Download - SM6 Kit Assembly Instructions
-
7/29/2019 SM6 Kit Assembly Instructions
1/14
notice de kit
kit assemblyinstructions
surge arresters GAMcubicle level C
parafoudres pourcellule GAM niveau C
SM6
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
2/14
Les centres de services du
groupe Schneider Electric sontoprationnels pour :
ingnierie et assistance techniquemise en serviceformationmaintenance prventive etcorrectiveadaptationspices de rechange
Faites appel votre agentcommercial qui vous mettra enrelation avec le centre deservices du groupe Schneider
Electric le plus proche.
group Schneider Electric servicecenters are there for:
engineering and technicalassistancestart-uptraining
preventive and correctivemaintenanceadaptation workspare parts
Call your sales representative
who will put you in touch withyour nearest group SchneiderElectric service centre.
Edition du : 09/10/2009S1A23043 revision : 00
En raison de lvolution des normes et du matriel,les caractristiques indiques par le texte et les imagesde ce document ne nous engagent quaprs confirmationpar nos services.
Conception, rdaction: Service DocumentationTechnique T&D
As standards, specifi cations and designs change from timeto time, please ask for confirmation of the information givenin this publication.
SCHNEIDER ELECTRIC http://www.schneider --- electric.com
35 rue Joseph Monier
CS 30323
92506 RUEIL MALMAISON CEDEX
Tl : +33 (0)1 41 29 70 00
Fax :+33 (0)1 41 29 71 00 Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
3/14
INFORMATION--CONSEIL
Nous attirons votre attention sur ce point particulier
DANGER
AVERTISSEMENT suivant iso 3864---2
suivant iso 3864---2
suivant iso 3864---2
ATTENTION
as per iso 3864---2
as per iso 3864---2
as per iso 3864---2
DANGER : si cette directive nest pas respecte,cela entranera la mort ou blessures graves.
DANGER: failure to follow thisinstruction will result in death or seriousinjury.
AVERTISSEMENT : si cette directive nest pas respecte,cela peut entraner la mort ou blessures graves.
WARNING: failure to follow this instruction may result in death or seriousinjury.
ATTENTION : si cette directive nest pas respecte,cela peut entraner des blessures.
Ce signal dalerte peut galement tre utilis pour signalerdes pratiques pouvant entraner des dommages pour le matrielRM6.
CAUTION: failure to follow this instruction may result in injuries.This alert signal can also be used to indicate practices that coulddamage the RM6 unit.
INFORMATION- ADVICE
We draw your attention to this specific point.
WARNING
CAUTION
S1A23043 revision : 00 1
symboles etconventions
symbols andconventions
Attention :vous trouvez lensemble
de ces symbolesci---dessous durantlintgralit du document,vous indiquant les degrsdes dangerosits selon lesdiffrentes mises ensituation.
Caution:you will find all the symbols
below throughout thedocument, indicatingthe hazard levelsdepending on thedifferent types of situation.
SCHNEIDER ELECTRIC votreservice/ foreword
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
4/142 S1A23043 revision : 00
contacter lunit servicede Schneider Electric pour
diagnostics et conseils
contact the SchneiderElectric service unit for
diagnosis and advice
Faites appel votre agentcommercial qui vousmettra en relation avec lecentre de services dugroupeSCHNEIDER ELECTRICle plus proche.
www.schneider--electric.comvous pouvez vous connectersur :
Call your sales representative who
will put you in contact with the closest
SCHNEIDER ELECTRIC group service
centre.
You can log on to:
www.schneider---electric.com
rgles de diffusion
distribution rulesATTENTION
CAUTION
Le but de cette publicationest de permettre linstallationcorrecte du matriel SM6.
The aim of this publicationis to enable the SM6 unitto be installed correctly.
ATTENTIONCAUTION
La reproduction totale ou partiellede ce manuel est interdite et seulsles agents de Schneider Electricpossdent un droit exclusifdutilisation.
This document is not a commercialdocument.It is a strictly technicaldocument drawn up bySchneider Electric.
rgles de scurit
safety rules
ATTENTIONCAUTION
Toutes les oprations dcritesci---aprs doivent tre effectuesen respectant les normes descurit en vigueur, sous laresponsabilit dune autorit
comptente.All the operations described belowmust be performed in compliancewith applicable safety standards,under the responsibilityof a competent authority.
