GETCO / E / 4S-001/ PP - 015 – 1A / R1 Dt. 05.11.2011
Page 1 of 4
Control & Relay Protection Philosophy for 400KV KOSAMBA Sub Station
A) Bus Bar Configuration 400kV System : Two Main Bus (1 & ½ ‘I’ type scheme) 220kV System : Three Bus (Two Main and Transfer) 66kV System : Two Bus (Two Main Bus)
Isolator system400kV System: Five isolator configuration for ½ Dia (One each for Bus &
Line/ICT/Reactor and Three for Tie Bay)220kV System: Four isolator configuration (Three Bus isolators and a Line isolator)66kV System: Three isolator configuration (Two Bus isolators and a Line isolator)
B) Control Voltage 220V DC
C) Control & Relay panels
Control & protection Panels to be mounted in Yard Kiosk
D) PLCC panels
PLCC Panels to be mounted in Control Room PLCC BCU panel to be mounted in Control Room for interface between Control &
protection Panels and PLCC Panels, through GOOSE commands
E) Nos. of Bays & Bus Bar Protection
400 KV System
Line W/o Reactor Bay – 1 Nos. ICT Bay – 1 No. Bus Reactor Bay – 1 No. Tie Bay – 3 Nos. Bays connected to Bus Bar Protection in first phase - 11 Nos. Bays to be connected to Bus Bar Protection - 6 Nos. Future bays – 13 Nos. Total bays in the Sub Station will be - 30 Bus Bar Protection
o Control Unit - 24 Bays (Siemens make 7SS52)o Bay Units - 6 Nos. + 1 No. Spare (Siemens make 7SS523)
220 KV System
Feeder Bay – 2Nos. ICT LV (400/220KV) Bay – 1 No. Transformer HV (220/66KV) Bay – 2 Nos. Bays connected to Bus Bar Protection in first phase - 13 Bays to be connected to Bus Bar Protection - 5 Nos. Future bays – 1 No. Total bays in the Sub Station will be – 19 Nos. Bus Bar Protection
o Control Unit - 24 Bays (Siemens make 7SS52)
o Bay Units - 5 Nos.
8/20/2019 Protection Philosophy R1
http://slidepdf.com/reader/full/protection-philosophy-r1 2/4
GETCO / E / 4S-001/ PP - 015 – 1A / R1 Dt. 05.11.2011
Page 2 of 4
66 KV System
Feeder Bay – 5 Nos. Transformer LV (220/66KV) Bays – 2 No. Transformer HV (66/11KV) Bay – 1 No. Bus Coupler Bay – 1 No.
Bays to be connected in first phase - 9 Future bays - 3 Total bays in the Sub Station will be - 12
Control Philosophy – KOSAMBA Sub Station
System Controlling Device to be Adopted Type of Controlling Device
400 KV Bay Bay Control Unit BCU with IEC 61850 Protocol
220 KV Bay Bay Control Unit BCU with IEC 61850 Protocol
66 KV Bay Bay Control & Protection Unit BCPU with IEC 61850
Protocol
PROTECTION PHILOSOPHY – KOSAMBA Sub Station
A) Transmission Lines Protection
Line Protection Adopted Type of Relay
1 Two Distance Protection[shall be of two different make (i.e.from different manufacturers) or ofsame make with two differentplatforms with same specifications]-Main-I Protection &-Main II Protection
Numerical Relays with IEC61850 Protocol
2 Two Stage Over Voltage Protection- Stage I- Stage II
- Static Relay- Integrated in Main I &
Main II Protection
400 KV Lines
3 Local Breaker Backup (LBB) Protn. Integrated in Main I Protectionand Bus Bar protection
1 Two Distance Protection
[shall be of two different make (i.e.from different manufacturers) or ofsame make with two differentplatforms with same specifications]-Main-I Protection &-Main II Protection
Numerical Relays with IEC
61850 Protocol
2 Two Stage Over Voltage Protection- Stage I- Stage II
Integrated in Main I & Main IIProtection.
