Basics of Substation Protection
Said Salim PalayiAEE,
Electrical Division, KSEB Limited, Manjeri, Kerala, South India
![Page 2: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/2.jpg)
Protection - Why Is It Needed?
FAULT• Short circuit produced by failure of insulation.
PROTECTION IS INSTALLED TO :• Detect fault occurrence and isolate the faulted equipment.
SO THAT :• Damage to the faulted equipment is limited;• Disruption of supplies to adjacent equipment is minimized.• Danger to staff or the public is avoided
All Power Systems may experience faults at some time.
![Page 3: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/3.jpg)
Faults Are Mainly Caused By Insulation Failure
Underground Cables
Diggers
Overloading
Oil Leakage
Ageing
![Page 4: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/4.jpg)
Faults Are Mainly Caused By Insulation Failure
Overhead Lines
LightningKitesTreesMoistureSaltBirdsFailure of discsBroken Conductors
![Page 5: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/5.jpg)
Faults Are Mainly Caused By Insulation Failure
Machines
Mechanical Damage
Unbalanced Load
![Page 6: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/6.jpg)
Types of Faultabce
Ø/E
Ø/Ø/E
Ø/Ø
e
abc
3Ø3Ø/E
e
abc
abc
abc
![Page 7: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/7.jpg)
EQPT / FEEDER
BREAKER
RELAY
BATTERY
INSTRUMENT TRANSFORMERS
![Page 8: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/8.jpg)
Types Of Protection - Principles
Most of the protective relays in substation works in the following principle.
1.Over current Protection 2.Differential Protection3.Pilot wire protection4.Distance Protection
![Page 9: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/9.jpg)
1. Overcurrent Protection
Requires secure DC auxiliaryNo trip if DC fails
IF'IF
DCBATTERY
SHUNTTRIP COIL
51
![Page 10: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/10.jpg)
1. Overcurrent ProtectionEarth Fault Relay Connection - 3 Wire System
Combined with OC relays
E/F OC OC OC E/F OC OC
Economise using 2x OC relays
![Page 11: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/11.jpg)
Over current protection Parallel Feeders
Consider fault on one feeder :-
Relays ‘C’ and ‘D’ see the same fault current (I2). As ‘C’ and ‘D’ have similar settings both feeders will be tripped.
51 A 51C
51 B 51D
LOAD
I1 + I2I1
I2
![Page 12: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/12.jpg)
Parallel FeedersSolution:- Directional Control at ‘C’ and ‘D’
Relay ‘D’ does not operate due to current flow in the reverse direction.
51 A 67C
51 B 67D
LOAD
I1 + I2I1
I2
![Page 13: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/13.jpg)
Establishing Direction:- Polarising Voltage
The DIRECTION of Alternating Current may only be determined with respect to a COMMON REFERENCE.
The most convenient reference quantity is POLARISING VOLTAGE taken from the Power System Voltages.
![Page 14: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/14.jpg)
Polarizing Voltage for Directional Over current Relay
IA
VA
90
VBVC
MAX SENSITIVITYLINEOPERATE
IA FOR MAXSENSITIVITYRESTRAIN 45
45
135
VA
VBC VBC
RELAY CURRENTVOLTAGE
A IA VBC
B IB VCA
C IC VAB
![Page 15: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/15.jpg)
Residual Voltage for E/F RelayMay be obtained from ‘broken’ delta V.T. secondary.