AVERTISSEMENT
WARNING
Linstallateur doit tre habilitet autoris pour intervenir etmanipuler le matriel SM6.
The contractor must be certifiedand authorised to manipulateand perform work on the SM6unit.
ATTENTIONCAUTION
Nentreprenez le travail quaprsavoir lu et compris toutesles explications contenuesdans ce document.
Si la moindre difficult respecterces rgles se prsentait,veuillez vous adresser Schneider Electric.
Only undertake the work afterhaving read and understoodall the explanations given in thisdocument.If you have any difficultycomplying with these rules,
please contactSchneider Electric.
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
5/14
N.1
5
7
N.2 N.3
N.4 N.5
N.6 N.7
N.8 N.9
N.10 N.11
S1A23043 revision : 00 3
Contenu du kit S1A12712pour cellule GAM level C
Contents of kit S1A12712for cubicle GAM level C
tableau rfrence picesParts reference table
repre
repere
quantit
quantity
Nde pices
N parts
description
description
utilis pour parafoudre
used for surge arrestor
N1 1 3736266 collecteur horizontal/ horizontal collector HE30---HE21 ---HE15 ---HE12 ---HE9
N2 3 3736264 collecteur intermediaire/ intermediatecollector
HE30---HE21---HE15---HE12---HE9
N3 3 3736263 support/ support HE30---HE21---HE15---HE12---HE9
N4 1 3731025 tresse/ braid HE30---HE21---HE15---HE12---HE9
N5 3 3730633 connexion / connection HE30
N6 3 51238721F0 entretoise/ spacer HE30---HE21---HE15
N7 3 3730634 connexion / connection HE21---HE15---HE12---HE9
N8 3 51238720F0 entretoise/ spacer HE12---HE9
N9 6 3736275 entretoise/ spacer HE15(qte3)---HE12---HE9(qte6)
N10 1 S1A12540 sachet visserie/ srews and bolts bag HE30---HE21---HE15---HE12---HE9
N11 1 S1A23043 manuel dinstructions/ instructionsmanual
HE30---HE21---HE15---HE12---HE9
description du kit/description of the kit
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
6/14
A
4 S1A23043 revision : 00
prparation de lacellule
Enlever la tleinter---cellule A pour aiderau montage desparafoudres
preparing the cubicle
Remove the inter---cubiclepartition A to facilitatemounting the surgearresters
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
7/14
12
3
12
3
N.10
S1A12540
1
2
3
4
5
6
N.10
S1A12540
S1A23043 revision : 00 5
pr---quip lextrieur dela cellule
Monter 3 crous--cage M8) surla poutre parafoudre
pre ---equipping the cubicleexterior
Mount 3 cage---nuts M8 (onthe cubicle exterior) on thesurge arrester beam
pr---quip lintrieur de lacellule
Monter 6 vis--cage M6x20 (lintrieur de la cellule) sur lapoutre parafoudre
pre ---equipping the cubicleinterior
Mount 6 cage---nuts M6x20 (on
the cubicle interior) on thesurge arrester beam
pr--quipement de la cellule GAM /pre ---equipping the GAM cubicle
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
8/14
BB
3
2
1
3
1
2
1
N.10
N.10
N.10
6 S1A23043 revision : 00
principe dassemblage despices du kit S1A12712
HE30--HE21--HE15--HE12--HE9
Important : ne pas serrerlensemble de la visserie afin depermettre dajuster ulterieurementles pices 1,2 et 3.
RAPPEL
Le tableau reference des picesest disponible dans le chapitreprecedent description.
N
3: support (3736263) x3
Mode de fixation : 6 rondellescontacts de 6 mm+ 6 crou M6.
N2 : collecteur intermediaire(3736264) x3
N1 : collecteur horinzontal(3736266) x1
Nota : il est conseill de raliser lemontage des collecteurs (1) et (2)simultanment.
Mode de fixation : 3 rondellescontacts de 8 mm+ 3 visHM8.25
principle for assembling theparts in the S1A12712 kit
HE30---HE21---HE15---HE12---HE9
Important: do not tightenall the screws so thatit is possible to subsequentlyadjust the parts 1,2 and 3.
REMINDER
The parts reference table isavailable in the previous chapterdescription.
