WGQH series high voltage solid soft starter

6KV、10KV/300KW-9000KW

Preface

Thanks for selecting WGQH Series Liquid Starter from Worldwide Electric Co., Ltd. It is a high-tech product

suitable for various load class drive motors such as production machineries, fan and water pump, integrating soft

starter、energy saving and protection. It is designed by our company with many years of experiences and we are

responsible for professional production and sales.

This manual provides the user with the relevant precautions for installation, setting of operating parameters,

abnormality diagnosis, routine maintenance and safety operation. Please read this manual carefully before

installation to ensure correct installation and operation of this product.

As regards our products and our service, all the staff of our company firmly believes the principle that the

customer is God. In case of any difficulty or unsettled problem arising in operation, please contact the dealer or

directly contact us.

After the arrival of the starter, check the product for its type, specification and etc. If any part of the product

does not go well with the written documents or materials due to updating, consult our company. Check quality

indicator, product manual, maintenance guaranteed manual and packing list. Contact the supplier if any problem.

Please keep this manual well, which will be helpful for maintenance, take-caring and other applications in the

coming future.

Unpacking for check

WGQH series solid soft starter for cage motor has passed the strict quality inspection and performance

testing before ex-factory. After purchasing, please check whether there is any damage due to careless

transportation, and whether the model of the product conforms to the ordered one prior to unpacking. In case of

any problem, please contact us or the supplier.

1. Check if the information attached to the equipment is complete and in line with the content of packing list of

the equipment.

2. Check the nameplate on the cabinet body to confirm that the equipment is in line with the ordered equipment.

3. Check whether the spare parts and components are damaged or lost. The spare parts and components shall be

governed by procurement contract.

Application environment

Rated voltage AC three-phase symmetric current, 6KV-10KV(+10%, -15%), 50HZ

Matching motor Standard three-phase AC asynchronous case induction motor

Startup frequency Frequent startup, time space is 10 minutes

Cooling-down method Natural cooling-down or force wind cooling

Phase order Working in the condition that input phase order is completely the same as output

Protection class III class

Page 2: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Capacity of relay contact IP20 IP30

Environment Altitude is not more than 2000 meters, no corrosive gas, no conductive dust, no

severe shock (less than 0.5G), well-ventilated.

Temperature -25℃ to +40℃

Storage temperature -40℃ to +70℃

Max relative humidity 5%- 95%

Note: Please notice us if you have special requirements

Safety Warnings

Warning!

Be free from raff handling or installation, rain and far away from the electromagnetic interference.

Warning!

Prevent the children and the public from touching or approaching to this equipment. This equipment, with

dangerous voltage, controls the dangerous rotary mechanism.

Warning!

This equipment shall be only used for the purpose specified by the manufacturer; any modification without

authorization or the operation not conforming to the regulations of this manual will result in severe personal

injury and other injuries.

Warning!

Please read the installation operation and safety instructions of maintenance in this manual carefully before

operating this equipment.

WGQH series high voltage solid soft starter is high voltage equipment which has a potential voltage that can

harm the human body. Only the authorized and trained persons can operate and maintain this equipment. For the

induction high voltage on the motor, it is dangerous after powering off. Thus the operation can be done only after

discharging.

All the panels and cabinet doors have to be closed during normal operating. Take care of the interlocks of the

high voltage switchgear and the soft starter because they are the important methods for safety.

There are high voltage power supply and control power supply of the soft starter. Pay attention to switching

off the control power supply after powering off the high voltage power supply before the operation. When operate

the charging equipment, do stand on an insulating plane to ensure that the operation men are not grounding.

The safe operation of this equipment need correct transportation, operation, installation and maintenance.

Special attention:

The application of the compensating capacitor: the reactive power compensating capacitor used for

improving the power factor can be connected only to the input terminal of WGQH. Do not connect it to the output

terminal to avoid the damage of the power elements of the silicon control.

The insulation test of the megohm meter: do not measure the insulation resistance between the input and

output terminals of WGQH, otherwise, the silicon control and the control panel may be damaged by overvoltage.

The megohm meter can measure the interphase insulation and phase-to-ground insulation of WGQH. But the

input terminals shall be short circuited respectively with the output terminals by three short circuit wires and all

the plugs shall be pulled out before measuring. The above principles have to be followed when measure the

insulation of the motor.

Page 3: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Chapter 1 Introduction

1.1. General

WGQH series high voltage solid soft starter is a new type soft starter for high and medium voltage AC motor

of the voltage below 10KV. It controls and protects the motor complexly by advanced control technology, electric

power and electron technology and the technology of series/parallel connection of the silicon control. Compare

with traditional starting methods, WGQH has the intelligent control mode, which not only can set the starting

torque, starting current, starting time and stopping parameter and other parameters, but also can inter-control with

the computer and PLC. It adopts original binding high quality thyristor and other import silicon control. It makes

the motor start and stop smoothly by stepless controlling the output voltage to avoid the harmful impact on the

electric network by starting overcurrent. Thus, large power motor can be used when the capacity of the electric

network is limited and the lifespan of the motor can be prolonged. High voltage AC motor has the advantages of

small volume, low consumption, high reliability and sensitivity, no contact, being free of maintenance, no

pollution and convenient installation and so on.

1.2 Advantages:

1. Reducing the starting current of the motor, reducing the distribution capacity, avoiding investment in capacity

increase

2. Reducing the mechanical stress in starting, prolonging the service life of motor and related equipment

3. The smooth starting and stopping avoid the surge problem and water hammer effect.

4. Variable starting modes and wide range of the current and voltage setting can apply to many kinds of load

occasions and be easy to improve the technology.

5. Perfect and reliable protection function can protect the motor and other relative equipments effectively.

6. It can apply to the occasion that frequent starting and stopping are needed.

1.3 Brief introduction to typical application

1. Water pump: use the control function of pump, in starting and stopping to reduce the water hammer of pump

flow due to the impact from liquid flow and saving the maintenance fee of the system;

2. Ball mill: by means of the slope starting of voltage, reduce the wearing of the gear torque, reduce the

workload of maintenance and prolong the service life;

3. Blower fan: replace traditional starter with the solid soft starter and reduce the wearing of belt and the

mechanical impact;

4. Compressor: realize smooth starting and reduce temperature rise of motor theough limiting the current ;

5. Crusher: avoid burning of the motor due to over-heat caused by mechanical fault and blockage via block

protection and fast protection;

6. Conveying machinery: realize smooth and gradual starting process and smooth speed-reducing stopping

process and avoid the damage to materials and equipment due to impact by means of soft starting and soft

stopping control.

Chapter 2 Working principles

High voltage thyristor softer device is series connected between three-phase AC voltage and the input

terminal of three-phase AC asynchronous/synchronous motor. It changes the effective value of three-phase input

Page 4: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

current in order to fulfill the aims of starting of constant current and the starting of some slope variety voltage.

After finishing starting, three-phase bypass contactor J automatically pulls-on and the motor is brought into the

service of electric network (see fig.1). In the condition without impact current, please see fig.2 for the oscillogram

of the input/output voltage and the variety of the current.