VRES = VA-G + V B-G + VC-G = 3V 0
ABC
VRES
VC-GVB-GVA-G
![Page 16: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/16.jpg)
Application of Overcurrent Protection
Overcurrent & Earth fault Protection is used.•HT lines•Transformers•Generators•Reactors•Capacitor Banks•Motors•Neutral displacement relays in capacitor banks•EHT lines (Directional overcurrent &E/F)•Breaker failure Protection
![Page 17: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/17.jpg)
2. Differential Principle
It works on the principle of comparing the current entering and leaving a protected object. If there is a difference, It is assumed that there is some internal fault and relay operates according to the setting
Protected object
Relay
![Page 18: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/18.jpg)
Differential Protection Principle (1)
ProtectedCircuit
R
P1 P2
S2 S1P1P2
S2S1
External fault - Current circulates between the HV & LV CTs; no current thro’ the relay No Trip
![Page 19: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/19.jpg)
Differential Protection Principle (2)
ProtectedCircuit
R
For an internal fault the unbalanced current flows thro’ the relay So Relay operates
P1P1 P2P2
S1S1 S2S2
![Page 20: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/20.jpg)
Differential Relays are used for Transformers Generators
Application of Differential Relay
![Page 21: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/21.jpg)
Restricted Earthfault Protection Increased sensitivity for earth
faults REF elements for each transformer winding
CTs may be shared with differential element
Uses differential principle
6464
64
![Page 22: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/22.jpg)
![Page 23: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/23.jpg)
Restricted Earthfault Protection
P1S1
P2S2
P1S1
P2S2P1S1
P2S2
P1
P2
S1
S2
Stability level : usually maximum through fault level of transformer
REF Case I : Normal Condition
Under normal conditions no current flows thro’ RelaySo, No Operation
![Page 24: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/24.jpg)
Restricted Earthfault ProtectionREF Case II : External Earth Fault
External earth fault - Current circulates between the phase & neutral CTs; no current thro’ the relay
So, No Operation
![Page 25: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/25.jpg)
Restricted Earthfault ProtectionREF Case III : Internal Earth Fault
For an internal earth fault the unbalanced current flows thro’ the relay
So, Relay Operates
![Page 26: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/26.jpg)
Bus bar protection Relay
• Bus bar protection works on the differential principle.
![Page 27: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/27.jpg)
Single bus - Busbar Protection
BUSBARZONE
F1
• Fast clearance by breakers at the busbars
![Page 28: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/28.jpg)
3. Pilot wire Protection using OFC communication
Relay at End ‘B’ measures current and transmits the value to Relay at end ‘A’ thru optical fibre cable. Relay ‘A’ compares measured value and the value recived from ‘B’.
If both values are same, relay keeps restraint state. If there is difference in values. Relays operates.
A B
R RRelayin
gPoint
Trip A
Trip B
CommunicationChannel
RelayingPoint
PGCIL Areakode S/S
![Page 29: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/29.jpg)
Pilot wire protection
Used for – EHT cables – short distance EHT transmission lines
![Page 30: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/30.jpg)
4.Distance• . Distance
For : Transmission and Sub-Transmission CircuitsAlso used as Back-up Protection for Transformers and Generators
![Page 31: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/31.jpg)
Impedance Relay
Operate
IF
VF
Restrain
Spring
Trip
zF
Ampere Turns : VF IZ
Trip Conditions : VF < IFZ
jIX
IZ V1V2V3
IR
TRIP STABLE
Voltage to Relay = VCurrent to Relay = IReplica Impedance = ZTrip Condition : S2 <
S1where : S1 = IZ Z
S2 = V ZFIncreasing VR has a Restraining Effect VR called Restraining VoltageIncreasing IR has an Operating Effect
![Page 32: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/32.jpg)
Basic Principle of Distance Protection
LOADLRRR Z Z V Zmeasured Impedance
RelayPT.
Normal Load
IR ZLZS
VRVS ZLOAD
The relay is set based on the line impedance.The measured ZR is more than the relay
setting Z , hence relay restrains
![Page 33: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/33.jpg)
Basic Principle of Distance Protection
Fault
IRZS
VRVS ZLOAD
ZL
ZF
Impedance Measured ZR = VR/IR = ZF
Relay Operates if ZF < Zwhere Z = setting
Increasing VR has a Restraining Effect VR called Restraining Voltage
Increasing IR has an Operating Effect
![Page 34: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/34.jpg)
• It is assumed that there will be an error up to 20% in distance relay measurements.
