Shared Services PartnershipF iliti S iFacilities Services
Fire Compartmentationi H lthin Healthcare
Prince Philip Hospital - Thursday 7th November 2013Ysbyty Glan Clwyd - Tuesday 19th November 2013
Royal Glamorgan Hospital Thursday 21st November 2013Royal Glamorgan Hospital - Thursday 21st November 2013
![Page 2: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/2.jpg)
Shared Services PartnershipF iliti S iFacilities Services
Common Problems&
S SFire Stopping Solutions
![Page 3: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/3.jpg)
Standards & Guidance(S ) f fAD B3 (Sect 10) - Protection of openings and fire stopping
10 2 ‘If a fire-separating element is to be effective10.2 If a fire-separating element is to be effective, every joint or imperfection of fit, or opening to allow services to pass through the element, should be adequately protected by sealing or fire stopping soadequately protected by sealing or fire-stopping so that the fire resistance of the element is not impaired’
10.17 adds the requirement that:Joints between fire separating elements should be fire stopped; andp g pp ;All openings for pipes, ducts, conduits or cables to pass through any part of a fire separating element should be:• Kept as few in number as possible; and• Kept as small as practical; and• Fire stopped (which in the case of a pipe or duct should allow for• Fire stopped (which in the case of a pipe or duct, should allow for
thermal movement).
![Page 4: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/4.jpg)
Pipe Wraps & Collarsp pHTM05/02 Clause 6.16 - To maintain the integrity of compartmentation, openings should be limited to:
b. openings for pipes of not more than 160mm diameter which, if exposed to a temperature of
p g
diameter which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flames or hot gases will pass through the wall of the pipe;wall of the pipe;
c. pipes of materials other than those in (b) above of not more than 40mm diameter;;
d. pipes of any diameter which are provided with a proprietary seal which has been shown by test (for the diameter of pipe proposed) to maintain the fire resistance of the compartment structure;
![Page 5: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/5.jpg)
Pipe Wraps & C llCollars
SleevingCast in slab or belowCast in slab or belowOne or both sides of wall
Hilti CP645PFC CorofilPFC CorofilRockwool Fire Pro
![Page 6: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/6.jpg)
Pipe WrapsPipe Wraps
![Page 7: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/7.jpg)
![Page 8: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/8.jpg)
![Page 9: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/9.jpg)
Pipe WrapsPipe Wraps
![Page 10: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/10.jpg)
Check the fieldof application
Ensure installationi t ti f ll dof application instructions are followed
If in doubt refer toIf in doubt refer to product testing details
Refer to allRefer to all documentation
![Page 11: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/11.jpg)
Coordination issues
Solution to maintain FRReposition or ‘box-out’
![Page 12: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/12.jpg)
PU Expanding FoamPolyurethane Foamp gy
Normal PU Expanding Foam is not an intumescent productan intumescent product
(i.e. It will not expand when heated).
![Page 13: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/13.jpg)
Which of these is ‘fire rated’?
A B C
Methods for identification: -Coloured pigmentsPot of paint, and/orLabels
R l ti 38 P i i f i f tiRegulation 38 – Provision of information.
![Page 14: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/14.jpg)
PU ‘Fire-Block’ Foam
![Page 15: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/15.jpg)
PU ‘Fire Rated’ Foam Many ‘fire-rated’ PU foams are available
& product identification difficult‘Reaction to Fire’ B1 & B2 Rating
DIN 4102 Claimed periods of fire resistance are
achieved under strictly controlled test conditions, with a high standard of quality
DIN 4102
, g q ycontrol for installation of sample tested
Products used on site Often used on irregular shaped openings
of varying widths beyond scope of application (hollow stud partitions)
Do contractors understand the limitations of products in use?Littl lit t l ( id l t l Little quality control (are voids completely filled?)
Before specifying/using any product p y g g y pensure it’s fit for the intended application review test reports. Up to 5 hours protection
![Page 16: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/16.jpg)
Fire Test 117611Horizontal exposure220mm Masonry Wall220mm Masonry Wall
Vertical exposureVertical exposure250mm Concrete Floor
![Page 17: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/17.jpg)
Horizontal Apertures Through Wall220 M W ll220mm Masonry Wall
Integrity Insulation (mins) (mins)
71 69
240 240
86 86
240 240
240 240
![Page 18: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/18.jpg)
Vertical Apertures Through Floor250 C t Sl b250mm Concrete Slab
Integrity 240 240 115 59 206
Insulation 240 240 113 58 206
![Page 19: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/19.jpg)
PU Foam and Stud PartitionsAd-hoc fire resistance test f ll i i i l ffollowing principles of BS476:20:1987 testing regime
Integrity 94 minutesg yInsulation 69 minutes
![Page 20: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/20.jpg)
PU Expanding Foamp g
![Page 21: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/21.jpg)
Expanding / Intumescent FoamExpanding / Intumescent Foam
Re-penetrable
Graphite and PU based, two part,
intumescent sealant
Tested in unlined dry wall openings up towall openings up to
400 x 400mm
![Page 22: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/22.jpg)
Fire Seals for Electrical P t tiPenetrations
IET Regs (17th edition):–IET Regs (17th edition):527.1.2 A wiring system shall be installed so that the general
building structural performance and fire safety are g p ynot reduced
527.2.1 Where a wiring system passes through elements of g y p gbuilding construction such as floors, walls ...., the opening remaining after passage of wiring system shall be sealed according to the degree of fireshall be sealed according to the degree of fire resistance (if any) prescribed for the respective element of building construction before penetration
611.3 vii Requires inspection of the presence of fire barriers and suitable seals – before being put into service.
![Page 23: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/23.jpg)
Trays, Cables & Pillowsy ,
Polystyrene infill at head of wall
![Page 24: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/24.jpg)
Trays, Cables & Pillowsy ,
![Page 25: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/25.jpg)
Trays, Cables & Pillowsy ,
Pl ti bl ti ?Plastic cable ties?
Date, size and unique reference numberreference number
![Page 26: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/26.jpg)
Trays, Cables & Pillowsy ,
![Page 27: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/27.jpg)
Removable pillow secured to cable traysecured to cable tray
![Page 28: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/28.jpg)
Innovative ProductsHILTI - CFS-SL Fire SleeveHILTI - CFS-SL Fire Sleeve
![Page 29: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/29.jpg)
Wiremold LegrandWiremold LegrandFlamestopper (US Product)
![Page 30: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/30.jpg)
Abesco - CT120 Cable Transit System Easy Retro-fit
![Page 31: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/31.jpg)
Fire Seals for Electrical P t tiPenetrations
IET Regs (17th edition)527.2.2 A wiring system such as a conduit system, cable
ducting system, .... which penetrates elements of building construction having specified fire resistance shall beconstruction having specified fire resistance shall be internally sealed to the degree of fire resistance of the respective element before penetration ....p p
![Page 32: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/32.jpg)
Intumescent Putty Insertsy
![Page 33: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/33.jpg)
Fire Dampersp
HTM05 02 D1 t tHTM05-02 D1 states: -
All fire dampers should be installed so that they maintain their integrity against the passage of fire for the required period of fire resistanceagainst the passage of fire for the required period of fire resistance
A fire damper should be adequately fixed into, or to, the construction it is protecting.
![Page 34: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin](https://reader033.vdocument.in/reader033/viewer/2022060216/5f0611ee7e708231d41623d2/html5/thumbnails/34.jpg)
Fire/Smoke or Fire dampers dependent on wall designation
Fire rated ductwork in-lieu of dampers Kitchens, Isolation Rooms, Fume Cupds
Future workshops will specifically address Fire Dampers.