO
G
PH
ILIPS
X2
C3
PH
ILIPS
PH
ILIPS
U3
CX5
R3
R9
85
83
CX6
D3
U424
C1
28
CX4
74HC259
U1
U2
CX
2
R3
R2
U14
C8
CX
9
C7
47
0uF5
0v
10
00
uF1
0v
47
0uF5
0v
47
0uF5
0v
10
00
uF1
0v
R12
R11
CO
MM
OU
TC
OM
MO
UT
CO
MM
INC
OM
MIN
D6
C4
R13
MC
34
06
4A
U9
99
36
D5
L1
U1
0
74HC540
CX
14
C6
P3
CX10
C5
74
HC
92
3
R10
D4
CX
3
82B715
PJ1
D2
R6
R5
D1
U3
DSPY1
R7
RV1
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)RED (24 VAC)
BROWN (GND)
GREEN (GND)
Class 2 TransformerRated For 6 VA Minimum
Controller Board
TSHLDR
05/12/04
FILENAME
DATE:B. CrewsB. Light
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
VAV-SYSTEMMGRWIRE1A.CDR
OE392 Modular System Manager1 of 2
Notes:
1.) All wiring to be in accordance with local and national electrical codesand specifications.
System Manager Wiring Schematic For Using The Pigtail
See Page 2 of this Diagram for Additional Pigtail Wiring Details
System Manager Modular Cable Pigtail - Wiring Schematic
Component & System Wiring 43
Notes:
1.) All wiring to be in accordance with local and national electrical codesand specifications.
FILENAME
DATE:
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
OE392 Modular System Manager2 of 2
Modular System ManagerBack of Front Cover
P1
P2
VAR1
U1
3
RS-485PCOMM
R14
U6
V62C518256L-70P
CX
11
CX
11
CX
12
U12
U11
CX7
PAL
EPRO
MRA
M
CX
13
75176
U8
74HC573
CX
8
RN1
SC1
YS101830PREV.YS101830PREV.2PMODULARPSYSTEMMANAGERMANAGER
PC
B8
0C
55
2-5
-16
WPP4
42
86
0=
2/5
PC
B8
0C
55
2-5
-16
WPP4
42
86
0=
2/5
PD
fD9
72
2V7
YPD
fD9
72
2V7
YC2
U7
X1
C1
R1
R4
EW
DO
G
PH
ILIPS
X2
C3
PH
ILIPS
PH
ILIPS
U3
CX5
R3
R9
85
83
CX6
D3
U424
C1
28
24
C1
28
CX4
74HC259
U1
U2
CX
2
R3
R2
U14
C8
CX
9
C7
47
0uF5
0v
47
0uF5
0v
10
00
uF1
0v
10
00
uF1
0v
47
0uF5
0v
47
0uF5
0v
10
00
uF1
0v
10
00
uF1
0v
R12
R11
CO
MM
OU
TC
OM
MO
UT
CO
MM
INC
OM
MIN
D6
C4
R13
MC
34
06
4A
MC
34
06
4A
U9
99
36
D5
L1
U1
0
74HC540
CX
14
C6
P3
CX10
C5
74
HC
92
3
R10
D4
CX
3
82B715
PJ1
D2
R6
R5
D1
U3
DSPY1
R7
RV1
Class 2 TransformerRated For 6 VA Minimum
(By Others)
Handy Box , Conduit,Fittings, Wire Nuts,Butt Splices Etc.,
( By Others)
Controller Board
TSHLDR
HZ000121Modular Pigtail CableSupplied With System Manager
WH
ITE
(T)
BLA
CK
(R)
RED(2
4 VAC)
BROWN
(GND)
GR
EE
N(G
ND
)
Drain Wire (Shld)
LINEVOLTAGE
LINE VOLTAGE
2-Conductor Shielded18-GuageCommunications Wire
B. CrewsB. Light
System Manager Wiring Details For Using The Pigtail
See Page 1 of this Diagram for Pigtail Wiring Schematic
VAV-SYSTEMMGRWIRE1A.CDR
05/12/04
System Manager Modular Cable Pigtail - Wiring Detail
Component & System Wiring44
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Connection Diagram
JOB NAME
02/11/04
G-ModServiceTool1A.CDR
OE391 Modular Service Tool1 of 1
Typical Controller Board
Connector Cable
Modular Service Tool
Female DIN Connector
T Block Baseerminal
(Remove Terminal Block)
PL101904 Adapter Board
Optional Connection ForControllers Without DIN Connector
Male DIN Connector
Mode
Selection
ENTER
CLEARESC
PREV NEXT
DOWN
UP
654
DEC
7
0
8
1 32
9
MINUS-
STATUS
SETPOINTS
SCHEDULES
CONFIGURATION
ALARMS
ON
OVERRIDES
BALANCE - TEST
Be Sure The Modular ServiceTool Is Connected To TheSupplied Power Pack Or HasFresh Batteries Installed BeforeAttempting Programming Of TheController. Be Sure The Power IsTurned Off On The ModularService Tool Before ConnectingThe Cable To The Controller.
The Modular Service Tool Can Be Connected To MostControllers By Plugging One End Of The SuppliedCable Into the Modular Service Tool DIN ConnectorAnd The Other End Into The DIN Connector On TheControllers.
Some Controllers Without DIN Connectors RequireUse Of The Supplied PL101904 Adapter Board ShownAbove. To Connect With Adapter Board, First UnplugCOMM Terminal Block From Controller Board. PlugPL101904 Adapter Board Terminal End Into TerminalBlock Base On Controller. Plug DIN Connector CableInto DIN Connector On PL101904 Adapter Board . SeeOptional Connection For Controllers Without DINConnector Above For Illustration Of This Connection.
Power On Button
TSHLDR
COMM
Modular Service Tool Connections
Component & System Wiring 45
Connect To Remote Link .Remote Link Is Part # OE419-04
Only
Commlink II Communications Interface
(Jumper Set For Multiple Loop)
Caution: Use The “Molded Cable” ToConnect To The Computer (DCE) Connector.This Cable Is Only To Be Used To ConnectFrom The CommLink (DTE) Connection To TheRemote Link (When Used).
Do Not
Caution:Disconnect All Communication Loop WiringFrom The CommLink Before Removing PowerFrom The CommLink. Reconnect Power And ThenReconnect Communication Loop Wiring.
Use 25 Pin Or 9 Pin Connector AsRequired By Available Serial (COM) PortOn Computer.
JOB NAME
Caution: Use The “25 Pin Or 9 Pin Cable” ToConnect To The Remote Link (DTE) Connector. ThisCable Is Only To Be Used To Connect From TheCommLink (DCE) Connection To The Computer
Serial Port (COM) Connection.
Do Not
(When Used) Note:Place Jumper BetweenPins 1 & 2 for MultipleLoop Applications &Between Pins 2 & 3 forSingle Loop ApplicationsSee Note 4.
