Download - Tb 03600001 e
February 2007
CA08102001E For more information visit:
www.eaton.com
Contents
Vacuum Contactors & Starters 36-1
36
Vacu
um
Co
nta
cto
rs &
Sta
rte
rs
Description Page
NEMA, Special Purpose and Mining Rating
Product Family Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-2
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-3
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-4
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-6
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-8
NEMA, Enclosed Control
Product Family Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-11
Contactors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-14
Non-combination Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-15
Combination Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-17
Modification Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36-23
Size 4 Vacuum Contactor
February 2007
36-2
For more information visit:
www.eaton.com
CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining Rating
Product Family Overview
Size 4 Vacuum Contactor
Product Description
Vacuum Contactors and Starters were designed for starting and controlling three-phase, 50/60 Hz, AC motors. Each contact is enclosed in a vacuum bottle to reduce and contain contact arcing. This design offers excellent performance for plugging and jogging applications.
Application Description
The Vacuum Contactors and Starters are offered in three classifications. They are NEMA rated devices up to 600V AC, Special Purpose rated devices up to 1500V AC and Mining rated devices rated up to 1500V AC. Each device is tested to different stan-dards to serve their market.
Typical applications include full voltage control of three-phase squirrel cage motors, primary control of low voltage wound rotor motors and circuit switching for low voltage capac-itors for power factor improvement.
A vacuum contactor is affected by atmospheric pressure on the bellows of the vacuum bottles. Up to an alti-tude of 6600 feet, the contactor is designed to tolerate normal variations in barometric pressure. If the contactor is to be operated above 6600 feet above sea level, consult your Eaton’s Cutler-Hammer representative.
Features
■
Rugged, compact and lightweight
■
Quiet operation
■
Electrical and mechanical interlocks available
■
Long service life
Benefits
■
Easy maintenance with front remov-able coil and auxiliaries
■
Eliminate extra surge suppressors with the standard low chop interrupters
■
Plan your preventative mainte-nance schedule by utilizing the con-tact wear indicator, standard on all vacuum bottles
Operation
The contact structure of the vacuum break contactor is located inside sealed ceramic tubes that have been evacuated of air. Any arc occurring across the contacts upon opening is automatically extinguished because ionized air is not available to sustain it — the arc breaks when the current passes through zero. The arc typically does not service beyond the first half cycle once the contacts begin to sepa-rate. The large arc chutes normally associated with contactors of this size are not required. The ceramic tube with the moving and stationary con-tacts is called a
vacuum interrupter
or
bottle
. There is one bottle for each pole on the contactor. A metal bellows (like a small, circular accordion) within the bottle allows the moving contact to be closed and pulled open from the outside without leaking air into the bottle. Both the bellow and the metal-to-ceramic seals of these state-of-the-art bottles have been refined to the point where the possibility of loss of vacuum has been virtually eliminated.
Standards and Certifications
■
NEMA Devices
❑
UL Listed File #E1491, Guide Number NLDX
❑
CSA Approved
■
Special Purpose Devices
❑
IEC 947-4-1
❑
CE Approved EN 60947-4-1
❑
UL Listed File #E1491, Guide Number NLDX
❑
CSA Approved
February 2007
CA08102001E For more information visit:
www.eaton.com
36-3Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining Rating
Product Selection
Product Selection
When Ordering Specify
■
Catalog Number
■
Heater Pack if ordering a Starter, order in quantities of three
■
Any required Accessories
Table 36-1. NEMA Rated Product Selection
�
Starters use Type B overload relay. Refer to Heater Coil Selection Table,
Page 36-5
. Starters do not include Heater Packs.
�
Coils are rated for 50/60 Hz applications.
Table 36-2. Special Purpose Product Selection
�
Starters use Type B overload relay. Refer to Heater Coil Selection Table,
Page 36-5
. Starters do not include Heater Packs.
�
Coils are rated for 50/60 Hz applications.
�
The 540A device does not carry CE or IEC ratings.
NEMASize
Ampere Rating
Motor Voltage
Maximum Horsepower Rating
Magnet
�
Coil Voltage
ContactorNon-reversing
ContactorReversing
Starter Non-reversing
�
Catalog Number
Price U.S. $
Catalog Number
Price U.S. $
Catalog Number
Price U.S. $
4 135 200230380460575
405075
100100
110/120
V201K4CJ V211K4CJ V200M4CJC
220/240
V201K4CK V211K4CK V200M4CK
440/480
V201K4CU V211K4CU V200M4CU
5 270 200230380460575
75100150200200
110/120
V201K5CJZ1 V211K5CJZ1 V200M5CJC
220/240
V201K5CKZ1 V211K5CKZ1 V200M5CK
440/480
V201K5CUZ1 V211K5CUZ1 V200M5CU
6 540 200230380460575
150200300400400
110/120
V201K6CJZ1 V211K6CJZ1 V200M6CJC
220/240
V201K6CKZ1 V211K6CKZ1 V200M6CK
440/480
V201K6CUZ1 — V200M6CU
AmpereRating
Motor Voltage
Maximum Horsepower Rating
Magnet
�
Coil Voltage
Contactor Non-reversing
ContactorReversing
StarterNon-reversing
�
StarterReversing
�
Catalog Number
Price U.S. $
Catalog Number
Price U.S. $
Catalog Number
Price U.S. $
Catalog Number
Price U.S. $
160 200230380460575800
1500
5060
100125150200400
110/120
V201KRCJ V211KRCJ —
—
—
—
220/240
V201KRCK V211KRCK —
—
—
—
380/415
V201KRCH V211KRCH —
—
—
—
440/480
V201KRCU V211KRCU —
—
—
—
320 200230380460575795
1500
100125200250300400800
110/120
V201KTCJZ1 V211KTCJZ1 V200MTCJC V210MTCJC
220/240
V201KTCKZ1 V211KTCKZ1 V200MTCK V210MTCK
380/415
V201KTCHZ1 V211KTCHZ1 V200MTCH V210MTCH
440/480
V201KTCUZ1 V211KTCUZ1 V200MTCU V210MTCU
540
�
200230380460575795
1500
150200300400500700
1300
110/120
V201KVCJZ1 V211KVCJZ1 V200MVCJ V210MVCJ
220/240
V201KVCKZ1 V211KVCKZ1 V200MVCK V210MVCK
380/415
V201KVCHZ1 — V200MVCH —
440/480
V201KVCUZ1 — V200MVCU —
610 200230380460575795
1500
200200300450500800
1600
110/120
V201KZCJZ1 V211KZCJZ1 —
—
—
—
220/240
V201KZCKZ1 V211KZCKZ1 —
—
—
—
380/415
V201KZCHZ1 — —
—
—
—
440/480
V201KZCUZ1 — —
—
—
—
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . .
1CD1C
February 2007
36-4
For more information visit:
www.eaton.com
CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining Rating
Accessories
Table 36-3. Mining Rated Product Selection
�
Coils are rated for 50/60 Hz applications.
Accessories
Lug Sizes
■
Size 4 — 12 – 4/0
■
NEMA Size 5 & 6 and 320A, 540A & 610A — Supplied without Line or Load Lugs.
Table 36-4. Lug Kits — Consist of 6 Lugs
Field Modification Kits
Auxiliary Electrical Contacts
Size 4 — Three Type J auxiliary contacts may be mounted on the top of Size 4 contactors to provide six auxiliary, isolated 600V, 10A contacts for use in control circuits.
Sizes 5 – 6 — Two Type J auxiliary contacts may be mounted on each side of Size 5 and 6 contactors to provide four auxil-iary, isolated 600V,10A contacts for use in control circuits.
Table 36-5. Auxiliary Electrical Contacts
Table 36-6. Horizontal Mechanical Interlock
AEGIS Powerline Filters
Ideal for applications that utilize 120V AC or 240V AC control voltage and have the likelihood of harmonics or noise being present on the control signal. These are stand-alone devices, not mounted to thecontactor.
Hardwired Surge Filler that Protects Critical Loads (3 and 5 Ampere Models)
AEGIS Powerline Filters Protect Against the Full Spectrum of Transient Disturbances
AEGIS filters the entire sine wave and is effective against both frequently occurring low energy and occasional high energy transients. High energy transients can create imme-diate damage, while low energy transients cause coil failure over time.
Table 36-7. AEGIS-HW (Hard Wire Application) Catalog Numbering System
�
Model tested at 15A UL/CSA = 16A CE.
Table 36-8. AEGIS Powerline Filters
�
See AEGIS Powerline Filters in Tab 10 of Distribution Catalog.
�
Discount Symbol
22-CD.
AmpereRating
Motor Voltage
Maximum Horsepower Rating
Magnet
�
Coil Voltage
Contactor Non-reversing
Catalog Number
Price U.S. $
160 200230380460575800
1500
5060
100125150200400
110/120
VM160CJ
220/240
VM160CK
440/480
VM160CU
320 200230380460575795
1500
100125200250300400800
110/120
VM320CJZ1
220/240
VM320CKZ1
440/480
VM320CUZ1
610 200230380460575795
1500
150200300400500700
1300
110/120
VM610CJZ1
220/240
VM610CKZ1
440/480
VM610CUZ1
Size Description CatalogNumber
PriceU.S. $
5 and 320A 1/0 – 500 kcmil
C325KAL8
6, 540A and 610A 1/0 – 500 kcmil Dbl. Barrel
C325KAL9
610A 1/0 – 600 kcmil Dbl. Barrel
80-19825-2
Contact Arrangement CatalogNumber
PriceU.S. $
1NO, 1NC2NO2NC
J11J20J02
Size CatalogNumber
PriceU.S. $
456
180C113G04180C113G16180C113G17
Catalog Number
��
Price U.S. $
AGSHWCH120N03XCAGSHWCH120N03XSAGSHWCH120N05XCAGSHWCH120N05XS
AGSHWCH230L03XCAGSHWCH230L03XSAGSHWCH230L05XCAGSHWCH230L05XS
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . .
1CD1C
Voltage Code
120N230L
Current Capacity
030510
15 �20
AGSHW CH X
Options
S = StandardC = Form C contact
for Remote Monitor
Note: 230V applies to 220V and 240V applications.
February 2007
CA08102001E For more information visit:
www.eaton.com
36-5Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingAccessories
Heater Coils Table 36-9. Heater Coil Selection for Type B Overload Relay
� Three are required per overload relay.
Replacement CoilsTable 36-10. Vacuum Contactor — Replacement Coils
� 125V DC can be directly applied to the Size 5 and 6 coil rated for 120V/60 Hz AC (cannot be applied to Size 4).
� 250V DC can be directly applied to the Size 5 and 6 coil rated for 240V/60 Hz AC (cannot be applied to Size 4).
