Download - Pdt-cs-10 Ch04 en p320 El p8
P320 EL 4 C
P8 Software package
September 2009September 2009
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 2 / 23
ALSPA 8000 - P320 EL
P8 SOFTWARE
PACKAGE
P8 SOFTWARE
PACKAGE
Displays browser
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 3 / 23
P320 EL
P8 SOFTWARE
– Progiciel P8 Version > 9.01
– PC et CPU protocol SNP, Serial Network Protocol for ALSPA 8000 PLC serial
– Power supply port in RS 422
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 4 / 23
P320 EL
P8 SOFTWARE
– MAIN MENU
• CONTROLLER SELECTION :
� SHIFT - F1 ... ALSPA C80-05
� SHIFT - F2 ... ALSPA C80-25
� SHIFT - F3 ... ALSPA C80-35
� SHIFT - F5 ... ALSPA C80-75
• SELECTION OF FUNCTIONALITIES :
� F1 … ALSPA P8 PROGRAMMMING SOFTWARE
� F2 … ALSPA P8 CONFIGURATION SOFTWARE
� F3 ... PCM DEVELOPMENT SOFTWARE (PCOP)
� F4 ... AXIS MODULE DEVELOPMENT SOFTWARE
� F5 ... OPERATOR INTERFACE UTILITIES
� F7 ... ALSPA P8 UTILITIES
� F8 ... USER MENU
� F9 … ALSPA P8 GENERAL PARAMETERIZATION
� F10 ... RETURN TO DOS
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 5 / 23
P320 EL
P8 SOFTWARE
�Main Short Cut Keys For P8 :
– ALT-H Interactive on line HELP, "escape" to exit
– ALT-K List of short cut keys "ESCAPE" to exit
– ALT-M To create or to break the communication between PC and plc
monitor / online / offline/ ...
– ALT-R If the link between pc and plc is "on line", ALT R stop or run the plc.
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 6 / 23
AFTER SELECTION OF "CONFIGURATION SOFTWARE..." IN THE MAIN MENU USING F2
F1 F2 F3 F7 F8 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓
INPUT/ OUTPUT
CONFIGURATION
CPU
CONFIGURATION
PLC
TESTING
AND
STATUS
SETTING
OF
CONSOLE
PARAMETERS
PROGRAM
FOLDERS
UTILITIES :
TRANSFERS,
DELETING
PRINTING
FUNCTIONS
PASSWORD
IF A CPU CONFIGURATION WAS PREVIOUSLY COMPLETED, PASSWORD DISABLED :
- THE MEMORY OF THE PROGRAMMABLE CONTROLLER MUST BE DELETED AND THE BATTERY
REMOVED FOR MORE THAN AN HOUR TO RECONFIGURE "PASSWORD : ENABLED" AND ENTER
THE DIFFERENT LEVELS.
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 7 / 23
AFTER SELECTING "INPUT/ OUTPUT CONFIGURATION" USING F3
⇑⇑⇑⇑ F1 ⇑⇑⇑⇑ F2 ⇑⇑⇑⇑ F3 ⇑⇑⇑⇑ F4 ⇑⇑⇑⇑ F5
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓RACK COPY I/ O VIEW DELETE RECOVER
NO ACTION IN
THIS VERSION
GO TO A
CONFIGURED
MODULE AND
MOVE TOWARDS
THE POSITION TO
WHICH IT IS TO
BE COPIED. THEN
PRESS TO
CONFIRM
SHOWS
THE HIGHEST
VALUE
CONFIGURED
ACCORDING TO
THE LOCATIONS
TO DELETE
A
MODULE
TO
RECOVER
A MODULE
JUST DELETED
F1 F2 F4 F5 F6 F8 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ES N80 PWR S RCKSEL COMM OTHERS ZOOM
SELECTION
OF TYPE OF
MODULE (I/ O,
DISCRETE,
ANALOG) WITH
DISPLAY OF LISTS
SELECT
DES MODULES
N80 OR NBC
WITH DISPLAY OF
LISTS
SEE ZOOM
ON
PWR SUPPLY
MODULE
DISPLAY OF LIST