COMM DRIVER CHIP( U1 )
EPROM CHIP
PIN 1
MULTI
SINGLE
12
3
CommLink Jumper Switch Settings
4 Piece ComputerCable Kit.Part # HZ000112Supplied WithCommLink
FILENAME
B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
CommLink II Wiring1
02/11/04
G-CommLinkWire.CDR
OE361-04
Notes:
DATE:
R
SH
T
R
SH
T
R
SH
T
R
SH
T
All Communication LoopWiring Is Straight Through
Connect To First Device On Loop. SeeSystem Application Documentation For
Your Specific Systems ControllerConnection & Wiring Information
RS-48519200 Baud
Line Voltage
See Note 1
24VAC
Required VA For TransformerCommLink = 14VA Max.
CommLink Is Supplied With 110/24VAC Power Supply.If Desired A Transformer (By Others)
May Be Wired To The CommLink Instead
Molded Modem Cable.Part #HZ000098
Supplied With CommLink
(DTE)REMOTE LINKREMOTE LINK
485 LOOP485 LOOP
COMPUTER(DCE)
GT R
G2
V4
DN
POWER
9P
inF
em
ale
9 PinFemale
25 PinFemale
9P
inF
em
ale
120/24 VacTransformer
Part # PX000015
25 PinMale
Part #OE361-04
Connect Supplied RJ12 Modular Phone CableTo Supplied 9 Pin Or 25 Pin Connector As ReqdBy Your Computer Com Port Connection
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.
3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent.
4.)CommLink Is Usually Shipped With TheJumper In The Multiple LoopConfiguration. Check The ApplicationDocumentation For Your Specific SystemFor Correct Jumper Position Setting.
CommLink II Wiring & Cabling Connections
Component & System Wiring46
No
tes
:
1.)
All
Wirin
gTo
Be
InA
ccord
ance
With
LocalA
nd
NationalE
lectr
icalC
odes
And
Specific
ations.
2.)
All
Com
munic
ation
Wirin
gTo
Be
2C
onducto
rTw
iste
dP
air
With
Shie
ld.
Use
Beld
en
#82760
Or
Equiv
ale
nt.
Co
mp
on
en
tW
irin
gD
iag
ram
03
/24
/04
VA
V-M
iniL
inkP
olD
evW
r1A
.CD
R
Min
iLin
kP
olli
ng
De
vic
e1
of
1
Min
iLin
kP
oll
ing
De
vic
e Co
mm
Lin
kTerm
inals
On
lyF
irst
Min
iLin
kP
DTo
Be
Co
nn
ecte
dTo
Co
mm
Lin
k,
Oth
erw
ise
Co
nn
ect
Min
iLin
kP
DTo
Ne
two
rkTe
rmin
als
Of
Pre
vio
us
Or
Ne
xt
Min
iLin
kP
DO
nL
oo
p
24
VA
CC
lass
2Tra
nsfo
rmer
Ra
ted
Fo
r6
VA
Lo
ad
Min
imu
m
No
tU
sed
To
WM
VA
VC
on
tro
lle
rTe
rmin
als
Min
iLin
kP
DN
etw
ork
Te
rmin
als
Co
nn
ect
Min
iLin
kP
DTo
Ne
two
rkTe
rmin
als
Of
Pre
vio
us
Or
Ne
xt
Min
iLin
kP
DO
nL
oo
p.
EP
RO
M
U3
U5
RA
M
CX2
1
U2
R1
C3
U4
CX
3
CX
4
YS
101818P
552
PR
OC
ES
SO
RP
BO
AR
D
CX
5C
1
U1
R2
CX
1
CX
6
WD
OG
U6
PH
ILIP
S
D1
P1
X1
C2
C4
0-1
0V
4-2
0m
A
TH
ER
M
R27
R31
D4
GNDGND
24VAC24VAC
TB1
D5
C11
U1
2
LE
D2
PO
WE
R
V1
R25
R26
C7
CX15
CX13
PR
OC
.D
RIV
ER
LO
OP
DR
IVE
R
LO
CA
LLO
OP
GND
AIN2
AIN1
+5V
TB2
P4
OF
F=
0-5
VAIN
2A
IN1
0-1
0V
4-2
0m
A
TH
ER
M
TB3
U15
LD
5LD
6
U13
C8
LE
D1RV
1
R4VREF
CX2
U11
YS
10
19
00
PM
INIL
INK
PO
LL
ING
DE
VIC
ER
EV
.1
OF
F
12481632
CX14
NE
TW
OR
KD
RIV
ER
RN
3
SHLD
SHLD
SH
LD
SHLD
T
TG
T
T
T
TB4
R R485
LO
OP
R
R
R
U14
NE
TW
OR
KLO
OP
P5
ADD
P3
R24
LD
4
C9
U1
0
RN
2
SW
1R3
0
X2
R2
9
R2
8
C1
0
U6
CX6CX1
U7
U1
X1
C3
C1
R3
CX
7
Lin
eV
oltage
16
328421
Addre
ss
Sw
itch
Show
nIs
SetF
orA
ddre
ss
1A
ddre
ss
Sw
itch
Show
nIs
SetF
orA
ddre
ss
13
Contr
olle
rA
ddre
ss
Sw
itch
This
Sw
itch
Should
Be
InT
he
OF
FP
ositio
nA
sS
how
n
No
te:
The
Pow
er
To
The
Min
iLin
kP
DM
ustB
eR
em
oved
And
Reconnecte
dA
fter
Changin
gT
he
Addre
ss
Sw
itch
Settin
gs
InO
rder
ForA
ny
Changes
To
Take
Effect.
Cau
tio
nD
isco
nn
ectA
llC
om
mu
nic
atio
nL
oo
pW
irin
gF
rom
Th
eM
iniL
ink
PD
Be
fore
Re
mo
vin
gP
ow
er
Fro
mT
he
Min
iLin
kP
D.
Re
co
nn
ect
Po
we
rA
nd
Th
en
Re
co
nn
ect
Co
mm
un
ica
tio
nL
oo
pW
irin
g.
AD
D
ADD
ADD
The
Addre
ss
For
Each
Min
iLin
kP
DM
ustB
eU
niq
ue
To
The
Oth
er
Min
iLin
kP
Ds
On
The
LocalLoop
And
Be
Betw
een
1and
60
FIL
EN
AM
E
DA
TE
:B
.C
rew
s
DE
SC
RIP
TIO
N:
PA
GE
DR
AW
NB
Y:
JO
BN
AM
E
Com
munic
ation
Wirin
gTo
Be
Wired
Tto
T,S
HL
D(G
)to
SH
LD
(G)
&R
toR 3.)
All
Co
mm
un
icati
on
Wir
ing
To
Be
2C
on
du
cto
rTw
iste
dP
air
Wit
hS
hie
ld.U
se
Beld
en
#82760
Or
Eq
uiv
ale
nt.