Motor Full Load Current in Amperes for Use with 3 Heaters Only
Open Starter HeaterCatalog Number�
PriceU.S. $Ambient Compensated
Overload Relay
Size 4 and 160A12.8 – 14.114.2 – 15.515.6 – 17.117.2 – 18.919.0 – 20.8
FH68FH69FH70FH71FH72
20.9 – 22.923.0 – 25.225.3 – 27.827.9 – 30.630.7 – 33.5
FH73FH74FH75FH76FH77
33.6 – 37.537.6 – 41.541.6 – 46.346.4 – 5051 – 55
FH78FH79FH80FH81FH82
56 – 6162 – 6667 – 7374 – 7879 – 84
FH83FH84FH85FH86FH87
85 – 9293 – 101
102 – 110111 – 122123 – 129130 – 133—
FH88FH89FH90FH91FH92FH93FH94
Size 5 and 320A with 300/5 Current Transformers107 – 117118 – 129130 – 141142 – 155156 – 170
FH23FH24FH25FH26FH27
171 – 187188 – 205206 – 224225 – 244245 – 263
FH28FH29FH30FH31FH32
264 – 292293 – 318319 – 350
FH33FH34FH35
Size 6 and 540A with 600/5 Current Transformers236 – 259260 – 283284 – 310311 – 340341 – 374
FH24FH25FH26FH27FH28
375 – 411412 – 448449 – 489490 – 527528 – 585586 – 600
FH29FH30FH31FH32FH33FH34
Description Suffix Part Number Price U.S. $
Size 4110/120V AC, 50/60 Hz220/240V AC, 50/60 Hz380/415V AC, 50/60 Hz440/480V AC, 50/60 Hz
JKHU
9085A57G019085A57G02ID89221G079085A57G03
Size 5110/120V AC, 50/60 Hz220/240V AC, 50/60 Hz380/415V AC, 50/60 Hz440/480V AC, 50/60 Hz
JKHU
7874A09G01 �
7874A09G04 �
7874A09G107874A09G05
Size 6110/120V AC, 50/60 Hz220/240V AC, 50/60 Hz380/415V AC, 50/60 Hz440/480V AC, 50/60 Hz
JKHU
7874A24G01 �
7874A24G02 �
7874A24G077874A24G03
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-6
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingTechnical Data and Specifications
Technical Data and SpecificationsTable 36-11. Specifications
� For transformers having inrush currents of not more than 20 times the rated full load current.
Table 36-12. Electrical Characteristics — Apply to Both NEMA and Special Purpose Types
Table 36-13. Electrical Characteristics Coil Data (AC Supply Rectified)
Description NEMA Special Purpose
Size 4 Size 5 Size 6 160A 320A 540A 610A
V201K4_ V201K5_ V201K6_ V201KR_ V201KT_ V201KV_ V201KZ_
PolesMaximum Voltage RatingAmpere RatingFrequency, HzMaximum Closing Current
3600V135A50/601600A
3600V270A50/603000A
3600V540A50/606000A
31500V160A50/601600A
31500V320A50/603000A
31500V540A50/606000A
31500V610A50/606000A
Maximum Interrupting CurrentShort Time Current: 1 Second
2 SecondDielectric Strength
1600A2400A RMS1600A RMS2200V AC
3000A4500A RMS3000A RMS5375V AC
6000A9000A RMS6000A RMS5375V AC
1600A2400A RMS1600A RMS2200V AC
3000A4500A RMS3000A RMS5375V AC
6000A9000A RMS6000A RMS5375V AC
6000A9000A RMS6000A RMS5375V AC
Maximum Allowable InterruptingImpulse Voltage (1 x 40 mS)
1200/Hr.15 kV
—15 kV
—15 kV
1200/Hr.15 kV
—15 kV
—15 kV
—15 kV
Maximum Motor Horsepower at:200V230V380V460V575V
40 hp50 hp75 hp
100 hp100 hp
75 hp100 hp150 hp200 hp200 hp
150 hp200 hp300 hp400 hp400 hp
50 hp60 hp
100 hp125 hp150 hp
100 hp125 hp200 hp250 hp300 hp
150 hp200 hp300 hp400 hp400 hp
200 hp200 hp300 hp450 hp500 hp
800V1000V1500V
———
———
———
200 hp250 hp400 hp
400 hp—800 hp
——1300 hp
800 hp1000 hp1600 hp
3-Phase Capacitive Switching (kVAR)230V460V600V
1500V
40 kVAR80 kVAR
100 kVAR—
80 kVAR160 kVAR200 kVAR—
160 kVAR320 kVAR400 kVAR—
50 kVAR100 kVAR125 kVAR205 kVAR
80 kVAR160 kVAR200 kVAR500 kVAR
160 kVAR320 kVAR400 kVAR—
176 kVAR356 kVAR400 kVAR
1000 kVAR
Transformer Switching (kVA) �
Single-Phase, 2-Pole:120V240V480V600V
6.8 kVA14 kVA27 kVA34 kVA
14 kVA27 kVA54 kVA68 kVA
27 kVA54 kVA
108 kVA135 kVA
8 kVA16 kVA32 kVA40 kVA
14 kVA27 kVA54 kVA68 kVA
27 kVA54 kVA
108 kVA135 kVA
27 kVA54 kVA
108 kVA135 kVA
Three-Phase, 3-Pole:240V480V600V
23 kVA47 kVA59 kVA
47 kVA94 kVA
117 kVA
94 kVA188 kVA234 kVA
27 kVA55 kVA70 kVA
47 kVA94 kVA
117 kVA
94 kVA188 kVA234 kVA
94 kVA188 kVA234 kVA
Description Size
4 (160A) 5 (320A) 6 (540A and 610A)
DC Coil Data — Burden:(AC Supply Rectified)Open VAClosed VAClosed Watts
300 VA30 VA6W
500 VA25 VA20W
1450 VA32 VA30W
Pick-Up VoltsDrop-Out VoltsPick-Up Time in HzDrop-Out Time in Hz
70% of Rated Voil Volts50% of Rated Coil Volts
1.5 – 2 Hz6 – 6.15 Hz
Max. Voltage RatingMax. Closing CurrentMax. Interrupting CurrentShort Time Current:
1 Second2 Second
600V1600A1600A
2400A RMS1600A RMS
600V3000A3000A
4500A RMS3000A RMS
600V6000A6000A
9000A RMS6000A RMS
Burden Size 4 (160A) Size 5 (320A) Size 6 (540A and 610A)
Inrush VASealed VASealed Watts
300306
6002020
17002828
Pick-Up VoltsDrop-Out Volts
70% of Rated Coil Volts50% of Rated Coil Volts
Pick-Up Time in HzDrop-Out Time in Hz
1.5 – 26 – 7.5
1.5 – 26 – 6.15
1.5 – 26 – 6.15
February 2007
CA08102001E For more information visit: www.eaton.com
36-7Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingWiring Diagrams
Wiring Diagrams
Figure 36-1. Typical Wiring Diagrams
L1 L2 L3
M
M
M
M
M
T1
T2T3
Motor
StartStop
1 2 3A B
+
-
C
Coil Aux. Contact
Size 4 Contactor
D
"C"
L1 L2 L3
M
M
M
S
R
T1
T2
T3
0T
1T
2T
OL
OL
OL
Motor
StartStop
1
2 3
A B OL
95 96
+
-C
L63 Coil Aux. Contact
Sizes 5 & 6 Starter
D
"C"
EncapsulatedCoils and Diode
DisconnectMeans
February 2007
36-8
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingDimensions
Dimensions
Figure 36-2. Open Type Contactors and Starters — Size 4 and 160A — Approximate Dimensions in Inches (mm)
Reset
Front View Shownwithout Cover Plateand Overtravel Gauge.
Recess forAuxiliary Interlock
1.44(36.6)
MechanicalInterlock
Recess forAuxiliary Interlock
10.12(257)
.281 (7.14) Dia.3 Mtg. Holes
.28 (7.1) Dia.3 Mtg. Holes
1.44 (36.6)1.44 (36.6)
3.60(91.4)
4.83 (122.7) 5.94 (150.9)
6.11 (155.2)Max. to Reset6.34 (161.0)Hand Reset
.46(11.7)
.58(14.7)
1.31 (33.3) 1.31 (33.3).65 (16.5)
.46 (11.7)
.38 (9.7).94 (23.9)1.88 (47.8)
9.25(235)
9.97(253.2)
Reset
8.00 (203.2)
9.25(235)
.44(11.2)
4.00(101.6)
.47 (11.9) 6.61 (168)Max. to Reset6.86 (174.2)Hand Reset
.66 (16.8)
.47(11.9)
1.03(26.2)
1.13 (28.7) 4.10(104.1)1.44 (36.6)
1.44 (36.6)4.88 (124)
9.96 (253)
6.38 (162.1)
Size 4 Non-reversing Starter
1.88 (47.8) 1.88 (47.8)
6(152.4)
.28 (7.1)3 Mtg.Slots
3.5 (88.9)
2(50.8)
.44 (11.2) 5.13 (130.3)2.56 (65)
4.88 (124)
7.0 (177.8)
Rear View — Drilling Plan
Rear View — Drilling Plan
Front View
Front View
Size 4 and 160A Reversing Contactor
Size 4 and 160A Non-reversing Contactor
Side Vew
Side View
8.5(215.9)Max.
6.88(174.8)
6.63(168.4)
6(152.4)
.38 (9.7)
9.96 (253)1.44 (36.6)
1.13 (28.7)1.44 (36.6) 6.54
(166.1)
4.2 (106.7)
5.96 (151.4)4.83 (122.7)1.44 (36.6)
1.88 (47.8)
1.88 (47.8)3.6 (91.4)
.94 (23.9)
.94 (23.9)
.28 (7.1) Dia.3 Mtg. Slots
Front View Shownwithout Cover Plate
and OvertravelGauge.
1.44 (36.6)
MechanicalInterlock
Recess forAuxiliaryInterlock
Recess forAuxiliaryInterlock
Rear View — Drilling Plan Front View Side Vew
Size 4 Reversing Starter
Rear View — Drilling Plan Front View Side Vew
2.88 (73.2)
February 2007
CA08102001E For more information visit: www.eaton.com
36-9Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingDimensions
Figure 36-3. Open Type Contactors and Starters — Size 5 and 320A — Approximate Dimensions in Inches (mm)
8(203.2)
.38(9.7)
3.75(95.3)
1.75(44.5)
.62(15.7)
2.74 (69.6)
.38(9.7)
3.75(95.3)
4.1(104.1)
Nameplate
7.5(190.5)
6.75 (171.5)Drilling Plan — Rear View Size 5 and 320A Non-reversing Contactor
.58 (14.7)
3(76.2)
1.5(38.1)
7.28 (184.9)Term. Holes
12.5(317.5)
8.94(227.1)Term.
toTerm.
.13(3.3)
A
B
1.38(35.1)
2.75 (69.9)
A
CoilInterlockLocation
B
6.13 (155.7)
7.75 (196.9)Line End
3.37(85.6)LoadEnd
“A”Dim.
“A” Dim.
22 (558.8)5.73
(145.5)
1.5(38.1)
4.25(108)
2.5(63.5)
2.5(63.5)
3.87(98.3)
1.9(48.3)
1.62 (41.1)
4.21(106.9)
3.65 (92.7)2.5(63.5)
5.22 (132.6)Line Term.
Nameplate
1.5(38.1)
24.24 (615.7) 9.48 (240.8)
6.61 (167.9)
5.93 (150.6)
7.9 (200.7)
2.5(63.5)
2.5(63.5)
1.45(36.8)
5.09 (129.3)Load Term.