OF AVAILABLE
BASE PLATES OR
RACKS
DISPONIBLES
SELECT
ETHERNET
OR CMM311
MODULES
SELECT
OF MODULES
PCM, HSC,
EXTERN, ADC,
APM, IOLINK
AND IOP, WITH
DISPLAY OF
LISTS
GO TO POSITION
OF A MODULE
ALREADY
CONFIGURED,
SEEN FROM ITS
DETAILED
CONFIGURATION
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 8 / 23
AFTER SELECTING "CONFIGURATION CPU" USING F2
FOR ALL KEYS THE ACTIONS ARE THE SAME AS FOR THE FIRST CONFIGURATION SCREEN ⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10
F1 F3 F4
↓↓↓↓ ↓↓↓↓ ↓↓↓↓
TIME IDSNP LIMIT
SET CONTROLLER TIME
IDENTIFICATION OF CONTROLLER BY A
NAME, ESPECIALLY USEFUL WHEN
USING A P8 CONNECTED TO SEVERAL
C80-35s AND WITH INTER-PLC SNP
COMMUNICATION
DISPLAYS CONFIGURED DATA AND PLC
MEMORY LIMITS
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 9 / 23
P320 ELP8 CONFIGURATION SOFTWARE
AFTER SELECTING "CONTROLLER CHECK AND STATUS" USING F3
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F4 F5
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓RUN PLC PASSWORD PLC FLTS ES FLTS PLC MEM
CHOICE OF RUN OR STOP
WITH OR WITHOUT I/ O
SCANNING
4 PASSWORD LEVELS
IF ENABLED IN CPU
CONFIG.
DISPLAYS TABLE
OF PLC FAULTS
DISPLAYS TABLE OF
FAULTS ON MODULE
(HARDWARE)
GIVES AMOUNT OF
PROGRAM MEMORY USED
AND REMAINING
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 10 / 23
AFTER SELECTING "CONSOLE PARAMETERIZATION" USING F7
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3
↓↓↓↓ ↓↓↓↓ ↓↓↓↓MODE CONNEC PLC COM
SAME COMMAND AS SELECTION SNP
CONNECTIONS WITH CHOICE
SETTING OF PARAMETERS OF
THE CONSOLE
ALT M OF PLC IDENTIFIER NAME TO COMMUNICATION PORT
FOR
OFFLINE/ MONITOR/ ONLINE
MODE CHANGE
BE PROGRAMMED
1 PC WITH P8 CAN BE
CONNECTED TO 8 PLCs ALSPA
C80-35 WITH DIFFERENT
SNP- ID, IF THE "PORT
CONNECTION" SELECTED
IS : MULTIPOINTS
A TABLE SHOWS ALL THE SNP
ID NAMES
CONNECTED TO
THE ALSPA C80-35
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 11 / 23
AFTER SELECTING "PROGRAM FOLDERS" USING F8
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F4 F5 F7 F8
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓
SELECT DELETE AUTO SAVE RESTORE ERASE LOCK
CREATION
A NEW PROGRAM
FOLDER
OR SELECTION FROM
LIST OF THOSE
ALREADY CREATED
DELETES A FOLDER
FROM THE LIST BUT
CANNOT DELETE THE
FOLDER BEING
WORKED ON, CALLED
THE:
"CURRENT FOLDER "
AUTO-SELECTION
FROM LIST OF FOLDER
CORRESPONDING TO
THE ONE LOADED INTO
THE CONTROLLER
(AFTER SELECTING
WITH F1)
SAVES THE CURRENT
FOLDER ON THE HARD
DISK OR ON THE
DISKETTE WITH THE
APPROPRIATE PATH
A:\FOLDER NAME
RESTORAL IN THE
CURRENT FOLDER
FROM THE BACKUP OF
THE HARD DISK OR
DISKETTE A:\FOLDER
NAME
ERASES THE CONTENTS
OF THE CURRENT
PROGRAM FILE
WITHOUT ERASING
THE NAME
LOCKS OR UNLOCKS
THE CURRENT
PROGRAM FOLDER TO
PREVENT CERTAIN
PRECEDING
OPERATIONS
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 12 / 23
