ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
HOT WATER COILS
266718
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 1 2© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
1 ROW 2 ROW 1 ROW 2 ROW 1 ROW 2 ROW 1 ROW 2 ROW
10 12 8 ½ ⅞ 21 8 ½ ⅞ 10 305 203 13 22 533 203 13 22
20 12 10 ½ ⅞ 21 10 ½ ⅞ 20 305 254 13 22 533 254 13 22
30 12 10 ½ ⅞ 21 10 ½ ⅞ 30 305 254 13 22 533 254 13 22
UNIT
SIZE
STANDARD COILS HIGH CAPACITY COILS
IMPERIAL UNITS (INCHES)
B CCONNECTION SIZES
B CCONNECTION SIZES
HIGH CAPACITY COILS
CONNECTION SIZES
SI UNITS (mm)
STANDARD COILS
B CUNIT SIZE
B CCONNECTION SIZES
C
5" [127] B
1/2" [13] DIA @ 3" [76]7/8" [22] DIA @ 4 1/4" [108]
WATERCONNECTION
SLIP & DRIVECONNECTION
IN
OUT
SEE NOTE #6
AIRFLOW
CADQ - COIL ACCESS DOORW/QUARTER TURN SASH LATCHES4" [102] X 6 ¾" [171]
CADL - ACCESS DOORW/SNAP LATCHES4" [102] x 6 ¾" [171]
CAD - ACCESS DOOR W/SCREWS4" [102] x 6 ¾" [171]
ACCESS DOOR OPTIONS:
HE
AT
ING
CO
IL
NOTES:1. FABRICATED FROM 22 GA. GALVANIZED STEEL MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.2. HOT WATER COILS HAVE COPPER TUBES AND ALUMINUM FINS WITH O.D. SWEAT CONNECTIONS.3. REFER TO SUBMITTED SCHEDULE FOR AIR VOLUMES AND HOT WATER COIL CAPACITIES.4. METHOD OF VENTING HOT WATER COIL IS TO BE PROVIDED BY INSTALLING CONTRACTOR.5. HAND OF HOT WATER COIL CONNECTIONS IS DETERMINED WHEN VIEWED FROM AIR INLET SIDE.
6. ALLOW 1 1/2" (38) MINIMUM CLEARANCE FOR
INSTALLATION AT THIS END.7. WATER COILS ARE MOUNTED ON DISCHARGE OF UNIT.8. PERFORMANCE RATED AND CERTIFIED IN ACCORDANCE WITH THE CURRENT EDITION OF AHRI STANDARD 410.9. STANDARD COILS SUPPLIED WITH 10 FINS PER INCH, HC COILS - WITH 12 FINS PER INCH.
OPTIONS:�HC - HIGH CAPACITY WATER COIL
DISCHARGE
AIR
PRIMARY
AIR
1" (25) 6 1/2" (165)
B
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
OPTIONAL COIL ACCESS SECTION
LOW PROFILEFAN POWERED TERMINAL
CONSTANT VOLUMECONFIGURATION
SIZES 10,20,30
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
HOT WATER COILS
266718
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 2 2© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
1 ROW 2 ROW 1 ROW 2 ROW 1 ROW 2 ROW 1 ROW 2 ROW
50 21 10 ½ ⅞ 36 10 ⅞ ⅞ 50 533 254 13 22 914 254 22 22
B CCONNECTION SIZES UNIT SIZE
B C
UNIT
SIZE
STANDARD COILS HIGH CAPACITY COILS
IMPERIAL UNITS (INCHES)
B CCONNECTION SIZES
SI UNITS (mm)
CONNECTION SIZESCONNECTION SIZES
HIGH CAPACITY COILSSTANDARD COILS
B C
C
5" [127] B
1/2" [13] DIA @ 3" [76]7/8" [22] DIA @ 4 1/4" [108]
WATERCONNECTION
SLIP & DRIVECONNECTION
IN
OUT
SEE NOTE #6
AIRFLOW
B
HE
AT
ING
CO
IL
CADQ - COIL ACCESS DOORW/QUARTER TURN SASH LATCHES4" [102] X 6 ¾" [171]
CADL - ACCESS DOORW/SNAP LATCHES4" [102] x 6 ¾" [171]
CAD - ACCESS DOOR W/SCREWS4" [102] x 6 ¾" [171]
ACCESS DOOR OPTIONS:
DISCHARGE
AIR
PRIMARY
AIR
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
OPTIONAL COIL ACCESS SECTION
1" (25) 6 1/2" (165)
NOTES:1. FABRICATED FROM 22 GA. GALVANIZED STEEL MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.2. HOT WATER COILS HAVE COPPER TUBES AND ALUMINUM FINS WITH O.D. SWEAT CONNECTIONS.3. REFER TO SUBMITTED SCHEDULE FOR AIR VOLUMES AND HOT WATER COIL CAPACITIES.4. METHOD OF VENTING HOT WATER COIL IS TO BE PROVIDED BY INSTALLING CONTRACTOR.5. HAND OF HOT WATER COIL CONNECTIONS IS DETERMINED WHEN VIEWED FROM AIR INLET SIDE.