2(50.8)
Nameplate
Nameplate
TerminalClamps
AreOptional
Coil InterlockLocation
3/8-16 TapLine TerminalsSix (6) Places
3/8-16 TapLine TerminalsSix (6) Places
18.24(463.3)
14(355.6)
2.12(53.8)
16.43(417.3)
1.45(36.8)
2.5(63.5) 7.89 (200.4)
10.88(276.4)
toCenter
ofReset Rod
.33 (8.4)to Center ofReset Rod
2.48(63)
.86(21.8)
.33 x .75(8.4 x 19.1)Key Holes3 Places
.41 (10.4)Dia.
2 Holes
.33 (8.4)Slot
2 Places
.31 (7.9)Slot
2 Places
A – Two Dual Circuit Interlocks Located on Both Sides of Contactor. (When Used)B – Coil Terminals Located on Both Sides of Contactor.
A – Two Dual Circuit Interlocks Located on Both Sides of Starter. (When Used)B – Coil Terminals Located on Both Sides of Starter.
Size 5 and 320A Reversing Contactor
320A Reversing Starter
8(203.2)
.38(9.7)
7.5(190.5)
6.75 (171.5)Drilling Plan — Rear View Size 5 and 320A Non-reversing Starter
.58 (14.7)
3(76.2)1.88
(47.8)
1.5(38.1)
1.32(33.5)
.53(13.5)
2.56(65.0)
14(355.6)
18(457.2)
.14(3.6)1.38
(35.1)
2(50.8)
.33 x .75(8.4 x 19.1)Key Holes3 Places
.41 (10.4)Dia.
2 Holes
.31 (7.9)Slot
2 Places
.33 (8.4)Slot
2 Places
2.5(63.5)
24 (609.6)1.89 (48.0)
4(101.6)
22.25(565.2)
8 (203.2) Line
3.25(82.6)
10.71(272.0)
7 (177.8)Normal
or Tripped
7 (177.8)Normal
or Tripped
Type B RelayMax. Dim to Reset
Type A RelayMax. Dim to Reset
Type B RelayAutomatic Reset
6.75(171.5)
6.73(170.9)
6.61(167.9)
4.08(103.6)
February 2007
36-10
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingDimensions
Figure 36-4. Open Type Contactors and Starters — Size 6, 540A and 610A — Approximate Dimensions in Inches (mm)
Overload RelayReset Rod
2.38(60.5)
8.16 (207.3)Normal or Tripped
8.90 (226.1)
3.86 (98.0)Load
7.94 (201.7)Reset
2.67(67.8)
2.67(67.8)
1.70(43.2) 2.75
(69.9)2.75
(69.9)
12.62(320.5)
To Centerof Reset
15.94(404.9)Term.Mtg.
20.50(520.7)
WithoutTerm.
17.10(434.3)WithTerm.
8(203.2)
.38(9.7)
8.75(222.3)
12.9(327.7)Term.Holes
13.99(355.3)
6.75 (171.5) .58(14.7)
.33 (8.4)Slot
2 Places
.33 x .75(8.4 x 19.1)Key Holes
2.73(69.3)
2.73(69.3)
4.39(111.5)
5 (127)2.67 (67.8) 2.67 (67.8)
2.67 (67.8)2.67 (67.8)
7 (177.8)
3.75(95.3)
7.87(199.9)
4.88(124)
1.5(38.1)
14.01(355.9)
2.09(53.1)
18.24(463.3)
4.62(117.3)
6.5(165.1)
4.12(104.6)
17.02(432.3)
24.24(615.7)
22(558.8)
2.67(67.8)
2.67(67.8)
Size 6, 540A and 610A Reversing Contactor
4.4(111.8)
1.64(41.7)
7.84(199.1)
3.72 (94.5)Load
1.28(32.5)
Size 6, 540A and 610A Non-reversing Contactor
7.9 (200.7)
A
B
AB
CoilInterlock
CoilInterlock
A – Two Dual Circuit Interlocks Located on Both Sides of Contactor. (When Used)B – Coil Terminals Located on Both Sides of Contactor.
A – Two Dual Circuit Interlocks Located on Both Sides of Starter. (When Used)B – Coil Terminals Located on Both Sides of Starter.
Nameplate
Rear View — Drilling Plan
8(203.2)
.38(9.7)
8.75(222.3)
6.75 (171.5) .58(14.7)
.33 (8.4)Slot
2 Places
.33 x .75(8.4 x 19.1)Key Holes
Rear View — Drilling Plan
Front View Side ViewFront ViewSide Vew
Size 6 and 540A Non-reversing Starter
Front ViewSide View
5 (127)7 (177.8)
24 (609.6)
22 (558.8)
18(457.2)
21.5(546.1)
26(660.4)
16.06(407.9)
14(355.6)
4.13(104.9)
5.43(137.9)
3.23(82)
5.81(147.6)
1.75(44.5)
3.23(82)
3.23(82)
3.23(82)
1.17(29.7)
540A Reversing Starter
1.17(29.7)
8(203.2)
3.64(92.5)
6.5(165.1)
9.16 (232.7)Normal
8.94 (227.1)Reset
1(25.4)
February 2007
CA08102001E For more information visit: www.eaton.com
36-11Vacuum Contactors & Starters
36
NEMA, Enclosed ControlProduct Family Overview
Product Description■ 3-Phase Magnetic■ 3-Pole Full Voltage■ Non-reversing and Reversing■ 600 and 1500V AC Maximum■ Starters with Interchangeable
Heater OLR
Application DescriptionCutler-Hammer® Vacuum Contactors from Eaton’s electrical business are designed for starting and controlling three-phase, 50/60 Hz, AC motors. Motor full load current should not exceed the contactor current rating. These contactors are built in several versions — the nameplate on a spe-cific contactor states the authorized ratings.
Low voltage vacuum contactors can be applied to a wide range of voltages up to 1500V. These applications include full voltage control of three-phase squirrel cage motors, primary control of low voltage wound rotor motors and circuit switching for low voltage capacitors for power factor improvement.
Cat. No. AV10GNOA or V200M5CJCVacuum Break Starter
Features/Benefits■ Rugged, compact, lightweight■ Quiet operation■ Front removable coil and auxiliaries■ Electrical and mechanical interlock-
ing capability■ Low chop interrupters eliminate the
need for surge suppressors■ Contact wear indication allows for
planned maintenance program■ Long service life■ Manual push-to-reset button on
Sizes 5 and 6■ Freedom overload■ SSOL
OperationThe contact structures of these vac-uum break contactors are located inside sealed ceramic tubes which have been evacuated of air. Any arc occurring across the contacts upon opening is automatically extinguished because ionized air is not available to sustain it — the arc breaks when the current passes through zero. The arc typically does not survive beyond the first half cycle once the contacts begin to separate. The large arc chutes nor-mally associated with starters of this size are not required. The ceramic tube with the moving and stationary con-tacts enclosed is called a vacuum interrupter or a bottle, and there is one bottle for each pole of the contac-tor. A metal bellows (like a small, circu-lar accordion) within the bottle allows the moving contact to be closed and pulled open from the outside without leaking air into the bottle. Both the bel-lows and the metal-to-ceramic seals of these state-of-the-art bottles have been refined to the point where the possibility of loss of vacuum has been virtually eliminated.
Contact Force and AltitudeA vacuum contactor is affected by atmospheric pressure on the bellows of the vacuum bottles. Up to an altitude of 6600 feet, the contactor is designed to tolerate normal variations in barometric pressure. If the contactor is to be operated above 6600 feet above sea level, consult Eaton.
Standards and Certifications■ UL listed■ cUL Listed (indicates appropriate
CSA Standand investigation)■ CE Mark available■ ABS Type Approved
February 2007
36-12
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlProduct Family Overview
Cover Control
Non-Reversing
Flange Control KitsFor on-the-job conversion of Type 1, 3R, 4X and 12 enclosed starters. Knockouts are provided on the Type 1 flange. Type 3R, 4X and 12 have prepunched holes with removable hole plugs.
Factory InstalledTo order factory installed pilot devices, change the 9th character of the Catalog Number to the alpha shown in the table below. Example: to order an ECV0548AAA with START/STOP push-buttons and a red pilot light, change the A to a C, i.e. ECV0548ACA.
Reversing
Flange Control KitsFor on-the-job conversion of Type1, 3R, 4X and 12 enclosed starters. Knockouts are provided on the Type1 flange. Type 3R, 4X and 12 have prepunched holes with removable hole plugs.
Factory InstalledTo order factory installed pilot devices, change the 9th character of the Catalog Number to the alpha shown in the table below. Example: to order an ECV1748AAH with FOR/REV/STOP pushbuttons and 2 red pilot lights, change the A to a C, i.e. ECV1748ACH.
Table 36-14. Non-reversing Pilot Device Field Kits and Factory Installation
� Add Code Letter from table below to Catalog Number for voltage — Kits only. Example: C400T9B.
� Type 1 Non-combination, Size 4.� Type 1 Non-combination, Sizes 5 & 6; Type 3R, 4X, 12 Non-combination, all Sizes; All Combination
Control.
Table 36-15. Reversing Pilot Device Field Kits and Factory Installation
� Add Code Letter from table below to Catalog Number for voltage — Kits only. Example: C400T9B.
� Type 1 Non-combination, Size 4.� Type 1 Non-combination, Sizes 5 & 6; Type 3R, 4X, 12 Non-combination, all Sizes; All Combination
Control.� Order quantity 2 of C400T9�.