• Hence distance relay setting is divided into Zones • Normally 3 zones are for dist. Relay• Zone-1 is instantaneous and covers 80% of protected
line.• Zone- 2 covers 120% of line & is normally with 0.4 s time
delay• Zone -3 covers next line from the substation also & 0.75
seconds timedelay.
Distance Protection - Zones
![Page 35: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/35.jpg)
Zones of Protection
RA
D
CB
Z1A
Z2A
Z3A
jX
![Page 36: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/36.jpg)
Zones of Protection
Z2A Z2C
Z3A Z3C
Time
T3
T2
Z1CZ1A
Z1B DCA
Z2BT2
Z1A = 80% of ZAB
Z2A = 120% of ZAB
Z3A(FORWARD) = 120% of {ZAB + ZCD}
B
![Page 37: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/37.jpg)
Distance Relay -features
POWER SWING BLOCKING Provides Stability during Power swing.
VT SUPERVISION Blocks tripping of Distance Relay when VT supply fails.
SOTF (Switch- On-To-Fault.) Function enables high speed tripping when line is energized to a persisting fault.
![Page 38: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/38.jpg)
AUTORECLOSINGMAINTAINS STABILITY AND SUPPLY BY FAST RECLOSING OF THE TRIPPED FEEDER.
CARRIER INTERTRIPS are provided for fast clearance of faults for entire line.
Distance Protection- features
![Page 39: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/39.jpg)
Distance Relay Applications
• Transmission lines• Sub transmission line• Backup protection for generators
![Page 40: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/40.jpg)
Other type of relays used in substation
![Page 41: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/41.jpg)
1.Under / Over Voltage Relays
– Used for protection of capacitor banks.– Under voltage relays are also used for interlocking of line
Earth switches.
![Page 42: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/42.jpg)
2.Under Frequency Relays
– Monitors the frequency of Power system– Initiates commands for load shedding if system goes
below specified value.
![Page 43: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/43.jpg)
3.DC supervision
DC supervision relay– Indicates the failure of DC supply to the panel.– DC source holds the flag in reset condition– When DC fails, the flag drops. – N/C contact is wired to the annunciator for alarm.– N/O contact is wired to the SCADA
![Page 44: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/44.jpg)
4.AC supervision relay
• Indicates the failure of AC to the panel.• AC is necessary for the operation of space
heaters.
![Page 45: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/45.jpg)
5.Overfluxing Relay
Low frequency High voltage Geomagnetic disturbances
Causes
Over fuxing = V/F
![Page 46: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/46.jpg)
Overfluxing Relay
Transient Over fluxing - Tripping of differential element Prolonged Over fluxing - Damage to transformers
Over flux relay measures V/f ratio and in it gives alarm in stage-1 (usually set at 110%)
It gives trip signal in stage-2 (set at 120%)
Effects
![Page 47: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/47.jpg)
6.Master Trip Relay• It will transfer the actuation of trip signal from
relays to the circuit breaker• A circuit breaker normally open (52a) contact
is used to interrupt trip coil current. This saves trip coil from burning out due to continuous current flow.
• Burning of trip coil may happen if this contact is faulty.
![Page 48: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/48.jpg)
7.Trip circuit supervision
• It gives supervision of trip circuit healthiness• Pre close supervision checks the
healthiness of CB when the CB is open condition. (It is wired through the Normally Closed ( 52b) auxiliary contact of the CB).
• Post close supervision checks the healthiness of CB when the CB is in Closed condition. (it is wired though Normally Open ( 52b) auxiliary contact of the CB)
![Page 49: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/49.jpg)
8.Pole discordance relay
• Used in CBs with single pole tripping• This relay confirm whether all poles are
Opened or Closed, if not it will generate a trip signal.
![Page 50: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/50.jpg)
pole discordance relay scheme
![Page 51: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/51.jpg)
9.Breaker Failure Protection (LBB)A PROTECTION WHICH IS DESIGNED TO CLEAR A SYSTEM FAULTY BY INITIATING TRIPPING OTHER CIRCUIT BREAKER(S) IN THE CASE OF FAILURE TO TRIP OF THE APPROPRIATE CIRCUIT BREAKER.
