Princeton University Substation & Electrical
Upgrade Project
February 28, 2019
![Page 2: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/2.jpg)
Project Background
► Princeton University connected to PSE&G at 26kV in two locations
• Elm Substation
• Charlton Substation
► 2018 Peak Load ~28 MW
• Gas Turbine Generator
• Solar
► PSE&G 26kV overhead distribution is at capacity
• Future campus expansion limitation
• Overhead distribution exposure
![Page 3: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/3.jpg)
![Page 4: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/4.jpg)
Design Goals
► Support Campus Expansion
• Increase electrical capacity
• Lake Campus, etc.
► Support Campus Goals
• Sustainability
• Redundancy – N+1
• Reliability
• Resiliency
• Maintainability
• Improve Campus Voltage Regulation
![Page 5: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/5.jpg)
![Page 6: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/6.jpg)
Project Scope
► Construct new 69kV Substation (69kV – 26.4kV)
• Greater reliability at 69kV transmission vs. 26kV Utility O/H distribution system
► Reconfigure Charlton & Elm Substations to be served from new Princeton
Substation
• Overhead -> Underground Service
► Elm Substation Upgrades
• Two new 12/16/20 MVA transformers
• New 5kV switchgear
► Replace 5kV Switchgear at Dillon Gym
![Page 7: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/7.jpg)
Project Team
► Princeton University
• Technical & Operations Team
• Construction Management & Project Management
• Civil Construction
► Burns & McDonnell
• Electrical
• Structural
• Communications/SCADA/Automation
• HDD Design (Brierley)
► Van-Note Harvey
• Civil Engineering/Local Codes
![Page 8: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/8.jpg)
69kV Substation
► Location• Adjacent to existing PSE&G Station
• Coordinated with expansion
► Ring Bus Design• High reliability
► Three 69kV transmission system connections• Geographically distinct
► Two 69kV:26kV 50/67/83 MVA transformers• 2-hour fire-rated separation wall
• Oil containment
• LTC – 26kV Voltage Regulators
![Page 9: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/9.jpg)
69kV Substation
► 69kV Relay/Control House – University Owned
• Utility Controlled 69kV Pass-Thru Yard (2 x 69kV Lines)
• Future (3 x 69kV Lines)
► Two 26kV Switchgear Buildings - University Owned/Controlled
• Main-Tie-Tie-Main
• Relay & Synchronizing Panel
► Future Telecom Entrance Point
► Backup Generator
► Aesthetic Considerations
![Page 10: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/10.jpg)
![Page 11: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/11.jpg)
![Page 12: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/12.jpg)
Horizontal Directional Drill
►Two 2000’ bores – 60’
deep
►36” Diameter Holes
►26kV - A & B Feeders
►Telecom
![Page 13: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/13.jpg)
Elm Substation
► 26kV Service to new
substation
• Utility ->Owner-served
► Upgrade transformers
• 12/16/20 MVA
► Replace 5kV Switchgear
► Synchronizing Panel
► Construction Phasing
![Page 14: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/14.jpg)
Charlton Substation
► 26kV Service from new
substation
• Utility ->Owner-served
► Protective Relaying Upgrades
► Coordination of Utility Outage
![Page 15: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/15.jpg)
Project Schedule
► 69kV Substation Energization: April 1st, 2019
► Charlton Substation Cut-Over: June 2019
► Elm Substation Cut-Over: Fall 2019
► Substantial Completion: Fall 2019
![Page 16: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/16.jpg)
Considerations and Project Applications
► Utility Coordination – Early and Often!
► Aesthetics and Site Location
► Factory Equipment Testing
► Load Growth
• Integration with Utility Master Plan
► Underground Utilities
• Close coordination with Princeton
![Page 17: Princeton University Substation & Electrical Upgrade Project](https://reader031.vdocument.in/reader031/viewer/2022013001/61cb28b2a38c347e6e225e7d/html5/thumbnails/17.jpg)