MiniLink Polling Device Wiring Using Wire Terminals
Component & System Wiring 47
C O N T R O L S
FILENAME
DATE: 08/20/03 B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
OE299
RS-232 to USB Converter1
JOB NAME
USB-RS232Cnvrt1A.CDR
Top View
End View
Connection Detail
Features & Specifications
Packages Includes
:
:
Converts a USB port into a 9-pin male RS-232 serial port capable ofspeeds up to 115 Kbps.The USB Serial Adapter is designed to make serial port expansionquick and simple.Installs as a standard Windows COM port,Full RS-232 modem control signals,RS-232 data signals; TxD, RxD, RTS, CTS, DSR, DTR, DCD, RI,GNDSelf Powered by USB portSupports Windows 98/SE, ME & 2000 and XP
USB-232 Converter cable with short 12inch USB Type A endInstallation InstructionsUSB Driver CD for win98/ME/2K/XP
Installing the USB adapter
Changing the COM ports:
Follow the instructions provided inside the USB Serial Adapterpackage for installation and driver setup of the USB Serial Adapter.A CD-ROM is included that contains the correct drivers.
To change the COM port to a different COM port is accomplishedby changing the COM port I/O range in the Windows DeviceManager.
Right-click on "My Computer"Click the "Device Manager" tab.Click the "+" by "Ports"Select "USB to Serial Port (COM5)"Click the "Properties" buttonClick the "Resources" Tab.Uncheck the box that says "Use automatic settings".Select the "Input/Output range"Click the "Change Settings " button.Click the little arrows until you find an appropriate setting."02E8-02EF" should give you a COM4 setting after you restart thecomputer.Make sure to click "OK" on all screens.Use the following settings to get the following COM ports:COM1 - 3F8h-03FFhCOM2 - 2F8h-02FFhCOM3 - 3E8h-03EFhCOM4 - 2E8h-02EFh
24
V
T G R GN
D
REMOTE LINK(DTE)
COMPUTER(DCE)
48
5L
OO
P
PO
WE
R
SERIAL #
Connect ToUSB PortOn Computer
CommLink
Cable Length = 12 inches
USB SerialAdapter
Connect 9 Pin SerialCable Supplied WithCommLink To USBSerial Adapter As Shown
9 Pin Serial CableAssembly Supplied WithCommLink
Connect 9 Pin SerialCable Supplied WithCommLink To PortLabeled “Computer (DCE)On CommLink As Shown
9 PinFemale
9P
inF
em
ale
RS-232 Serial Port To USB Port Converter
Component & System Wiring48
Component & System Wiring 49
Add-On Devices Diagrams
Component & System Wiring50
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Using Standard Lighting Relays
JOB NAME
05/12/04
W-LightingPnlStd1.CDR
OE310 Lighting Panel Controller Wiring1
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
4.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
Local Loop RS-485Communications To OtherControllers On The Local
LoopNote:
All Circuit Board Contacts Are N.O.All Contacts Are Rated For 2 Amps @24VAC Pilot Duty OnlyDo Not Apply Any Voltage Greater Than24VAC
�
�
�
EP
RO
M
RA
M
PAL
PIN 1PIN 1
PIN 1PIN 1
CPU
+V
+V
1
3
45678GG
2
ANALOGINPUTS
GN
D
SIG
+5
V
ANALOGOUTPUTS
A1A2
G
T
SH
R
GND
24VAC
Lighting Panel Controller
Light Circuit 1
Light Circuit 2
Light Circuit 3
Light Circuit 4
Light Circuit 5
Light Circuit 6
Light Circuit 7
T
SHR
K1
K2
K3
K4
K5
K6
K7
Light Sensor (Optional)
Momentary Pushbuttons(Optional)
Override Circuit #1
Override Circuit #2
Override Circuit #5
Override Circuit #3
Override Circuit #6
Override Circuit #4
Override Circuit #7
Line Voltage
Line Voltage
See Note 1
16 8 4 2 1
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
These Switches Should BeIn The OFF PositionAs Shown
AD
D
ADDADD
The Address For Each ControllerMust Be Unique To The Other Controllers
On The Local Loop
Required VA For TransformerEach Controller = 10 VA Min.
C1
C2
C3
C4
C5
C6
C7
Lighting Contactors OrPilot Duty Relays(By Others)
All Lighting ContactorsMust Be Wired For N.C.Operation So That SystemFails To Lights On Mode.
Caution: If Lighting Contactor Coil CurrentDraw Is More Than 2 Amps And/Or DoesNot Use A 24VAC Coil, A Pilot Duty RelayThat Has A Current Draw Of Less Than 2Amps @ 24VAC Must Be Used To EnergizeThe Lighting Contactor. A SeparateTransformer Rated For The Total LightingContactor(s)Or Pilot Relay Current DrawMust Always Be Used To Power The Circuit.
24V
GND
Note:Set-up, Programming And Monitoring Of The LightingPanel Controller Requires The Use Of A PersonalComputer And Prism Software.
Caution!Controller Must Have Address Switch Set Between 1 And 60
C O N T R O L S
Lighting Panel Wiring For Standard Lighting Contactors
Component & System Wiring 51
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Using GE Latching Relays
JOB NAME
05/12/04
W-LightingPnl-GE1.CDR
OE310 Lighting Panel Controller Wiring1
Note:Set-up, ProgrammingAnd Monitoring OfThe Lighting PanelController RequiresThe Use Of APersonal ComputerAnd PrismSoftware.
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
4.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
Local Loop RS-485Communications To OtherControllers On The Local
Loop
Ribbon Connector
Relay Expansion Board
Ground
24V
All switches(1 thru 4)must be in the“ON” position
EP
RO
M
RA
M
PAL
PIN 1PIN 1
PIN 1PIN 1
CPU
+V
+V
1
3
45678GG
2
ANALOGINPUTS
GN
D
SIG
+5
V
ANALOGOUTPUTS
A1A2
G
T
SH
R
GND
24VAC
Lighting Panel Controller
Light Circuit 1
Light Circuit 2
Light Circuit 1
Light Circuit 2
Light Circuit 3
Light Circuit 3
Light Circuit 4
Light Circuit 4
Light Circuit 5
Light Circuit 5
Light Circuit 6
Light Circuit 6
Light Circuit 7
Light Circuit 7
T
SHR
ON
OFF
24VAC
GE Lighting Relay- Circuit #1(By Others)
Typical Wiring Shown For Circuit #1All Other Circuits Are To Be WiredIdentically. Up to 7 Lighting Circuits MayBe Wired To Each Lighting Panel Controller.
K1
R1
R2
R3
R4
R5
R6
R7
R8
K2
K3
K4
K5
K6
K7
Light Sensor(Optional)
See Note 1
Line Voltage
Line Voltage
16 8 4 2 1
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
These Switches Should BeIn The OFF PositionAs Shown
AD
D
ADDADD
The Address For Each ControllerMust Be Unique To The Other Controllers
On The Local Loop
Required VA For TransformerEach Controller = 10 VA Min..