IN MODERN NETWORKS THE CRITICAL FAULT CLEARING TIME MAY BE LESS THAN 200ms. HENCE, IF THE FAULT IS NOT CLEARED DUE TO FAILURE OF THE PRIMARY PROTECTIVE RELAYS OR THEIR ASSOCIATED CIRCUIT BREAKER, A FAST ACTING BACK-UP PROTECTIVE RELAY MUST CLEAR THE FAULT.
![Page 52: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/52.jpg)
LBB/BFR FLOW CHART
MAIN PROTECTIONOPERATED
YES
YES
TRIP MAINBREAKER
INITIATE BFR
WAIT FOR FAULT CLEARENCE
AND
FAULT CLEARED
YES
NO
RESET BREAKER FAILURE SCHEME
TRIP BACK-UP BREAKERS
![Page 53: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/53.jpg)
10.Low SF6 alarm/lockout
Stage-1 : Alarm•Alarm stage indicates the inadequate gas pressure inside CB.Stage-2 :Lockout.•Lock out stage blocks the operation of CB. No tripping or closing will happen then.
![Page 54: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/54.jpg)
11.Control Relays
• Auto-Reclose Relay Used to auto reclosing of EHT feeders
• Tap change control RelayUsed for regulating the output voltage of transformer by raising/lowering the tap
![Page 55: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/55.jpg)
12. Transformer Accessories • 1) Buchholz Relay.• 2) Oil Temperature Indicator.• 3) Winding Temperature Indicator.• 4) Magnetic Oil Level Gauge ( MOLG).• 5) Pressure relief device ( PDR).
![Page 56: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/56.jpg)
Oil temperature Indicator.
• Indicates the temperature of the oil inside transformer.
• Gives alarm/Trip signal
![Page 57: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/57.jpg)
Wednesday, May 3, 2023
Sensing device
Temperature indicator
Capilary tube
![Page 58: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/58.jpg)
Oil Temperature Indicator
Fitted on the Thermometer pocket.
![Page 59: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/59.jpg)
Winding Temperature relay
• Give indications about the temperature of winding temperature of oil.
![Page 60: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/60.jpg)
WTI with HOT spot simulation CT arrangement.
![Page 61: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/61.jpg)
FAN CONTROL CUBICLE
S1=alarm S2=trip
S3=cooler control 1S4=cooler control 2
Winding temperature indicator
![Page 62: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/62.jpg)
12.2 Pressure Relief Device (PRD)
• When pressure inside transformer exceeds the PRV will operate to release excessive pressure inside the transformer.
• It issues a trip command and visual indication by operation of a liver (from horizontal position to vertical position)
![Page 63: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/63.jpg)
Spring Operated Pressure relief device
![Page 64: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/64.jpg)
12.3 Buchholtz relay
• Mechanical relay which has two mercury switches.
• When gas enters the chamber the position of switches deflects and it will make alarm in stage-1 and trip in stage-2 in Main tank Buchholz relay.
• Only trip signal is provided in OLTC buchholz relay.
![Page 65: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/65.jpg)
Buchholz Relay Installation
5 x internal pipediameter (minimum)
3 x internal pipediameter (minimum)
Transformer
3 minimum
Oil conservator
Conservator
![Page 66: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/66.jpg)
Buchholtz Relay arrangement.
![Page 67: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/67.jpg)
12.4 MAGNETIC OIL LEVEL GAUGE (MOLG)
• Mounting 15 0 Inclination.• The movement of the float is transmitted to
the pointer by using a magnetic coupling.• The follower magnet follows the driving
magnet.• The driving magnet remains inside the
conservator and the other magnet out side the conservator.
![Page 68: Substation protection basics](https://reader035.vdocument.in/reader035/viewer/2022081414/5887b2161a28ab817a8b4a8b/html5/thumbnails/68.jpg)
Wednesday, May 3, 2023
EMPT
Y
1/41/
23/
4FULL
MOLGFLOATING MEMBER
PERMANENT MAGNET
BEARING