6. ALLOW 1 1/2" (38) MINIMUM CLEARANCE FOR
INSTALLATION AT THIS END.7. WATER COILS ARE MOUNTED ON DISCHARGE OF UNIT.8. PERFORMANCE RATED AND CERTIFIED IN ACCORDANCE WITH THE CURRENT EDITION OF AHRI STANDARD 410.9. STANDARD COILS SUPPLIED WITH 10 FINS PER INCH, HC COILS - WITH 12 FINS PER INCH.
OPTIONS:�HC - HIGH CAPACITY WATER COIL
LOW PROFILEFAN POWERED TERMINAL
CONSTANT VOLUMECONFIGURATION
SIZE 50
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
ELECTRIC COILS
CONSTANT VOLUMEFDCLP2266719
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 1 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
q 0 to 10 Vdc CONTROL SIGNALq 4 to 20 mA CONTROL SIGNALq 24 VAC PULSE CONTROL
STANDARD FEATURES HINGED ACCESS DOOR AUTOMATIC RESET THERMAL CUTOUT MANUAL RESET THERMAL CUTOUT FAN INTERLOCKED WITH HEATING ELEMENTS MAGNETIC CONTACTORS 20 GA. GALVANIZED STEEL CONTRUCTION HIGH GRADE NICKEL CHROME HEATING ELEMENTS REFER TO SUBMITTED CONTROL DIAGRAMS FOR
STANDARD CONTROL COMPONTS TO BE SUPPLIED SINGLE POINT ELECTRICAL CONNECTION, EXCEPT
SEPARATE POWER SUPPY FOR 600/3O/3 WIRE SUPPLY VOLTAGE:q 115/1Oq 208/1O (3 WIRE)q 240/1Oq 277/1Oq 480/1O (3 WIRE)q 208/3O (4 WIRE)q 480/3O (4 WIRE)q 600/3O (3 OR 4 WIRE)
••••••••
•
•
OPTIONAL FEATURES
q AIR FLOW SWITCHq CHICAGO CONSTRUCTION (CBC2000)q CONTROL CIRCUIT FUSEq DOOR INTERLOCK DISCONNECT SWITCHq MAIN SUPPLY FUSEq MOTOR FUSEq MERCURY CONTACTORSq SCR CONTROLSq SCR-DAT CONTROLS
q DP - DUAL POINT POWER CONNECTION
NOTES 70 CFM PER KW MINIMUM AIR FLOW ACROSS HEATER COILS. MINIMUM 0.2" w.g.(50 Pa) EXTERNAL STATIC PRESSURE TO OPERATE.