220 KV Lines
3 Local Breaker Backup (LBB)Protection.
Integrated in Main I Protectionand Bus Bar protection
1 Directional O/C & E/F Protection Integrated in Bay Control &
Protection Unit (BCPU) with IEC61850 Protocol
66 KV Lines
2 Local Breaker Backup (LBB)Protection.
Integrated in BCPU
8/20/2019 Protection Philosophy R1
http://slidepdf.com/reader/full/protection-philosophy-r1 3/4
GETCO / E / 4S-001/ PP - 015 – 1A / R1 Dt. 05.11.2011
Page 3 of 4
B) Power Transformer Protection
Equipment Protection Adopted Type of Relay
1 Differential Protection Numerical Relay with IEC61850 Protocol
2 Restricted Earth Fault Protection Numerical Relays with IEC
61850 Protocol3 Directional O/C & E/F Protection
(on HV & LV side)Numerical Relays with IEC61850 Protocol
4 Over Fluxing Protection- 400KV side
- 220KV side
-Integrated in DifferentialProtection
- Separate static relay
5 Local Breaker Backup (LBB) Protn.- 400 KV side
- 220 KV side
-Integrated in DifferentialProtection and Bus Bar
protection
-Integrated in Dir. O/C & E/FProtection & Busbar protection
6 Buchholz Relay Integrated in Transformer,
7 Pressure Relief Device Integrated in Transformer
8 Oil & Wdg Temp. Alarm & Tripping Integrated in Transformer
9 OLTC Oil Surge Relay Integrated in Transformer
400/220 KV Transformer
10 Oil Level Low Alarm Integrated in Transformer
1 Reactor Differential Protection Numerical Relay with IEC61850 Protocol
2 Restricted Earth Fault Protection Numerical Relays with IEC61850 Protocol
3 Backup impedance protection Numerical Relays with IEC61850 Protocol
4 Buchholz Relay Integrated in Reactor
5 Pressure Relief Device Integrated in Reactor
6 Oil & Wdg Temp. Alarm & Tripping Integrated in Reactor
400 KV Bus reactor
7 Oil Level Low Alarm Integrated in Reactor
1 Differential Protection Numerical Relay with IEC61850 Protocol
2 Restricted Earth Fault Protection(on HV & LV side)
Numerical Relays with IEC61850 Protocol
3 Directional O/C & E/F Protection(HV side)
Numerical Relays with IEC61850 Protocol
4 Directional O/C & E/F Protection (LVside)
Integrated in Bay Control &Protection Unit (BCPU) with IEC61850 Protocol
220/66KV Transformer
5 Over Fluxing Protection Integrated in DifferentialProtection
8/20/2019 Protection Philosophy R1
http://slidepdf.com/reader/full/protection-philosophy-r1 4/4
GETCO / E / 4S-001/ PP - 015 – 1A / R1 Dt. 05.11.2011
Page 4 of 4
6 Local Breaker Backup (LBB) Protn.- 220 KV side
- 66 KV side
-Integrated in DifferentialProtection and Bus Barprotection
- Integrated in BCPU7 Buchholz Relay Integrated in Transformer
8 Pressure Relief Device Integrated in Transformer
9 Oil & Wdg Temp. Alarm & Tripping Integrated in Transformer
10 OLTC Oil Surge Relay Integrated in Transformer
11 Oil Level Low Alarm Integrated in Transformer
1 Differential Protection Numerical Relay with IEC61850 Protocol
2 Non Directional O/C & E/FProtection- 66 KV side
Integrated in Bay Control &Protection Unit (BCPU) with IEC61850 Protocol
3 Local Breaker Backup (LBB)Protection.
Integrated in BCPU
4 Buchholz Relay Integrated in Transformer
5 Pressure Relief Device Integrated in Transformer
6 Oil & Wdg Temp. Alarm & Tripping Integrated in Transformer
7 OLTC Oil Surge Relay Integrated in Transformer
66/11 KV Transformer
8 Oil Level Low Alarm Integrated in Transformer
C) Bus Coupler Protection
1 Non Directional O/C & E/FProtection
Integrated in Bay Control &Protection Unit (BCPU) with IEC61850 Protocol
66 KVBus coupler
2 Local Breaker Backup (LBB) Protn. Integrated in BCPU
D) Tie Bay Protection
1 Teed Differential Protection - LowImpedance
Numerical Relay with IEC61850 Protocol
400KVTie Bay
2 Teed Differential Protection - HighImpedance
Numerical Relay with IEC61850 Protocol
E) Bus Bar Protection
400 KV Bus bar 1 Augmentation of Existing Siemens
make Bus Differential Protectionscheme (Control unit - 7SS52Bay units – 7SS523)
Numerical Relay with IEC
61850 Protocol
220 KV Bus bar 1 Augmentation of Existing Siemensmake Bus Differential Protectionscheme (Control unit - 7SS52Bay units – 7SS523)
Numerical Relay with IEC61850 Protocol
E) Disturbance Recorder & Event Loggers
Integrated feature of protective relays is used to provide the information about the Disturbance andto log the events.
F) GPS based Time Synchronizing Equipment
Existing SANDS make SYNTIME Global Positioning System based Time Synchronizing Equipment(IEC 61850 compatible)