Momentary Pushbuttons(Optional)
Override Circuit #1
Override Circuit #2
Override Circuit #5
Override Circuit #3
Override Circuit #6
Override Circuit #4
Override Circuit #7
Caution: If Lighting Contactor Coil Current Draw Is More Than 2Amps And/Or Does Not Use A 24VAC Coil, A Pilot Duty RelayThat Has A Current Draw Of Less Than 2 Amps @ 24VAC MustBe Used To Energize The Lighting Contactor. A SeparateTransformer Rated For The Total Lighting Contactor(s) Or PilotRelay Current Draw Must Always Be Used To Power The Circuit.
Note:All Circuit BoardContacts Are N.O.All Contacts AreRated For 2 Amps@ 24VAC PilotDuty OnlyDo Not Apply AnyVoltage GreaterThan 24VAC
�
�
�
Caution!Controller Must Have Address Switch Set Between 1 And 60
C O N T R O L S
Lighting Panel Wiring For GE® Latching Relay Lighting Contactors
Component & System Wiring52
FILENAME
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Component Wiring
JOB NAME
05/12/04
WM-OptStartSched1.CDR
OE310 Optimal Start Scheduler1
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
4.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
Note:All Circuit Board Contacts Are N.O.All Contacts Are Rated For 2 Amps @24VAC Pilot Duty OnlyDo Not Apply Any Voltage Greater Than24VAC
�
�
�
Equipment Circuit 1
Equipment Circuit 2
Equipment Circuit 3
Equipment Circuit 4
Equipment Circuit 5
Equipment Circuit 6
Equipment Circuit 7
Line Voltage
C1
C2
C3
C4
C5
C6
C7
Equipment Contactors OrPilot Duty Relays(By Others)
Caution: If Equipment Contactor CoilCurrent Draw Is More Than 2 Amps And/OrDoes Not Use A 24VAC Coil, A Pilot DutyRelay That Has A Current Draw Of LessThan 2 Amps @ 24VAC Must Be Used ToEnergize The Equipment Contactor. ASeparate Transformer Rated For The TotalPilot Relay Current Draw Must Always BeUsed To Power The Circuit.
24V
GND
Note:Set-up, Programming And Monitoring Of The OptimalStart Scheduler Requires The Use Of A PersonalComputer And Prism Software.
Local Loop RS-485Communications To OtherControllers On The Local
Loop
EP
RO
M
RA
M
PAL
PIN 1PIN 1
PIN 1PIN 1
CPU
+V
+V
1
3
45678GG
2
ANALOGINPUTS
GN
D
SIG
+5
V
ANALOGOUTPUTS
A1A2
G
T
SH
R
GND
24VAC
Optimal Start Scheduler
T
SHR
K1
K2
K3
K4
K5
K6
K7
Momentary Pushbuttons(Optional)Direct Control Of Equipment
(Optional)Override Circuit Schedule #1
Override Circuit Schedule #2
Override Circuit Schedule #3
Override Circuit Schedule #4
Override Circuit Schedule #5
Override Circuit Schedule #6
Override Circuit Schedule #7
Line Voltage
See Note 1
16 8 4 2 1
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
These Switches Should BeIn The OFF PositionAs Shown
AD
D
ADDADD
The Address For Each ControllerMust Be Unique To The Other Controllers
On The Local Loop
Required VA For TransformerEach Controller = 10 VA Min.
Caution!Controller Must Have Address Switches Set Between 1 And 60
C O N T R O L S
Optimal Start Scheduler Wiring
Component & System Wiring 53
DATE: B. Crews
DESCRIPTION:PAGE
DRAWN BY:
Controller Wiring
JOB NAME
05/12/04
W-GPC-Control1.CDR
OE330 GPC1
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
4.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
Relay Output(s) ToDevice(s) AsRequiredBy Application
Analog Input(s)And/Or DigitalInput(s) FromDevicesAs Required ByApplication
Analog OutputTo Device (WhenUsed)(0-10 VDC)
Notes:
GPC Controller
Caution!GPC Controllers Must Have Address Switches SetBetween 1 And 60.
Note:The Power To The GPC Controller Must BeRemoved And Reconnected After Changing TheAddress Switch Settings In Order For Any ChangesTo Take Effect.
Caution:Disconnect All Communication Loop WiringFrom The GPC Controller Before Removing PowerFrom The GPC Controller. Reconnect Power AndThen Reconnect Communication Loop Wiring.
Note:Set-up, Programming And Monitoring Of The GeneralPurpose Controller Requires The Use Of A PersonalComputer And Prism Software.
12V
LIN
EV
OLTA
GE
AIN1
2
3
4
5
GND
GND
AIN
AIN
AIN
AIN
RELAYOUTPUT
COM1-3
OUT
OUT1
2
COM4-5
OUT
OUT
OUT
3
4
5
24VAC 24VAC
GNDGND
PWR
COMM
TT
SHLDSHLD
LD4
REC.
AOUT
4-5
OUT
COMM
TEST
32K
8K
RAM EPROM
ADDRESS ADD
PRESSURESENSOR
485COMM
RR
YS101564
EW
DO
G
0-5
VD
C
0-1
VD
C
PU1
PU2
PU3
PU4
PU5
GPC Controller Address Switch Setting
Local Loop9600 Baud
See Note 1
16
8421
Caution!GPC Controller Must Have Address Switch Set Between 1 And 60
Address Switch Shown IsSet For Address 9
Address Switch Shown IsSet For Address 28
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
These Switches Should BeIn The OFF PositionAs Shown
ADDRESS ADD
ADDRESSADD
ADDRESSADD
Required VA ForTransformer = 8 VA Min.
C O N T R O L S
GPC Wiring
Component & System Wiring54
Note:Set-up, ProgrammingAnd Monitoring OfThe GPC-17Controller RequiresThe Use Of APersonal ComputerAnd Prism Software.
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
4.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
Local Loop RS-485Communications To Other
ControllersAnd/Or System Manager
Ribbon Connector
OptionalAnalogOutputBoard
Ground
24V
All switches(1 thru 4)must be in the“ON” position
EP
RO
M
RA
M
PAL
PIN 1PIN 1
PIN 1PIN 1
CPU
+V
+V
1
3
45678GG
2
ANALOGINPUTS
GN
D
SIG
+5V
ANALOGOUTPUTS
A1A2
G
T
SH
R
GND
24VAC
GPC-17 Controller
T
SHR
K1
R1
R2
R3
R4
R5
R6
R7
R8
K2
K3
K4
K5
K6
K7
Line Voltage
Line Voltage
See Note 1
16 8 4 2 1
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
This Switch Must BeIn The ON PositionAs Shown
These Switches Should BeIn The OFF PositionAs Shown
AD
D
ADDADD
The Address For Each ControllerMust Be Unique To The Other Controllers
On The Local Loop
Required VA For TransformerEach Controller = 10 VA Min.
Note:All Circuit BoardContacts Are N.O.All Contacts AreRated For 2 Amps@ 24VAC PilotDuty OnlyDo Not Apply AnyVoltage GreaterThan 24VAC
�
�
�
Caution!Controller Must Have Address Switch Set Between 1 and 60
24
VC
OM
ANALOG OUT1
ANALOG OUT2
WA
TT
MA
ST
ER
AN
AL
OG
OU
TP
UT
BO
AR
DY
S1
01
42
8R
EV
.1
AD
DR
+
-
+
-
12
LD
1
PWR
ANALOG OUT3
ANALOG OUT4
+
-
+
-
RN1
Optional Relay Expansion Board
Relay OutputsTo Devices AsRequiredBy Application
Analog Inputs And/OrDigital InputsFrom Devices AsRequired ByApplication
RelayOutputs toDevicesAsRequiredByApplication
Analog OutputTo Device(0-10 VDC)
FILENAME
DATE:
DESCRIPTION:PAGE
DRAWN BY:
GPC-17 Controller1
JOB NAME
W-GPC-17CNTRL1A.CDR
OE310-21-GPC
B. Crews05/12/04
C O N T R O L S
Ribbon Connector
GPC-17 Wiring
Component & System Wiring 55
Miscellaneous Diagrams
& Technical Information
Component & System Wiring56
Over Voltage Board Wiring
C O N T R O L S
FILENAME
DATE:
DESCRIPTION:PAGE
DRAWN BY:
1
JOB NAME
03/24/04
VAV-OE268-OVBoard.cdr
OE-268 Over Voltage Board
Barry Light
HV POWER BD.YS101750
REV 1.0
C2
+
+
R3D1
U1R2AC_IN GND
TB1INPUT
24-32VAC C3
D2
R1
+V GND
TB2POWEROUTPUT
This output is DC voltage. Ourcontrollers will accept DC voltageif the voltage is above 28 VDC.
Note:
NOTE: This board goes between the supply transformerslow voltage output and the controllers low voltage input.WattMaster Controllers do not like to see more than28 VAC on their input side. When the line voltage to thetransformer is too high, generally the output side of thetransformer (low voltage) is too high, thus requiring thisOver Voltage Board.
To the 24 VAC input sideof WattMaster ControllerTRANSFORMER
LINE VOLTAGE
OE-268 Over Voltage Board
This board is designed to power onecontroller with expansion boards only.
Warning
Component & System Wiring 57
Chip Locations
C2
GND
R7
MADE IN U.S.A.
YS101693 REV 3
CX10
CR2
RN
1
C11
SERIAL NUMBER
Y2
C10
C12
WD
OG
CX7
R1
2
R11
U7
JO
3R1
3
U6
C5
U8
R9CX8
R1
6
R1
5
R1
4
CO
MP
LO
OP
D1
MO
DE
M
D2 D3
CX9U9
U10
R10
C4
SH
LD
C1
L1
VA
R1
CR
1
J1
R3
R4
GNDCOMM
J01
TE
RM
RS
-48
5
TB1
24VAC R1
TB2
R
COMPUTER P
DCE PORT
P
U1
CX5
R5
CX1
R2
P1
CX
2
U2
R6
C3
P2T
MODEL
GND
TP1
CX11U11
JO
4
C7
SINGLE
MULTI
C8
C9
C6
Y1
MODEM P
DTE PORT
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
JOB NAME
VAV-DRCHPREP.CDR
MG392System Manager
MG331-21-VAVWMVAV Controller
Comm Driver Chip(U1) Pin 1
Comm Driver Chip(U10) Pin 1
Comm Driver Chip(U5) Pin 1
RAM Chip(U2) Pin 1
EPROM Chip(U3) Pin 1
PAL Chip(U4) Pin 1
EPROM Chip(U11) Pin 1
Single/MultiLoop Jumper
(J04)
EPROM Chip(U3) Pin 1
OE361-04 Commlink II
MG320 - VAVVAVBOX Controller
Comm Driver Chip(U13) Pin 1
RAM Chip(U12) Pin 1
EPROM Chip(U11) Pin 1
PAL Chip(U7) Pin 1
PAL Chip(U1) Pin 1
Warning!Use Extreme Caution When Removing Any ChipsTo Avoid Damaging Any Circuit Board Traces WhichAre Under The Chip.
Be Sure That Any Small Screwdriver Or OtherSharp Object Used To Remove The Chip Does NotCome Into Contact With The Printed Circuit BoardSurface.
A Small Screwdriver May Be Inserted Between TheChip And The Socket To Aid In Removal Of The Chip.
Be Very Careful Not To Insert The Screwdriver UnderThe Socket!! Damage To The Board Is Not CoveredBy Warranty.