No. 3: support(3736263) x3Fastening method: 6 contactwashers 6 mm + 6 nuts M6.
No. 2: intermediate collector(3736264) x3
No. 1: horizontal collector(3736266) x1
Note: It is recommended to mount
the collectors (1) and (2)simultaneously.
Fastening method: 3 contactwashers 8 mm + 3 screwsHM8.25
principe dassemblage pour parafoudreHE30--HE21--HE15--HE12--HE9/
surge arrester assembling principleHE30---HE21---HE15---HE12---HE9
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
9/14
A
3736266
4
4
partie suprieure
partie infrieure
4
A
B
N.10
N.10
upper part
lower part
S1A23043 revision : 00 7
prparation de la tresse dela mise la terre
avant montageDmonter lcrou A ( M 8 ) etrondelle contact ( 8 mm).
preparing the earthingbraid
before mounting
Remove the nut A (M8) andthe contact washer ( 8 mm).
montage de la tresse demasse
3731025
4
AB
A : partie suprieure
La tresse (4) se fixe sur lecollecteur horizontal (3736266).
Mode de fixation : 2 rondellescontacts ( 8 mm) + 1 visHM8.25, crou M8.
B : partie infrieure
Mode de fixation : rondellecontacts ( 8 mm) + crou M8.
mounting the earthing braid
A : upper partThe braid(4) is fixed on the
horizontal collector(3736266).
Fastening method: 2 contactwashers ( 8 mm) + 1 screwHM8.25, nut M8.
B : lower part
Fastening method: contactwashers ( 8 mm) + nut M8.
adaptation de la tresse de masse/adapting the earthing braid
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
10/14
N.3
x3
A
A
N.10
barre GAM N.6
N.5
N.6
partie basse
partie haute
connection barre GAM
x3
x3
N.5
N.6
N.5
N.10
N.10
N.5
lower part
upper part
GAM bar
GAM bar connection
8 S1A23043 revision : 00
montage de 3 parafoudresde type (HE30)
niveau infrieur de lacellule (1re tape)
Adapter les 3 parafoudres A(1 parafoudre par phase) sur les 3supports existants N3
Fixation par 3 rondelles contacts 12+3 vis HM12.30, utiliser lesachet visserie N10.
mounting 3 HE30 surgearresters
lower section of thecubicle (1st step)
Adapt the 3 surge arresters A(1 surge arrester/per phase) on the3 existing supports no. 3
Fastening with 3 contact washers 12 + 3 screws HM 12.30, usethe screw sachet no. 10.
2 me tape
partie haute :
Fixation des 3 connexions N5 surles barres GAM avec 3 rondellescontacts 10 + 3 crous M10.
2nd step
upper part :
Fastening the 3 connections no. 5
on the GAM bars with 3 contactwashers 10 + 3 nuts M10.
partie basse :
Monter les 3 entretoises N6 etles connections N5.
Fixation sur parafoudre : 3rondelles Grower 12 et 3 visHM12.50.
lower part :
Mount the 3 spacers no. 6 and theconnections no. 5.
Fastening on surge arrester: 3Grower washers 12 and 3
screws HM12.50.
adaptation dun parafoudre de typeHE30 / adapting a HE30 surge arrester
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
11/14
N.3
x3A
A
N.10
barre GAM
N.7
N.7
N.6
N.7
N.6
lower part
partie haute
GAM bar connection
x3
x3 N.10
N.10upper part
connection barre GAM
GAM bar
partie basse
S1A23043 revision : 00 9
montage de 3 parafoudresde type (HE21)
niveau infrieur de lacellule (1re tape)
Adapter les 3 parafoudres (1parafoudre par phase) A sur les 3supports existants N3
Fixation par 3 rondelles contacts12+3 vis HM12.30, utiliser lesachet visserie N10.
mounting 3 HE21surge arresters
lower section of thecubicle (1st step)
Adapt the 3 surge arresters A(1 surge arrester per phase) on the3 existing supports no. 3
Fastening with 3 contact washers12 + 3 screws HM12.30, use the
screw sachetno. 10.
2 me tape
partie haute :
Fixation des 3 connexions N7 surles barres GAM avec 3 rondellescontacts 10 + 3 crous M10.