••
DISCHARGE
AIR
HINGED DOOR
NEMA1 ELECTRIC COIL ENCLOSURE
SLIP & DRIVE CONNECTION
PRIMARY
AIR
OUTLET DUCT
SIZE B x C
10 12x8 (305x203) 8 1/2" (216) 19" (483)
UNIT SIZE D E
9 1/2" (241)
6" (152)
24" (610) SZ.10 DOOR SWING
E
C
B
D
NEMA1 CONTROLS ENCLOSURE (OPTIONAL)
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
SIZES 10
10 1/2" (267)
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
ELECTRIC COILS
CONSTANT VOLUMEFDCLP2266719
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 2 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
OUTLET DUCT
SIZE B x C
20
30
UNIT SIZE D E
12x10 (305x254) 10 1/2" (267) 10 1/2" (267)
STANDARD FEATURES HINGED ACCESS DOOR AUTOMATIC RESET THERMAL CUTOUT MANUAL RESET THERMAL CUTOUT FAN INTERLOCKED WITH HEATING ELEMENTS MAGNETIC CONTACTORS 20 GA. GALVANIZED STEEL CONTRUCTION HIGH GRADE NICKEL CHROME HEATING ELEMENTS REFER TO SUBMITTED CONTROL DIAGRAMS FOR
STANDARD CONTROL COMPONTS TO BE SUPPLIED SINGLE POINT ELECTRICAL CONNECTION, EXCEPT
SEPARATE POWER SUPPY FOR 600/3O/3 WIRE SUPPLY VOLTAGE:q 115/1Oq 208/1O (3 WIRE)q 240/1Oq 277/1Oq 480/1O (3 WIRE)q 208/3O (4 WIRE)q 480/3O (4 WIRE)q 600/3O (3 OR 4 WIRE)
••••••••
•
•
OPTIONAL FEATURESq AIR FLOW SWITCHq CHICAGO CONSTRUCTION (CBC2000)q CONTROL CIRCUIT FUSEq DOOR INTERLOCK DISCONNECT SWITCHq MAIN SUPPLY FUSEq MOTOR FUSEq MERCURY CONTACTORSq SCR CONTROLSq SCR-DAT CONTROLSq DP - DUAL POINT POWER CONNECTION
NOTES 70 CFM PER KW MINIMUM AIR FLOW ACROSS HEATER COILS. MINIMUM 0.2" w.g.(50 Pa) EXTERNAL STATIC PRESSURE TO OPERATE.
••
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
23 3/4" (603)
E
NEMA1 ELECTRICCOIL ENCLOSURE
NEMA1 CONTROLSENCLOSURE (OPTIONAL)
9 1/2" (241)
DISCHARGE
AIR
B
C D
PRIMARY
AIR
SLIP & DRIVE CONNECTION
SIZES 20&30
20" DOOR SWING SZ.20,30
6" (152)
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
ELECTRIC COILS
CONSTANT VOLUMEFDCLP2266719
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 3 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
OUTLET DUCT
SIZE B x C
50 21x10 (533x254) 10 1/2" (267) 11 1/2 (292)
UNIT SIZE D E
DISCHARGE
AIR
PRIMARY
AIR
NEMA1 CONTROLS ENCLOSURE (OPTIONAL)
SLIP & DRIVE CONNECTION
HINGED DOORNEMA1 ELECTRIC COIL ENCLOSURE
C
B
D
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
q 0 to 10 Vdc CONTROL SIGNALq 4 to 20 mA CONTROL SIGNALq 24 VAC PULSE CONTROL
STANDARD FEATURES HINGED ACCESS DOOR AUTOMATIC RESET THERMAL CUTOUT MANUAL RESET THERMAL CUTOUT FAN INTERLOCKED WITH HEATING ELEMENTS MAGNETIC CONTACTORS 20 GA. GALVANIZED STEEL CONTRUCTION HIGH GRADE NICKEL CHROME HEATING ELEMENTS REFER TO SUBMITTED CONTROL DIAGRAMS FOR
STANDARD CONTROL COMPONTS TO BE SUPPLIED SINGLE POINT ELECTRICAL CONNECTION, EXCEPT
SEPARATE POWER SUPPY FOR 600/3O/3 WIRE SUPPLY VOLTAGE:q 115/1Oq 208/1O (3 WIRE)q 240/1Oq 277/1Oq 480/1O (3 WIRE)q 208/3O (4 WIRE)q 480/3O (4 WIRE)q 600/3O (3 OR 4 WIRE)
••••••••
•
•
OPTIONAL FEATURES
q AIR FLOW SWITCHq CHICAGO CONSTRUCTION (CBC2000)q CONTROL CIRCUIT FUSEq DOOR INTERLOCK DISCONNECT SWITCHq MAIN SUPPLY FUSEq MOTOR FUSEq MERCURY CONTACTORSq SCR CONTROLSq SCR-DAT CONTROLS
q DP - DUAL POINT POWER CONNECTION
NOTES 70 CFM PER KW MINIMUM AIR FLOW ACROSS HEATER COILS. MINIMUM 0.2" w.g.(50 Pa) EXTERNAL STATIC PRESSURE TO OPERATE.
••
SIZES 50 W/ ROUND INLET
9 1/2" (241)
1 1/3" (34)
20" (508)DOOR SWING
23 3/4" (603) E
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
ELECTRIC COILS
CONSTANT VOLUMEFDCLP2266719
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 4 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
OUTLET DUCT
SIZE B x C
50 21x10 (533x254) 10 1/2" (267) 11 1/2 (292)
UNIT SIZE D E
DISCHARGE
AIR
PRIMARY
AIR
C
B
D
q 0 to 10 Vdc CONTROL SIGNALq 4 to 20 mA CONTROL SIGNALq 24 VAC PULSE CONTROL
STANDARD FEATURES HINGED ACCESS DOOR AUTOMATIC RESET THERMAL CUTOUT MANUAL RESET THERMAL CUTOUT FAN INTERLOCKED WITH HEATING ELEMENTS MAGNETIC CONTACTORS 20 GA. GALVANIZED STEEL CONTRUCTION HIGH GRADE NICKEL CHROME HEATING ELEMENTS REFER TO SUBMITTED CONTROL DIAGRAMS FOR
STANDARD CONTROL COMPONTS TO BE SUPPLIED SINGLE POINT ELECTRICAL CONNECTION, EXCEPT
SEPARATE POWER SUPPY FOR 600/3O/3 WIRE SUPPLY VOLTAGE:q 115/1Oq 208/1O (3 WIRE)q 240/1Oq 277/1Oq 480/1O (3 WIRE)q 208/3O (4 WIRE)q 480/3O (4 WIRE)q 600/3O (3 OR 4 WIRE)
••••••••
•
•
OPTIONAL FEATURES
q AIR FLOW SWITCHq CHICAGO CONSTRUCTION (CBC2000)q CONTROL CIRCUIT FUSEq DOOR INTERLOCK DISCONNECT SWITCHq MAIN SUPPLY FUSEq MOTOR FUSEq MERCURY CONTACTORSq SCR CONTROLSq SCR-DAT CONTROLS
q DP - DUAL POINT POWER CONNECTION
NOTES 70 CFM PER KW MINIMUM AIR FLOW ACROSS HEATER COILS. MINIMUM 0.2" w.g.(50 Pa) EXTERNAL STATIC PRESSURE TO OPERATE.
••
SIZES 50 W/14X8 INLET
23 3/4" (603)
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
SLIP & DRIVE CONNECTION
NEMA1 CONTROLS ENCLOSURE (OPTIONAL)
NEMA1 ELECTRIC COIL ENCLOSURE
6" (152)
E
23" (584)
20" HINGED DOOR SWING
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
B
ATTENUATOR
DISCHARGEFDCLP2/FDCLP2-DOAS266720
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/30/2020
OF REVSHEET 1 2© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
B C B C
10 12 8 305 203
20 12 10 305 254
30 12 10 305 254
NO COIL OR STANDARD REHEAT COIL
UNIT
SIZE
IMPERIAL UNITS (INCHES) SI UNITS (mm)
B C B C
10 21 8 533 203
20 21 10 553 254
30 21 10 533 254
SI UNITS (mm)UNIT
SIZE
IMPERIAL UNITS (INCHES)
HIGH CAPACITY REHEAT COIL
36" (914)OR 59" (1499)
B
C
DISCHARGE
AIR
PRIMARY
AIR
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
OPTIONAL COIL ACCESS SECTION
HEATING COIL
SIZES 10-30
SIZES 10-30 W/ STANDARDREHEAT COIL
NOTES: 22 GA. GALVANIZED STEEL HOUSING, MECHANICALLY SEALED LEAK RESISTANT CONSTRUCTION. INTERNAL INSULATION - 1/2" [13] THICK, MIN. 1.5# DENSITY WHICH MEETS REQUIREMENTS OF NFPA90A AND UL181. SLIP AND DRIVE CONNECTION ENDS AS SHOWN.ATTENUATORS SHIPPED LOOSE. SLIP AND DRIVE CLEATS PROVIDED WHERE REQUIRED.
OPTIONS:� 3FT DISCHARGE ATTENUATOR SECTION (DAS3)� 5FT DISCHARGE ATTENUATOR SECTION (DAS5)
••••
LINERS:� 1/2" FIBERFREE (FF50)� 5/8" FOIL FACED FIBERBOARD (FB)
DISCHARGE ATTENUATOR
DISCHARGE
AIR
PRIMARY
AIR
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)SIZES 10-30 W/ NO COIL
DISCHARGE ATTENUATOR
1" (25)
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
B
ATTENUATOR
DISCHARGEFDCLP2/FDCLP2-DOAS266720
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/30/2020
OF REVSHEET 2 2© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
NOTES: 22 GA. GALVANIZED STEEL HOUSING, MECHANICALLY SEALED LEAK RESISTANT CONSTRUCTION. INTERNAL INSULATION - 1/2" [13] THICK, MIN. 1.5# DENSITY WHICH MEETS REQUIREMENTS OF NFPA90A AND UL181. SLIP AND DRIVE CONNECTION ENDS AS SHOWN.ATTENUATORS SHIPPED LOOSE. SLIP AND DRIVE CLEATS PROVIDED WHERE REQUIRED.
OPTIONS:� 3FT DISCHARGE ATTENUATOR SECTION (DAS3)� 5FT DISCHARGE ATTENUATOR SECTION (DAS5)
••••
SIZES 50
DISCHARGE
AIR
PRIMARY
AIR
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
OPTIONAL COIL ACCESS SECTION
SIZE 50/14x8 W/ STANDARDREHEAT COIL
LINERS:� 1/2" FIBERFREE (FF50)� 5 / 8" FOIL FACED FIBERBOARD (FB)
36" (914)OR 59" (1499)
B
C
B C B C
50 21 10 533 254
NO COIL OR STANDARD REHEAT COIL
UNIT
SIZE
IMPERIAL UNITS (INCHES) SI UNITS (mm)
DISCHARGE
AIR
PRIMARY
AIR
SENSIBLE COOLING COIL (FDCLP2-DOAS ONLY)
SIZE 50/14x8 W/ NO COIL
HEATING COIL
1" (25)
DISCHARGE ATTENUATOR
DISCHARGE ATTENUATOR
B C B C
50 36 10 914 254
HIGH CAPACITY REHEAT COIL
UNIT
SIZE
IMPERIAL UNITS (INCHES) SI UNITS (mm)
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
D
FILTERS
266722
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/30/2020
OF REVSHEET 1 3© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FAN POWERED TERMINALSFDCLP2
SIZES 10-50
FDCLP2-1-1
MERV 3
NOTES:1. 1" [25] NOMINAL FILTER MEDIA2. CARDBOARD FRAME3. MERV3 RATING (THROWAWAY)
W H W H
10 16 8½ 406 216
20,30 16 11 406 279
50 26 11 660 279
IMPERIAL UNITS (INCHES) S.I. UNITS (mm)UNIT
SIZE
W WMERV 3 FILTER MERV 3 FILTER
SIZES 10,20,30,50 SIZE 50/14x8
MERV 3 FILTERFILTERS CLIPPED TO HOSUING
REINFORCED MEDIA SIDE W
H
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
D
FILTERS
266722
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/30/2020
OF REVSHEET 2 3© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FAN POWERED TERMINALSFDCLP2
SIZES 10-50
FDCLP2-1-1
MERV 3, MERV 8, MERV 13
MERV8/ MERV13 FILTER RACKFILTERS SLIDE INTO RAIL, RAILFASTENED TO COOLING COILHOUSING
MERV 3 FILTERFILTERS SLIDE INTO RAIL, RAILFASTENED TO COOLING COILHOUSING
NOTES:1. CARDBOARD FRAME2. 2 FILTERS PER UNIT REQUIRED
OPTIONS:� 1" [25] NOMINAL FILTER MERV3 RATING [FTRM81]� 2" [51] NOMINAL FILTER MERV8 RATING [FTRM82]� 2" [51] NOMINAL FILTER MERV13 RATING [FTRM132]
W H W H
10 21 3/4 7 1/2 552 191
20,30 18 1/4 10 464 254
50 26 10 660 254
IMPERIAL UNITS (INCHES) S.I. UNITS (mm)UNIT
SIZE
W
H
W
H
1" (25)
2" (51)
MERV FILTER 1" (25) FOR MERV3 FILTER2" (51) FOR MERV8/MERV 13 FILTERS
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
D
FILTERS
266722
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/30/2020
OF REVSHEET 3 3© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FAN POWERED TERMINALSFDCLP2
SIZES 10-50
FDCLP2-1-1
NOTES:1. 1" [25] NOMINAL FILTER MEDIA2. CARDBOARD FRAME3. MERV3 RATING (THROWAWAY)
W H W H
10 16 8½ 406 216
20,30 12 11 305 279
IMPERIAL UNITS (INCHES) S.I. UNITS (mm)UNIT
SIZE
W
H
MERV 3 FILTERFILTERS CLIPPED TO HOUSING
MERV3 FILTER
REINFORCED MEDIA SIDE W
W/ IAS
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
O
HBS
HANGER BRACKETSPRING ISOLATION241538
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/24/2020
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
NOTES:1. HANGER BRACKETS AND SPRING LOADED BRACKETS ARE SHIPPED LOOSE FOR FIELDINSTALLATION BY OTHERS2. ORIENT THE ISOLATOR AS SHOWN TO PROPERLY DAMPEN TERMINAL3. RED SPRING LOAD RANGE: 16 LBS - 35 LBS4. YELLOW SPRING LOAD RANGE: 36 LBS - 65 LBS5. FOR FDCLP2 DOAS SIZE 50 8 ROW COIL USE YELLOW (X2)
BASE UNIT DAS/SLR IAS/IAS90 EC/WCEC+SM/PM
LINERRSLR
DOAS SENSIBLE
COOLING COIL
FxV 20-30 RED (X4) RED (X2) RED (X2) - RED (X2) - -
FxV 40-60 YELLOW (X4) RED (X2) RED (X2) - - - -
FxVLP 20-40 RED (X4) RED (X2) RED (X2) - - - -
FDCLP2 10 RED (X4) RED (X2) RED (X2) - - - -
FDCLP2 20-30 RED (X4) RED (X2) RED (X2) RED (X2) - - -
FDCLP2 50 YELLOW (X4) RED (X2) - YELLOW (X2) - - -
FDCLP2 50 14x8 YELLOW (X6) RED (X2) - YELLOW (X2) - - -
FDCLP2 DOAS 10 YELLOW (X4) RED (X2) - - - RED (X2) RED (X2)
FDCLP2 DOAS 20,30,50 YELLOW (X4) RED (X2) - YELLOW (X2) - RED (X2) RED (X2) SEE NOTE 5
FDCLP2 DOAS 50 14x8 YELLOW (X6) RED (X2) - YELLOW (X2) - RED (X2) RED (X2) SEE NOTE 5
PRODUCT
HBS QTY REQUIRED
1.50 38MAX
3.47 88MAX
FASTEN HANGER BRACKETTO ISOLATOR
HANGER BRACKET
TERMINAL UNIT
FROM CEILING SUPPORT SYSTEM
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
ACCESSORIES
HANGER BRACKETS [HB]LOCATIONS
FOR FDCLP2 / FDCLP2-DOAS266727
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 1 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
C FDCLP2-1-1
NOTES: HANGER BRACKETS ARE 12 GAUGE ZINC COATED STEEL 4 PER FAN UNIT (6 FOR SIZE 50, 14x8), 2 PER DISCHARGE
ATTENUATOR, 2 PER INLET ATTENUATOR BRACKETS ARE SHIPPED LOOSE FOR FIELD INSTALLATION FOR
USE WITH THREADED HANGER RODS (BY OTHERS) LAYOUT INDICATES SUGGESTED HANGER BRACKET LOCATIONS
••
•
•
3 3/16" [81]
1" [25]
O1/2" [13]
3/4" [19]
1 1/2" [38]2" [51]
UNIT SIZE W L
10 32 48
20 26 41
30 26 41
50 44 54
UNIT SIZE L W
10 813 1219
20 660 1041
30 660 1041
50 1118 1372
IMPERIAL UNITS (INCHES) SI UNITS (mm)
FDCLP2 SIZES 10-50 WITHOUT PROTECTIVESHROUD
FDCLP2 SIZE 50 14X8 WITHPROTECTIVE SHROUD
FDCLP2 SIZES 10-50 WITH PROTECTIVESHROUD
FDCLP2 SIZE 50 14X8 WITHOUTPROTECTIVE SHROUD
W
1 25 TYP
L
1 25 TYP
L W
1 25 TYP
W L W L
1 25 TYP
1 25 TYP1 25 TYP
UNIT HANGER BRACKET3 3/16" [81]
1" [25] 1/2" [13]1 1/2" [38]
3/4" [19]
O1/2" [13]
SENSIBLE COOLING COIL HANGER BRACKET
SENSIBLE COOLING COIL HANGERBRACKETS MOUNT FLUSHWITH FLANGE ON COIL INLETDO NOT SCREW THROUGH TUBES
SENS
IBLE C
OOLIN
G COIL
(FDCL
P2-D
OAS O
NLY)
SENS
IBLE C
OOLIN
G COIL
(FDCL
P2-D
OAS O
NLY)
SENS
IBLE C
OOLIN
G COIL
(FDCL
P2-D
OAS O
NLY)
SENS
IBLE C
OOLIN
G COIL
(FDCL
P2-D
OAS O
NLY)
SENSIBLE COOLING COIL HANGERBRACKETS MOUNT FLUSHWITH FLANGE ON COIL INLETDO NOT SCREW THROUGH TUBES
SENSIBLE COOLING COIL HANGERBRACKETS MOUNT FLUSHWITH FLANGE ON COIL INLETDO NOT SCREW THROUGH TUBES
SENSIBLE COOLING COIL HANGERBRACKETS MOUNT FLUSHWITH FLANGE ON COIL INLETDO NOT SCREW THROUGH TUBES
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
ACCESSORIES
HANGER BRACKETS [HB]LOCATIONS
FOR FDCLP2 / FDCLP2-DOAS266727
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 2 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
C FDCLP2-1-1
NOTES: HANGER BRACKETS ARE 12 GAUGE ZINC COATED STEEL 4 PER FAN UNIT (6 FOR SIZE 50, 14x8), 2 PER DISCHARGE
ATTENUATOR, 2 PER INLET ATTENUATOR BRACKETS ARE SHIPPED LOOSE FOR FIELD INSTALLATION FOR
USE WITH THREADED HANGER RODS (BY OTHERS) LAYOUT INDICATES SUGGESTED HANGER BRACKET LOCATIONS
••
•
•
3 3/16" [81]
1" [25]
O1/2" [13]
3/4" [19]
1 1/2" [38]2" [51]
UNIT SIZE W L
10 32 48
20 26 41
30 26 41
50 44 54
UNIT SIZE L W
10 813 1219
20 660 1041
30 660 1041
50 1118 1372
IMPERIAL UNITS (INCHES)
SI UNITS (mm)
FDCLP2 SIZE 10 WITH ELECTRICCOIL
FDCLP2 SIZE 20, 30, & 50 WITHELECTRIC COIL
L
W
1 25 TYP
1 25 TYP
1 25 TYP
L
W
1 25 TYP
1 25 TYP
1 25 TYP
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