RS-485PCOMM
R14 U14
CX
11
EP
RO
M
CX
12
U12
U11
RA
M
CX7
PA
L
U8
CX
8
RN1
C2
C1
EW
DO
G
U7
X1
X2
C3
U3
CX5
R3
YS101830PREV.2MODULARSYSTEM MANAGER
R4
R1
U1
U6
U9
CX
13
U13
VAR1
C7
P2
SC1
P1 CO
MM
OU
T
D6
CO
MM
IN
R11
R12
CX
9
C8
CX
14
C6
R13
C4
L1
D5
CX10
C5 U
10
D4
R10
CX
3CX4
CX6
R9
D3
U4
PJ1
U2
CX
2 R2
R3
U3
D1
D2
R5
R6
DSPY1
P3
R7
RV1
1 of 3Chip Replacement Information
WattMaster VAV Components
RLY
1
D1
D2
D3
D4
D5
CX
3
RAM EPROM
C3
C2
U6
PH
ILIP
S
CX6
C1
CX2U2
U3
PAL
CX4
U4
TUC-5R PLUS
YS101816 REV. 2
V1
V2
V3
V5
V4
TB2
4
NETWORK
TOKEN
16
32
8
SW1
ADD
2
1
ADDRESS
V6
PO
WE
R
GND
24VAC
L1
D16
R6
C9
SC1
R11
U11
MC34064A
D13
C16
9936
VR2
7824CT
M
TB4
R27
C13
R10
VR1
C19
C18
NE5090NPB31920PS
U8
CX
8
U9
X1
R7
D10
R13D12
C7CX10
U10
CX12
U12
U14
CX14
PJ3
PJ2
PJ1
EXPANSION
PRESSURESENSOR
T'STAT
C17D15
R26
C20 R25
R24
R22
U15
CX13
U13
C15
R19
R15
C14
D18
D17
PU1
PU2
PU3
PU4
PU5
PU7
D6
D7
D8
D9
D11
D14
C12
C10
0-5
VD
C
0-1
VD
C
JP1
C11
X2
GNDTB3
INPUTS
GND
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AOUT1
AOUT2
AIN7
RN
4
1
RN5
RS-485
CX5
U5
R
TB1
SHLD
T
COMM
COMM
RN
3
1
RN1
U1
CX1
1
LD6
COMM
PWRLD7
LED1
LED2
LD9
LD8
R1
U7
RV1
VREF ADJ R28
+VREF
5.11V
TEST POINT
EWDOG
D19
RN
2
1
COM1-3
COM4-5
R5
R4
R3
R2
R1
RLY
2R
LY
3R
LY
4R
LY
5
CX15
(1 MEG)HH
P1
C2
1
05/12/04
CX6
SW1
U10
75176
EXPANSION
Q3Q2
D3
VR17824
GN
D
24
VA
C
M
78
24
C
T
MC
34
0
99
36
R17
R16
U7
C7
R15
POWER R21
REV. 2
YS101562
D4
R2
6
LD
3
L1
SC
AN
RE
C
R12
C6
R11
TO
KE
N
NE
T
LD2
32
R14
R13
R100
LD1
C5
D1
K1
V2
G5
L-1
14
P-P
S
24
VD
C
CO
NTA
CT:
UL
/C
SA
5A
25
0V
AC
K2
D2
ACTUATOR
G5
L-1
14
P-P
S
24
VD
C
CO
NTA
CT:
UL
/C
SA
5A
25
0V
AC
R10
R9
PJ2
V1C4
74HC573N
B31920PS
9936
MS6264L-70PC
EP
RO
M
VREF
ADJ
R2
3
C10
PCB80C552-5-16WP
500650=1/3
DFD9940SM
PHILIPS
EWDOG
COMM
D7
CX
10
R2
5
R28
T'S
TA
T
U11C15
R20
C11R2
4
8 16
2 4
AD
DR
ES
S
AD
D
1
U6
93C46
U5
R19
PHILIPS
U9
CX
9
R3
2
D5
C14
P.U
.
R2
2
C13
LMC662
R27
D5
RA
M
C9
C8
80C
55
2
CX5PJ1
C3R8
R7
R5
R6
R4
C2C1
X1
74HC259
B31920PS
U2
R1
R2
R3
CX
2
Q1
16
L8
32K
R34
FL
OW
U8
1RN
1
CX
8U
4
R18
CX
48
KRA
M
U3
CX
3
U1
CX
1
Component & System Wiring58
Chip Locations (Cont’d)
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
Chip Replacement Information
JOB NAME
OE330 - GPC Controller
MG391Service Tool
MG364-22 - MiniLink Polling Device
OE310 - GPC-17 Controller,Lighting Controller, OSS Scheduler
Comm Driver Chip(U5 ) Pin 1
ProcessorComm Driver Chip
(U15) Pin 1
Local LoopComm Driver Chip
(U13) Pin 1
Network LoopComm Driver Chip
(U14) Pin 1
Comm Driver Chip(U3) Pin 1
Comm DriverChip
(U1) Pin 1
RAM Chip(U3) Pin 1
Polling DeviceRAM Chip(U4) Pin 1
RAM Chip(U11) Pin 1
EPROMChip(U2) Pin 1
Polling DeviceEPROM Chip
(U3) Pin 1
EPROMChip(U10) Pin 1
EPROM Chip(U10) Pin 1
PAL Chip(U4) Pin 1
Polling DevicePAL Chip(U2) Pin 1
MiniLinkEPROM Chip
(U6) Pin 1
PAL Chip(U6) Pin 1
PAL Chip(U6) Pin 1
D1
D2
D3
D4
D5
CX3
C13
C1
2
80C552
CX7
C2
CX2U2 U3 CX4
U4
V1
V2
V3
TB2
SW1
ADDADDRESS
V6
PO
WE
R
GND
24VAC
L1
D2
1
R37
C20
SC1
U1
2
VR2
TB1
R39
R3
6
VR1
C19
C17
U8
CX8
X1
CX9
U9
PRESSURE
SENSOR
R21
U11
0-5
VD
C
0-1
VD
CJP
1
TB3
INPUTS
GND
GND
12V
AIN1
AIN2
AIN3
AIN4
AIN5
AOUT
485
CX5
U5
R
TB4
SHLD
T
COMM
COMM
RN
1 U1
CX1
REC.
U6
R11
COM
OUT
COM
Q1R1
R2
R3
R4
R5D6
R7
R6Q3
Q2
C3
R8
PU1
R6
D7C4
D8C5
D9
R13
D10
PU2
PU3
D11
R15
D12
R17
PU4
C6
C7D13
R19
PU5
C8
D14
D15
D16
R20
YS101564
REV.4
TUC-5R
U7
R2
9R
30
K1
K2
1-3
32K8K
RAM
PA
L4-5
V4
V5
1
2
3
4
5
OUT
OUT
OUT
OUT
K3
K4
K5
COMM
TEST
X2
C14
CX10
C16
R31
D1
9
R3
2
R3
3R
34
1.2
1K
PWR
D17
R2
2R
23
R2
4
R2
5
CX
11
C9
C10
R38
C21
C18
R26
R27
R28
D1
8
EW
DO
G
C22
C11
D2
0
SERIAL#
1
2
4
8
16
32
NET
D2
2
U1
0
CLK
RV1
C2
VR
EF
R4
CX
2
LED 1
U1
CX
1
P2
CX
6
U6
CX7
U7
R3
C1
X1
C3
CX
10 U10
RN2
YS101900MINILINK
POLLINGDEVICEREV. 1
U11CX
11
R2
4
RN3
C9 C10
X2
R28
R29
R30
AD
D
P5
P3
LD4
U1
4
NETWORKLOOP
LOCAL LOOP
NETWORKDRIVER
LOOPDRIVER
PROC.DRIVER
CX
14
CX
13
U1
3
U1
5
CX
15
P4
LD5
T SH
LD
RT SH
LD
R
THERM
4-20mA
0-10V
THERM
4-20mA
0-10V
AIN1 AIN2
OFF=0-5V
AIN
1
AIN
2
GN
D
TB
3
TB
4
SW1
24
VA
C
GN
D
R R
V1
C8C7
R2
7
D5C11
TB
2
TB
1
LED 2
R3
5
VR2
C1
3
UL LABEL
SERIAL #
1 2 4 8 16
32
C12
D4
R31
+2
4V
DC LD6
POWER
EPROM
EPROM
U3
U5
RAM
CX
2
U2
R1
C3
U4
CX3CX4
YS101818P552
PROCESSORBOARD
CX5C1
U1
R2
CX1
CX6
WDOG
U6
D1
P1
X1
C2
C4
+
+
PAL
1
C21U5W
DO
G
P3
U13
U5
V8
C27
R63
VR
3
VR
2 C26 R42
R41
R62
C30
TB4
REC
OUT1
C29 U
16
BA
TT
EW
DO
G
C32
24V
R58
CX
14
D33
C28
C31
P3
GN
D
D34
R61
PWR
SC
1
R44
U14
R46
D25
R45
R40
Q2
Q3
C21
JO
4
JO
5
R43
C22
CX
17
U17
L1
R60
U15
R59
LED DISPLAY
V1
P2
C25
X2
C24
C23
R49
R50
U9
R36
R35
R34
R47
SE
NS
OR
JA
CK
+5V
SERIAL #
R33
PR
ES
SU
RE
SIG
GN
D
7
ANALOG
+V
+V
1
2
3
4
5
6
8
G
G
INPUTS
R14
C34
T.P
.