2nd step
upper part :
Fastening the 3 connections no. 7on the GAM bars with 3 contactwashers 10 + 3 nuts M10.
partie basse :
Fixation des 3 entretoises N6 etles 3 connexions N7.
Fixation sur parafoudre : 3rondelles Grower 12 et 3 visHM12.50.
lower part :
Mount the 3 spacers no. 6 and theconnections no. 7.
Fastening on surge arrester: 3Grower washers 12 and 3
screws HM12.50.
adaptation dun parafoudre de typeHE21/ adapting a HE21 surge arrester
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
12/14
N.3
x3
A
A
N.10
N.9
N.6
N.7
N.7
GAM bar connection
N.7
N.7
x3
N.10
x3
A B
lower mounting upper mounting
A B
N.10
connection barre GAM
montage infrieur montage suprieur
10 S1A23043 revision : 00
montage de 3 parafoudresde type (HE15)
niveau infrieur de lacellule (1re tape)
Adapter les 3 parafoudres (1parafoudre par phase) A sur les 3supports existants N3
Fixation par 3 rondelles contacts12+3 vis HM12.30, utiliser lesachet visserie N10.
mounting 3 HE15 surgearresters
lower section of thecubicle (1st step)
Adapt the 3 surge arresters A(1 surge arrester/per phase) on the3 existing supports no. 3
Fixation par 3 rondelles contacts12+3 vis HM12.30, utiliser le
sachet visserie N10.
2 me tape
H A : partie basse, monter les 3entretoises (1 entretoise parphase) N9, ainsi que les 3entretoises (1 entretoise parphase) N6 et les 3 connexionsN7.
Fixation sur parafoudres :3rondelles Grower 12 et 3 visHM12.90.
2nd step
H A : lower part, mount the 3
spacers (1 spacer per phase)no. 9, as well as the 3 spacers(1 spacer per phase) no. 6 andthe 3 connections no. 7.
Fastening on surge arresters: 3Grower washers 12 and 3 screwsHM12.90.
H B : partie haute ,fixation des 3connexions N7 sur les barres dela GAM par 3 rondelles contacts10 et 3 crous M10.
H B : upper part, fastening of the3 connections no. 7 on the GAM
bars with 3 contact washers10 and 3 nuts M10.
adaptation dun parafoudre de type HE15/adapting a HE15 surge arrester
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
13/14
N.8
N.3surge arresters
B
N.10
parafoudres
N.10
N.9
N.7
N.7
N.7
N.7
N.10
N.7
N.7N.10
N.7N.10N.10
connection barre
GAM
N.10
S1A23043 revision : 00 11
montage parafoudres (HE9
ou HE12)
niveau infrieur de la cellule(1 re tape)
Monter les 3 entretoises N8 et les3 parafoudres B sur les 3 supportsN3Fixation par 3 rondelles contacts 12 et 3 vis HM12x50, utiliser lesachet visserie N10.
mounting surge arresters(HE9 or HE12)
lower section of the cubicle
(1st step)Mount the 3 spacers no. 8 and the3 surge arresters B on the 3
supports no.3Fastening with 3 contact washers12 and 3 screws HM12x50, usethe screw sachet no. 10.
2me tape : partie basse
Monter les 6 entretoises N9 avecles 3 connexions N7.
Fixation sur parafoudre par 3rondelles Grower 12 et 3 vis
HM12.110
2nd step: lower part
Mount the 6 spacers no. 9 with the3 connections no. 7.
Fastening on surge arrester with 3Grower washers 12 and 3 screwsHM12.110
partie haute :
Fixation des 3 connexions N7 surles barres GAM avec 3 rondellescontacts 10 + 3 crous M10.
upper part :
Fastening of the 3 connectionsno. 7 on the GAM bars with 3contact washers 10 and 3 nutsM10.
adaptation dun parafoudre de type HE9ou HE12 / adapting a HE9 or HE12 surge
arrester
Released for ManufacturingPrinted on 2010/06/24
-
7/29/2019 SM6 Kit Assembly Instructions
14/14
A
vrification aprsmontageAprs assemblage desparafoudres, sassurer que toutesles pices sont correctementbloquesRemettre la tle inter---cellule A.
checking aftermounting
After assembling the surgearresters, ensure that all the partsare blocked properly
Refit the inter---cubicle partition A.
verification /verification
Released for Man fact ring