Specifications

AC012MNADCH/AASamsung, High-Wall Evaporator, Split System

AC012MNADCH/AAAC012KXADCH/AA

12,000 / 14,0003,400 - 14,5003,000 - 16,20018.0 / 9.84

2.449.5

10227622

1 / 208-230 / 60176 - 254 (max. 3% deviation from each)

1.6 / 5.7 / 6.61.3 / 7.4 / 10.0

1510.7

29 1/2 x 9 11/16 x 9 13/1631 1/8 X 21 5/8 X 11 3/16

16.7679.81

Aluminum Fin / Copper Tube181/4

Aluminum, flat fin, micro channel23 / 26 / 32 / 38

48 / 4823 ~ 115°F(-5 ~ 46°C)

0 ~ 115°F(-18 ~ 46°C) w/ baffle-4 ~ 76°F(-20 ~ 24°C)61 ~ 90°F(16 ~ 32°C)

T ≤ 80(27°C)1/4"3/8"65.649

11/16" ODR410A

Electronic Expansion Valve36.96

25 ft0.11 oz/ft over 25 ft

SamsungInverter Driven, BLDC, Rotary

8.1BLDC with Crossflow fan (1)

194 / 247 / 30027 W / 0.40 A

BLDC With Axial Type Fan (1)0.17 A / 39 W / 1,271 CFM

WBF-3M

25' - ILS250650' - ILS5006

• Wall-mounted evaporator

• Low ambient control built in

• The outdoor unit shall supply power to indoor unit via 14 AWG X 3 power wire

• Auto-restart after power loss

• The outdoor unit shall have a snow accumulation prevention option setting to prevent snow drifting against an idle outdoor unit.

• The indoor unit shall have a removable EEPROM that stores system programming information, unit name, and other data

• All indoor unit addressing and option settings shall be done digitally; the indoor unit does not contain rotary dials or setting switches.

• The outdoor unit shall have a night time quiet mode option to reduce operating sound during the night.

Construction The outdoor unit shall be galvanized steel with a baked on powder coated finish for durability

Indoor unit chassis shalle be UL94 V0 with a galvanized steel mounting plate

Heat Exchanger The indoor unit heat exchanger shall be mechanically bonded fin to copper tube

The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel

Controls Control signal shall be a DDC type signal

Interconnect control wire between outdoor indoor unit shall be 16AWG X 2 shielded

Wired controls must be purchased separately

Connection to optional wired controllers shall be 2 X 16AWG shielded wire

Controls shall integrate with a BMS system

The system shall integrate with the Samsung NASA Controls Solution

No additional interface modules/adapters are required when connecting to Samsung NASA DVM S central control options.

Refrigerant System The refrigerant shall be R410A

The compressor shall be hermetically sealed, inverter controlled, BLDC Rotary

Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit

Soft-start to reduce current demand during compressor start

Warranty 10 years compressor, 10 years parts, 1 year limited labor (conditions apply)

WBB-5M

Nominal Capacity Cooling / Heating (Btu/h)Cooling (Btu/h)Heating (Btu/h)

Voltage ø / V / Hz

Cooling (A)Heating (A)

Max. Breaker Amps

Indoor UnitOutdoor UnitIndoor UnitOutdoor Unit

TypeFPIPipe Diameter (in.)

Outdoor Unit Type

Indoor Unit dB(A) (Silent) / L / M / HOutdoor Unit dB(A) Cooling / Heating (high)

HeatingCoolingHeating

High side (flare)Low side (flare)

Factory Charge oz.

RLA Amps

Air Volume CFM (L/M/H)

CertificationsSafety

ETL (UL 1995)Devices: PCB fuses, indoor unit terminal block thermal fuse, current transformer, over-voltage protection, crankcase heating, temperature limit protection logic, compressor overload sensing

FLA / Watts / CFM (max.)

Refrigerant

TypeControl Method

Charged for Additional Refrigerant

CompressorManufacturer Type

Evaporator FanType

Condenser FanMotor

Output (W) / FLA (A)

Operating Temperatures °F(°C)

OutdoorCooling

Indoor

Pipe Connections

Indoor & Outdoor

Maximum (ft.)Maximum Vertical Separation (ft.)Condensate Connection

W X H X D (in.)Weight (lbs.)

Heat ExchangerIndoor & Outdoor Unit

Sound Pressure Level

Dimensions

ModelIndoor Unit Model NumberOutdoor Unit Model Number

AHRI Certification Number

Power

Working Voltage Range (VAC)Operating Current(min. / std. / max.)

Min. Circuit Ampacity (A)

Performance

Capacity Range

SEER / EER COP (nominal heating)HSPF

The indoor unit shall have easy-access to wire, pipe, and drain connections via access panel on front of unit for easier installation and service

© 2020 Samsung HVAC SHA-CAC-01102020

888-699-6067 www.SamsungHVAC.com

*Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240.

Wireless controller included

MWR-WG00UN

MRW-TAMIM-B14

MIM-N01

CKN-250

MIM-H04UN

Advanced Wired ControllerSimplified Touch Controller

FrontBack

Optional Accessories

External Contact ControlCentral Control Interface Module for Connection to DVM Plus Controls (non-NASA)

Wall Bracket (for outdoor unit)

Wind Baffles

Line Sets - insulated and flared, interconnect cables included

External Temperature SensorWi-Fi Adapter

Wired ControllerMWR-SH11UN

Condensate pump Aspen Mini Orange ASP-MO-UNIV 110-250Blue Diamond BD-BLUE230

Page 2: SUBMITTAL AC012MNADCH/AA Samsung, High-Wall …

888-699-6067 www.SamsungHVAC.com

Page 2 of 3 SUBMITTAL AC012MNADCH/AASamsung, High-Wall Evaporator, Split System AC012MNADCH/AA Dimensional Drawing

No. Name Description1 Liquid pipe connection 1/4"2 3/8"3 Drain pipe connection 11/16" OD4 Power supply & Communication wiring conduit

Knockout hole for left piping

Knockout hole forright piping

29 1/2"

9 3/4"

2 13

/16"

3 7/

16"

9 13

/16"

1 3/4"

1 7/

8"

Knockout hole forlower piping

2 1/4"4 3/4"

29 1/2"

7 1/2" 7 1/2"

5 3/8"

14 15/16"

3 5/16"

2 3/8"

Wall hole for Left Rear Piping

Ø 2 9/16"

5 3/16"

3 5/16"

2 5/8"

13/1

6"

9 13

/16"

1 7/

16"

Installation Plate

Wall hole for RightRear Piping

Ø 2 9/16"

1 7/

16"

Gas pipe connection

Page 3: SUBMITTAL AC012MNADCH/AA Samsung, High-Wall …

888-699-6067 www.SamsungHVAC.com

Page 3 of 3 SUBMITTAL AC012MNADCH/AASamsung, High-Wall Evaporator, Split System AC012KXADCH/AA Dimensional Drawing

24 1/16"

33 9/16"

31 1/8"

13 1

/2"4

7/16

"

21 9

/16"

17 1

5/16

"

21 1

/16"

12 1

/2"

6 7/

8"

4 3/

4"

31 1/8" 11 1/4"

18"

LEFT FRONT RIGHT

TOP

BACK

BOTTOM

No. Name Description

123

Pipe ConnectionPipe Connection

Ø 1/4" FlareØ Flare