SECTION XUL EX-4510 4-1-05 Page 10-1
REV. 1
Electronic data processing involves storage, recall and useof information via electronic equipment. Electronic data pro-
cessing equipment is found in almost every industry today.
The equipment is very sensitive and operates within minute
tolerances. Additionally, many computer installations are
designed with a subfloor area containing data and power
cable bundles.
Because of the high dollar valve of the equipment, the data
managed by that equipment and the productivity provided
by electronic data processing, rapid detection and efficient
fire protection are imperative. Time lost to cleanup and ven-
tilation of a computer room means lost time throughout the
company, so these areas require a clean, no residue gas
agent that disperses easily.
The computer room and subfloor space can be protected
with an SAPPHIRE suppression system, even when the
computer room is normally occupied.
Fires can occur within the computer electrical insulation and
in the cable bundles in the subfloor. Paper debris that has
been allowed to accumulate in the subfloor is also a source
of fuel.
Computer room/subfloor protection can be accomplished by
installation of a total flood SAPPHIRE system. The
system is designed in accordance with the ANSUL design,
installation manual and NFPA Standard 2001, Standard for
Clean Agent Fire Extinguishing Systems. It is importantthat an effective agent concentration not only be achieved,
but shall be maintained for a sufficient period of time to
allow effective emergency action by trained personnel.
The SAPPHIRE system consists of a tank(s), a piping
arrangement and discharge nozzles located in the comput-
er room, storage room, and subfloor space.
Occasionally, drainage is installed in the subfloor area.
Provisions must be made for making the drain piping a
closed system unless water is present to assist in assuring
the necessary concentration.
When the computer room is normally occupied, personnel
safety is of first concern. Alarms or warning devices mustbe located in the room to provide sufficient annunciation of
agent discharge. The rooms and subfloor must be tight to
prevent loss of agent.
All air handling equipment must be shut down and
dampered prior to system discharge.
Smoke detectors, operated by an electronic control panel,
are usually employed with a SAPPHIRE system to provide
detection and thus suppression of a fire before it has a
chance to do serious damage.
The authority having jurisdiction may have additiona
requirements.
HAZARD
A computer room having dimensions of 33 ft. x 15 ft. x
10 ft.
A storage room having dimensions of 12 ft. x 12 ft. x 10 ft
A subfloor having dimensions of 33 ft. x 15 ft. x 1 ft.
No unclosable openings.
Ventilation to be shut down at system actuation.
Example Computer Room,Storage Room, and Subfloor
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
2/18
SECTION XUL EX-4510 12-1-03 Page 10-2
Example Computer Room, Storage Room, and Subfloor
10 FT.
10 FT.
12 FT.
33 FT.
1 FT.
12 FT.
006891
15 FT.
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
3/18
SECTION XUL EX-4510 12-1-03 Page 10-3
Example Computer Room, Storage Room, and Subfloor
006905a
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
4/18
SECTION XUL EX-4510 12-1-03 Page 10-4
Example Computer Room, Storage Room, and Subfloor
006905b
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
5/18
SECTION XUL EX-4510 12-1-03 Page 10-5
Example Computer Room, Storage Room, and Subfloor
006905c
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
6/18
SECTION XUL EX-4510 12-1-03 Page 10-6
Example Computer Room, Storage Room, and Subfloor
006905d
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
7/18
SECTION XUL EX-4510 4-1-05 Page 10-7
REV. 1
Example Computer Room, Storage Room, and Subfloor
006905e
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
8/18
SECTION XUL EX-4510 12-1-03 Page 10-8
Example Computer Room, Storage Room, and Subfloor
006905f
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
9/18
SECTION XUL EX-4510 12-1-03 Page 10-9
Example Computer Room, Storage Room, and Subfloor
006905g
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
10/18
SECTION XUL EX-4510 12-1-03 Page 10-10
Example Computer Room, Storage Room, and Subfloor
006906a
John M KehoeOne Stanton Street
Marinette WI 54143-2542Phone: 715-735-7411
Sapphire Designer ProgramProject: Example
File Name: Manual1.FLC
Customer InformationCompany Name: Ansul Incorporated
Address:
Phone:
Contact:
Title:
John M. Kehoe
Project DataProject Name: Example
Designer:
Number:
Account:
Location:
Description:
Anywhere, USA
Computer Room, Subfloor and Storage Room
Consolidated Report
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 1 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
11/18
SECTION XUL EX-4510 12-1-03 Page 10-11
Example Computer Room, Storage Room, and Subfloor
006906b
Consolidated Report
Elevation: 4000 ft (relative to sea level)
Atmospheric Correction Factor: 0.86
Enclosure Information
Enclosure Number: 1
Name: Computer Room
Enclosure Temperature...