5.1
1V
PU
PJ1
D5
D3
D1
D7
CX
5C
33
Q4
+ R31
Q5
R10
R8
R9
R7
C4
C3
PU
PU
R12
R11
R13
C6
C5
PU
D9
D15
D13
D11
R32ADJ
5.11V
R39
R38
R37
R65
VR
1
C16C17 R18 PU
R16
R15
R17
C8
C7
PU
R20
R21
R19
C10
PU
C9
TB1
D19
TB
5T
B6
TB
7T
B8
TB
9
OUT2
OUT3
OUT4
OUT5
K3
R51
R52
K1
V2
D26
K2
V3
D27
OUT1
CX13
R48
OUT2
R53
R54
K4
V4
D28
V5
K5
D29
OUT3
OUT4
JO
3R
64
TB
11
TB
10
OUT6
OUT7
R57
D32
SW
1
R55
R56
V6
K6
D30
V7
K7
D31
D24
D23
D22
OUT5
U12
OUT6
D21
D20
OUT7
AC B 16 8 4
G
A2
A1
ANALOG
OUTPUTS
U10
X1
U11RAM
C18
EPROM
C19
YS
101560
JO1
R22
RE
V.4
THERM 8
PU
CX1
32K
8K
C20
CX
10
R24
U1
R23 RN1
R25
U2
R1
TB2
EXP
SH
C2
C15
CX
3
AD
DC
X12
RN2
D17
D18
C13
C14
C12
CX
6
U6
R29
CX2
R6
R27
C11 R
28
R30
Q1
U7
ABC
TERM
JO2U3
R26
2 1
T
C1
P1
COMM
R
TB3
BUSS
2 of 3
9V
SC1
C7
D5
D7
R10
R11
R12
R13
U12
Q1
C6R9
L1 B1 B2
D9C8
D8
R8
D4
D6
D1
P2
R5
R6
D2
U8
CX8
U6
R4
R3
U11X2
C5
CX
4
SERIAL #
CX
10
R7
D3
CX11
U10
CX7
U7
SYSM HAND HELDYS101890REV 2
EP
RO
M
C3
C4
U9
CX9
PA
L
U4
RN1
CONT.
RV1
P3
P1
14
85
DR
IVE
R
U1
CX1
R1
Display Must Be RemovedTo Access Driver Chip
VAV-DRCHPREP.CDR
05/12/04
WattMaster VAV Components
Component & System Wiring 59
Chip Installation Procedures
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
JOB NAME
3 of 3
Small FlatheadScrewdriver
Chip
Chip
Printed CircuitBoard
Printed CircuitBoard
Printed CircuitBoard
Chip
WARNING!
Direction Of Pull
Notch
Dot
Pin1
Be sure the chip you have selected to replace is asocketed chip. Not all driver chips on the boardsare field replaceable. Only socketed chips may beremoved and replaced in the field. All other chipsthat are not socketed will require sending the boardto the WattMaster factory for repair.
Once you have determined that thechip needing replacement is indeed a socketed chipplease proceed in the following manner.
Remove the communications loop connector andthen the 24VAC power connector on the controllerbefore attempting to change any components.
will occur if components are removed orinstalled with power applied.
If you are unsure how to safely remove the chip orabout the correct pin placement, please consult thefactory before proceeding.
Use extreme care to avoid inserting the screwdriveror I.C. Puller under the socket. You must insert the tipof the screwdriver or ends of the I.C. Puller betweenthe body of the chip and the chip socket.
Each chip be installed with Pin 1 in the correctlocation. Installing the chip “backwards” will in mostcases destroy the device when power is reapplied.
Pin 1 can be located by looking for the notch in the endof the chip. Pin 1 on "some" chips is identified with a dot.
Be certain that pins are lined up in the socketbefore pressing the chip in. Failure to properly lineup the pins will result in damage to the chip.This is a common error -
Only after confirming that the chip has been correctlyinstalled with Pin 1 in the proper position and that thepins are lined up and none are bent or out of the socket,should communication or power wiring be reconnectedto the board. Tp prevent possible damage alwaysreconnect the power wiring first and then thecommunication wiring.
If you try toremove a chip that is not socketed it will destroythe circuit board.
DAMAGE
Damage to the board caused by failure to correctlyremove or install the chip is not covered by theWattMaster warranty.
MUST
ALL
VERY BE CAREFUL.
Using I.C. Puller To Remove Socketed Chip
Using Screwdriver To Remove Socketed Chip
End View Of Socketed Chip AssemblyTop View Of Socketed Chip Assembly
I.C. Puller
Chip Socket
Chip Socket
Chip Socket
Gently Rock Chip Side To Side And ThenLift Straight Up To Remove Chip FromChip Socket.
Gently Lift The Chip On One End And Rock ChipBack And Forth With Screwdriver As Shown.Repeat This Process On The Other End Of Chip.Alternate This Process On Both Ends Of Chip UntilThe Chip Is Free From The Chip Socket.
Pin 1
Dot
Socket
PrintedCircuitBoard
Typical RS-485 CommunicationsDriver Chip Detail
Chip Replacement Information
VAV-DRCHPREP.CDR
05/12/04
WattMaster VAV Components
Component & System Wiring60
Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors
Temp
(ºF)
Resistance
(Ohms)
Voltage @ Input (VDC)
Temp
(ºF)
Resistance
(Ohms)
Voltage @ Input (VDC)
Temp
(ºF)
Resistance
(Ohms)
Voltage @ Input (VDC)
-10 93333 4.620 60 14681 3.042 86 8153 2.297
-5 80531 4.550 62 14014 2.985 88 7805 2.242
0 69822 4.474 64 13382 2.927 90 7472 2.187
5 60552 4.390 66 12758 2.867 95 6716 2.055
10 52500 4.297 68 12191 2.810 100 6047 1.927
15 45902 4.200 69 11906 2.780 105 5453 1.805
20 40147 4.095 70 11652 2.752 110 4923 1.687
25 35165 3.982 71 11379 2.722 115 4449 1.575
30 30805 3.862 72 11136 2.695 120 4030 1.469
35 27140 3.737 73 10878 2.665 125 3656 1.369
40 23874 3.605 74 10625 2.635 130 3317 1.274
45 21094 3.470 75 10398 2.607 135 3015 1.185
50 18655 3.330 76 10158 2.577 140 2743 1.101
52 17799 3.275 78 9711 2.520 145 2502 1.024
54 16956 3.217 80 9302 2.465 150 2288 0.952
56 16164 3.160 82 8893 2.407
58 15385 3.100 84 8514 2.352
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while discon-nected from the controllers (not powered). Use the voltage column tocheck sensors while connected to powered controllers. Read voltage
with meter set on DC volts. Place the “-”(minus) lead on GND terminaland the “+”(plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Sensor ChecksThe following sensor voltage and resistance tables are provided to aidin checking sensors that appear to be operating incorrectly. Many sys-tem operating problems can be traced to incorrect sensor wiring. Besure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly,check voltage and/or resistance to confirm that the sensor is operatingcorrectly per the tables. Please follow the notes and instructions beloweach chart when checking sensors.