Chapter 3 Technical performance and characteristics

3.1 Technical Indexes

Specifications of product

standard of the product and

approval

Q/XWZ13--2008

range of the power 300kW--15000kW

Working power

Main line power supply 3AC 6~10KV±10% 50HZ

Control power supply: 3AC 380V±10% 3-phase 4-line 50HZ

Control board power supply: AC220±10% 50HZ

pressure loss of the starter below 1V when with bypass contactor

Trigger technology of the

thyristor CT trigger (optical or mix)

Rated tolerance capacity when

short circuit ≥20KA

Overload ability 500%/30S 120% of controller nominal

Technical parameter

Soft start time 0~180s can be set

Initial voltage 30~80% can be set

Page 5: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Rated current can be set

Kick time 200—800ms can be set

Start mode can be set(constant control、voltage slope、pulse kick)

Constant current coefficient can be set(times of rated current)

Start limit current 100%~600% can be set

Kick current 50%~80%可 can be set

Stop mode Free stop or soft stop

Soft stop time 0~30s can be set

Overload protection time 0~180s can be set

Control mode Can be selected

Protection function

I²t overload protection curve Auto inverse-time-limit protection, CPU control, protection curve can be

chose

Running definite time overload

protection

Overload capacity and protection time can be set

Missing phase protection Protection of input missing phase and output missing phase

External fault protection when the controlling panel is external fault, lock the triggering signal

shutdown protection

Phase order protection When the input phase order is not the same as output phase order, block

the start signal and alarm

Current unbalance, over-current

protection

Upper limit current, can be set

Start overtime protection Exceeds soft start time, but the start is not completed, so shutdown

protection

Starting interval protection Start time is less than 6 per hour, and start time interval between 2 times is

more than 10 minutes, the interval time can be set

Insulation Ground and phase frequency is 28~32kV/1min, lighting impulse 60 KV

Inspection function

Current inspection A、B、C 3-phase current and motor current

Voltage inspection Input power supply voltage and motor working voltage

Input and output interface

Input interface Start(2-line, 3-line), stop, fault

Output interface Ready, start, running, fault

Communication and 4-20mA

interface

RS485 interface, modbus protocol,4~20mA standard analog signal

output

Bypass output interface After starting, switch to bypass contactor

Operation interface

LED display Display fault code and current

Keyboard Including 6 operation buttons

3.2. Characteristics of the equipment

This equipment adopts unit construction and module installation. It has the absorption and protection

technology for multiple over-voltage; multi-step limiting clamp of the transient dv/dt lightning impact voltage and

the operation wave over-voltage and other transient excess processes; it has a special methods for di/dt, open

Page 6: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

valve, the voltage-sharing in shutting-off process of the valve; it adopts high anti-interference digital trigger and

CT isolating transmission trigger impulse which make this high voltage equipment as safe and reliable as the low

voltage one.

Adopting double single-chip microcomputer full-digital control;

With the function of 5-bit LED nixie tube display, with the current display range of 0~99999A, displaying

the working state of the motor in an all-round way;

Harvard SCM has interference-resistance capability, guaranteeing the control system works reliably in the

complex industrial environment with strong interference;

With three starting modes including constant flow soft starting, voltage slope starting and pulse jumping

starting, suitable for various loads, with smooth starting process and small starting current (the constant soft

starting mode can control the starting current within 1~3.5 times of the rated current), the starting time can be

adjusted according to the requirements of the working conditions. The constant current soft starting is

suitable for the non-load starting and light load starting of motor, voltage slope starting is suitable for the

heavy load starting of motor; in case that the static friction of the load machinery of the motor is relatively

large, please select the pulse jumping starting mode.

With two stopping modes including free stopping and soft stopping; the characteristics of soft stopping can

satisfy the mechanical requirements on different occasions and the soft stopping time can be adjusted; the

characteristics curve of soft stopping is shown in Fig. 4;

With reliable function of over-current protection, overload protection, overheat protection, power supply

open-phase protection and output open-phase protection, guaranteeing reliable and safe starting and stopping

of the motor. It will protect the open-phase fault of the motor within 1 second and it has the function of

current amplitude limiting protection. When the motor is overloaded, it has the function of I2t protection,

with the performance superior over the protection of thermal relay. In addition, the monitor will display the

corresponding fault codes.

With spanning operation (through contactor bypass) mode;

With DCS remote interface and computer RS485 interface;

4~20mA standard simulation current output;

With compact and original product structure and small volume, easy for installation, use and maintenance

3.3 Characteristics of the performance

1. Flexible control

Field button start: Use two-wire or three wire control mode, two-wire accept passive relay contacts open

and close signal, three-wire accept passive button signal

Keyboard keys start

PC remote start

Combination start: keyboard + remote control, keyboard + PC, remote control + PC

2. Many kinds of starting

The control modes of the soft starter: current limiting start and voltage slope start. Besides, the starter has

crawl operating function settable and selectable by the user according to the load and other specific requirements.

(1) the current limiting soft starting:

When the motor starts, its output voltage value increases rapidly until the output current reaches the setting

limiting value Im as it is shown in fig. 1-1. The voltage increases gradually, which makes the motor accelerate

gradually. When the speed of the motor is close to the rated value, the output current reduces to the rated current

Ie rapidly and the starting is finished. The current limiting value can be set according to the load condition and the

setting range is 1 to 4 times of the rated current of the motor.

Page 7: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

(2)the voltage slope starting

Please see fig.1-2 for the oscillogram of the voltage variation of the voltage slope starting. U1 is the initial

voltage value output by the soft starter. When the motor starts, the output voltage of the soft starter increases to U1

rapidly and increase gradually according to the setting time t, the motor speed increased by the increase of voltage,

when voltage reaches the rated value Ue, the motor reaches to the rated speed, the starting is finished. The starting

voltage U1 and the starting time t can be set according to the load. The setting range of U1 is 30%-80% UeV and

the setting range of t is 0-180 s.

(3)stop

Free stop and soft stop modes settable by the user according to the load and working conditions

Free stop: Upon receiving the stop command, solid soft starter will switch off the bypass contactor

immediately blocks the output of the thyristor of the main circuit to stop the motor along with

the inertia.

Soft stop: In this stop mode, the power supply of the motor load switches from bypass contactor to the

thrysitor of the main circuit and the output voltage of the softer reduces gradually until the

motor stops operating. The stop time can be set according to the load requirement and the

setting range is 0-30S.

3.The protection function

Missing phase protection: When missing phase, block the pulse to prevent the motor winding burn out caused

by power supply missing phase.

External protection: When the control panel is fault, cut off the power supply

Start overtime protection: If the start time of voltage slope start, constant current start, pulse kick start

Page 8: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

exceeds the setting “start time”, block the pulse, shut down the soft starter, carry on overtime protection.

Then, re-set the initial voltage and start time.

Over-current protection: When starting, motor current exceeds the limit value, then cut off the power within 1

s

Running current overload protection: When running, motor current overload exceeds setting time, then cut

off motor power

Running current inverse time overload protection: I ² t overload protection

Phase sequence protection: When input phase sequence is not the same as output phase sequence, block the

start signal, send signal to protect

Start interval protection: start times is less than 6 per hour, and time interval between 2 times is more than 10

minutes, or block start signal to protect.

4. Widely used in many occasions:

Normal start: Such as, the load of the bow propeller, compressor, lifter, centrifugal pump, conveyer belting

and elevator and others can selects the type according to the rated power of the motor. The starting voltage of

the motor can be adjusted between 40% and 50%.

Heavy load start: Such as, select the type as 120% of the rated power of the centrifugal machine, crusher,

mixing machine, grinding mill and agitator and others. The starting voltage of the motor can be adjusted

between 50% and 60%.

Chapter 4 Type Selection

4.1. Type description:

4.2 The structure and dimension (Please contact us if you have special requirements)

The softer starter The rated The rated current The matching Overall dimension (mm)

Page 9: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Chapter 5 Installation and debugging

Warning: WGQH series high voltage solid soft starter is high voltage equipment which has a potential

voltage that can harm the human body. Only the authorized and trained persons can operate and maintain this

equipment. For the induction high voltage on the motor, it is dangerous after powering off. Thus the operation can

be done only after discharging.

5.1. Primary check

Generally, WGQH series high voltage soft starter is upright during transportation.

Unpack the equipment carefully and check if it is damaged during transportation. Write damage report and

inform us within 15 days after receiving the bill of loading.

Check if there are loose mechanical parts, circuit break and loose wiring phenomenon during transportation

and carriage. Please inform us if there are above phenomenon.

5.2. Installation and wiring

WGQH series soft starter is series connected between the high voltage switchgear and the high voltage motor.

Please cut off all the power supply before installation. The installation of the specifications of high voltage electric

shall be followed during installation. Ensure the safety distance and horizontal installation. A certain space has to

be kept around the cabinet to ensure the free opening and closing of the cabinet door and for the convenience of

the operation and maintenance.

The grounding cables shall be connected to the ground terminals at the bottom of the cabinet. Inspect all the

resistance among the ground lines by ohm meter to ensure reliable grounding. The wiring of the power cord of the

soft starter is bottom inlet and bottom outlet.

The output power cord of the high voltage switchgear is connected to the output interfaces R, S and T of the

vacuum contactor though the inlet holes of the cabinet via the high voltage cables. The outlet of the cabinet is

connected to the high voltage motor through the outlet holes of the cabinet via the high voltage cables by U, V and

W interfaces. The interfaces shall be protected by insulating bushing. If there is zero sequence mutual-inductor,

the inlet cable shall go through it.

For the control power supply of the soft starter, select 1.5mm2 four-cord cable for AV 380V, which shall be

voltage power of the

motor

type (KV) (A) (KW) height width depth

WGQH-6/710

6-6.9

85 710 2300 1000 1500

WGQH-6/1250 160 1250 2300 1000 1500

WGQH-6/1500 200 1500 2300 1260 1500

WGQH-6/2400 300 2400 2300 1260 1500

WGQH-6/3200 400 3200 2300 1500 1500

WGQH-6/4000 500 4000 2300 1500 1500

WGQH-10/1100

10

85 1100 2300 1260 1500

WGQH-10/2230 160 2230 2300 1260 1500

WGQH-10/2500 200 2500 2300 1500 1500

WGQH-10/4000 300 4000 2300 1500 1500

Page 10: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

connected to connecting terminals through the inlet holes for the control power supply of the soft starter.

Inspect if the connecting line for the power supply and for the load are in good connections. Make sure that

the input phase-sequence is exactly the same as that of the output.

5.3. The tests of the dielectric strength and of the protection functions

1 The test of the power-frequency tolerance voltage

The test of the dielectric strength can be done if the condition at the user side is allowable:

a. the primary to the second grounding

Short circuit all the input and output terminals of the primary loop. Short circuit the two terminals of the

thyristor. Short circuit the terminals of all the secondary loops and then connect them to the shell and the

earth. Add power frequency AC 35KV 1min between the terminals of the primary and secondary loops and

the earth. There shall be no breakdown or flashover.

b. between the primary loop

Shot circuit respectively the three-phase input and output terminals A, B and C of the primary loop, including

the two terminals of the thyristor. Add power frequency AC 35KV 1min among any of one phase, the other

two phase of the A, B and C phase of the primary loop and the earth. There shall be no breakdown or

flashover.

c. the secondary loop to the shell

Short circuit all the terminals of the secondary loop. Cut off the line connected to the shell and the earth line.

Add power frequency AC 2.0 KV 1min between the terminals of the secondary loop and the shell. There

shall be no breakdown or flashover.

2. The test of the protection function

The aim of the test is to check if the inspection and protection units of the soft starter can work coordinately

and reliably. Because some faults have to be simulated, suggest to testing in the system of the voltage 380V

or below for the safety of the equipment.

a. the test of no-voltage protection function

Press the start button of the soft starter and then short circuit 380V power supply. The soft starter shall alarm

and display “no-voltage”. The control system will reset.

b. the test of the over-current protection of the soft starter

Set “the upper limiting value of the current” of the soft starter. Start the motor with light load and then

increase the load of the motor to the upper limiting value of the current. The soft starter will trip and alarm

with “over-current” displayed.

c. the test of the operating over-current protection

Set “the upper limiting value of the operating current” of the soft starter. Start the motor with light load until

bypass operation and add the load of the motor to he upper limiting value of the current. The soft starter will

trip and alarm with “over-current” displayed.

d. the test of the protection function of starting overtime

Modify the “starting time” value of the soft starter to the value more than the actual starting time of the motor.

The soft starter will trip and alarm with “over-time” displayed if the protective time of starting is up.

e. the test of start phase sequence protection

Change the input terminal of starter and the wiring terminal of motor, to make they are different, when press

start button it trip immediately, display “phase sequence is error”

f. the test of external fault protection

Make fault relay operate, the starter will alarm, display “external fault”

Page 11: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

g. the test of starting time interval protection

Start immediately when the first start is completed, the starter will block the start signal, and display the start

time interval.

5.4. Low voltage simulation (only for the technicians for installation and debugging from our company)

Low voltage (380V) simulation function has been designed for WGQH soft starter. Select one low voltage

(380V) motor of the power about 10KW before connecting the high voltage power supply and the high voltage

motor. Connect respectively as the requirements of the inlet/outlet of the soft starter. Open the small door of the

soft starter, and then open P4, P5, and P6 of the main panel. The rotary switch of the cabinet door shall be in test

status and the ready indicating light will be off. The soft starter will be in low voltage working status. Operate it as

the operation process and it shall work normally. If not, find the reason and solve it.

If the low voltage (380V) simulation debugging function is normal, short circuit P4, P5, P6 of the main panel

and make the rotary switch turn from test position to high voltage working position.

Special attention: add high voltage electricity in low voltage working status will damage the equipment.

5.5 High voltage debugging

If the low voltage (380V) simulation debugging function is normal, connect high voltage cables according to

the requirements of installation wiring in 2 and 3 after returning to high voltage working status. Please check the

followings before powering on:

Check if all the conductor lines are wiring correctly and in good conditions.

Check if the grounding of the system is good.

Check if any of the mechanical parts and wiring is loose. Check if there are metal powder, screws and

sundries inside the cabinet.

Check if the wiring of the motor and the insulating are good.

Close the front and back doors to check if high-voltage interlocking mechanisms are working normally.

Check if all the parameters are correct. Modify them if necessary.

In high voltage working condition, operate it as the operation specifications of the soft starter and the starter

shall work normally.

Chapter 6 Operation

6.1. Operation panel

Page 12: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Meanings of unit indicator light:

A-if this light is on in starting or running of the motor, it refers to current unit A (ampere),in setting

parameter; If this light is on, it refers to viewing this parameter value; In case of fault, it will be off;

P - this light will be on after the motor starts and switches over to the bypass, in setting the

parameter; If this light is on, it refers to parameter editing state; In case of fault, it will be off.

The key functions are described in the following table:

Key ID Key name Functional description

RUN Starting key In Ready state of starting, press this key and it can start the motor

STOP Stopping key

1.In inputting password, it can exit directly; in viewing the parameter state,

press this key and it can exit the parameter setting state and return to the

powering-on initial state.

2.In operation of motor, press this key for stopping.

SHIFT Shifting key

1.Press it together with PRG key, it will enter the password input state;

2.In the password input state, press this key to enter (no flash of the

corresponding position) or exit the modification state (flash of the

corresponding position);

3.After inputting the password, press this key for two seconds, if the

password is correct, it will display “PASS”,otherwise, it will return back to

the powering-on initial state; in the following two seconds, in case of no

press on the key, it will automatically enter the parameter setting state; if

press this key within 2 minutes, it will enter the password modification

state; the modification method is same to the one in inputting password;

after modification, press PRG for storage, it will display “Good”, after 2

seconds, it will automatically enter parameter setting state; in case of not

saving the modified password, press this key for two seconds to enter the

parameter setting state.

4.In setting the parameter, press this key to modify the data or exit the

modification state;

A

P

Worldwide Group SHIFT PRG

RUN

STOP

Parameter modification key

Shift key Programming key Stop/Reset key

Starting key

Unit indication

WGQ micro-controller

Page 13: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

PRG Programming

key

1.Press it together with Key SHIFT to enter the password input state;

2.In modify the password, press this key to store the modified password;

3.In setting parameter, press this key to store the parameter value.

▲ Increasing key

1.Move the flash position towards left in inputting the password or increase

its value;

2.In viewing the parameters, press this key to view its function code and its

parameter value

3.In modifying the parameter, press this key to increase its value;

▼ Reducing key

1.Move the flash position towards right in inputting the password or

increase its value;

2.In viewing the parameters, press this key to view its function code and its

parameter value

3.In modifying the parameter, press this key to reduce its value;

Flow chart of parameter setting

Page 14: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Ready

Press SHIFT + PRG

Password is

right?

Yes

Power on

Yes

Press SHIFT for 2 s

Enter main

menu

Press ^V to modify parameter

Press PRG to save parameter

Normal ? Fault displayNo

Input passord

Press STOP

Press ^V to move

Press SHIFT to enter modify function, press ^V to

modify parameter

No

0 P 0 0 1

-PASSModify

passwordPress SHIFT in 2 S

Press ^V to move

Press SHIFT to modify function, press ^V to

modify parameter

Good

Press

PRG

Wait for 2 s

Wait

for 2s

Modify

parameterPress SHIFT

1 P 0 0 1

2 P 0 3 0

3 P 0 3 0

4 P 2 0 0

5 P 0 5 7

6 P 4 0 0

7 P 0 7 0

8 P 4 0 0

9 P 0 0 0

A P 0 3 0

b P 0 0 0

C P 0 0 0

d P 0 1 0

E P 0 2 0

F P 0 0 1

Press VPress ^

Press ^

Press V

Good

Press PRG

Press SHIFT

twicePress ^+V

Ex-factory

value

Press

RUNYes

Start

normal ?

N

o

Operation

normal ?

No

Yes

Press STOP

Yes

1P≠2

1P≠0

9P=0

Stop ?

No

g P 0 0 0

h P 0 1 5

H P 0 0 1

gP=0

HP=0

HP=0

HP=1

L P 0 0 0

Page 15: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

6.2、Method of setting password and parameters

In order to guarantee the parameter of the soft starter will not be illegally modified, it is necessary to set the

parameters only when the password is validated. The password input method is shown as follows (an example

with 0200 as the existing password):

After entering the password input state, press “STOP” for direct exit in case of not modifying the parameters.

Password modification method is shown as follows (an example of modifying the former password 0200

into 0205):

When the soft starter is firstly used to control the operation of a motor, it is necessary to set the parameters

according to the related parameters of the motor and the load of the motor, otherwise, the starter will control the

starting motor according to the present value, which may result in the failure of the starting or abnormal

operation.

The parameter setting steps are shown as follows: an example of setting soft starting mode (9P=1) and soft

stopping (AP=20) to 20 seconds:

- P A S S Set to “-PASS” state according to the above password input method.

It will display the initial password and the lowest position will flash. Press “SHIFT” within 2 second in the state of displaying “-PASS”. - 0 2 0 0

- 0 2 0 0 Press “SHIFT” to enter the position modifying status and

this position will stop flashing.

- 0 2 0 5 Press “▲” or “▼” to modify the lowest position to “5”.

- 0 2 0 5 Press “SHIFT” to allow “5” flashing, and press “▲”

or “▼” to the corresponding position to

modify other positions, as above.

- G o o d Press “PRG” to save the new password after modification, and display “Good”.

Step to the parameter setting status after 2s. 0 P x x x

----- Initial state of powering on displays five“-”

- 0 0 0 0

- 0 0 0 0 Press“▲” or“▼” key to move the flash position left or right,

press it once, move a bit; Press “▲” to flash the second position

- 0 0 0 0 Press “SHIFT” to modify it, this position will stop flash

- 0 2 0 0 Press “▲” or“▼” to modify the second position to “2”

- 0 0 0 2

Press “SHIFT” to flash “2”, in case that the password has other non-zero position,

Press “▲” or“▼” to move to the corresponding position just like the above setting

- P A S S Otherwise, back to stopping state and display “-----”

Press “SHIFT”+ “PRG”, begin to input password, at the same time, the

lowest position flashes (expressed with italic);at this time, press “STOP”

for direct exit.

Press “SHIFT” for 2 seconds, in case of correct password, display “-PASS”

Begin to parameter setting after 2s,”0” before P presents the 1st parameter 0 P x x x “xxx” following P presents the set value of the first parameter.

Page 16: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Note: in “Good” state, press Key “▲” and “▼” at the same time to reset all the parameters to ex-factory value.

6.3、Parameter function

1 Table of parameter function

Function Setting range

Ex-factory

value Description

Code Name

0P CT variety scale 1, 2 1 1 :1000/0.5A 2 :2000/0.5A

1P Starting mode 0, 1, 2 1 0: constant current 1: voltage ramp 2: impulse step

2P Starting voltage 30~80(%) 30 Valid voltage ramp mode

3P Starting time 0~180(S) 30 Valid of all starting modes

4P Constant current 100~400(%) 200 Valid constant current mode

5P Rated current 0~1060 57 Rated current of the motor (Unit: A)

6P Starting amplitude

limiting current 100~600(%) 400 Valid voltage ramp mode

7P Step voltage 50~80(%) 70 Valid impulse step mode

8P Step duration 200~800(ms) 400 Valid impulse step mode

9P Stopping mode 0, 1 0 0: free stopping 1: soft stopping

AP Soft stopping time 0~30(S) 30 Valid soft stopping mode

bP I2t overload protection

curve 0, 1, 2, 3, 4 1

0: output inverse time lag protection

1,2,3,4:four curves of inverse time lag protection, the

starting current value of inverse time lag protection is

max{1.14Ie,(1+EPparameter)*Ie}

0 P x x x

No. Operation

Press ▲ 9 times

Press SHIFT

Press ▲ once

Press PRG

Press SHIFT

Press SHIFT once

Press ▲ once

Press SHIFT once

Press ▲ 10 times

Press PRG

Press SHIFT once

Press SHIFT once

Press STOP once

Display Description

Display the parameter view state after password was validated. Light A is on. 1

2

3

4

5

6

7

8

9

10

11

12

13

14

9 P 0 0 0

9 P 0 0 0

9 P 0 0 1

G o o d

A P 03 0

-----

9 P 0 0 1

9 P 0 0 1

A P 0 3 0

A P 0 2 0

G o o d

A P 0 2 0

A P 0 2 0

The ex-factory value of parameter 9P is 0, presenting free stopping

Enter parameter modification state, light P on and light A off.

Parameter increasing and changing into 1, presenting soft starting

Storing the new parameter value

Back to parameter modification state, light P and A on

Exit parameter modification state and enter parameter view state, light P off, A on.

Ready to modify AP parameter (soft starting time), light A on

Enter parameter modification state, light P on and light A off

Parameter increasing and changing into 20, presenting soft stopping time is 20S

Store new parameter value

Back to parameter modification state, light P on and A is off

Exit parameter view state and enter ready state

Exit parameter modification and begin parameter view state, light P off, light A on

Page 17: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

CP Control mode 0~5 0

0:keyboard control 1: remote control

2: controlled by PC computer 3: keyboard+remote

control 4: keyboard+PC 5: remote control+PC

dP Specified time overload

protection time 0~180(S) 10

Valid, when the running current is equal or more than

(1+EP parameter) ×Ie

EP

Overload quantity of

specified time overload

protection

0~400(%) 20 The protective current value is equal to (1 +EP

parameter) ×Ie

FP Local address 1~255 1 Used for serial-port communication

gp Test function of

minitype motor 0, 1, 2 0

0: function invalid 1: function valid

2:the main loop no-load test with no power

transmission

hp Rated current of

minitype motor 1-100 15

When the test function of minitype motor is valid, set

to the rated current of minitype motor for testing (unit:

A)

HP Connection mode of the

starter 0, 1 1

0: connect the starter by triangle wiring mode

1: connect the starter by ordinary wiring mode

LP

Current display error

correction

-999~999 0

Shows I= measured I + LP, can set it in the menu in

ready state, can also adjust it when the bypass is

running.

Note:

In the mode of constant current starting: skip parameters 7P and 8P, don’t display;

In the mode of voltage ramp starting: skip parameters 4P, 7P and 8P, don’t display;

In the starting mode of impulse step: skip the parameter 4P, don’t display;

In the mode of free stopping: skip AP, don’t display;

When the test function of mini type motor is invalid, skip hp parameter without display;

When the HP is set to 0, skip 9P and AP parameter without display;

● When CP is set as 1, the remote control can adopt two-wire or three-wire system, and can only adopt

three-wire system if CP is set as 3 or 5.

6.4、Description of function parameters:

1 CT variety scale (function code OP)

Choose the parameters basing on the real variety scale of the inner set current transformer. The parameters

have been set by us before ex-factory, so it is not necessary for you to adjust.

2 Starting mode (function code 1P)

According to the different operating conditions on site, three kinds of starting modes will be offered: set

1P as (0,1,2).

0 means constant current soft start, applicable to no-load starting, light-load starting of the motor, low

capacity of the electric network or the occasion that the starting current is strictly limited. The current will be

kept at the set point of 4P from starting to the end of starting if this mode selected; (the starting characteristic

curve is as Fig. 1)

1 means voltage ramp starting, applicable to the starting of the motor with short time start and without

strictly limitation of the starting current, supplying terminal voltage for motors in voltage ramp mode, initial

voltage of the ramp will be set by 2P and the slope of voltage ramp will be adjusted by 3P; (the starting

characteristic curve is as Fig. 2), normally adopt this method.

2 means impulse step starting, applicable to the operating condition of load machinery for motor with

Page 18: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

relatively bigger static friction, it is also started in voltage ramp mode and the different point is that a high

voltage with ultra-short duration will be added to the motor at the beginning of starting. (The starting

characteristic curve is as Fig. 3)

3 Starting voltage (function code 2P)

Valid when 1P is selected as 1 or 2, indicating the initial voltage value of voltage ramp, setting according

to the voltage percentage within the range of 30-80%. As the higher the starting voltage the larger the value is;

the larger the initial torque of the motor, the larger starting current of the motor is, please set carefully, normally

set as 40% (add this value appropriately in case of heavy load to guarantee the starting torque is more than static

torque of the mechanism) and adjust with 3P and 6P to allow the motor to complete the starting smoothly while

the starting current not exceeding 6P set point and within the 3P setting time range.

4 Starting time (function code 3P)

Set as 0~180S according to the load status of the motor; if the time is set relatively longer, the starting

current change slowly and the actual starting time of the motor will be prolonged correspondingly, so the time is

normally set as 30s, which will be increased properly in present of overtime protecting.

5 Constant current (function code 4P)

This parameter shall be valid only when 1P is set as 0, and the set value is the percentage of the rated

current of the motor (100~400%) ; When the motor is started, the soft starter will control the starting current of

the motor and shall reach and keep this parameter setting value to the end of starting. If the parameter setting is

small, the starting torque of the motor will be smaller and the starting time will be longer.

6 Rated current (function code 5P)

The parameter refers to the rated current of the motor and input the parameter value according to

nameplate of the motor. (Unit: A)

The setting range is 0-1060. Take A to present 10 when the rated current of the motor reaches 1000A or

above. For example, “5PA60” presents that the rated current is set to 1060A. If the starter is triangle mode wiring,

it will transfer the current automatically to make the current value displayed corresponding to the wire current of

the power supply.

7 Starting amplitude limiting current (function code 6P)

Set the parameter according to the percentage of rated current of the motor within the range100~600%,

and normally set as 300~500% of the rated current of the motor on the basis of the load of the motor. Cut off the

power supply of the motor when the starting current of the motor exceeds the set value, and the relevant fault

code will be shown on the monitor.

8 Step voltage (function code 7P)

This parameter shall be valid only when 1P is set as 2. It means that add an unexpected high-voltage

amplitude of ultra-short duration to the motor at the time of starting, and it can be set to 50~80% of the supply

voltage.

9 Step duration (function code 8P)

When the motor is in the starting mode of impulse step, the duration of unexpected high-voltage added to

the motor at the beginning of starting shall be set as 200~800ms.

10 Stopping mode (function code 9P)

Two stopping modes are offered according to the operating conditions on site when the wiring mode of the

starter is ordinary wiring mode (that is, set HP to 1):

0 presents free stopping; upon receiving the stop command, solid soft starter will switch off the bypass

contactor immediately and cut off the power supply of the motor to stop the motor along with the inertia.

1 presents soft stopping; after receiving the stop command, solid soft starter will make the silicon control

on state firstly, secondly switch off the bypass contactor, and then reduce the terminal voltage of the motor

Page 19: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

gradually by controlling the silicon control until the motor stops, cut off the power supply. Applicable for the

stopping of the load of water pump to overcome the water-hammer effect, and the stopping of the load of

transmission band to eliminate the inertia attack of the object.

【Note】When soft stop mode is selected, the starter will have the function of soft stop only after starting and

stopping is completed after bypass operation. It has no soft stop function if it is stopped during operation; the

starter has no soft stop function when the HP is set as 0.

11 Soft stopping time (function code AP)

When the motor is in soft stopping mode, this parameter can adjust the soft stopping time of the motor (if

the pump head is high and the inertia of the object on transmission band is large, a relatively large parameter

value should be set; or a small value should be set. The value is adjustable between 0 and 180s), and it is skipped

in mode of free stopping.

12 I2t overload protection curve (function code bP)

Inverse-time-lag overload protection function for running current of the motor provides 4 inverse-time-lag

overload protection curves for users to choose (1, 2, 3, and 4). The relationship between overload multiple and

protection time is shown in figure 1, and the larger the overload current the shorter the response time is. The

starting current value of inverse time lag protection takes the larger one between 1.14Ie and (1+EP parameter)*Ie.

For example, set EP parameter to 20, thus (1+EP parameter)*Ie =1.2Ie which is above 1.14Ie, and the starting

current value of inverse time lag protection will be 1.2Ie.

Relationship between overload multiple and time of protection operation:

Overload

Multiple

Protection

grade

6Ie 5Ie 4Ie 2Ie 1.5Ie 1.2Ie

1 0.6s 0.9s 1.5s 8s 23s 156s

2 1.3s 1.8s 3s 16s 47s 519s

3 3s 4s 7s 38s 109s 742s

4 6s 9s 14s 77s 218s 1485s

Take protection grade 3 as an example, the overload protection curve is shown below:

Page 20: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

T(S)

742

109

38743

1.2 1.5 2 4 5 6 I/Ie运行电流I t过载保护曲线2

13 Control mode (function code CP)

Offering six control modes in all and the parameters shall be set as (0 to 5).

0 represents keyboard control (only the keyboard is valid while others are invalid)

1 represents remote control (there are two-wire and three-wire control modes, see the secondary wiring

diagram for details. Other control modes are invalid)

2 represents PC computer control (Other control modes are invalid)

3 represents keyboard + remote control (Other control modes are invalid)

4 represents keyboard + PC computer (Other control modes are invalid)

5 represents remote control + PC computer (Other control modes are invalid)

14 Specified time overload protection time (function code dP)

If the current overload of the motor exceeds the setting time during the running process of the motor,

switch to the emergency protection state and cut off the power supply of the motor. When the running current

of the motor reaches (1+EP) ×Ie, begin timing, and the protection time is adjustable between 0 and 180s.

15 Specified time overload protects the overload quantity (function code EP)

Set the parameter according to the percentage of the rated current of the motor within the range of 0 to

400%, specific time overload protection current of the motor =(1+EP parameter)×Ie .

16 Local address (function code FP)

Used for serial-port communication, and is unique in the same network.

17 Test function of minitype motor (function code gP)

Test function of minitype motor is invalid when gP is set to be 0;

Test function of minitype motor is valid when gP is set to be 1. It can enable the motor whose power is far

smaller than the rated starting value of the motor to conduct the routine inspection of the starter in testing or

maintenance environment. In the main loop power transmission condition, the starter turns to bypass operation

when the starting process is finished or reaches the starting time set by 3P. It has no protection functions of

overtime starting or output open-phase. gP returns to 0 state when the control voltage is broken.

Start the device with no-load test in main loop with no power transmission condition, and the device output

bypass signal when the starting time reaches the starting time 3P set. It has no protection functions of overtime

starting or output open-phase. gP returns to 0 state when the control voltage is broken.

18 The rated current of the motor (function code hP)

Running current I2t overload protection curve

Page 21: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

When the test function of minitype motor is valid, set to the rated current of the minitype motor for test, and

the range of the setting current is 1 to 100. The amplitude current, I2t overload protection, the rated current of the

motor in specific time lag over load protection at this time is hP.

5P can also be set according to the rated current of the actual large motor, and the modification is not necessary.

19 Connection mode of the starter (function code HP)

The motor has two connection modes. For the motor of triangle wiring mode, the starter can concatenate into

it, and HP shall be set as 0 at this time; for the motor of routine wiring mode, HP shall be set as 1.

【attached table】parameter setting reference in different load statues:

Load type Start mode Initial voltage

(or constant current)

Start

time

Start

limit

Motor actual

start time

Fan Voltage slope 40% - 60% 35s-60s ≤420% 35s-45s

Water

pump

Voltage slope 30%-40%

30s-40s ≤400% 15s-25s Constant current 300%

crusher Voltage slope 40% - 60% 35s-50s ≤430% 25s-35s

Transfer

mechanism

Voltage slope

40%-50% 40s-50s ≤400% 30s-40s impulse step

elevator Voltage slope 30%-40% 30s-40s ≤380% 20s-30s

compressor Voltage slope 30%-40% 35s-45s ≤400% 25s-30s

6.5.Instruction of main control board terminals

READ

Y

STAR

T

RUN

FAUL

T

LEDC

OM

BYPI

BYPO

KSTA

RT

KSTO

P

KFAU

LT

KCOM

GRND L N

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Signal output

Start

Operation

Fault

Public terminal

Bypass output

Ready

Control input

StopStart

Power supplyGrounding terminal

FaultPublic terminal

Instruction of external terminals:

No. of terminal Name of terminal Description

1 Ready signal output Closing after normal self-inspection with

powering-on(relay contact output)

2 Starting signal output Closing in starting (relay contact output)

3 Operation signal output Closing in operation after starting

(relay contact output)

4 Fault signal output Closing in fault (relay contact output)

5 Public end of output signal Public end of output relay signal

Page 22: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

6, 7 Terminal of bypass relay Switching over to the bypass contactor after

starting

8 Starting control input Beginning starting after connecting 11

(passive)

9 Stopping control input Beginning stopping after connecting 11

(passive)

10 Fault input Beginning fault stopping state in disconnecting

with 11 (passive)

11 Public end of input control signal Public end of input control signal

12 Grounding terminal Functional grounding

13,14 Input end of control power supply Access to AC/DC 220V power supply allowed

Simulation current signal 4~20mA output interface and RS 485 communication interface

No. of terminal Terminal ID Functional description of terminal

3J7-1 I- Negative output of 4-20mA simulation current

3J7-2 I+ Positive output of 4-20mA simulation current

3J7-3 B Inverted output end of drive

3J7-4 A Inverted output end of receiver

Note:

1. The standard RS485 serial port is used for the communication with the upper PC to control the soft

starting and stopping as well as monitor the running current and fault state; the communication protocol

is Modbus protocol;

2. For multi-computer parallel communication, there can be 245 subcomputers at most, and the maximum

length of communication line can be 1km

6.6 Powering on for running

1. Check before powering on

Before switching on the power supply, confirm whether the AC input voltage is within the allowed range;

Check whether the power of the motor is in line with the attached soft starter;

Detect if the resistance value of silicon control is normal with multi meter (the detection method of silicon

control is attached hereafter);

Check whether any of the fastening screws, connections and connecting terminals are loosened;

Connect the power supply to the input end of the solid soft starter through air switch, which are separately L1,

L2, L3 and N;

Check whether there is short circuit event existing in phase to the ground or interphase at the input and

output ends of the power supply of the starter;

Finish the connection in accordance with the installation requirements;

2 Trial run

● Close the breaker of incoming line, it will display “―――――” if the self-check is normal; it will display

emergency protection code if the self-check is abnormal, please read the description of protection display

and refer to the fault treatment to eliminate the fault, it will be ok after being powered on again. If the fault

can be eliminated without the need of powering off, press the key STOP to reset, and it will display

Page 23: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

“―――――” for normal state.

Adjust the parameters of the soft starter reasonably according to the nameplate of the motor, to enable the

motor torque to the optimum condition. Note: the parameters can only be modified in stop state.

Press the key RUN to start the motor, and meanwhile observe whether the rotation direction of the motor

conforms to the requirements and whether the running is normal, press STOP to stop the motor in case the

running is abnormal. Switch over two ends of L1, L2 and L3 or two ends of U, V and W randomly if it is

necessary to change the rotation direction of the motor.

If the motor torque is not enough or the starting time is too long, please increase the starting voltage or

constant current value to increase the motor torque.

The motor can only be restarted when the motor completely stop running.

3 Running

Please refer to the <function table of parameters> when setting the parameters.

Press RUN key (use terminal signal in remote control), start the soft starter, the motor will speed up

smoothly; if the current is within the ideal range, it indicates that the parameter settings are appropriate; or

else adjust the parameters to the suitable status.

Press STOP key (use terminal signal in remote control) to execute stop order.

Chapter 7 Protection display and fault treatment

7.1 Description table of protection display

Protection code Function Examination method

FA001 input open phase Check whether the inlet power supply, connection line

of the controlled and the silicon is in good

FA002 output open phase Inspect the cables if inlet and outlet

FA003 Starting over current Surcharge or 6P parameter of current amplitude

limiting is set too low.

FA004 Starting over time

The 4P parameter of constant current value for constant

current starting is set too low, or the starting time 3P is

set too small.

FA005 Overload of the

running specified time

Surcharge or the parameter EP of overload quantity of

specified time overload protection is set too low.

FA006 Overload of the

running current I2t

Surcharge

FA007 Overheat Frequent starting and whether the terminals 10 and 11

are closed.

FA008 uninitialized Uninitialized parameter, no memory or memory broken

Note: if parameter of the memory chip is uninitialized, no memory or memory broken of solid soft starter

WGQ7, FA008 fault will be showed, and the motor will not start until the fault is eliminated. Except this, any

other fault will lead to a stop and the fault code will be indicated.

7.2 Fault treatment

Maintenance should be carried out by professional technical personnel

In case of abnormality in the process of starting and running, the solid soft start will turn to fault protection

status. Relevant fault code parameter be showed on the display to indicate the current failure information and the

power supply of the motor will be cut off at the same time. Please refer to the following steps to check and remove

Page 24: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

the fault:

1 The noise is abnormal when starting and running the motor:

Check if the activating line of silicon control (or module) is of poor contact, whether the silicon control

(or module) is damaged;

Check if the bypass contactor is damaged or is of poor contact, the contactor shall be shut off when

starting in normal status and closed while running;

Check whether there is open phase at the power end or load end, and check the connecting line;

Check if the settings of parameters are correct and appropriate.

2 The motor can’t be started or the starting failed:

Whether the terminals 13 and 14 are powered on 220VAC;

Check whether the indicator lamp of switching power supply is on, if not, check whether the fuse in

switching power supply is blown;

Check if the starting signal is normal or not, and terminal 11 is connected to terminal 8 in remote control

(detect the voltage between the two terminals with the 200VDC step of the multimeter, 0V for

connected), terminal 11 is disconnected to terminal 9 (detect the voltage between the two terminals with

the 200VDC step of the multimeter, 24V for disconnected), in case of one in fault, the on-off state is

incorrect, and it is necessary to change the switch;

Check if the main power supply is connected to the terminals L1, L2 and L3 or not;

Whether the power frequency is normal or not (50Hz);

Check whether the setting of parameters is correct and proper;

Check whether all of the connections are disconnected or getting loose according to the secondary

wiring diagram;

Whether the soft starter is overheated, it is necessary to reduce the number of starts in this case, and

restart after cooling;

If the soft starter is not hot, check whether the fault input terminal 10 is disconnected to 11 (detect the

voltage between the two terminals with the 200VDC step of the multimeter, 24V for disconnected), it

indicates that the temperature switch (85℃, normally closed) is damaged if disconnected, and it is

necessary to replace it;

Check whether all of the connections inside the soft starter are disconnected or get loose.

3 Abnormal stopping while running:

Check whether the voltage of the main power is abnormal and open phase is available or not;

Check whether terminals 6 and 7 are closed (detect the voltage between the two terminals with the

1000VDC step of the multimeter, 0 for closed), and then check according to the following steps if the

terminals are switched off; check whether the voltage at both ends of the control coil of bypass

contactor is 220VAC in case of being closed, if the voltage is 220VAC and the contactor is switched off,

which indicates the contactor is faulty, it is necessary to replace it;

In remote control, check whether the terminals 11 and 9 are closed (the method is as above), it indicates

that the remote control switch is damaged if closed, and it is necessary to replace it;

Whether the soft starter is overheated, and whether the temperature switch is switched off (i.e. whether

the fault input terminal 10 is disconnected to 11); if it is not hot and the temperature switch is switched

off, it indicates that the temperature switch is damaged and needs to be replaced;

Check whether all of the connections are disconnected or get loose according to the secondary wiring

diagram;

Check whether all of the connections inside the soft starter are disconnected or get loose.

4. Solutions for common faults

Page 25: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

the fault the reasons solutions

the monitor doesn’t

display after powering on

poor connection of the control power supply inspect the power supply

the displaying panel is in trouble replace the displaying panel

open phase protection open phase of the power supply inspect the power supply

short circuit protection

open phase of the motor inspect the motor and the its wiring

the silicon control short circuits replace the silicon control

the breakdown and short circuit of the

voltage-sharing board replace the voltage-sharing board

overheat protection

without bypass after finishing starting inspect the bypass vacuum

contactor and its circuit

too frequent starting prolong the starting interval

damage of the fan replace the fan

large fluctuation current

of the motor during

starting

fault of the current transformer replace the current transformer

fault of the control panel replace the control panel

bypass vacuum contactor

doesn’t operate

fault of the peripheral circuit inspect the peripheral circuit

fault of the control panel replace the control panel

bypass vacuum contactor

trips

bypass vacuum contactor can’t protect itself inspect the circuit

the heat relay protects inspect the reason of the protection

short starting time and

protection

the setting of the starting voltage is too high reduce the starting voltage

the setting of the starting voltage is too low increase the starting voltage

7.3. Routine maintenance:

Remove the dust on electric device, control panel and copper bar regularly.