Minimum: 60 F
Maximum: 80 F
Maximum Concentration: 4.388 %
Design Concentration...
Adjusted: 4.216 %
Minimum:
Minimum Agent Required:
Width:
Length:
Height:
Volume:
Non-permeable:
Total Volume:
Adjusted Agent Required:
Number of Nozzles:
4.200 %
165.2 lbs
33.0 ft
15.0 ft
10.0 ft
4950.0 cubic ft
0.0 cubic ft
4950.0 cubic ft
165.8 lbs
2
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 2 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
12/18
SECTION XUL EX-4510 12-1-03 Page 10-12
Example Computer Room, Storage Room, and Subfloor
006906c
Consolidated Report
Elevation: 4000 ft (relative to sea level)
Atmospheric Correction Factor: 0.86
Enclosure Information
Enclosure Number: 2
Name: Storage Room
Enclosure Temperature...
Minimum: 60 F
Maximum: 80 F
Maximum Concentration: 4.386 %
Design Concentration...
Adjusted: 4.213 %
Minimum:
Minimum Agent Required:
Width:
Length:
Height:
Volume:
Non-permeable:
Total Volume:
Adjusted Agent Required:
Number of Nozzles:
4.200 %
48.1 lbs
12.0 ft
12.0 ft
10.0 ft
1440.0 cubic ft
0.0 cubic ft
1440.0 cubic ft
48.2 lbs
1
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 3 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
13/18
SECTION XUL EX-4510 12-1-03 Page 10-13
Example Computer Room, Storage Room, and Subfloor
006906d
Consolidated ReportAgent Information
Agent: Novec / Propellant N2
(Novec is a trademark of 3M)
Adjusted Agent Required: 214.0 lbs
Container Name: 390 lb Cylinder Assemby
Container Part Number: 570640
Number of Main Containers:
Number of Reserve Containers:
1
0
Manifold: No Manifold
HorizontalPipe Take Off Direction:
Agent Per Container: 214.0 lbs
Fill Density: 41.2 lbs / cubic ft
Container Empty Weight: 198.2 lbs
Weight, All Containers + Agent: 412.2 lbs
Floor Area Per Container: 1.40 square ft
Floor Loading Per Container: 295 lbs / square ft
360 psigStarting Pressure:
Pipe NetworkPart 1 - Pipe
Description Start End Type Diameter Length Elevation
Pipe
Main Cyl. X 1 0 1 2 in 4.44 ft 4.44 ft
Flex Hose 1 2 2 in 0.39 ft 0.00 ft
Flex Hose 2 3 2 in 1.71 ft 1.71 ft
Pipe 3 4 40T 2 in 4.45 ft 4.45 ft
Pipe 4 5 40T 1-1/4 in 2.25 ft 0.00 ftPipe 5 6 40T 1-1/4 in 1.50 ft 0.00 ft
Pipe 6 7 40T 1-1/4 in 17.00 ft 0.00 ft
Pipe 7 8 40T 1-1/4 in 1.25 ft 0.00 ft
Pipe 8 9 40T 1 in 8.25 ft 0.00 ft
Pipe/E1-N1 9 10 40T 1 in 0.75 ft -0.75 ft
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 4 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
14/18
SECTION XUL EX-4510 12-1-03 Page 10-14
Example Computer Room, Storage Room, and Subfloor
006906e
Consolidated ReportPart 1 - Pipe
Description Start End Type Diameter Length Elevation
Pipe
Pipe 8 11 40T 1 in 8.25 ft 0.00 ft
Pipe/E1-N2 11 12 40T 1 in 0.75 ft -0.75 ft
Pipe 5 13 40T 3/4 in 1.00 ft 0.00 ft
Pipe 13 14 40T 3/4 in 4.25 ft 0.00 ft
Pipe 14 15 40T 3/4 in 4.50 ft 0.00 ft
Pipe/E2-N1 15 16 40T 3/4 in 0.75 ft -0.75 ft