AFTER SELECTING "UTILITIES : TRANSFERS, ERASE" USING F9
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F5 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓
→→→→ CON →→→→ PLC CHECK ERASE PROM
TRANSFERS
THE
CONFIGURATION
FROM THE PLC TO
THE CONSOLE IN
"RUN" OR "STOP"
MODE
TRANSFERS THE
CONFIGURATION
FROM THE CONSOLE
TO THE PLC
THE PLC MUST BE IN
:
"STOP" MODE
AND
"ON LINE"
BETWEEN
PLC AND CONSOLE
COMPARISON
BETWEEN THE
CONFIGURATION
CREATED IN THE
CONSOLE AND THE
ONE EXISTING IN
THE PLC
ERASES FROM THE
CONTROLLER
MEMORY WITH THE
SELECTION OF
ERASE :
- PROGRAM
- CONFIGURATION
- REFERENCE TABLE
- FORCING TABLE
USED TO READ OR
WRITE OR CHECK
BETWEEN EEPROM
AND RAM
MEMORIES OF THE
PLC
PLC IN STOP MODE
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 13 / 23
AFTER SELECTING "PRINTING FUNCTIONS " USING F10
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F4 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓
PARAM SCREEN PRINT PAUSE SAVE
SETTING
PARAMETERS OF
PRINTER
- - NO. OF LINES
PER PAGE
- ETC...
DESTINATION
OF PRINTING
SCREEN :
- PORT
- FILE
CONFIGURATION
OF
PRINT FOLDER
FOR
CONFIGURATION
OF PLC
TO PRINTER OR TO A
FILE
FOR TEMPORARY
STOPPING DURING
PRINTING
SAVING OF
PRINTING
PARAMETERS
CONFIGURED
PREVIOUSLY IN A
PRINT.SET FILE
P320 ELP8 CONFIGURATION SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 14 / 23
AFTER SELECTING "PROGRAMMING SOFTWARE" IN THE MAIN MENU USING F1
F1 F2 F3 F7 F8 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓
TO EDIT
OR TO READ
THE PROGRAM
REFERENCE
TABLES
PLC
TESTING
AND
STATUS
CONSOLE MODE
AND
CONFIGURATION
PROGRAM
FOLDERS
UTILITIES :
TRANSFERS,
ERASE
FUNCTIONS
DISPLAYS
VARIABLES
OF DATA MEMORY
BY TYPE WITH
THEIR VALUE
OR THE
PERSONALIZED
TABLES
FROM 1 TO 99
- RUN / STOP
- PASSWORD
- 2 FAULT TABLES
. PLC
. I/ O
- PLC MEMORY
RS-232 PORT N0.
AND ALL ITS
PARAMETERS
CONNECTION
MODE
- WITH 1 PLC
- WITH SEVERAL
PLCs AND SNP ID
- SELECTION
OF
MODES
SEEN BY
PROGRAM
- CREATION
- SELECTION
- DELETION
- SAVE
- RESTITUTION
- ERASE
- LOCKED
- COPY
- ESTABLISHES
THE LINK WITH
THE PLC TO LOAD
OR READ OR
CHECK A FOLDER
- ALLOWS
ERASING OF PLC
MEMORY
- READ, WRITE,
CHECK BETWEEN
RAM AND
EEPROM OF THE
PLC
SETTING
PARAMETERS OF
PRINTER
PRINTING
ALT N THE WHOLE
FOLDER
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 15 / 23
AFTER SELECTING … USING F1
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F4 F7 F8 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓INSERT EDIT MODIFY SEARCH OPTION GOTO MORE ZOOM
INSERT
A NEW RUNG
BEFORE THE
CURRENT RUNG
EDIT
THE CURRENT
RUNG
WORD
– FOR –
WORD
EDIT THE
CURRENT RUNG
(TO MODIFY OR
TO REPLACE AN
INSTRUCTION BY
ANOTHER WITH
THE SAME
MEMORY
LENGTH)
SEARCH FOR A
REFERENCE,
NICHNAME OR
INSTRUCTION.
REPLACE THE
FOUND TARGET
WITH THE
REPLACEMENT
ITEM.
DISPLAYS A
SEARCH
CONTROL
WINDOW.