Description Factory Installed Flange Control
Field Installation Kits
Position9 Alpha
AdderU.S. $
Non-combination � Combination �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
No Cover Mounted Pilot DevicesSTART/STOP Pushbuttonswith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
ABCD
C400GK0C400GK1C400GK12 �
C400GK16 �
—C400T1——
ON/OFF Pushbuttonswith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
EFG
———
C400T2——
HAND/OFF/AUTO Selector Switchwith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
HJK
C400GK3C400GK32 �
C400GK36 �
C400T12——
START PushbuttonON PushbuttonOFF PushbuttonRed RUN Pilot LightGreen OFFRed RUN/Green OFF Pilot Lights
LMNPQR
———C400GK42 �
C400GK41 �
C400GK46 �
C400T3C400T4C400T5C400T9 �
C400T10 �
C400T11 �
START/STOP Selector Switchwith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
STU
———
C400T13——
ON/OFF Selector Switchwith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
VWX
———
C400T14——
Rating CodeLetter
Rating CodeLetter
Rating CodeLetter
120V 60 Hz208V 60 Hz
AE
240V 60 Hz380V 50 Hz
BL
480V 60 Hz600V 60 Hz
CD
Description Factory Installed Flange Control
Field Installation Kits
Position9 Alpha
AdderU.S. $
Non-combination � Combination �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
No Cover Mounted Pilot DevicesFOR/REV/STOP Pushbuttonswith 2 Red Pilot Lightswith 2 Red/1 Green Pilot Lights
ABCD
C400GK0C400GR1C400GR14 �
—
—C400T6——
UP/STOP/DOWN Pushbuttonswith 2 Red Pilot Lights
EF
C400GR2C400GR24 �
——
FOR/OFF/REV Selector Switchwith 2 Red Pilot Lightswith 2 Red/1 Green Pilot Lights
HJK
———
C400T15——
Two Red Pilot LightsOne Green Pilot LightTwo Red/One Green Pilot LightsOPEN/OFF/CLOSE Selector Switchwith 2 Red Pilot Lightswith 2 Red/1 Green Pilot Lights
PQRV
WX
C400GK44 �
C400GK41 �
——
——
�
C400T10 �
—C400T16
——
Rating CodeLetter
Rating CodeLetter
Rating CodeLetter
120V 60 Hz208V 60 Hz
AE
240V 60 Hz380V 50 Hz
BL
480V 60 Hz600V 60 Hz
CD
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-13Vacuum Contactors & Starters
36
NEMA, Enclosed ControlProduct Family Overview
Catalog Number SelectionTable 36-16. NEMA Vacuum Break Catalog Numbering System
Table 36-17. Alternate “Open” Catalog NumbersListed “Open”Catalog Number
Alternate “Open”Catalog Number
AV10FNOAAV10GNOABAV10JNOAB
V200M4CJCV200M5CJCV200M6CJC
CV10FN3ACV10GN3ACV10JN3A
V201K4CJV201K5CJZ1V201K6CJZ1
E C V 0 5 5 1 A A A -
Design
V = Vacuum
Modification Codes
See Pages 36-23 – 36-32
Contactors
3 = 3 Poles
Starters
Cover Control
Coil Voltage or Motor Voltage
A = 120VB = 230VC = 460V
D = 575VE = 200VV = 380V
Disconnect Fuse Clip Ratings
A =H =J =K =
None200A/250V R200A/600V R400A/250V R
L =M =N =
400A/600V R600A/250V R600A/600V R
Breaker Ratings
A =H =J =
None150A250A
K =L =M =
400A600A800A
NEMA Size
4 5 6
Class Page
01 =02 =05 =06 =07 =
ContactorsReversing ContactorsFVNR Starter, Non-combinationReversing Starter, Non-combinationFVNR Starter, Non-combination, with CPT
36-1436-1436-1536-1536-16
16 =17 =18 =22 =23 =24 =
Combination with Disconnect SwitchReversing Combination with Disconnect SwitchCombination with Disconnect Switch, with CPTCombination with Circuit BreakerReversing Combination with Circuit BreakerCombination with Circuit Breaker, with CPT
36-1736-1836-1936-2036-2136-22
Enclosure Type
1 = 1 — General Purpose2 = 3R — Rainproof3 = 4 — Painted Steel4 = 4X — 304-Grade Stainless Steel8 = 12 — Dust-Tight9 = 4X — 316-Grade Stainless Steel
February 2007
36-14
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlContactors
Product SelectionTable 36-18. Class ECV01 — Non-reversing Contactors — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0144A3A. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.
Table 36-19. Class ECV02 — Reversing Contactors — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X
304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV024A3A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.
Field Modification KitsAuxiliary Electrical ContactsTwo Type J auxiliary contacts may be mounted on each side to provide four auxiliary, isolated 600V, 10A double break contacts for use in control circuits.
Table 36-20. Auxiliary Contacts
Table 36-21. Horizontal Mechanical Interlock
Enclosed Ampere Rating
Motor Voltage
Max. hpRating
Magnet Coil Voltage �
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight Industrial
Component Contactor (Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4135 —
200230380460575
—405075
100100
110/120 ECV0141A3A ECV0142A3A ECV0144A3A ECV0148A3A CV10FN3A
NEMA Size 5270 —
200230380460575
—75
100150200200
110/120 ECV0151A3A ECV0152A3A ECV0154A3A ECV0158A3A CV10GN3A
NEMA Size 6540 —
200230380460575
—150200300400400
110/120 ECV0161A3A ECV0162A3A ECV0164A3A ECV0168A3A CV10JN3A
Enclosed Ampere Rating
Motor Voltage
Max. hpRating
Magnet Coil Voltage �
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight Industrial
Component Contactor (Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4135 —
200230380460575
—405075
100100
110/120 ECV0241A3A ECV0242A3A ECV0244A3A ECV0248A3A V211K4CJ
NEMA Size 5270 —
200230380460575
—75
100150200200
110/120 ECV0251A3A ECV0252A3A ECV0254A3A ECV0258A3A V211K5CJZ1
NEMA Size 6540 —
200230380460575
—150200300400400
110/120 ECV0261A3A ECV0262A3A ECV0264A3A ECV0268A3A V211K6CJZ1
Contact Arrangement
CatalogNumber
PriceU.S. $
1NO-1NC2NO2NC
J11J20J02
Size CatalogNumber
PriceU.S. $
456
180C113G04180C113G12180C113G13
Technical Data . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-15Vacuum Contactors & Starters
36
NEMA, Enclosed ControlNon-combination Starters
Product SelectionTable 36-22. Class ECV05 — Non-reversing Non-combination Starters — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0544AAA. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.
Table 36-23. Class ECV06 — Reversing Non-combination Starters — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X
304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0644AAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� All Type 12 enclosures are standardized with external reset. For internal reset, order Mod-ification Code R5.
Enclosed Ampere Rating
Motor Voltage
Max. hpRating
Magnet Coil Voltage �
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset �
Component Starter(Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4135 —
200230380460575
—405075
100100
110/120 ECV0541AAA ECV0542AAA ECV0544AAA ECV0548AAA AV10FNOA
NEMA Size 5270 —
200230380460575
—75
100150200200
110/120 ECV0551AAA ECV0552AAA ECV0554AAA ECV0558AAA AV10GNOAB
NEMA Size 6540 —
200230380460575
—150200300400400
110/120 ECV0561AAA ECV0562AAA ECV0564AAA ECV0568AAA AV10JNOAB
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Enclosed Ampere Rating
Motor Voltage
Max. hpRating
Magnet Coil Voltage �
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset �
Component Starter(Open)
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4135 —
200230380460575
—405075
100100
110/120 ECV0641AAA ECV0642AAA ECV0644AAA ECV0648AAA V210M4CJC
NEMA Size 5270 —
200230380460575
—75
100150200200
110/120 ECV0651AAA ECV0652AAA ECV0654AAA ECV0658AAA V210M5CJC
NEMA Size 6540 —
200230380460575
—150200300400400
110/120 ECV0661AAA ECV0662AAA ECV0664AAA ECV0668AAA V210M6CJC
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Technical Data . . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-16
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlNon-combination Starters
Table 36-24. Class ECV07 — Non-reversing Non-combination Starters with CPT — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0744EAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.
Enclosed Ampere Rating
Motor Voltage
Max. hpRating
Magnet Coil Voltage
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset �
Component Starter(Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4135 200
230380460575
405075
100100
110/120 ECV0741EAAECV0741BAAECV0741VAAECV0741CAAECV0741DAA
ECV0742EAAECV0742BAAECV0742VAAECV0742CAAECV0742DAA
ECV0744EAAECV0744BAAECV0744VAAECV0744CAAECV0744DAA
ECV0748EAAECV0748BAAECV0748VAAECV0748CAAECV0748DAA
AV10FNOA
NEMA Size 5270 200
230380460575
75100150200200
110/120 ECV0751EAAECV0751BAAECV0751VAAECV0751CAAECV0751DAA
ECV0752EAAECV0752BAAECV0752VAAECV0752CAAECV0752DAA
ECV0754EAAECV0754BAAECV0754VAAECV0754CAAECV0754DAA
ECV0758EAAECV0758BAAECV0758VAAECV0758CAAECV0758DAA
AV10GNOAB
NEMA Size 6540 200
230380460575
150200300400400
110/120 ECV0761EAAECV0761BAAECV0761VAAECV0761CAAECV0761DAA
ECV0762EAAECV0762BAAECV0762VAAECV0762CAAECV0762DAA
ECV0764EAAECV0764BAAECV0764VAAECV0764CAAECV0764DAA
ECV0768EAAECV0768BAAECV0768VAAECV0768CAAECV0768DAA
AV10JNOAB
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Technical Data . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-17Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Product SelectionTable 36-25. ECV16 — Non-reversing Combination Starters — Fusible and Non-fusible with Disconnect Switch — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV01644AAH. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
NEMA Size
Motor Voltage
Max. hpRatingDualElementFuses
Fuse ClipAmperes/DisconnectAmperes
Type 1General Purpose
Type 3RRainproof
Type 4XWatertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset ��
Component Starter(Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
Fusible — 110/120 Magnet Coil Voltage �
4 200230380460575
405075
100100
200A ECV1641AAHECV1641AAHECV1641AAJECV1641AAJECV1641AAJ
ECV1642AAHECV1642AAHECV1642AAJECV1642AAJECV1642AAJ
ECV1644AAHECV1644AAHECV1644AAJECV1644AAJECV1644AAJ
ECV1648AAHECV1648AAHECV1648AAJECV1648AAJECV1648AAJ
AV10FNOA
5 200230380460575
75100150200200
400A ECV1651AAKECV1651AAKECV1651AALECV1651AALECV1651AAL
ECV1652AAKECV1652AAKECV1652AALECV1652AALECV1652AAL
ECV1654AAKECV1654AAKECV1654AALECV1654AALECV1654AAL
ECV1658AAKECV1658AAKECV1658AALECV1658AALECV1658AAL
AV10GNOA
6 200230380460575
150200300400400
600A ECV1661AAMECV1661AAMECV1661AANECV1661AANECV1661AAN
ECV1662AAMECV1662AAMECV1662AANECV1662AANECV1662AAN
ECV1664AAMECV1664AAMECV1664AANECV1664AANECV1664AAN
ECV1668AAMECV1668AAMECV1668AANECV1668AANECV1668AAN
AV10JNOA
Non-fusible — 110/120 Magnet Coil Voltage �
4 —200230380460575
—405075
100100
200A ECV1641AAA ECV1642AAA ECV1644AAA ECV1648AAA AV10FNOA
5 —200230380460575
—75
100150200200
400A ECV1651AAA ECV1652AAA ECV1654AAA ECV1658AAA AV10GNOA
6 —200230380460575
—150200300400400
600A ECV1661AAA ECV1662AAA ECV1664AAA ECV1668AAA AV10JNOA
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Type 12 Non-reversing Vacuum Starter with Fused Disconnect
Technical Data . . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-18
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-26. ECV17 — Reversing Combination Starters — Fusible and Non-fusible with Disconnect Switch — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV1744AAH. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
NEMA Size
Motor Voltage
Max. hpRatingDualElementFuses
Fuse ClipAmperes/DisconnectAmperes
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset ��
Component Starter(Open)
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
Fusible — 110/120 Magnet Coil Voltage4 200
230380460575
405075
100100
200A ECV1741AAHECV1741AAHECV1741AAJECV1741AAJECV1741AAJ
ECV1742AAHECV1742AAHECV1742AAJECV1742AAJECV1742AAJ
ECV1744AAHECV1744AAHECV1744AAJECV1744AAJECV1744AAJ
ECV1748AAHECV1748AAHECV1748AAJECV1748AAJECV1748AAJ
V210M4CJC
5 200230380460575
75100150200200
400A ECV1751AAKECV1751AAKECV1751AALECV1751AALECV1751AAL
ECV1752AAKECV1752AAKECV1752AALECV1752AALECV1752AAL
ECV1754AAKECV1754AAKECV1754AALECV1754AALECV1754AAL
ECV1758AAKECV1758AAKECV1758AALECV1758AALECV1758AAL
V210M5CJC
6 200230380460575
150200300400400
600A ECV1761AAMECV1761AAMECV1761AANECV1761AANECV1761AAN
ECV1762AAMECV1762AAMECV1762AANECV1762AANECV1762AAN
ECV1764AAMECV1764AAMECV1764AANECV1764AANECV1764AAN
ECV1768AAMECV1768AAMECV1768AANECV1768AANECV1768AAN
V210M6CJC
Non-fusible — 110/120 Magnet Coil Voltage4 —
200230380460575
—405075
100100
200A ECV1741AAA ECV1742AAA ECV1744AAA ECV1748AAA V210M4CJC
5 —200230380460575
—75
100150200200
400A ECV1751AAA ECV1752AAA ECV1754AAA ECV1758AAA V210M5CJC
6 —200230380460575
—150200300400400
600A ECV1761AAA ECV1762AAA ECV1764AAA ECV1768AAA V210M6CJC
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Technical Data . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-19Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-27. ECV18 — Non-reversing Combination Starters — Fusible and Non-fusible with Disconnect Switch and CPT — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV1844EAH. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
NEMA Size
Motor Voltage
Max. hpRatingDualElementFuses
Fuse ClipAmperes/DisconnectAmperes
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset ��
Component Starter(Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
Fusible — 110/120 Magnet Coil Voltage4 200
230380460575
405075
100100
200A ECV1841EAHECV1841BAHECV1841VAJECV1841CAJECV1841DAJ
ECV1842EAHECV1842BAHECV1842VAJECV1842CAJECV1842DAJ
ECV1844EAHECV1844BAHECV1844VAJECV1844CAJECV1844DAJ
ECV1848EAHECV1848BAHECV1848VAJECV1848CAJECV1848DAJ
AV10FNOA
5 200230380460575
75100150200200
400A ECV1851EAKECV1851BAKECV1851VALECV1851CALECV1851DAL
ECV1852EAKECV1852BAKECV1852VALECV1852CALECV1852DAL
ECV1854EAKECV1854BAKECV1854VALECV1854CALECV1854DAL
ECV1858EAKECV1858BAKECV1858VALECV1858CALECV1858DAL
AV10GNOA
6 200230380460575
150200300400400
600A ECV1861EAMECV1861BAMECV1861VANECV1861CANECV1861DAN
ECV1862EAMECV1862BAMECV1862VANECV1862CANECV1862DAN
ECV1864EAMECV1864BAMECV1864VANECV1864CANECV1864DAN
ECV1868EAMECV1868BAMECV1868VANECV1868CANECV1868DAN
AV10JNOA
Non-fusible — 110/120 Magnet Coil Voltage4 200
230380460575
405075
100100
200A ECV1841EAAECV1841BAAECV1841VAAECV1841CAAECV1841DAA
ECV1842EAAECV1842BAAECV1842VAAECV1842CAAECV1842DAA
ECV1844EAAECV1844BAAECV1844VAAECV1844CAAECV1844DAA
ECV1848EAAECV1848BAAECV1848VAAECV1848CAAECV1848DAA
AV10FNOA
5 200230380460575
75100150200200
400A ECV1851EAAECV1851BAAECV1851VAAECV1851CAAECV1851DAA
ECV1852EAAECV1852BAAECV1852VAAECV1852CAAECV1852DAA
ECV1854EAAECV1854BAAECV1854VAAECV1854CAAECV1854DAA
ECV1858EAAECV1858BAAECV1858VAAECV1858CAAECV1858DAA
AV10GNOA
6 200230380460575
150200300400400
600A ECV1861EAAECV1861BAAECV1861VAAECV1861CAAECV1861DAA
ECV1862EAAECV1862BAAECV1862VAAECV1862CAAECV1862DAA
ECV1864EAAECV1864BAAECV1864VAAECV1864CAAECV1864DAA
ECV1868EAAECV1868BAAECV1868VAAECV1868CAAECV1868DAA
AV10JNOA
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Type 12 Non-reversing Vacuum Starter with HMCP
Technical Data . . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-20
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-28. Class ECV22 — Non-reversing Combination Starters with HMCP or Magnetic Trip Circuit Breakers — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV2244AAH. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Motor Voltage
Max. hpRating
Magnet Coil Voltage �
CircuitBreakerType
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset ��
Component Starter(Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4200230380460575
405075
100100
110/120 HMCP 150A ECV2241AAH ECV2242AAH ECV2244AAH ECV2248AAH AV10FNOA
NEMA Size 5200230460575
6075
150200
110/120 HMCP 250A ECV2251AAJ ECV2252AAJ ECV2254AAJ ECV2258AAJ AV10GNOA
200230380460
75100150200
110/120 HMCP 400A ECV2251AAK ECV2252AAK ECV2254AAK ECV2258AAK AV10GNOA
NEMA Size 6200230460575
100150300300
110/120 HMCP 600A ECV2261AAL ECV2262AAL ECV2264AAL ECV2268AAL AV10JNOA
230460575
200400400
110/120 MD 800A ECV2261AAM ECV2262AAM ECV2264AAM ECV2268AAM AV10JNOA
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Technical Data . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-21Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-29. Class ECV23 — Reversing Combination Starters with HMCP or Magnetic Trip Circuit Breakers — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV2344AAH. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Motor Voltage
Max. hpRating
Magnet Coil Voltage �
CircuitBreakerType
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset ��
Component Starter(Open)
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4200230380460575
405075
100100
110/120 HMCP 150A ECV2341AAH ECV2342AAH ECV2344AAH ECV2348AAH V210M4CJC
NEMA Size 5200230460575
6075
150200
110/120 HMCP 250A ECV2351AAJ ECV2352AAJ ECV2354AAJ ECV2358AAJ V210M5CJC
200230380460
75100150200
110/120 HMCP 400A ECV2351AAK ECV2352AAK ECV2354AAK ECV2358AAK V210M5CJC
NEMA Size 6200230460575
100150300300
110/120 HMCP 600A ECV2361AAL ECV2362AAL ECV2364AAL ECV2368AAL V210M6CJC
230460575
200400400
110/120 MD 800A ECV2361AAM ECV2362AAM ECV2364AAM ECV2368AAM V210M6CJC
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Technical Data . . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-22
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-30. Class ECV24 — Non-reversing Combination Starters with HMCP or Magnetic Trip Circuit Breakers and CPT — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV2444EAH. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Motor Voltage
Max. hpRating
Magnet Coil Voltage
CircuitBreakerType
Type 1General Purpose
Type 3RRainproof
Type 4X Watertight & Dust-TightStainless Steel �
Type 12Dust-Tight IndustrialExternal Reset ��
Component Starter(Open) �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
NEMA Size 4200230380460575
405075
100100
110/120 HMCP 150A ECV2441EAHECV2441BAHECV2441VAHECV2441CAHECV2441DAH
ECV2442EAHECV2442BAHECV2442VAHECV2442CAHECV2442DAH
ECV2444EAHECV2444BAHECV2444VAHECV2444CAHECV2444DAH
ECV2448EAHECV2448BAHECV2448VAHECV2448CAHECV2448DAH
AV10FNOA
NEMA Size 5200230460575
6075
150200
110/120 HMCP 250A ECV2451EAJECV2451BAJECV2451CAJECV2451DAJ
ECV2452EAJECV2452BAJECV2452CAJECV2452DAJ
ECV2454EAJECV2454BAJECV2454CAJECV2454DAJ
ECV2458EAJECV2458BAJECV2458CAJECV2458DAJ
AV10GNOA
200230380460
75100150200
110/120 HMCP 400A ECV2451EAKECV2451BAKECV2451VAKECV2451CAK
ECV2452EAKECV2452BAKECV2452VAKECV2452CAK
ECV2454EAKECV2454BAKECV2454VAKECV2454CAK
ECV2458EAKECV2458BAKECV2458VAKECV2458CAK
AV10GNOA
NEMA Size 6200230460575
100150300300
110/120 HMCP 600A ECV2461EALECV2461BALECV2461CALECV2461DAL
ECV2462EALECV2462BALECV2462CALECV2462DAL
ECV2464EALECV2464BALECV2464CALECV2464DAL
ECV2468EALECV2468BALECV2468CALECV2468DAL
AV10JNOA
230460575
200400400
110/120 MD 800A ECV2461BAMECV2461CAMECV2461DAM
ECV2462BAMECV2462CAMECV2462DAM
ECV2464BAMECV2464CAMECV2464DAM
ECV2468BAMECV2468CAMECV2468DAM
AV10JNOA
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Technical Data . . . . . . . . . . . . . . . . . Page 36-6Accessories, Kits . . . . . . . . . . . . . . . Page 36-4Wiring Diagrams . . . . . . . . . . . . . . . . Page 36-5Cover Control . . . . . . . . . . . . . . . . . . . Page 36-12Modifications . . . . . . . . . . . . . . . . . . . Page 36-23Dimensions . . . . . . . . . . . . . . . . . . . . PG03300001EDiscount Symbol . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-23Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Modification Codes Table 36-31. A — Ammeters, Auxiliary Contacts, Accelerating Relays, Autotransformers
� Oversize enclosure will be provided for IT. Starters.� Top mounted auxiliary contacts cannot be added to contactors in Box 1
(Type 1).� Not available for IT. Starters.
Table 36-31. A — Ammeters, Auxiliary Contacts, Accelerating Relays, Autotransformers (Continued)
� Not available for IT. Starters.
Table 36-32. B — Breaker Modifications, Backspin Timer,Undervoltage Release, Bell Alarm, Bus Choke
� A DC bus choke may be used in place of an AC line reactor for line harmonic current reduction and for power source exceeding 500 kVA. The DC bus choke will not provide any protection for line voltage unbalance or transients.
Modification CatalogNumberSuffix
Description AdderU.S. $
Ammeter � A1 Panel Type Wired to Current Transformer in Line 1, Type 1, 12
Panel Type Wired to Current Transformer in Line 1, Type 3R, 4X
A2 Panel Type, Selector Switch and 3 Current Transformers Wired to Ammeter via Switch, Type 1, 12
Panel Type, Selector Switch and 3 Current Transformers Wired to Ammeter via Switch, Type 3R, 4X
A3 Miniature (Single-Phase), Type 1, 12
A4 Miniature with Selector Switch, Type 1, 12
A5 Switchboard (Single-Phase), Type 1, 12
Switchboard (Single-Phase), Type 3R, 4X
A6 Switchboard with Selector Switch, Type 1, 12
Switchboard with Selector Switch, Type 3R, 4X
A7 3-Panel Type (Single-Phase), Type 1, 12
3-Panel Type (Single-Phase), Type 3R, 4X
A10 3 Miniature (Single-Phase), Type 1, 3R, 4X, 12
A11 3 Switchboard Type (Single-Phase), Type 1, 12
3 Switchboard Type (Single-Phase),Type 3R, 4X
A12 Ammeter Order by Description, Type 1, 3R, 4X, 12
Auto-transformers
A8 hp Rating selection, see Enclosed Control Product Guide
A9 Order by Description
Top Mounted AuxiliaryContacts � �(Unwired)
Type Sizes 00 – 2 only(Unwired)
IEC SizesA – K Only(Unwired)Freedom Series
A13 1NO
A14 1NC
A15 1NO-1NC
A16 2NO
A17 2NC
A18 2NO-1NC
A19 1NO-2NC
A20 3NO
A21 3NC
A22 3NO-1NC
A23 2NO-2NC
A24 1NO-3NC
A25 4NO
A26 4NC
Side Mounted Auxiliary Contacts Freedom Series
A27 1NO
A28 1NC
A29 1NO-1NC
A30 2NO
A31 2NC
A32 2NO-1NC
A33 1NO-2NC
A34 3NO
Modification CatalogNumberSuffix
Description AdderU.S. $
Side Mounted Auxiliary Contacts Freedom Series, continued
A35 3NC
A36 3NO-1NC
A37 2NO-2NC
A38 1NO-3NC
A39 4NO
A40 4NC
Auxiliary Contacts �
A42 Contacts Mounted on Operating Mecha-nism of Disconnect Switch, 1NO-1NC
A43 Contacts Mounted on Operating Mecha-nism of Disconnect Switch, 2NO-2NC
A44 With Auxiliary Contact Omitted
Accelerating Relay
A46 For 2-Speed
A47 2NO/2NC 24V DC Auxiliary Relay — IT. Only
Modification CatalogNumberSuffix
Description AdderU.S. $
Breaker B1 1NO-1NC Auxiliary Contact on Breaker
B2 2NO-2NC Auxiliary Contacts on Breaker
B3 Shunt Trip on Circuit Breaker — 48 – 127V AC or DC
B4 Shunt Trip on Circuit Breaker —9 – 24V AC or DC
B5 Shunt Trip on Circuit Breaker —208 – 380V AC
B6 Shunt Trip on Circuit Breaker —415 – 600V AC or 220 – 250V DC
B8 Undervoltage Release for Breaker
B9 Current Limiter Mounted to Breaker
B10 Breaker — Order by Description
B11 Thermal Magnetic Breaker
Backspin Timer
B12 180 Seconds
Undervoltage Release
B13 Undervoltage Release for Circuit Breaker — 208 – 240V AC
B14 Undervoltage Release for Circuit Breaker — 380 – 480V AC
B15 Undervoltage Release for Circuit Breaker — 525 – 600V AC
Bell Alarm B16 Bell Alarm for Circuit Breaker
Bus Choke(MVX)
B20 DC Bus Choke, Open Core and Coil �
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-24
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-33. C — Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors
� Not available for IT. Starters.
Table 36-33. C — Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors (Continued)
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
Control PowerTransformers
Make sure 8th character specifies primary/secondaryvoltage. SeePage 33-129.
C1 Standard Size Control Transformer, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C2 Standard Size Control Transformer,24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C42 50 VA Extra Capacity CPT 120V/60 Hz, 110V/50 Hz with 2 Primary and1 Secondary
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C3 100 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C4 100 VA Extra Capacity CPT, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C5 200 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C6 200 VA Extra Capacity CPT, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C7 300 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C8 400 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C9 1 kVA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
C10 2 kVA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
C11 Control Transformer — Order by Description
C34 CPT with Power Supply for IT.
Modification CatalogNumberSuffix
Description AdderU.S. $
Power Supplies (IT. Only)
C27 Separate Control 120V AC to 24V DC
C28 Power Supply with Extra Capacity — Order by Description
Control Relays
C12 4-Pole Interposing Relay, 600V (2NO/2NC)
C13 Run Relay, 24V DC (MVX)
C14 � 4-Pole, Unwired, A600 Rtg. — 2NO-2NC
C15 � 8-Pole, Unwired, A600 Rtg. — 4NO-4NC
C16 Control Relay — Order by Description
C20 � 2-Wire Control Relay for Mechanical/Magnetic Lighting Contactors
Cover Control
C17 � Convert Position 7 to E30 Type Cover Control
C19 � Lock-Off Attachment Added on Cover Control
Current Trans-former(s)
C21 In Phase 1
C22 In Phases 1 and 2
C23 In 3 Phases
CompellingRelay
C25 � —
ControlWiring
C26 Omit Control Wiring
C30 � With Separate Control Wiring and Two 250V Fuses in Holder
C31 � With Common Control Wiring and Two 600V (Class C) Fuses in Holder
C33 Control Wiring Type — Order by Description
Control CircuitBreaker
C32 � Order by Description
SeparateControl
C35 Wired for Separate Control (Reduced Voltage)
CustomerSuppliedComponents
C36 Customer Supplied Components to Be Installed
C37 Customer Supplied Wiring Diagram to Use
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-25Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-33. C — Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors (Continued)
� Not available for IT. Starters.� Includes CPT, Pilot Lights, Selector Switch, Auxiliary Contacts and
Control Relay.
Table 36-34. D — Device Labels, Deceleration Relay, Drain and Breather, DeviceNet, Duplex Modifications
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
Contactor/Starter
C40 � Contactor/Starter — Order by Description
Counter C41 � Operations Counter
E-Stop Relay C43 � E-Stop Relay (DeviceNet)
DC/AC Interface
C44 � DC/AC Interface Module
SeparateSource Disconnect
C45 � IEC Separate Source Disconnect for Control Circuitry
Bypass Contactorsfor IT./MVXStarters (MVX: 1/2 to 5 hp Only)
C46/J1 Isolation Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J2 Output Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J3 Bypass Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J4 Isolation/Output/Bypass Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J5 3-Contactor Bypass Pkg. for MVX �
Modification CatalogNumberSuffix
Description AdderU.S. $
Device Labels D1 (each label)
Decel. Relay � D2 2-Speed
Drain andBreather(Type 7/9 Enclosure) �
D5 Drain and Breather
D6 Drain OnlyBreather OnlyD7
DeviceNet D8 DSNAP
D9 DN65
DuplexModifications
D12 Alternator Omitted (Deduct Price)
D14 START/STOP Pushbuttons — Sup-plied for Each Motor
D15 HAND/OFF/AUTO Selector Switch — Supplied for Each Motor
D16 No. 1 Lead - No. 2 Lead Selector Switch for Manual Selection of Lead Pump (Alternator is Omitted)
D17 Red RUN Pilot Light — Supplied for Each Motor
D18 Push-to-Test Red RUN Pilot Light — Supplied for Each Motor
D19 TEST Pushbutton for Each Motor
D20 CPT, 120V Secondary, 2 Pri. Fuses & 1 Sec. Fuse — Supplied for Ea. Motor
00 – 1 2 3 4 – 9
D21 CPT w/100VA Extra Capacity, 120V Sec., 2 Pri. Fuses & 1 Sec. Fuse — Supplied for Each Motor
00 – 1 2 3 4 – 9
D22 CPT w/200VA Extra Capacity, 120V Sec., 2 Pri. Fuses & 1 Sec. Fuse — Supplied for Each Motor
00 – 1 2 3 4 – 9
D23 CPT for Duplex — Order by Description
D24 Add 2 Relays to Modify Controller to Operate w/Single-Pole Pilot Devices
D25 Add 3 Relays to Modify Controller to Operate w/Single-Pole Pilot Devices
D26 Green — OFF for each starter
D27 Green — Push-to-Test OFF for ea. starter
D28 Green RUN Light
D29 Red STOP Light
D30 P-T-T green RUN Light
D31 P-T-T red STOP Light
D32 Elapsed Time Meter
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-26
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-35. E — Enclosure Modifications, Elapsed Time Meter, Duplex Outlet, Starter
� Not available for IT. Starters.
Table 36-36. F — Fuse Clips, Fuse Blocks, Fungus Protection, Fingerproof Covers, EMI Filter
� The EMI filter is not necessary to meet the CE mark requirements for EMC when installing the MVX in an EC country.
� Consult Eaton.
Table 36-37. G — Ground Fault Relay, Grounding
Table 36-38. H — Heater (Space), Heater Packs Installed
Modification CatalogNumberSuffix
Description AdderU.S. $
EnclosureModifications
E3 Oversize Enclosure
E4 Enclosure — Order by Description
E5 Enclosure w/Pole Mounting Hardware
E7 Service Entrance Rating with Ground/Neutral for Lighting Contactors (30 – 200A)
E65K 65K AIC Rated Explosion Proof Enclosure
E8 Service Entrance Rating w/Ground Bar
E11 Safety Door Interlock
Elapsed Time Meter
E9 Wired Across Coil, Type 1, 12
Wired Across Coil, Type 3R, 4X
E10 Elapsed Time Meter — Order by Description
Duplex Outlet E12 Convenience Duplex Outlet Mounted in Side of Enclosure
Starter � E13 Horizontal Combination Starter, Size 0 – 2
E14 Narrow Combination Starter, Size 0 – 2
Modification CatalogNumberSuffix
Description AdderU.S. $
Fuse Clips F1 Change Fuse Clips in Position 8 to Class J
00 – 1A – H
2J – K
3L – M
4N
5P – S
F2 Change Fuse Clips in Position 8 to Class H & K (30 & 60 Ampere Only)
Fuse Blocks F4 Power Fuses Included — Order byDescription
F5 30 Ampere Control Circuit Fuseholder (KTK) Mounted on Panel (Unwired), Fuse Not Supplied
F6 30 Ampere Control Circuit Fuseholder Mounted on Panel (Unwired), FNQR Fuse Supplied
F7 3-Pole Power Fuseholder Mounted on Front Contactor
F8 Separate Fusing of Control Power Supply — IT.
F10 Blown Fuse Indicator (Not for PFC)
F21 Class CC Fuses
EMI Filter(MVX)
F22 3-Phase �
240V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
480V — 1 hp 2 hp 3 hp 5 hp
U.S. $
F23 1-Phase �
240V 1/2 hp 1 hp 2 hp 3 hp
U.S. $
Modification CatalogNumberSuffix
Description AdderU.S. $
Ground Fault Relay
G1 Ground Fault Relay (Wired)
G3 Ground Fault Relay (Unwired)
Grounding G5 Special Grounding — Order by Description
Modification Cat.No.Suffix
Description AdderU.S. $
SpaceHeater
H1 Space Heater and Thermostat
00 – 1A – H37A
2J – K
66 – 105AMVX
3L – M135A
4N
180A
5P – S
240 – 304A
6 – 9—
360 – 850A
H2 Space Heater and NC Interlock
00 – 1A – H37A
2J – K
66 – 105AMVX
3L – M135A
4N
180A
5P – S
240 – 304A
6 – 9—
360 – 850A
Install HeaterPacks (FreedomSeries)
H5 Class 20 Class 10
/D1 H2001B-3/D2 H2002B-3/D3 H2003B-3/D4 H2004B-3/D5 H2005B-3
/D25 H2101B-3/D26 H2102B-3/D27 H2103B-3/D28 H2104B-3/D29 H2105B-3
/D6 H2006B-3/D7 H2007B-3/D8 H2008B-3/D9 H2009B-3/D10 H2010B-3
/D30 H2106B-3/D31 H2107B-3/D32 H2108B-3/D33 H2109B-3/D34 H2110B-3
/D11 H2011B-3/D12 H2012B-3/D13 H2013B-3/D14 H2014B-3/D15 H2015B-3
/D35 H2111B-3/D36 H2112B-3/D37 H2113B-3/D38 H2114B-3/D39 H2115-3
/D16 H2016B-3/D17 H2017B-3/D18 H2018-3/D19 H2019-3/D20 H2020-3
/D40 H2116-3/D41 H2117-3
/D21 H2021-3/D22 H2022-3/D23 H2023-3/D24 H2024-3
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-27Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-39. K — MVX Keypad
Table 36-40. L — Lightning Arrestor, Lugs, Labels, Line and Load Reactors, Lighting Contactors
� If the power source exceeds 500 kVA, 3% line unbalance, or if transient voltages from power factor capacitor switching events are present, an input line reactor must be used. The input line reactor will also reduce line current harmonics.
� The output line DV/DT filter is required when the distance from the drive to the motor exceeds 33 feet (10m). The total cable run should not exceed 165 feet (50m).
Table 36-40. L — Lightning Arrestor, Lugs, Labels, Line and Load Reactors, Lighting Contactors (Continued)
Table 36-41. M — Solid-State Controllers
Table 36-42. N — Nameplates
Modification CatalogNumberSuffix
Description AdderU.S. $
Keypad(MVX)
K1 Door-Mounted AFD Keypad (Type 1 and 12)
K2 Door-Mounted AFD Keypad (Type 3R)
K3 AFD Copy Keypad (mounted on drive)
K4 Door-Mounted AFD Copy Keypad (Type 1 and 12)
K5 Door-Mounted AFD Copy Keypad (Type 3R)
Modification CatalogNumberSuffix
Description AdderU.S. $
Lighting Arrestor
L3 Installed on Panel
Lugs L9 Special Lugs — Order by Description
Carton Label L10 Customer Marking — Specify
LineReactors(MVX)
L12 3% Input Line Reactor, 3-Phase, Open Core and Coil �
240V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
480V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
L13 3% Input Line Reactor, 1-Phase, Open Core and Coil �
480V 1/2 hp 1 hp 2 hp 3 hp
U.S. $
L14 5% Input Line Reactor, 3-Phase, Open Core and Coil �
240V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
480V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
L15 5% Input Line Reactor, 1-Phase, Open Core and Coil �
480V 1/2 hp 1 hp 2 hp 3 hp
U.S. $
L16 Line Reactor — Order by Description
LoadReactors(MVX)
L17 Output Line DV/DT Filter, Open Core and Coil �
480V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
L18 Load Reactor — Order by Description
Modification CatalogNumberSuffix
Description AdderU.S. $
Lighting Contactors
L21 1 NC Pole
L22 2 NC Pole
L23 3 NC Pole
L24 4 NC Pole
L25 5 NC Pole
L26 6 NC Pole
L27 7 NC Pole
L28 8 NC Pole
L29A 3-Wire 120V AC
L29B 3-Wire 240V AC
L29C 3-Wire 24V AC
L29D 3-Wire 24V DC
L29E 2-Wire 120V AC
L29F 2-Wire 240V AC
L29G 2-Wire 24V AC
Modification CatalogNumberSuffix
Description AdderU.S. $
Solid-State Controller
M1 S701 3.5A Solid-State Controller
M2 S701 15A Solid-State Controller
M3 S701 25 Solid-State Controller
M4 S701 25A with DB Solid-State Controller
M5 Torque Limiter 15A
M6 Torque Limiter 25A
Modification CatalogNumberSuffix
Description AdderU.S. $
Nameplates N1 Enclosure Nameplates
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-28
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-43. P — Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction Capacitors, Program Timer, Percentage Timer, Photocell
� Not available for IT. Starters.
Table 36-43. P — Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction Capacitors, Program Timer, Percentage Timer, Photocell (Continued)
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
Push-to-TestPilot Lights
P1 Push-to-Test Pilot Light (Red RUN)Wired to Coil
P2 Push-to-Test Pilot Light (Green OFF)Wired in Series with Auxiliary Contact
P3 Combination of P1 and P2 Above
P4 Push-to-Test Pilot Light (Amber RUN)Wired to Coil
P49 Push-to-Test Pilot Light (Green RUN)
P54 � Push-to-Test Pilot Light — RedBYPASS (MVX)
P55 � Push-to-Test Pilot Light — AmberINVERTER ENABLE (MVX)
P56 � Push-to-Test Pilot Light — RedINVERTER RUNNING (MVX)
P57 Push-to-Test Pilot Light — Green STOP
Pushbuttons P5 EMERGENCY STOP — MushroomHead
P6 � Pushbutton Omitted
P7 START/STOP
P8 ON/OFF
P9 START
P10 ON
P11 OFF
P12 � FORWARD/REVERSE/STOP
P13 � FAST/SLOW/STOP
P14 � FAST/OFF/SLOW
P15 � HIGH/LOW/STOP
P16 � HIGH/LOW
P17 � SLOW/FAST
P18 � Pushbutton with Legend Plate
P52 UP/STOP/DOWN
P53 OPEN/STOP/CLOSE
P73 START/STOP Pushbuttons Located in Top 2 Holes
Pilot Lights P19 With 1 Amber Pilot Light MarkedPOWER AVAILABLE Wired to LoadSide of 2 Fuses or Circuit Breaker
P20 Pilot Light (Amber RUN) Wired to Coil
P21 � With 1 Red Pilot Light Marked RUNWired thru NO Auxiliary Contact
P22 � With 1 Push-to-Test Red Light MarkedRUN Wired thru NO Auxiliary Contact
P23 Pilot Light — Red RUN
P24 Pilot Light — Red ON
P25 Pilot Light — Green OFF
P26 Pilot Light — Order by Description
P29 Pilot Light — Red STOP
Modification CatalogNumberSuffix
Description AdderU.S. $
Pilot Lights(Continued)
P58 Pilot Light — Red BYPASS (MVX)
P59 � Pilot Light — Amber INVERTER ENABLE (MVX)
P60 � Pilot Light — Red INVERTER RUNNING (MVX)
P61 Pilot Light — Green STOP
P62 � FORWARD/REVERSE Red Pilot Lights
P63 � UP/DOWN Red Pilot Lights
P64 � OPEN/CLOSE Red Pilot Lights
P65 � HIGH/LOW Red Pilot Lights
P66 � FAST/SLOW Red Pilot Lights
P67 Green RUN Light
P68 LED Bulbs
P69 Blue OVERLOAD Light
Illuminated Pushbutton
P27 Illuminated Pushbutton — Order by Description
Phase Loss Relay
P28 Phase Loss Relay
Phase Reversal Relay
P30 Phase Reversal Relay
Phase UnbalanceRelay
P32 Phase Unbalance Relay
Phase MonitoringRelay
P34 Phase Monitoring Relay
Power Factor Correction Capacitors
P38 /F1 20KVAR/F2 25KVAR/F3 30KVAR/F4 35KVAR/F5 40KVAR/F6 45KVAR/F7 50KVAR/F8 60KVAR
/F9 70KVAR/F10 75KVAR/F11 80KVAR/F12 90KVAR/F13 100KVAR/F14 125KVAR/F15 150KVAR/F16 175KVAR
/F17 200KVAR/F18 225KVAR/F19 250KVAR/F20 300KVAR/F21 350KVAR/F22 400KVAR
PotentialTrans-formers
P39 � Potential Transformer — Wired L1 – L2
P40 � Potential Transformer — Wired L1– L2 and L2 – L3
P41 � Potential Transformer — 3 Phases
PumpController
P42 Pump Controller for IT.
ProgramTimers
P43 15-Minute Program Timer
P44 24-Hour Program Timer
P45 7-Day Program Timer with Day Omission Feature
PercentageTimers
P47 15-Minute Percentage Timer
P48 60-Minute Percentage Timer
Photocell P70 � Photoelectric Receptacle with Photocell
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-29Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-44. Q — IQ Products, DN50
� Not available for IT. Starters.
Table 36-45. R — Ramp, Relays, Resets, Overload Relay Modifications, DeviceNet Interface
� Not available for IT. Starters.
Table 36-45. R — Ramp, Relays, Resets, Overload Relay Modifications, DeviceNet Interface (Continued)
� Not available for IT. Starters.� Features:
• Self-Powered• Phase Loss Protection• Current Adjustment Knob• ± 1% Repeat Accuracy• 1NO and 1NC Isolated Contacts
� Complete Modification Code includes reset code. Example R52/G102.
Modification CatalogNumberSuffix
Description AdderU.S. $
IQ Products Q14 IQ 220 with cable
Q1 IQ 500
Q3 MP3000
Q5 IQ 4000
IQ Data MeteringModule
Q12 � IQ Data Metering Module
Q14 IQ 220 with Cable
DN50 Q13 � DeviceNet Input/Output Module
Modification CatalogNumberSuffix
Description AdderU.S. $
Ramp R1 Extended Ramp of IT.
Relay � R2 Overvoltage Relay
R4 Omit Overload Relay (Deduct Price)
00 – 0A – F
1G – H
2J – K
3L – M
4N
5 – 9P – S
R7 Overload Relay — Order by Description
Fixed Heater Overload Relay
R8 C316FNA3C .25 – .40A
R9 C316FNA3D .40 – .63A
R10 C316FNA3E .63 – 1.00A
R11 C316FNA3F 1.00 – 1.40A
R12 C316FNA3G 1.30 – 1.80A
R13 C316FNA3H 1.70 – 2.40A
R14 C316FNA3J 2.20 – 3.10A
R15 C316FNA3K 2.80 – 4.00A
R16 C316FNA3L 3.50 – 5.00A
R17 C316FNA3M 4.50 – 6.50A
R18 C316FNA3N 6.00 – 8.50A
R19 C316FNA3P 7.50 – 11.00A
R20 C316FNA3Q 10.00 – 14.00A
R21 C316FNA3R 13.00 – 19.00A
R22 C316FNA3S 18.00 – 24.00A
R23 C316FNA3T 24.00 – 32.00A
R24 C316KNA3A 18.00 – 25.00A
R25 C316KNA3B 22.00 – 32.00A
R26 C316KNA3C 29.00 – 42.00A
R27 C316KNA3D 36.00 – 52.00A
R28 C316KNA3E 45.00 – 63.00A
R29 C316KNA3F 60.00 – 80.00A
R30 C316PNA3A 65.00 – 90.00A
R31 C316PNA3B 80.00 – 100.00A
R32 C316PNA3C 100.00 – 135.00A
R33 C316PNA3D 110.00 – 150.00A
R34 C316PNA3E 130.00 – 175.00A
R35 C316PNA3F 150.00 – 200.00A
R36 C316SNA3A 130.00 – 185.00A
R37 C316SNA3B 165.00 – 235.00A
R38 C316SNA3C 220.00 – 310.00A
R39 C316SNA3D 285.00 – 400.00A
Modification CatalogNumberSuffix
Description AdderU.S. $
Fixed Heater Overload Relay, continued
R40 C316UNA3A 355.00 – 500.00A
R41 C316UNA3B 465.00 – 650.00A
R42 C316UNA3C 610.00 – 850.00A
R43 Fixed Heater Overload Relay — Order byDescription
R55 C316FNA3F w/Current Trans.