Part 2 - Equivalent LengthStart End 90 45 Thru Side Union Other Added Total
0 1 0 0 0 0 0 0.00 ft 35.0 ft
1 2 0 0 0 0 0 2inFlexN1 0.00 ft 0.4 ft
2 3 1 0 0 0 0 2inFlexN2 0.00 ft 17.2 ft
3 4 0 0 0 0 0 0.00 ft 4.5 ft
4 5 1 0 0 0 0 0.00 ft 6.0 ft
5 6 0 0 1 0 0 0.00 ft 3.8 ft
6 7 1 0 0 0 0 0.00 ft 20.7 ft
7 8 1 0 0 0 0 0.00 ft 5.0 ft
8 9 0 0 0 1 0 0.00 ft 14.0 ft
9 10 1 0 0 0 0 0.00 ft 3.6 ft
8 11 0 0 0 1 0 0.00 ft 14.0 ft
11 12 1 0 0 0 0 0.00 ft 3.6 ft
5 13 0 0 0 1 0 0.00 ft 5.5 ft
13 14 1 0 0 0 0 0.00 ft 6.5 ft
14 15 1 0 0 0 0 0.00 ft 6.7 ft
15 16 1 0 0 0 0 0.00 ft 3.0 ft
Part 3 - Nozzles
Start End Flow Name Size Type Nozzle Area0 1 214.0 lbs
1 2 214.0 lbs
2 3 214.0 lbs
3 4 214.0 lbs
4 5 214.0 lbs
5 6 165.8 lbs
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 5 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
15/18
SECTION XUL EX-4510 12-1-03 Page 10-15
Example Computer Room, Storage Room, and Subfloor
006906
Consolidated ReportPart 3 - Nozzles
Start End Flow Name Size Type Nozzle Area
6 7 165.8 lbs
7 8 165.8 lbs
8 9 82.9 lbs
9 10 82.9 lbs E1-N1 1 in 16 Port - BR 0.2963 square in
8 11 82.9 lbs
11 12 82.9 lbs E1-N2 1 in 16 Port - BR 0.2963 square in
5 13 48.2 lbs
13 14 48.2 lbs
14 15 48.2 lbs
15 16 48.2 lbs E2-N1 3/4 in 16 Port - BR 0.2524 square in
Parts Information
Total Agent Required: 214.0 lbs
Container Name: 390 lb Cylinder Assemby (Part: 570640)
Number Of Containers: 1
Field1
Nozzle Type Diameter Nozzle Area Part Number
E1-N1 16 Port - BR 1 in 0.2963 square in 570517
E1-N2 16 Port - BR 1 in 0.2963 square in 570517
E2-N1 16 Port - BR 3/4 in 0.2524 square in 570516
Nozzle Drill Diameter Drill Size
E1-N1 0.1535 inches 3.90 mm
E1-N2 0.1535 inches 3.90 mm
E2-N1 0.1417 inches 3.60 mm
Pipe: Type Diameter Length
40T 3/4 in 10.50 ft
40T 1 in 18.00 ft
40T 1-1/4 in 22.00 ft
40T 2 in 4.45 ft
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 6 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
16/18
SECTION XUL EX-4510 4-1-05 Page 10-16
REV. 1
Example Computer Room, Storage Room, and Subfloor
006906g
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
17/18
SECTION XUL EX-4510 12-1-03 Page 10-17
Example Computer Room, Storage Room, and Subfloor
006906h
Consolidated ReportMinimumAgent
RequiredNozzle
AdjustedAgent
Required
PredictedAgent
Delivered
NozzlePressure(Average)
E2-N1 48.1 lbs 48.2 lbs 48.9 lbs 142 psig
Drawing View: 1
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 8 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM
-
8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example
18/18
SECTION XUL EX-4510 12-1-03 Page 10-18
Example Computer Room, Storage Room, and Subfloor
006906i
Consolidated ReportDrawing View: 5
Drawing View: 9
Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated
Page: 9 9of
Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM