Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Heating Plantroom 7400 mm wide x 6000 mm deep x 3000 mm high (overall)
-
8/12/2019 Solutions Schedule3
3/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Plantroom
Reference Area Location NotesHeating Plantroom 44 m Ground Floor -
Equipment
Reference Duty SelectionSidestream Filter 1 No. sidestream filter(s) Sidestream filter, 600 mm wide x 600 mm deep x 2000 mm high,
100 kg, 100 kgEnwamatic, TBCwww.enwamatic.com
Calorifiers 2 No. calorifiers @ 1340 litres/hr to meet 2000 litres/hr total capacityVenting: unvented
Arrangement: vertical
Generic semi storage vertical, 440 litres/hr, 735 mm wide x 1060mm deep x 2050 mm high, 850 kgIMI Rycroft semi storage vertical, model MX440V, 1760 litres/hrhttp://www.rycroft.com/ HRS semi storage vertical, model Aquasave AS515, 2500 litres/hrhttp://www.hrs.co.uk/
Calorifiers heating pumps 1 No. duty / 1 No. standby @ 6.52 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519mm high, 56 kg
Armstrong in-line vertical pump, model Starline50-150www.armstrongpumps.com
Hot water circulating pump 1 No. duty @ 10.8 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com
Calorifiers expansion vessels 2 No. expansion vessels3350 litres system volume3.00 bar g feed pressure3.55 bar g final pressure75C maximum system temperature
0% glycol370 litres expansion volume
Generic expansion vessel, 500 litres, 581 kgRycroft expansion vessel, model EXP500V, 500 litreshttp://www.rycroft.com/ Smedegaard expansion vessel, model Type 2 500, 500 litreshttp://www.smedegaard.com/
MCC 200 Amp incomer, 8 starters415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp
Primary Heating circulatingpumps
1 No. duty / 1 No. standby @ 15.22 l/s, 250 kPaPump type: in-line vertical
Generic in-line vertical pump, 214 mm wide x 458 mm deep x 564mm high, 73 kg
http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.enwamatic.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.enwamatic.comhttp://www.rycroft.com/http://www.rycroft.com/http://www.hrs.co.uk/http://www.hrs.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.rycroft.com/http://www.rycroft.com/http://www.smedegaard.com/http://www.smedegaard.com/http://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.smedegaard.com/http://www.rycroft.com/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hrs.co.uk/http://www.rycroft.com/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.enwamatic.com -
8/12/2019 Solutions Schedule3
4/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Pump arrangement: singlePump fluid: water
Armstrong in-line vertical pump, model Starline50-200www.armstrongpumps.com
Boilers 3 No. boilers @ 400 kW to meet 700 kW loadMinimum natural gas efficiencies:- Maximum output: 90.0% (nett)- Seasonal (UK): 86.0% (gross)
Minimum oil efficiencies:- Maximum output: 90.0% (nett)- Seasonal (UK): 84.0% (gross)
Boiler type: condensingFuel: natural gas
Generic condensing boiler, 410 kW, 1110 mm wide x 1755 mmdeep x 2095 mm high, 1342 kgHoval condensing boiler, model UltraGas450, 410 kWhttp://www.hoval.co.uk/
Boiler shunt pumps 1 No. duty per boiler @ 8.7 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519mm high, 56 kg
Armstrong in-line vertical pump, model Starline50-150www.armstrongpumps.com
Heating pressurisationunit(upper floors)
1 No. pressurisation unit9000 litres system volume8.0 bar g maximum working pressure1.6 bar g maximum system pressure
60C maximum system temperature0% glycolPressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1170 mm wide x 800 mm deepx 1660 mm high, 802 kgHoval standard pressurisation unit, model PressVal Micron SM600,600 litres
http://www.hoval.co.uk/
Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk
Boilers vents Vent type: Natural high level, natural low level
High level vents to provide 0.27 m/s ventilation air exhaustLow level vents to provide 0.52 m/s combustion and ventilation airintake(Based on BS6644, BS5410-2 and manufacturer recommendations)
2 No. generic vents at high level, 800 mm wide x 200 mm high, 50
% free area2 No. generic vents at low level, 800 mm wide x 400 mm high, 50 %free area
Notes
Auditorium AHU 8200 mm wide x 3500 mm deep x 1700 mm high
http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.com -
8/12/2019 Solutions Schedule3
5/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Plantroom
Reference Area Location Notes Auditorium AHU 28 m Ground Floor -
Equipment
Reference Duty SelectionBasement AHU Air flow 1.2 m/s
Configuration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components:- Louvre- Attenuator (600 mm)
- Bag filter (long)- Access (short)- Thermal wheel- Thermal wheel- Access (short)- Fan (backward curved)- Access (short)- Humidifier (steam)- Attenuator (600 mm)
Generic modular AHU, SFP 1.6 W/l/s (estimated), 7000 mm wide x1404 mm deep x 1548 mm high, 1820 kgFlakt Woods modular AHU, model EU22http://www.flaktwoods.com/products/air-handling-units/
http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/ -
8/12/2019 Solutions Schedule3
6/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
- ConnectionExtract components:- Louvre- Attenuator (600 mm)- Access (short)- Thermal wheel- Heating coil (2 row)- Access (short)- Thermal wheel- Access (short)- Humidifier (steam)- Fan (backward curved)- Panel filter- Access (short)- Attenuator (600 mm)- Connection
Notes
...
-
8/12/2019 Solutions Schedule3
7/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Main AHU 11300 mm wide x 8500 mm deep x 5400 mm high
Plantroom
Reference Area Location NotesMain AHU 96 m Ground Floor -
Equipment
Reference Duty SelectionBasement AHU Air flow 8.5 m/s
Configuration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components:- Louvre- Attenuator (600 mm)- Bag filter (long)- Access (short)- Thermal wheel- Thermal wheel- Access (short)- Fan (backward curved)- Access (short)- Humidifier (steam)- Attenuator (600 mm)
Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x2650 mm deep x 4100 mm high, 9630 kgFlakt Woods modular AHU, model EU62http://www.flaktwoods.com/products/air-handling-units/
http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/ -
8/12/2019 Solutions Schedule3
8/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
- ConnectionExtract components:- Louvre- Attenuator (600 mm)- Access (short)- Thermal wheel- Heating coil (2 row)- Access (short)- Thermal wheel- Access (short)- Humidifier (steam)- Access (short)- Fan (backward curved)- Panel filter- Attenuator (600 mm)- Connection
Basement AHU Air flow 8.5 m/sConfiguration: stacked, intake bottomMaximum velocity 2.2 m/s
Supply components:- Louvre- Attenuator (600 mm)- Bag filter (long)- Access (short)- Thermal wheel- Thermal wheel- Access (short)- Fan (backward curved)- Access (short)- Humidifier (steam)- Attenuator (600 mm)- Connection
Extract components:- Louvre- Attenuator (600 mm)- Access (short)- Thermal wheel- Heating coil (2 row)- Access (short)- Thermal wheel
Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x2650 mm deep x 4100 mm high, 9630 kgFlakt Woods modular AHU, model EU62
http://www.flaktwoods.com/products/air-handling-units/
http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/ -
8/12/2019 Solutions Schedule3
9/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
- Access (short)- Humidifier (steam)- Access (short)- Fan (backward curved)- Panel filter- Attenuator (600 mm)- Connection
Notes
...
-
8/12/2019 Solutions Schedule3
10/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Sump Pump 2000 mm wide x 2000 mm deep x 1200 mm high (overall)
Plantroom
Reference Area Location NotesSump Pump 4 m Roof -
Equipment
Reference Duty SelectionSump pump 1 No. @ 2 l/s, 100 kPa
Pump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 131 mm wide x 285 mm deep x 446
mm high, 21 kg Armstrong in-line vertical pump, model Starline32-120www.armstrongpumps.com
Notes
...
http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.com -
8/12/2019 Solutions Schedule3
11/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Rain Water Storage Plantroom 8000 mm wide x 4600 mm deep x 4000 mm high (overall)
Plantroom
Reference Area Location NotesRain Water Storage Plantroom 37 m Ground Floor -
Equipment
Reference Duty SelectionRain water pre-treatment tank 1 No. water tanks @ 7,000 litres Generic water tank, 2000 mm wide x 2000 mm deep x 3000 mm
high300 mm bund height requirement
Treated Rain Water booster 1 No. booster @ 2 l/s, 20 mwg1 No. pump + standby
Generic cold water booster, 665 mm wide x 1034 mm deep x 1565mm high, 270 kgGrundfos cold water booster, model Multi E 1 CRE10http://www.grundfos.com/
AquaTech Pressmain cold water booster, model Aquamatic BTE210http://www.aquatechpressmain.co.uk/
http://www.grundfos.com/http://www.grundfos.com/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.grundfos.com/ -
8/12/2019 Solutions Schedule3
12/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk
Rain water booster pre-treatment
1 No. booster @ 2 l/s, 20 mwg2 No. pumps + standby
Generic cold water booster, 920 mm wide x 1034 mm deep x 1565mm high, 310 kgGrundfos cold water booster, model Multi E 2 CRE5http://www.grundfos.com/
AquaTech Pressmain cold water booster, model Aquamatic BTE3 5http://www.aquatechpressmain.co.uk/
Treated Rain water tank 1 No. water tanks @ 7,500 litres Generic water tank, 3000 mm wide x 2000 mm deep x 2000 mmhigh300 mm bund height requirement
Notes
...
http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.grundfos.com/http://www.grundfos.com/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.grundfos.com/http://www.eaton.com/ukhttp://www.moeller.co.uk/ -
8/12/2019 Solutions Schedule3
13/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
HV Plantroom 7100 mm wide x 4900 mm deep x 3400 mm high (overall)
Plantroom
Reference Area Location NotesHV Plantroom 35 m Ground Floor -
Equipment
Reference Duty SelectionRMU Rating 200 Amps
12000 V, TP&N, 50 HzGeneric RMU, 771 mm wide x 765 mm deep x 1510 mm high, 300kg
ABB RMU, model SafeRinghttp://www.abb.com/ Schneider RMU, model Ringmaster RN2http://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm
HV switchpanel 12000 V, TP&N, 50 HzModule type: withdrawable
Generic HV switchpanel, 2600 mm wide x 1550 mm deep x 2300mm high
http://www.abb.com/http://www.abb.com/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.abb.com/ -
8/12/2019 Solutions Schedule3
14/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Modules:- Incomer- Bus section- Feeder
Future expansion 25%Note: For some manufacturers VTs are integral to other components
ABB HV switchpanel, model Unigear ZS1http://www.abb.com/ Schneider HV switchpanel, model MCSethttp://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm
Notes
...
http://www.abb.com/http://www.abb.com/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.abb.com/ -
8/12/2019 Solutions Schedule3
15/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)
lantroomReference Area Location NotesLV Plantroom 21 m Ground Floor -
Equipment
Reference Duty SelectionLV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,
100 kg
Notes
...
-
8/12/2019 Solutions Schedule3
16/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Life Safety LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)
PlantroomReference Area Location Notes
Life Safety LV Plantroom 21 m Ground Floor -
Equipment
Reference Duty SelectionLV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,
100 kg
Notes
...
-
8/12/2019 Solutions Schedule3
17/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Gas Meter Plantroom 1200 mm wide x 2000 mm deep x 2500 mm high (overall)
PlantroomReference Area Location NotesGas Meter Plantroom 3 m Ground Floor -
Equipment
Reference Duty Selection
Gas Meter 1 No. gas meter(s) Gas meter, 800 mm wide x 480 mm deep x 600 mm high, 100 kg,100 kg
Notes
...
-
8/12/2019 Solutions Schedule3
18/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Telecoms Plantroom 4000 mm wide x 2000 mm deep x 2500 mm high (overall)
Plantroom
Reference Area Location NotesTelecoms Plantroom 8 m Ground Floor -
Equipment
Reference Duty SelectionCopper Rack 1 No. rack(s) Rack, 2000 mm wide x 500 mm deep x 1600 mm high, 100 kg, 100
kg
Notes
...
-
8/12/2019 Solutions Schedule3
19/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Transformers Plantroom 5200 mm wide x 4300 mm deep x 3500 mm high (overall)
Plantroom
Reference Area Location NotesTransformers Plantroom 22 m Ground Floor -
Equipment
Reference Duty SelectionTransformers supply duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum
Maximum aspect ratio: 4.0Insulation: none(Air flow requirement based on transformers losses)
500 mm wide x 300 mm deepNo insulation
Transformers 1 No. @ 800 kVAHV 12000 V, LV 415 V, TP&N, 50 HzTransformer type: dryDerating factor: 1.25
Generic dry transformer, 1000 kVA, 2000 mm wide x 1210 mm deepx 2400 mm high, 2870 kg
ABB dry transformer, model Cast resin 1000, 1000 kVAhttp://www.abb.com/ Schneider dry transformer, model Cast Resin 1000, 1000 kVAhttp://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm
Transformers extract duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximumMaximum aspect ratio: 4.0Insulation: none
500 mm wide x 300 mm deepNo insulation
http://www.abb.com/http://www.abb.com/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.abb.com/ -
8/12/2019 Solutions Schedule3
20/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
(Air flow requirement based on transformers losses)
Notes
...
-
8/12/2019 Solutions Schedule3
21/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Satellite 4000 mm wide x 2200 mm deep x 1800 mm high (overall)
Plantroom
Reference Area Location NotesSatellite 9 m Roof -
Equipment
Reference Duty SelectionSATELLITE DISH 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100
kg, 100 kgSATELLITE DISH 1 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100
kg, 100 kg
Notes
...
-
8/12/2019 Solutions Schedule3
22/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Computer AC Units 10100 mm wide x 2200 mm deep x 1200 mm high
Plantroom
Reference Area Location NotesComputer AC Units 22 m Roof -
Equipment
Reference Duty SelectionComputer Room AC units 5 No. condensers @ 10 kW
Condenser type: vertical air flowMean condensing temperature: 50C
Ambient temperature: 35CNoise: 70 dBA @ 10 m
Generic vertical air flow condenser, 14 kW, 907 mm wide x 972 mmdeep x 1076 mm high, 62 kg
Airedale vertical condenser, model CR12, 14 kWhttp://www.airedale.com/
Notes
...
http://www.airedale.com/http://www.airedale.com/http://www.airedale.com/ -
8/12/2019 Solutions Schedule3
23/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
MER Room 5900 mm wide x 4200 mm deep x 3400 mm high (overall)
Plantroom
Reference Area Location NotesMER Room 25 m Ground Floor -
Equipment
Reference Duty SelectionIT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kgRack, Rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack, Rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack
-
8/12/2019 Solutions Schedule3
24/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Battery Unit 1 No. battery unit(s) Battery unit, 800 mm wide x 1000 mm deep x 2200 mm high, 100kg, 100 kg
AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,500 kg
AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,500 kg
Electrical board 160 Amp incomer, 12 waysType: MCCB415 V, TP&N, 50 Hz
Generic mccb electrical board, 12 way, 400 Amp incomer, 900 mmwide x 230 mm deep x 1605 mm high, 168 kgMoeller mccb electrical board, model PB12-400, 12 way, 400 Ampincomerhttp://www.moeller.co.uk/ MEM mccb electrical board, model PBJG1240M, 12 way, 400 Ampincomerhttp://www.eaton.com/uk
UPS 1 No. ups(s) Ups, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100kg
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgrack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgrack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgrack
Notes
...
http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/ -
8/12/2019 Solutions Schedule3
25/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Security Room 5600 mm wide x 3600 mm deep x 3700 mm high (overall)
Plantroom
Reference Area Location NotesSecurity Room 20 m Ground Floor
Equipment
Reference Duty SelectionIT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kgRack, Rack
IT Rack Copy 1 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack, Rack
IT Rack Copy 2 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack
Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30kg, 30 kg
Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100kg
Electrical board 100 Amp incomer, 12 ways Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
-
8/12/2019 Solutions Schedule3
26/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Type: MCB415 V, TP&N, 50 Hz
wide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30kg, 30 kg
http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/ -
8/12/2019 Solutions Schedule3
27/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
AV Room 2900 mm wide x 2300 mm deep x 3700 mm high (overall)
Plantroom
Reference Area Location Notes AV Room 7 m Ground Floor
Equipment
Reference Duty SelectionIT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kgRack, Rack
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg
Desk 1 No. desk(s) Desk, 1200 mm wide x 750 mm deep x 850 mm high, 100 kg, 100kg
Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,30 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,30 kg
http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/ -
8/12/2019 Solutions Schedule3
28/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
BEMS and Maintenance Room 3600 mm wide x 2300 mm deep x 3700 mm high (overall)
Plantroom
Reference Area Location NotesBEMS and Maintenance Room 9 m Ground Floor
Equipment
Reference Duty SelectionDesk 1 No. desk(s) Desk, 1800 mm wide x 750 mm deep x 850 mm high, 100 kg, 100
kgLocker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kgElectrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk
http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/ -
8/12/2019 Solutions Schedule3
29/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg
Locker2 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg
-
8/12/2019 Solutions Schedule3
30/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Sprinkler Tank 8800 mm wide x 7300 mm deep x 4000 mm high (overall)
PlantroomReference Area Location NotesSprinkler Tank 64 m Basement -
Equipment
Reference Duty SelectionWater tank 1 No. water tanks @ 70,000 litres Generic water tank, 6000 mm wide x 5000 mm deep x 3000 mm
highBunding requirement exceeds 1000 mm
Sprinkler Pump Set 1a 1 No. sprinkler pump set 1a(s) Sprinkler pump set 1a, 750 mm wide x 2200 mm deep x 1000 mmhigh, 100 kg, 100 kgTBC, TBCTBC
Sprinkler Pump Set 2a 1 No. sprinkler pump set 2a(s) Sprinkler pump set 2a, 600 mm wide x 600 mm deep x 1000 mmhigh, 100 kg, 100 kgTBC, TBCTBC
Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomer
http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://www.moeller.co.uk/http://www.moeller.co.uk/http://www.moeller.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBC -
8/12/2019 Solutions Schedule3
31/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
http://www.eaton.com/uk MCC 200 Amp incomer, 5 starters
415 V, TP&N, 50 HzGeneric MCC, 1200 mm wide x 652 mm deep x 2263 mm high
ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp
Notes
...
http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.eaton.com/uk -
8/12/2019 Solutions Schedule3
32/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Chillers Plantroom 9600 mm wide x 8200 mm deep x 3200 mm high (overall)
Plantroom
Reference Area Location NotesChillers Plantroom 78 m Basement -
Equipment
Reference Duty SelectionWater cooled chillers 2 No. chillers @ 850 kW to meet 300 kW total load
Minimum EER (or CoP):- 3.85 kW/kW 750 kW
Chiller types: scroll, screw, c entrifugalChilled water: 12C on / 7C off
Condenser water: 30C on / 35C off
Generic water cooled chiller, 892 kW, 3924 mm wide x 1600 mmdeep x 2060 mm high, 6202 kgTrane screw water cooled chiller, model RTHD C2-D5-E4, 892 kWhttp://www.trane.com/ Carrier screw water cooled chiller, model 30HXC0260, 897 kWhttp://www.carrieraircon.co.uk/
Cooling primary pumps 1 No. duty / 1 No. standby @ 11.96 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com
Heat rejection pumps 1 No. duty / 1 No. standby @ 17.43 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622mm high, 82 kg
Armstrong in-line vertical pump, model Starline100-150www.armstrongpumps.com
http://www.trane.com/http://www.trane.com/http://www.carrieraircon.co.uk/http://www.carrieraircon.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.carrieraircon.co.uk/http://www.trane.com/ -
8/12/2019 Solutions Schedule3
33/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Heat rejection pressurisationunit
1 No. pressurisation unit2190 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure50C maximum system temperature35% glycolPressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1199 mm wide x 634 mm deepx 1446 mm high, 347 kgHoval standard pressurisation unit, model PressVal Micron SM200,200 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N200, 200 litreshttp://www.mikrofill.com/
MCC 200 Amp incomer, 6 starters415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp
Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomer
http://www.eaton.com/uk Cooling circulating pumps 1 No. duty / 1 No. standby @ 14.35 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 214 mm wide x 458 mm deep x 564mm high, 73 kg
Armstrong in-line vertical pump, model Starline50-200www.armstrongpumps.com
Cooling pressurisation unit 1 No. pressurisation unit2700 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure40C maximum system temperature0% glycolPressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1077 mm wide x 600 mm deepx 1095 mm high, 207 kgHoval standard pressurisation unit, model PressVal Micron SM80,80 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N80, 80 litreshttp://www.mikrofill.com/
Notes
...
http://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.mikrofill.com/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.eaton.com/ukhttp://www.moeller.co.uk/http://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.mikrofill.com/http://www.hoval.co.uk/ -
8/12/2019 Solutions Schedule3
34/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Generators Plantroom 9100 mm wide x 4200 mm deep x 4200 mm high (overall)
Plantroom
Reference Area Location NotesGenerators Plantroom 38 m Basement -
Equipment
Reference Duty SelectionLV generators board 1 No. incomer
1 No. feeder415 V, TP&N, 50 Hz
Access: front
Generic generators LV switchboard, 2650 mm wide x 655 mm deepx 2429 mm highGE Power Controls generators LV switchboard, model System 4http://www.ge.com/ Eaton generators LV switchboard, model Bill Classic Form 4http://www.eaton.com/ Minimum connection space above: 600 mm
Generators 1 No. generators @ 400 kVA415 V, TP&N, 50 Hz
Generic diesel generator, 400 kVA, 3500 mm wide x 1150 mmdeep x 2158 mm high, 3700 kgBroadcrown diesel generator, model BCC 440-50 E2, 440 kVA,Emissions compliance EU Stage 2http://www.broadcrown.com/ FG Wilson diesel generator, model P350P4, 400 kVA, Emissionscompliance EU Stage 2http://www.fgwilson.com/
http://www.ge.com/http://www.ge.com/http://www.eaton.com/http://www.eaton.com/http://www.broadcrown.com/http://www.broadcrown.com/http://www.fgwilson.com/http://www.fgwilson.com/http://www.fgwilson.com/http://www.broadcrown.com/http://www.eaton.com/http://www.ge.com/ -
8/12/2019 Solutions Schedule3
35/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Day tanks 1 No. day tanks @ 8 hours storageGenerator fuel tank capacity : 650 litresDay tank capacity (nett): 38 litres
Generic day tank , 1364 litres, 1750 mm wide x 1170 mm deep x1250 mm highJoseph Ash day tank, model D01, 1364 litreshttp://www.jaenvirotanks.com/ Blake day tank, model TEBU FO 1000, 1000 litreshttp://www.blakegroup.co.uk/
Notes
...