SETUP COIL USE
CHECKING AND
AUTOMATIC
EDITOR OPTIONS.
GOTO A RUNG
OR A BLOCK.
ENTER THE RUNG
NUMBER OR
BLOCK NAME
AND THEN PRESS
"GOTO"
ACCESS FEATURES
FOR EDITING
GROUPS OF
RUNGS, E.G.,
CUT, PESTO
ZOOM INT A
BLOCK,
FUNCTION
BLOCK,
COMMENT, OR
MARKER RUNG
UNDER
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 16 / 23
P320 ELP8 PROGRAMMING SOFTWARE
AFTER SELECTING "INSERTION OF A NEW RUNG ...", TO CHOICE AN INSTRUCTION
⇑⇑⇑⇑ F1 ⇑⇑⇑⇑ F2 ⇑ F3 ⇑⇑⇑⇑ F4 ⇑⇑⇑⇑ F5 ⇑⇑⇑⇑ F6 ⇑⇑⇑⇑ F7 ⇑⇑⇑⇑ F8 ⇑⇑⇑⇑ F9 ⇑⇑⇑⇑ F10
RELAY TMPCTR MATH RELATN BIT OP DATAMV TABLES CONVERT CONTRL OPN SP *
-¦ +- TMR ADD EQ AND MOVE SRH EQ BCD - 4 CALL DROITE
-¦/+- OFDT SUB NE OR BLKMOV SRH NE INT DO IO BAS
-( )- ONDTR MUL GT XOR BLKCLR SRH GT PID ISA EFF CO
-(M)- UPCTR DIV GE NOT SHFREG SRH GE PID IND EFF LI
-(/M)- DNCTR MOD LT SHL BITSEQ SRH LT SFCRES EFF SYM
-(S)- TMBASE SQRT LE SHR COMREQ SRH LE END EFF INS
-(R)- RANGE ROL ARR MOV COMMNT
-(SM)- (TIME TYPES : TYPES : ROR TYPES : TYPES : SVCREQ
-(RM)- BASE (INTEGER : INT BITTST WORD . BYTE MCR
(VERT.) 0,1 S INT AND BITSET AND . WORD ENDMCR
0,01 S DOUBLE DINT BITCLR DINT . INT MCRN
(HORIZ.) 0,001 S) INTEGER : BITPOS . DINT ENDMCRN
-(↑↑↑↑)- DINT) MKCOMP JUMP
-(↓↓↓↓)- TYPES : LABEL
<<<<+ >>>>−−−− WORD JUMPN
−−−−<<<<+ >>>> LABELN
* OPEN SPACE : TO ALLOW RUNG MODIFICATIONS
LIS
T O
F I
NS
TR
UC
TIO
NS
AF
TE
R T
HE
AB
OV
E C
HO
ICE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 17 / 23
AFTER SELECTING "EDIT, READ PROGRAM" USING F1
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 THE ACTIONS ARE THE SAME AS FOR THE FIRST PROGRAMMING SCREEN
F1 F2 F3 F4 F7 F8 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓INSER.. EDIT MODIFY SEARCH OPTION TO ... OTHERS ZOOM
INSERTION
OF A NEW
SEGMENT BEFORE
THE POINTED
SEGMENT
EDITION
OF POINTED
SEGMENT.