Check the fastening status of the connecting terminals and screws regularly.

Chapter 8 WGQH soft starter Modbus communication protocol

WGQH soft starter communication adopts MODBUS RTU communication protocol, using 3 kinds of

function code to complete 6 functions. Information transfer is asynchronous, in bytes, the baud rate is 9600 bps.

Each character includes 1 start bit, 8 data bits(firstly send the smallest significant bit ), no Odd-even check bit, 1

stop bit, check method is CRC16 cyclic tediously long check. Details are as follows:

Totally use 3 kinds of function code, complete the following 6 function

Function code 1:send switch amount, work status and fault codes

The data host send to the slave is:

No 1 2 3 4 5 6 7 8

Unit box

address

0x 01 0x00 0x00 0x00 0x18 Check code

low

Check code

high

Unit box address valid range is 4-30 。

For example:01 01 00 00 00 18 3C 00

The data from slave to the host is: data is BIT type

No 1 2 3 4—6 7 8

Page 26: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Unit box

address

0x 01 0x 03 Details are as

follows

Check code

low

Check code

high

The 4-6 bytes information of the data from slave to the host is as follows:

The fourth byte input amount status information, corresponding to the input status of terminal 3J1 and 3J6

from the WGQH motherboard, read it according to bit data format. D7-D3 bits are spare, D2 bit indicates external

fault input status (1 for external fault, that’s to say, the terminals KFAULT and KCOM of 3J1 are cut off, or the

fourth and fifth feet of 3J6 are cut off; 0 for no fault), D1 bit indicates remote control stop input status(1 for

remote control stop, that’s to say, the terminals KFAULT and KCOM of 3J1 are short connected, 0 for no remote

control stop signal ), D0 byte indicates remote control start input status(1 for remote control start, that’s to say, the

terminals KFAULT and KCOM of 3J1 are short connected, 0 for no remote control start signal)

The fifth byte working status information, corresponding to WGQH actual working conditions, read it

according to bit data format. D7-D4 bits are spare, D3 is fault status bit(1 for fault status, 0 for not in fault status),

D2 is running status bit(1 means has been transferred to bypass operation, o for not to bypass), D1 is start status

bit(1 for start status, 0 for not in start status), D0 is ready status bit(1 for ready status, o for not in ready status)

The sixth byte fault status information, corresponding to WGQH actual working conditions, read it according to

bit data format. D7-D0 are corresponding to fault status FA008-FA001(1 for in this fault status, o for not in this

fault status)

Totally 14 bits information, can be summarized as the following table:

No n byte The fourth byte

The fifth

byte The sixth byte

D0 Remote control

start

ready FA001 is fault(input missing phase)

D1 Remote control

stop

start FA002 is fault(output missing phase)

D2 External fault running FA003 is fault(start over current)

D3 - fault FA004 is fault(start over time)

D4 - - FA005 is fault(running current time-limit

overload)

D5 - - FA006 is fault(running current I2t overload)

D6 - - FA007 is fault(over heat)

D7 - - FA008 is fault(storage is fault)

1、

Function code 4:send current analog amount

The data host send to the slave is:

No 1 2 3 4 5 6 7 8

Unit box

address 0x04 0x00 0x00 0x00 0x01

Check code

low

Check code

high

For example:01 04 00 00 00 01 31 CA

The data from slave to the host is: data is INT type

No 1 2 3 4-5 6 7

Unit box

address

0x04 0x02 current analog

amount

Check code

low

Check code

high

The 4-5 bytes information of the data from slave to the host is as follows:

4-5 byte storage uploaded current analog signal; high byte first, low byte second

2、 Function code 16,send start, stop/reset order

Page 27: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

The data host send to the slave is:

No 1 2 3 4 5 6 7 8

Unit box

address 0x10 0x00 0x00 0x00

Order

code

Check code

low

Check code

high

Instruction of the sixth byte: when the order code is 0x55, start WGQH soft starter, when it is 0xAA, stop or

reset the fault

For example:01 10 00 00 00 55 00 36(start) 01 10 00 00 00 AA 40 76(stop or reset)

The data from slave to the host is:

No 1 2 3 4 5 6 7 8

Unit box

address

0x10 0x00 0x00 0x00 Order

code

Check code

low

Check code

high

Slave carry on the order from the host, and return the control commands from the host

【Note】

1. When there is no PC control, the start, stop or reset order from host to slave and the sixth byte of the data from

slave to host are 00, and can’t remote start or stop.

2. When there is PC, and the device is not in ready status, the start order from host to slave and the sixth byte of

the data from slave to host are 00, and can’t remote start; when the device is in ready status, the stop and reset

order from host to slave and the sixth byte of the data from slave to host are 00

Chapter 9 Quality assurance

The quality assurance of this product shall be handled according to the following rules and regulations:

1.The maintenance period of this product shall be 12 months after purchase, but should not exceed 15 months

after the manufacturing date recorded on the nameplate. However, failures due to the following reasons shall be

compensated repairing even in the maintenance period.

Problems due to incorrect operation or impermissible repair and reconstruction of one’s own-self.

Problems due to using exceeding the requirements of standard specification.

Damage due to falling or carrying ferociously after purchase.

Aging or failures of the device resulting from use in the circumstances not conforming to the requirements of

this manual.

Failures resulting from earthquake, fire, wind and flood disaster, lightning stroke, abnormal voltage or other

natural disasters, or the causes concomitant.

2.You will enjoy the tech support lifetime whenever and wherever using our product.

The sales, production and agency of this company over the country shall provide after-sale service.

For the products failing to operate, this company has the right to assign other persons to be responsible for

maintenance.

3.Matters concerning dissolution of responsibility

This company will not undertake the responsibilities resulting or reducing from using this product departing

from the regulations of this manual.

This company will not be responsible for compensating the losses or affected and subsequent damage of your

party due to the failure of the product.

Page 28: Soft Starter Supplied by EAGLE TECHNOLOGY_WGQH Type_Technical Datasheet

EAGLE TECHNOLOGY

Eagle Technology Address: No. 201, L-2, B-11, Surya City, Chandapura, Bangalore, India- 560081.

E-mail- [email protected] , Phone No- +91-9535-122013, Website:http://eaglewanlida.com

Chapter 10 Notice for order

1、 The equipment type should be selected according to the rated power, rated voltage and working condition of

the motor.

2、 Provide all the parameters of the motor name plate(Noted in the contract)

3、 If the use site can’t meet the working condition or there is any special requirement, uesrs should state in

advance.

4、 Note the delivery time

[Attached table 1] Detection method of silicon control:

The simple method for judging whether the silicon control is good is that test the resistances among poles and

the resistances among poles of the good silicon control are as follows:

Trigger electrode and negative electrode — some dozens of ohms;

Trigger electrode and positive electrode — some dozens of kilohm,

Negative electrode and positive electrode — some dozens of kilohm.