Temperature & Humidity Sensor Voltage-Resistance Tables
OE265-03 Relative Humidity Transmitter – Humidity vs. Voltage
Humidity
Percentage(RH)
Voltage @
Input
(VDC)
Humidity
Percentage(RH)
Voltage @
Input
(VDC)
Humidity
Percentage(RH)
Voltage @
Input
(VDC)
Humidity
Percentage(RH)
Voltage @
Input
(VDC)
0% 1.00 26% 2.04 52% 3.08 78% 4.12
2% 1.08 28% 2.12 54% 3.16 80% 4.20
4% 1.16 30% 2.20 56% 3.24 82% 4.28
6% 1.24 32% 2.28 58% 3.32 84% 4.36
8% 1.32 34% 2.36 60% 3.40 86% 4.44
10% 1.40 36% 2.44 62% 3.48 88% 4.52
12% 1.48 38% 2.52 64% 3.56 90% 4.60
14% 1.56 40% 2.60 66% 3.64 92% 4.68
16% 1.64 42% 2.68 68% 3.72 94% 4.76
18% 1.72 44% 2.76 70% 3.80 96% 4.84
20% 1.80 46% 2.84 72% 3.88 98% 4.92
22% 1.88 48% 2.92 74% 3.96 100% 5.00
24% 1.96 50% 3.00 76% 4.04
OE265-03 Relative Humidity Sensor
Testing Instructions:
Use the voltage column to check the Humidity Sensor while connectedto a powered expansion board. Read voltage with meter set on DC volts.
Place the “-”(minus) lead on terminal labeled GND and the “+” lead onterminal AIN4 on the Analog Input/Output Expansion Board.
Component & System Wiring 61
OE271 Duct Static Pressure Sensor
Pressure @
Sensor (“ W.C.)
Voltage @
Input
(VDC)
Pressure @
Sensor (“ W.C.)
Voltage @
Input
(VDC) 0.00 0.25 2.60 2.20 0.10 0.33 2.70 2.28 0.20 0.40 2.80 2.35 0.30 0.48 2.90 2.43 0.40 0.55 3.00 2.50 0.50 0.63 3.10 2.58 0.60 0.70 3.20 2.65 0.70 0.78 3.30 2.73 0.80 0.85 3.40 2.80 0.90 0.93 3.50 2.88 1.00 1.00 3.60 2.95 1.10 1.08 3.70 3.03 1.20 1.15 3.80 3.10 1.30 1.23 3.90 3.18 1.40 1.30 4.00 3.25 1.50 1.38 4.10 3.33 1.60 1.45 4.20 3.40 1.70 1.53 4.30 3.48 1.80 1.60 4.40 3.55 1.90 1.68 4.50 3.63 2.00 1.75 4.60 3.70 2.10 1.83 4.70 3.78 2.20 1.90 4.80 3.85 2.30 1.98 4.90 3.93 2.40 2.05 5.00 4.00 2.50 2.13
OE258 Building Pressure Sensor
Pressure @
Sensor (“ W.C.)
Voltage @
Input
(VDC)
Pressure @
Sensor (“ W.C.)
Voltage @
Input
(VDC) -0.25 0.00 0.01 2.60 -0.24 0.10 0.02 2.70 -0.23 0.20 0.03 2.80 -0.22 0.30 0.04 2.90 -0.21 0.40 0.05 3.00 -0.20 0.50 0.06 3.10 -0.19 0.60 0.07 3.20 -0.18 0.70 0.08 3.30 -0.17 0.80 0.09 3.40 -0.16 0.90 0.10 3.50 -0.15 1.00 0.11 3.60 -0.14 1.10 0.12 3.70 -0.13 1.20 0.13 3.80 -0.12 1.30 0.14 3.90 -0.11 1.40 0.15 4.00 -0.10 1.50 0.16 4.10 -0.09 1.60 0.17 4.20 -0.08 1.70 0.18 4.30 -0.07 1.80 0.19 4.40 -0.06 1.90 0.20 4.50 -0.05 2.00 0.21 4.60 -0.04 2.10 0.22 4.70 -0.03 2.20 0.23 4.80 -0.02 2.30 0.24 4.90 -0.01 2.40 0.25 5.00 0.00 2.50
OE271 Pressure Sensor Testing Instructions
Use the voltage column to check the Duct Static Pressure Sensor whileconnected to powered controllers. Read voltage with meter set on DCvolts. Place the “-”(minus) lead on GND terminal and the “+”(plus)lead on the 0-5 pin terminal on (JP1) with the jumper removed. Be sureto replace the jumper after checking.
OE258 Building Pressure Sensor Testing Instructions
Use the voltage column to check the Building Static Pressure Sensorwhile connected to a powered expansion board. Read voltage with meterset on DC volts. Place the “-”(minus) lead on terminal labeled GNDand the “+” lead on terminal AIN4 on the Analog Input/Output Expan-sion Board.
Pressure Sensors Voltage-Resistance Tables
OE271 Duct Static Pressure Sensor
This sensor is used to sense duct static pressure for the WattMasterVAV system controllers. The OE271 sensor is a 0-5” W.C. pressurerange, 0-5 VDC voltage range sensor. Use the table and testing infor-mation below to check for proper sensor operation.
OE258 Building Pressure Sensor
This sensor is used to sense building pressure for the WattMaster VAVsystem controllers. The OE258 sensor is a -0.25” to +0.25” W.C. pres-sure range, 0-5 VDC voltage range sensor. Use the table and testinginformation below to check for proper sensor operation.
Component & System Wiring62
Notes
Component & System Wiring 63
Notes
Form: WM-VAVWIRE-TGD-01C Printed in the USA February 2008All rights reserved Copyright 2008
WattMaster Controls Inc. • 8500 NW River Park Drive • Parkville MO • 64152
Phone (816) 505-1100 E-mail: [email protected] Fax (816) 505-1101