60.00 – 84.00 FLA
R56 C316FNA3G w/Current Trans.
78.00 – 108.00 FLA
R57 C316FNA3H w/Current Trans.
102.00 – 144.00 FLA
R58 C316FNA3J w/Current Trans.
132.00 – 186.00 FLA
R59 C316FNA3K w/Current Trans-former
168.00 – 240.00 FLA
R60 C316FNA3L w/Current Trans-former
210.00 – 310.00 FLA
Electronic Relay �
IEC Frame
NEMASize
Full Load Current Adjust-ment Range (A)
3-Phase Manual Reset Overload
3-Phase Automatic/Manual Reset
Class10
Class20
Class10
Class20
AAAA
00 0.1 – 0.30.3 – 1.01.0 – 2.91.6 – 5.0
G101G102G103G104
G81G82G83G84
G141G142G143G144
G121G122G123G124
A,B,C 3.7 – 12 G105 G85 G145 G125
AAAA
0 & 1 0.1 – 0.30.3 – 1.01.0 – 2.91.6 – 5.0
G101G102G103G104
G81G82G83G84
G141G142G143G144
G121G122G123G124
A,B,C 3.7 – 12 G105 G85 G145 G125
D,E 12 – 32 G106 G86 G146 G126
D,E,F,H 2 12 – 37 G107 G87 G147 G127
G,H 14 – 45 G108 G88 G148 G128
G,H,J,K,L 3 26 – 85 G109 G89 G149 G129
M,N,L 4 57 – 180 G112 G92 G152 G132
N/A 5 96 – 300 G104 G84 G144 G124
N/A 6 192 – 600 G104 G84 G144 G124
Catalog Number Suffix ➟ � R52_ R50_ R53_ R51_
Adder U.S. $
Resets � R5 Change External Reset to Internal Reset — Hole Covered with Plug
R6 Internal Reset — No Hole Plug
R44 Manual Reset Only on Overload Relay
R45 Auto Reset Only on Overload Relay
R71 N3R Reset Boot Added (Type 1/12 Only)
Reversing � R54 Reversing Contactor/Starter
DeviceNet Interface
R69 DeviceNet Interface
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-30
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-46. S — System Voltage, Selector Switches, Suppressor, Incomplete Sequence Protection, Single-Phase Jumper, Surge Capacitor, Speed Potentiometer
� When using 3-position selector switch with magnetic lighting contactor, mod C20 must also be used (ECL04, ECL13, ECL15).
� Not available for IT. Starters.
Table 36-46. S — System Voltage, Selector Switches, Suppressor, Incomplete Sequence Protection, Single-Phase Jumper, Surge Capacitor, Speed Potentiometer (Continued)
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
System Voltage Selection
S1 System Voltage Selection for Internal Components/H1 208V 60 Hz/H2 240V 60 Hz/H3 277V 60 Hz, 1-Ph/H4 480V 60 Hz/H5 600V 60 Hz/H6 796V 60 Hz/H7 220V 50 Hz/H8 380V 50 Hz/H9 415V 50 Hz/H10 550V 50 Hz/H11 660V 50 Hz/H12 380V 60 Hz/H13 1500V 60 Hz
S2 System Voltage Selection — Specify on Order
Selector Switches �
S3 HAND/OFF/AUTOS4 HAND/AUTOS5 HAND/OFF/AUTO Selector Switch
with 1 Red RUN Pilot LightS6 RUN/OFF/AUTOS7 AUTO/OFF/TESTS8 AUTO/OFF/TEST Selector Switch
with 1 Red RUN Pilot LightS9 AUTO/OFF/TEST Selector Switch with
1 Red RUN Pilot Light and 1 Green Pilot Light
S10 OFF/AUTOS11 START/STOPS12 OFF/ONS13 � HIGH/LOWS14 � FAST/OFF/SLOWS15 � SLOW/FASTS16 � FORWARD/REVERSES17 � HIGH/OFF/LOWS18 � HIGH/LOW/OFF/AUTOS21 HAND/OFF/AUTO Spring Return from
LeftS38 � INVERTER/OFF/BYPASS (MVX)S41 � OPEN/OFF/CLOSES42 � FORWARD/OFF/REVERSES43 � FAST/OFF/SLOW/AUTOS45 LOCAL/REMOTES46 RUN/OFFS19 � Selector Switch Omitted (Pump Panels Only)S40 Selector Switch — Order by Description
Suppressor S24 � Transient Suppressor Mountedon Magnet Coil
Modification CatalogNumberSuffix
Description AdderU.S. $
SurgeSuppression
S20 MOV (IT.)
Sequence Timer
S26 � Sequence Timer (Pump Panels)
Sequence Protection
S27 � Incomplete Sequence Protection
Pump S28 480V BP9000 PumpSingle Phase �
S29 Convert Contactor or Starter from Three-Phase to Single-Phase — Install Jumper
S30 Single-Phase Rev. 120VS31 Single-Phase Rev. 240V
SurgeCapacitor
S37 � Surge Capacitor Wired to Disconnect Line Side
Speed Potentiometer
S39 � Speed Potentiometer (MVX)
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
CA08102001E For more information visit: www.eaton.com
36-31Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-47. T — Timers, Time Delay Relays, Terminal Blocks, Terminal Points, Ring Lug Connections
� Not available for IT. Starters.
Table 36-47. T — Timers, Time Delay Relays, Terminal Blocks, Terminal Points, Ring Lug Connections (Continued)
Modification CatalogNumberSuffix
Description AdderU.S. $
Timers T1 � Pneumatic Timer Installed on Contactor, Unwired, 30 Sec. Max.
T2 � Pneumatic Timer Installed on Contactor, Unwired, 180 Sec. Max.
T3 Pneumatic Timer Mounted in Enclosure, Unwired, 180 Sec. Max.
T25 Timer — Order by Description
Time DelayRelays
T6 Time Delay Relay, 3 Minutes Maximum, Unwired, ON DELAY
T7 Time Delay Relay, 3 Minutes Maximum, Unwired, OFF DELAY
T8 Time Delay Low Voltage Release Relay
TerminalBlocks
T9 With 1 Single Circuit Terminal Block, Unwired
T10 With 2 Single Circuit Terminal Block, Unwired
T24 � Power Terminal Block for DeviceNet Overload
TerminalPoints
T11 With 6 Terminal Points, Unwired
T12 With 12 Terminal Points, Unwired
T13 With 18 Terminal Points, Unwired
T14 Terminal Point per Customer Specifica-tion, Unwired (Price Each)
T15 Terminal Point per Customer Specifica-tion, Wired (Price Each)
T21 � 3 Terminals Mounted Between Contactor and Overload for Power Factor Capacitors — Sizes 0 – 2
T22 � 3 Terminals Mounted Between Contactor and Overload for Power Factor Capaci-tors — Sizes 3 – 4
T23 � Quick-Connect Terminals Added to DP Contactor/Starter
Ring LugConnectors
T16 Ring Lug Connections on Power Wires
T17 � Ring Lug Connections on Control Wires
IT./EM T30 Reset Only
T31 STOP with Reset
T32 START/STOP with Reset
T33A HAND/OFF/AUTO with Reset 120V AC
T33D HAND/OFF/AUTO with Reset 24V DC
T34 ON/OFF
T40 Reset Only (DeviceNet)
T41 STOP with Reset (DeviceNet)
T42 START/STOP with Reset (DeviceNet)
T43A HAND/OFF/AUTO with Reset 120V AC (DeviceNet)
T43D HAND/OFF/AUTO with Reset 24V DC (DeviceNet)
T44 ON/OFF
T50 Reset Only
T51 STOP with Reset
T52 FORWARD/REVERSE/STOP with Reset
T53A FORWARD/REVERSE/STOP with Reset 120V AC
T53D FORWARD/REVERSE/STOP with Reset 24V DC
T54 ON/OFF
Modification CatalogNumberSuffix
Description AdderU.S. $
IT./EM, continued
T60 Reset Only (DeviceNet)
T61 STOP with Reset (DeviceNet)
T62 FORWARD/REVERSE/STOP with Reset (DeviceNet)
T63A FORWARD/REVERSE/STOP with Reset 120V AC (DeviceNet)
T63D FORWARD/REVERSE/STOP with Reset 24V DC (DeviceNet)
T64 ON/OFF
T70 Reset Only
T71 START/STOP with Reset
T72 HAND/OFF/AUTO – START with Reset
T73 FORWARD/REVERSE/STOP with Reset
T74 HAND/OFF/AUTO – FORWARD/REVERSE with Reset
T75 ON/OFF with Reset
T76 FAST/SLOW/STOP with Reset
T77 HAND/OFF/AUTO – FAST/SLOW with Reset
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
February 2007
36-32
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-48. U — Undervoltage Relay, Time Delay Undervoltage Relay
� Not available for IT. Starters.
Table 36-49. V — Voltmeter
� Type 1/12 only.
Table 36-50. W — Wattmeter, Watt-Hour Meter, Wiremarkers, Wiring Diagram
� Type 1/12 only.
Modification CatalogNumberSuffix
Description AdderU.S. $
Undervolt-age Relays
U2 Undervoltage Relay, Adjustable
Time Delay Undervolt-age Relays
U4 � Time Delay Undervoltage Relay,Non-adjustable
U5 Time Delay Undervoltage Relay, Adjustable
Under- and Overvoltage Relay
U7 Under- and Overvoltage Relay
Modification CatalogNumberSuffix
Description AdderU.S. $
Voltmeters V1 1 Panel Type Voltmeter Wired L1 – L2
V2 Panel Type Voltmeter and Selector Switch Wired to Read Three Line Voltages
V3 � Miniature Voltmeter Wired L1 – L2
V4 � Miniature Voltmeter and Selector Switch Wired to Read Three Line Voltages
V5 Switchboard Type Voltmeter Wired L1 – L2
V6 � Switchboard Type Voltmeter and Selector Switch Wired to Read Three Line Voltage
V7 3 Panel Type Voltmeters Wired in Each Phase
V8 � 3 Miniature Voltmeters Wired in Each Phase
V9 3 Switchboard Type Voltmeters Wired in Each Phase
V10 Voltmeter — Order by Description
Modification CatalogNumberSuffix
Description AdderU.S. $
Wattmeter � W1 Wattmeter
Watt-Hour Meter �
W5 Watt-Hour Meter with Demand Attachment
Wiremarkers W7 Wiremarkers
W8 Wiremarkers — Order per Customer Diagram or Specifications
W9 Wiremarkers — Order by Description
WYE-Delta hp
W10 See Enclosed Control Product Guide
Wiring Diagram
W12 Reduced Copy of Custom Wiring Diagram Laminated on Inside of Door
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD1C
These fi les are the same as the last printed version of the catalog dated February 2007.For the most up-to-date information, install the Automatic Tab Updater (ATU) by visiting
www.gathermydata.com/install or visitour web site at www.eaton.com/electrical.
NOTICE
Click HERE to Continue