ALL
MODIFICATIONS
ARE AUTHORIZED
MODIFICATION
OF POINTED
SEGMENT
CERTAIN
CONDITIONS
ARE
OBLIGATORY :
THE SIZE OF THE
INSTRUCTIONS
MUST BE SIMILAR
(SEE CHAPTER
3-12-2 ALS DOC
52201)
SEARCH IN A
PROGRAM FOR
- A REFERENCE
- A MEMONIQUE
- A DESCRIPTION
- AN IDENTIFIER
- AN
INSTRUCTION
REPLACEMENT
AFTER SEARCH BY
DATA OF THE
SAME TYPE
FOR THE EDITOR
- CHECK MULTIPLE
USE OF COILS
- AUTOMATICALLY
INSERT
THE REFERENCES IN
THE VARIABLE
DECLARATION TABLE
(SEGMENT 001)
ALLOWS
DIRECT POINTING
TO A SEGMENT
OR A BLOCK
MANIPULATION
OF SEGMENTS OF
PROGRAMS AND
POSSIBLE CHOICE
BETWEEN
STORAGE TO
BUFFER MEMORY
OR FILES
AFTER
POSITIONING
ON :
- A BLOC
- AN
INSTRUCTION
- A COMMENT
- SEE DETAILS
OF THE
CONFIGURATION
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 18 / 23
AFTER SELECTING "REFERENCE TABLES" USING F2
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F2 F3 F5 F6 F7 F8 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓INT DINT HEX BIN ASCII TMCTR MIXTE CHGTOU
CONVERTS
THE POINTED
REFERENCE TO
"SIGNED INTEGER"
VALUE
CONVERTS
THE POINTED
REFERENCE TO
"SIGNED DOUBLE
INTEGER"
VALUE
CONVERTS
THE POINTED
REFERENCE TO
HEXADECIMAL
VALUE
CONVERTS
THE POINTED
REFERENCE
TO BINARY VALUE
(16 BITS)
CONVERTS
THE POINTED
REFERENCE TO
"ASCII
CHARACTER"
CONVERTS
THE POINTED
REFERENCE TO
GROUPS OF 3
CONSECUTIVE
REGISTERS
REPRESENTING A
COUNTER OR A
TIME DELAY
CALLS A
PERSONALIZED
MIXED,
REFERENCE TABLE
(1 TO 99)
INSIDE A TABLE
TO IN ITIALIZE OR
CANCEL FORCING
IN AN ENTIRE
TABLE
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 19 / 23
AFTER SELECTING "PLC TESTING AND STATUS" USING F3
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F4 F5 F6 F7 F8
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓RUN MOT PSS DEF AP DEF ES MEM AP MEM BLC TAIL RF CYCLE
IN "ON-LINE"
MODE, ALLOWS THE
CHOICE OF RUN OR
STOP WITH OR
WITHOUT I/ O
SCANNING
4 PASSWORD
LEVELS IF
ENABLED IN THE
CPU
DISPLAYS THE
TABLE OF
CONTROLLER
FAULTS
DISPLAYS THE
TABLE OF FAULTS
ON MODULE
(HARDWARE)
DISPLAYS
PROGRAM
MEMORY
QUANTITIES USED
AND REMAINING
DISPLAYS
DISTRIBUTION OF
MEMORY USED
FOR THE PARTS :
- PROGRAM
- DECLARATION
- COMMENTS
DISPLAYS THE
HIGHEST
ADDRESS USED IN
THE PROGRAM
FOR EACH TYPE
OF VARIABLE
DISPLAYS THE
CYCLE TIME
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 20 / 23
AFTER SELECTING "CONSOLE MODE AND CONFIGURATION" USING F7
⇑⇑⇑⇑ F1 TO F10 SAME AS FOR FIRST SCREEN
F2 F3 F4 F5
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓MODE CONNEX CON AP DISPLAY MODE
SAME AS COMMAND SELECTION SNP CONNECTIONS
WITH CHOICE OF PLC
SETTING OF PARAMETERS OF
THE CONSOLE
SELECTION OF DIFFERENT
DISPLAY MODES ON THE
ALT M IDENTIFIER NAME TO BE SNP COMMUNICATION PORT SCREEN OF THE PROGRAM,
FOR
OFFLINE/ MONITOR/ ONLINE
PROGRAMMED 1 PC
WITH P8 CAN BE CONNECTED
TO 8 PLCs ALSPA C80-35
CONNECTED
TO THE ALSPA C80-35
BY PRESSING SUCCESSIVELY
ON :
MODE CHANGE WITH DIFFERENT SNP ID, IF ALT N
THE "PORT CONNECTION"
SELECTED IS : MULTIPOINTS.