ACCESSORIES
HANGER BRACKETS [HB]LOCATIONS
FOR FDCLP2 / FDCLP2-DOAS266727
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 3 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
C FDCLP2-1-1
3 3/16" [81]
1" [25]
O1/2" [13]
3/4" [19]
1 1/2" [38]2" [51]
UNIT SIZE W L
10 32 48
20 26 41
30 26 41
50 44 54
UNIT SIZE L W
10 813 1219
20 660 1041
30 660 1041
50 1118 1372
IMPERIAL UNITS (INCHES)
SI UNITS (mm)
NOTES: HANGER BRACKETS ARE 12 GAUGE ZINC COATED STEEL 4 PER FAN UNIT (6 FOR SIZE 50, 14x8), 2 PER DISCHARGE
ATTENUATOR, 2 PER INLET ATTENUATOR BRACKETS ARE SHIPPED LOOSE FOR FIELD INSTALLATION FOR
USE WITH THREADED HANGER RODS (BY OTHERS) LAYOUT INDICATES SUGGESTED HANGER BRACKET LOCATIONS
••
•
•
L
W
1 25 TYP
FDCLP2 WITH WATER COIL
1 25 TYP
W
1 25 TYP
L 1 25 TYP
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
ACCESSORIES
HANGER BRACKETS [HB]LOCATIONS
FOR FDCLP2 / FDCLP2-DOAS266727
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 4 4© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
C FDCLP2-1-1
UNIT SIZE W L
10 32 48
20 26 41
30 26 41
50 44 54
UNIT SIZE L W
10 813 1219
20 660 1041
30 660 1041
50 1118 1372
IMPERIAL UNITS (INCHES)
SI UNITS (mm)
3 3/16" [81]
1" [25]
O1/2" [13]
3/4" [19]
1 1/2" [38]2" [51]
FDCLP2 SIZE 50 14X8 WITHRETURN SILENCER
FDCLP2 SIZE 10-50 WITHRETURN SILENCER
W L
1 25 TYP
5 127 TYP
W L
1 25 TYP
5 127 TYP
1 25 TYP
UNIT HANGER BRACKET3 3/16" [81]
1" [25] 1/2" [13]1 1/2" [38]
3/4" [19]
O1/2" [13]
SENSIBLE COOLING COIL HANGER BRACKET
SENSIBLE COOLING COIL HANGERBRACKETS MOUNT FLUSHWITH FLANGE ON COIL INLETDO NOT SCREW THROUGH TUBES
SENSIBLE COOLING COIL HANGERBRACKETS MOUNT FLUSHWITH FLANGE ON COIL INLETDO NOT SCREW THROUGH TUBES
-
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
0
RETURN SILENCER
FDCLP2-DOASALL SIZES
271378
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
06/25/2020
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2020
So
lid E
dge
FDCLP2-1-1
B C B C
10 43 1/2 7 1/2 1105 191
20/30 36 1/2 10 927 254
50 50 10 1270 254
UNIT SIZEIMPERIAL UNITS (INCHES) SI UNITS (mm)
STANDARD CONSTRUCTION: MEDIUM PRESSURE STYLE, 22 GAUGE GALVANIZED CASING WITH PERFORATED LINER
OVER FIBERGLASS ACOUSTIC MEDIA.•
SIZE 10, 20, 30, 50
PRIMARY
AIRDISCHARGE
AIR
RETURN SILENCER RETURN
AIR
B
C
13 330
12 305
1 25
SENSIBLE COOLING COIL
SIZE 50/14x8
PRIMARY
AIR
DISCHARGE
AIR
SENSIBLE COOLING COIL
RETURN SILENCER RETURN
AIR
266718-C (003).PDF266719-C.PDF266720-B.PDF266722-D.PDF241538-O.PDF266727-C.PDF271378-0.PDF