http://www.jaenvirotanks.com/http://www.jaenvirotanks.com/http://www.blakegroup.co.uk/http://www.blakegroup.co.uk/http://www.blakegroup.co.uk/http://www.jaenvirotanks.com/ -
8/12/2019 Solutions Schedule3
36/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Hybrid Coolers 13000 mm wide x 4400 mm deep x 2600 mm high
Plantroom
Reference Area Location NotesHybrid Coolers 58 m Roof To reject 500 kW of heat to roof
Equipment
Reference Duty SelectionHybrid Cooler 1 1 No. hybrid cooler 1(s) Hybrid cooler 1, 5000 mm wide x 2400 mm deep x 2500 mm high,
100 kg, 100 kgHybrid Cooler 2 1 No. hybrid cooler 2(s) Hybrid cooler 2, 5000 mm wide x 2400 mm deep x 2500 mm high,
100 kg, 100 kg
Notes
...
-
8/12/2019 Solutions Schedule3
37/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Chillers Plantroom 9000 mm wide x 6100 mm deep x 3000 mm high (overall)
-
8/12/2019 Solutions Schedule3
38/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
Plantroom
Reference Area Location NotesChillers Plantroom 54 m Basement -
Equipment
Reference Duty SelectionWater cooled chillers 2 No. chillers @ 200 kW to meet 400 kW total load
Minimum EER (or CoP):- 3.85 kW/kW 750 kW
Chiller types: scroll, screw, c entrifugalChilled water: 12C on / 7C offCondenser water: 30C on / 35C off
Generic water cooled chiller, 244 kW, 3510 mm wide x 980 mmdeep x 1929 mm high, 2664 kgTrane screw water cooled chiller, model RTWD70, 244 kWhttp://www.trane.com/ Carrier screw water cooled chiller, model 30HXC080, 286 kWhttp://www.carrieraircon.co.uk/
Cooling primary pumps 1 No. duty / 1 No. standby @ 15.95 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com
Heat rejection pumps 1 No. duty / 1 No. standby @ 23.92 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622mm high, 82 kg Armstrong in-line vertical pump, model Starline100-150www.armstrongpumps.com
Heat rejection pressurisationunit
1 No. pressurisation unit3000 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure50C maximum system temperature35% glycolPressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1199 mm wide x 634 mm deepx 1480 mm high, 447 kgHoval standard pressurisation unit, model PressVal Micron SM300,300 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N250, 250 litreshttp://www.mikrofill.com/
MCC 200 Amp incomer, 6 starters415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp
Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/
h h l h d l
http://www.trane.com/http://www.trane.com/http://www.carrieraircon.co.uk/http://www.carrieraircon.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.co.uk/http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.mikrofill.com/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.carrieraircon.co.uk/http://www.trane.com/ -
8/12/2019 Solutions Schedule3
39/39
Chapman Bathurst Plantroom & Riser Schedule
Chapman BDSP
MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk
Cooling circulating pumps 1 No. duty / 1 No. standby @ 19.14 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water
Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622mm high, 82 kg
Armstrong in-line vertical pump, model Starline100-150www.armstrongpumps.com
Cooling pressurisation unit 1 No. pressurisation unit3600 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure40C maximum system temperature0% glycolPressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1077 mm wide x 600 mm deepx 1095 mm high, 231 kgHoval standard pressurisation unit, model PressVal Micron SM110,110 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N100, 100 litreshttp://www.mikrofill.com/
Notes
...
http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.mikrofill.com/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.eaton.com/uk