A TABLE SHOWS ALL THE SNP
ID NAMES
ALSO SELECTS DIRECTION OF
READING IN TABLE OF
VARIABLES
SAME AS A
ALT N
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 21 / 23
AFTER SELECTING "PROGRAM FOLDERS" USING F8
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F4 F5 F6 F7 F8 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓SELECT SUPPRM AUTO SAUVEG RESTIT REN OMM EFFACE VERROU COPY
CREATION
A NEW
PROGRAM
FOLDER
OR SELECTION
FROM LIST OF
THOSE ALREADY
CREATED
DELETES A
FOLDER FROM
THE LIST BUT
CANNOT DELETE
THE FOLDER
BEING WORKED
ON, CALLED
THE :
"CURRENT
FOLDER "
AUTO-
SELECTION
FROM LIST OF
FOLDER SAME
AS THE ONE
LOADED INTO
THE
CONTROLLER
(AFTER
SELECTING
WITH F1)
SAVES THE
CURRENT
FOLDER ON THE
HARD DISK OR
ON THE
DISKETTE WITH
THE
APPROPRIATE
PATH
A:\ FOLDER
NAME
RESTORAL IN
THE CURRENT
FOLDER FROM
THE BACKUP OF
THE HARD DISK
OR DISKETTE
A:\ FOLDER
NAME
USED TO
CHANGE THE
NAME OF THE
CURRENT
FOLDER
ERASES THE
CONTENTS OF
THE CURRENT
PROGRAM FILE
WITHOUT
ERASING THE
NAME
LOCKS OR
UNLOCKS THE
CURRENT
PROGRAM
FOLDER TO
PREVENT
CERTAIN
PRECEDING
OPERATIONS
COPIES THE
CONTENTS OF
ANY FILES INTO
THE CURRENT
FILE MAY BE
DONE FROM A
DISKETTE
P320 ELP8 PROGRAMMING SOFTWARE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 22 / 23
P320 ELP8 PROGRAMMING SOFTWARE
AFTER SELECTIN G "UTILITIES : TRAN SFERS, ERASE" USIN G F9
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F3 F5 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓→→→→ CON →→→→ PLC CHECK ERASE PROM
TRAN SFERTS
A COM PLETE
OR IN COM PLETE
FOLDER FROM PLC
TO THE CON SOLE IN
"RUN " OR "STOP"
M ODE
TRAN SFERTS
A COM PLETE
OR IN COM PLETE
FOLDER FROM
CON SOLE TO THE
PLC IN "ON LIN E"
M ODE
COM PARISON
OF CON TEN TS OF
FOLDER ON HARD
DISKETTE AN D THE
ON E EXISTIN G
IN THE PLC
ERASES FROM THE
PLC M EM ORY, AS
CHOSEN :
- THE PROGRAM
- THE
CON FIGURATION
- THE REFEREN CE
TABLES
- THE FORCIN G
TABLES
USED TO READ,
WRITE OR CHECK
BETWEEN THE
EEPROM AN D RAM
M EM ORIES OF THE
PLC
PLC IN STOP M ODE
September 2009 PDT-CS-10/P320 EL 4 C Chapter 04 page 23 / 23
AFTER SELECTING "PRINTING FUNCTIONS" USING F10
⇑⇑⇑⇑ F1 TO ⇑⇑⇑⇑ F10 SAME AS FOR FIRST SCREEN
F1 F2 F4 F5 F6 F9 F10
↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓ ↓↓↓↓PARAM SCREEN PROGRM XREF VALUE PAUSE SAVE
SETTING OF PRINTER
PARAMETERS
- PAGE WIDTH
- NUMBER OF LINES
PER PAGE
- ETC…
DESTINATION
OF
PRINTING SCREEN
PORT OR FILE
CONFIGURATION
OF FOLDER FOR
PRINTING TO A
PRINTER OR A FILE
WHEN PRINTING IS
STARTED, MAKES IT
POSSIBLE TO
INSERT THE CROSS
REFERENCES
ACCORDING TO
THE CHOICE OF
SORTING IN THIS
SCREEN
ALLOWS THE
PRINTING OF
VALUES OF
VARIABLES
SPECIFIED IN TABLE
FORM TO THE
PRINTER OR TO A
FILE
ALLOWS A
TEMPORARY STOP
DURING PRINTING
SAVES
PRINTING
PARAMETERS
CONFIGURED
PREVIOUSLY IN A
FILE :
PRINT.SET
P320 ELP8 PROGRAMMING SOFTWARE